ep series ups

Post on 26-Oct-2014

122 Views

Category:

Documents

1 Downloads

Preview:

Click to see full reader

TRANSCRIPT

GE Power Quality

EP Series UPS

GE C&I PWQ AsiaSep., 2006 2

1. Market intelligence

2. Power Model

3. Features

4. Cabinet views

5. Technical description

6. Battery management

7. Communication

Content

GE C&I PWQ AsiaSep., 2006 3

Pluggable market

kVA CAGR< 1 4.8%1 - 5 8.4%

5.1 - 20 9.6%21 - 100 9.9%101 - 250 8.5%251 - 1000 6.3%

> 1000 3.7%

2006: $5.1B

<5kVA = 52% of global market

Total <20kVA equals 68% of global market

< 1kVA18%

>200 kVA13%

1-5 kVA34%

5.1-20 kVA16%

21-50 kVA9%

50-200 kVA10%

15%

33%18%

16%

10% 6% 2% <1kVA

1 - 5kVA

5 - 20kVA

20 - 100kVA

100 - 250kVA

250 - 1000kVA

>1000kVA

China

•Dominated by China made

•APC – made in Suzhou

•Local brands – Santak, Delta, Powercom etc

•Clones – illegal copies

Rest of Asia

•International brands – China or Taiwan sourced

•APC – own manufacturing

•MGE, Liebert, Powerware – OEM or ODM with Santak, Delta or Powercom

AsiaGlobal

2006: $1.4B

GE C&I PWQ AsiaSep., 2006 4

EP series family

Tower ModelStandard Model

• Range: 700VA, 1000VA, 2000VA, 3000VA, 6000VA

• With internal battery providing 5~7 mins back time

Long runtime model

• Range: 700VA, 1000VA, 2000VA, 3000VA, 6000VA

• Without internal battery

• With high capacity internal battery chargerRack Model

Standard Model (Only)

• Range: 700VA, 1000VA, 2000VA, 3000VA, 6000VA

• With internal battery providing 5~7 mins back time

• Battery is in additional cabinet for 2000/3000/6000VA

GE C&I PWQ AsiaSep., 2006 5

Feature

General

• Double conversion, on line (VFI)

• LED display – overload, on-line & battery status

• Full digital microprocessor controlled

• Programmable computer shutdown

• Lightning and transient surge protection

• Automatic bypass switch

• Battery Start (cold start)

Performance

• Input Power Factor: 0.97/0.98

• Wide input voltage window (115~300Vac/0.7~3K, 176~276Vac/6KVA)

• Frequency (50/60HZ), Voltage (220/230/240), auto sensing

Battery

• Programmable automatic test

• Protection against deep discharge

• Extended runtime available and auto-recognition

Communication

• RS232, USB

• SNMP

GE C&I PWQ AsiaSep., 2006 6

Cabinet view

700/1000VA

Front Panel

2000/3000VA

6000VA

700/1000VA (2U)

2000/3000VA (2U)

6000VA (3U)

GE C&I PWQ AsiaSep., 2006 7

Cabinet view Rear Panel (Tower)

GE C&I PWQ AsiaSep., 2006 8

Cabinet view Rear Panel (Tower)

GE C&I PWQ AsiaSep., 2006 9

Cabinet view Rear Panel (Rack)

GE C&I PWQ AsiaSep., 2006 10

Block Diagram

700/1000VA

2000/3000VA

6000VA

GE C&I PWQ AsiaSep., 2006 11

Battery

Model EP 700 T/R EP 1000 T/R EP 2000 T/R EP 3000 T/R EP 6000 T/R

Num. & Model

3x12V

7.2Ah

3x12V

7.2Ah

3x12V

7.2Ah

3x12V

7.2Ah

3x12V

7.2Ah

Model 100% Load

50% Load

EP 700 T/R 5 mins 10 mins

EP 1000 T/R

5 mins 10 mins

EP 2000 T/R

5 mins 10 mins

EP 3000 T/R

5 mins 10 mins

EP 6000 T/R

7 mins 14 mins

Standard Model

Tower & Rack

Long Runtime Tower Model

Model EP 700 LRT EP 1000 LRT

EP 2000 LRT

EP 3000 LRT

EP 6000 LRT

Charging Current (max)

7A 8A 9.6A 9.6A 4.3A

GE C&I PWQ AsiaSep., 2006 12

Communication

Connection

• RS232, USB

• LAN (SNMP)

• Internet

GE C&I PWQ AsiaSep., 2006 13

Communication

GE C&I PWQ AsiaSep., 2006 14

Package

• Olympics• Product pictures• Key features• Back panel labeling

Listing all connectivity and electrical connections

• Internal CD packaging for software connectivity.

Box Labeling

GE C&I PWQ AsiaSep., 2006 15

Q&A