emax brochure
Post on 13-Apr-2018
231 Views
Preview:
TRANSCRIPT
7/27/2019 Emax Brochure
http://slidepdf.com/reader/full/emax-brochure 1/20
604060/011 e n
J uly '99
ABB SACE L.V.
SACE Emax.A system that’s opento any solution.
7/27/2019 Emax Brochure
http://slidepdf.com/reader/full/emax-brochure 2/20
2
SACE Emax: the reference standardin air circuit-breakers
SACE Emax low-voltage air circuit-breakers
have been designed and manufactured by
ABB SACE L.V. with the aim of satisfying the
most advanced mark et requirements.
Building on the highly-acclaimed results
obtained by the SACE Isomax S series of
moulded-case circuit-breakers, this new series
extends the characteristics of safety, reliability,
integration and coordination that distinguish
the entire ABB SACE L.V. low-voltage productfamily to high rated current values.
T he SACE Emax series won the favour of users
on all markets as soon as it was launched,
proving itself to be the perfect solution to the
requirements of even the most technologically
sophisticated installations.
T hanks to its new versions and performance
features, combined with a further-increased
range of accessories, SACE Emax makes it
possible to anticipate the design trends of the
future.
7/27/2019 Emax Brochure
http://slidepdf.com/reader/full/emax-brochure 3/20
3
The SACE Emax series benefits from
ABB SACE L.V. ’s experience in the manufacture
of ai r circuit- breakers, which began in the late
Fifties wi th the SACE O tomax series - the first
air circuit-breaker designed and manufactured
entirely in I taly. The series comprised a
swi tchgear range wi th rated currents of 1250 to
5000 amps and a maxi mum breaking capacity
of 100 kA .
The success of this fi rst series was echoed by
that of the G 30 series in the Seventies, which
was the first to offer electronic releases
alongside traditional electromagnetic releases.
T his takes us to 1979, when AB B SACE L.V .
started manufacturing the SACE Novomax
series - the first high-performance current-
limi ting air circuit-breakers on the market.
1989 marked the arrival of the SACE
M egamax, a signifi cant step forwards that
introduced PR1 mi croprocessor-based releases
installed on-board the circuit-breakers. T hanks
to this innovation, air circuit-breakers were
transformed from a simple component to anintegral and sophisticated part of a complex
“system” .
T he strengths of the current SACE Emax series
build on over half a century’s development
and are the logical consequence of a design
and manufacturing philosophy firmly focused
on innovation, safety and reliability.
1955Otomax:
Iu = 1250 … 5000A,
Icu = up to 100kA
1971G30: … from
thermomagnetic to
electronic releases
1979Novomax: increased
performance (6300 A)
and introduction of
current-limiting circuit-
breakers
1989Megamax: new design
of microprocessor-
based releases (PR1)
TODAY
Emax: technological
progress with high-performance.
Iu = 800 … 6300A,
Icu = 40 ... 150kA.
Maximised modular
strengths and
standardisation.
3
7/27/2019 Emax Brochure
http://slidepdf.com/reader/full/emax-brochure 4/20
4
Continually developing qualityand performance
The comp act
dimensions of a
SACE Emax are a result of its perfect
integration of
comp onents and
performance
• Customised solutions with safety in mind;
- possibili ty of using two opening coi ls ( dual
O C) for special environments such as
hospitals
- SACE SO R T est Unit for check ing that all
the components of the opening coil are
work ing correctly at regular intervals;
• Ease of moni toring using accessories for the
electroni c releases:
- PR010/T test, programming and parameter
readout unit
- PR010/K signalling unit that also provides
load control function.
Sliding contacts
Microprocessor-basedprotection release
Pushbutton for manual
opening operation
Lever for loading theclosing springs manually
Mechanical indicatorshowing circuit breakeropen “O” or closed “I”
Compartment for rackingin/out operation
Indicator showingsprings loaded orreleased
Pushbutton formanual closingoperation
T he results achieved by ABB SACE L.V . with
the SACE Emax series speak louder than
words regarding the continual progress made
by the range through important new
developments such as:
• Ci rcuit-breakers for special applications with
voltages of up to 1000 V in alternating
current;
• Range of direct current switch-
disconnectors;
• Range of switchgear in accordance with
ANSI standards also certified by the
Underwriter Laboratories in conformity wi th
UL Standard 1066;
• T wo possible ways of calculating the earth
fault current:
- Residual ( using function G of the release)
- Source Ground Return (wi th external
toroid coil on the transformer star centre’s
earth connection) ;
4
Anti-insertion
lock
Earthing
contact
Safetyshutters
7/27/2019 Emax Brochure
http://slidepdf.com/reader/full/emax-brochure 5/20
5
A complete range to satisfy any installation
The SACE Emax series is offered in a complete
range of rated currents and available as five
different models in fixed, withdrawable, three
and four-pole versions. Characterised by
uninterrupted rated currents of from 800 to
6300 amps and breaking capacities of up to
150 kA, the series is able to satisfy the most
demanding requirements of modern industrial
and naval installations. Each model is available
in a variety of di fferent circuit-breaker options
that have the same dimensions but different
rated currents and breaking capacities. Look ed
at from a manufacturing and use standpoint,
SACE Emax circuit-breakers can be divided into
two main categories of use: selective circuit-
breakers and current-limi ting circuit-breakers.
The former make it possible to implement
different types of selectivi ty thanks to high
short-time withstand current values and the
SAC E PR111 and PR112 overcurrent releases.
The different types of selectivi ty available are:
current, energy, time and zone.
Series
Breaking capacity
B= Base
N= Normal
S= Standard
H= High breaking
capacity
V= Very high breaking capacity
L= Current-limiting
circuit-breaker
Rated uninterrupted current IuModel
T he current-limi ting circuit-breakers mak e it
possible to achieve a considerable reduction
in the peak current compared to the
prospective current and, therefore, to limit the
specifi c let-through energy. T he resultant
benefits include a reduction in electrodynamic
and thermal stresses, consequently mak ing i t
possible to
reduce the
dimensioning
of the
installation.
5
7/27/2019 Emax Brochure
http://slidepdf.com/reader/full/emax-brochure 6/20
6
Electrical characteristics
SACE Emax E1 SACE Emax E2Voltage
Rated service voltage Ue 690 ~ / 250 ~ [V]
Rated insulation voltage Ui 1000 [V]
Rated impulse withstand voltage Uimp 12 [kV]
Frequency f 50-60 [Hz]
Number of poles 3-4
Version Fixed - Withdrawable
Data common to the entire range
B
800
1250
100
40
40
36
36
40
40
36
36
36
-
84
84
75,6
B
296/386324/414
42/50
65/80
Performance level
Currents
Rated uninterrupted Iu [A]
current (at 40°C) [A]
[A]
[A]
[A]
Capacity of neutral pole for four-pole circuit -breakers [ %I u]
Rated ul timate short -c ir cui t Icu 220 /230 /380 /400 /415 V~ [kA]
breaking capacity 440 V~ [kA]
500/660/690 V~ [kA]
250 V– [kA]
Rated service short-circuit I cs 220/230/ 380/ 400/ 415 V ~ [ kA ]
breaking capacity 440 V~ [kA]
500/660/690 V~ [kA]
250 V– [kA]
Rated short-time Icw (1 s) [kA]
withstand current Icw (3 s) [kA]
Rated short-circuit making capacity Icm 220/230/380/400/415 V~ [kA]
(peak value) 440 V~ [kA]
500/660/690 V~ [kA]
Category of use (CEI EN 60947-2)
Isolation behaviour (CEI EN 60947-2)
Dimensions
Fixed: H = 418 mm -D = 302 mm L (3/4 poles) [mm]Withdrawable: H = 461 mm - D = 396,5 mm L(3/4 poles) [mm]
Weight (circuit-breaker complete with releases and CT, excluding accessories)
Fixed 3/4 poles [kg]
Withdrawable 3/4 poles (including fixed part) [kg]
(1) A version with a 4000A neutral pole current capacity is available
(2) The performance at 500 V is 100 kA
B N L
1600 1250 1250
2000 1600 1600
2000
100 100 100
40 65 130
40 65 110
40 55 85
40 55 -
40 65 130
40 65 110
40 55 65
40 55 -
40 55 10
40 40 -
84 143 286
84 143 242
84 121 187
B B A
296/386324/414
46/55 46/55 45/53
72/89 72/89 70/87
E1 B E2 B-N E2 L
Rated uninterrupted current (at 40ºC), Iu [A]
Mechanical life
with regular routine maintenance [No. operations x 1000]
Frequency of operations [Operations per hour]
Electrical life (440 V~) [No. operations x 1000]
Frequency of operations [Operations per hour]
800 1250 1250 1600 2000 1250 1600 1250 16
25 25 25 25 25 20 20 20 2
60 60 60 60 60 60 60 60 6
10 10 15 12 10 4 3 12 1
30 30 30 30 30 20 20 20 2
Circuit-breaker model E1 E2
7/27/2019 Emax Brochure
http://slidepdf.com/reader/full/emax-brochure 7/20
7
SACE Emax E3 SACE Emax E4 SACE Emax E6
N S H L
2500 1250 1250 2000
3200 1600 1600 2500
2000 2000
2500 2500
3200 3200
100 100 100 100
65 75 100 130
65 75 100 110
65 75 85 85
65 75 75 -
65 75 85 130
65 75 85 110
65 75 85 65
65 75 75 -
65 75 75 15
65 65 65 -
143 165 220 286
143 165 220 242
143 165 187 187
B B B A
404/530432/558
68/80 68/80 68/80 67/79
100/125 100/125 100/125 100/120
S H
4000 3200
4000
50 (1) 50
75 100
75 100
75 85(2)
75 100
75 100
75 100
75 85(2)
75 100
75 100
65 65
165 220
165 220
165 187
B B
566/656594/684
95/115 95/115
147/190 147/190
H V
5000 3200
6300 4000
5000
6300
50 50
100 150
100 150
100 100
100 100
100 125
100 125
100 100
100 100
100 100
- -
220 330
220 330
220 220
B B
782/908810/936
140/170 140/170
210/260 210/260
E3 N-S-H E3 L E4 S-H E6 H-V
1600 2000 2500 3200 2000 2500 3200 4000 3200 4000 5000 6300
20 20 20 20 15 15 15 15 12 12 12 12
60 60 60 60 60 60 60 60 60 60 60 60
10 9 8 6 2 1,8 7 5 5 4 3 2
20 20 20 20 20 20 10 10 10 10 10 10
E3 E4 E6
7
7/27/2019 Emax Brochure
http://slidepdf.com/reader/full/emax-brochure 8/20
8
An intelligent and flexible answerto all your protection requirements
SACE PR111 and SACE PR112microprocessor-basedovercurrent releasesAlongside its modern series of ai r circuit-
breakers, A BB SACE L.V. presents a complete
and innovative range of microprocessor-based
electronic overcurrent releases, the SAC E
PR111 and PR112. Anyone installing SACE
Emax circuit-breakers has the option of
choosing the release that is best suited to thei rinstallation needs in any given situation,
together with the designer’s requirements
regarding safety and reliabil ity. T he advances
made by electrical installations implementing
distributed intelligence systems has made the
role played by releases increasingly important,
demanding that they offer:
• high operating precision;
• a wide range of settings;
• complete protection against all types of faults;
• measurement and monitoring of the main
electrical parameters;
• dialogue with supervision and control
systems such as SACE SD -View 810.
T hese functions are provided on SAC E Emax
circuit-breakers using the SACE PR111 and
PR112 microprocessor-based releases, whi ch
provide protection functions against overloads
( L) , short-circuit’s ( instantaneous I and
selective S) and earth faults ( G ) .
Maincharacteristics
Possibility of self-
powered operation
High operating precision
Sensitivity to true root-
mean-square value of the
current
Possibility of setting
neutral to 100% of the
phases with rated
currents up to 4000 A
Advanced
microprocessor
technology
(8-bit for PR111
and 16-bit for PR112)
Integrated dialogue unit
SACE PR111
SACE PR112
K eyswitch selector for choosingread only mode (R EAD ) or settingmode (EDIT)
L S I GL S I
PR111/P
L I
PR112/P
L S I G
PR112/PD
L S I
PR112/P
L S I
M icroprocessor faultindicator
Auxiliary powersupply indicator
Dialogue indicators
Prealarm/alarmindicators
C onnection toexternal unit(SACE PR010/Tand PR110/B)
Programming k eys
Liquid crystal display
R ating plate showing therated current of the CTs forneutral and the serialnumber of the release
Testpushbutton
P rotection functions foroperation indicators
R eleaseovertemperatureindicator
Reset button
PR112/PD
L S I G
8
PR111/PPR111/P
7/27/2019 Emax Brochure
http://slidepdf.com/reader/full/emax-brochure 9/20
9
Main characteristics of the releases
Protection releases give circuit-breakers the intelligence to m anage the protect ion of circuits and
users.
L
S
I
G
Protection functions SACE PR111 SACE PR112
O verload protection with
inverse long time-delay trip • •
Selective short-circuit protectionwith inverse short
time-delay trip • •
Instantaneous short-circuit protection
with adjustable trip current threshold • •
R esidual • •
Earth fault protectionSource groundreturn •
Thermal memory for functions L and S •
Measurements
C urrents (phases, neutral and earth fault) •
Event and maintenance data marking
Event mark ing with time event occurred •
Events stored in chronological order •
C ounting of number of operations and contact wear •
Communication with centralisedsupervision and control system
(using dialogue unit)R emote setting of parameters,protection functions,
unit configuration and communication •
Transmission of measurements, statuses and
alarms from circuit-breaker to system •
Transmission of events and maintenance data
from circuit-breaker to system •
Self-test
Alarm and tripping for release overtemperature •
Alarm for microprocessor fault •
User interface
Parameter setting using DIP switches •
Parameter setting using keysand liquid crystal display •
Alarm indication for functions L and S •
C omplete management of prealarmsand alarms for all protection and
self-monitoring functions •
K ey for enabling usewith “READ” mode forconsultation only or “EDIT ” mode for
consultation and setting •
Load control (with auxiliary unit)
C onnection-disconnection of loadsin relation to the value of the current passing
through the circuit-breaker •
Zone selectivityC an be activated for protection functions S and G •
Earth fault protectionA number of different options are available for
earth fault protection:
• using protection function “G ” of the release:
in this case the earth current is calculated by
the release itself using the vector sum of the
phase and neutral currents ( “residual”
method)
• using a special toroid coi l that is installed onthe connection between the star centre and
earth of the MV/LV transformer, wi th direct
reading of the earth leakage current ( “Source
ground return”)
• using electronic residual-current relays from
a SACE RCQ switchboard with separate
toroid coil.
T his range of di fferent options makes it
possible to cover every earth fault protection
and selectivity requirement.
7/27/2019 Emax Brochure
http://slidepdf.com/reader/full/emax-brochure 10/20
10
T he growing complexi ty of installations
together with the need for increasingly
efficient and safe swi tchgear has led A BB
SACE L.V . to develop uni ts that complete the
functions offered by a mi croprocessor-based
release, the “brains” of a circuit-breaker.
T he SACE P R010/T and SACE PR010/K units
are the result this product development
approach.
SACE PR010/T:fingertip controlT his unit is able to provi de test, programming
and parameter readout functions for SACE
Emax series protection releases.
T hanks to its compact dimensions, simplicity
of operation and handling, this unit is
particularly easy to use in all conditions, even
when the circuit-breaker i s installed. T he Test
function, which can be implemented using
both releases, mak es it possible to check all
the protection functions in two different ways,
either manually or automatically,
simultaneously monitoring whether the
mi croprocessor is operating correctly. I t is also
possible to store any test results of interest in
the unit itself and export them to a personal
computer using the “report download”
function. Parameters can only be set and read
out on the PR112 range of releases.
ABB SACE L.V. also supplies a floppy disk
with the unit containing the application
software for updating or adapting the Test
unit in line with the development of new
products.
SACE PR010/K T his is a signalling unit able to convert the
digital signals from the SACE PR112 release to
electric signals, thus making it possible to
monitor the status of the protection device,
including remotely. T he information provided
mainly concerns the alarm conditions of all
the protection functions and the release’s
alarm situations. T his unit also allows one to
implement a load control function that acts
directly on the operating means of other
circuit-breakers installed downstream.
T he “intelligence” of the unit resides in the
fact that i t is able to recognise the type of
release concerned, enabling it to configure
itself to suit the characteristics of the latter.
SACE PR010/K
Accessory units for overcurrentreleases:SACE PR010/T - SACE PR010/ K
SACE PR010/T
7/27/2019 Emax Brochure
http://slidepdf.com/reader/full/emax-brochure 11/20
11
From releases to an integrated system
M icroprocessor-based releases offering
measurement and dialogue functions are the
final link in distributed control systems for low
and medium voltage electrical installations,
based on the use of intelligent units connected
to one another using a local network .
The new SACE PR112 releases also mak e it
possible to achieve integration in the “logic” of
the centralised management system of the
installations using circuit-breakers that are
suitable both for the protection and
automation of electrical i nstallations.
I t is possible to control and monitor the
following using the dialogue unit:
• circuit-breaker status
• protection function parameters
• number of operations ( opening/closing)
• value of the current interrupted
• operating status of the release
• prealarm/alarm indications
• operating mechanism (opening/closing).
The mi croprocessor-based protection releases
in the SACE PR112/PD series inserted in theSAC E SD -View 810 control system represent
ABB SACE L.V .’s basic answer for the control
and automation of electrical installations in
industry and the servi ce sector.
It is also possible to interface the SACE PR112/PD
release with the main
communication protocols
present on the mark et.
• circuit-breaker status• protection function
parameters• number of operations
(opening/closing)• value of the current
interrupted
• operating status ofthe release
• prealarm/alarmindications
• operatingmechanism (opening/ closing).
11
Main characteristics
7/27/2019 Emax Brochure
http://slidepdf.com/reader/full/emax-brochure 12/20
12
Accessories: a standard rangeto make customising simpler
The entire series of
SACE Emax circuit-
breakers is served by a
single line of
accessories. In
particular, the electrical
accessories can be
used both in
alternating current and
direct current
applications, and are
always installed from
the front without the
need for any wiring.
The ease with w hich
the accessories can be
fitted also makes
installation operations
fast and safe, such
that even the end
customer can carry out
the customising
necessary in each
phase of an
installation’s life. Thecurrent transformers
for the different rated
currents of the
releases are extremely
easy to change,
including by the end
customer. What’s
more, conversion kits
are available to obtain
different terminal
solutions and versions.
12
IP 54 protection door
cover
Lock for open
position
Lock for circuit breaker in racked-in/
test isolated/racked-out position
G earmotor for automatic loading of
closing springs
Flange
Tamper-proof protective cover for
opening and closing pushbuttons
7/27/2019 Emax Brochure
http://slidepdf.com/reader/full/emax-brochure 13/20
13
M echanical indication
of overcurrent releases
tripped
Duty releases
M echanical operation
counter
Electrical indication of
circuit-breaker op en/closed
Homopolar toroid for
earth conductor
C urrent transformer for
external neutral conductor
M echanical lock
for cell door
Interlock across
circuit-breakers
Padlock device
for shutters
Electronic time-lag device for
undervoltage release
15 additional auxiliary
contacts
C urrent
transformer
Electrical indication of
circuit-breaker racked in/
test isolated/racked out
13
7/27/2019 Emax Brochure
http://slidepdf.com/reader/full/emax-brochure 14/20
14
These versions are based on the movi ngpart of the corresponding wi thdrawablecircuit-breaker on whi ch all the break ingcomponents and the operating mechanismhave been replaced by simple connectionsbetween the top and bottom contacts. T heyare used as no-load isolators in situationswhere this function is provided for in theinstallation.
These versions are simi lar to isolatingtrolleys but with the bottom or top isolatingcontacts replaced by connections that areconnected in a short-circuit and earthed.They are used by temporarily rack ing theminto the fixed part of a withdrawable circuit-breaker for earthing the top or bottomterminals before carrying out maintenance
operations on the external circuit.
Isolating trolley - CS
Earthing switch with making capacity - MTP
Earthing trolley - MT
T hese versions are based on the movingpart of the correspondi ng withdrawablecircuit-breaker without the overcurrentreleases and the top or bottom isolatingcontacts, which are replaced by connectionsthat short circuit and earth the phasesthrough the circuit-breaker. T he earthingcircuit is dimensioned for a short-timecurrent equal to 60% of the maxi mum I cwof the circuit-breaker on which it is based.T hey are used for earthing duringinspection or maintenance work on
installations where the earthing operationcould be performed in the presence of residual or return voltages.
D isconnectors only differ from automaticcircuit-breakers in not having anovercurrent release. T hey have the sameversions and range of accessori es.
Switch-disconnectors- MS
Derived versions
7/27/2019 Emax Brochure
http://slidepdf.com/reader/full/emax-brochure 15/20
15
SACE Emax circuit-breakers for1000 V AC
The 1000 V AC circuit-breakers are based on
the standard range ( rated service voltage up to
690 V) and retain the same dimensions, use
the same accessories and have the same
“names” plus the ending “/E” . T hey are
available in fixed and withdrawable versions
with the three or four poles and areparticularly suitable for installation in special
environments such as mines, petrochemical
installations and for traction.
Electrical characteristics
Rated uninterrupted current Iu [A] 1600 2000 1250 1600 2000 1250 1600 2000 2500 3200 3200 4000
R ated service voltage U e [V] 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Rated ultimate short-circuit
breaking capacity Icu [kA ] 20 20 30 30 30 50 50 50 50 50 65 65
R ated service short-circuit
breaking capacity Ics [kA ] 20 20 30 30 30 50 50 50 50 50 65 65
R ated short-time
withstand current Icw [kA ] 20 20 30 30 30 50 50 50 50 50 65 65
E2B/E E2N/E E3H/ E E4H/E
Special versions
Other versions
SAC E Emax circuit-breakers can also besupplied to order in appropriate special
versions suitable for particularly aggressive
environments ( SO2 or H
2S, etc.) and for anti-
seismic installations.
7/27/2019 Emax Brochure
http://slidepdf.com/reader/full/emax-brochure 16/20
16
The range comprises power circuit-breakers wi th their related accessories,
manufactured in accordance with ANSI standards C37.13, C37.16, C37.17
and C 37.50, and certified in conformity with the UL1066 standard ( Low
Voltage AC and D C Power Ci rcuit Breakers Used in Enclosures) .
T he UL Listed SACE Emax series is suitable for use in electrical
swi tchboards in accordance wi th the U L 1558 and U L 891 standards.
Performance level B-A B-A N-A N-A S-A H-A S-A H-A V-A H-A V-A
Currents
Rated continuous current [A] 800 1600 1200 2000 1200 1200 3200 3200 3200 4000 4000
[A] 1200 1600 2500 1600 1600 3600 3600 3600 5000 5000
[A] 2000 2000
[A] 2500 2500
Rated short circuit current 240 V [kA] 42 42 65 65 85 85 85 100 100 125 125
480 V [kA] 42 42 50 50 65 85 65 85 100 85 125
600 V [kA] 35 42 50 50 65 65 65 85 85 85 85
Rated short time current [kA] 35 42 50 50 65 65 65 85 85 100 100
Overall dimensions
Fixed: H= 418 mm / 16.46 in
D= 302 mm / 11.89 inW (3 poles) [mm/in] 296/11.65 296/11.65 404/15.91 566/22.28 782/30.79
Withdrawable: H= 461 mm /18.15 in
D= 396,5 mm /15.61 in
W (3 poles) [mm/in] 324/12.76 324/12.76 432/17.01 594/23.39 810/31.89
Weights (CB fitted with releases, RH terminals and CTs, accessories excluded)
Fixed 3 poles [Kg/Ibs] 42/93 46/101 68/150 95/209 140/309
Withdrawable 3 poles [Kg/Ibs] 65/143 72/159 100/220 147/324 210/463
E1 E2 E3 E4 E6
Specifications common to the entire rangeVoltages
Rated maximum voltage 635 [V]
Rated voltage 600 [V]
Test voltage (1 min 50/60 Hz) 2,2 [kV]
Frequency 50-60 [Hz]
Number of poles 3
Versions Fixed - Withdrawable
Rated continuous current [A] 800 1200 1200 1600 1200 1600 2000 2500 3200 3600 4000 5000
Mechanical life
[N o. operations x 1000] 15 15 12 12 10 10 10 10 5 5 5 5
Electrical life
[N o. operations x 1000] 10 10 10 10 10 10 8 8 5 5 5 3
E1 B-A E2 B-A/N-A E3 N-A/S-A/H-A E4 S-A/H-A/V-A E6 H-A/V-A
New range complying with ANSI standardsand UL certified
7/27/2019 Emax Brochure
http://slidepdf.com/reader/full/emax-brochure 17/20
17
They’ve passed the toughest exams.Here’s the proof
SACE Emax circuit-breakers and their
accessories comply with the international
Standards IEC 947, EN 60947 (harmonised in
17 countries by CENELEC) , C EI EN 60947 and
IEC 1000, together wi th the followi ng
European directives:
• “Low Voltage D irectives” ( LVD ) No. 73/23/
CEE ( and subsequent variants) ;
• “Electromagnetic Compatibili ty D irective”
( EM C) No. 89/336/CEE.
The switchgear complies wi th the
requirements set out in the regulations for
installations on ships and has been approved
by the followi ng Naval Registers:
• RINA ( Registro Italiano Navale)
• D et Norske Veritas
• Bureau Veritas
• G ermanischer Lloyd
• Lloyd’s Register of Shipping
• Polsk j Reiestr Statkow
T his certification of conformity with the
product Standards mentioned is carried out, in
compliance wi th European Standard EN 45011,
by the Italian certification body AC AE ( Asso-
ciazione per la Certificazione delle Apparec-
chiature Elettriche) recognised by the
European body LO VAG ( Low Voltage
Agreement G roup) .
T he ABB SACE L.V . Q uality System compli es
with the ISO 9001 international Standard( model for quality assurance in design,
development, manufacture, installation and
service) and the equivalent European Standard
EN ISO 9001 and its I talian version UNI EN
ISO 9001.
T he third-party certifying body is RI NA-
Q UACER. ABB SACE obtained its first three-
year certification in 1990 and is now on its
third certification.
T he Frosinone factory has achieved ISO 14001
environmental certification.
7/27/2019 Emax Brochure
http://slidepdf.com/reader/full/emax-brochure 18/20
18
SACE Emax presents all the benefits of the linePoint by point
Easyinstallation
The number of mountingpoints required has beenreduced compared to theprevi ous series and theyhave all been placed on thebase of the circuit-breakerto make it easier to installthe circuit-breakers inswitchboards.The availabili ty of a widerange of terminals makes itpossible to build wall-mounted switchboards orswitchboards that can beaccessed from the rear withrear connections.The circuit-breakers areavailable with di fferentcombinations of top andbottom terminals to meetspecial requirements.
Easycustomisation
Accessory installationoperations have beenoptimised and simplifiedthanks to a range of specialconstruction features. Allthe electrical accessories arefitted from the front. Thismakes it simpler to fit theaccessories and means thattheir installation can beplanned in the lastinstallation phase. What’smore, the simplicity andsafety of the operationsmeans that the endcustomer can also carry outany customisation thatmight become necessaryduring the life of theinstallation. To this end, thecurrent transformers for thedifferent rated currents arealso extremely easy tochange.
Optimal answers to
problems of design,
operation and
management.
The protection releases
feature sophisticated
protection functions and
wide adjustment ranges.
Particularly compact
dimensions.
The same height and
depth for the entire
series.
The same accessories
for the entire range both
for DC and AC.
Operator safety is
ensured by a multitude
of diff erent features,
including:• double insulation
between accessories
and power circuit;
• key locks and padlock
devices on operating
mechanisms;
• racking out with door
closed on
withdrawable circuit-
breakers;
• anti-insertion locks for
preventing the insertion
of moving parts in fixed
parts with differentrated currents.
Accessories that don’t
need wiring.
T he entire series of SACEEmax air circuit-breakers isnot only characterised byhaving constantdimensions but the sameheight and depth as well.T his facili tates the designphases, making for easierfabrication withstandardised supportingframes. T he sheet steelstructure of the circuit-breaker is extremelycompact and enablessignif icant space savings. Asingle front flange for theentire series simplifies theconstruction of switchboard doors,enabling a single type of drilling to be used.
Modular strengthsand compactdimensions
18
7/27/2019 Emax Brochure
http://slidepdf.com/reader/full/emax-brochure 19/20
19
Optimalwarehousemanagement
Stock management in thewarehouses of electricalmaterial distributors andcustomers who need tomanage the maintenanceand spare parts of largeinstallations is made muchsimpler and rationalised bythe adoption of highly-effective solutions,including:• a single line of
accessories for the entireseries
• an opening and closingrelease that can be usedas a single accessory.The function isdetermined exclusivelyby the mounting position
• duty releases that can bepowered in DC or ACwithout any modification
• single fixed part for eachcircuit-breaker model(even if they havedifferent rated currentsand different breakingcapacities)
• interchangeability of SACE PR111 and PR112overcurrent releases
• conversion kit fordifferent terminal andversion solutions.
Efficient andsafe installations
SACE Emax circuit-breakersprovide a high level of safety for those operatingon the installation:• a series of locks ( key
locks or padlockdevices) ensurecomplete safety againstany incorrect operations
• the accessories areinstalled from the frontand operator safety isensured by the doubleinsulation thatguarantees totalsegregation of theaccessory seatings fromthe power circuit
• circuit-breakers can alsobe racked out with thecompartment doorclosed
• option of mechanicalinterlock ing across twoor three circuit-breakers,irrespective of theirmodel or version ( fixedor wi thdrawable) usingflexible cables. Thecircuit-breakers can beinstalled vertically orhorizontally.
• different protectiongrades available,including IP54,
implemented using atransparent tamper-proof guard for fitting on thefront of the switchboard
Easy and safemaintenance
Just a few simpleoperations allow fullinspection of the arcingchamber and powercontacts wi th the circuit-breaker out of service;( withdrawable versions caneven be racked out withthe door closed) .Isolation of the accessorycompartment from thepower circuit prevents anypossibility of accidentalcontact with live parts.
The intelligence of thenew-design SACE PR111and PR112 microprocessor-based overcurrent releasesenables: very highoperating precision, a wideadjustment range,protection against all typesof faults and monitoring of the main electricalparameters, operationwithout the need for anauxiliary power supply,sensiti vity to the true root-mean-square value of thecurrent, and the option of dialogue with computerisedsupervision and controlsystems such as the SACESD-View 810.
Intelligentprotection
19