LEDEMERGENCY DRIVER
Model: VEML20MV-1
Input Voltage120-277 VAC, 50/60 Hz
Lamps Operated●
● Other Class 2 LED lamp or module
Output Voltage12-50 VDC
Operating Temperature0°C/30°F - 50°C/122°F
Battery24-48 hr recharge, LiFePO4options in 90 minutes: 5W, 10W,15W and 20W
ApprovalUL and cUL 924 Listed
Technical Specifications
IMPORTANT SAFEGUARDSREAD AND FOLLOW ALL SAFETY INSTRUCTIONS
This guide contains important information regarding installation and operation.Please keep this guide for future reference.
WARNING: READ AND FOLLOW ALL SAFETY INSTRUCTIONS.
When using electrical equipment, basic safety precautions should always be followed including the following:
1. Do not use outdoors.2. Do not mount near gas or electric heaters.3. Equipment should be mounted in locations and at heights where it will not be subjected to tampering by unauthorized personnel.4. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.5.Do not use this equipment for other than its intended use.6. This equipment has not been investigated for use in an air-handling fixture, it is not suitable in a heated air outlet.7. Use with grounded, UL Listed, damp location rated fixtures and case should be connected to grounding.8. The drivers are intended for ordinary locations and for permanent installation into one or more Listed emergency luminaires.
Operation · Suitable for use in 0°C/30°F - 50°C/122°F · The charging indicator light would be on to indicate the battery is being charged when AC power is appied
Installation · AC power has to be off before installation · Follow the wiring diagram to connect the LED emergency dirver to LED driver and lamp · Please ensure the electricity connections confirm to the National Electrical Code and local regulations · Do not connect to AC power until the battery connection is jointed · The battery needs to be charged for one hour in order to have short-term testing on the emergency function. Before having a long-term emergency function testing, the battery in the EM driver has to be charged for 24-48 hours according to battery charging rate
Operates with Espen CoreTech type C LED lamp, VersaLinear LED module, or any other
ESPEN Technology, Inc.12257 Florence Ave ● Santa Fe Springs, CA 90670
Phone: (562) 529-2938 ● Fax: (562) 529-2978 ● Toll Free: (886) 933-7736Email: info@espentech.com ● www.espentech.com
Emergency Operation90 mins
Emergency mode rated power90 min in 5W, 10W, 15W and 20Wselectable
Class 2 LED lamp or module
2’ - 4’ of Espen CoreTech type C LED lamp or VersaLinear LED module
Installation Instruction
Wiring Diagram:
Specification data is based on tests performed in a controlled environment and represents relative performance. Actual performance can vary depending on operating conditions. Application and performance data subject to change without notice. All specifications are nominal unless noted otherwise.
ESPEN Technology, Inc.12257 Florence Ave ● Santa Fe Springs, CA 90670
Phone: (562) 529-2938 ● Fax: (562) 529-2978 ● Toll Free: (886) 933-7736Email: info@espentech.com ● www.espentech.com
BATTERY
YEL
RED/WHT
EmergencyDriverVEML20MV-1
Current adjustment (dip switch):
Driver (N)
WHT/BLK
Driver (L)
L
NBLACK
WHITE
Case must be grounded
Test Switch
RED (Driver +)
LED Driver
LED lamp/module+
_
BLUE (Driver -)
RED
Dip Switch SettingEmergency Mode
Output PowerBattery Charging
CurrentEmergency Mode
Output VoltageEmergency Mode
Output Current
5W
10W
15W
20W
12-50V
12-50V
12-50V
12-50V
416-100mA 60mA
1250-300mA
1400-400mA
830-200mA 100mA
160mA
210mA
12
31
23
12
31
23