comision federal de electricidad simefas … · comision federal de electricidad simefas mexico´s...
Post on 21-Sep-2018
225 Views
Preview:
TRANSCRIPT
COMISION FEDERAL DE ELECTRICIDAD
SIMEFASMEXICO´S WIDE AREA MEASUREMENT
SYSTEMS
VANCOUVER, B. C. CANADA JUNE 7-8 2010
NORTH AMERICAN SYNCHROPHASOR INITIATIVE WORKING GROUP MEETING
CONTENTS
MEXICAN ELECTRIC POWER SYSTEM WHY PMUS? APLICATIONS REAL-TIME OFF-LINE SPS
CONCLUSIONS
NORTH AMERICAN SYNCHROPHASOR INITIATIVE WORKING GROUP MEETING
PHASORS, PMUS & PDCS
CDPMUSBCS
GRT AC NOR
CDGRT-OCC
CDGRT-OTE
GRT-CEN
CDGRT-STE
GRT Y AC PEN
CDPMUBCN
LA VENTA DOS
GENS MMT
GENS MPUCH CARACOL
272 PMUs732 PHASORS 1 PDC/SYSTEM12 LOCAL PDCSPS-AGSSSYNCHRONIZER
GUATEMALA
GRT Y AC NTEGRT Y AC NES
WHY PMU´S?
20 SAMPLES PER SECONDIEEEC37.118
CONVENTIONAL MEASUREMENTONE SAMPLE EVERY TWO SECONDS
ON-LINE APPLICATIONS
ANGULO EN EL DOMINIO DEL TIEMPO
FRECUENCIA
INTERCONNECTION MEXICO-CENTRAL AMERICAMONITORING IN REAL TIME
CENTRAL AMERICAFREQUENCY
CFEFREQUENCY
THP-115 KV
REGIONAL DATA CONCENTRATOR
OFF-LINE APPLICATIONSWECC SYSTEM
OFF-LINE APPLICATIONS
-100
-50
0
50
100
150
200
250
300
0
20
40
60
80
100
120
140
160
180
200
59.4
59.6
59.8
60
60.2
60.4
MWSAMPLES
HZ
MZD-U1
MZD-DGD
HLI
EFR
REC-U4
SYC-U1
THREE DIMENSIONAL ANALYSIS OF OSCILLATIONS
POWER FLOW BUS FREQUENCY
COLLABORATION CFE-KTHLuigi Vanfretti, Mehrdad Ghandhari (KTH Royal Institute of Technology, Sweden),
Associated Collaborators: Dan Trudnowski (Montana Tech) & Joe H. Chow (RPI)
MODE METER DAMPING AND FREQUENCY ESTIMATES FROM THE BUS FREQUENCY SIGNAL
COLLABORATION CFE-KTHLuigi Vanfretti, Mehrdad Ghandhari (KTH Royal Institute of Technology, Sweden), Associated Collaborators: Dan Trudnowski (Montana Tech) & Joe H. Chow (RPI)
SPECIAL PROTECTION SCHEMSCHICOASEN-ANGOSTURA AGSS
ΣP=P1+P2
EIA-232 EIA-232
150 MW
ΣP=P1+P2
FIBER OPTIC
AGSS CONDITIONS• VOLTAGE• FREQUENCY• 10 ≤ ΣP 800 • 52
• ANG = α - α1
V1F1P1, Q1P2, Q2α
V2F2P1, Q1P3, Q3α1
POWER FLOW
MUX MUX
≤
ANGLE DIFFERENCE CALCULATIONS AND MEASUREMENTS FOR THREE DIFFERENT
LINE TRIPS
CONCLUTIONS
MAIN TECHNICAL FACTORS MEASUREMENT LOCATION PMU, PMCU or RD/PMU SAMPLES ONE PHASOR or MULTI-PHASOR WAMS ARCHITECTURE SUPERPDC or PDCs COMMUNICATION SYSTEM
YOUR QUESTIONS?
THANK YOU