Page 1
(SE 95 02 08)
Line distance protection terminal
REL 511*2.0
1MRK 606 003-BEN
Issued May 2002Changed since June 1999
Data subject to change without notice
Features • Line distance functionality comprises;
- simultaneous measurement of the differ-ent phase - phase and phase - earth impedances within the numerical mea-suring elements, individually for each type of fault and each distance zone for fast and reliable fault detection
- five zone protection with completely indi-vidual settings
- separate and independent impedance measuring elements for the General Fault Criteria with advanced characteris-tic and phase preference logic
- scheme communication logic with cur-rent reversal and weak end infeed logics
- power swing detection
• Additional protection functionality such as;
- phase overcurrent, residual current and voltage functions
- breaker failure protection
- fuse failure and current transformer circuit supervision
- fast interbay communication of binary signals
- single- or multi-pole tripping
• Control;
- command control
- autoreclosing and synchro-check with phasing and energising check
• Monitoring;
- event recorder
- disturbance recorder
- fault locator
- trip value recorder
- status indication of all input and internal binary signals
- presentation of measured mean values of line current, voltage, active power, reactive power and frequency with accu-racy up to 0.25%
• Metering;
- pulse counter logic
• Remote-end data communication alternatives;
- multiplexed, dedicated fibre and galvanic channel
- allows for remote-end binary signal transfer
- communication channel supervision
• Serial communication;
- SPA or IEC 870-5-103 port (monitoring)
- LON port (control)
• Extensive configuration possibilities by use of internal logical gates, timers and user configurable connections between differ-ent functions, binary inputs and outputs
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 2
Features (cont’d) • Several input/output module options includ-ing measuring mA input module (for trans-ducers)
• Extensive software ’tool-box’ for monitor-ing, evaluation and user configuration of the terminal
• Flexible software and hardware
• Selected processor design guarantees high availability together with excellent possibilities for extensive combination of different functions without prolonging the operation time
• Numerical filtering and measuring tech-niques ensuring correct performance dur-ing transient conditions
• Versatile local human-machine interface (HMI) from the front panel
• Various local HMI language options
• Extensive self-supervision with fault diagnostics
General The REL511 line distance protection termi-nal is one of the basic units for distribution and sub-transmission line distance protection applications and forms a part of a PAN-ORAMA Station Automation. The PAN-ORAMA Station Automation concept includes a complete range of single-function
units and multi-functional terminals, Substa-tion Monitoring System (SMS) and Substa-tion Control System (SCS). The units in the PANORAMA concept are available as stand alone relays/terminals or as building blocks in a total power network management system.
Functions Line impedance
Distance protection (ZM1–5)
ApplicationDistance protection provides fast and reliable protection for overhead lines and power cables in all kinds of power networks. For each independent distance protection zone, full scheme design provides continuous mea-surement of impedance separately in three independent phase-phase measuring loops as well as in three independent phase-earth mea-suring loops.
Phase-earth distance protection serves as basic earth-fault protection in networks with directly or low-impedance earthed networks. Together with an independent phase-prefer-ence-logic, it also serves as selective protec-tion function at cross-country faults in isolated or resonantly earthed networks.
Independent reactive reach setting for phase-phase and for phase-earth measurement secures high selectivity in networks with dif-ferent protective relays used for short-circuit and earth-fault protection.
Fig. 1 Schematic presentation of the operate characteristic for one distance protection zone in forward direction
The distance protection zones can operate, independently of the others, in directional (forward or reverse) or non-directional mode. This makes it suitable, together with different communication schemes, for the protection of power lines and cables in complex network configurations, such as double-circuit, parallel lines, multiterminal lines, etc. Zone one, two and three has a built-in option for a phase selective operation.
R
jX
Rph-eRph-ph
Xph-e
Xph-ph
Zline
98000062.vmf
Xph-e reactive reach for ph-e faults
Xph-ph reactive reach for ph-ph faults
Rph-e resistive reach for ph-e faults
Rph-ph resistive reach for ph-ph faults
Zline line impedance
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 3
The additional distance protection zones four and five have the same basic functionality as zone 1–3, except phase-selective output sig-nals.
DesignDifferent digital signal processors calculate the impedance as seen for different measuring loops in different distance protection zones. The results are updated each millisecond for all measuring loops and each distance protec-tion zone separately. Measurement of the impedance for each fault follows the differen-tial equation, which considers a complete line replica impedance, as presented schemati-cally on Fig. 2.
Fig. 2 Schematic presentation of the impedance measuring principle.
Setting of all line parameters, such as positive sequence resistance and reactance as well as zero-sequence resistance and reactance, together with expected fault resistance for phase-phase and phase-earth faults, are inde-pendent for each zone. The operate character-istic is thus automatically adjusted to the line
characteristic angle. The earth-return com-pensation factor for the earth-fault distance protection is calculated automatically by the terminal itself.
Voltage polarisation for directional measure-ment uses continuous calculation and updat-ing of the positive sequence voltage for each measuring loop separately. This secures cor-rect directionality of the protection on differ-ent evolving faults within the complex network configurations. Positive-sequence memory voltage secures reliable directional operation on close-up three-phase faults.
The distance protection function blocks are independent of each other for each zone. Each function block comprises a number of different functional inputs and outputs, which are freely configurable to different external functions, logic gates, timers and binary inputs and outputs. This makes it possible to influence the operation of the complete mea-suring zone or only its trip function by the operation of the fuse-failure function, the power-swing-detection function, etc.
General fault criteria (GFC)
ApplicationThe general fault criteria is an independent impedance measuring function, which serves as an overall fault detection and/or phase selection element in all kinds of networks. Observe that the GFCn function is not used as start function, because full scheme measure-ment is utilised for the distance protection zones.
The GFC function is specially suitable in cases when the fault resistance to be detected exceeds the minimum expected load imped-ance. The shaped operate characteristic in the impedance plane (see Fig. 3) prevents the operation of the impedance measuring ele-ments for low load impedances and at the same time allows coverage of higher fault resistance with remote infeed of the fault current.
Rl jXl
Rfu(t)
i(t)
98000063.vmf
u t( ) Rl Rf+( ) i t( )Xl
ω-----∆ i t( )
∆ t------------⋅+⋅=
Rl line resistance
Rf fault resistance
Xl line reactance
ω 2 . π . f
f frequency
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 4
Functions (cont’d)Functions (cont’d)
Fig. 3 General fault criteria - schematic presen-tation of the operate characteristic in the impedance plane
Independent measurement for each fault loop secures reliable phase selection and correct operation for complex network faults, such as simultaneous faults on parallel circuits, evolving faults, etc. It also serves, together with an independent phase-preference-logic, as a selective protection function on cross-country faults in isolated or high-impedance earthed networks.Independent reactive reach setting for phase-phase and for phase-earth measurement secures high selectivity in net-works with different protective relays used for short-circuit and earth-fault protection.
DesignThe basic operate principle is the same as for the basic distance protection zones (see Fig. 2). It is possible to set the reactive reach in forward and reverse direction for phase-phase and for phase-earth measurement separately and independently of each other. Setting of the resistive reach can also be different for phase-phase and for phase-earth measure-ment.
The user can program the influence of the GFC function on the operation of the distance protection zones used. The GFC function can prevent the operation of the distance protec-tion zones with a reach longer than the reach
of the GFC elements, as long as the measured impedance is outside the GFC operate charac-teristic.
Operation of the distance protection zones can also be completely independent on the operation of the GFC function.
Power swing detection (PSD)
ApplicationThe power swing detection function detects power swings with a periodic swing time as low as 200 ms (i.e. slip frequency as high as 10% of the rated frequency on a 50 Hz basis). It detects swings under normal system condi-tions as well as during the dead-time of the single-pole reclosing cycle.
DesignThe operation of the PSD function is based on the measurement of the transition time that the power swing transient impedance needs to pass the impedance area between two imped-ance measuring characteristics (known as ∆Z/∆t measurement). The impedance measuring principle is the same as the one used for the distance protection zones (see Fig. 2). The transient impedance time is measured in all three phases separately and one-out-of-three or two-out-of-three operating modes can be selected permanently or according to the spe-cific system operate conditions.
The use of different timers for initial and con-secutive swings secures a high degree of dif-ferentiation between power swing and fault conditions. Built-in logic circuits and config-urable functional inputs makes it possible to combine the function with other functions and conditions, as well as to use it in the same way as with older distance relays.
Scheme communication logic (ZCOM)
ApplicationTo achieve fast fault clearing for a fault on the part of the line not covered by the instanta-neous zone 1, the stepped distance protection function can be supported with logic, utilising communication channels. One communica-tion channel, capable of transmitting an on/off signal, is required in each direction.
(98000064.vmf)
jXXfw
-Rf -Rld
Xrv
RRfRldARGld
Xfw Reactive reach in forward direction
Xrv Reactive reach in reverse direction
Rf Resistive reach related to fault resistance
Rld Resistive reach related to minimum load impedance
ARGld Load impedance angle
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 5
Depending on whether a reverse or forward directed impedance zone is used to issue the send signal, the communication schemes are divided in ‘Blocking’ and ‘Permissive’ schemes, respectively. This function can support any scheme communication require-ments.
Current reversal and weak end infeed logics (ZCAL)
ApplicationThis function is a complement to the ZCOM or to the ZC1P function.
In interconnected systems, the fault current can change direction when circuit breakers open to clear the fault. The permissive over-reach scheme should have a current reversal logic which, when activated, will prevent unwanted operation in case of current rever-sal.
If the infeed of the fault current at the remote end is too low to operate the forward directed measuring element, no carrier signal will be obtained from the remote end when there is a fault on the line and the communication scheme will not operate properly. This will be the case if the zero sequence source at the remote line end is too high, e.g. if the line cir-cuit breaker is open. The permissive commu-nication scheme should therefore include a weak end infeed logic which, when activated, reflects the carrier signal and thereby secures tripping. It can also be used to trip the local circuit breaker in cases when fault current distribution prevent carrier signal.
Automatic switch onto fault logic (SOTF)
ApplicationThe switch-onto-fault protection secures high-speed operation of the distance protec-tion on energising of faulty or short-circuited (earthed for safety reasons) power lines. Two operating modes are available for the detection of a breaker closing condition: Use of an auxiliary contact from a line CB control switch or the operation of a built-in dead-line-detection (DLD) function. The sec-ond mode is highly recommended for busbar
configurations where more than one circuit breaker can energise the protected line at one line end.
DesignThe function is active for one second after the breaker closing conditions have been reported by the external auxiliary contact or by the DLD function (automatic mode). The output signal will be generated if the fault has been detected within the non-directional reach of the selected distance protection zone. Config-urable function inputs and outputs make it possible to configure different use of the function. Note: The presence of the dead-line-detection function is absolutely required, if the function shall operate in the automatic mode.
Local acceleration logic (ZCLC)
ApplicationTo achieve fast fault clearing for faults on the whole line, also in cases where no communi-cation channel is available, local acceleration logic is used. The logic can be controlled either by the autorecloser or by the loss of the load current.
Current, phase wise
Instantaneous phase over-current protection (IOC)
ApplicationDifferent system conditions, such as source impedance and the position of the faults on long transmission lines, influence the fault currents to a great extent. The IOC function, with low overreaching of the measuring ele-ments, secure very short operate times, down to 10 ms and selective tripping for close-in faults on long power lines, where short fault clearing times are extremely important in maintaining system stability
DesignThe IOC function comprises a three phase instantaneous overcurrent protection. When single-pole tripping is required, the single and/or three-pole trip logic allows for phase selective starting signals from the function.
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 6
Functions (cont’d)Functions (cont’d) Time delayed phase over-current protection (TOC)
ApplicationThe time-delayed overcurrent protection operates in different system conditions for currents exceeding the pre-set value and remain high for longer than the delay time set on the corresponding timer. The function can also be used as supervision and fault detector for some other protection functions, to increase the security of a complete protection system. It can serve as a reserve function for the line distance protection, if activated under fuse failure conditions which disables the operation of the line distance protection.
DesignThe TOC function comprises a three phase time-delayed overcurrent protection. Phase selective starting signals are available from the function.
Breaker failure protection (BFP)
ApplicationThe breaker failure protection provides back-up protection in case of failure of the breaker to trip and clear the fault as requested by the object protection. It is obtained by checking that fault current persists after a brief time from the operation of the object protection.
DesignThe breaker failure protection is initiated by the trip commands from the protection func-tions, either internal to the terminal or from external commands through binary inputs. The start can be single-phase or three-phase.
The operate values of the three current mea-suring elements are settable within a wide setting range. The measurement is stabilised against the dc-transient that can cause unwanted operation with saturated current transformers. Time measurement is individ-ual for each phase. Two independent timers are available, T1 for repeated tripping of ‘own’ breaker and T2 which operates trip logic for adjacent breakers.
Current, residual (earth fault)
Current residual
ApplicationIn case of single-phase to earth faults, the primary fault resistance will vary with the network conditions and location of the fault. In many cases the fault resistance is much higher than the resistance that can be covered by an impedance measuring distance func-tion.
Earth faults with high fault resistance can be detected by measuring the residual current (3Io). Hence, the current residual functions can be used as complement to the impedance measuring distance function for sensitive earth fault detection.
To prevent unwanted operation when energis-ing a directly grounded power transformer, the functions are provided with 2nd harmonic restraint blocking feature.
The inverse time delayed function is provided with minimum operate current and minimum operate time for improved selectivity in cer-tain applications.
The instantaneous and time-delayed functions can be made directional together with logics for communication scheme cooperation, weak-end-infeed and current reversal.
DesignFollowing current residual functions are selectable;
1. Instantaneous
2. Time delayed;
- Independent time delay
3. Inverse time delayed;
- Normal inverse (NI)
- Very inverse (VI)
- Extremely inverse (EI)
- Logarithmic inverse (IDG)
NI, VI and EI according to IEC 255-3
4. Directional check and communication schemes
5. 4-Step earth fault protection (4 ele-ments)
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 7
The 4-step earth fault overcurrent protection has three current steps with independent time delay and a fourth current step with indepen-dent time delay or inverse time characteris-tics.
For all four steps, one of the following modes can be selected independently of other steps:
• Non-directional overcurrent function with-out second harmonic restraint
• Non-directional overcurrent function with second harmonic restraint
• Forward directional overcurrent function without second harmonic restraint
• Forward directional overcurrent function with second harmonic restraint
• Overcurrent function without second har-monic restraint, with blocking from the reverse direction measuring element
• Overcurrent function with second har-monic restraint, with blocking from the reverse direction measuring element
Voltage
Time delayed undervoltage protection (TUV)
ApplicationThe time-delayed undervoltage protection function is applicable in all situations, where reliable detection of low phase voltages is necessary. The function can also be used as a supervision and fault detection function for some other protection functions, to increase the security of a complete protection system.
DesignThe function operates as a three-phase volt-age measuring function, which issues an out-put signal if any of the three measured phase voltages falls below the pre-set value. The operation can be delayed by a built-in timer with settable time delay. The function can be disabled by various external conditions, for example by the operation of a fuse-failure
function or by an auxiliary contact detecting the open position of a line isolator. The func-tion has phase-selective indication.
Time delayed overvoltage protection (TOV)
ApplicationDifferent system conditions might increase the system voltage and cause damage to exposed primary and secondary equipment. The overvoltage protection detects such volt-age changes and initiates different measures to the power system. Both instantaneous and time-delayed operation of the overvoltage function are available.
DesignThe function measures the phase voltages of a three-phase system and calculates the residual (3U0) voltage. It initiates the corresponding output signals if the measured phase or the residual voltages exceed the pre-set value (starting) and remains high longer than the time delay set on the corresponding timers (trip). The function detects the phases which caused the operation.
Power system supervision
Broken conductor check (BRC)
ApplicationThe broken-conductor check function detects non-symmetrical current conditions in the three phases. The BRC function is especially suitable for the detection of broken conduc-tors on protected power lines and cables (series faults) without the presence of the additional short circuits (phase-earth or phase-phase faults). It will also detect inter-ruptions in secondary current circuits.
DesignThe function measures all three-phase cur-rents and operates when the ratio between the minimum of measured phase currents and the maximum phase current falls below the set value. The phase current must be higher than 20% of the terminal rated current.
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 8
Functions (cont’d)Functions (cont’d) Loss of voltage check (LOV)
ApplicationThe loss-of-voltage function is suitable for use in networks with automatic restoration function. The LOV function initiates a three-pole tripping of a circuit breaker, if all three phase voltages fall below the set value for longer than 7 seconds. The operation of the function is supervised by the fuse-failure function and the information about the closed position of an associated circuit breaker.
Overload supervision (OVLD)
ApplicationThe overload protection prevents excessive loading of power lines. Its operation is based on the measurement of the maximum phase current and its duration, which must not exceed the pre-set values. The operate current and the operate time are settable within a wide range.
Secondary system supervision
Current circuit supervision (CTSU)
ApplicationWrong information on current flowing in a protected element might influence the security (line differential protection) or dependability (line distance protection) of a complete protection system. The current cir-cuit supervision function, as built in REx 5xx terminals, detects different types of faults in CT secondary circuits and influence the oper-ation of corresponding main protection func-tions.
DesignThe function compares the 3I0 secondary currents from two different sets of current instrument transformers or different cores of the same instrument transformer. The func-tion issues an output signal when the differ-ence is greater than set value. The signal can be configured to block different protection functions or initiate the alarm.
Fuse failure supervision (FUSE)
ApplicationThe fuse-failure-supervision function contin-uously supervises the ac voltage measuring circuits between the voltage transformers and
the terminal. Different output signals can be used to block, in the case of faults in the ac voltage secondary circuits, the operation of the distance protection and other voltage-dependent functions, such as the synchro-check function, the undervoltage protection function, etc.
Negative-sequence based measurement is recommended in isolated or high-impedance earthed systems.
Zero-sequence based measurement is recom-mended in directly- or low-impedance earthed systems.
DesignThe function continuously measures the zero-sequence and/or the negative-sequence volt-age and current in three-phase ac voltage cir-cuits. It operates if the measured zero and/or negative-sequence voltage increases over the pre-set operate value, and if the measured zero and/or negative-sequence current remains below the pre-set operate value.
Two function output signals are available. The first depends directly on the voltage and current measurement. The second depends on the operation of the dead-line detection func-tion, to prevent unwanted operation of the distance protection if the line has been de-energised and energised under fuse-failure conditions. A special function input serves the connection to the auxiliary contact of the MCB (when used), to secure correct opera-tion of the function on simultaneous interrup-tion of all three measured phase voltages.
Control
Command control (16 signals)
ApplicationThe terminals may be provided with 16 out-put functions that can be controlled either from a Substation Automation system or from the built-in HMI. The output functions can be used, for example, to control high-voltage apparatuses in switchyards. For local control functions, the built-in HMI can be used. Together with the configuration logic circuits, the user can govern pulses or steady output signals for control purposes within the terminal or via binary outputs.
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 9
Synchro-check and energising check (SYNX)
ApplicationThe synchro-check function is used for con-trolled interconnection of a line in an already interconnected network. When used, the function gives an enable signal at satisfactory voltage conditions across the breaker that is to be closed. The synchro-check function measures the voltages on the busbar side and the line side. It operates and permits closing of the circuit-breaker when the set conditions are met, with respect to the voltage difference (UDiff), the phase-angle difference (PhaseDiff), and the frequency difference (FreqDiff).
The energising condition can be set to allow energising in one, or the other, or both direc-tions, e.g. live busbar and dead line. It is pos-sible to have different energising settings for a manual close command and an autoreclose command.
DesignThe synchro-check for double busbar arrangements includes the voltage selection function. From the auxiliary contacts of the breakers and disconnectors, the terminal can select the right voltage for the synchronism and energising function. The function is also designed to allow manual closing when both sides of the breaker are dead.
PhasingNote: This function is not separately avail-able. It is an addition to the Synchro-check and energising check described above.
ApplicationPhasing of network breakers is to be per-formed, together with synchro-check, when two asynchronous systems are going to be connected in order to avoid stress on the net-work and its components. The phasing func-tion compensates for measured slip frequency as well as the circuit-breaker closing delay.
DesignThe phasing function also includes the synchro-check function. The phasing func-tion is used when the difference in frequency is less than the set value of the frequency difference for phasing and larger than the set value for synchro-check.
Autoreclosing (ARxx)
ApplicationThe reclosing function can be selected to perform single-, two- and/or three-phase reclosing from eight single-shot or multi-shot reclosing programs. The three-phase auto-reclose open time can be selected to give either high-speed autoreclosing or delayed autoreclosing. Three-phase autoreclosing can be performed with or without the use of the synchronism check or energising function.
DesignThe autoreclosing function co-operates with the line protection functions, the trip function, the circuit breaker and the synchro-check function. It can also be influenced by other protection functions through binary input sig-nals.The autoreclosing is a logical function built up by logical elements.
Logic
Three-pole trip logic (TRIP)
ApplicationThe function is intended for use when only a simultaneous three-pole tripping of the circuit breaker(s) is required.
DesignTwo functional inputs initiate the outgoing trip command. The first will initiate the trip command only if the function is not blocked or its operation has not been switched off or the terminal is not in a test mode. The second functional input overrides all the above con-ditions. It is intended for use together with station protection functions, such as breaker failure protection or transfer trip commands received from the remote ends of protected power lines.
Single- or two-pole trip logic (TRIP)
ApplicationTRIP operates in single-pole trip mode for single-phase faults, in two-pole operating mode for two-phase faults (with or without earth) and in three-pole trip mode for three-phase faults. It is also possible to achieve three-pole tripping for both one-phase and two-phase faults.
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 10
Functions (cont’d)Functions (cont’d) The function is applicable for all terminals which have built-in phase selection function-ality and is used in applications where single-pole tripping is required for single-phase faults due to system stability reasons. The two-pole operating mode can be used on double-circuit parallel lines with single-pole breakers.
DesignSpecial functional inputs are provided for the initiation of a single, two and three-pole trip command. Decision to initiate outgoing trip signals in different phases depends on a pres-ence of corresponding phase selective signals on specially provided functional inputs. Additional logic circuits secure a three-pole final trip command in the absence of the required phase selection signals.
The function is equipped with logic circuits, which secure correct operation on evolving faults as well as after the reclosing on persis-tent faults. Special function inputs are pro-vided to override the internal conditions and initiate an instantaneous three-pole trip com-mand. These inputs could be initiated by dif-ferent external functions, such as station breaker failure protection, transfer trip from the remote end line terminal, etc.
Pole discordance logic, contact based (PD)
ApplicationBreaker pole position discordance can occur on operation of a breaker with independent operating gears for the three poles. The rea-son may be an interruption in the closing or trip coil circuit, or a mechanical failure result-ing in a stuck breaker pole. A discordance caused by one pole failing to close or open can be tolerated for a limited time, for instance during a single-phase trip-reclosing cycle.
DesignThe operation of the pole discordance protec-tion is based on checking the position of the breaker auxiliary contacts. Three parallel nor-mally-open contacts in series with three nor-mally-closed contacts in parallel for the respective breaker poles form a condition of pole discordance, connected to a binary input dedicated for the purpose.
Additional configurable logic
ApplicationConfigurable logic is included in basic. Addi-tional logic circuits including more AND/OR gates are also available as an option. With this logic the user can configure different logical functions in the terminals to suit special requirements for different applications.
Communication channel test logic (CCHT)
ApplicationMany applications in secondary systems require testing of some functionality with confirmed information about the result of the test. Channel test function perform testing of communication (power line carrier) channels in applications, where it is not possible to monitor them continuously by some other means.
DesignThe logic initiates the sending of an impulse (carrier send signal), which starts the opera-tion of different external functions and checks the feedback from the external function. It reports the successful or non-successful response on initiated test. It is also possible to abort the test with an external signal, which overrules all internal process.
Binary signal transfer to remote end (RTC)
ApplicationThe binary signal transfer function is prefera-bly used for sending communication scheme related signals, transfer trip and/or other binary signals required at the remote end. Up to 32 freely selectable binary signals, internal or external to the terminals, can be transmit-ted in both directions over a protected line.
DesignTogether with the binary signals internal to the terminal, the function is utilising binary inputs and outputs. The function can be pro-vided with various 56/64 kbit/s communica-tion modules for fibreoptic or galvanic connection. For more information about the available communication alternatives, see ‘Remote end data communication’.
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 11
Binary signal interbay communication
ApplicationOne receiving function block for 16 binary signals and with fast execution time is used to receive information over the LON bus from other REx 5xx terminals. The other terminals must have a corresponding Event function block to send the information. Additional 79 receiving blocks with slower execution time are also available as an option.
Monitoring
Disturbance recorder (DREP)
ApplicationThe disturbance recording function is an important part of a station monitoring system, which enables the evaluation of different events within the power system. The high-performance disturbance recorder can memo-rise up to 10 analogue channels and 48 binary signals (internal signals to the terminal and/or external signals connected to the binary inputs of the terminal). Any of the recorded analogue channels and binary signals can be programmed to start a recording.
Furthermore, analogue channels are program-mable for over- and under-functions and the binary signals can start recording on transi-tion from a logical 0 to a logical 1 and vice versa. Pre-fault, post-fault and limit time can be set in wide ranges. Collection of distur-bance records is possible locally as well as remotely, using HMI software. Evaluation of the disturbances can be done in the program, type REVAL.
Event recorder (EVR)
ApplicationAn event recording function is available. It presents in a logical order, starting and trip-ping signals that have occurred in the termi-nal. Up to 150 time-tagged events for each of the last 10 recorded disturbances are stored. Also internal events, such as setting changes, are stored in the event recorder.
Fault locator (FLC)
ApplicationAn accurate fault locator is an essential com-plement to the line protection. The fault locator provides distance to the fault together with information about the measuring loop that has been used in the calculation. Possi-bility of recalculation with changed para-meter settings exists. Information on the last 10 disturbances are available.
The fault locator algorithm compensates the effect of the load currents, the apparent fault resistance and zero sequence mutual imped-ance.
Trip value recorder (TRVAL)
ApplicationInformation on the actual primary and secon-dary phasors of the voltages and currents are available in the trip value recorder. The pre-fault and fault values of the applicable volt-ages and currents are recorded with their phase relations for the last 10 disturbances.
Increased measuring accuracy for U, I, P, Q
ApplicationTo reach a high accuracy in the measure-ments, a factory calibration of the five current and the five voltage input transformers is made.
Metering
Pulse counter logic
ApplicationThe pulse counter function provides the Sub-station Automation system with the number of pulses, which have been accumulated in the terminal during a defined period of time, for calculation of, for example, energy val-ues. The pulses are captured on the Binary input module that is read by the Pulse counter function. The number of pulses in the counter is then reported via LON to the station HMI or read via SPA as a service value. The nor-mal use for this function is the counting of energy pulses for kWh and kVarh in both directions from external energy meters.
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 12
Functions (cont’d)Functions (cont’d) Miscellaneous
Activation of active setting group (GRP)
ApplicationDifferent system operate conditions require different settings of protection functions used. The 500 series terminals have basically four sets of independent setting groups built-in, which contains all setting parameters for all protection-, control- and monitoring func-tions used. The user can change the active setting group at any time, locally by means of local HMI or a personal computer, or remotely by means of SMS and SCS as well as by activation of the corresponding func-tional inputs to the GRP function. Adaptive changing of the active setting group is possi-ble by means of the GRP and some other functions, available within the 500 series ter-minals.
DesignThe GRP functional block has four functional inputs, each corresponding to one of the set-ting groups stored within the terminal. Acti-vation of any of these inputs changes the active setting group. Four functional output signals are available for the configuration purposes, so that continuous information on active setting groups is available for different purposes.
Dead-line detection (DLD)Note: This function is not separately avail-able. It is an addition to the automatic switch-onto-fault function, the weak-end infeed detection function and the fuse failure func-tion.
ApplicationDifferent protection, control and monitoring functions require for their proper operation information on the condition of a protected element, such as power lines, etc. The DLD function detects the conditions of a protected element, whether or not it is connected to the rest of the power system.
DesignThe function continuously measures all three phase currents and phase voltages of a pro-tected power line. The line is declared as a dead (non-energised) line if all three mea-sured currents and voltages fall below the pre-set values for longer than 200 ms.
The function operates on a phase-segregated basis, if single-pole trip logic has been selected for a particular terminal.
Serial communication
ApplicationOne or two optional optical serial interfaces, one with SPA or IEC 870-5-103 and the other with LON protocol, for remote communica-tion, enable the terminal to be part of a Sub-station Control System (SCS) and/or Substation Monitoring System (SMS). These interfaces are located at the rear of the termi-nal.
Two buses can be built up, one independent of another, each of them with different func-tionalities regarding monitoring and setting of the functions in the terminal. Plastic fibres can be used up to a distance of 30 m (90 ft.). Glass fibres for distances up to 500 m (1500 ft.).
An optical network can be used within the SCS system. This enables communication with the terminal through the LON bus from the operator’s workplace and the control centre.
The second bus is used for SMS. It can include different numerical relays/terminals from the PANORAMA range with remote communication possibilities. Connection to a personal computer (PC) can be made directly (if the PC is located in the substation) or by telephone modem through a telephone net-work with CCITT characteristics.
Time synchronisation
ApplicationThe terminal has an internal clock, which can be synchronised by means of a minute pulse through a binary input or via the station bus communication.
Local HMI
ApplicationThe HMI (Human-Machine-Interface) serves as an information unit, presenting in a logical order starting and tripping signals that have appeared during each of the last ten recorded disturbances.
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 13
Furthermore, each of the two local HMI pos-sibilities takes over the functionality of the measuring instruments such as the A-meter, V-meter, VAr-meter, W-meter and Hz-meter. The current statuses of all binary input sig-nals and internal logical signals are available too.
Ac/dc measurements
ApplicationThis function provides three-phase or single-phase values of voltage and current. At three-phase measurement, the values of active power (W), reactive power (var), frequency (Hz) and the mean value for voltage (U) and current (I) can be calculated.
Alarm limits to be used as conditions in the configuration logic can be set. Besides the direct inputs of voltage and current, analogue inputs for mA signals are also available.
Self-supervision with internal event recorder
ApplicationThe self-supervision function operates con-tinuously and includes:
- Normal micro-processor watchdog function
- Checking of digitized measuring signals
- Checksum verification of PROM contents
- Checksum verification of types of signal communication
- Read-Write-Read-Write cycling of the memory cells and internal registers
The self-supervision status is available from the local HMI or via a SMS or SCS system.
When an internal fault has occurred, you can retrieve extensive information about the fault from the list of internal events available in the terminal from SMS or SCS. A time-tagged list with the date and time of the last 40 inter-nal events is available here.
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 14
Functions (cont’d)Functions (cont’d) Remote end datacommunication
ApplicationThe line distance protection terminals are using the communication facilities below, except the dedicated links, together with the optional function, binary signal transfer to remote end.
The fibre optical module can communicate without additional units over dedicated fibres up to around 30 km. When greater distances are required to be covered, an external FOX 20 system, available from ABB Net-work Partner Ltd. (Switzerland), can be used. The FOX 20 works as a repeater in this case and is optically connected, sending the sig-nals on dedicated fibres. With this configura-tion it is possible to cover distances up to 120 km on single-mode fibres. The FOX 20 can also operate as a multiplexer, in which case a number of 64 kbit/s data channels and RS 232 channel can be transmitted in parallel.
Direct galvanic connection to a multiplexer can be done up to a distance of 100 m. The built-in interface in these modules can sup-port the CCITT standard V.35/36 contra-directional, X.21 64 kbit/s and EIA RS 530/544 contra-directional 56 kbit/s communica-tion modes. V.35/36 and RS 530/544 co-directional communication modes can be sup-plied upon request.
The CCITT G.703 can be connected over an optional RS 530/544 contra-directional to G.703 converter. The distance between the terminal and the converter is limited to 10 meters.
When the distance is too great for direct galvanic connection, a short-range optical modem is used. The distance can be up to 5 km and the optical/galvanic converter can directly support CCITT standard V.35/36 contra-directional as well as X.21 and G.703 communication modes.
Direct galvanic communication over twisted pair cable for distances up to 4 km can be done using the short range galvanic modem.
Fig. 4 Communication alternatives(not applicable for REC 561)
OpticalfibresREx 5xx 21-15X/16X V.35/36 (15X)
X.21 (16X)G.703 (16X)
< 5 km
RS 530/422REx 5xx ConverterG.703
< 10 m
(X80
039-
2_2)
Opticalfibres
< 30 km
REx 5xx REx 5xx
otherusers
REx 5xx
< 30 km MUX
FOX 20
Opticalfibres
to theother end
Twistedpair cable
< 4 km
REx 5xx REx 5xx
V.35, V.36, X.21, RS53056/64 kbit/s
REx 5xx
< 100 m
otherusers
MUX
Galvanic
to theother end
Dedicated link, fibre optical connection
Multiplexed link, fibre optical connection
(X80
039-
2_5)
Multiplexed link, galvanic connection
Multiplexed link, short-range fibre optical connec-tion
(X80039-2_7)
(X80
039-
2_6)
Dedicated link, short-range galvanic modem
(X80
039-
2_4)
(X80039-2_8)
G.703 con-
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 15
Hardwaredesign
The REx 5xx series mechanical packaging and connecting system consist of a case in which printed circuit boards are inserted. The case is available in different sizes (widths) with the height 6U (265.9 mm). REL 511 is normally assembled in a case with the width 1/2x19". The cover is made of preplated steel sheet, with the different details spot welded together. The outside surfaces are painted light beige.
The front plate, which is made of aluminium profile, has a cut-out with a local HMI module.
The degree of protection is IP 40, according to IEC 529, for cases with the widths 1/2x19" and 3/4x19". IP 54, for the front area, can be obtained with accessories for flush and semi-flush mounting.
The REx 5xx series can be flush, 19"-struc-ture or projection mounted with different mounting kits available. Products assembled in the 1/2x19" and 3/4x19" cases can also be semi-flush mounted. Two cases 1/2x19" can be mounted side-by-side for maximum utilis-ing of space in 19" panels. A test switch, type RTXP, and/or COMBIFLEX modules are added in separate cases of the same basic design as the mechanical packaging of the 500 series. These cases, type RHGS, exist in sizes 1/4x19" and 1/2x19" and can be mounted by the side of REx 5xx products smaller than 1/1x19".
All connections are made on the rear of the cases with compression type screw terminal blocks for electrical connections. Serial com-munication connections are made by fibre optic connectors type Hewlett Packard (HFBR) for plastic fibres or bayonet type ST for glass fibres.
Hardware modules
Transformer module;Five current and five voltage input transformers.
Power supply module;– For case size 1/2x19" and 3/4x19", this module includes a regulated DC/DC converter that provides
stabilised auxiliary voltage to all static circuits together with 4 binary inputs and 5 binary outputs.
A/D conversion module;For 10 analogue signals, operating with a sampling frequency of 2000 Hz.
Main processing module;All information is processed or passed through this module, such as configuration, settings and communication.
Signal processing module;Module with up to 12 digital signal processors, performing all measuring functions.
Binary input/output modules;Binary I/O module with 8 inputs, 10 outputs and 2 fast signalling outputs.Binary input module with 16 inputs.Binary output module with 24 single outputs or 12 double-pole command outputs including super-vision function.
Analogue input module;mA input module for 6 analogue channels.
Communication modules;Module for multiplexed link, galvanic connection. Connector type 25 pin D-sub for V35/36, RS 530/422 contra-directional or 15 pin D-sub for X.21.Module for multiplexed link, fibre optical connection. The same module is used for dedicated link, fibre optical connection (≤ 30 km). Connector type FC (FC/PC).Module for multiplexed link, short range fibre optical connection (≤ 5 km). Connector bayonet type ST.Module for dedicated link, short range galvanic connection (≤ 4 km), twisted pair cable. Connection made on screw terminals.
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 16
Hardware design (cont’d)Hardware design (cont’d)
Layout and dimensions
C = 4-10 mmD = 16.5 mmE = 187.6 mm without protective cover,
228.6 mm with protective coverF = 106.5 mmG = 97.6 mm without protective cover,
138.6 mm with protective cover
Case size A B C D E F G H I J K
6U x 1/2 223.7 205.7 203.7 – –
6U x 3/4 265.9 336 204.1 245.1 255.8 318 190.5 316 – 227.6 –
(mm)
Protection cover
9600
0310
9600
0309
Mounting angle
9600
0285
Flush mounting Semi-flush mounting
9600
0286
Cut-out dimensions
Case size A ±1 B ±1
6U x 1/2 210.1
6U x 3/4 322.4 259.3
(mm)
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 17
Case size A B C D E
6U x 1/2 292 267.1
6U x 3/4 404.3 379.4 272.8 390 247
(mm)
9600
0287
960 0
0288
Wall mounting
Side-by-side mounting
Fixing plate
9600
0311
9600
0312
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 18
Hardware design (cont’d)Hardware design (cont’d)
Rear view layout
Fig. 5 Rear view of REL 511 (standard case size, 1/2x19”)
Terminal connections
Fig. 6 Terminal connection without test switch
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 19
Fig. 7 Terminal connection with test switch (internal earthing)
Fig. 8 Terminal connection with test switch (external earthing)
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 20
Technical dataTable 1: Energising quantities, rated values and limits
Quantity Rated value Nominal range
Current
Operation rangePermissive overload
Burden
Ir = 1 or 5 AIr = 1 or 5 A for I5(0.004-100) × Ir4 × Ir cont.100 × Ir for 1 s *)
< 0.25 VA at Ir
(0.2-30) x Ir
Ac voltage Ph-Ph
Operation rangePermissive overload
Burden
Ur = 100/110/115/120 VUr = 200/220/230/240 V(0.001-1.5) x Ur1.5 × Ur cont.2.5 × Ur for 1 s< 0.2 VA at Ur
(80-120) % of Ur
Frequency fr = 50/60 Hz ± 5 %
Auxiliary dc voltage ELpower consumption
basic terminaleach output relay
power dissipationRL24 = (24/30)VRL48 = (48/60)VRL110 = (110/125)VRL220 = (220/250)V
EL = (48-250) V
≤ 16 W≤ 0.15 W
max. 0.05 W/inputmax. 0.1 W/inputmax. 0.2 W/inputmax. 0.4 W/input
± 20 %
Binary input/output moduledc voltage RL
power consumptioneach I/O-moduleeach output relay
power dissipationRL24 = (24/30)VRL48 = (48/60)VRL110 = (110/125)VRL220 = (220/250)V
RL24 = (24/30) VRL48 = (48/60) VRL110 = (110/125) VRL220 = (220/250) V
≤ 1.0 W≤ 0.15 W
max. 0.05 W/inputmax. 0.1 W/inputmax. 0.2 W/inputmax. 0.4 W/input
± 20 %± 20 %± 20 %± 20 %
Binary input moduledc voltage RL
power consumptioneach input module
power dissipationRL24 = (24/30)VRL48 = (48/60)VRL110 = (110/125)VRL220 = (220/250)V
RL24 = (24/30) VRL48 = (48/60) VRL110 = (110/125) VRL220 = (220/250) V
≤ 0.5 W
max. 0.05 W/inputmax. 0.1 W/inputmax. 0.2 W/inputmax. 0.4 W/input
± 20 %± 20 %± 20 %± 20 %
Binary output modulepower consumption
each output moduleeach output relay
≤ 1.0W≤ 0.25 W
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 21
mA input moduleinput range
input resistance
power consumptioneach mA-moduleeach mA-input
± 20 mA
Rin = 194 Ω
≤ 4 W≤ 0.1 W
Ambient temperature 20 °C -5 °C to +55 °C
Ripple in dc auxiliary voltage max. 2 % max. 12 %
Relative humidity (10-90) % (10-90) %
*) max. 350 A for 1 s when COMBIFLEX test switch included together with the productI2t = 10 kAs
Table 2: Influencing factors, Permissible influence
Dependence on: Within nominal range Within operative range
Ambient temperature 0.01 % / °C Correct function
Ripple in auxiliary dc voltage Negligible Correct function
Interruption in auxiliary dc voltagewithout resettingcorrect functionrestart time
< 50 ms0 - ∞< 100 s
< 50 ms0 - ∞< 100 s
Table 3: Electromagnetic compatibility tests
Test Type test values Reference standards
1 MHz burst disturbanceFor short-range galvanic modemFor galvanic interface *)
- common mode- differential mode
2.5 kV2.5 kV
1 kV0.5 kV
IEC 60255-22-1, Class IIIIEC 60255-22-1, Class III
Class IIClass II
Electrostatic dischargeFor short-range galvanic modemFor galvanic interface *)
8 kV8 kV-
IEC 60255-22-2, Class IIIIEC 60255-22-2, Class III
Fast transient disturbanceFor short-range galvanic modemFor galvanic interface *)
4 kV4 kV1 kV
IEC 60255-22-4, Class IVIEC 60255-22-4, Class IVClass II, level 2
Radiated electromagnetic field disturbance
10 V/m, (25-1000) MHz IEC 60255-22-3, Class IIIIEEE/ANSI C37.90.2
*) For FOX6Plus the following modes are not applicable:- V.36/V11 Co-directional according to CCITT- RS530/RS422 Co-directional according to EIA
Table 4: Insulation tests (reference standard: IEC 60255-5)
Test Type test values
Dielectric testFor short-range galvanic modemFor galvanic interface *)
2.0 kV ac, 1 min2.5 kV ac, 1 min1.0 kV ac, 1 min
Impulse voltage testFor short-range galvanic modemFor galvanic interface *)
For other circuits
5 kV, 1.2/50 µs, 0.5 J1 kV, 1.2/50 µs, 0.5 J5 kV, 1.2/50 µs, 0.5 J
Insulation resistance >100 MΩ at 500 V dc
Table 1: Energising quantities, rated values and limits
Quantity Rated value Nominal range
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 22
Technical data (cont’d)Technical data (cont’d)Table 5: CE-mark
Test Type test values
Immunity EN 50082-2
Emissivity EN 50081-2
Low voltage directive EN 50178
Table 6: Mechanical tests
Test Type test values Reference standards
Vibration Class I IEC 60255-21-1
Shock and bump Class I IEC 60255-21-2
Seismic Class I IEC 60255-21-3
Table 7: Contact data (reference standard: IEC 60255)
Function or quantity Trip and Signal relays Fast signal relays
Max system voltage 250 V ac, dc 250 V ac, dc
Test voltage across open contact, 1 min 1000 V rms 800 V dc
Current carrying capacitycontinuous1 s
8 A 10 A
8 A10 A
Making capacity at inductive load with L/R>10 ms
0.2 s1.0 s
30 A10 A
0.4 A0.4 A
Breaking capacity for ac, cos ϕ>0.4 250 V/8.0 A 250 V/8.0 A
Breaking capacity for dc with L/R<40ms 48 V/1 A110 V/0.4 A220 V/0.2 A250 V/0.15 A
48 V/1 A110 V/0.4 A220 V/0.2 A250 V/0.15 A
Maximum capacitive load - 10 nF
Table 8: Additional General Data
Weight approx. 1/2 of 19" rack: ≤ 8.5 kg3/4 of 19" rack: ≤ 11 kg
Dimensionswidth
heightdepth
1/2 of 19" rack: 223.7 mm3/4 of 19" rack: 336 mm267 mm245 mm
Storage temperature -40 °C to +70 °C
Table 9: Front communication
Function Value
Protocol SPA
Communication speed 300, 1200, 2400, 4800 or 9600 bit/s
Slave number 1 to 899
Remote change of active group allowed yes
Remote changed of settings allowed yes
Connectors special electric/optic cable
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 23
Line impedance
Table 10: Serial communication (SPA)
Function Value
Protocol SPA
Communication speed 300, 1200, 2400, 4800, 9600, 19200 or 38400 bit/s
Slave number 1 to 899
Remote change of active group allowed yes/no
Remote changed of settings allowed yes/no
Connectors and optical fibres glass or plastic
Table 11: Serial communication (LON)
Function Value
Protocol LON
Communication speed 1.25 Mbit/s
Connectors and optical fibres glass or plastic
Table 12: Serial communication (IEC 870-5-103)
Function Value
Protocol IEC 870-5-103
Communication speed 9600, 19200 bit/s
Connectors and optical fibres glass or plastic
Table 13: ZM1, 2, 3, 4, 5 - Zone impedance measuring elements
Function Value
Operate timetypicalmin and max
28msPlease refer to the separate isochrone diagrams
Min. operate current (10-30) % of Ir in steps of 1 %
Resetting ratio typical 105 %
Resetting time typical 40 ms
Output signals start and tripzone 1-3zone 4,5
three-phase or single-phase and three-phasethree-phase
Setting accuracy included in the measuring accuracy
Number of zones 3, 4 or 5, direction selectable
Impedance setting range at Ir = 1 A *)
reactive reachpositive-sequence reactancezero-sequence reactance
resistive reachpositive-sequence resistancezero-sequence resistance
fault resistancefor phase - phase faultsfor phase - earth faults
(0.1-400) Ω /phase in steps of 0.01 Ω(0.1-1200) Ω /phase in steps of 0.01 Ω
(0.1-400) Ω /phase in steps of 0.01 Ω(0.1-1200) Ω /phase in steps of 0.01 Ω
(0.1-400) Ω /loop in steps of 0.01 Ω(0.1-400) Ω /loop in steps of 0.01 Ω
Setting range of timersfor impedance zones (0-60) s in steps of 1 ms
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 24
Technical data (cont’d)Technical data (cont’d)
Static accuracy at 0° and 85°voltage range (0.1-1.1) x Urcurrent range (0.5-30) x Ir
± 5 %
Static angular accuracy at 0° and 85°voltage range (0.1-1,1) x Urcurrent range (0.5-30) x Ir
± 5°
Max dynamic overreach at 85° measured with CVT’s 0.5 < SIR < 30
± 5 %
*) Divide specified values by 5 for Ir = 5A
Table 14: GFC - General fault criteria
Function Value
General fault criteria (GFC) - impedance setting range at Ir = 1A *)
reactive reach forwardpositive-sequence reactancezero-sequence reactance
reactive reach reverse positive-sequence reactancezero-sequence reactance
resistive reach (forward & reverse)for phase - phase faultsfor phase - earth faultsload encroachmentsafety load impedance angle
(0.1-400) Ω/phase in steps of 0.01 Ω(0.1-1200) Ω/phase in steps of 0.01 Ω
(0.1-400) Ω/phase in steps of 0.01 Ω(0.1-1200) Ω/phase in steps of 0.01 Ω
(0.1-400) Ω/loop in steps of 0.01 Ω(0.1-400) Ω/loop in steps of 0.01 Ω(0.1-400) Ω/loop in steps of 0.01 Ω(5-45)° in steps of 1°
General fault criteria (GFC) - overcurrent setting range
phase currentsresidual current
(10-400) % of Ir in steps of 1 %(10-150) % of Ir in steps of 1 %
Timers for the GFC criteriafor phase measuring for earth fault measuring
(0-60) s in steps of 1 ms(0-60) s in steps of 1 ms
Phase preference logic:operate residual current 3I0operate residual voltage 3U0voltage phase selectionphase - phasephase - earthcyclic tripping phase preferencenon-cyclic tripping phase preferencenon-cyclic blocking phase preference
(20-200) % of Ir in steps of 1 %(30-70) % of Ur in steps of 1 %
(10-100) % of Ur in steps of 1 %(20-170) % of Ur in steps of 1 %L1L3L2, L3L1L2L1L3L2, L1L2L3, L3L2L1, L3L1L2, L2L1L3, L2L3L1L1L3L2, L1L2L3, L3L2L1, L3L1L2, L2L1L3, L2L3L1
*) Divide specified values by 5 for Ir = 5A
Table 13: ZM1, 2, 3, 4, 5 - Zone impedance measuring elements
Function Value
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 25
Table 15: PSD - Power swing detection
Function Setting range Accuracy
Impedance setting range at Ir =1A *)
reactive reach, XINresistive reach, RIN
reach multiplication factorreach multiplication factor
(0.1-400) Ω/phase in steps of 0.01 Ω(0.1-400) Ω/phase in steps of 0.01 Ω(120-200) % of XIN in steps of 1 %(120-200) % of RIN in steps of 1 %
Initial PSD timerFast PSD timerHold timer for activation of fast PSD timerHold timer for PSD detectedTimer overcoming 1ph reclosing dead timeTimer to time delay block by the residual currentOn delay timer for blocking of output signal at very slow swings
(0-60) s in steps of 1 ms(0-60) s in steps of 1 ms
(0-60) s in steps of 1 ms(0-60) s in steps of 1 ms
(0-60) s in steps of 1 ms
(0-60) s in steps of 1 ms
(0-60) s in steps of 1 ms
Static accuracy at 0° and 85° voltage range (0.1-1.1) x Urcurrent range (0.5-30) x Ir
± 5 %
Static angular accuracy at 0° and 85° voltage range (0.1-1.1) x Urcurrent range (0.2-30) x Ir
± 5°
*) Divide specified values by 5 for Ir = 5A
Table 16: ZCOM, ZC1P - Communication logic - Single- and/or three-phase
Function Setting range
Operational mode Intertrip / Permissive underreach / Permissive overreach / Blocking
Coordination timersCoordination timerMinimum send time
(0-60) s in steps of 1 ms (0-60) s in steps of 1 ms
Unblocking logicsecurity timer (0-60) s in steps of 1 ms
Table 17: ZCAL - Communication additional logic
Function Setting range
Weak end infeed trip and echo functionOperate voltage U<
phase - phase
phase - earthCoordination time
(20-170) % Ur in steps of 1%
(10-100) % Ur in steps of 1%(0-60) s in steps of 1 ms
Current reversal logicactivation time delaytime delay of CR, CS
(0-60) s in steps of 1 ms(0-60) s in steps of 1 ms
Table 18: SOTF - Automatic switch onto fault logic
Function Setting range
Minimum duration for openbreaker condition
200 ms
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 26
Technical data (cont’d)Technical data (cont’d)
Current
Table 19: DLD - Dead line detection
Function Setting range
Automatic check of dead line conditionoperate phase voltageoperate phase current
(10-100) % of Ur in steps of 1%(5-100) % of Ir in steps of 1%
Table 20: ZCLC - Local acceleration logic
Function Setting range
Operation zone extension On / Off
Operation loss of load On / Off
Table 21: IOC - Instantaneous overcurrent protection
Setting range Operate time Accuracy
Operate current I>>phase measuring elements
residual measuring elements
(50-2000)% of Irin steps of 1%
(50-2000)% of Irin steps of 1%
-
Minimum operate time at I > 10 x Iset max 15 ms
Dynamic overreach at τ < 100 ms - - < 5 %
Table 22: TOC - Time delayed overcurrent protection
Function Setting range Accuracy
Operate current I>phase measuring elements
residual measuring elements
(10-400) % of Ir in steps of 1 %
(10-150) % of Ir in steps of 1 %
Time delayphase measuring elementsresidual measuring elements
(0-60) s in steps of 1ms(0-60) s in steps of 1ms
Dynamic overreach at τ < 100 ms - < 5 %
Table 23: BFP - Breaker failure protection
Function Setting range
Operate current (one measuring element per phase)
(5-200) % of Ir in steps of 1 %
Retrip time delay t1 (0-60) s in steps of 1 ms
Back-up trip time delay t2 (0-60) s in steps of 1 ms
Value
Trip operate time max 18 ms
Operate time for current detection max 10 ms
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 27
Table 24: TEF - Time delay earth-fault
Function Setting range Accuracy
Basic current, inverse time delay: 3I0 (5-300) % of Ir in steps of 1 %
Selection of E/F protection Non-directional or Directional
Operate value for directionalcurrent measurement
forward 3I0 at ϕ = 65°reverse
(5-35) % of Ir in steps of 1 %60 % of the setting for forward operation
Characteristic angle 65° lagging
Independent time delay (0-60) s in steps of 1 ms ± 0.5 % ± 10 ms
Normal inverse characteristic k = (0.05-1.1) in steps of 0.01 IEC 255-3 class 5 ± 60 ms
Very inverse characteristic k = (0.05-1.1) in steps of 0.01 IEC 255-3 class 7.5 ± 60 ms
Extremely inverse characteristic k = (0.05-1.1) in steps of 0.01 IEC 255-3 class 7.5 ± 60 ms
Logarithmic characteristic± 5 % of t at I = (1.3-29) x 3I0
Min. operate current for dependent characteristic IMin (100-400) % of 3I0 in steps of 1 %
tMin for dependent charact. (0-60) s in steps of 1 ms
Rated voltage Ur
Minimum polarising voltage 1 % of Ur
Operate time Value
Resetting time < 70 ms
Table 25: EFC - Earth-fault communication
Function Setting range
Communication scheme None, Permissive, Blocking
Coordination timer (0-60) s in steps of 1 ms
Table 26: EFCA - Earth-fault communication additional logic
Function Setting range
Operate voltage for WEI tripCurrent reversal pickup timerCurrent reversal delay timer
(5-70) % of Ur in steps of 1 %(0-60) s in steps of 1 ms(0-60) s in steps of 1 ms
Table 27: EF4 - 4 Step earth-fault overcurrent protection
Function Setting range Accuracy
Current level for step 1 (50-2500) % of Ir in steps of 1 %
Definite time delay for step 1 (0-60) s in steps of 1 ms
Current level for step 2 (20-1500) % of Ir in steps of 1 %
Definite time delay for step 2 (0-60) s in steps of 1 ms
Current level for step 3 (20-1500) % of Ir in steps of 1 %
Definite time delay for step 3 (0-60) s in steps of 1 ms
Current level for step 4 definite time delay or minimum operate current for inverse time delay
(4-440) % of Ir in steps of 1 %
t 5 8 1– 35 ln× I3I0--------,,=
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 28
Technical data (cont’d)Technical data (cont’d)
Voltage
Power system supervision
Definite time delay for step 4 or inverse time additional delay
(0-60) s in steps of 1 ms
Basic current for inverse time delay (4-110) % of Ir in steps of 1 %
Time multiplier for inverse time delay (0.05-1.10) s in steps of 0.01 s
Inverse time minimum delay (0-60) s in steps of 1 ms
Operate value for directional current measurement
forward 3I0 at ϕ = 65°reverse
(5-40) % of Ir in steps of 1 %60 % of the setting for forward operation
Level of harmonic restrain (20 or 32) % of fundamental level
Characteristic angle 65° lagging
Normal inverse characteristic k = (0.05-1.1) in steps of 0.01 IEC 255-3 class 5 ± 60 ms
Very inverse characteristic k = (0.05-1.1) in steps of 0.01 IEC 255-3 class 7.5 ± 60 ms
Extremely inverse characteristic k = (0.05-1.1) in steps of 0.01 IEC 255-3 class 7.5 ± 60 ms
Logarithmic characteristic± 5 % of t at I = (1.3-29) x 3I0
Switch onto fault active time (0-60) s in steps of 1 ms
Rated voltage Ur
Table 27: EF4 - 4 Step earth-fault overcurrent protection
Function Setting range Accuracy
t 5 8 1– 35 ln× I3I0--------,,=
Table 28: TUV - Time delayed undervoltage protection
Function Setting range
Operate voltage U< (10-100) % of Ur in steps of 1%
Time delay (0-60) s in steps of 1ms
Table 29: TOV - Time delayed overvoltage protection
Function Setting range
Operate voltage U>phase measuring elementsresudual measuring elements
(50-200)% of Ur in steps of 1%(5-100)% of Ur in steps of 1%
Time delayphase measuring elementsresidual measuring elements
(0-60) s in steps of 1ms(0-60) s in steps of 1ms
Table 30: BRC - Broken conductor check
Function Setting range
Operate currenttime delay
(10-100) % of Ir in steps of 1 %(0-60) s in steps of 1 ms
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 29
Secondary system supervision
Control
Table 31: LOV - Loss of voltage check
Function Setting range
Operate voltage U< (10-100) % of Ur in steps of 1%
Table 32: OVLD - Overload supervision
Function Setting range
Operate current I>Time delay
(20-300) % of Ir in steps of 1 %(0-60) s in steps of 1 ms
Table 33: CTSU - CT supervision
Function Setting range
Operate current I> (5 - 100)% of Ir in steps of 1%
Table 34: FUSE - Fuse failure supervision function
Function Setting range
Zero-sequence quantities:operate voltage 3U0operate current 3I0
(10 - 50)% of Ur in steps of 1%(10 - 50)% of Ir in steps of 1%
Negative-sequence quantities:operate voltage 3U2operate current 3I2
(10 - 50)% of Ur in steps of 1%(10 - 50)% of Ir in steps of 1%
Table 35: SYNX - Synchro-check with phasing and energising check
Function Setting range
Synchro check frequency difference limitvoltage difference limitphase difference limit
(50-300) mHz in steps of 10 mHz(5-50) % of Ur in steps of 1 %(5-75)° in steps of 1°
Energisingvoltage level highvoltage level lowauto-energising periodmanual energising period
(50-120)% of Ur in steps of 1%(10-100) % of Ur in steps of 1%(0-60) s in steps of 1 ms(0-60) s in steps of 1 ms
Phasingslip frequencybreaker closing pulse durationbreaker closing time
(50-500) mHz in steps of 10mHz(0-60) s in steps of 1ms(0-60) s in steps of 1ms
Phase shift ϕ line - ϕbusVoltage ratio Ubus/Uline
(0-360)° in steps of 5°(0.20-5.00) in steps of 0.01
Operate time Value
For synchro check functionFor energising check function
typical 190 mstypical 80 ms
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 30
Technical data (cont’d)Technical data (cont’d)
Logic
Table 36: ARxx - Autoreclosing
Function Setting range
Number of autoreclosing shots 1 - 4
Number of autoreclosing programs 6
Auto-reclosing open time:shot 1 - t1 1phshot 1 - t1 2phshot 1 - t1 3phshot 2 - t2 3phshot 3 - t3 3phshot 4 - t4 3ph
(0-60) s in steps of 1 ms(0-60) s in steps of 1 ms(0-60) s in steps of 1 ms(0-9000) s in steps of 0.1 s(0-9000) s in steps of 0.1 s(0-9000) s in steps of 0.1 s
Reclaim time (0-9000) s in steps of 0.1 s
Inhibit reclosing, reset time (0-60) s in steps of 1 ms
Duration of reclosing pulse (0-60) s in steps of 1 ms
Synchro-check/Dead line time limit (0-9000) s in steps of 0.1 s
Breaker closed before start 5 s
Resetting of “AR Started“ after reclosing (0-60) s in steps of 1 ms
Wait for Master release (0-9000) s in steps of 0.1 s
Table 37: Remote end data communication
Function Value
Data communication between the terminals
transmission typedata transfer rate
synchronous56 or 64 kbit/sFor G.703 only 64 kbit/s
Galvanic interface Connection
Interface type V.36/V11 Co-directionalV.36/V11 Contra-directional X.21/X27 RS530/RS422 Co-directional RS530/RS422 Contra-directional G.703
According to CCITTAccording to CCITTAccording to CCITTAccording to EIAAccording to EIAAccording to CCITT
Connector type D-sub 15 or 25 pins (G.703 screw)
Short-range galvanic modem
RangeLine interfaceConnectorIsolation
max 4 kmBalanced symmetrical three-state current loop5-pin divisible connector with screew connectionGalvanic isolation through optocouplers and isolating DC/DC-converter
Optical interface
Type of fibreGraded-index multimode 50/125µm Single mode 9/125 µm
Optical connector
Wave length Optical transmitter
injected power Optical receiver
sensitivityTransmission distance
Type FC e.g. Diamond HFC-13
1300 nmLED-16 dBmPIN diode-40 dBmmax 20 km
Type FC-PC, e.g. Diamond HPC-101300 nmLED-21 dBmPIN diode -40 dBmmax 30 km
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 31
Interface type ABB FOX specific protocol
Short-range fibre optical modem
Transmission distanceOptical fibreOptical connectorsOptical budgetInterface type
max 5 km1300 nm, multimode fibreST15dBFiberdata specific protocol
Table 38: Trip logic
Function Setting range
Tripping action 3-ph, 1/3-ph, 1/2/3-ph
Table 39: PD - Pole discordance, contact based
Function Setting range
Auxiliary-contact-based function - time delay (0-60) s in steps of 1 ms
Table 40: CCHT - Communication channel test logic
Function Setting range
Time interval for automatic start of testing cycle (0-90000) s in steps of 0.1 s
Time interval available for successful test of an external function (0-90000) s in steps of 0.1 s
Minimum time interval for repeated tests of an external function (0-90000) s in steps of 0.1 s
Duration of CCHT-CS functional output signal (0-90000) s in steps of 0.1 s
Duration of a CCHT-CHOK functional output signal (0-90000) s in steps of 0.1 s
Duration of an inhibit condition after the CCHT-BLOCK input signal resets (0-90000) s in steps of 0.1 s
Table 41: Basic logic
Timers
Function Number Setting range
Timer 10 (0-60) s in steps of 1 ms
Long timer 10 (0-90000) s in steps of 0.1 s
Pulse timer 10 (0-60) s in steps of 1 ms
Pulse long timer 10 (0-90000) s in steps of 0.1 s
Logic
Function Number Description
AND 30 4 inputs (1 inverted),2 outputs (inverted and non-inverted)
OR 60 6 inputs, 2 outputs (inverted and non-inverted)
XOR 39 2 inputs, 2 outputs (inverted and non-inverted)
INV 20
SR 5 2 inputs, 2 outputs (inverted and non-inverted)
Table 37: Remote end data communication
Function Value
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 32
Technical data (cont’d)Technical data (cont’d)
Monitoring
Table 42: Additional logic
Timers
Function Number Setting range
Pulse timer 40 (0-60) s in steps of 1 ms
Logic
Function Number Description
AND 239 4 inputs (1 inverted),2 outputs (inverted and non-inverted)
OR 159 6 inputs, 2 outputs (inverted and non-inverted)
INV 59
Table 43: DREP - Disturbance recorder
Function Setting range
Number of binary signals 0 - 48
Number of analogue signals 0 - 10
Sampling rate 2 kHz
Recording bandwidth (5-250) Hz
Overcurrent triggering (0 - 5000) % of Ir in steps of 1 %
Undercurrent triggering (0 - 200) % of Ir in steps of 1 %
Overvoltage triggering (0 - 200) % of Ur in steps of 1 % at 100 V sec
Undervoltage triggering (0 - 110) % of Ur in steps of 1 %
Pre-fault time (10 - 300) ms in steps of 10 ms
Post fault time (100 - 3000) ms in steps of 100 ms
Limit time (500 - 4000) ms in steps of 100 ms
Number of recorded disturbances Max 10 disturbances
Total recording time with 10 analogue and 48 binary signals *) recorded
maximum 40 s
Voltage channelsdynamic range
resolution(0.01-2.0) x Ur at 100 V sec.0.1 % of Ur
Current channelsdynamic range
without dc offsetwith full dc offsetresolution
(0.01-110) x Ir(0.01-60) x Ir0.5 % of Ir
Built-in calendar for 30 years with leap years
*) The amount of harmonics can affect the maximum storage time
Table 44: Event recorder
Function Value
Time tagging resolutionEvent buffering capacity
Max. number of events/disturbance reportMax. number of disturbance reports
Time tagging error with synchronisation once/1sTime tagging error with synchronisation once/10sTime tagging error with synchronisation once/60s
(minute pulse synchronisation)Time tagging error without synchronisation
1 ms
15010± 1.5 ms± 1.5 ms
± 1.5 ms± 3 ms/min
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 33
Table 45: FLC - Fault locator
Function Setting range
Distance to fault locatorreach for Ir =1 A in
resistive directionreactive direction
phase selection
(0 - 1500) Ω/phase(0 - 1500) Ω/phaseinternal
Table 46: mA measuring function
Function Setting range
mA measuring function ± 5, ± 10, ± 20 mA0-5, 0-10, 0-20, 4-20 mA
Max current of transducer to input (-25 to +25) mA in steps of 0.01
Min current of transducer to input (-25 to +25) mA in steps of 0.01
High alarm level for input (-25 to +25) mA in steps of 0.01
High warning level for input (-25 to +25) mA in steps of 0.01
Low warning level for input (-25 to +25) mA in steps of 0.01
Low alarm level for input (-25 to +25) mA in steps of 0.01
Alarm hysteresis for input (0 - 20) mA in steps of 1
Amplitude dead band for input (0 - 20) mA in steps of 1
Integrating dead band for input (0 - 1000) mA in steps of 0.01
Table 47: Mean values
Function Setting range Accuracy
Frequency (0.95-1.05) x fr ± 0.2 Hz
Voltage (0.1-1.5) x Ur ± 2.5 % of Ur at U ≤ Ur± 2.5 % of U at U > Ur
Current (0.2-4) x Ir ± 2.5 % of Ir at I ≤ Ir± 2.5 % of I at I > Ir
Active power *)
Reactive power *)at |cos ϕ| > 0.9at |cos ϕ| ≤ 0.8
± 5 %± 7.5 %
*) Measured at Ur and 20 % of Ir
Table 48: Mean values with increased accuracy
Function Setting range Accuracy
Frequency (0.95-1.05) x fr ± 0.2 Hz
Voltage (0.8-1.2) x Ur ± 0.25 % of Ur at U ≤Ur± 0.25 % of U at U > Ur
Current (0.2-2) x Ir ± 0.25 % of Ir at I ≤ Ir± 0.25 % of I at I > Ir
Active power *) at |cos ϕ| > 0.90.8 x Ur < U < 1.2 x Ur0.2 x Ir < I < 2 x Ir
± 0.5 % of Pr at P ≤ Pr*)
± 0.5 % of P at P >Pr*)
*) Pr active power at U = Ur , I = Ir and |cos ϕ| = 1
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 34
Technical data (cont’d) Metering
Ordering The standard version of REL 511 is a phase-to-phase and phase-to-earth line distance protec-tion terminal with five impedance measuring zones and separate general fault criteria. Indepen-dent time-delayed phase overcurrent protection is also included in the standard version.
Table 49: Pulse counter for metering
Function Setting range
Cycle time for pulse counter (0.5-60) min in steps of 30 s
Basic functions
Self-supervision with internal event recorder
Real-time clock with external time synchronisation
Four groups of setting parameters
Local Human Machine Interface (HMI)
Configurable logic
Service value reading
Monitoring of ac analogue measurements
Monitoring of dc analogue measurementsNote: mA input module required
Ordering Number: 1MRK 002 492-AA Quantity:
Includes basic functions and the selected functions and hardware options below
Basic data:
Frequency, fr 50/60 Hz
Dc voltage, EL 48/60/110/125/220/250 V
Basic data to specify:
Ac inputs
1 A, 110 V 1MRK 000 157-MB
5 A, 110 V 1MRK 000 157-NB
1 A, 220 V 1MRK 000 157-VB
5 A, 220 V 1MRK 000 157-WB
Interface dc voltage
24/30 V 1MRK 000 179-EB
48/60 V 1MRK 000 179-AC
110/125 V 1MRK 000 179-BC
220/250 V 1MRK 000 179-CC
Factory configurations
Standard configuration, three pole tripping Quantity:
Standard configuration, single or two pole tripping Quantity:
Standard configuration, scheme communication logic, phase segregated
Quantity:
Customer-specific configuration Quantity:
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 35
Functions;
= function always included
Line impedance
General fault criteria protection, impedance and/or current-based 1MRK 001 456-AA
General fault criteria protection with phase preference logic, impedance and/or current based 1MRK 001 456-MA
3 zones phase-phase protection 1MRK 001 456-CA
3 zones phase-earth protection 1MRK 001 456-DA
Additional zone 4 protection 1MRK 001 456-FA
Additional zone 5 protection 1MRK 001 456-GA
Power swing detection 1MRK 001 456-LA
Scheme communication logic 1MRK 001 456-NA
Current reversal and weak end infeed logic 1MRK 001 455-PA
Automatic switch onto fault logic 1MRK 001 456-RA
Local acceleration logic 1MRK 001 456-TA
Current, phase wise
Instantaneous phase overcurrent protection 1MRK 001 457-AA
Time-delayed phase overcurrent protection 1MRK 001 457-BA
Breaker failure protection 1MRK 001 458-AA
Current, residual (earth fault)
Instantaneous residual overcurrent protection (non-directional) 1MRK 001 456-VA
Time-delayed residual overcurrent protection (non-directional) 1MRK 001 456-XA
Inverse time residual overcurrent protection (non-directional)Note: Not selectable in combination with 4-step residual overcurrent protection and residual directional check and communication logic
1MRK 001 456-YA
Residual directional check, inverse time residual overcurrent protection and communication logic (directional element)
1MRK 001 456-ZA
4-step residual overcurrent protection (directional and non-directional) 1MRK 001 459-HA
Voltage, phase wise
Time-delayed undervoltage protection 1MRK 001 457-RA
Time-delayed overvoltage protection 1MRK 001 457-GA
Voltage, residual (earth fault)
Time-delayed residual overvoltage protection 1MRK 001 459-FA
Power system supervision
Broken conductor check 1MRK 001 457-UA
Loss of voltage check 1MRK 001 457-VA
Overload supervision 1MRK 001 457-FA
Secondary system supervision
Current circuit supervision (current-based) 1MRK 001 457-XA
Fuse failure supervision (Negative sequence) 1MRK 001 457-YA
Fuse failure supervision (Zero sequence) 1MRK 001 457-ZA
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 36
Ordering (cont’d)Ordering (cont’d)ControlNote: Only one alternative for Command control, Synch-check and Autorecloser can be selected respectively.
Command control (16 signals) 1MRK 001 458-EA
Synchro-check and energising-check, single CB 1MRK 001 458-GA
Synchro-check and energising-check, double CB 1MRK 001 458-FA
Synchro-check with phasing and energising-check, single CB 1MRK 001 458-KA
Synchro-check with phasing and energising-check, double CB 1MRK 001 457-HA
Autorecloser logic, 1 and/or 3 phase, single CB 1MRK 001 458-LA
Autorecloser logic, 1 and/or 3 phase, double CB 1MRK 001 457-KA
Autorecloser logic, 3 phase, single CB 1MRK 001 458-MA
Autorecloser logic, 3 phase, double CB 1MRK 001 457-LA
Logic
Three pole tripping logic 1MRK 001 458-VA
Single or two pole tripping logic 1MRK 001 458-XA
Pole discordance logic (contact based) 1MRK 001 458-UA
Additional configurable logic 1MRK 001 457-MA
Communication channel test logic 1MRK 001 459-NA
Binary signal transfer to remote endNote: See Communication module alternatives for selecting a comm. module
1MRK 001 458-ZA
Binary signal interbay communication, high speed (protection application) 1MRK 001 455-RA
Monitoring
Disturbance recorder, 40 s 1MRK 001 458-NA
Event recorder 1MRK 001 459-KA
Fault locator 1MRK 001 458-RA
Trip value recorderNote: This function is already included in the Fault locator, if selected
1MRK 001 458-SA
Increased measuring accuracy for U, I, P, Q 1MRK 000 597-PA
Metering
Pulse counter logic 1MRK 001 458-TA
Hardware options;
Casing
Case size 1/2 x 19" (max. 3 I/O)1MRK 000 151-FA
Standard
3/4 x 19" (max. 8 I/O)1MRK 000 151-GA
Optional
Combined binary input/output and output modules (max) 3 4
mA input module (max) 1 3
Note: The communication module option, if selected, occupies one I/O position
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 37
I/O modules
8 modules are available in the 3/4 x 19" case and 3 modules are available in the 1/2 x 19" case.
InterfaceDC voltage
Quantity Ordering number
Binary input module(16 inputs)
24/30 V 1MRK 000 508-DB
48/60 V 1MRK 000 508-AB
110/125 V 1MRK 000 508-BB
220/250 V 1MRK 000 508-CB
Binary input module with enhanced pulse counter capabilities (16 inputs)
Rule: Can only be ordered together with the pulse counter logic optional function
24/30 V 1MRK 000 508-HA
48/60 V 1MRK 000 508-EA
110/125 V 1MRK 000 508-FA
220/250 V 1MRK 000 508-GA
Binary input/output module (8 inputs and 12 outputs)
24/30 V 1MRK 000 173-GB
48/60 V 1MRK 000 173-AC
110/125 V 1MRK 000 173-BC
220/250 V 1MRK 000 173-CC
Binary output module (24 single outputs or 12 command outputs)
1MRK 000 614-AB
mA input module (6 channels) 1MRK 000 284-AB
Note: One binary input/output module is required for standard factory configuration.
Remote end data communication module alternativesNote: Applicable only when function Binary signal transfer to remote end is selected. Only one alternative can be selected. Optical fibre or electrical wire is not included.
V.35/V.36 contra-directional galvanic interface 1MRK 000 185-BA
X.21 galvanic interface 1MRK 000 185-CA
RS 530/422 contra-directional galvanic interface 1MRK 000 185-EA
Fibre optical modem 1MRK 000 195-AA
Short range galvanic modem 1MRK 001 370-AA
Short range fibre optical modem 1MRK 001 370-BA
V.35/V.36 and RS 530/422 co-directional galvanic interfaces On Request
Serial communication modules
Serial communication for SMS and SCS; (one alternative per port)
SMS, port SPA/IEC 870-5-103 (location X13)
Plastic/Plastic 1MRK 000 168-FA
Glass/Glass 1MRK 000 168-DA
SCS, port LON (location X15)
Plastic/Plastic 1MRK 000 168-EA
Glass/Glass 1MRK 000 168-DA
Engineering facilities
HMI languageSecond language besides English
German 1MRK 001 459-AA
Russian 1MRK 001 459-BA
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 38
Ordering (cont’d)Ordering (cont’d) French 1MRK 001 459-CA
Spanish 1MRK 001 459-DA
Italian 1MRK 001 459-EA
Customer-specific ordering
Customer-specific order number
Combiflex
COMBITEST test switch module RTXP 24 mounted withthe terminal in RHGS6 case with window door 1MRK 000 371-CA
Internal earthing RK 926 215-BB External earthing RK 926 215-BC
On/Off switch for the dc supply RK 795 017-AA
Mounting details with IP40 degree of protection from the front:
19" rack 1MRK 000 020-BR
Wall mounting 1MRK 000 020-DA
Flush mounting 1MRK 000 020-Y
additional for IP54 (protection terminal only) 1MKC 980 001-2
Semi-flush mounting 1MRK 000 020-BS
additional for IP54 (protection terminal only) 1MKC 980 001-2
Accessories:
User documentation
Technical reference manual, REL 511 Quantity: 1MRK 606 003-UEN
Combiflex
Key switch (for locked Settings) Quantity: 1MRK 000 611-A
Resistor unit for creation of 3Uo voltage (RXTMA 1) Quantity: 1MRK 000 486-AA
Communication (remote terminal communication)
Interface converter (dc voltage 48 V)
RS 530/422 contra-directional to G.703 co-directional converter *) Quantity: 1MRK 001 295-AA
Optical/electrical converters for short-range optical modems (dc voltage 48-110 V)
V.35/V.36 Quantity: 1MRK 001 295-CA
X.21/G.703 / RS 530 Quantity: 1MRK 001 295-DA
Fibre optic repeater and multiplexer (FOX 20) **)available from ABB Network Partner Ltd (Turgi, Switzerland)
*) For dc-supply 110-250 V an extra dc/dc converter type RXTUG 22H is needed, see 1MRK 513 001-BEN.**) Compatible with Fibre optical modem according to 1MRK 000 195-AA.
Configuration and monitoring tools
Front connection cable for PC (Opto/9-pol D-sub) Quantity: 1MKC 950 001-2
CAP 531, Graphical configuration tool (IEC 1131-3) Quantity: 1MRK 000 876-KB
CAP/REx 500, CAP software module Quantity: 1MRK 000 876-PA
LNT 505, LON configuration tool Quantity: 1MRS 151 400
SLDT, LON configuration module REx 500available on our website: www.abb.se/net
1MRK 001 700-4
SMS-BASE, Basic program for all SMS applications Quantity: RS 881 007-AA
SM/REx 500, SMS software module Quantity: 1MRK 000 314-MA
REPORT, program for event and alarm handling in SMS Quantity: RS 881 011-AA
RECOM Disturbance collection program Quantity: 1MRK 000 077-DC
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 39
References Series RE 500Mechanical design and mounting accessories
Technical reference manual, REL 511
Reference list REL 511
LIB 520
SMS 010
CAP 531
1MRK 514 003-BEN
1MRK 606 003-UEN
1MRK 506 002-REN
1MRK 511 057-BEN
1MRK 511 014-BEN
1MRK 511 056-BEN
Manufacturer ABB Automation Technology Products ABControl & Force MeasurementSubstation Automation SE-721 59 VästeråsSwedenTel: +46 (0) 21 34 20 00Fax: +46 (0) 21 14 69 18
REVAL Disturbance evaluation program, English version Quantity: 1MRK 000 078-AB
MicroSCADA tools
LIB 520, MicroSCADA engineering tool Quantity: On request
For our reference and statistics we would be pleased to be provided with the following application data:
Country: End user:
Station name: Voltage level: kV
Line distance protection terminal REL 511*2.01MRK 606 003-BEN
Page 40