Honeywell Process Solutions
MasterLogic PLC Software Change Notice
R220
July 2012
Release 220 Honeywell
ii MasterLogic PLC Software Change Notice R220 Honeywell July 2012
Notices and Trademarks Copyright 2012 by Honeywell International Sárl.
Release 220 – July, 2012
While this information is presented in good faith and believed to be accurate, Honeywell disclaims the implied warranties of merchantability and fitness for a particular purpose and makes no express warranties except as may be stated in its written agreement with and for its customers.
In no event is Honeywell liable to anyone for any indirect, special or consequential damages. The information and specifications in this document are subject to change without notice.
Honeywell, PlantScape, Experion, and TotalPlant are registered trademarks of Honeywell International Inc.
Other brand or product names are trademarks of their respective owners.
Honeywell Process Solutions
1860 W. Rose Garden Lane
Phoenix, AZ 85027 USA
1-800 822-7673
R220 MasterLogic PLC Software Change Notice iii July 2012 Honeywell
About This Document This document contains information related to MasterLogic PLC software and firmware releases only for ML-200R. It is recommended that user fully understands the notices covered in this document before start working with the MLPLC.
Release Information
Document Name Document ID
Release Number
Publication Date
MasterLogic PLC Software Change Notice R220 July 2012
Reference
Document Model Number
ML200 CPU and SoftMaster Users Guide
Analog Input Module 2MLF-AV8A, AC8A User's Guide
ML200-AI
Analog Output Module 2MLF – DV4A/8A, 2MLF – DC4A/8A User's Guide
ML200-AO
Digital Input/Output Modules ML 200 DI/DO Module User's Guide
ML200 - DI/DO
Fast Ethernet I/F Module 2MLL-FEnet User's Guide
ML200 – Fenet
2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide
2MLF-HO2A, 2MLF-HD2A
MasterLogic PLC Instruction List ML200-IL
Isolated Analog Input Module 2MLF-AD4S User's Guide
ML200-IAI
Isolated Analog Output Module 2MLF-DV4S, 2MLF-DC4S User's Guide
ML200-IAO
Support and Other Contacts
iv MasterLogic PLC Software Change Notice R220 Honeywell July 2012
Document Model Number
Isolated Thermocouple Input Module TC4S User's Guide
ML200-ITIM
Profibus-DP Pnet I/F Module 2MLL-PMEA User's Guide
ML200-PMEA
Resistance Temperature Detector 2MLF-RD4A User's Guide
ML200-RTD
Serial Communication I/F Module 2MLL-C22A, 2MLL-CH2A, 2MLL-C42A User's Guide
ML200-Snet
Support and Other Contacts
R220 MasterLogic PLC Software Change Notice v July 2012 Honeywell
Support and Other Contacts
United States and Canada Contact:
Phone: Fascimile: Mail:
Honeywell Solution Support Center 1-800-822-7673 Calls are answered by dispatcher between 6:00 am and 4:00 pm Mountain Standard Time. Emergency calls outside normal working hours are received by an answering service and returned within one hour. 1-973-455-5000 Honeywell TAC, MS L17 1860 W. Garden Lane Phoenix, AZ, 85027 USA
Europe, Middle East, and Africa (EMEA) Contact:
Phone: Fascimile: Mail:
Honeywell TAC-EMEA +32-2-728-2345 +32-2-728-2696 TAC-BE02 Hermes Plaza Hermeslaan, 1H B-1831 Diegem, Belgium
Pacific Contact:
Phone: Fascimile: Mail: Email:
Honeywell Global TAC – Pacific 1300-364-822 (toll free within Australia) +61-8-9362-9559 (outside Australia) +61-8-9362-9564 Honeywell Limited Australia 5 Kitchener Way Burswood 6100, Western Australia GTAC@honeywell.com
India Contact:
Phone: Fascimile: Mail: Email:
Honeywell Global TAC – India +91-20- 6603-9400 +91-20- 6603-9800 Honeywell Automation India Ltd 56 and 57, Hadapsar Industrial Estate Hadapsar, Pune –411 013, India Global-TAC-India@honeywell.com
Support and Other Contacts
vi MasterLogic PLC Software Change Notice R220 Honeywell July 2012
Korea Contact:
Phone: Fascimile: Mail: Email:
Honeywell Global TAC – Korea +82-80-782-2255 (toll free within Korea) +82-2-792-9015 Honeywell Co., Ltd 4F, Sangam IT Tower 1590, DMC Sangam-dong, Mapo-gu Seoul, 121-835, Korea Global-TAC-Korea@honeywell.com
People’s Republic of China Contact:
Phone: Mail: Email:
Honeywell Global TAC – China +86- 21-2219-6888 800-820-0237 400-820-0386 Honeywell (China) Co., Ltd 33/F, Tower A, City Center, 100 Zunyi Rd. Shanghai 200051, People’s Republic of China Global-TAC-China@honeywell.com
Singapore Contact:
Phone: Fascimile: Mail: Email:
Honeywell Global TAC – South East Asia +65-6580-3500 +65-6580-3501 +65-6445-3033 Honeywell Private Limited Honeywell Building 17, Changi Business Park Central 1 Singapore 486073 GTAC-SEA@honeywell.com
Taiwan Contact:
Phone: Fascimile: Mail: Email:
Honeywell Global TAC – Taiwan +886-7-536-2567 +886-7-536-2039 Honeywell Taiwan Ltd. 17F-1, No. 260, Jhongshan 2nd Road. Cianjhen District Kaohsiung, Taiwan, ROC Global-TAC-Taiwan@honeywell.com
Support and Other Contacts
R220 MasterLogic PLC Software Change Notice vii July 2012 Honeywell
Japan Contact:
Phone: Fascimile: Mail: Email:
Honeywell Global TAC – Japan +81-3-6730-7160 +81-3-6730-7228 Honeywell Japan Inc. New Pier Takeshiba, South Tower Building, 20th Floor, 1-16-1 Kaigan, Minato-ku, Tokyo 105-0022, Japan Global-TAC-JapanJA25@honeywell.com
Elsewhere Call your nearest Honeywell office.
World Wide Web Honeywell Solution Support Online:
http://www.honeywellprocess.com
Training Classes Honeywell Automation College:
http://www.automationcollege.com
Symbol Definitions
viii MasterLogic PLC Software Change Notice R220 Honeywell July 2012
Symbol Definitions The following table lists those symbols used in this document to denote certain conditions.
Symbol Definition
ATTENTION: Identifies information that requires special consideration.
TIP: Identifies advice or hints for the user, often in terms of performing a task.
CAUTION
Indicates a situation which, if not avoided, may result in equipment or work (data) on the system being damaged or lost, or may result in the inability to properly operate the process.
CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
CAUTION symbol on the equipment refers the user to the product manual for additional information. The symbol appears next to required information in the manual.
WARNING: Indicates a potentially hazardous situation, which, if not avoided, could result in serious injury or death.
WARNING symbol on the equipment refers the user to the product manual for additional information. The symbol appears next to required information in the manual.
R220 MasterLogic PLC Software Change Notice ix July 2012 Honeywell
Contents
1. BEFORE YOU BEGIN ................................................................... 11
1.1 Review the latest information ..................................................................... 11 Checking for updates ............................................................................................... 11
1.2 Overview ....................................................................................................... 11
2. ABOUT THIS RELEASE ............................................................... 13
2.1 Components of this release ........................................................................ 13
2.2 Hardware and software compatibility matrix ............................................. 13
2.3 Hardware list ................................................................................................. 14
2.4 New features in this release ........................................................................ 18 Firmware 2.10 .......................................................................................................... 18 SoftMaster 3.63 ........................................................................................................ 18 SoftMaster 3.64 ........................................................................................................ 19
2.5 Problems resolved ....................................................................................... 20
2.6 Known issues with MLPLC.......................................................................... 21
3. SOFTMASTER INSTALLATION ................................................... 23
3.1 Installing SoftMaster .................................................................................... 23
4. PLC FIRMWARE UPGRADE ........................................................ 25
4.1 Overview ....................................................................................................... 25
4.2 Upgrading PLC firmware for ML200R Expansion driver module (redundant and non-redundant) ..................................................................................... 25
4.3 Upgrading PLC firmware for ML200R Expansion Manager (Built inside CPU module) ................................................................................................. 27
4.4 Upgrading PLC firmware for ML200R CPU offline .................................... 29
4.5 Upgrading PLC firmware for ML200R CPU online .................................... 31
Contents
x MasterLogic PLC Software Change Notice R220 Honeywell July 2012
4.6 Upgrading OS for Communication Module using SoftMaster-NM ........... 33
R220 MasterLogic PLC Software Change Notice 11 July 2012 Honeywell
1. Before you begin
1.1 Review the latest information Checking for updates Before installing any software, check the extranet site using the following link http://acsnet.honeywell.com/sites/ML_Globalization/Shared%20Documents/Forms/AllItems.aspx?RootFolder=%2fsites%2fML%5fGlobalization%2fShared%20Documents%2fUser%20Documents&FolderCTID=&View=%7b5432F171%2dB69C%2d4A59%2dA336%2dF5651317A9DA%7d, for documentations including the updates to this SCN.
1.2 Overview ML200R is Honeywell’s next generation Programmable Logic Controllers which supports CPU level redundancy.
It provides the following:
• Real power
• Performance and versatility with compact size
• High speed scanning of I/O Channels and execution of program instructions
• Open network through Ethernet
• Profibus, remote I/O, engineer-friendly programming and diagnostic software tools.
Experion interface is qualified with ModBus and MLDP.
1. Before you begin 1.2. Overview
12 MasterLogic PLC Software Change Notice R220 Honeywell July 2012
R220 MasterLogic PLC Software Change Notice 13 July 2012 Honeywell
2. About this release
2.1 Components of this release The following table lists the components and their version numbers.
Component Version Number
SoftMaster 3.64
CPU firmware 2.10
Expansion Manager 2.10
Expansion Driver 2.10
FENet OS 3.20
SNet OS 3.0
2.2 Hardware and software compatibility matrix
ATTENTION
For more information on compatibility versions, contact Honeywell TAC.
The following table provides the hardware and software compatibility matrix.
Model Number Hardware Version OS Version
SoftMaster - V3.64
SoftMaster-NM - V3.64
2MLR-CPUH/T 2MLR-CPUH/F
V5.0 V2.10
V5.1 V2.10
2MLR-DBSH 2MLR-DBSF 2MLR-DBST
V5.0 V2.10
2MLR-DBDH 2MLR-DBDF 2MLR-DBDT
- V2.10
2. About this release 2.3. Hardware list
14 MasterLogic PLC Software Change Notice R220 Honeywell July 2012
Model Number Hardware Version OS Version
2MLF-AC8A V6.3 V1.12
2MLF-AD4S V5.0 V1.02
2MLF-AD8A V5.1 V1.02
2MLF-AD16A V5.0 V1.02
2MLF-AV8A V6.3 V1.12
2MLF-DC4A V6.0 V1.10
2MLF-DC4S V5.1 V1.00
2MLF-DC8A V5.1 V1.00
2MLF-DV4A V6.2 V1.10
2MLF-DV8A V5.1 V1.00
2MLF-HO2A 2MLF-HD2A V6.0 V1.14
2MLF-RD4A V6.0 V1.00
2MLF-TC4S V6.1 V1.01
2MLL-C22A 2MLL-C42A 2MLL-CH2A
V5.1 V3.0
2MLL-EFMF 2MLL-EFMT V5.0 V3.20
2.3 Hardware list The following table provides the list of hardware.
Model Number Specifications
2MLR-CPUH/F CPU
Max. I/O:23,808Pts., Redundant CPU, FO
2MLR-CPUH/T Max. I/O:23,808Pts., Redundant CPU, TP
2. About this release 2.3. Hardware list
R220 MasterLogic PLC Software Change Notice 15 July 2012 Honeywell
Model Number Specifications
2MLR-AC12
Power
Redundant Power 110V, 5.5A
2MLR-AC22 Redundant Power 220V, 5.5A
2MLR-AC13 Redundant Power 110V, 8.5A
2MLR-AC23 Redundant Power 220V, 8.5A
2MLR-DC42 Redundant Power DC24V
2MLR-M02P
Base
Main Base 2 slot
2MLR-M06P Main Base 6 slot
2MLR-E12P Expansion Base 12 slot
2MLR-E12H Expansion Redundancy Base 12 slot
2MLR-DBST Expansion Driver
Expansion Driver, TP
2MLR-DBSF Expansion Driver, FO
2MLR-DBSH Expansion Driver, TP/FO
2MLR-DBDT Expansion Redundancy Driver
Expansion Redundancy Driver, TP
2MLR-DBDF Expansion Redundancy Driver, FO
2MLR-DBDH Expansion Redundancy Driver, TP/FO
2MLC-F201 Sync Cable Multimode Fiber Optic Cable, LC connector, 2.0m
2MLI-D21A
Digital Input
8Pts. DC24V Input (Sink/Source Type)
2MLI-D22A 16Pts. DC24V Input (Sink/Source Type)
2MLI-D22B 16Pts. DC24V Input (Source Type)
2MLI-D24A 32Pts. DC24V Input (Sink/Source Type)
2MLI-D24B 32Pts. DC24V Input (Source Type)
2MLI-D28A 64Pts. DC24V Input (Sink/Source Type)
2. About this release 2.3. Hardware list
16 MasterLogic PLC Software Change Notice R220 Honeywell July 2012
Model Number Specifications
2MLI-D28B 64Pts. DC24V Input (Source Type)
2MLI-A12A 16Pts. AC110V Input
2MLI-A21A 8Pts. AC220V Input
2MLI-A21C 8Pts. AC220V Input
2MLQ-RY1A
Digital Output
8Pts. Relay Output, 2A , 1Pts./COM
2MLQ-RY2A 16Pts. Relay Output, 2A (5A/COM)
2MLQ-RY2B 16Pts. Relay Output, 2A , BuiVaristor
2MLQ-SS2A 16Pts. Triac Output, 1A
2MLQ-TR2A 16Pts. TR Output, 0.5A (Sink Type)
2MLQ-TR4A 32Pts. TR Output, 0.1A (Sink Type)
2MLQ-TR8A 64Pts. TR Output, 0.1A (Sink Type)
2MLQ-TR2B 16Pts. TR Output, 0.5A (Source Type)
2MLQ-TR4B 32Pts. TR Output, 0.1A (Source Type)
2MLQ-TR8B 62Pts. TR Output, 0.1A (Source Type)
2MLQ-TR1C 8Pts. TR Output, 2A (Sink Type)
2MLF-AV8A
Analog Input
Voltage Input, 8channels
2MLF-AC8A Current Input, 8channels
2MLF-AD8A Voltage/Current Input, 8channels
2MLF-AD4S Voltage/Current Input, 4channels, Isolated
2MLF-AD16A Voltage/Current Input, 16channels
2MLF-RD4A RTD Input RTD Input, 4channels
2MLF-TC4S TC Input Thermocouple Input, 4channels, Isolated
2MLF-DV4A Analog Output Voltage Output, 4channels
2. About this release 2.3. Hardware list
R220 MasterLogic PLC Software Change Notice 17 July 2012 Honeywell
Model Number Specifications
2MLF-DC4A Current Output, 4channels
2MLF-DC8A Current Output, 8channels
2MLF-DV8A Voltage Output, 8channels
2MLF-DC4S Current Output, 4channels, Isolated
2MLF-HO2A High Speed Counter
Pulse Input, 2channels, Open Collector
2MLF-HD2A Pulse Input, 2channels, Line Drive
2MLL-EFMT FEnet
Fast Ethernet, 100/100Mbps, RJ-45 (Electric)
2MLL-EFMF Fast Ethernet, 100/100Mbps, SC Type (Fiber Optic)
2MLL-C22A
Snet
Serial Communication, RS-232C 2channels
2MLL-C42A Serial Communication, RS-422 2channels
2MLL-CH2A Serial Communication, RS-232C/RS-422 (1ch each)
2MLL-PMEA Pnet Profibus, Master, 12Mbps, DP Standard
2MLL-DMEA Dnet DeviceNet Interface Card
2MLT-DMMA DUMMY
DUMMY Module for empty I/O slots
2MLR-DMMA DUMMY Module for empty Power Supply slots - used for ML200R
USB-301A USB Cable Engineering cable for SoftMaster
SmartLink Board & Connection Cable for Digital I/Os (Only for 32/64 points Sink Type)
Model Number Specifications
R32C-NS5A-40P Relay Board SmartLink Relay Board, 40point
2. About this release 2.4. New features in this release
18 MasterLogic PLC Software Change Notice R220 Honeywell July 2012
Model Number Specifications
TG7-1H40S Terminal Board SmartLink Terminal Board, 40point
C40HF-15PB-1
Cable between SmartLink and PLC I/Os
Cable Assembly for Terminal Board, 40p-40p, 1.5m
C40HF-30PB-1 Cable Assembly for Terminal Board, 40p-40p, 3.0m
C40HF-15PB-1 Cable Assembly for Relay Board, 40p-40p, 1.5m
C40HF-30PB-1 Cable Assembly for Relay Board, 40p-40p, 3.0m
2.4 New features in this release The following are the new features/enhancements in this release.
Firmware 2.10 • Support for dual I/O link redundancy (2MLR-DBDT/F/H and 2MLR-E12H)
• Support for Profibus slave interface module (2MLL-PSEA)
• Support for two new digital I/O cards.
− 2MLI-A21C
− 2MLQ-TR1C
SoftMaster 3.63 • Inclusion of above mentioned firmware features.
• Addition of the following instructions.
− AB Expression: CPT
− ARY instruction: ARY_CMP_EQ, ARY_CMP_NE
• Support for downloading binary file to CPU without opening the source file.
2. About this release 2.4. New features in this release
R220 MasterLogic PLC Software Change Notice 19 July 2012 Honeywell
• Addition of the following flags for SOE event information.
− _SOE_LOG_CNT
− _SOE_LOG_ROTATE
− _SOE_READ_LOG_CNT
− _SOE_READ_LOG_ROTATE
• Addition of the following flags to enable/disable HS/P2P link in ladder program.
− _HS_ENABLE_STATE, _HS_REQ_NUM, _HS_REQ
− _P2P_ENABLE_STATE, _P2P_REQ_NUM, _P2P_REQ
• Addition of scan time information flag for fixed cycle task: _CYCLE_TASK_SCAN_TIME
SoftMaster 3.64 • Support for two new digital I/O cards.
− 2MLI-A21C
− 2MLQ-TR1C
• In I/O Parameter window, Digital module list shows the module name instead of module type.
• “Audo Detect” function is added to check connected port number automatically for RS-232C setting.
• “Refresh User Function/FB function” is added to update all if UDF or UDFB is modified.
2. About this release 2.5. Problems resolved
20 MasterLogic PLC Software Change Notice R220 Honeywell July 2012
2.5 Problems resolved This section describes the notable problems resolved in this release.
PAR Brief description of the problem
1-MN2NVY Error 104 does not have any information on error message.
1-MN2O2P Warning 43 does not have any information.
1-MN2O6J SoftMaster tool shows a user incomprehensible dialog box on selecting the Module Change Wizard.
1-MN2O9A
When SoftMaster is connected to ML200R through USB and if you continuously perform power OFF/ON, remove/connect DBDT modules, DBDT cables, DBDT reset and so on., then SoftMaster does not responds at times.
1-MN2OAY
In the SoftMaster-NM window, when you right-click the FENet module and selecting Properties in the tree view, the properties of the module are not displayed.
1-MN3EO5 In SoftMaster 3.63, the updated MLPLC user guide is not displayed from the Help menu.
1-MN3EQX
CPU status does not come to online automatically after power OFF both the Master and Standby CPUs and power ON one after another.
1-P2HHZ5 SoftMaster is crashing occasionally while performing online edit operation continuously.
1-P2HHZZ Unable to install SoftMaster on Windows 2K8 server systems.
1-QY2KSI Masterlogic Address Configuration Error for P2P when we use the data size in multiple of 16.
1-R9219U
There is no possiblity to do ON-LINE EDITING. During write an on-line change of Softmaster 3.61 program is terminated with message (It is general information from Windows about problem in application, which needs to close Softmaster and detail information about dll).
2. About this release 2.6. Known issues with MLPLC
R220 MasterLogic PLC Software Change Notice 21 July 2012 Honeywell
2.6 Known issues with MLPLC This section describes the notable known issues with MLPLC.
PAR Brief description of the
problem Work-around/Preventive action
1-IDQPMD Separate flags are needed for ML200R types to differentiate ML200R - CPUH/T & CPU H/F types. This is required to appear in MLDP Communication display.
This is only for display notification and is not on function. At present, common ML200R types are displayed as 2MLR-CPUH/T.
1-IDQPMZ E039 does not show proper LED status.
Remove the power supply of both CPU A and B and connect it again. The PLC shows E039. But the Master - RUN/STOP LED is Green that shows PLC is running, Standby - RUN/STOP LED is RED that shows CPU is stopped. The small sync window in SoftMaster shows both PLC is running.
Functionality is working properly. Only LED status mismatch occurs.
1-IDQPOA After changing and downloading only IO parameters in SoftMaster, if you select Start Monitor, a warning message appears before the monitoring starts.
Functionality is working properly. This warning message can be ignored.
1-IDQPPR Any of the variable name that contains 'load' (For example, overload) in the SoftMaster may result an unexpected behavior of program execution.
Avoid using variable names which contains the word ‘load’.
1-HXO8AD Sometimes, Average Value parameter for an AI module in I/O parameter window shows Red and this does not allow to changing any of the module parameters.
Delete the module from I/O parameter, add manually and then configure it.
2. About this release 2.6. Known issues with MLPLC
22 MasterLogic PLC Software Change Notice R220 Honeywell July 2012
PAR Brief description of the problem
Work-around/Preventive action
1-CWHPS4 In SoftMaster, Communication Module Info under System Monitoring for the CPU module, the Port 1 Number and Port 2 Number information is reversed.
No workaround exists.
1-IZFAPN In DISOE module, Force I/O feature is not available.
No workaround exists.
1-J60Q9B In SoftMaster, when we add some function blocks in a ladder diagram, the shortcut of the function block is also added in the Most Recently Used option in the Function/FB pane. But this shortcut is not appearing in SoftMaster 3.61.
No workaround exists.
R220 MasterLogic PLC Software Change Notice 23 July 2012 Honeywell
3. SoftMaster Installation
3.1 Installing SoftMaster To install SoftMaster, perform the following steps.
Step Action
1 Double-click setup.exe and execute the installation file. The Installation Wizard appears.
2 Click Next. The Customer Information window appears.
3 Type your name and company name and then click Next.
You are prompted to specify the folder to install SoftMaster.
4 The default installation folder is displayed. If you want to change the folder, click Browse… and select a new folder.
ATTENTION
SoftMaster needs 30 MB of free disk space. In case of inadequate free space, you are prompted to select a disk with enough capacity.
5 After selecting a folder, click Next.
The installation may take a few minutes.
6 Click Finish to complete the installation.
3. SoftMaster Installation 3.1. Installing SoftMaster
24 MasterLogic PLC Software Change Notice R220 Honeywell July 2012
R220 MasterLogic PLC Software Change Notice 25 July 2012 Honeywell
4. PLC firmware upgrade
4.1 Overview PLC firmware must be upgraded in the following sequence.
• Upgrading ML200R PLC firmware for Expansion Driver (2MLR-DBST, F, H)
• Upgrading ML200R PLC firmware for Expansion Manager (Built inside CPU)
• Upgrading PLC firmware for ML200R CPU (2MLR-CPUH/T,F)
ATTENTION
• For more details on firmware upgrade and firmware files, contact Honeywell TAC.
• During PLC firmware upgradation, ensure to connect the USB cable to Master CPU.
4.2 Upgrading PLC firmware for ML200R Expansion driver module (redundant and non-redundant)
ATTENTION
• The Expansion Manager/Driver module OS cannot be upgraded online.
• The following procedure is given by considering the CPU A as Master and CPU B as Standby.
To upgrade PLC firmware for Expansion Driver module (redundant and non-redundant), perform the following steps.
Step Action
1 Change both the CPUs to STOP mode, and ensure that the key switch is in REMOTE mode.
2 Connect the USB cable to the master CPU.
3 Execute MasterLogic OS Downloader 1.1.exe.
The MasterLogic OS Downloader dialog box appears.
4. PLC firmware upgrade 4.2. Upgrading PLC firmware for ML200R Expansion driver module (redundant and non-redundant)
26 MasterLogic PLC Software Change Notice R220 Honeywell July 2012
Step Action
4 Choose Connect > Serial Port/CPU Setup.
The Connection Setup dialog box appears.
5 Click USB in the Media drop-down list.
6 Click
7
Click .
The OS Download dialog box appears.
8 In the OS Download window, perform the following:
a) Under Download Mode, click USB.
b) In the OS Type drop-down list, click ML200R-ExtDriver.
c) Click Open and select OS as 2MLR_SLAVE_Vxxx.bin.
After the download is complete, the downloader tool changes to initial mode and LED in the Expansion driver module blinks.
9 Power off and on (Reset CPU and IO base) to make upgrade firmware online.
ATTENTION
If there are more than two expansion bases in the system, all the expansion bases (particular ring) are upgraded at once.
10 If dual I/O link redundant topology is used, then follow the below steps to upgrade the expansion driver module for both ring network.
a) Change CPU A to CPU B.
b) Connect USB to CPU B and repeat the steps 2 through 9.
4. PLC firmware upgrade 4.3. Upgrading PLC firmware for ML200R Expansion Manager (Built inside CPU module)
R220 MasterLogic PLC Software Change Notice 27 July 2012 Honeywell
4.3 Upgrading PLC firmware for ML200R Expansion Manager (Built inside CPU module)
ATTENTION
The following procedure is given by considering the CPU A as Master and CPU B as Standby.
To upgrade PLC firmware for Expansion Manager (redundant and non-redundant), perform the following steps.
Step Action
1 Change both the CPUs to STOP mode, and ensure that the key switch is in REMOTE mode.
2 Connect the USB cable to the Master CPU.
3 Execute MasterLogic OS Downloader 1.1.exe.
The MasterLogic OS Downloader dialog box appears.
4 Choose Connect > Serial Port/CPU Setup.
The Connection Setup dialog box appears.
5 Click USB in the Media drop-down list.
6 Click
7
Click .
The OS Download dialog box appears.
4. PLC firmware upgrade 4.3. Upgrading PLC firmware for ML200R Expansion Manager (Built inside CPU module)
28 MasterLogic PLC Software Change Notice R220 Honeywell July 2012
Step Action
8 In the OS Download dialog box, perform the following:
a) Under Download Mode, click USB.
b) Click ML200R-ExtManager in the OS Type drop-down list.
c) Click Open and select OS as 2MLR_CPUH_Master_Vxxx.bin.
After the download is complete, downloader tool changes to initial mode and waits for CPU ACT LED to blink.
9 Power off and on (Reset CPU) to make upgrade firmware online.
ATTENTION
In case of expansion manager, OS of Master and Standby are migrated at once. Ensure to check if OS is updated in the Standby CPU and reset.
10 If dual I/O link redundant topology is used, then follow the below steps to upgrade the expansion manager module for CPU B.
a) Change CPU A to CPU B.
b) Connect USB to CPU B and repeat the steps 2 through 9.
4. PLC firmware upgrade 4.4. Upgrading PLC firmware for ML200R CPU offline
R220 MasterLogic PLC Software Change Notice 29 July 2012 Honeywell
4.4 Upgrading PLC firmware for ML200R CPU offline To upgrade PLC firmware for CPU during offline mode, perform the following steps.
Step Action
1 Change both the CPUs to STOP mode, and ensure that the key switch is in REMOTE mode.
2 Connect the USB cable to the Master CPU.
3 Execute MasterLogic OS Downloader 1.1.exe.
The MasterLogic OS Downloader dialog box appears.
4 Choose Connect > Serial Port/CPU Setup.
The Connection Setup dialog box appears.
5 Click USB in the Media drop-down list.
6 Click
7
Click .
The OS Download dialog box appears.
8 In the OS Download window, perform the following:
a) Under Download Mode, click USB.
b) Click ML CPU Series in the OS Type drop-down list.
c) Click ML200R Boot. The following actions occur by default.
− CPU Dot Matrix: OSwr
− CPU LED: Blink in RUN/STOP → WAR. → ERR order
− Standby CPU shows the same indication
d) Click Open and select OS as 2MLR_CPUH_Main_Vxx.bin.
4. PLC firmware upgrade 4.4. Upgrading PLC firmware for ML200R CPU offline
30 MasterLogic PLC Software Change Notice R220 Honeywell July 2012
Step Action
After the download is complete in Master CPU,
• The downloader tool change to initial mode
• CPU LED blinks for few times
• Master CPU changes to STOP mode.
9 Power off and on (Reset CPU) to make upgrade firmware online.
CPU OS upgradation for Master CPU is completed.
ATTENTION
Ensure the following status in Standby CPU.
• CPU Dot Matrix: OSwr
• CPU LED: Blink in RUN/STOP → WAR. → ERR order
10 Connect USB to Standby CPU and repeat the steps 4 through 7.
11 In the OS Download dialog box, click Open and select OS as 2MLR_CPUH_Main_Vxx.bin.
After the download is complete,
• The downloader tool change to initial mode
• CPU LED blinks for few times
• Standby CPU changes to STOP mode.
12 Power off and on (Reset CPU) to make upgrade firmware online.
CPU OS upgradation for Standby CPU is completed.
4. PLC firmware upgrade 4.5. Upgrading PLC firmware for ML200R CPU online
R220 MasterLogic PLC Software Change Notice 31 July 2012 Honeywell
4.5 Upgrading PLC firmware for ML200R CPU online
ATTENTION
• Only CPU firmware version can be upgraded online and not Expansion Manager/Driver.
• Ensure that the CPU OS version to be installed is compatible with the existing Expansion driver/Expansion manager OS version.
To upgrade PLC firmware for CPU during operation (online), perform the following steps.
ATTENTION
The following procedure is given by considering the CPU A as Master and CPU B as Standby.
Execute the procedure carefully based on your current status of CPU or ensure CPU A as Master and follow the procedure.
Step Action
1 Remove the synchronization cable (OFC) between Master CPU (A) and Standby CPU (B) and all I/O cables connected to Standby CPU (B) to isolate the Standby CPU (B) from operation.
2 Change the mode from ‘REMOTE’ to ‘RUN’ using a key switch. Hence, the isolated Standby CPU (B) becomes a Master CPU (B).
3 Change the isolated CPU to STOP mode, and ensure that the key switch is set back to REMOTE mode
4 Execute MasterLogic OS Downloader 1.1.exe.
The MasterLogic OS Downloader dialog box appears.
5 Choose Connect > Serial Port/CPU Setup.
The Connection Setup dialog box appears.
6 Click USB in the Media drop-down list.
7 Click
4. PLC firmware upgrade 4.6. Upgrading OS for Communication Module using SoftMaster-NM
32 MasterLogic PLC Software Change Notice R220 Honeywell July 2012
Step Action
8
Click .
The OS Download dialog box appears.
9 In the OS Download window, perform the following:
a) Under Download Mode, click USB.
b) Click ML CPU Series in the OS Type drop-down list.
c) Click ML200R Boot. The following actions occur by default.
− CPU Dot Matrix: OSwr
− CPU LED: Blink in RUN/STOP → WAR. → ERR order
d) Click Open and select OS as 2MLR_CPUH_Main_Vxx.bin.
After the download is complete in the isolated CPU (B),
• The downloader tool change to initial mode
• CPU LED blinks for few times
• CPU (B) changes to STOP mode.
• Power off the CPU (B) and connect the synchronization cable and I/O cable to CPU (B).
10 Power off and on (Reset CPU) to make upgrade firmware online.
CPU OS upgradation for this CPU (B) is completed.
11 Power on CPU (B) and change its mode to RUN (by Key switch or SoftMaster). Both CPUs are in RUN mode even if the OS versions are different.
12 Change Master CPU (A) to STOP mode. Then, this Master CPU (A) becomes Standby CPU (A) and the Standby CPU (B) becomes Master CPU (B)
4. PLC firmware upgrade 4.6. Upgrading OS for Communication Module using SoftMaster-NM
R220 MasterLogic PLC Software Change Notice 33 July 2012 Honeywell
Step Action
13 Repeat steps 1 through 10 for CPU (A) which is Standby CPU.
CPU OS upgradation for this CPU (A) is completed.
14 Power on CPU (A) and change its mode to RUN (by Key switch or SoftMaster). Both CPUs are in RUN mode being CPU (B) as Master and CPU (A) as Standby.
4.6 Upgrading OS for Communication Module using SoftMaster-NM To upgrade Communication module using SoftMaster-NM, perform the following steps.
Step Action
1 Connect USB cable to Master CPU (for example, CPU A) and launch SoftMaster-NM.
2 From SoftMaster-NM, choose Online > Upload/Download (File).
The Download/Upload(File) dialog box appears.
4. PLC firmware upgrade 4.6. Upgrading OS for Communication Module using SoftMaster-NM
34 MasterLogic PLC Software Change Notice R220 Honeywell July 2012
Step Action
3 Select the communication module and then click BBMBoot. The LED of FENet module is changed to Download mode and PLC CPU will reset after BBMBoot is selected.
4 From SoftMaster-NM, choose Online > Connect and then Online > Upload/Download (File).
The Download/Upload(File) dialog box appears.
The mode is changed to OS Update Mode.
ATTENTION
FDEnet is displayed as communication module only after BBMBoot execution. Ensure to select the proper Base and Slot number.
5 Select the OS and then click Download.
The Open dialog box appears.
4. PLC firmware upgrade 4.6. Upgrading OS for Communication Module using SoftMaster-NM
R220 MasterLogic PLC Software Change Notice 35 July 2012 Honeywell
Step Action
6 Select the FEnet OS Firmware file and then click Open.
The OS download begins. It takes few minutes to complete.
After the download is complete the following message appears.
4. PLC firmware upgrade 4.6. Upgrading OS for Communication Module using SoftMaster-NM
36 MasterLogic PLC Software Change Notice R220 Honeywell July 2012
Step Action
7 Power off the Master CPU A and then re-connect the synchronization cable and I/O cables to CPU A and it changes back to Standby mode.
8 From SoftMaster, choose Online > Control Redundancy and then click Change Master.
Repeat Step 1 to 8 with CPU B (Master).
9 Choose Online > System Diagnosis from SoftMaster-NM to verify if the OS version is downloaded to the System.
4. PLC firmware upgrade 4.6. Upgrading OS for Communication Module using SoftMaster-NM
R220 MasterLogic PLC Software Change Notice 37 July 2012 Honeywell
Honeywell Process Solutions 1860 W. Rose Garden Lane Phoenix, AZ 85027 USA