MDI/Estate/ AC/Chanakya/2017 29 March 2017
Sub: Providing & installation of Imported Variable Refrigerate volume Air-condition, Ductable split AC & Cassette AC in Chankaya GF at MDI Campus , Gurgaon
Dear Sir, 1. Quotations are invited for providing and installation of Imported Variable Refrigerate
volume Air-condition in GF, Ductable split AC & Cassette AC in Chankaya GF at MDI Campus, Gurgaon. Please submit your Technical & Commercial bids in a two separate envelopes. The envelop should be clearly marked separately as Commercial Bid and Technical Bid. The tenders should be submitted in a sealed cover addressed to:-
The Resident Engineer Management Development Institute Post Box No. 60, Mehrauli Road GURUGRAM – 122001
The quotes should reach on or before 1500 hours on 14 April 2017. Schedule of quantities and drawing attached as Annexure 1 & 2. The terms and conditions are given below:-
2. Terms and Conditions
(a) The prices quoted shall include the supply and installation at site for all equipment’s, ancillary material and other items required for carrying out the complete job.
(b) All taxes shall be indicated separately. Service tax on Supply & installation heads shall be paid extra as per rules, however the details of taxes be worked out and given in the quote.
(c) Secured advance not exceeding 75% of the value of materials brought at site can also be considered and the recovery of the same shall be done on pro-rata basis of progress achieved at site.
(d) No form C & D for shall be supplied. The rates should be quoted inclusive of LST/CST and excise duty, if applicable.
(e) TDS and WCT shall be deducted from the bills as per rules.
(f) The contractor shall submit an EMD of Rs.25,000/- by way of demand draft or banker cheque drawn in favour of Management Development Institute payable either at
Gurgaon or Delhi. The quotation shall not be considered without EMD. Once the offer is accepted, the EMD shall be treated as Security Deposit.
(g) Quotations shall be valid for acceptance for 90 days from the date of submission.
(h) Time of completion is one month from the date of receipt of Letter of Intent (LOI) from the Institute.
(i) Extra work, if executed, shall be analyzed and paid based on market rate added with 15% contractor’s profit and overhead. Vouchers/bills in support of the claim shall also be enclosed.
(j) Contractor shall arrange to provide at no extra cost necessary personnel and material to carry out all routine and special maintenance of the plant regularly for a period of 12 months from the date of completion.
(k) All works executed under the contract shall be guaranteed for a period of 12 months from the date of commissioning and handing over of the complete systems to the Institute. Any or all components found defective shall be replaced or repaired free of charge and any short comings found in the system shall be removed at no extra cost. The guarantee does not include refrigerant and oil.
(l) Terms of Payment :-
(i) 75% pro-rata payment against supply of equipment, component etc. (ii) 15% of the contract value on erection/installation. (iii) 10% of the contract value against testing and commissioning
(m) Defect and liability period would be 12 months from the date of completion. 5%
retention amount will be retained for a period of Six month.
(n) The air conditioning work shall be carried out at our Chankaya building GF.
(o) Routing, testing, pressure testing of fabricated components and performance testing shall be carried out at site.
(p) The AC units proposed are:-
(i) Imported Variable Refrigerant Volume-Air-conditioning System 22 TR x 1 No. (ii) Ductable Split AC 2.65 TR x 1 No. (iii) Cassette AC 2.65 TR x 8 No.
(q) If any cutting/opening is made for passing the ducts or pipe line etc. the same shall be
rectified at no extra cost.
(r) Conditioned air from the units shall be distributed using insulated GI ducting and good quantity of aluminum powder coated grills / diffusers and each indoor unit shall have individual control system.
(s) Acceptable makes are as under:-
(i) Imported Variable Refrigerant Vol. –Air conditioners system - Daikin, Mitsubishi, Toshiba, Blue star.
(ii) Ductable Split AC - Scroll Compressor (Copper condenser) (iii) GI Sheet - SAIL/National/NIPPON/TATA (iv) Insulation - Paramount /Trocellence/ (v) Grills/ diffusers - MAPRO/CARYAIRE/SERVAX/RAVISTAR (vi) Cables - CCI /Delton/Gloster/ECKO.
(t) The price quoted and accepted by the Institute shall be firm throughout the currency of
the contract.
(u) The contractor is expected to use best material and good workmanship and defects /discrepancy, if any, shall be rejected and no payment for such work shall be made.
(v) Electricity and water shall be provided free of cost.
3. The letter of intent (LOI) for the machines shall be placed with the principal supplier and low side components and execution with the dealer. If desired. Declaration to the effect that the units ordered are for the use of the Institute and not for resale shall also be given.
4. Contractor has to make own arrangement for storing materials and its watch and ward shall also be their responsibility. However we may consider to provide some temporary storage within the building which has to be vacated immediately after the completion of the work.
5. Above terms and conditions supersedes the general terms and conditions and technical specifications enclosed separately with the quotation.
6. MDI reserves the right to accept or reject any or all the quotations without assigning any reason whatsoever. No conditional quotation shall be considered.
Sdxxxxxxxxxx (Subhash Chand)
Resident Engineer Encl: Two only
Annexure-1
S.No Description Unit QtyUnit Rate
Supply
Unit Rate
Installation
Amount
Supply
Amount
Installation
1 Imported Variable Refrigerant Volume ‐ Air‐conditioning System
A Outdoor Unit
Supply, Instalaltion, testing and commissioning of Variable Refrigerant Volume modular type
airconditioning system Invertor Controlled with stepless modulation complete with indoor and
outdoor units, individual remote controller and centralized controller, interconnected refrigerant
piping ,full charge of refrigerant gas & oil, control cabling etc.as per detail given in specifications and
having following items.
iRXYQ28TRTRY6(E) - 22 TR
(RXYQ12TRY6(E) + RXYQ16TRY6(E))No. 1
B Indoor Units
2 Ductable Split AC
2.1
Supply, Installation, Testing & Commissioning of aircooled type ductable airconditioning units, each
comprising of an outdoor unit and a single concealed type
indoor unit. Outdoor condensing unit shall comprise of compressors & air cooled
condenser with fan. Evaporating unit shall consist of a fan section with dynamically
balanced centrifugal fan driven by TEFC squirrel cage induction motor, multirows deep
copper cooling coil with aluminium fins, thermostatic expansion valve etc. The
evaporating unit shall be equipped with synthetic fibre filters, Insulated drain pan,
safety controls, thermostat all complete in a unit.
i Capacity - 2.65 TR (FXMQ80PVE) No.s 1
3 Cassette AC
Supply, Installation, Testing & Commissioning of aircooled type Cassette airconditioning units, each
comprising of an outdoor unit and a single concealed type
indoor unit. Outdoor condensing unit shall comprise of compressors & air cooled
condenser with fan. Evaporating unit shall consist of a fan section with dynamically
balanced centrifugal fan driven by TEFC squirrel cage induction motor, multirows deep
copper cooling coil with aluminium fins, thermostatic expansion valve etc. The
evaporating unit shall be equipped with synthetic fibre filters, Insulated drain pan,
safety controls, thermostat all complete in a unit.
i Capacity - 2.65 TR (FXCQ80) Nos 8
ii Y-Joints Nos 9
Price BOQ
III Corded Remote Nos 10
4 Refrigerant Piping
Supply, Installation, testing & commissioning of refrigerant grade copper piping
interconnecting outdoor and indoor units duly insulated with 9mm thick elastomeric
nitrile rubber tubing to prevent any heat loss, suitable sizes.
i RM 100
5 Electrical Work
5.1Supply, Installation, testing & commissioning of Control cables in PVC counduiting duly
complete with all fittings as per specification of suitable sizes from indoor units to
outdoor units of Ductable AC .The wiring shall be as per the manufacturer's recommendations.
i Size - 1.5 Sqmm X 2C - Shielded RM 120
ii Size - 16 Sqmm X 4C RM 20
5.2Supply & Installation of flexible double earthing for outdoor units & Isolator Panel with 6 Sqmm X 1
Core Green wire.RM 20
5.3Supply & Installation of Isolator box with Isolator switch for Outdoor Units (Rating for
MCB - 40 Amps).Nos 2
6 Cable Trays
Supply, installation of ladder type/perforated type cable trays of the following sizes
fabricated out of galvanised MS sheets of minimum 2 mm thick with 50 mm flange to
be installed horizontally or vertically. The cable tray shall be complete including cost of
bends, elbows, cross, tees, reducers etc as per drawings/site condition and rate shall
include cost of anchor fasteners, screws, nuts, bolts and misc. other fixing hardware
painting of support.
i 300mm wide RM 20
ii 150mm wide RM 20
7 Insulated Drain Piping
Supply, Installation, testing and commissioning of heavy duty UPVC drain piping in
floor / wall / surface / recessed including chase cutting & making good of strength
6Kg/sq.cm for indoor machines complete with necessary elbows, tees, reducers etc.
Insulation for Drain Pipes 6mm thick elastomeric nitrile rubber tubing.
i 25mm Dia. RM 60
8 M.S Stands
Supply and Installation of outdoor stands for outdoor units of VRV System.
i For 18 HP & 12 HP Nos 2
9 Ducting
Supply, Fabrication, Installation and testing of sheet metal ducts in accordance with the approved
shop drawings and specifications.
26 gauge Sqm
24 gauge Sqm
10Supply & Installation of fire retardent canvass connections for Indoor unit of Ductable
unit.Nos
11 Acoustic Lining
Supply & Installation of acoustic lining of ducting with 25 mm thick fibre glass
insulation, covered with RP tissue paper & finally cladded with AL perforated sheet.Sqm 10
12 Ducting Thermal Insulation
Supply & Installation of thermal insulation of ducting with 9 mm thick cross linked polyethylene
instulation.Sqm 25
13 Supply/Return Air Grill
Supply, Installation ,Testing and commissioning of Supply/Return air grill. Sqm 1
14 Collar Dampers
Supply, Installation, Testing and commissioning of collar dampers for supply air grilles. Sqm 1
15 Volume Control Damper
Supply, Installation and Testing & commissioning of multiblade volume control damper
of galvanised steel sheet for duct branches to provided with suitable links, levers and
quadrants for manual control of volume of air flow and for proper balancing of air
distribution as per approved shop floor drawings and specifications.
Sqm 1
16 Fresh Air Louver
Supply & Installation of fresh air louver & bird screen for fresh air intake. Sqm 1
17 Drain Pump
Supply, installation and testing of drain pump for ductable unit. Nos 1
18 SS Plate
Supply & installation SS plate for covering Cu piping in corridor. Nos 2
19 Refnut
Supply & installation of refnuts for Indoor & Outdoor. Nos 10
20 Dismentling & reinstallation of grid ceiling Lot 1
Total
Note :-
1. All taxes to be indicated at the end of the quote.
2. Single Phase power supply with isolator switch to be provided to each indoor unit ( In customer scope ).
3. Three Phase power supply to be provided to our isolator box near Outdoor unit ( In customer scope ).