With Logix™ Brand Integrated Ceiling Systems from USG, you can design ceilings that meet building requirements without being constrained by the limits of traditional acoustical ceilings. Logix transforms visual distractions such as lighting, air vents, and other utilities into dramatic design elements by concentrating these fixtures on narrow bands that run the length of a ceiling. This allows for open ceilings that are uncluttered by ceiling utilities.

A wide selection of acoustical and specialty panels as well as corresponding suspension system components and accessories are available to enhance and customize your design. Plus, with a wide selection of Logix partners, you can be assured that ceiling utilities will complement your design and integrate seamlessly into the ceiling.

This guide is a comprehensive resource for the critical dimensions of a Logix Integrated Ceiling System.¹

1 Please refer to IS268 for complete information about the various layouts and sizes available.

LOGIX™

Integrated Ceiling Systems

LOGIX™ INTEGRATED CEILING SYSTEMSCRITICAL SYSTEM DIMENSIONS

WHITE PAPER

2 CRITICAL SYSTEM Logix Integrated Ceiling Systems DIMENSIONS

Example Reflected Ceiling Plan (RCP) Layout

A-A

1 1 1

2 3 32

4

4

2

2 2

2

2

5 5

6

6

6

6

B-B

1 Utility Channel

Yoke1 4

Opening for Luminaire or Mechanical Grille

2

Infill Panel3

Channel SectionYoke AssemblyDetails on pages 3 – 5.

Channel Panel

Channel Section Connector Panel Assembly Details on pages 17 – 18.

Note: This is one reflected ceiling plan (RCP) layout. Numerous configurations are possible. Please contact your sales representative for more information.

¹ The USG Logix yoke is an optional suspension system installation accessory that facilitates the spacing and suspension of parallel main tees with one hanger wire. The Logix yoke is compatible with both metric and imperial utility channel sizes. The yoke also keeps hanger wire wraps away from linear luminaires and can reduce the number of hanger wires required. The yoke also helps to brace the utility channel.

Connector PanelDetails on pages 15-18.

LOGIX INTEGRATED CEILING SYSTEMS

Integration with Lighting and Mechanical Systems

3 CRITICAL SYSTEM Logix Integrated Ceiling Systems DIMENSIONS

Centricitee™ DXT™

CHANNEL SECTION A-A

A B C D E

Channel Profiles

Channel Spacing o.c.

Clear Opening Clear Space Clear Depth Grid Height (Reveal)

CHANNEL CLEARANCES Imperial 4 in. Channel 4.000 in. 3.425 in. 3.750 in. 8.187 in. 0.050 in.

6 in. Channel 6.000 in. 5.425 in. 5.750 in. 8.187 in. 0.050 in.

12 in. Channel 12.000 in. 11.425 in. 11.750 in. 8.187 in. 0.050 in.

Metric 100 mm 100 mm 85.40 mm 93.65 mm 207.95 mm 1.27 mm

150 mm 150 mm 135.40 mm 143.65 mm 207.95 mm 1.27 mm

300 mm 300 mm 285.40 mm 293.65 mm 207.95 mm 1.27 mm

CHANNEL LENGTHS Channel lengths can vary to meet the architectural design intent. Coordination of light fixtures, AND INFILL PANEL mechanical grilles, channel panels, and infill panels can vary based on function and architectural

design intent. Contact your sales representative for more information.

E

D

C

B

A

LOGIX INTEGRATED CEILING SYSTEMS LOGIX INTEGRATED CEILING SYSTEMS

Integration with Lighting and Mechnical Systems

4 CRITICAL SYSTEM Logix Integrated Ceiling Systems DIMENSIONS

D

C

B

E

A

Identitee™

CHANNEL SECTION A-A

LOGIX INTEGRATED CEILING SYSTEMS

Integration with Lighting and Mechanical Systems

A B C D E

Channel Profiles

Channel Spacing o.c.

Clear Opening Clear Space Clear Depth Grid Height (Reveal)

CHANNEL CLEARANCES Imperial 4 in. Channel 4.000 in. 3.438 in. 3.750 in. 8.187 in. 0.272 in.

6 in. Channel 6.000 in. 5.438 in. 5.750 in. 8.187 in. 0.272 in.

12 in. Channel 12.000 in. 11.438 in. 11.750 in. 8.187 in. 0.272 in.

Metric 100 mm 100 mm 85.73 mm 93.65 mm 207.95 mm 6.91 mm

150 mm 150 mm 135.73 mm 143.65 mm 207.95 mm 6.91 mm

300 mm 300 mm 285.73 mm 293.65 mm 207.95 mm 6.91 mm

CHANNEL LENGTHS Channel lengths can vary to meet the architectural design intent. Coordination of light fixtures, AND INFILL PANEL mechanical grilles, channel panels, and infill panels, can vary based on function and architectural

design intent. Contact your sales representative for more information.

5 CRITICAL SYSTEM Logix Integrated Ceiling Systems DIMENSIONS

D

C

B

A

E

Donn® DX® DXL™

CHANNEL SECTION A-A

LOGIX INTEGRATED CEILING SYSTEMS LOGIX INTEGRATED CEILING SYSTEMS

Integration with Lighting and Mechanical Systems

A B C D E

Channel Profiles

Channel Spacing o.c.

Clear Opening Clear Space Clear Depth Grid Height (Reveal)

CHANNEL CLEARANCES Imperial 4 in. Channel 4.000 in. 3.063 in. 3.750 in. 8.187 in. 0.050 in.

6 in. Channel 6.000 in. 5.063 in. 5.750 in. 8.187 in. 0.050 in.

12 in. Channel 12.000 in. 11.063 in. 11.750 in. 8.187 in. 0.050 in.

Metric 100 mm 100 mm 76.19 mm 93.65 mm 207.95 mm 1.27 mm

150 mm 150 mm 126.19 mm 143.65 mm 207.95 mm 1.27 mm

300 mm 300 mm 276.19 mm 293.65 mm 207.95 mm 1.27 mm

CHANNEL LENGTHS Channel lengths can vary to meet the architectural design intent. Coordination of light fixtures, AND INFILL PANEL mechanical grilles, channel panels, and infill panels can vary based on function and architectural

design intent. Contact your sales representative for more information.

IMPERIAL 49 CHANNELfastener placement(2 required)

4 in.

8.187 in.

9.500 in.10.000 in.4.800 in.

69 CHANNEL

8.187 in.

9.500 in.10.000 in.6.800 in.

6 in.

fastener placement(2 required)

129 CHANNEL

8.187 in.

9.500 in.10.000 in.12.800 in.

12 in.

fastener placement(4 required)

cut main tee to be used as a bridge to lengthen yoke

hanger wires (2 required)

The USG Logix Yoke is an optional suspension system installation accessory that facilitates

the spacing and suspension of parallel main tees with one hanger wire. The Logix yoke is

compatible with both metric and imperial utility channel sizes. The yoke also keeps hanger

wire wraps away from linear luminaires and can reduce the number of hanger wires required.

The yoke also helps to brace the utility channel.

LOGIX INTEGRATED CEILING SYSTEMS

Yoke Configurations

6 Critical System Dimensions Logix Integrated Ceiling Systems

7 CRITICAL SYSTEM Logix Integrated Ceiling Systems DIMENSIONS

METRIC 100 mm CHANNEL

120.40 mm

100 mm

207.95 mm

241.30 mm254.00 mm

fastener placement(2 required)

150 mm CHANNEL

170.18 mm

207.95 mm

241.30 mm254.00 mm

150 mm

fastener placement(2 required)

300 mm CHANNEL

320.18 mm

300 mm

207.95 mm

241.30 mm

254.00 mm

fastener placement(4 required)

cut main tee to be used as a bridge to lengthen yoke

hanger wires (2 required)

LOGIX INTEGRATED CEILING SYSTEMS LOGIX INTEGRATED CEILING SYSTEMS

Yoke Configurations

8 CRITICAL SYSTEM Logix Integrated Ceiling Systems DIMENSIONS

Dimensions (inches)

Profile Heavy Duty Intermediate Duty

CENTRICITEE™ DXT™

1.640

0.438

0.250

0.810

0.830

0.0500.575

1.5

0.438

0.250

0.893

0.607

0.0500.575

0.016

IDENTITEE® DXI™

0.282

0.050

1.820

0.500

0.250

1.068

0.752

0.562

0.016

0.282

0.050

1.820

0.500

0.250

1.068

0.752

0.562

0.014

DONN® DX®/DXL™

1.640

0.500

1.051

0.5900.110

0.016

0.942

0.250

0.050

1.640

0.500

1.035

0.6050.125

0.014

0.942

0.250

0.050

Note: Figures above are inch dimensions.

LOGIX INTEGRATED CEILING SYSTEMS

Suspension System Dimensions

9 CRITICAL SYSTEM Logix Integrated Ceiling Systems DIMENSIONS

IMPERIAL 4 in. Channel

4.000 in. Channel

0.250 in. 3.750 in. Bulb to Bulb

3.425 in. Opening

0.575 in.

6 in. Channel

6.000 in. Channel

5.425 in. Opening

0.575 in.

0.250 in. 5.750 in. Bulb to Bulb Fit Dim.

12 in. Channel

12.000 in. Channel

11.425 in. Opening

0.575 in.

0.250 in. 11.750 in. Bulb to Bulb Fit Dim.

METRIC 100 mm Channel

100 mm Channel

93.65 mm Bulb to Bulb

85.40 mm Opening

6.35 mm

14.60 mm

150 mm Channel

150 mm Channel

143.65 mm Bulb to Bulb Fit Dim.

135.40 mm Opening

6.35 mm

14.60 mm

300 mm Channel

300 mm Channel

293.65 mm Bulb to Bulb Fit Dim.

285.40 mm Opening

14.60 mm

6.35 mm

LOGIX INTEGRATED CEILING SYSTEMS CHANNEL WIDTHS

Centricitee™ DXT™

10 CRITICAL SYSTEM Logix Integrated Ceiling Systems DIMENSIONS

CHANNEL WIDTHS

Identitee® DXI™

IMPERIAL 4 in. Channel

0.250 in.

4.000 in. Channel

3.750 in. Bulb to Bulb

3.438 in. Opening

0.562 in.

6 in. Channel

0.250 in.

6.000 in. Channel

5.750 in. Bulb to Bulb Fit Dim.

5.438 in. Opening

0.562 in.

12 in. Channel

0.250 in.

12.000 in. Channel

11.750 in. Bulb to Bulb Fit Dimension

11.438 in. Opening

0.562 in.

METRIC 100 mm Channel

100 mm Channel

93.65 mm Bulb to Bulb

85.73 mm Opening

6.35 mm

14.27 mm

150 mm Channel

150 mm Channel

143.65 mm Bulb to Bulb Fit Dim.

135.73 mm Opening

6.35 mm

14.27 mm

300 mm Channel

300 mm Channel

293.65 mm Bulb to Bulb Fit Dim.

285.73 mm Opening

6.35 mm

14.27 mm

11 CRITICAL SYSTEM Logix Integrated Ceiling Systems DIMENSIONS

Donn® DX®/DXL™

CHANNEL WIDTHS

Donn® DX®/DXL™

IMPERIAL 4 in. Channel

0.250 in.

4.000 in. Channel

3.750 in. Bulb to Bulb

3.063 in. Opening

0.937 in.

6 in. Channel

0.250 in.

6.000 in. Channel

5.750 in. Bulb to Bulb Fit Dim.

5.063 in. Opening

0.937 in.

12 in. Channel

0.250 in.

12.000 in. Channel

11.750 in. Bulb to Bulb Fit Dimension

11.063 in. Opening

0.937 in.

METRIC 100 mm Channel

100 mm Channel

93.65 mm Bulb to Bulb

76.19 mm Opng.

6.35 mm

23.81 mm

150 mm Channel

150 mm Channel

143.65 mm Bulb to Bulb Fit Dim.

126.19 mm Opening

6.35 mm

23.81 mm

300 mm Channel

300 mm Channel

293.65 mm Bulb to Bulb Fit Dim.

276.19 mm Opening

6.35 mm

23.81 mm

12 CRITICAL SYSTEM Logix Integrated Ceiling Systems DIMENSIONS

Module

Opening

0.575 in.

0.250 in. Bulb-to-Bulb

Module

Bulb-to-Bulb Opening

Max. Min. Max. Min.

IMPERIAL 20 in. 19.75 in. 19.719 in. 19.437 in. 19.409 in.

24 in. 23.75 in. 23.719 in. 23.437 in. 23.409 in.

30 in. 29.75 in. 29.719 in. 29.437 in. 29.409 in.

48 in. 47.75 in. 47.719 in. 47.437 in. 47.409 in.

60 in. 59.75 in. 59.719 in. 59.437 in. 59.409 in.

72 in. 71.75 in. 71.719 in. 71.437 in. 71.409 in.

96 in. 95.75 in. 95.719 in. 95.437 in. 95.409 in.

120 in. 119.75 in. 119.719 in. 119.437 in. 119.409 in.

METRIC 300 mm 293.7 mm 292.9 mm 276.200 mm 276.176 mm

600 mm 593.7 mm 592.9 mm 576.200 mm 576.176 mm

1200 mm 1193.7 mm 1192.9 mm 1176.200 mm 1176.176 mm

2400 mm 2393.7 mm 2392.9 mm 2376.200 mm 2376.176 mm

INFILL DIMENSIONS

Centricitee™ DXT™

13 CRITICAL SYSTEM Logix Integrated Ceiling Systems DIMENSIONS

0.250 in.

0.562 in.

Module

Bulb-to-Bulb

Opening

Module

Bulb-to-Bulb Opening

Max. Min. Max. Min.

IMPERIAL 20 in. 19.75 in. 19.719 in. 19.437 in. 19.409 in.

24 in. 23.75 in. 23.719 in. 23.437 in. 23.409 in.

30 in. 29.75 in. 29.719 in. 29.437 in. 29.409 in.

48 in. 47.75 in. 47.719 in. 47.437 in. 47.409 in.

60 in. 59.75 in. 59.719 in. 59.437 in. 59.409 in.

72 in. 71.75 in. 71.719 in. 71.437 in. 71.409 in.

96 in. 95.75 in. 95.719 in. 95.437 in. 95.409 in.

120 in. 119.75 in. 119.719 in. 119.437 in. 119.409 in.

METRIC 300 mm 293.7 mm 292.9 mm 285.70 mm 285.09 mm

600 mm 593.7 mm 592.9 mm 585.70 mm 585.09 mm

1200 mm 1193.7 mm 1192.9 mm 1185.70 mm 1185.09 mm

2400 mm 2393.7 mm 2392.9 mm 2385.70 mm 2385.09 mm

INFILL DIMENSIONS INFILL DIMENSIONS

Identitee® DXI™

14 CRITICAL SYSTEM Logix Integrated Ceiling Systems DIMENSIONS

0.250 in.

0.937 in.

Module

Bulb-to-Bulb

Opening

Module

Bulb-to-Bulb Opening

Max. Min. Max. Min.

IMPERIAL 20 in. 19.75 in. 19.719 in. 19.075 in. 19.051 in.

24 in. 23.75 in. 23.719 in. 23.075 in. 23.051 in.

30 in. 29.75 in. 29.719 in. 29.075 in. 29.051 in.

48 in. 47.75 in. 47.719 in. 47.075 in. 47.051 in.

60 in. 59.75 in. 59.719 in. 59.075 in. 59.051 in.

72 in. 71.75 in. 71.719 in. 71.075 in. 71.051 in.

96 in. 95.75 in. 95.719 in. 95.075 in. 95.051 in.

120 in. 119.75 in. 119.719 in. 119.075 in. 119.051 in.

METRIC 300 mm 293.7 mm 292.9 mm 276.200 mm 276.176 mm

600 mm 593.7 mm 592.9 mm 576.200 mm 576.176 mm

1200 mm 1193.7 mm 1192.9 mm 1176.200 mm 1176.176 mm

2400 mm 2393.7 mm 2392.9 mm 2376.200 mm 2376.176 mm

INFILL DIMENSIONS

Donn® DX®/DXL™

15 CRITICAL SYSTEM Logix Integrated Ceiling Systems DIMENSIONS

Reveal Edge Flush Mount (FM)

49 x 129 Connector Panel

12.55 in. 12.53 in.

49 x 249 Connector Panel

24.55 in. 24.53 in.

69 x 129 Connector Panel

12.55 in. 12.53 in.

69 x 249 Connector Panel

24.55 in. 24.53 in.

Connector panels are a unique option for USG Logix ceiling systems. Connector panels

visually connect various utilities in a utility channel such as luminaires and channel panels.

Connector panels are configured to carry the adjacent panel or fixture. No special fixture

types or tile edges are needed. Connector panels are metal and available in perforated and

smooth finishes. Imperial and metric sizes are available.

INFILL DIMENSIONS CHANNEL PANEL INTERFACE

Connector Panels

16 CRITICAL SYSTEM Logix Integrated Ceiling Systems DIMENSIONS

Reveal Edge Flush Mount (FM)

CENTRICITEE DXT 49 Connector Panel 4.000 in. Channel

3.80 in.

3.37 in.

4.000 in. Channel

3.76 in.

69 Connector Panel 6.000 in. Channel

5.80 in.

5.37 in.

6.000 in. Channel

5.76 in.

IDENTITEE DXI 49 Connector Panel 4.000 in. Channel

3.80 in.

3.37 in.

69 Connector Panel 6.000 in. Channel

5.80 in.

5.37 in.

Reveal Edge connector panels are designed for DXT and DXI suspension systems.

Flush Mount connector panels are recommended with DXT suspension systems.

CHANNEL PANEL INTERFACE

Connector Panels

17 CRITICAL SYSTEM Logix Integrated Ceiling Systems DIMENSIONS

Reveal Edge

1 1 1

2 3 32

4

2

25 5

6

6

B-B

1 Utility Channel

Yoke4

Luminaire or Mechanical Grille

2

Infill Panel3

Channel Panel

Connector Panel

Channel Section B-B

B B

SECTION B-B

2

6

65

265

Reveal Edge

Centricitee DXT

Identitee DXI

CHANNEL PANEL INTERFACE CHANNEL PANEL INTERFACE

Connector Panel Assembly

18 CRITICAL SYSTEM Logix Integrated Ceiling Systems DIMENSIONS

1 1 1

2 3 32

4

2

25 5

6

6

B-B

1 Utility Channel

Yoke4

Luminaire or Mechanical Grille

2

Infill Panel3

Channel Panel

Connector Panel

Channel Section B-B

B B

SECTION B-B

6

265

265

Flush Mount

Centricitee DXT

Flush Mount (FM)

CHANNEL PANEL INTERFACE

Connector Panel Assembly

CHANNEL PANEL INTERFACE

IC609/rev. 11-15 © 2015, USG Corporation or its affiliates. All rights reserved.The trademarks CENTRICITEE, DONN, DX, DXI, DXL, FINELINE, IDENTITEE, LOGIX, USG, IT’S YOUR WORLD BUILD IT, the USG Logo, the red and grey design element, and related marks are trademarks of USG Corporation or affiliate.

Manufactured byUSG Interiors, Inc.550 West Adams StreetChicago, IL 60661

PRODUCT INFORMATIONSee usg.com for the most up-to-date product information. Dimensions listed are for reference purposes only. Other factors including, but not limited to installation techniques and structural forces can affect suspension system dimensions and final fit of components.

INSTALLATIONMust be installed in compliance with ASTM C636, ASTM E580, CISCA, and standard industry practices.

CODE COMPLIANCEThe information presented is correct to the best of our knowledge at the date of issuance. Because codes continue to evolve, check with a local official prior to designing and installing a ceiling system. Other restric-tions and exemptions may apply. This is only intended as a quick reference.

ICC EVALUATION SERVICE, INC., REPORT COMPLIANCESuspension systems manufactured by USG Interiors, Inc., have been reviewed and are approved by listing in ICC-ES Evaluation Report 1222. Evaluation Reports are subject to reexamination, revision and possible cancellation. Please refer to usg.com for current reports.

L.A. RESEARCH REPORT COMPLIANCEDonn brand suspension systems manufactured by USG Interiors, Inc., have been reviewed and are approved by listing in the following L.A. Research Report number: 25764.

NOTICEWe shall not be liable for incidental and consequential damages, directly or indirectly sustained, nor for any loss caused by application of these goods not in accordance with current printed instructions or for other than the intended use. Our liability is expressly limited to replacement of defective goods. Any claim shall be deemed waived unless made in writing to us within thirty (30) days from date it was or reasonably should have been discovered.

SAFETY FIRST! Follow good safety/industrial hygiene practices during installation. Wear appropriate personal protective equipment. Read MSDS and literature before specification and installation.

WEBSITES