FIRE MANAGEMENT
PRODUCTS
TRACK 1000
TECHNICAL PRODUCT GUIDE
Effective September 1, 2014
FAS TRACK 1000™
ARCHITECT SPECIFIED CONTRACTOR PREFERRED
RE-THINK FIRE CAULKING:
FAS Track 1000 requires NO fire sealant or fire spray when used on solid
concrete construction or when used with spray applied fireproofing at
fluted pan decks for 1 and 2 hour fire rated walls.
FAS Track costs up to 25% LESS than other brands claiming the same
type of fire/acoustical/sound abatement.
With FAS Track 1000 you are guaranteed that once installed the
intumescent tape will not wear off, tear off, or fall off, making it the most
reliable intumescent track on the market.
On fluted deck applications mineral wool can be replaced with spray
applied fireproofing, this assembly will not require any additional fire
spray or fire caulking
CODE COMPLIANCEFAS Track 1000 meets current building codes and its unique profile design
provides industry solutions for meeting deflection requirements where
other materials or systems are restricted by design, compressibility,
elasticity, or bond strength characteristics.
FAS Track 1000 has no restrictions providing 100% unencumbered
movement. FAS Track 1000 has been tested for compliance with Section
713.3 of the 2009 and 2012 IBC and 2010 CBC and is listed with UL
Underwriters Laboratories in accordance with:
UL 2079: Tests for Fire Resistance of Building Joint Systems.
ASTM E 1966: Standard Test Method of Fire Tests of Firestop Systems.
ULC S115-M95: Standard Method of Fire Tests of Firestop Systems.
ICC-ESR 2012 *Pending
ASTM E-119 Standard Test Methods for Fire Tests of Building Construction and Materials
Sound tested in accordance to ASTM E90-09
SEISMIC REQUIREMENTSFAS Track 1000 is approved for Class III cycling requirements, 500 cycles
at 30 cycles per minute,meeting seismic building codes requirements.
The class III movement provides design advantages over mastic reliant
systems which are currently limited to class II (wind sway) capabilities
of 500 cycles at 10 cycles per minute.
AIR LEAKAGE RATINGAir leakage tests conducted for compliance with Section 713.6 of the
2009 and 2012 IBC and 2010 CBC are witnessed by UL on conditions
using FAS Track as the joint treatment established L-Ratings of less
than 1 CFM per lineal foot. Any rating below 1 CFM is also considered
the best possible L-Rating. This is achieved with the FAS Track 1000
profile which provides a consistent seal against the drywall.
TECHNICAL ASSISTANCEFor technical questions and assistance please call 1.800.775.2362 or
1.800.416.2278. Email dpilz@cemcosteel.com or visit our website at
www.cemcosteel.com
SOUND BENEFITS: Whether the protection you need is Fire, Air (Smoke), or Sound FAS Track
1000 is all the protection you need in one easy application.
Sound tests were performed at Western Electro-Acoustic Laboratory in
Southern California to prove that the FAS Track 1000 profile will maintain
maximum STC ratings without secondary acoustic sealant applications.
In fact several sound tests were conducted with a ½” to ¾” open joint at
the head-of-wall and with a sealed head-of-wall joint on the same wall
assembly. Both open and closed joints rendered the exact same STC
rating proving that no sound is lost through the open head of wall joint.
Sound tests were also conducted on a 2-1/2” wide stud double wall
a.k.a. plumbing-wall or chase-wall with a single layer on both sides
rendered an STC rating of 60. Adding one layer to only one side of the
double wall increased the STC rating to 63.
The UBC requires Sound Transmission Class (STC) ratings and Impact
Insulation Class (IIC) ratings for dwelling units, which include hotels,
motels, apartments, condominiums, dormitories, and monasteries to
be at a minimum 50 STC or IIC rating. Sound ratings can be greatly
reduced through sound flanking paths. To reduce flanking paths drywall
should be sealed tight to the framing member around the perimeter.
BW-S-0024
FAS Track 1000
WW-D-0104
Bottom of Wall Static Joint Assembly Rating 2 Hour
HW-D-0624 (Option 1)
Vertical Wall Tie Into Concrete Slab Assembly Rating 2 Hour
FAS TRACK 1000 DETAILS ¾” JOINT PROTECTION FOR 1* AND 2 HOUR FIRE RATED WALLS
CEMCO
FAS TRACK 1000BT
5/8" TYPE "X"
DRYWALL
12" JOINT
PROTECTION
#8 x 1/2" FRAMING
SCREW
CONCRETE SLAB
METAL STUD
BY DESIGN
TYPICAL STEEL
FASTENERS BY DESIGN
DRYWALL SCREW
1" LOWER THAN
TRACK LEG
DRYWALL SCREW
5/8" TYPE "X" DRYWALL
CONCRETE
METAL STUD
BY DESIGN
TYPICAL STEEL
FASTENERS BY DESIGN
CEMCO
FAS TRACK DL 1000
“A”Track Member Width
(inch)Flange Size
(inch)Length
(ft)Steel Thickness
mils (gauge)
2 ½, 3 5/8, 4, 6 and 8 2” 10 33 (20)
43 (18)
54 (16)
US Patent 8,640,415 B2
“A”Track Member Width
(inch)
Flange Size (inch)
Length(ft)
Steel Thickness mils
(gauge)
2 ½, 3 5/8, 4,6 and 8 1 ¼” 10
30 (20)
43 (18)
54 (16)
US Patent 8,640,415 B2
FAS Track 1000 DL / FAS Track 1000 (BT)
HW-D-0554 CHASE WALL
#8 x 1/2" FRAMING
SCREWCEMCO FAS TRACK 1000
(TAPE ON FINISH SIDE ONLY)
5/8" TYPE "X"
DRYWALL
METAL STUD
SPACING BY DESIGN
CONCRETE SLAB
3/4" JOINT
PROTECTION
DRYWALL SCREW
1" LOWER THAN
TRACK LEG
FAS TRACK 1000
5/8" TYPE "X" DRYWALL
3/4" JOINT
PROTECTION
#8 x 1/2" FRAMING
SCREW
CONCRETE SLAB
METAL STUD
BY DESIGN
TYPICAL STEEL
FASTENERS BY DESIGN
DRYWALL SCREW
1" LOWER THAN
TRACK LEG
“A”Track Member Width
(inch)
Flange Size (inch)
Length(ft)
Steel Thickness mils
(gauge)
2 ½, 3 5/8, 4, 6 and 8 2 ¾” 10 20, 18, 16
US Patent # 8,640,415,B2
*Single Layer of 5/8” type “X” Gypsum Panel For 1 Hour Fire Rating
Standard Chase Wall, Concrete Slab Assembly Rating 2 Hour
Concrete Slab Assembly Rating 2 Hour
FAS J-TRACK (SHAFT WALL) ¾” JOINT PROTECTION FOR 1* AND 2 HOUR FIRE RATED WALLSAdditional joint systems can be found @ www.cemcosteel.com
HW-D-0525 HW-D-0525 (2)
HW-D-0622 HW-D-0625
Shaft Wall, Directly Under Beam Assembly Rating 2 Hours
Additional UL Joint System for FAS J-Track can be found at www.cemcosteel.com
“A”Track Member Width
(inch)
Flange Size
(inch)
Length
(ft)
Steel Thickness mils (gauge)
2 ½, 4, and 6 1 ½” short leg 2 ½” long leg
10 33 20
US Patent #8,640,415 B2
HW-D-0653FAS J-Track
Shaft Wall, Concrete Slab Assembly Rating 2 Hours
Shaft Wall, Perpendicular To Fluted Deck Assembly Rating 2 Hours
Shaft Wall, Perpendicular To Fluted Deck Assembly Rating 2 Hours
CEMCO FAS
J- TRACK
1" SHAFT LINER
MINERAL WOOL
CONCRETE SLAB
5/8" TYPE "X" DRYWALL
34" JOINT PROTECTION
CONCRETE SLAB
OR FLUTED METAL
DECK WITH
CONCRETE FILL
STEEL BEAM
STRUCTURAL
FIREPROOFING
(THICKNESS BY OTHERS)EXPANDED METAL
LATH
1/2" x 20 GA. Z-BAR OR
16 GA. CRC @ 16" O.C.
MINERAL WOOL OR
SPRAY FIREPROOFING
CH STUD
5/8" TYPE "X" DRYWALL
1" SHAFT LINER
MINERAL WOOL
38" NOMINAL GAP
(3 4" JOINT PROTECTION)
CEMCO FAS J-TRACK
8"
Standard Shaft Wall, Parallel & Cantilever Under Beam Assembly Rating 2 Hours
WITH CONCRETE FILL
MINERAL WOOL
TYPICAL STEEL
FASTENERS BY DESIGN
CH STUD
5/8" TYPE "X" DRYWALL
1" SHAFT LINER
CEMCO FAS J-TRACK
38" NOMINAL GAP
(3 4" JOINT PROTECTION)
FLUTED METAL DECK
WITH CONCRETE FILL
MINERAL WOOL
TYPICAL STEEL
FASTENERS BY DESIGN
CH STUD
5/8" TYPE "X" DRYWALL
1" SHAFT LINER
CEMCO FAS J-TRACK
38" NOMINAL GAP
(3 4" JOINT PROTECTION)
SPRAY FIREPROOFING
STEEL BEAM
MINERAL WOOL OR
SPRAY FIREPROOFING
CONCRETE SLAB OR FLUTED
METAL DECK WITH CONCRETE FILL
STRUCTURAL STEEL
FIREPROOFING
(THICKNESS BY OTHERS)
1/2" x 20 GA. Z-BAR OR
16 GA. CRC @ 16" O.C.
CH STUD
5/8" TYPE "X" DRYWALL
1" SHAFT LINER
MINERAL WOOL
38" NOMINAL GAP
(34" JOINT PROTECTION)
CEMCO FAS J-TRACK
*Single Layer of 5/8” type “X” Gypsum Panel For 1 Hour Fire Rating
FAS Track 1000 Fluted Deck Details For 1* And 2 Hour Fire Rated Walls Additional joint systems can be found @ www.cemcosteel.com
HW-D-0620 (2)
HW-D-0620
HW-D-0550
HW-D-0652
Standard Wall, Parallel And Directly Under Fluted Deck Assembly Rating 2 Hour
HW-D-0514
Standard Wall, Perpendicular To Fluted Deck Assembly Rating 2 Hour
Standard Wall, Parallel & Offset Under Fluted Deck Assembly Rating 2 Hour
Standard Wall, Gypsum Wallboard Ceiling Assembly Rating 2 Hour
WITH CONCRETE
SPRAY FIREPROOFING
CEMCO
FAS TRACK 1000
DRYWALL SCREW
1" LOWER THAN
TRACK LEG
5/8" TYPE "X"
DRYWALL
38" NOMINAL GAP
(34" JOINT PROTECTION)
#8 x 1/2" FRAMING SCREW
METAL STUD
BY DESIGN
SPACING BY DESIGN
5/8" TYPE "X"
DRYWALL
#8 x 1/2" FRAMING
SCREW
3/4" JOINT PROTECTION
CEMCO FAS TRACK 1000
CONCRETE DECK
DRYWALL SCREW
1" LOWER THAN
TRACK LEG
METAL STUD
SPACING BY DESIGN
5/8" TYPE "X"
DRYWALL
#8 x 1/2" FRAMING
SCREW
3/4" JOINT PROTECTION
CEMCO FAST RACK 1000
MINERAL WOOL
CONCRETE DECK
DRYWALL SCREW
1" LOWER THAN
TRACK LEG
FASTENERS BY DESIGN CONCRETE SLAB
OPEN WEB TRUSS OR
JOIST
FURRING CHANNEL @
24" O.C.
58" TYPE "C" GYPSUM
WALLBOARD
CEMCO
FAS TRACK 1000
DRYWALL SCREW
1" LOWER THAN
TRACK LEG
5/8" TYPE "X"
DRYWALL
38" NOMINAL GAP
(34" JOINT PROTECTION)
#8 x 1/2" FRAMING SCREW
METAL STUD
BY DESIGN
HW-D-0518
FLUTED METAL DECK WITH
CONCRETE FILL
1/2" x 20 GA. Z-BAR OR
16 GA. CRC BY DESIGN
5/8" TYPE
"X" DRYWALL
FIREPROOFING OR
MINERAL WOOL
3.4 EXPANDED
RIB LATH
METAL STUD
BY DESIGN
STEEL BEAM
STRUCTURAL STEEL
FIREPROOFING
(THICKNESS BY OTHERS)
3/4" JOINT
PROTECTION
#8 x 1/2" FRAMING
SCREW
CEMCO FAS
TRACK 1000
TYPICAL STEEL
FASTENERS BY DESIGN
DRYWALL SCREW
1" LOWER THAN
TRACK LEG
Standard Wall, Cantilevered Under Beam Assembly Rating 2 Hour
Standard Wall, Perpendicular To Fluted Deck Assembly rating 2 Hours
FLUTED METAL DECK
WITH CONCRETE FILLMINERAL WOOL
TYPICAL STEEL
FASTENERS BY DESIGN
CEMCO
FAS TRACK 1000
DRYWALL SCREW
1" LOWER THAN
TRACK LEG
5/8" TYPE "X"
DRYWALL
3/4" JOINT
PROTECTION
#8 x 1/2" FRAMING
SCREW
METAL STUD
BY DESIGN
*Single Layer of 5/8” type “X” Gypsum Panel For 1 Hour Fire Rating
FAS Track 1000 Fluted Deck Details For 1* and 2 Hour Fire Ratings Additional joint systems can be found @ www.cemcosteel.com
HW-D-0551 HW-D-0553
HW-D-0573 HW-D-0623 I-Beam Penetration at Shaft Wall
Standard Wall, @ Fluted Deck Beam Penetration Assembly Rating 2 Hours
Shaft Wall, @ Fluted Deck Beam Penetration Assembly Rating 2 Hours
HW-D-0524
Standard Chase Wall, Perpendicular To Fluted Deck Assembly Rating 2 Hours
Standard Wall, Centered Directly Under Beam Assembly Rating 2 Hours
FIRE PROOFING OR
MINERAL WOOL
STEEL BEAM
STRUCTURAL STEEL
FIREPROOFING
(THICKNESS BY OTHERS)1/2" x 20 GA. Z-BAR OR
16 GA. CRC BY DESIGN.
3/4" JOINT PROTECTION
5/8" TYPE
"X" DRYWALL
#8 x 1/2" FRAMING
SCREW
FLUTED METAL DECK WITH
CONCRETE FILL
CEMCO FAS
TRACK 1000
METAL STUD
BY DESIGN
TYPICAL STEEL FASTENERS
BY DESIGN
DRYWALL SCREW
1" LOWER THAN
TRACK LEG
#8 x 1/2" FRAMING
SCREWCEMCO FAS TRACK 1000
(TAPE ON FINISH SIDE ONLY)
5/8" TYPE "X"
DRYWALL
METAL STUD
SPACING BY DESIGN
MINERAL WOOL
FLUTED METAL DECK
WITH CONCRETE FILL
3/4" JOINT
PROTECTION
DRYWALL SCREW
1" LOWER THAN
TRACK LEG
MINERAL WOOL STUFFED
BETWEEN FRAMING AND
FIREPROOFING 50%
COMPRESSED
(2) LAYERS
DRYWALL
Z-CLIP
CEMCO
FAS TRACK 1000
METAL STUD
DRYWALL CUT
AROUND I-BEAM WITH
2" GAP
38" NOMINAL GAP
(34" JOINT PROTECTION)
I-BEAM
CEMCO
FAS TRACK 1000
FAS STRAP
MINERAL WOOL STUFFED
BETWEEN FRAMING AND
FIREPROOFING 50%
COMPRESSED
(2) LAYERS
DRYWALL
Z-CLIP
CEMCO
FAS J-TRACK
CH STUD
DRYWALL CUT
AROUND I-BEAM WITH
2" GAP
38" NOMINAL GAP
(34" JOINT PROTECTION)
I-BEAM
CEMCO
FAS J-TRACK
Standard Wall, Parallel & Directly Under Deck Flute Assembly Rating 2 Hours
FLUTED METAL DECK
FILLED WITH CONCRETECEMCO FAS STRAP
MIN. #6 FRAMING
SCREW BY DESIGN
TYPICAL STEEL
FASTENERS BY DESIGN
CEMCO
FAS TRACK 1000
DRYWALL SCREW
1" LOWER THAN
TRACK LEG
5/8" TYPE "X"
DRYWALL
3/4" JOINT
PROTECTION
#8 x 1/2" FRAMING
SCREW
METAL STUD
BY DESIGN
1/2" to 1 1/4" intumescent strip
10 3/6"
*Single Layer of 5/8” type “X” Gypsum Panel For 1 Hour Fire Rating
The Innovators of Quality Framing and Lath Systems
CEMCO FAS 093X Specification Sheet
CEMCO’s FAS-093X Fire Rated control joint is a composite control joint with intumescent tape factory applied to the back side of the
control joint. The FAS-093X has been tested according to UL-2079 “Test For Fire Resistance of Building Joint Systems” and is used to
relieve stresses of expansion and contraction of drywall interior partitions or ceilings running in a horizontal or vertical direction. The
opening is protected by an orange plastic tape to indicate the fire rating. This tape is removed after joint compound has been applied and
the finish is completed. The section is fabricated from hot-dipped galvanized steel complying with ASTM A653, and ASTM A1003 Grade
33 Type H for 33 Ksi yield strength steel 13 mil thickness.
CALIFORNIA EXPANDED METAL LATH PRODUCTS CO.
Corporate Headquarters:
263 North Covina Lane
City of Industry, CA 91744
Phone: 800.775.2362
Fax: 626.330.7598
1001-A Pittsburg Antioch Hwy
Pittsburg, CA 94565
Phone: 925.473.9340
Fax: 925.473.9341
490 Osage Street
Denver, CO 80204
Phone: 303.572.3626
Fax: 303.572.3627
8600 Will Rogers Blvd
Ft. Worth, TX 76140
Phone: 817.568.1525
Fax: 817.568.2759
N0 Fire Sealant
No Drywall Rips
NO Mineral Wool
1 and 2 hour Fire Ratings
Single Step Application
US Patent 8,671,632
800.775.2362 WWW.CEMCOSTEEL.COM
Corporate Headquarters &
Main Manufacturing Facility
Northern California
Manufacturing Facility
263 North Covina Lane
City of Industry, CA 91744
Phone: 800.775.2362Fax: 626.330.7598
1001-A Pittsburg Antioch Hwy
Pittsburg, CA 94565
Phone: 925.473.9340Fax: 925.473.9341
Denver Colorado
Manufacturing Facility
490 Osage Street
Denver, CO 80204
Phone: 303.572.3626
Fax: 303.572.3627
8600 Will Rogers Blvd
Ft. Worth, TX 76140
Phone: 817.568.1525
Fax: 817.568.2759
Ft. Worth Texas
Manufacturing Facility
Effective September 1, 2014
EQ 4.1 LOW-EMITTING MATERIALS – ADHESIVES AND SEALANTS:FAS Track’s intumescent fire-resistive seal is a solid, factory-applied layer, so it is not required to comply with the Adhesives and Sealants VOC limits. Moreover, because BlazeSeal provides all the fire protection required for many partitions, no spray-applied smoke seals or elastomeric fire-resistive sealants are required, so their VOC contributions are eliminated.
IEQ 4.6 LOW-EMITTING MATERIALS – CEILING AND WALL SYSTEMS (LEED FOR SCHOOLS): This credit does not apply to FAS Track. Only the gypsum board and the wall coverings are required to be tested.
IEQ 9 ENHANCED ACOUSTICAL PERFORMANCE (LEED FOR SCHOOLS): FAS Track improves the Sound Transmission Class (STC) of partitions, and can even eliminate the need for acoustical sealant at the head of partitions. Its resilient BlazeSeal layer helps damp sound transmission of partitions around core learning spaces and can help achieve this credit.
For other LEED credit contributions, see HYPERLINK “http://www.cemcosteel.com” www.cemcosteel.com and click “LEED Certification”.
If you have any questions, concerns, or clarifications, please contact our Technical Services Department at (800) 416-2278 or HYPERLINK “http://www.cemcosteel.com” www.cemcosteel.com.
FAS Track™ represents an environmental advancement for interior partition construction. Its resilient intumescent layer of Blaze Seal makes it a one-piece solution to acoustical and fire resistive head assemblies. FAS Track’s partition head assembly eliminates most bridging, elastomeric sealants, mineral wool, and the need to cut drywall to fit the flutes of decking. FAS Track reduces scraps and waste and often does not require any sealant to be applied to the head of wall joint. Resources are saved, and indoor air quality is improved.
FAS Track contributes to a number of LEED credits in the 2009 New Construction, Core and Shell, Commercial Interiors, and Schools rating systems.
RESOURCE CONSERVATION: Because even very short pieces of FAS Track are used in construction, very little is wasted. Scraps as small as 16 inches are often retained. The metal portion of smaller scraps can be recycled, once the BlazeSeal is peeled off by hand. For projects with high targets for MR 2 Construction Waste Management, this method of recycling FAS Track scraps will contribute to this credit.
MR CREDIT 4 RECYCLED CONTENT: Like all of CEMCO’s framing products, FAS Track contributes 32.7% recycled content to this credit.
IEQ 3.2 INDOOR AIR QUALITY MANAGEMENT PLAN – BEFORE OCCUPANCY: If the Air Testing option is selected by the project team, FAS Track is a valuable player in achieving this credit. FAS Track eliminates the need for spray-applied smoke seal and elastomeric fire sealant. It also can take the place of acoustical sealant in some assemblies. With no solvents and very low VOC content, FAS Track significantly reduces indoor air pollution. The Air Testing option is difficult to achieve, and every bit of indoor pollution that FAS Track eliminates from the project increases the chances of success.
FAS TRACK’S ENVIRONMENTAL BENEFITS AND LEED CONTRIBUTIONS