Today offer
TRIO-50/60.TL-OUTD
TRIO-50.0/60.0-TL-OUTD main features
− Developed for Commercial, industrial and utility-grade PV installations;
− Reduced installation cost by not requiring any major commissioning activity;
− Light weight construction to make the installation manageable by a team of 2 people;
− Multiple versions available to meet plant designer requirements;
Today offer
TRIO-50/60.TL-OUTD
TRIO-50.0/60.0-TL-OUTD main features
– Transformer-less (TL) topology
– Separated DC and AC compartments offered in multiple versions (factory pre-configured) to include:
• String fuses (in both poles)
• DC and AC Switch
• DC and AC type II SPDs
– IP65 construction for the electronic compartment
– Forced air cooling with field replaceable fan (blowsair over inverter’s external heatsink)
– World wide availability
Vertical installation Horizontal installation
Wall mounting bracketHorizontal mounting bracket
Today offer
TRIO-50/60.TL-OUTD
TRIO-GROUNDING-KIT
Only NEGATIVE. One kit for each Inverter (also in case of 3MPPT). It allows to use those PV panels that need a connection to the ground.
TRIO-AC-WIRING-KIT
Needed in case of bigger AC cables (specially aluminum). AC connection cable size up to 150 mm2 aluminum and copper (standard AC connection is 95mm2 aluminum/copper).
DISPLAY
The display is integrated in the DCWB. There are versions with display included for eachDCWB. They have to be ordered by dedicated PN
Additional options
TRIO-50/60.TL-OUTD
TRIO- “Unipack”
TRIO-50/60-TL-OUTD
Unique package for TRIO-50/60-TL-OUTD
To reduce custom duty, the most popular configurations of TRIO are available already grouped in single packages including:
1. Power Module2. ACWB3. DCWB4. Vertical mounting bracket5. Additional lower mounting bracket.
Each package can be ordered by a dedicated PN
Additional lower mounting bracket
This is suggested for those cases in which TRIO is subjectedto high tilting, like in strong winds areas
1
23
4
5
Next step: more flexible and smart
TRIO-TM
July 12, 2017 Slide 7
− 3 independent MPPT allowing for improved design flexibility
− External communication port and wireless interface for «touch less» commissioning
− Advanced communication features anabling smart functionalities
Same modular enclosure with many more functionalities
Inverter parameters
– VMPPT = 480 – 800 Vdc @50kW
– VMPPT = 570 – 800 Vdc @60kW
– 3 Independent MPP channels
– 15 Independent String (SX and SX2)
– VAC = 400Vc 3-Ph, 50/60Hz @50kW
– VAC = 480Vc 3-Ph, 50/60Hz @60kW
User Interface
– Integrated Web User Interface (AME);
– Standard level access to Aurora Vision remote monitoring service
– «Classic» Aurora manager lite SW
– Display available as option (integrated in the DCWB)
– Installer App (coming soon)
July 12, 2017* Value can vary by the models
Slide 9
Communication
– 2 x Ethernet;
– Wi-Fi Channel
– 2 x RS485;
– Modbus RTU/TCP (Sunspec compliant);
– Proprietary Aurora Protocol for back compatibility
Weight & Size
– Same of current version
TRIO-TM-50.0/60.0
TRIO-TM
Main technical Parameters
IP communication
1) DC Wiring box (DCWB)2) Power module3) AC Wiring box (ACWB)4) Mounting Bracket
To complete a TRIO-TM it is necessary to order 4components each of which is selectable from a listof possible available options (except the powermodule).1 2 3
4
TRIO-TM
TRIO-TM is made by the same parts of TRIO“classic”:
TRIO-TM components
Available options
TRIO-TM
TRIO-TM-50-400-POWER MODULE
DCWB-TRIO-TM-50.0-400
DCWB-S-TRIO-TM-50.0-400
DCWB-SX-TRIO-TM-50.0-400
DCWB-SX2-TRIO-TM-50.0-400
ACWB-TRIO-TM-50.0-400
ACWB-SX-TRIO-TM-50.0-400
TRIO-TM-50.0-400 TRIO-TM-60.0-480
TRIO-TM-60-480-POWER MODULE
DCWB-TRIO-TM-60.0-480
DCWB-S-TRIO-TM-60.0-480
DCWB-SX-TRIO-TM-60.0-480
DCWB-SX2-TRIO-TM-60.0-480
ACWB-TRIO-TM-60.0-480
ACWB-SX-TRIO-TM-60.0-480
DC wiring Box available
TRIO-TM
DC WIRING BOX OPTIONS
DC WIRING BOX
Input
FusesDC
switch
SPD
DisplayTerminal blocks
Quick connecti
ons Varistors
Type II (monitore
d)
Type I+II (monitored)
DCWB-TRIO-TM Yes - - - Yes - - OPTIONAL
DCWB-S-TRIO-TM Yes - - Yes Yes - - OPTIONAL
DCWB-SX-TRIO-TM - 15Only positive
poleYes Yes OPTIONAL - OPTIONAL
DCWB-SX2-TRIO-TM - 15 Both poles Yes Yes OPTIONAL OPTIONAL (*) OPTIONAL
(*) Non yet available
AC wiring Box available
TRIO-TM
AC WIRING BOX OPTIONS
AC WIRING BOX
OutputAC disconnect
switch
SPD
Terminal Block VaristorsSPD Type II(Monitored)
ACWB-TRIO-TM Yes - Yes -
ACWB-SX-TRIO-TM Yes Yes Yes OPTIONAL
TRIO-TM
TRIO-TM-60.0-480 TRIO-TM-50.0-400
MODEL DESIGNATION/OPTION MODEL DESIGNATION/OPTION
TRIO-TM-60.0-480-POWER MODULE TRIO-TM-50.0-400-POWER MODULE
DCWB-TRIO-TM-60.0-480
DCWB-S-TRIO-TM-60.0-480
DCWB-SX-TRIO-TM-60.0-480
DCWB-SX2-TRIO-TM-60.0-480
DCWB-SX-TRIO-TM-60.0-480;SPD
DCWB-SX2-TRIO-TM-60.0-480;SPD
DCWB-TRIO-TM-60.0-480;DISPLAY
DCWB-S-TRIO-TM-60.0-480;DISPLAY
DCWB-SX-TRIO-TM-60.0-480;DISPLAY
DCWB-SX2-TRIO-TM-60.0-480;DISPLAY
DCWB-SX-TRIO-TM-60.0-480;SPD;DISPLAY
DCWB-SX2-TRIO-TM-60.0-480;SPD;DISPLAY
DCWB-TRIO-TM-50.0-400
DCWB-S-TRIO-TM-50.0-400
DCWB-SX-TRIO-TM-50.0-400
DCWB-SX2-TRIO-TM-50.0-400
DCWB-SX-TRIO-TM-50.0-400;SPD
DCWB-SX2-TRIO-TM-50.0-400;SPD
DCWB-TRIO-TM-50.0-400;DISPLAY
DCWB-S-TRIO-TM-50.0-400;DISPLAY
DCWB-SX-TRIO-TM-50.0-400;DISPLAY
DCWB-SX2-TRIO-TM-50.0-400;DISPLAY
DCWB-SX-TRIO-TM-50.0-400;SPD;DISPLAY
DCWB-SX2-TRIO-TM-50.0-400;SPD;DISPLAY
ACWB-TRIO-TM-60.0-480
ACWB-SX-TRIO-TM-60.0-480
ACWB-SX-TRIO-TM-60.0-480;SPD
ACWB-TRIO-TM-50.0-400
ACWB-SX-TRIO-TM-50.0-400
ACWB-SX-TRIO-TM-50.0-400;SPD
SMART functionalities
TRIO-TM
TRIO-50.0-TL-OUTD smart capabilities
– Embedded multi-communication interfaces(2 x Ethernet , Wi-Fi and 2 x RS-485)
– Integrated Web User Interface (AME)
– Wireless Commissioning and system setting via any WLAN standard device
– Efficient Modbus RTU / TCP communication protocol, Sunspec compliant,
– Free of charge remote monitoring with no needof any external data logger
– FW update, both locally and remotely, with any IP based layout
– Comprehensive set of control functions enabling full grid support
Communication Interfaces
TRIO-TM
TRIO-50.0/60.0-TM communication interfaces
– Integrated Wi-Fi (IEEE 802.11 b/g/n @ 2.4 GHz)• For inverter touch free commissioniong• For wireless accessing to the inverter’s WUI• For wirelessly transferring of data to cloud
– 2 x Ethernet ports• 10/100 Mbit/s• RJ45 plug • Configured for daisy chain layout connection
(Linear topology)• Suitabel also for Star layout connection
Star topology• Direct transferring of data to Cloud
– 2 x RS485 ports• Mainly for back compability• To be used just like in -TL version• Not compatibile with all the communication
functions / services (i.e. remote FW update, logger-free remote monitoring, ….)2 x RJ45 for Ethernet Daisy Chain connection layout
2 x RS-485 ports(internal the DC box)
Communication Protocols
TRIO-TM
TRIO-50.0/60.0-TM communication protocols
– Modbus RTU/ TCP Sunspec• TCP over Wi-Fi and Ethernet / RTU over RS485_2 port• Sunspec Allineace certified• Full monitoring enabled
Modes: 1, 103, 160, 403• Basic controlling enabled
Modes: 120, 121, 123 • PICS available on Sunspec Alliance web site
http://sunspec.org/sunspec-certified-products/• Recommended for third party integration (enabling
monitoring and control)
– Modbus RTU proprietary map• Available over both RS-485 _1 and RS485_2 ports• No monitoring of DC box• Full control of the inverter via proprietary modes• Register maps available on ABB web site
– Aurora Protocol• NOT SUITABLE for customer’s application• For Service and back compatibility use only• Register map available by ABB Service upon the signing of
NDA
Recommended configuration
Inverter’s HMIs
TRIO-TM
TRIO-50.0/60.0-TM HMIs
1. Embedded Web User Interface• Accessible via Wi-Fi by using any WLAN enabled
standard device (PC, smartphone, tabled,….)• Enables single inverter parameters settings• Derived by UNO-DM-PLUS’s WUI (Aurora Manager
Embedded)
2. Local display• Just for reading settings• Enabled settign RS485 ports’ addresses and MPPT
functioning mode• Available on request (it is an accessory)
3. Aurora Manager Lite• Mainly for service purpose• No differences respect its use with TRIO-50.0/60.0-
TL version
1
RS485 port(internally available)
2
PC running Aurora Manager Lite
3
CLOUD
Cloud services
TRIO-TM
July 12, 2017 Slide 20
Plant Portfolio Manager
Plant Viewer
Plant Viewer for Mobile
wirelessly commissioning and system setting via any WLAN enabled device
Embedded logging and direct transferring od data to Aurora Vision Cloud
Lifetime free standard access level to Aurora Vision cloud:- Remote monitoring- FW updated- Asset managing- Remote diagnostics and troubleshooting- Intelligent fault detection- instant alerting- User friendly mobile app- Advanced reporting
Ethernet field bus (Daisy Chain or Star layout)
TRIO-TM
July 12, 2017 Slide 21
communication over Ethernet
− Standard Ethernet cable :• Cross-section: min. 2 x 2 x 0.22 mm2 or
min. 2 x 2 x AWG 24• Cable type: 100BaseTx, CAT5 with
shielding S-UTP, F-UTP or higher• UV-resistant if used outdoors• Type of plug: RJ45
− Two different topologies:1. daisy chain over Ethernet cable
(100 m @ maximum inverter – inverter)2. Star layout
(100 m @ maximum inverter – switch)
< 1
00
m
Ethernet switch
Internet
Plant Portfolio
Manager
Plant ViewerPlant Viewer
for Mobile
Aurora Vision
1
2
Commissioning procedure
TRIO-TM
July 12, 2017 Slide 22
Commissioning over Ethernet
− Automatic setting up of the communication afterthe turning on of the inverters(i.e. dynamic IP addresses, ….)
− Single inverter commissioning via Wi-Fi / AME by anyWLAN enabled device
− Installer App for plant commissioning coming soon
− Possibility to commission all the inverters by stayingconnected to the Ethernet Switch(multicast DNS service needed on the switch)
− Main network info available through a single page of any inverter Web User Interface
Ethernet switch
Internet
Plant Portfolio
Manager
Plant ViewerPlant Viewer
for Mobile
Aurora Vision
WLAN enabled device
Touch free inverter commissioning
TRIO-TM
July 12, 2017 Slide 23
Easy & fast commissioning
Four steps to start energy production
1. Add user and administrator
2. Connect inverter to web
3. Confirm date and time
4. Accept the grid parameters and time zone
Congratulation your TRIO-TM is up and running!
Log in the integrated web server for advanced parameter setting and don’t forget register to our Aurora Vision for more advantages!
What benefits from Ethernet & Wi-Fi communication
New TRIO-TM
July 12, 2017 Slide 24
From serial RS485 to IP based
− Remote monitoring and FW upgrade Ready-to-use just soon as the inverters are turned on
− Standard communication components for easily adapting plant layout to any environment conditions(switch , repeater, wireless sockets,…)
− IP supports many control protocols (TCP/UDP/ RTSP, etc.) and application protocols (HTTP/FTP, ….) for any needs
− IP supports multiple data streams that can be used for data, firmware upgrade, control
− Ip based allows ABB service to better support customer remotely
− Ethernet is much more robust and reliable than serial bus a so much more suitable for implementing remote inverter’s parameters settings over
− No need of manually configuring ports’s address (IP are automaticallyassigned to each ports with or without DHCP service
− No need to install any external logger for enabling remote monitoring
− No suitable standard protocol on RS485 for IoT functionality (IP is becoming the new standard)
Eth
ern
et (M
od
bu
sT
CP
)
Internet
Ethernet Switch
Third party monitoring &
control system(i.e. SCADA)
Plant Portfolio
Manager
Plant ViewerPlant Viewer
for Mobile
Aurora Vision
Ethernet (Modbus TCP)
TC
P /
IP
Standard devices for commissioning and
settings
What benefits from Modbus Sunspec
New TRIO-TM
July 12, 2017 Slide 25
From Aurora Protocol to Modbus Sunspec
− Aurora Protocol is not :• IT – secure• Reliable• efficient
− Aurora Protocol does not allows implementing advanced monitoring and control system as per modern requirements and regulatory norms (IEC61850, Rule21-Step-2 & 3,….)
− Modbus is an open and standard protocol commonly used in Solar industry
− Sunspec is recognized as standard for Modbus communication protocol in solar market
− Modbus Sunspec allows integrating ABB inverters with most of third party monitoring and control systems available on the market with no need of customizing
− Sunspec is compliant with IEC 61850 as main Industry relevant information model
− Aurora Protocol for back compatibility need only
Connectivity and smart inverter capabilities
TRIO-TM
July 12, 2017 Slide 26
Remote FW update
− Always possibile even if a third party monitoring and control solution isused
− Allow ABB Service to drastically reduce expenses for on-site visit
− New features enhancement
− Fast response to dynamic grid requirements
− Remote update capability available for components
Future proof
New TRIO-TM
July 12, 2017 Slide 27
ABB is ready for next generation of smart grid control
Integrated WUI and AME service tool
TRIO-TM
July 12, 2017 Slide 28
Aurora Manager EmbeddedWeb User Interface