GeneralSpecifications
<<Contents>> <<Index>>
Models SSS7700, SSS7710, SSS7711, SSS7720, SSS7750Plant Resource Manager
Yokogawa Electric Corporation2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 JapanTel.: 81-422-52-5634 Fax.: 81-422-52-9802
GS 33Y05Q10-32E
GS 33Y05Q10-32E©Copyright July 26, 2006 (YK)
20th Edition June 30, 2017 (YK)
GENERALPlant Resource Manager (PRM®) is an asset management software tool for the digital network era. The PRM software efficiently manages and supports maintenance work of field devices, which contributes in reducing total cost of ownership (TCO) of an industrial plant.The PRM software packages support intelligent devices such as Foundation™ fieldbus, HART, PROFIBUS, and ISA100.11a field wireless devices as well as conventional analog devices.
PRODUCT OVERVIEWPlant Resource Manager (PRM) consists of the following components:
lPRM server•Maintenancerelateddatasuchasdevicestatus,deviceparameters,devicealarms,andinspectionmemoofthefielddevicesarecollectedandstored.
•Centralizeddeviceinformationsuchasdevicemaster,inspectionschedulesandrecords,user-createdelectronicdocuments, and parts lists are generated and managed as database.
•Maintenancealarmsforfielddevicesaregeneratedwithattributessuchasproblem,cause,andaction,andthesealarmsarenotifiedtothepeoplewhoneedthem.
l PRM client•Devicenavigatorwindowsinhierarchytreeviewareprovidedformonitoringandmanagingfielddevices.•Automaticdevicerecognitionandregistration(plug&play)areperformedbyusingfulldigital,bi-directional,fielddigitalnetworkssuchasFoundationfieldbus,HART,PROFIBUS,andISA100.11a.Monitorsdevicehealthstatuswithmaintenancealarmsandcommunicationerrors.WithPRMAdvancedDiagnosticFunction,thePRMalsoperformsdevicestatusdiagnosis,deviceparametersettingusingdevicediagnostictools(i.e.DeviceViewer,DTMWorks,andDDmenu).
•Statusiconsaredisplayedreflectingthecommunicationanddevicestatustoletoperatorsgraspthedevicestatusintuitively.Statusiconsappearforthedeviceswithunacknowledgedmaintenancealarms(ofthedevicehealthstatus).
•AstatussignalofafielddevicecomplyingwithNAMURNE107specificationsisdisplayedontheSignalviewoftheDevicenavigator.TheNE107isarecommendationforself-monitoringanddiagnosisoffielddevicespublishedbyNAMUR,aninternationaluserassociationofautomationtechnologyinprocessindustriesheadquarteredinGermany.
•Deviceiconsdisplayedonthedevicenavigatorcanbefreelydefinedbyauser.Theusercancustomizethosefontsandiconsoutofthreechoicesdependingontheuserrequirementsandthescreensize.
•Maintenancemarksareakindofflagstobeassignedtodevicesforsettingandcheckingmaintenancestatus.Themaintenancemarkiconisdisplayeduponsetting,andenablestotemporarilychangedeviceaccesslevel.ThemaintenancemarkscanalsobelinkedwithCENTUM’soperationmarkssothatthemaintenanceengineersandoperators can share the same information and coordinate their work.
•Onlinedeviceadjustment/settingareperformedonscreenusingthesameuserinterfacewithFieldMateversatiledevicemanagementtoolwhichisanon-sitedeviceadjustment/settingtool.
•ParametersandmaintenanceinformationbetweenthePRMandtheFieldMatecanbeexchanged.•PRMadvanceddiagnosisapplication,devicediagnosisdatahistorian,andgeneral-purposediagnosistoolforPRMadvanceddiagnosisfunctionareprovided,inadditiontothemaintenancealarmfunctionanddevicediagnosticsfunction.
•RegistrationofconventionalanalogfielddevicesaswellasfielddigitaldevicessuchasFoundationfieldbus,HART,PROFIBUS,andISA100.11acanbeperformedforatrue,centralizeddevicemanagement.
•Third-partycalibrationanddiagnosticsoftwaretoolsasPLUG-INapplicationscanbeperformed.DeviceViewer(*1)andPLUG-INValveNaviareavailablefromYokogawa.
•FDT/DTM(Fielddevicetool/Devicetypemanager)andEDDL(Electronicdevicedescriptionlanguage)technologiesthatenablethePRMtointerfacewithfielddevicesaresupported.DTMsofFDT1.2andFDT2.0aresupported.
*1: AfielddeviceinformationanditsstatussignalcomplyingwithNAMURNE107aredisplayedontheDeviceViewer. DownloaddevicedefinitionfilesfromeachdevicevendortorunontheDeviceViewerpriortoitsuse.TheDeviceViewerisa
PLUG-INapplicationofthePRMclientanditcanbedisplayedonCENTUMVP/CENTUMCS3000(R3.07orlater)HIS. ToletonlytheDeviceViewerrunontheHIS,DeviceVieweronHIShastobeinstalled.
2
All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation
<<Contents>> <<Index>>
GS 33Y05Q10-32E Sep. 7, 2016-00
l Field communications serverThissoftwareistosetandacquirefielddevicedataonline.Thefieldcommunicationserverprovidesinformationsuchasdevicestatusmonitoring,deviceadjustment,anddevicediagnosistothemaintenancesupportapplication.
Connecting with field devicesFollowingmethodsareavailabletoconnectwithfielddevices.•FoundationfieldbusCommunicationModulesforCENTUMVP/CS3000•AI/AOmodulesoranalogdigitalI/OmodulewithHARTcommunicationforCENTUMVP/CS3000•PROFIBUS-DPcommunicationmoduleforCENTUMVP•FoundationfieldbusCommunicationModulesforSTARDOM•AI/AOmoduleswithHARTcommunicationforSTARDOM•PROFIBUScommunicationmoduleforSTARDOM•AI/AOmodulesoranalogdigitalI/OmoduleswithHARTcommunicationforProSafe-RS•NI-FBUScard•3rdpartyHARTmultiplexers(PepperandFuchs,MTL,ELCON,orSTAHL)•3rdpartyPROFIBUScommunicationdevices(CommunicationDTM/GatewayDTMcommunications)•FieldWirelessAccessPointandFieldWirelessManagementStation(CommunicationDTM/GatewayDTMcommunications)
l Multiple server switchoverPRMcanmanagefielddevicesthatarecontrolledbyaCENTUMVP/CS3000,ProSafe-RS,orSTARDOMproject.PRMcanalsomonitoralarge-scaleprojectwhichisgeographicallydistributedinremotelocationsatasinglelocation.Forthelarge-scaleprojectwheretensofthousandsoffielddevicesareinstalled,dividingthemintomultiplenumbersofPRMserversisinevitable.PRM’smultipleserverfunctionenablestoselectwhichPRMserverisreferredtobyaPRMclient.Inthisway,asinglePRMclientcanmonitorseveralPRMservers.
l PRM advanced diagnosis server function (optional)Thisseverfunctionprovidesanenvironmentforexecutingdiagnosticalgorithmsbyutilizingfielddeviceparameters.ThediagnosticalgorithmapplicationcanbeconfiguredbyusingthePRMadvanceddiagnosticsoftwaredevelopmentkit(PAA-developmentkit)withoutanyadditionalsoftwareprogram.Bymonitoringparametersandprocessdatatransmittedfromfielddevices,thePRMadvanceddiagnosisserverfunctionconfiguresandexecutesdiagnosisofthedevicesandassets.Formoredetails,refertotheGS“PRMadvanceddiagnosisserver”(GS33Y05Q21-32E).
l PST scheduler package (optional)PST(*1)standsforapartialstroketest.ThePSTschedulerschedulesPST,automaticallyexecutesPSTinaccordancewiththeschedule,andmanagestheresultsinunifiedmanners.FunctionstomodifytheplannedschedulesandswitchPSTexecutionfromautomatictomanualareavailable.Fordetails,refertotheGS“PSTSchedulerPackage”(GS33Y05Q23-32E).
*1: Byslightlyoperatingemergencyshutdown(ESD)valvesonlinewhicharenotactivatedundernormalconditions,PSTistocheckifESDvalvesfunctioncorrectlyincaseofemergency.ByusingPST,theintervalperiodbetweenfullstroketestscanbeprolongedwithoutdisturbingthesafetyoftheESDvalves,thusthemaintenancecostforthoseESDvalvescanbereduced.
l Interface for Computerized maintenance management system (optional)PRMhasaninterfacewithMaximoAssetManagement,acomputerizedmaintenancemanagementsystem(CMMS),fromIBMSoftware,Inc.Withthisinterface,PRMcanprovidemaintenanceinformationtothemaintenancemanagement system online.Fordetails,refertotheGS“InterfaceforCMMS”(GS33Y05Q20-32E).
l Interface for GE Energy’s System 1® (optional)PRMcanprovideasinglemonitoringwindowfordiagnosisofturbines,rotatingequipmentandreciprocatingequipmentundermanagementbyGEEnergy’sSystem1optimizationanddiagnosticssoftwareplatforminadditiontofielddevicessuchaspressuretransmittersandflowmeters.Fordetails,refertotheGS“InterfaceforGEEnergy’sSystem1”(GS33Y05Q22-32E).
3<<Contents>> <<Index>>
All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation GS 33Y05Q10-32E Sep. 7, 2016-00
SYSTEM CONFIGURATIONPRMmanagesinformationoffielddevicesbythePRMserverasaunit.ThePRMsystemcanbeconfigurableinscalableways–aminimumsystemconsistsofaPRMserver,aFieldcommunicationsserver,andaPRMclientallresidedinasinglecomputer,oralargesystemwithmultipleclients.ExamplesofPRMsystemconfigurationsareshown in this section.
l System configurationCENTUM VP/CS 3000
CENTUM HIS/ENG
PRM client
PRM server
Ethernet
Ethernet
Control network
HART devices
AnalogHART I/O module
ALP121(*2)
PROFIBUS-DP
PROFIBUS devices
FieldMate
ALF111
FCS FCS FCS
F01E.ai
Terminator
YFGW410Field wirelessmanagementstation
FOUNDATION fieldbusPower supply + Terminator
YFGW410Field wirelessmanagement
station
Firewall
L3 switch
Wide-area field network
Field wireless devicesHIS: Human interface stationENG: FCS: Field control stationALF111: FOUNDATION fieldbus communication module
FF-H1 devices
Field wireless devices
(*1)
ALE111
ALE111: Ethernet communication moduleALP121: PROFIBUS-DP communication module
Field communications server
Engineering station
TM1READY
FUSE RL1 CN1 (PSU-L) TM2 100-120V AC
CN2 (PSU-R)
TM1READY
FUSE RL1 CN1 (PSU-L) TM2 100-120V AC
CN2 (PSU-R)
TM1READY
FUSE RL1 CN1 (PSU-L) TM2 100-120V AC
CN2 (PSU-R)
Figure CENTUM VP System Configuration (for FIO)Note:APRMserver,aPRMClientandaFieldCommunicationsServercanrunonasinglecomputer. APRMclientcanrunonthesamecomputerwhereHIS/ENGisalreadyinstalled. APRMserveroraFieldcommunicationsservercannotrunonthesamecomputerwhereHIS/ENGisalreadyinstalled.*1: ProcessdataanddiagnosisstatuscanbedisplayedonanHIS. AsforconfigurationofISA100.11afieldwireless,refertotheGS“Fieldwirelesssystemoverview”(GS01W01A01-01EN).*2: ALP121issupportedbyCENTUMVPR5.02orlaterrevision.
4
All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation
<<Contents>> <<Index>>
GS 33Y05Q10-32E
CENTUMHIS/ENG
A2EN40: N-ESB Bus coupler moduleNIU: Node interface unit
PRM serverField communications server
Control network
Ethernet
F12E.ai
HARTdevices
FCS (A2FV50) (*1)
PRM client
N-IO I/O unit
A2EN40
TM1READY
FUSE RL1 CN1 (PSU-L) TM2 100-120V AC
CN2 (PSU-R)
HARTdevices
FCS (A2FV70) (*2)
I/O unit
A2EN40
TM1READY
FUSE RL1 CN1 (PSU-L) TM2 100-120V AC
CN2 (PSU-R)
NIUNIU
Figure CENTUM VP System Configuration (for N-IO)Note:APRMserver,aPRMclientandaFieldcommunicationsservercanrunonasinglecomputer. APRMclientcanrunonthesamecomputerwhereHIS/ENGisalreadyinstalled. APRMserveroraFieldcommunicationsservercannotrunonthesamecomputerwhereHIS/ENGisalreadyinstalled.*1: A2FV50issupportedbyCENTUMVPR6.01orlaterrevisionandPRMR3.02orlaterrevision.*2: A2FV70issupportedbyCENTUMVPR6.03orlaterrevisionandPRMR3.31.00orlaterrevision.
June 30, 2017-00
5<<Contents>> <<Index>>
All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation GS 33Y05Q10-32E
STARDOMMessagesfromSTARDOMcontrollersaretransmittedtoaPRMserverviaanOPCserver.FCN/FCJOPCserverforWindows(asoftwarepackage)isrequired.
HMI client
FCN/FCJ
HMI serverData server
OPC server
Control network
Ethernet
FCN
PRM client
PRM serverField communications server
Logic designer resource configurator
Controller
VDS/HMI PRM
CPU NFLF 111 PSU
FCJ (with FOUNDATION fieldbus H1 port)
F10E.ai
FOUNDATION fieldbus H1 Fieldbus
FOUNDATION fieldbus H1 Fieldbus
Terminator
Coupler
Terminator
Coupler
Field wireless devices
YFGW410Field wireless managementstation
YFGW510Field wirelessaccess point
HART I/O module
PROFIBUS-DP
HART devices
FCN Controller
PSU NFAI 141
CPU NFAI 841
NFAI 835
NFAI 135
PROFIBUSslave devices
NFLP 121
CPU
FieldMate
VDS: STARDOM versatile data serverHMI: Human machine interfaceFCU: STARDOM autonomous controller (field control node)FCJ: STARDOM autonomous controller (field control junction)NFLF111: FOUNDATION fieldbus communication moduleNFAI***: Analog I/O modules (with HART communication function)NFLP121: PROFIBUS-DP communication module
FF-H1 devices
FF-H1 devices
Figure STARDOM system configuration
Note: APRMserver,aPRMclientandaFieldcommunicationsservercanrunonasinglecomputer. APRMclientandanHMIclientcanrunonthesamecomputer. APRMserveroraFieldcommunicationsservercannotrunonthesamecomputerwhereVDSisalreadyinstalled.
Sep. 7, 2016-00
6
All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation
<<Contents>> <<Index>>
GS 33Y05Q10-32E
Notes for STARDOM configuration:PRMpackagescannotbeinstalledonacomputerwhereSTARDOMversatiledataserver(VDS)isalreadyinstalled.InstallingtheFCN/FCJOPCserverforWindowspackageonadifferentcomputerseparatelyfromthePRMpackagesis recommended.RefertothetablebelowforcombinationofthesoftwarerevisionnumberswheninstallingFCN/FCJOPCserverforWindowspackageonthesamecomputerwiththePRM.Thosecombinationsotherthanshownhere,FCN/FCJOPCserverforWindowsmustbeinstalledonadifferentcomputerseparatelyfromthePRMpackages.
FCN/FCJ OPC server for Windows PRM
Revision R1.90 R3.02
R2.20 R3.03, R3.04
R3.01 to R3.10 R3.05
– R3.10
R3.20 to R3.40 R3.11
– R3.12 or later
Upto100unitsofFCN/FCJcontrollerscanbeconnectedtoaFieldcommunicationsserver.Asforalarge-scalesystem,multi-serverfunctionshouldbeusedtodividethenumberofcontrollersconnectedtoaPRMserverbythegroup of 100 units or less.
ProSafe-RSPRMcanmanageHARTfielddevicesconnectedtoProSafe-RS’sHARTI/Oanalogmodules.
HIS/ENG PRM clientPRM serverField communications server
Control networkBus 2Bus 1
F15E.ai
HART devices
ProSafe-RS
HART I/Omodule
SCS (S2SC70) (*1)
NIU
S2MMM843
SENG
HART devicesSENG: Safety engineering stationSCS: Safety control stationNIU: Node interface unit
TM1READY
FUSE RL1 CN1 (PSU-L) TM2 100-120V AC
CN2 (PSU-R)
Figure ProSafe-RS System ConfigurationNote:APRMclientandSENGcanrunonasinglecomputer. APRMserveroraFieldcommunicationsservercannotrunonthesamecomputerwhereSENGisalreadyinstalled.Note: FromR3.12onwards,PRMsupportsVnet/IP-Upstreamwherethecontrolbus’sbandwidthis2Mbpsorfaster.Formore
details,refertotheGS“ProSafe-RSSafetyInstrumentedSystemOverview(forVnet/IP-Upstream)”(GS32P01B30-01EN).*1: S2SC70issupportedbyProSafe-RSR4.01orlaterrevisionsandPRMR3.30orlaterrevisions.
Sep. 7, 2016-00
7<<Contents>> <<Index>>
All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation GS 33Y05Q10-32E
Communication with HART devices via multiplexerPRMcancommunicatewithHARTdevicesviaaHARTmultiplexerconnectedtotheserialportsoftheFieldcommunicationsserver.
Ethernet
Field communications server
PRM client
HART devices
HART devices
HART devices
PRM server
Control network
Analog I/O module
F05E.ai
FCS
HIS/ENG
HART multiplexer(3rd party)
HART multiplexer(3rd party)
RS-485/ Ethernet converter
HART devices
HART digital signals
4 - 20 mA
TM1READY
FUSE RL1 CN1 (PSU-L) TM2 100-120V AC
CN2 (PSU-R)
Figure Serial port connection via HART multiplexer (Parallel connection and two-way data flow)Note:APRMserver,aPRMclient,andaFieldcommunicationsservercanrunonasinglecomputer.
Sep. 7, 2016-00
8
All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation
<<Contents>> <<Index>>
GS 33Y05Q10-32E
FUNCTIONAL SPECIFICATIONSl Organization of functionsThefollowingfigureshowstheorganizationoffunctions.
Device navigator
PRM
Maintenance information management
Audit trail management
Adjustment and diagnosis
Other functions
Plant viewNetwork viewClass viewSignal viewCustom view
Device masterInspection memoInspection scheduleParts listLink to document
Parameter setting and tuning - DTM works - Parameter mangerFF DD menu windowDeviceViewerCalibration management (Optional)
Operation logEvent log of deviceInspection logRecord filtering
PRM advanced diagnosis (Optional)
BrowserSecurityExportSelf-documentationPLUG-IN applicationDevice templateDatabase maintenance toolOnline instruction manualPRM system backupFieldMate synchronization
Diagnostic navigatorPRM advanced diagnosis application (PAA)Device diagnosis data historianGeneral-purpose diagnosis tool
Maintenance alarm
Message acquisitionDevice patrolFiltering
Maintenance mark
PST scheduler (Optional)
Interface for GE Energy’s System 1 (Optional)
PRM advanced diagnostic application softwaredevelopment kit (Optional)
Interface to computerized maintenance management system (Optional)
F03E.ai
Figure Organization of functions
Sep. 7, 2016-00
9<<Contents>> <<Index>>
All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation GS 33Y05Q10-32E
l Device navigatorFourdifferentviews-plantview,networkview,classview,signalview,andcustomview–areprovided.Eachviewdisplaysdevicesinaplantintheformofaplanthierarchytreeview,intheWindowsexplorer-likeformat.Intheseviews,devicestatusanddevicepriority are shown with icons so that operators are able tojudgethemaintenancepriorityofthedevicesataglance.Wheretherearedeviceswithunacknowledgedmaintenance alarms, unacknowledged alarm icons are displayed.Useraccessescanberestrictedbasedonthedevicenavigatorhierarchy,whichpreventsanunauthorizedpersonnelfromoperatingdevicesbymistake.
Plant viewFacilitiesandequipmentintheplantinhierarchytreeviewaccordingtotheactualstructureoftheplantortheplantlayeraredisplayed.Not-in-usedevicescanbeallocatedeithertothe“Spare”folderforsparesandfailedorin-servicedevicestothe“Outofservice”folder.
Network viewThenetworkhierarchyoffielddevicesconnectedtothefieldnetworkinthetreeviewformisdisplayed.
Class viewFielddevicesinatreeviewbyvendors,models,andrevisionsaredisplayed.Userscanidentifythestatusofhowsparedevicesareusedwhiledevices-in-usearefailedorundermaintenance.Devicetemplatescanbecreated using this function.
Signal viewBasedonthefielddevicediagnosisresult,fielddeviceswhichareeitherhavingoperationalproblemorrequiringmaintenancearedisplayedinatablesortedbythestatussignals.Onlythefielddevicesthatrequiremaintenance can be shown on the list sorted by the category,whichenablestomaintainthefielddevicesknowing the priority. Four status signals - failure, check function,outofspecification,andmaintenancerequired-areprovidedbasedontheNE107recommendedbyNAMUR.
Custom viewUser-createdviewscanbecreatedanddisplayedinthehierarchicalstructure.Fielddevicescanbecategorizedby persons in charge of maintenance, inspection or replacement schedule, operation or failure status, and so on.
l Maintenance mark Maintenance marks are assigned electronically to each devicetoletmaintenanceengineersidentifystatusofadevice.ThemaintenancemarksareenabledtolinkwithCENTUM’soperationmarkssothatmaintenanceengineers and operators can share the same information and coordinate their work.
l Maintenance alarm functionAmessagesystemtonotifymaintenanceinformationandinformationnecessaryforfielddevicemaintenanceto all the maintenance engineers. The information contains not only messages generated by the fielddevices,butalsoattributessuchasmessageinformation,phenomenon,causes,andactions.Alarmsgeneratedbydiagnosticfunctionscanalsobedeliveredto the users.
Message acquisitionMessagesfromfielddigitaldevicesaswellaseventmessagesgeneratedbyCENTUM,STARDOMProSafe-RS,andthird-partysystemsareacquired.User-definedinformationsuchaseventpriorities,objectiveinformation,phenomenon,causes,andactionsareautomaticallyaddedtotheoriginaleventmessages, which are acknowledged as maintenance alarms,andpassedontothefilteringfunction.
Device patrolFielddevicestatusprovidedbydevice’sself-diagnosticsareacquiredtogeneratemaintenancealarmswiththeuser-definedattributessuchasmessagepriorities,objectiveinformation,phenomenon,causes, and actions. These maintenance alarms are handedovertothefilteringfunction.Dataacquisitionisperformed periodically or on demand. Information from deviceswhichdonotgeneratealarmmessagesbythemselvescanalsobeacquired.
Filtering functionAllthealarmsgeneratedbymessageacquisition,devicepatrol,advanceddiagnosticapplication,andmanually-enteredmessagesarefilteredandtheresultsarenotifiedtobyeachuser.
Sep. 7, 2016-00
10
All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation
<<Contents>> <<Index>>
GS 33Y05Q10-32E
l Maintenance information managementPRMactsasacentraldatabasefordevicemaintenance information.
Device masterAlistoffielddevicesaregeneratedandmanagedwithalltherelevantinformation.Thelistofalltheregisteredfielddevicesanddetailedinformationoftheindividualfielddevicescanbedisplayed.Fielddeviceswithfieldcommunication function can be added automatically tothedevicelistbyplug&playwhenthedevicesarerecognized.
Inspection memoDetailsofinspection,maintenance,andservicingtasksperformedonadeviceorataplantareincluded.Comments and remarks by maintenance engineers duringservicingormaintenancecanalsobeincludedastheservicelogs.
Inspection scheduleSchedulesforinspection,adjustment,andcalibrationscanbemanagedbythefielddevice.
Parts listComponents and attribute information of parts whichcomposeofafielddeviceareincluded.AsforYokogawafielddeviceswithdigitalnetworkcommunication function, dedicated templates are provided.
Document linksFielddevicerelateddocumentssuchasplantstructures(e.g.P&IDandcontroldrawings),componentsparepartslist,onlineinstructionmanuals,anddeviceimages are freely allocated and enables users to accessthembythedevicetagnameaskeys.ThesedocumentscanbestoredinadocumentserveronanEthernetandaccessedbyURLaddresses.
l Audit trail managementHistoricalrecordsofPRMoperations,inspectionrecords,andeventinformationgeneratedbythemaintenance alarm function are managed and displayed on the PRM client. These historical records canbeshowninchronologicalorders,devicepriority,or message priority. The records can also be displayed filteringbythedeviceIDsordevicetagnames.
l Adjustment and diagnostic functionsOnlineadjustmentanddiagnosticfunctionsoffielddevicesaresupported.
Parameter tuning and comparisonDeviceparameterscanbesetanddisplayedonline.ThisfunctionenablesPRMtocomparethesavedparameterswithactualones.Theparametersetvaluesaresavedaslogs.Thedevicedatacanbeuploadedand stored to the database at any time. PRM also supports one-time uploading of all the connected devices.
ToolsDDmenu:forFoundationfieldbus UsingDDfilesprovidedbyvendors,PRMimplementsdevicediagnosticsandparametertuningandsetting,andcalibrations.ThespecificationsoftheDDfilesaredifferentbythefielddevices.
DeviceViewer:forFoundationfieldbus,HARTandISA100.11a
APLUG-INapplicationtodisplayresultsoffielddeviceself-diagnosis.Mostofthefielddevicesholdself-diagnosticresultsasthevendor-specificparameters.TheDeviceViewerreadsthoseself-diagnostic results and displays them in user-friendly ways.TheDeviceVieweralsodisplaysfielddeviceinformationwhichisusuallydisplayedontheLCDofthedevices,whichenablesuserstoremotelymonitorthedevicesconnectedtoPRMwithoutviewingthelocalLCDs.
DTMWorks:forFoundationfieldbus,HART,PROFIBUSandISA100.11a
UsingdeviceDTMsprovidedbyvendors,PRMimplementsdevicediagnosticsandparametertuningand setting, and calibrations.
PRMAdvancedDiagnosticFunction:forFoundation fieldbusandHART
PRMconductsadvanceddiagnosticanalysisforfielddevices.
Calibration data managementThedevicecalibrationdataaremanagedandmaintained by the PRM. Calibration results, differences,andjudgment(passorfail)areregisteredto the database and displayed on a PRM client. The calibrationdataapprovalfunctionallowsonlytheauthorizedpersontomodifythecalibrationdataonceitisapproved.Themodificationofthecalibrationdatais recorded as an operation history by the historical operation management function.When the documenting calibrator is used, the calibrationdatacanbeupload/downloadviacommunication. The calibration results are automaticallysavedintothedatabase.Thedocumentingcalibratorconnectionisprovidedasoptional.
Sep. 7, 2016-00
11<<Contents>> <<Index>>
All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation GS 33Y05Q10-32E
l Other functionsBrowserAspecificdevicecanbesearchedbythedeviceattributesinformationaskeywordssuchasdeviceID,devicetagname,devicetagcomments,blockname,and parameters.
SecurityFormaintainingfielddevices,onlytheauthorizedpersonnel is allowed to access PRM or the scope of workislimitedsoastopreventtroublescausedbymis-operations from happening or secure system safety.Ausernameisusedtoidentifytheuserandtheusername is recorded to the operation records. The user operationsanditsprivilegesarerestrictedbytheusergroup where they belong.Byusingthedevicesecurityfunction,fielddevicescanbedisplayedonthedevicenavigatoronlyforthespecifiedusergroup.
ExportAdevicelist(deviceID,devicetagname,devicetagcomments, etc.) registered to the PRM database can beexportedasatextfileinCSVfileformatsothatthePRM’sdeviceinformationcanbeutilizedbyothersoftware such as asset management.
Self-documentationThe data stored in the PRM database can be output inadocumentformattolettheusersmanagedevice-related information electronically and print out on demands. The information displayed on each window can also be printed out in a format to be used as a maintenance report.The following printing properties can be edited.•Printingrange•Tableofcontents•Header/footer•Coverpage
PLUG-IN applicationsAPLUG-INapplicationisYokogawaorathird-partysoftware program that runs on a PRM client computer. FielddevicesandPRMdatabaseareaccessedviaPLUG-INapplicationlibrary.
Supported PLUG-IN applications•DeviceViewer•PLUG-INValveNaviforYVP110(PRMR2.1orlater)(*1)
•OtherthirdpartyPLUG-INapplicationsapprovedbyYokogawa.
*1: PLUG-INValveNaviisasoftwareprogramforYVP110valvepositionercompliedwithFoundation fieldbus to calibrate and execute advanceddiagnosticsusingsignaturefunctionsuchasdevicediagnosis.ItsfunctionsareequivalenttoYVP20S,astand-alonetypeValveNavi.FormoredetailsoftheValveNavifunctions,pleaserefertotheGS"YVPManagementSoftware"(GS21B04C50-01E).
Device template functionTemplatesareprovidedwithwhichausercandefinedeviceinformationofitsown.Thesetemplateshelpsimplifyengineeringworkofindividualdevicesettings.
Database maintenance toolPRM’sdatabasesizeincreasesinaccordancewiththenumberoffielddevicesconnected.Historicalrecordsofparametersalsoincreaseoveralongperiodofoperations.ThistoolhelpstuningandoptimizingthePRMdatabasetobeusedefficiently.Thedatacanalsobe maintained easily.
Online instruction manualAlltheinstructionmanualsareprovidedinPDFformatonaCD-ROM.Usersareabletoviewandprinttheelectronic instruction manuals on-demand.
PRM system back-up scriptUserscanbackupandrestorethePRMdatabasedontheuserenvironment.Registryinformation,PRMdatabase,advanceddiagnosisdatabaseandsooncanbe backed up.
l Relevant solutionField asset KPI reportThistoolprovidesservicesolutionsforplantequipmentsuch as status monitoring, performance diagnosis, andefficiencyimprovements.Usingtheintelligentfunctionsofthefielddevices,thetoolacquiresdevicestatus,availability,numberofalarms&events,andtheir rankings to automatically create the KPI report. Thereporthelpsoperatorstograsptheoverallstatusofthefielddeviceswiththeirowneyes.TheKPI report also helps make maintenance plans with prioritiesdependingonthedeviceconditions.Fordetails,refertotheGS“FieldAssetKPIReport”(GS43D02S03-02EN).
F13E.ai
Figure Field Asset KPI Report for PRM
Sep. 7, 2016-00
12
All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation
<<Contents>> <<Index>>
GS 33Y05Q10-32E
l Supported functionsPRM’ssupportedfunctionsdifferbythekindsoffielddevices.Therelationshipbetweenthefielddevicesandtheircomplied functions are as shown below.
Table Supported Functions
Function Conventional
Devices(*1)
Foudation fieldbus
HART (*2)
ISA100.11a(*3)
PROFIBUS(*4)
Devicenavigationfunction
Plantview XX XX XX XX XXNetworkview — XX XX XX XXClassview XX XX XX XX XXSignalview — XX XX XX XXCustomview XX XX XX XX XX
Maintenance mark XX XX XX XX XX
Maintenance information management functions
Devicemaster XX XX XX XX XXPlug&Play — XX XX XX XXRegister from host fileset — XX X — X
Inspection memo XX XX XX XX XXInspection schedule XX XX XX XX XXParts list XX XX XX XX XXLinktodocument XX XX XX XX XX
Audittrailmanagement function
Parameter history — XX XX XX XXInspection memo history XX XX XX XX XX
Operationhistory XX XX XX XX XXDeviceeventmessage — XX XX — XX(*5)
Adjustmentanddiagnosis
Parameter tuning and comparison — XX XX XX —
Status display — XX XX XX XXTool — XX XX XX XXCalibration — XX XX — —
Maintennancealarm
Plantview — XX XX XX XXNetworkview — XX XX XX XXClassview — XX XX XX XXCustomview — XX XX XX XX
Otherfunctions
Browser XX XX XX XX XXSecurity XX XX XX XX XXPrinting XX XX XX XX XXPLUG-INapplication — XX XX XX —FieldMate synchronization XX XX XX XX XX
XX: Supported X: Partly supported —: Not applicable
*1: Theconventionaldevicesreferto4to20mAanalogdevicesandstaticdevicessuchasmotors.*2: HART5,6,and7aresupported,butWirelessHARTisnotsupported.*3: ConformstoISA100.11awirelesssystemforindustrialautomation.(ISA=InternationalSocietyofAutomation)*4: ConditionmonitoringwithdevicenavigatorisavailableforPROFIBUSPAdevicewhichconformstoPAprofile.Tofindoutif
thedevicesconformtoPAprofile,visitthePROFIBUSInternationalwebsiteoritsdevicevendors.*5: PROFIBUSdeviceeventmessagesareacquiredviaALP111orALP121PROFIBUS-DPCommunicationmodule.
Sep. 7, 2016-00
13<<Contents>> <<Index>>
All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation GS 33Y05Q10-32E
MULTIPLE SERVER SWITCHOVERAssetmanagementofmultipleplantscanbeintegrallymanaged.A“server-set”concepthasbeenintroducedandenablesaPRMclienttoswitchfromaFieldcommunicationsserverandaPRMservertootherservers.Auserhastodefinetheserver-setbeforeuse.Withthisswitchoverfunction,aPRMclientmanagesallthedevicemanagementinformation of the multiple plants at a single location.
PRMcanbeconnectedwithCENTUM,STARDOM,orProSafe-RSsystemsonthesameEthernet.
Ethernet
Ethernet
Router
Control network
Server set A
PRMclient
PRM clientwith multiple servertswitchover function
F07E.ai
PRMserver
Switchover between the server sets
Field communications server
HIS
FCS
Ethernet
Control network
Server set B
PRMclient
PRMserver
Field communications server
HIS
FCS
Router
TM1READY
FUSE RL1 CN1 (PSU-L) TM2 100-120V AC
CN2 (PSU-R)
TM1READY
FUSE RL1 CN1 (PSU-L) TM2 100-120V AC
CN2 (PSU-R)
Figure Multiple server switchover
Sep. 7, 2016-00
14
All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation
<<Contents>> <<Index>>
GS 33Y05Q10-32E
OPERATING ENVIRONMENTl Hardware requirementsTherequiredmainmemorysizeanddiskcapacitydependonthenumberoffielddevicesregisteredtothePRM.Theminimumhardwarerequirementisdescribedherewhennomorethan3000devicesareconnectedtoaPRMserver.Forconnectingmorethan3000devices,pleaseconsultYokogawa.IncasethesizeoftherequiredmainmemorydiffersbetweentheWindowsOSandthePRMpackages(PRMserver,PRMclient,andFieldcommunicationsserver),applythelargerofthetwovalues.
Main memory size required by Windows OSThemainmemorysizesrequiredbytheapplicableWindowsOSareasdescribedasbelow:
Table Required main memory size by Windows OS
Memory Size OS
Minimum memoryrequirement
Recommended(for better performance)
Windows Vista Business Edition SP2 512MB 1GBormore
Windows Server 2008 Standard Edition SP2 or Windows Server 2008 R2 Standard Edition SP1 512MB 2GBormore
Windows 7 Professional Edition SP1 2GB 4GBormore
PRM serverCPU:Refertothetablebelow.Main memory: Refer to the table below.Harddiskspace:Refertothetablebelow.Peripheraldevices:DVD-ROMdrive Ethernet cardDisplayresolution/colors:256colorsormore
Table PRM server hardware requirements (without Advanced diagnosis server)
Number of field devices300 units or less 1000 units or less 3000 units or less
CPU Pentium-1GHzorhigher(required)
Pentium-1GHzorhigher(required)Pentium4-2.8GHzorhigher(recommended)
Pentium4–2.8GHzorhigher(required)XeonDual–2.8GHzorhigher(recommended)
Main memory 512MBormore(required)2GBormore(recommended)
512MBormore(required)2GBormore(recommended)
1GBormore(required)2GBormore(recommended)
Harddiskcapacity(*1) 6GBormore(required)
8GBormoreoffreespace(required)Useofahigh-speeddiskdrivesuchasSCSIorRAIDdriveisrecommended.
13GBormoreoffreespace(required)Useofahigh-speeddiskdrivesuchasSCSIorRAIDdriveisrecommended.
Devicedatabasecapacity(*2) 600MB 2GB 6GB
Note: WhenthesystemconfigurationincludesAdvanceddiagnosisserver,refertotheGSof“PRMAdvanceddiagnosisserver(R3)”(GS33Y05Q21-32E)forhardwarerequirements.
*1: Therequiredharddiskcapacityincludesthedatabasecapacityspecifiedin(*2).*2: Thedevicedatabasecapacitycoverstherequiredsizeforoneyearoperation.Thesizeiscalculatedwiththeassumption
thatcomparingandsavingtheparametersofalldevicesandfunctionblockswithparametermanagerforfivetimesayear.
PRM clientCPU:Pentium1GHzorhigherMainmemory:512MBormore(required),1GBormore(recommended)Harddiskspace:2GBormoreCommunication unit: Ethernet cardPeripheraldevices:DVD-ROMdriveDisplayresolution/colors:1024x768orhigher,256colorsormore
Sep. 7, 2016-00
15<<Contents>> <<Index>>
All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation GS 33Y05Q10-32E
Field communications serverCPU:PentiumIII1GHzorhigherForconnecting2000devicesormore,2.8GHzorhigherisrequired.Main memory: Refer to the table below.Harddiskspace:1GBormoreCommunication unit: Refer to the table below.Peripheraldevices:DVD-ROMdriveDisplayresolution/colors:256colorsormore
Table Hardware requirements for Field communications server
Connecting with CENTUM VP/CS
3000 or ProSafe-RSConnecting with
STARDOM
Connecting via NI-FBUS simplified
system for Foundation fieldbus
Connecting withsimplified system
for HART device or HART multiplexer
Connecting viacommDTM/
gatewayDTM
Main memory (*1)(*2)
•FCS/SCS1-16units(100+80 x number ofFCS/SCS)MBormore recommended
•FCN/FCJ1-16units(100+60 x number ofFCN/FCJ)MBormore recommended 256MBormore
required512MBormorerecommended
256MBormorerequired512MBormorerecommended
256MBormorerequired{30+(commDTM/gatewayDTMmainmemory)×(No. of node)}MBormorerecommended
•FCS/SCS17-44units (1380+10 x (numberofFCS/SCS-16))MBormore recommended
•FCN/FCJ17-100units (1060+5 x (numberofFCN/FCJ-16)MBormorerecommended
Communication devices
Ethernet card Control bus interface card Control network interfacecard(VF702,VI702)
Ethernet card Ethernet cardFoundationfieldbusH1interfacecard
Ethernet cardCOMport Ethernet Card
*1: ThespecifiedhardwarerequirementsdonotincludetherequirementforthirdpartyCommDTM/GatewayDTM.RefertotherespectiveDTMdocumentation.
*2: Thetotalmemoryrequirementshouldbethesumofthememoryrequirementforeachrequiredfunctionandconnectedsystem.
All-in-one configuration (when all components – PRM server, Field communications server, and PRM client - are installed in a single computer)
NumberofconnectableFCS/SCS:Maximum24stationsorless.Whenthenumberofstationsexceeds25,installPRMserverandfieldcommunicationsserveronseparatecomputers.
CPU:ThemaximumCPUcapabilityamongthoserequiredfortherespectivepackages,orhigher.Mainmemory:Totalsumofmemorysizerequiredfortherespectivepackagesortheoperatingsystem(whichever
is higher) or more.Harddiskcapacity:Inadditiontothetotalsumofavailableharddiskspacesrequiredfortherespectivepackages,
approx.1GBormoreofvirtualmemoryareaisrequired.Displayresolution/colors:1024x768orhigher,256colorsormore
OPC server (for STARDOM system)CPU:Pentium300MHz,400MHz,orfasterrecommendedMainmemory:256MB,512MB,ormorerecommendedDiskcapacity:Minimum1GBoffreespace.Ethernetcard:100BASE-TX,10BASE-T,10BASE-5
ForSTARDOMconnection,twocommunicationdevicesarerequiredtosegregateinformationandcontrolnetworks.
Sep. 7, 2016-00
16
All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation
<<Contents>> <<Index>>
GS 33Y05Q10-32E
l Software requirementsPRM server, PRM client, and Field communications server
Windows XP Professional
Windows Server 2003
Windows Server 2003 R2
Windows Vista Business Edition
Windows 7 Professional
Windows Server 2008
Standard
Windows Server
2008 R2 Standard
32-bit 32-bit 32-bit 32-bit 64-bit 32-bit 64-bitSP2 SP3 SP1 SP2 — SP2 SP1 SP2 SP1 SP2 SP1
R3.01 X N/A X N/A X N/A N/A N/A N/A N/A N/A
R3.02 X N/A N/A X N/A X N/A N/A N/A N/A N/A
R3.03 N/A X N/A X N/A X X N/A N/A N/A N/A
R3.04 N/A X N/A X N/A X X N/A N/A N/A N/A
R3.05 N/A X N/A X N/A X X X N/A X N/A
R3.10 N/A N/A N/A N/A N/A N/A N/A X X X X
R3.11 N/A N/A N/A N/A N/A N/A N/A X X X X
R3.12 N/A N/A N/A N/A N/A N/A N/A X X X X
R3.20 N/A N/A N/A N/A N/A N/A N/A X X X X
R3.30 N/A N/A N/A N/A N/A N/A N/A X X X X
R3.31.00/R3.31.10 N/A N/A N/A N/A N/A N/A N/A X X X X
SP:Servicepack X:Applicable N/A:Notapplicable
PRM serverInternet Explorer 8.0, 9.0, or 11.0MicrosoftSQLServer2012SP3(32-bit)isusedasadatabasesoftwareandisincludedinthesoftwaremedia(SSSSM02) for the Plant Resource Manager. (R3.31.10)
PRM clientSoftwarefordocument:AdobeReader10.1,11.0,andDCField communication serverDriver: WhenPRMisconnectedwithCENTUMVP/CS3000and/orProSafe-RS,acontrolnetworkdriver (Vnet/IPorVnet)isrequired.(*1) ForconnectingwithsimplifiedsystemforFF-H1deviceadjustment,FF-H1fieldbusinterfacecarddriver
isrequired.Forcommunicatingwithdevicesviathird-partygatewaydevices,thethird-partyCommDTM/GatewayDTMarerequired(*2)
*1: Thecontrolnetworkdriverorcontrolnetworkitnerfacecards(VF702/VF701)arenotrequiredwhencommunicatingwithHARTdevicesviaHARTmultiplexersandCommDTM/GatewayDTM.
*2: Asforthethird-partysuppliedCommDTM/GatewayDTM,pleaseconfirmthevendorforwhichOSissupported.
l Software requirements for connected systemCENTUM VPCENTUMVP:R4.01orlater R4.01orlatertosupportHARTcommunication R4.02.30orlatertosupportISA100fieldwirelesscommunication R4.03.00orlatertosupportFastdevicepatrolforHARTForconnectingwithCENTUMVP,ExaopcOPCinterfacepackage(forHIS)R4.01orlaterorExaopcOPCInterfacePackage(NTPF100)R3.50orlaterisrequired.
CENTUM CS 3000CS 3000: R3.01 or later R3.02orlatertosupportHARTdevices R3.07orlatertonotifyHISofoperatorguidemessage R3.08orlaterforassociationwithConsolidatedalarmmanagementsoftwareforHIS(CAMSforHIS)ForconnectingwithCENTUMCS3000,ExaopcOPCinterfacepackage(forHIS)R3.01orlaterorExaopcOPCinterfacepackage(NTPF100)R3.01orlaterisrequired.AsforHARTdevicesupport,ExaopcOPCinterfacepackage(forHIS)R3.02orlaterisrequired.
June 30, 2017-00
17<<Contents>> <<Index>>
All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation GS 33Y05Q10-32E
Exaopc OPC interface packages required for connecting PRM with CENTUM systems
PurposeExaopc OPC interface package
(for HIS) (Model: LHS2411)
Exaopc OPC interface package(Model: NTPF100)
PRMtoacquirealarmmessagesfromCENTUMHIS X X
NotifyoperatorguidemessagesfromPRMtoCENTUMHIS X X(*1)
PRMtosynchronizethemaintenancemarkswithCENTUMoperation marks X X(*1)
X:Available*1: SupportedbyPRMR3.30orlaterrevision.
ProSafe-RSProSafe-RS: R1.02 or later R2.20orlatertosupportupstreamprojects R3.02.10orlatertosupportVnet/IPnarrowbandsystem R4.01.00orlatertosupportdevicestatusnotificationforHARTdevicesthatareconnectedtoN-IO.ForconnectingwithProSafe-RS,ExaopcOPCinterfacepackage(forHIS)needstobeR3.06orlater;andR3.07orlatertonotifyHISofoperatorguidemessage.Or,useExaopcOPCinterfacepackage(NTPF100)R3.01orlater.
STARDOMSTARDOM: R1.40orlater R1.60orlatertosupportHARTdevicesFCN/FCJOPCServerforWindows:R1.40orlater R1.60orlatertosupportHARTdevices
FieldMatePRM: R3.02orlatertosupportsynchronizationwithFieldMate.FieldMate: R1.03orlatertosupportsynchronizationwithPRM.
YOKOGAWA PRODUCTS AVAILABLE TO RESIDE WITH PRM ON THE SAME COMPUTER
l PRM clientCENTUMVPHIS CENTUMCS3000/HIS ProSafe-RS SENG STARDOMHMIClientComputer
MODELS AND SUFFIX CODESPRM Basic Set (for new installation)
Description Model PRMSET Plant resource manager basic set
Suffix Codes -S Basicsoftwarelicenseandmediafee 1 Always1 1 Englishversion
Option Codes
/N0025 Maximumnumberofconnecteddevices:25/N0300 Maximumnumberofconnecteddevices:300/N1000 Maximumnumberofconnecteddevices:1000/N3000 Maximumnumberofconnecteddevices:3000
Note: ThebasicsetincludeslicensesofaPRMclient,aPRMserver,andaFieldcommunicationsserver;asoftwaremediaforPRM;adevicefilesmedia;andanelectronicinstallationmanualmedia.
Sep. 7, 2016-00
18
All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation
<<Contents>> <<Index>>
GS 33Y05Q10-32E
PRM server (for new installation)
DescriptionModel SSS7700 PlantResourceManager(server)[Mediamodel:SSSSM02-C11]
Suffix Codes
-S Basicsoftwarelicense-C Multiple software licenses (for 2 or more) 1 Always1 1 Englishversion
Option Codes /N0300 MaximumNumberofconnecteddevices:300/N1000 MaximumNumberofconnecteddevices:1000/N3000 MaximumNumberofconnecteddevices:3000
Note: EveryprojectrequiresonePRMserver.Note: ThispackagecannotbeinstalledwithacomputerwhereCENTUMVP/CS3000HIS/ENG,ProSafe-RSSENG,or
STARDOMHMIclientisinstalled.Note: ThispackagecanbeinstalledinasinglecomputerwhereaPRMClientandaFieldcommunicationsserverareinstalled.Note: ExaopcOPCinterfacepackageforHIS(LHS2411)isrequiredtoacquiredevicealarmsandevents.
PRM server (for expansion)
Description Model SSS7700 PlantResourceManager(server)[Mediamodel:SSSSM02-C11]
Suffix Codes -A Softwarelicenseforadditionaldevices 1 Always1 1 Englishversion
Option Codes
/N0003 Expandmaximumnumberofconnecteddevices:25to300/N0010 Expandmaximumnumberofconnecteddevices:25to1000/N0310 Expandmaximumnumberofconnecteddevices:300to1000/N0030 Expandmaximumnumberofconnecteddevices:25to3000/N0330 Expandmaximumnumberofconnecteddevices:300to3000/T01 Add1000unitsofconnecteddevices/T02 Add2000unitsofconnecteddevices
Note: Optioncodesof/T01and/T02areapplicabletothePRMserverlicensefor1000devicesonlyandthetotalnumberofconnecteddevicesshouldnotexceed3000deviceswiththisoption.
PRM client
Description Model SSS7710 PlantResourceManager(client)[Mediamodel:SSSSM02-C11]
Suffix Codes
-S Basicsoftwarelicense-C Multiple software licenses (for 2 or more) 1 Always1 1 Englishversion
Note:ThispackagecanbeinstalledwithacomputerwhereCENTUMVP/CS3000HIS/ENG,ProSafe-RSSENG,orSTARDOMHMIclientisinstalled.
Note: ThispackagecanbeinstalledinasinglecomputerwhereaPRMServerandaFieldcommunicationsserverareinstalled.However,insuchcase,thispackagecannotbeinstalledonthesamecomputerwhereCENTUMVP/CS3000’sHIS/ENG,ProSafe-RS’sSENG,and/orSTARDOM’sHIMclientreside.
Field communications server
Description Model SSS7720 FieldCommunicationsServer[Mediamodel:SSSSM02-C11]
Suffix Codes
-S Basicsoftwarelicense-C Multiple software licenses (for 2 or more) 1 Always1 1 Englishversion
Note: The functions to communicate with Foundationfieldbus,HART,PROFIBUS,andISA100.11adevicesisincludedinthebasic software license.
Note: ThispackagecannotbeinstalledwithCENTUMVP/CS3000HIS/ENG,ProSafe-RSSENG,orSTARDOMHMIclientcomputer.
Note: ThispackagecanbeinstalledinasinglecomputerwhereaPRMserverandaPRMclientareinstalled.
Sep. 7, 2016-00
19<<Contents>> <<Index>>
All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation GS 33Y05Q10-32E
Documenting calibrator interface for PRM client
Description Model SSS7711 DocumentingCalibratorInterface[Mediamodel:SSSSM02-C11]
Suffix Codes -S Basicsoftwarelicense 1 Always1 1 Englishversion
Option Code /FLK01 ForFluke743B/744/754
Note: AbasiclicenseisvalidforinstallationsintwoormorePRMclientcomputers.Software media for Plant Resource Manager
Description Model SSSSM02 Software media for Plant Resource Manager
Suffix Codes -C Suppliedmedia:DVD-ROM 1 Always1 1 Englishversion
Note: TheelectronicinstructionmanualforthissoftwareisincludedinthemediamodelSSSSD02.Device files media
Description Model SSSSM03 Devicefilesmedia
Suffix Codes -C Suppliedmedia:DVD-ROM 1 Always1 1 Englishversion
Note: ThismediacontainsfielddevicerelatedfilessuchasDDandDTM.Electronic instruction manual media for PRM
Description Model SSSSD02 Electronic instruction manual media for Plant Resource Manager
Suffix Codes -C Suppliedmedia:CD-ROM 1 Always1 1 Englishversion
Note: ThePRMsoftwaremedia(SSSSM02)isrequiredtousethismedia.Note: Nolicenseisrequiredtousetheelectronicinstructionmanual.
PLUG-IN ValveNavi
Description Model SSS7750 PLUG-INValveNavi[Mediamodel:SSSAM02-C11]
Suffix Codes
-S Basicsoftwarelicense-C Multiple software license (for 2 or more) 1 Always1 1 Englishversion
Option Code /FF-H1 For Foundationfieldbusdevices(*1)
Note: This package runs on a computer where a PRM client (SSS7710) is installed.Note: OnlyFoundationfieldbusdevicesaresupported.Note: ThispackageisfortousewithYVP110advancedvalvepositioner.*1: ToconnectwithFoundationfieldbusdevices,ensuretospecifytheoptioncodeof“/FF-H1.”
Software media for PLUG-IN ValveNavi
Description Model SSSAM02 PLUG-INapplicationmediaforPlantResourceManager
Suffix Codes -C Suppliedmedia:CD-ROM 1 Always1 1 Englishversion
Note: ElectronicinstructionmanualforPLUG-INValveNaviisincludedinthissoftwaremedia.FCN/FCJ OPC server for WindowsFor more information, refer to GS 34P02Q61-01E.
Sep. 7, 2016-00
20
All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation
<<Contents>> <<Index>>
GS 33Y05Q10-32E
SOFTWARE LICENSE VERSION UPGRADE FROM R2 TO R3ThissectionisdedicatedforthePRMR2userswhowishtoupgradetoR3forthebenefitofusingnewfunctionsthatareonlyavailablefromR3.PurchaseeveryupgradingR3licensethatmatchwiththeexistingR2(basicandmultiplelicenses).SpecifythesamenumberofconnecteddevicesasR2.
PRM server for upgrading from R2 to R3
Description Model SSS7700RU PlantResourceManager(server)upgrade[Mediamodel:SSSSM02-C11]
Suffix Codes
-S Basicsoftwarelicense-C Multiple software license (for 2 or more) 1 Always1 1 Englishversion
Option Codes /N0300 Maximumnumberofconnecteddevices:300/N1000 Maximumnumberofconnecteddevices:1000/N3000 Maximumnumberofconnecteddevices:3000
Note: Theoptioncodeof“/N0100”inR2.10orearlierformaximumnumberofconnecteddevices100unitshasbeenexpandedto300unitsinR3.Specify“/N0300”inplaceof“/N0100.”
Note: PRMR3.12requiresMicrosoftSQLServer2012whichdoesnotsupportWindows2000/XP/2003.TherearetwowaystocopewithPRMR2operatingonWindows2000/XP/2003.OneistonewlyinstallR3.12.TheotheristoupgradetoR3.04first,replacetheOStothenewone,theninstallR3.12.Inthelattercase,thedevicefilesandotherdatabasecanbesaved.
PRM client for upgrading from R2 to R3
Description Model SSS7710RU PlantResourceManager(client)upgrade[Mediamodel:SSSSM02-C11]
Suffix Codes
-S Basicsoftwarelicense-C Multiple software license (for 2 or more) 1 Always1 1 Englishversion
Field communications server for upgrading from R2 to R3
Description Model SSS7720RU FieldCommunicationsServerupgrade[Mediamodel:SSSSM02-C11]
Suffix Codes
-S Basicsoftwarelicense-C Multiple software license (for 2 or more) 1 Always1 1 Englishversion
Note: CommunicationwithHARTdevicesisincludedasastandardfunctionfromR3,andthereisnoneedtospecify“/HART”option code which was necessary for R2.
Documenting calibrator interface for upgrading from R2 to R3
Description Model SSS7711RU DocumentingCalibratorInterfaceupgrade[Mediamodel:SSSSM02-C11]
Suffix Codes -S Basicsoftwarelicense 1 Always1 1 Englishversion
Option Codes /FLK01 ForFluke743B/744/754
Sep. 7, 2016-00
21<<Contents>> <<Index>>
All Rights Reserved. Copyright © 2006, Yokogawa Electric Corporation GS 33Y05Q10-32ESubjecttochangewithoutnotice.
PRM basic set for upgrading from R2 to R3
Description Model PRMSETRU Plant Resource Manager basic set upgrade
Suffix Codes -S Basicsoftwarelicenseincludesupgradesandmediafees 1 Always1 1 Englishversion
Option Codes
/N0025 Numberofconnecteddevice:25unitsorless/N0300 Numberofconnecteddevice:300unitsorless/N1000 Numberofconnecteddevice:1000unitsorless/N3000 Numberofconnecteddevice:3000unitsorless
Note: PRM basic set for upgrading can only be purchased when a user has R2 PRMSET. Specify the number of connecting devicesasthesameastheexistingone.
Note: ThebasicsetincludesaPRMserver,aPRMclient,afieldcommunicationsserver,asoftwaremediaforPRM,andanelectronic instruction manual media.
Note: Theoptioncodeof“/N0100”inR2.10orearlierformaximumnumberofconnecteddevices100unitshasbeenexpandedto300unitsinR3.Specify“/N0300”inplaceof“/N0100.”
ORDERING INFORMATIONSpecifymodelandsuffixcodes.
TRADEMARKS•PRMisaregisteredtrademarkofYokogawaElectricCorporation.•CENTUM,Vnet/IPandProSafeareregisteredtrademarksofYokogawaElectricCorporation.•STARDOMisatrademarkofYokogawaElectricCorporation.•Otherproductandcompanynamesappearinginthisdocumentaretrademarksorregisteredtrademarksoftheirrespectiveholders.