GRUNDFOS DATA BOOKLET
Fire NBF, Fire NKFGrundfos fire systems
Fire systems with electrically and diesel-powered pumps
according to EN 12845 and EN 12259-12
2
Contents
Performance rangeNKF, ordinay hazard (OH) 4
NBF, NKF, high hazard 5
Product descriptionIntroduction 6
EN standards 6
Fire NBF and NKF pumps 6
Identification 7
Fire system 7
Bare shaft pump 7
Pump characteristics 8
Electric motor 8
Diesel engine 8
Power rating 8
Controller 9
Other system components 9
Compressor 9
Scope of delivery 9
Commissioning 9
Curve chartsHow to read the curve charts 10
OH1 dry or alternate, OH2 wet or pre-action 11
OH2 dry or alternate, OH3 wet or pre-action 14
OH3 dry or alternate, OH4 wet or pre-action 17
High hazard 20
3
Fire NBF, Fire NKFPerformance range
Precalculated pumps
NBF and NKF pumps for Ordinary Hazard (OH)
classes.
(2-pole, 2950 to 3000 rpm)
Hazard class
Sprinkler height, height above the control valve set
[m]
Pump type
Nominal data Characteristics
Pressure[bar (m)]
Flow rate
[l/min (m3/h)]
Pressure[bar (m)]
Flow rate
[l/min (m3/h)]
Pressure[bar (m)]
Flow rate
[l/min (m3/h)]
OH1: wet or pre-action
0 < h 15 NKF 65-1601.2
(12.2)900(54)
2.2(22.4)
540(32.4)
2.5(25.5)
375(22.5)
15 < h 30
NKF 65-200
1.9(19.4)
1150(69)
3.7(37.7)
540(32.4)
4.0(40.8)
375(22.5)
30 < h 452.7
(27.5)1360(81.6)
5.2(53.0)
540(32.4)
5.5(56.1)
375(22.5)
OH1: dry or alternateOH2: wet or pre-action
0 < h 15 NKF 65-1601.4
(14.3)1750(105)
2.5(25.5)
1000(60.0)
2.9(29.6)
725(43.5)
15 < h 30
NKF 65-200
2.0(20.4)
2050(123)
4.0(40.8)
1000(60.0)
4.4(44.9)
725(43.5)
30 < h 452.6
(26.5)2350(141)
5.5(56.1)
1000(60.0)
5.9(60.1)
725(43.5)
OH2: dry or alternateOH3 wet or pre-action
0 < h 15 NKF 65-1601.4
(14.3)2250(135)
2.9(29.6)
1350(81.0)
3.2(32.6)
1100(66)
15 < h 30 NKF 80-2002.0
(20.4)2700(162)
4.4(44.9)
1350(81.0)
4.7(47.9)
1100(66)
30 < h 45 NKF 80-2502.6
(26.5)3100(186)
5.9(60.1)
1350(81.0)
6.2(63.2)
1100(66)
4
Performance range Fire NBF, Fire NKF
Calculated pumps
NBF and NKF pump for Ordinary Hazard (OH) and High
Hazard (HH) classes.
(2-pole, 2950 to 3000 rpm)
TM
04
66
16 0
61
0
10
15
20
30
40
50
60
80
100
150
200
300
400
500
600
Q [m³/h]
10
12
20
30
40
50
60
70
80
90
100
120
[m]
H
NBF/NKF
2 pole, 50 Hz
2950/3000 rpm
65-160
40-250
32-200
125-250
100-200
80-250
80-200
65-200
50-200
5
Fire NBF, Fire NKFProduct description
Introduction
Grundfos Fire NBF and Fire NKF fire systems are
typically used in fire-fighting applications for supplying
water to fire hose reels, fire hydrants or sprinkler
systems.
This data booklet covers fire systems with electric and
diesel-powered NBF and NKF end-suction pumps.
Designations
Fire NBF is an NBF end-suction pump with motor or
engine mounted on a common base frame.
Fire NKF is an NKF end-suction pump with coupling
and motor or engine mounted on a common base
frame.
The fire system can be incorporated into a fire-fighting
system.
EN standardsThe products in this data booklet have been built to
comply with EN standards on water-based fire-fighting
systems, described in the following documents:
• EN 12845: Fixed fire-fighting systems. Automatic
sprinkler systems. Design, installation and
maintenance
• EN 12259-12: Fixed fire-fighting systems. Pumps
for sprinkler and water spray systems.
Fire NBF and NKF pumps
Grundfos NBF and NKF pumps according to EN 12845
and EN 12259-12 are designed for the distribution of
water in stationary sprinkler systems using water spray.
They are operated in case of fire and during tests.
Materials
Requirements to pump materials according to
EN 12845 and EN 12259-12:
• Impeller and wear rings must be made of bronze.
• Wet parts such as shaft, washers and nuts must be
made of stainless steel.
• Castings must be made of cast iron.
6
Product description Fire NBF, Fire NKF
Identification
Fire system
Example of nameplate
Fig. 1 Example of nameplate
Type key for fire system
Bare shaft pump
Example of nameplate
Fig. 2 Example of nameplate
Type key for pumpTM
04
644
1 0
31
0
Example Fire NK F 80 -250 /270 E F X D B A B
Fire: Fire systems
Pump typeNBNK
F: Pump approved for fire-fighting
Nominal diameter of discharge port[mm]
Pump housing size[mm]
Actual impeller diameter[mm]
DriverD: Diesel engineE: Electric motor, 50 Hz
Approval of pumpG: EN
Approval of fire systemX: No approval
Pipe connectionsD: DIN
Control panel B:For mounting on base frameW:For wall mountingX:No panel
Shaft sealA: BAQE
CouplingA: Standard (NKF)B: Spacer (NKF)
Type:
part No.
serial No.
Main Supply:
impeller diameter:
Made in Germany P1 0640
Fire NKF 80-250/270-E-F-X-D-B-A-B
96157421
123456789
65542145624565
65542145624565
3X400V 50Hz
270
min2940n:55 kWP2:kg346G:55IP
Q: H: 112 m150 m /h3-1
TM
04
64
42
03
10
Example NKF 65 -200 /219 AH -F -B -BAQE -G
Type range:NBFNKF
Nominal diameter of discharge port [mm]
Nominal impeller diameter [mm]
Actual impeller diameter [mm]
Code for pump version:A = NBFAH = NKF
Code for pipework connection:F = DIN flange
Code for materials:B = EN-GJL-250 with bronze impeller
Code for mechanical shaft seal and rubber pump parts
Approval of pump:G = EN
-G
7
Product description Fire NBF, Fire NKF
Pump characteristicsEN 12845 and EN 12259-12 require stable QH
characteristics. The total head declines continuously
with increasing flow rate.
Fig. 3
Specific duty requirementsAn orifice plate can be included where the maximum
flow from the pump is critical (for determining the stored
water capacities). The effect of an orifice plate is to
throttle the pump curve and provide a steeper fall-off in
performance. This does, however, result in power
losses through loss of pump efficiency.
Impellers can be trimmed to provide a tailor-made
pump curve. This means that the closed-valve
pressure, power demand and potential maximum flow
rate from the pump are optimised to suit specific duty
requirements.
Performance curves of pumps used in precalculated
systems for hazard class OH1, OH2 and OH3 can be
seen on page 10 to 18. The pump impeller has been
trimmed and an orifice plate used to match the design
data requirements for the specific hazard class.
Electric motorThe electric motor is an MG or MMG motor complying
with local standards for electric motors. As from 16 July
2011, the motors used in Europe will be IE2 = EFF 1
motors.
Fig. 4 Fire NKF: An NKF end-suction pump with electric
motor and controller mounted on a base frame
Insulation class: F.
Enclosure class: IP55.
Diesel engineThe diesel engine can operate continuously at full load
at site elevation with rated output in accordance with
ISO 3046-1:1986. The pump is at full operational speed
within 15 seconds; the engine is capable of starting at
a room temperature of 5 °C.
Fig. 5 Fire NKF: An NKF end-suction pump with diesel
engine and controller mounted on a base frame
Each complete engine and pump unit is tested on the
manufacturers test bed for at least 1.5 hours at rated
flow rate. A supplier test is prepared, and the result
recorded on the test certificate.
TM
04
60
75
48
09
0 10 20 30 40 50 60 70 80 90 100 110 120
Q [m³/h]
0
5
10
15
20
25
30
35
40
45
50
55
60
65
[m]
H
0 200 400 600 800 1000 1200 1400 1600 1800 2000
Q [l/min]
NBF/NKF 50-200
ISO 9906 Annex A
2-pole, 50 Hz
EN12845/EN12259-12
2950/3000 rpm
ø170
ø194
ø207
ø219
15 kW
22 kW
18.5 kW
11 kW
0 10 20 30 40 50 60 70 80 90 100 110 120
Q [m³/h]
0
4
8
12
16
20
24
[kW]
P2
0
10
20
NPSH
[m]
ø170 (NPSH)
ø219 (NPSH)
ø170
ø194
ø207
ø219
GrA
17
19
TM
04
01
91
8
Product description Fire NBF, Fire NKF
Power ratingTo ensure that the motor (electric motor or diesel
engine) is capable of operating the pump at any time, to
ensure water supply, EN 12845 and EN 12259-12
stipulate an excess capacity of motor power.
According to EN 12845 and EN 12259-12, the motor
power is found at 16 m NPSH. The example below
show a required motor size of 22 kW.
Fig. 6 Required and stipulated power
ControllerGrundfos offers a complete, factory-assembled
controller in a steel plate cabinet, suitable for wall
mounting or free-standing.
The controller complies with the standard EN 12845.
The controller for pumps with electric motor can be
mounted on the wall or on the base frame.
The controller for diesel-powered pumps is always
mounted on the base frame.
Functions
The starting signal for the fire pump is given via two
redundant pressure switches. The fire pump can only
be switched off manually.
The control of the fire pump has been arranged in such
a way that motor failures, for example due to heating,
do not cause the fire pump to stop, but only in fault
indications and/or a potential-free signal to a
superordinate fault centre.
Other system components
Jockey pumps
Grundfos CR pumps are used as jockey pumps,
maintaining the water level in the pressure tank. Under
normal conditions, the jockey pump is activated by the
low-level switch in the pressure tank as a result of small
leakages in the pipe systems filled with water. The
jockey pump operates until it is deactivated by the high-
level switch. The jockey pump can also be activated in
case one or more sprinklers are open, in order to
maintain the water level in the pressure tank.
CompressorThe compressor can be operated manually or
automatically by using the selector switch.
During automatic operation, the compressor is
controlled by an external pressure switch, for example
connected to the pressure tank.
The compressor can be manually switched on and off
by means of the respective buttons.
Scope of delivery
A complete Fire NBF and Fire NKF unit assembled and
supplied from factory normally comprises these
elements:
• a pump and motor mounted on a common base
plate/frame
• a standard coupling protected by a coupling guard
(NKF).
Fire NBF and Fire NKF pumps can be ordered with or
without a controller according to EN 12845.
Commissioning
The installer should commission the complete fire set
before handing it over to the plant manager on site.
Many potential issues of the complete fire system must
be tested before commissioning to ensure a
satisfactory system performance and identify any
damage during installation.
Key components should be checked according to the
descriptions in the respective installation and operating
instructions. In addition, EN (12845) stipulates that fire
system tests should be carried out, for example:
• pressure test of sprinkler circuits
• values of all measuring devices (air pressure, water
level, etc.) to the system
• water flow to fire pumps
• test of alarm system and interface to municipal fire
department.
The installer should supply the plant manager with the
following documents:
• Installation certificate, stating that the fire system
has been installed according to EN (12845)
requirements.
• A complete set of installation and operating
instructions and system drawings with specification
of all components for the plant manager and the
owner of the system.
TM
04
64
92
05
10
0 10 20 30 40 50 60 70 80 90 100 110 120 130 Q [m³/h]
0
4
8
12
16
20
24
[kW]
P2
0
4
8
12
16
20
NPSH
[m]
ø170
ø194
ø207
ø219
ø170 (Min. NPSH)
ø219 (Max. NPSH)
P2 required
9
Fire NBF, Fire NKFCurve charts
How to read the curve charts
TM
04 6
07
3 4
80
9
0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300
Q [m³/h]
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
[m]
H
0 500 1000 1500 2000 2500 3000 3500 4000 4500
Q [l/min]
NBF/NKF 80-200
ISO 9906 Annex A
2-pole, 50 Hz
EN12845/EN12259-12
2950/3000 rpm
ø188
ø202
ø213
ø222
37 kW
55 kW
45 kW
30 kW
0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300
Q [m³/h]
0
10
20
30
40
50
[kW]
P2
0
10
20
NPSH
[m]
ø188 (NPSH)
ø222 (NPSH)
ø188
ø202
ø213
ø222
Pump type and frequency of motor
Impeller size
Total pump head:H = Htotal
The power curve indicates pump input power [P2]. P2 is found at 16 m NPSH.
The NPSH curves are according to the minimum and maximum impeller diameter.
QH curve for the individual pump
This line indicates the limit of the individual pump performance.
10
Performance curves
OH1 wet or pre-action
NKF 65-160
The performance envelope indicates the overall approved range for pump model NKF 65-160 and includes an
allowance for the minimum bypass flow rate of 30 l/min.
The design data refers to specific 15 m requirements of OH1 wet or pre-action.
TM
04
652
9 0
510
0 20 40 60 80 100 120 140 160
Q [m³/h]
0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
[m]
H
0 500 1000 1500 2000 2500
Q [l/min]
NKF 65-160
ISO 9906 Annex A
2-pole, 50 Hz
EN12845/EN12259-12
2950/3000 rpm
ø152
0 20 40 60 80 100 120 140 160
Q [m³/h]
0
2
4
6
8
10
12
[kW]
P2
2
4
6
8
NPSH
[m]
ø152
ø152 (NPSH)
Precalculated pumpsOH1 wet or pre-action
15 m
11
NKF 65-200
The performance envelope indicates the overall approved range for pump model NKF 65-200 and includes an
allowance for the minimum bypass flow rate of 30 l/min.
The design data refers to specific 30 m requirements of OH1 wet or pre-action.
TM
04 6
53
0 0
51
0
0 20 40 60 80 100 120 140 160
Q [m³/h]
0
5
10
15
20
25
30
35
40
45
[m]
H
0 500 1000 1500 2000 2500
Q [l/min]
NKF 65-200
ISO 9906 Annex A
2-pole, 50 Hz
EN12845/EN12259-12
2950/3000 rpm
ø182
0 20 40 60 80 100 120 140 160
Q [m³/h]
0
4
8
12
16
20
[kW]
P2
2
4
6
8
NPSH
[m]
ø182
ø182 (NPSH)
Precalculated pumpsOH1 wet or pre-action
30 m
Performance curves
12
NKF 65-200
The performance envelope indicates the overall approved range for pump model NKF 65-200 and includes an
allowance for the minimum bypass flow rate of 30 l/min.
The design data refers to specific 45 m requirements of OH1 wet or pre-action.
TM
04
65
37
051
0
0 20 40 60 80 100 120 140 160
Q [m³/h]
0
5
10
15
20
25
30
35
40
45
50
55
60
65
[m]
H
0 500 1000 1500 2000 2500
Q [l/min]
NKF 65-200
ISO 9906 Annex A
2-pole, 50 Hz
EN12845/EN12259-12
2950/3000 rpm
ø210
0 20 40 60 80 100 120 140 160
Q [m³/h]
0
4
8
12
16
20
24
28
[kW]
P2
2
4
6
8
NPSH
[m]
ø210
ø210 (NPSH)
Precalculated pumpsOH1 wet or pre-action
45 m
Performance curves
13
Performance curves
OH1 dry or alternate, OH2 wet or pre-action
NKF 65-160
The performance envelope indicates the overall approved range for pump model NKF 65-160 and includes an
allowance for the minimum bypass flow rate of 30 l/min.
The design data refers to specific 15 m requirements of OH1 dry and alternate, and OH2 wet or pre-action.
TM
04
65
35 0
51
0
0 20 40 60 80 100 120 140 160
Q [m³/h]
0
4
8
12
16
20
24
28
32
36
[m]
H
0 500 1000 1500 2000 2500
Q [l/min]
NKF 65-160
ISO 9906 Annex A
2-pole, 50 Hz
EN12845/EN12259-12
2950/3000 rpm
ø163
0 20 40 60 80 100 120 140 160
Q [m³/h]
0
2
4
6
8
10
12
14
[kW]
P2
2
4
6
8
NPSH
[m]
ø163
ø163 (NPSH)
Precalculated pumpsOH1 dry or alternate
OH2 wet or pre-action15 m
14
NKF 65-200
The performance envelope indicates the overall approved range for pump model NKF 65-200 and includes an
allowance for the minimum bypass flow rate of 30 l/min.
The design data refers to specific 30 m requirements of OH1 dry and alternate, and OH2 wet or pre-action.
TM
04 6
53
8 1
61
0
0 20 40 60 80 100 120 140 160
Q [m³/h]
0
5
10
15
20
25
30
35
40
45
50
55
[m]
H
0 500 1000 1500 2000 2500
Q [l/min]
NKF 65-200
ISO 9906 Annex A
2-pole, 50 Hz
EN12845/EN12259-12
2950/3000 rpm
ø188
0 20 40 60 80 100 120 140 160
Q [m³/h]
0
4
8
12
16
20
[kW]
P2
2
4
6
8
NPSH
[m]
ø188
ø188 (NPSH)
Precalculated pumpsOH1 dry or alternate
OH2 wet or pre-action30 m
Performance curves
15
NKF 65-200
The performance envelope indicates the overall approved range for pump model NKF 65-200 and includes an
allowance for the minimum bypass flow rate of 30 l/min.
The design data refers to specific 45 m requirements of OH1 dry and alternate, and OH2 wet or pre-action.
TM
04
65
39
05
10
0 20 40 60 80 100 120 140 160
Q [m³/h]
0
5
10
15
20
25
30
35
40
45
50
55
60
65
[m]
H
0 500 1000 1500 2000 2500
Q [l/min]
NKF 65-200
ISO 9906 Annex A
2-pole, 50 Hz
EN12845/EN12259-12
2950/3000 rpm
ø215
0 20 40 60 80 100 120 140 160
Q [m³/h]
0
4
8
12
16
20
24
28
[kW]
P2
2
4
6
8
NPSH
[m]
ø215
ø215 (NPSH)
Precalculated pumpsOH1 dry or alternate
OH2 wet or pre-action45 m
Performance curves
16
Performance curves
OH2 dry or alternate, OH3 wet or pre-action
NKF 65-160
The performance envelope indicates the overall approved range for pump model NKF 65-160 and includes an
allowance for the minimum bypass flow rate of 30 l/min.
The design data refers to specific 15 m requirements of OH2 dry and alternate, and OH3 wet or pre-action.
TM
04
653
6 0
51
0
0 20 40 60 80 100 120 140 160
Q [m³/h]
0
5
10
15
20
25
30
35
40
45
[m]
H
0 500 1000 1500 2000 2500
Q [l/min]
NKF 65-160
ISO 9906 Annex A
2-pole, 50 Hz
EN12845/EN12259-12
2950/3000 rpm
ø171
0 20 40 60 80 100 120 140 160
Q [m³/h]
0
2
4
6
8
10
12
14
16
[kW]
P2
2
4
6
8
NPSH
[m]
ø171
ø171 (NPSH)
Precalculated pumpsOH2 dry or alternate
OH3 wet or pre-action15 m
17
NKF 80-200
The performance envelope indicates the overall approved range for pump model NKF 80-200 and includes an
allowance for the minimum bypass flow rate of 30 l/min.
The design data refers to specific 30 m requirements of OH2 dry and alternate, and OH3 wet or pre-action.
TM
04 6
53
1 0
51
0
0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300
Q [m³/h]
0
5
10
15
20
25
30
35
40
45
50
55
60
[m]
H
0 500 1000 1500 2000 2500 3000 3500 4000 4500
Q [l/min]
NKF 80-200
ISO 9906 Annex A
2-pole, 50 Hz
EN12845/EN12259-12
2950/3000 rpm
ø205
0 20 40 60 80 100 120 140 160 180 200 220 240
Q [m³/h]
0
5
10
15
20
25
30
35
[kW]
P2
3
4
5
6
7
NPSH
[m]
ø205
ø205 (NPSH)
Precalculated pumpsOH2 dry or alternate
OH3 wet or pre-action30 m
Performance curves
18
NKF 80-250
The performance envelope indicates the overall approved range for pump model NKF 80-250 and includes an
allowance for the minimum bypass flow rate of 30 l/min.
The design data refers to specific 45 m requirements of OH2 dry and alternate, and OH3 wet or pre-action.
TM
04 6
53
2 0
51
0
0 20 40 60 80 100 120 140 160 180 200 220 240 260
Q [m³/h]
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
[m]
H
0 500 1000 1500 2000 2500 3000 3500 4000
Q [l/min]
NKF 80-250
ISO 9906 Annex A
2-pole, 50 Hz
EN12845/EN12259-12
2950/3000 rpm
ø227
0 20 40 60 80 100 120 140 160 180 200 220 240 260
Q [m³/h]
0
5
10
15
20
25
30
35
40
45
[kW]
P2
3
4
5
6
7
NPSH
[m]
ø227
ø227 (NPSH)
Precalculated pumpsOH2 dry or alternate
OH3 wet or pre-action45 m
Performance curves
19
Performance curves
Calculated pumps
NBF, NKF 32-200
Circulation flow = 2 % of rated flow rate.
The performance curves of electrically and diesel-powered pumps are approximately similar and based on the values
in table below.
TM
04 6
48
1 0
41
0
0 5 10 15 20 25 30 35 40
Q [m³/h]
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
[m]
H
0 100 200 300 400 500 600 700
Q [l/min]
NBF/NKF 32-200
ISO 9906 Annex A
2-pole, 50 Hz
EN12845/EN12259-12
2950/3000 rpm
ø190
ø176
ø206
ø219
11 kW
4 kW
5.5 kW
7.5 kW
0 5 10 15 20 25 30 35 40 45
Q [m³/h]
0
2
4
6
8
10
[kW]
P2
0
2
4
NPSH
[m]
ø219 (NPSH)
ø176
ø206
ø219
ø190
NBF, NKF 32-200Impeller sizes
P2 [kW]
Electric motor Diesel engine
> 206 219 11 (2930 rpm)
Contact Grundfos> 190 206 7.5 (2900 rpm)
> 176 190 5.5 (2900 rpm)
= 176 4 (2890 rpm)
Calculated pumpsNBF, NKF 32-200
20
NBF, NKF 40-250
Circulation flow = 2 % of rated flow rate.
The performance curves of electrically and diesel-powered pumps are approximately similar and based on the values
in table below.
TM
04
64
82 0
41
0
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85
Q [m³/h]
0
10
20
30
40
50
60
70
80
90
100
110
[m]
H
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300
Q [l/min]
NBF/NKF 40-250
ISO 9906 Annex A
2-pole, 50 Hz
EN12845/EN12259-12
2950/3000 rpm
/210
/230
/238
/250
/260
30 kW
15 kW
18.5 kW
22 kW
11 kW
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85
Q [m³/h]
0
4
8
12
16
20
24
[kW]
P2
0
4
8
12
16
NPSH
[m]
/210
/230
/238
/250
/260
NPSH
NBF, NKF 40-250Impeller sizes
P2 [kW]
Electric motor Diesel engine
> 255 260 30 (2960 rpm) Contact Grundfos
> 245 255 22 (2950 rpm) 26
> 230 245 18.5 (2940 rpm) 19
> 211 230 15 (2940 rpm)Contact Grundfos
= 211 11 (2930 rpm)
Calculated pumpsNBF, NKF 40-250
Performance curves
21
NBF, NKF 50-200
Circulation flow = 2 % of rated flow rate.
The performance curves of electrically and diesel-powered pumps are approximately similar and based on the values
in table below.
TM
04
607
5 4
80
9
0 10 20 30 40 50 60 70 80 90 100 110 120
Q [m³/h]
0
5
10
15
20
25
30
35
40
45
50
55
60
65
[m]
H
0 200 400 600 800 1000 1200 1400 1600 1800 2000
Q [l/min]
NBF/NKF 50-200
ISO 9906 Annex A
2-pole, 50 Hz
EN12845/EN12259-12
2950/3000 rpm
ø170
ø194
ø207
ø219
15 kW
22 kW
18.5 kW
11 kW
0 10 20 30 40 50 60 70 80 90 100 110 120
Q [m³/h]
0
4
8
12
16
20
24
[kW]
P2
0
10
20
NPSH
[m]
ø170 (NPSH)
ø219 (NPSH)
ø170
ø194
ø207
ø219
NBF, NKF 50-200Impeller sizes
P2 [kW]
Electric motor Diesel engine
> 207 219 22 (2950 rpm) 26
> 194 207 18.5 (2940 rpm) 19
> 170 194 15 (2940 rpm)Contact Grundfos
= 170 11 (2930 rpm)
Calculated pumpsNBF, NKF 50-200
Performance curves
22
NBF, NKF 65-160
Circulation flow = 2 % of rated flow rate.
The performance curves of electrically and diesel-powered pumps are approximately similar and based on the values
in table below.
TM
04
716
7 1
71
0
0 20 40 60 80 100 120 140 160
Q [m³/h]
0
5
10
15
20
25
30
35
40
45
[m]
H
0 500 1000 1500 2000 2500
Q [l/min]
NKF 65-160
ISO 9906 Annex A
2-pole, 50 Hz
EN12845/EN12259-12
2950/3000 rpm
ø152
ø163
ø171
0 20 40 60 80 100 120 140 160
Q [m³/h]
0
2
4
6
8
10
12
14
16
[kW]
P2
2
4
6
8
NPSH
[m]
ø171
ø163
ø152
ø152 (NPSH)
ø171 (NPSH)
NBF, NKF 65-160Impeller sizes
P2 [kW]
Electric motor Diesel engine
> 163 171 15 (2940 rpm)
Contact Grundfos> 152 163 11 (2930 rpm)
= 152 7.5 (2900 rpm)
Calculated pumpsNBF, NKF 65-160
Performance curvesPerformance curves
23
NBF, NKF 65-200
Circulation flow = 2 % of rated flow rate.
The performance curves of electrically and diesel-powered pumps are approximately similar and based on the values
in table below.
TM
04
60
72
48
09
0 20 40 60 80 100 120 140 160
Q [m³/h]
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
[m]
H
0 500 1000 1500 2000 2500
Q [l/min]
NBF/NKF 65-200
ISO 9906 Annex A
2-pole, 50 Hz
EN12845/EN12259-12
2950/3000 rpm
ø170
ø186
ø195
ø214
ø219
37 kW
18.5 kW
22 kW
30 kW
15 kW
0 20 40 60 80 100 120 140 160
Q [m³/h]
0
5
10
15
20
25
30
35
[kW]
P2
0
10
20
NPSH
[m]
ø170 (NPSH) ø219 (NPSH)
ø170
ø186
ø195
ø214
ø219
NBF, NKF 65-200Impeller sizes
P2 [kW]
Electric motor Diesel engine
> 215 219 37 (2960 rpm)Contact Grundfos
> 195 215 30 (2960 rpm)
> 186 195 22 (2950 rpm) 26
> 170 186 18.5 (2940 rpm) 19
= 170 15 (2940 rpm) Contact Grundfos
Performance curves Calculated pumpsNBF, NKF 65-200
24
NBF, NKF 80-200
Circulation flow = 2 % of rated flow rate.
The performance curves of electrically and diesel-powered pumps are approximately similar and based on the values
in table below.
TM
04
60
73
48
09
0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300
Q [m³/h]
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
[m]
H
0 500 1000 1500 2000 2500 3000 3500 4000 4500
Q [l/min]
NBF/NKF 80-200
ISO 9906 Annex A
2-pole, 50 Hz
EN12845/EN12259-12
2950/3000 rpm
ø188
ø202
ø213
ø222
37 kW
55 kW
45 kW
30 kW
0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300
Q [m³/h]
0
10
20
30
40
50
[kW]
P2
0
10
20
NPSH
[m]
ø188 (NPSH)
ø222 (NPSH)
ø188
ø202
ø213
ø222
NBF, NKF 80-200Impeller sizes
P2 [kW]
Electric motor Diesel engine
> 213 222 55 (2960 rpm) Contact Grundfos
> 202 213 45 (2980 rpm) 48
> 188 202 37 (2960 rpm)Contact Grundfos
= 188 30 (2960 rpm)
Calculated pumpsNBF, NKF 80-200
Performance curves
25
NBF, NKF 80-250
Circulation flow = 2 % of rated flow rate.
The performance curves of electrically and diesel-powered pumps are approximately similar and based on the values
in table below.
TM
04
607
4 4
80
9
0 40 80 120 160 200 240 280 320
Q [m³/h]
0
10
20
30
40
50
60
70
80
90
100
110
120
[m]
H
0 1000 2000 3000 4000 5000
Q [l/min]
NBF/NKF 80-250
ISO 9906 Annex A
2-pole, 50 Hz
EN12845/EN12259-12
2950/3000 rpm
ø216
ø233
ø255
ø270
55 kW
90 kW
75 kW
45 kW
0 40 80 120 160 200 240 280 320
Q [m³/h]
0
10
20
30
40
50
60
70
80
90
[kW]
P2
0
5
10
15
20
NPSH
[m]
ø216 (NPSH)
ø270 (NPSH)
ø216
ø233
ø255
ø270
NBF, NKF 80-250Impeller sizes
P2 [kW]
Electric motor Diesel engine
> 255 270 90 (2980 rpm) 96
> 233 255 75 (2970 rpm)Contact Grundfos
> 216 233 55 (2960 rpm)
= 216 45 (2980 rpm) 48
Calculated pumpsNBF, NKF 80-250
Performance curves
26
NBF, NKF 100-200
Circulation flow = 2 % of rated flow rate.
The performance curves of electrically and diesel-powered pumps are approximately similar and based on the values
in table below.
TM
04
60
69
48
09
0 50 100 150 200 250 300 350 400
Q [m³/h]
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
[m]
H
0 1000 2000 3000 4000 5000 6000 7000
Q [l/min]
NBF/NKF 100-200
ISO 9906 Annex A
2-pole, 50 Hz
EN12845/EN12259-12
2950/3000 rpm
ø209
ø215
ø219
75 kW
45 kW
55 kW
0 50 100 150 200 250 300 350 400
Q [m³/h]
0
10
20
30
40
50
60
70
[kW]
P2
0
4
8
12
16
NPSH
[m]
ø209
ø215
ø219
ø209 (NPSH) ø219 (NPSH)
NBF, NKF 100-200Impeller sizes
P2 [kW]
Electric motor Diesel engine
> 215 219 75 (2970 rpm)Contact Grundfos
> 209 215 55 (2960 rpm)
= 209 45 (2980 rpm) 48
Calculated pumpsNBF, NKF 100-200
Performance curves
27
NBF, NKF 125-250
Circulation flow = 2 % of rated flow rate.
The full lines show the performance curves of electrically powered pumps.
The dotted lines show the performance curves of diesel-powered pumps.
TM
04
60
70
48
09
0 50 100 150 200 250 300 350 400 450 500 550 600
Q [m³/h]
0
10
20
30
40
50
60
70
80
90
100
110
[m]
H
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000
Q [l/min]
NKF 125-250
ISO 9906 Annex A
2-pole, 50 Hz
EN12845/EN12259-12
ø242
ø250
ø262
ø265
ø237
ø245
ø255
ø269
200 kW
110 kW
132 kW
160 kW
0 50 100 150 200 250 300 350 400 450 500 550 600
Q [m³/h]
0
20
40
60
80
100
120
140
160
180
[kW]
P2
0
4
8
12
16
NPSH
[m]
ø237
ø245
ø255
ø269
ø237 (NPSH)
ø269 (NPSH)
NBF, NKF 125-250Impeller sizes
P2 [kW] NBF, NKF 125-250Impeller sizes
P2 [kW]
Electric motor Diesel engine
> 255 269 200 (2990 rpm) > 262 265 184
> 245 255 160 (2990 rpm) > 250 262 178
> 237 245 132 (2990 rpm) > 242 250 147
237 110 (2990 rpm) 242 119
Calculated pumpsNBF, NKF 125-250
Performance curves
www.grundfos.com
97641687 0410GB
Being responsible is our foundation