NSW GOVERNMENT Health
Certificate of Accreditation Sewage Management Facility
Sewage Ejection Pump Station
This Certificate of Accreditation is issued by the Secretary of the NSW Ministry of Health pursuant to Clause 41(1) of the Local Government (General) Regulation 2005.
System: XR XYLEM Series 600L, 900L, 1200L, 1500L, 2700L, 3750L, 4800L, 6500L, 8500L, & 10,000L SEPS in Single and Dual Pump Configurations
Manufacturer: Graf Plastics Australia Pty Ltd
Of: 23 Success Way, Henderson, WA, 6166
The XR XYLEM Series SEPS as described in the attached Schedule have been accredited as sewage management facilities for use in single domestic premises in NSW. The pump well is manufactured to the Australian / New Zealand Standard AS/NZS 1546.1:2008 On-site domestic wastewater treatment units - septic tanks.
A/Direct r, Environmental Health for Secretary (delegation PH335)
Issued: 19 June 2020 Certificate No: 5EP5005 Expires: 31 December 2024
tot NSW GOVERNMENT
Health
Accreditation Schedule
The Certificate of Accreditation applies to the following range of sewage ejection pump stations in accordance with the attached plans.
The Graf Plastics Australia XR XYLEM Series sewage ejection pump stations consist of:
• A moulded polyethylene pump well and lid, manufactured by Graf Plastics Australia Pty Ltd, of Henderson, Western Australia, with capacities of 600L, 900L, 1200L, 1500L, 2700L, 3750L, 4800L, 6500L, 8500L, & 10,000L litres;
• XYLEM Grinder pump/s in either single or dual configuration: • PVC pressure discharge pipe fitted to ball type anti-syphon
check valve and shut off valve on the outlet of the grinder pump. The discharge pipe is connected to either 50mm or 32mm diameter house pressure main to the sewer:
• A control panel with audible and visual alarm with start, stop and high level float switches.
Lifting Lugs
ter, / / I
rem
1200L 900L 600L
ACCREDITED
19 JUN2020
NSW MINISTRY OF HEALTH
THIS DOCUMENT IS SUPPLIED IN STRICT CONFIDENCE AND MUST NOT BE LENT, REPRODUCED OR DISCLOSED TO ABS THIRD PARTY IVITHOLT
THE WRITTEN CONSENT CIF GRAF PLASTICS AUSTRALIA
DO NOT SCALE - IF IN DOUBT ASK NOTES
I. Proposed Graf Meeks AuStlaa layout.
2.9 dimensions In min unless otherwise slated. 3. M temporery and anablIng works by others. 4. Normal vokene: 6001. 9001.. and 1200L
S. Rumps used:
- Davey Submersible Grinder Pumps 075G, 07554. 0120G, 0120GA. 0150G, 015054. 51080. 51125, (MSG 0T220 d 01375 • Grundlos SEE and SEE A UTOADAPT Sewage PenIFS 19 IC 4.0 kW - Amara, N Subrnersele motor pumpa DN 50 lo I CO, 50 Fle
a. Conhohrs used' - Ken *In TPS Tree Pump Starters TPS-6D.AV - Kenrahn LOS Level Regulator Starters LRS-6D-AV
TI CHANGE ON TANK GROUP Fil..
PO ERELIMINAEYEOEEPPROVAL SU 19 2 I
REV DESCRIPTION BY DATE
GRAF GRAF Plastics Au WA 51 S6
4949 corn a) E ink:kg/Wig
GRAF Pimples Ausrralle PG 1.1123 Success War, Handal. TEA) 9437 4949 F 10819437
0ShOsaustrale corn au www erne, lashosaustralus
DRAWN BU DATE 19 12 16 CHECKED BU F.CIAI E VARIOUS@A?
PRO.ECT
DESCRIPTION
SEWATEC Lifting Stations Single Freestanding Pump
DRAWING No
GAR.SLS.1200.SF1 P1
-
1200L 600L 900L
(.0
ACCREDITED
19 JUN 2020
NSW MINISTRY OF HEALTH
THIS DOCUMENT IS SUPPLIED IN STRICT CONFIDENCE AND MUST NOT RE I ENT, REPRODUCED OR DISCLOSED TO ANY THIRD PARTY W1THOLT
THE WRITTEN CONSENT OF GRAF PI ASTICS AUSTRALIA
DO NOT SCALE - IF IN DOUBT ASK NOTES
1. Proposed Graf Plashcs ;wakes layout.
2.51 dimensions In oar unless Paleness stated 3, 51 temporary and seeding works by others. A. Normal volume 6001. SCOL 060 12001 S. Pumps used:
-006.5 SultmerwNs Grinder Pumps 0750, 67505, U1200, 012055,
21500. 01500A. STOIC. 2T120, 21150 0T220 A 0137G
• Grundts SEG and SEG AUTOADAPT Sewage Pumps 0.9 to 4.0 kW -Amens, N Submemates motor pumps ON SO to 100.60 Kt
4 Contrellen used' - Kentalm ITS Test Peso Starlets TPSWD-AV
- Kenn*, IRS Level Reghlator Starters LOS-6D-AV
E MANGE ON TANK GROUP BU1302(1
P0 PREL I 'NARY FOR APPROVAL HU 24 06 1,
REV DESCRIPTION BY DATE
GRAF GRAF Plastics Au GRAF Mem Nasals Ph LIP 23 Success Way. tendon. WA 6(66
T 108) 943/4040 F 10819437 4949 E into€pgralpleshmauentha can au wow Palltestscsaustrate COT au
DRAWN BU DATE 130217 CHECKED BU SCALE VARIOUS41141
PROJECT
DESCRIPTION
SEWATEC Lifting Stations Dual Freestanding Pump
DRflV,1lI. II..
GAR.SLS.1200.DF1 P1
r
ACCREDITED
19 JUN 2020
NSW MINISTRY OF HEALTH
THIS DOCLNENT ISSUPPLIED IN STRICT CIDIFIDENCE AND MUST NOT BE LENT, REPRODUCED OR DISCLOSED TIT ANY THIRD PARTY WITHOUT
THE WRITTEN CONSENT BE GRAF AUSTRALIA
DO NOT SCALE - IF IN DOUBT ASK NOTES,
I. Proposed Graf Plastics Australia layout. 2. All dimensions In min unless otherwise stated. 3. Tanks are supplied with DN100 seals for Inlet 4. Tanks are supplied with 50mm outlet plpework
PO PRELIMINARY FOR APPROVAL
REV. DESCRIPTION
LB 264320
BY DATE
GRAF Australia lANE AustroUs Pty Ltd. 43 Sparks Road. Henderson VA 6166
T. (08) 9437 4949 n (08) 9437 4949
infoPprof. osticsoustrollo.conou
DRAWN LE DA It 26.0320 SCALE .VARIOUSRA3
PROJECT
DESCRIPTION
Lifting Pump station single freestanding 1500L
DRAWING No, REV.
PO
Li
_ V,
ACCREDITED
19 JUN 2020
NSW MINISTRY OF HEALTH sa-
PRELIMINARY FOR APPROVAL PO
GRAF GRAF Australia
DRAWN , LB DATE • 26.03.20 SCALE .VARIOUSRA3
26.0320 LB
NOTES.
1. Proposed Graf Plastics Australia layout. 2. All dimensions in mm unless otherwise stated. 3. Tanks are supplied with DN100 seals for Inie 4. Tanks are supplied with 50mm outlet pipework
REV. DESCRIPTION DATE BY
(RAF Australla Pay Ltd, 43 Sparks Road, litsokrson VA 6166 T. (043) 9437 4949 F. (08) 9437 4949
afplastIcsaustra6s.canou
PROJECT
DESCRIPTION
15001 Lifting Pump station Dual freestanding
DRAWING No. REV.
PO
THIS DOCUMENT IS SUPPLIED IN STRICT CONFIDENCE AND MUST HOT DE LENT, REPRODUCED OR DISCLOSED TEl ANY THIRD PARTY WITHOUT
TFE WRITTEN CONSENT OF GRAF AUSTRALIA
DO NOT SCALE-IF IN DOUBT ASK
1 ' N
! ,
1- --' i •
,
PRELIMINARY FOR APPROVAL PO
BY DATE
DRAWN LB DATE 26.03.20 SCALE .VARICUSIM3
CARAT L W H
2,700L 2080 1565 1680
3,750L 2280 1755 1870
4,800L 2280 1985 2100
6,500L 2390 2190 2380
26.03.29 LB
REV. DESCRIPTION
GRAF Australia CRAF Australia Pty Ltd, 43 Sparks Read, HetklarsaP VA 6146
T. (08) 9437 4949 0 (08) 9437 4949
0 Info!.
PROJECT
DESCRIPTION
Carat Ming Pump station single freestanding
THIS DOCUMENT IS SUPPLIED IN STRICT CONFIDENCE AND RUST MIT
BE LENT, REPRODUCED OR DISCLOSED TO NIT THIRD PARTY WITHOUT TFC WRITTEN CONSENT IF GRAF AUSTRALIA
DO NOT SCALE - IF IN DOUBT ASK NOTES.
1. Proposed Graf Plastics Australia layout. 2. AU dimensions In mm unless otherwise stated, 3. Tanks are supplied with DN100 seals for inlet 4. Tanks are supplied with 50rin outle-t plpework
ACCREDITED
19 JUN 2020
NSW MINISTRY OF HEALTH
CARAT L w H
2,700L 2080 1565 1680
3,750L 2280 1755 1870
4,800L 2280 1985 2100
6,500L 2390 2190 2380
THIS DOCUMENT IS SUPPLIED IN STRICT CONFIDENCE AND MUST MOT BE LENT, REPRODUCED CR DISCLOSED RI NIT THIRD PARTY WITHOUT
THE WRITTEN CONSENT OF GRAF AUSTRALIA
DO NOT SCALE - IF IN DOUBT ASK PEITES1
2. All 1. Proposed
a Tanks 4 Tanks
Graf Plastics Australia layout. dimensions in mm unless otherwise stated.
are supplied with DN100 seals for inlet are supplied with 50mm outlet pipewor
ACCREDITED
19 JUN 2020
NSW MINISTRY OF HEALTH
PO PRELIMINARY FIR APPROVAL LB 26.0320
REV DESCRIPTION BY DATE
T. (08) VA 6166
F. (08) 9437 4949 RIF
E. InfoRgrafplastIcsaustrallo
GRAF GRAF Australia Aus-b-fAs Ply Ltd, 43 Swim RNA, 1hrierson 9437 4949
conau
DATE . 26.0320 DRAWN LB .
SCALE . VARICUSPA3
PRCLECT
SCRIPTION
Carat Lifting Pump station dual freestanding
DRAWING No. REV.
PO
,
•
PRELIMINARY FOR APPROVAL PO
CARAT L W H
8,500L 3500 2040 2090
10,000L 3520 2240 2290
‘,/
2.0420 LB
BY DATE REV. DESCRIPTION
<T.
THIS DOCUMENT IS SUPPLIED IN STRICT CONFIDENCE AND MUST KIT BE LENT, REPRODUCED OR DISCLOSED 111 AIN THIRD PARTY WITHOUT
THE WRITTEN CONSENT OF GRAF AUSTRALIA
DO NOT SCALE - IF IN DOUBT ASK NOTES.
1. Proposed Graf Plastics Australia layout. 2. All dimensions in nn unless otherwise stated. 3. Tanks are supplied with DN150 seals for inle- 4. Tanks are supplied with 50nm outlet pipework
ACCREDITED
1 9 JUN 2020
NSW MINISTRY OF HEALTH
GRAF Australia IRE Al94lJ Pty Ltd, 43 Sparks Ronal, Mindoro:41 VA 6166
T. (08) 9437 4949 F. (08) 9437 4949
E. InFoPorof Plootkodustrallo.ron.au
PROJECT
DESCRIPTION
Carat XL Lifting Pump station single freestanding
BRAVING No. REV.
PO
BY DATE REV DESCRIPTION
CARAT L w H
8,500L 3500 2040 2090
10,000L 3520 2240 2290
ACCREDITED
1 9 JUN 2020
NSW MINISTRY OF HEALTH
GRAF Australia DRAI AusiroUs Pie L. 43 Sparks Road, Henderson VA 6166
T. (DE) 9437 4949 F. OW 9437 4949
E. Infoepreafplostksoustrolla.conoo
DATE . 2E03,20 SCALE . VARIOUSIA3
PROJECT
DRAWN . LB
THIS DOCU4ENT IS SUPPLIED IN STRICT COIFIDENCE AND 141351 1101 BE LENT, REPRODUCED OR DISCLOSED 111 ANY THIRD PARTY WITHOUT
THE WRITTEN CONSENT OF GRAF AUSTRALIA
DO NOT SCALE - IF IN DOUBT ASK NOTES.
I. Proposed Graf Plastics Australia layout. 2. All dimensions in mm unless otherwise stated. a Tanks are supplied with DN150 seals for Inte7, 4. Tanks are supplied with 50mm outlet pipework
DESCRIPTION
Carat XL Lifting Purip station Dual freestanding
/RAVING No. REV.
PO
V,
top related