AIR CONDITIONING SYSTEMS
HEAD OFFICE: MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPANhttp://Global.MitsubishiElectric.com
MEE05K440
MITSUBISHI ELECTRIC MULTIPLE SPLIT TYPE AIR CONDITIONERS Series
The Air Conditioning & Refrigeration Systems Works acquired ISO 9001 certification under Series 9000 of the International Standard Organization (ISO) based on a review of Quality management for the production of refrigeration and air conditioning equipment.
ISO Authorization SystemThe ISO 9000 series is a plant authorization system relating to quality management as stipulated by the ISO. ISO 9001 certifies quality management based on the "design, development, production, installation and auxiliary services" for products built at an authorized plant.
The Air Conditioning & Refrigeration Systems Works acquired environmental management system standard ISO 14001 certification.
The ISO 14000 series is a set of standards applying to environmental protection set by the International Standard Organization (ISO).
New publication effective Oct 2006Specifications subject to change without notice
http://Global.MitsubishiElectric.com/
FM33568 / ISO 9001;2000
Certificate Number EC97J1227
-
Air conditioning is an ideal way of
controlling the temperature, movement
and cleanliness of air inside any
building, large or small. With today's
buildings being so well insulated and
increasingly full of electronic equipment,
the need for effective climate control is
greater than ever. Not only does it cool
in the summer months, but air conditioning
can also heat, doing away with the
need for separate heating systems
altogether. More and more people today
are enjoying the benefits of comfortable working and living environments made
possible with air conditioning.
VRF systemVRF stands for Variable Refrigerant Flow. A VRF air conditioning system modulates the flow of refrigerant depending upon the capacity requirements of the building. A VRF system comprises of condensing unit sited externally and a series of multiple heating to the occupied space.
I nverter driven technologyAt Mitsubishi Electric we strive to continually meet the increasing demands of our customers, being the first in the industry to offer highly advanced inverter driven systems. Using inverter technology our systems produce just the right amount of output to match the exact requirement of any building. These systems work so efficiently that they dont waste valuable energy by over-heating or over-cooling, resulting in greatly reduced running costs. Alternative systems that may appear cheaper, can often cost substantially more to run, making us the most cost effective choice all round.
I ntelligent Power Module (IPM) technology
The City Multi range from Mitsubishi Electric provides precise control of energy input, through utilization of Intelligent Power Module (IPM) technology. Employing this technology it is possible to closely match the building requirements, achieving more accurate control of the occupied space. By using incremental 1Hz steps of capacity control, the amount of power input required is significantly reduced, resulting in greatly improved COPs.
R410A refrigerantAs scientific evidence points to man-made chemicals for the damage caused to the ozone layer, we only use chlorine-free refrigerants that are safe and have zero ozone depletion potential. Accordingly, as our systems require less energy to run, they have a significantly lower indirect global warming potential too. In short, our constant investment and product development possible, whilst protecting the environment at the same time.
Known the world over, the name
Mitsubishi is a trusted household name
associated with a variety of products and services. Founded in 1907, the
company known today as Mitsubishi Electric, quickly rose to the forefront of the air conditioning industry - a position we still enjoy today. We pride ourselves on offering some of the most energy efficient systems available on the market.
Page 1 Page 2
Our Latest Technologies
Unsurpassed air conditioning from Mitsubishi Electric
-
Sophisticated yet simple technology
VRF system
Our answer to VRF
Designed and manufactured to the highest standards, the City Multi range offers one of the most reliable air conditioning systems available. Simple to install and easy to maintain, this range provides ideal solutions you can trust to protect your investment.
Reliable
>All the City Multi outdoor units are made in Japan under stringent control.
Page 3 Page 4
Mitsubishi Electric sets the boundaries of VRF technology with the City Multi range, which is available using R410A refrigerant with zero ODP (Ozone Depletion Potential). The range has been specifically designed for todays building requirements and addresses key market issues such as energy efficiency, adaptability and reliability. With user friendly control systems utilizing Internet technology and integrated cooling and ventilation indoor units, City Multi is the benchmark and market leader in VRF technology.
VRF is a multi and direct expansion type air conditioning system that one outdoor unit can be connected with multiples of indoor units. The amount of refrigerant can be changed freely according to the load in the indoor unit because inverter compressor is used in the outdoor unit. Zoning in a small office is easily made possible with indoor unit whose minimum capacity is very small. Energy conservation is easily handled because individual indoor unit can stop and start its operation as needed. Indoor unit has a lot of models in order to suit various interior design needs. Appliance to control separating heat of cooling in evaporation from heat in condensation is becoming important in air conditioning in the building.
Outdoor unitJoint
Header
Inverter driven compressor
PEFY-VMS
PEFY-VMR
ON 27c
ON 25c
ON 25c
OFF
OFF
ON 23c
ON 26c
Controller
Indoor unit
-
Unbeatable Efficiency
I nverter Driven Compressor Technology - now up to 50HP
Using inverter driven technologysaves energy for several reasons:
The unique Heat Interchange Circuit (HIC) enhances efficiency by providing additional sub-cooling and allows the expansion device to control more effectively the refrigerant distribution, thereby increasing the operating efficiency and reducing the volume of refrigerant in each system.
Heat Interchange Circuit
The compressor varies its speed to match the indoor cooling and/or heating demand and therefore only consumes the energy that is required.
When an inverter driven system is operating at partial load, the energy efficiency of the system is significantly higher than that of a standard fixed speed, non inverter system. The fixed speed system can only operate at 100%, and partial load conditions prevail for the majority of the time. Therefore fixed speed systems cannot match the annual efficiencies of inverter driven systems.
Using proven single inverter driven compressor technology, the City Multi range is favoured by the industry for low starting currents (only 15 amps for a 16HP THM-A outdoor unit), a smooth transition across the range of compressor frequencies and for eliminating systems.
100%
15%
15Hz Cooling:97HzHeating:102Hz
Heating / Cooling Capacity
Linear CapacityControl
Compressor Frequency
LowStartingCurrents
LowStartingCurrents
City Multi Refrigerant CircuitCondenser
High temperature
Supercooled heat exchanger
Low temperatureElectric expansion valve
Medium temperatureBypass
Electric expansionvalve
Hea
t exc
hang
er
Compressor
Accumulator
Evaporator
Common Refrigerant CircuitCondenser
Expansionvalve
Compressor
Accumulator
Evaporator
Page 5 Page 6
>All the City Multi compressors are inverter-driven type (4~50HP).
-
3.68
Total Energy Conservation
Comparison of COP (energy efficiency) 10HP system
The difference between THM-A and previous Mitsubishi Electric modelsTechnology is key when increased efficiency is demanded. The City Multi THM-A range is able to deliver this in simple ways.
The importance of COP
The THM-A range from Mitsubishi Electric provides precise control of energy input, through utilization of Intelligent Power Module (IPM) technology. Employing this technology it is possible to closely match the building requirements, achieving more accurate control of the occupied space. By using incremental 1Hz steps of capacity control, the amount of power input required is significantly reduced, resulting in greatly improved COPs.
In addition, IPM technology ensures effective performance under part load conditions, a condition that most systems will be in for the majority of the normal working life cycle. By taking account the efficiency at both part load, and peak load conditions, R410A City Multi is designed to provide unbeatable year round/seasonal efficiency.
A highly efficient R410A scroll compressor design results in less friction losses at the motor. A simplified refrigerant circuit (low pressure loss) including new accumulator design also adds a few more points to the efficiency scale. Enhancements to the heat interchange circuit, an inverter driven fan motor and a heat exchanger design again add vital increases to overall system efficiency and COPs.
COP stands for Co-efficient of performance. It is a measure of the useful energy a system can deliver compared to the energy it consumes. It is calculated by dividing the energy output by the energy input of a system. The higher the figure then the more efficient the system is deemed to be, with commensurate reduced running costs. Mitsubishi Electric VRF models, the world's highest energy-efficient ACs, will undoubtedly reduce millions of tons of CO2 emissions.
0R22
2.0
2.5
3.0
3.5
4.0
4.5
5.0
As of September, 2006 (based on internal survey)
Our equivalent product 8 years before
23%Energy Saving
COP
2.85
Page 7 Page 8
I ntelligent Power Module (IPM) Technology
Industry leading high COP (Coefficient of Performance) is realized
IndustryLeaderIndustryLeader
-
For the Environment
History of refrigerantR22, an HCFC-based refrigerant, has been a popular choice for most chillers. R22 has been targeted by the Montreal Protocol to be phased out in new equipment. Additionally, the European Union and other countries governments are enforcing a ban of HCFC-based refrigerants for new installations.
Because of these restrictions, R410A refrigerants is increasingly available. R410A is a blend of HFCs, which do not deplete the ozone but may contribute to global warming.
Technical aspects of refrigerantR410A is a more efficient refrigerant as it has a higher specific heat capacity when compared to R407C or R22. This higher energy carrying capacity allows for smaller pipe sizes, longer pipe runs and reduces the volume of refrigerant within a system. This is a major factor when complying with EN378, a European standard concerning safety and environmental requirements in the design, manufacture, installation, operation, maintenance and disposal or refrigerating systems.
Enhancing environmental care(measures for the RoHS Directive and the refrigerant reduction)Every unit is in compliance with the RoHS Directive,* which stands for the restriction of hazardous substances: Lead-free soldering is used to avoid Lead Groundwater Contamination on the print board. The amount of refrigerant on the unit has also been reduced to enhance environmental care.* RoHS Directive: the restriction of the use of certain hazardous substances in electrical and electronic equipment that has been sold in EU since July 2006
Page 9 Page 10
Efficient R410A refrigerant
-
A Comprehensive City Multi Range
T he City Multi range Solutions for more demanding applications
Product Range Outdoor Units
The City Multi range is Mitsubishi Electrics answer to large scale VRF (Variable Refrigerant Flow) applications. The efficiency of City Multi (in particular the new R410A THM-A Series models) is second to none and offers a substantial increase in energy efficiency and corresponding EER/COP ratings.
The City Multi Y Series range offers a simple and flexible solution where there is a demand for a changeover capability between heating and cooling, ensuring a constant, comfortable indoor climate.It also provides a modular ap-proach to air conditioning re-quirements providing an ideal solution for new build, refurbishment projects and phased installations.With a wide range of 60 indoor units and 13 out-door units, that include single phase 4, 5 and 6HP models, the choice is impressive.
OutdoorUnits
IndoorUnits
Page 11 Page 12
HEAT PUMPCOP
cooling / heating
HEAT PUMPCOP
HEAT PUMPCOP
HEAT PUMPCOP
8HPPUHY-P200THM-A
3.90/4.13
10HPPUHY-P250THM-A
3.41/3.95
12HPPUHY-P300THM-A
3.68/3.98
14HPPUHY-P350THM-A
3.07/3.71
4HPPUMY-P100VHM
3.35/3.42
5HPPUMY-P125VHM
3.24/3.69
6HPPUMY-P140VHM
2.90/3.23
22HPPUHY-P550TSHM-A
3.49/3.73
24HPPUHY-P600TSHM-A
3.15/3.75
26HPPUHY-P650TSHM-A
3.25/3.81
28HPPUHY-P700TSHM-A
3.06/3.70
16HPPUHY-P400THM-A
3.39/4.04
18HPPUHY-P450THM-A
3.06/3.84
20HPPUHY-P500TSHM-A
3.16/3.67
36HPPUHY-P900TSHM-A
3.02/3.94
38HPPUHY-P950TSHM-A
3.50/4.03
40HPPUHY-P1000TSHM-A
3.47/4.00
42HPPUHY-P1050TSHM-A
3.26/3.89
30HPPUHY-P750TSHM-A
3.16/3.83
32HPPUHY-P800TSHM-A
3.03/3.79
34HPPUHY-P850TSHM-A
3.17/4.01
50HPPUHY-P1250TSHM-A
2.97/3.87
44HPPUHY-P1100TSHM-A
3.10/3.85
46HPPUHY-P1150TSHM-A
3.00/3.78
48HPPUHY-P1200TSHM-A
3.07/3.84
-
Due to the compact design of outdoor unit, industry leading space saving is realized. Therefore, the new outdoor unit can be installed more freely than the conventional model.
Page 13 Page 14
The manageability of the outdoor unit has been improved due to drastic reduction in unit weight, leading to easy transportation, installation, and reduction in withstand load.
The downsized outdoor unit can be transported through a 800mm wide door.
Industry leading weight saving is realized.
8-14HP outdoor units
10HP outdoor unit
As of September, 2006 (based on internal survey)
Approx. 230kg Approx. 185kg
Easy to transport
City Multi makes it easy.
Approx. 45kg reduction in weight
The narrow space between buildings makes it difficult to use a crane.
8HP 10HP 12HP 14HP 16HP 18HP 20HP 22HP 24HP 26HP 28HPWeight(kg) 185 185 210 210 240 240 370 395 395 420 420
30HP 32HP 34HP 36HP 38HP 40HP 42HP 44HP 46HP 48HP 50HPWeight(kg) 450 450 480 480 635 635 660 660 660 690 690
800 (31-1/2)
1400 (55-1/8)
850
(33-15
/32)
The unit can easily be transported even into slender buildings.
Depth760
(29-29/32)
mm (in.) mm (in.)
Height1650
(64-31/32)Height1650
(64-31/32)
Width920
(36-7/32)
Compact Design of New Outdoor Unit10(13/32)10(13/32) 10(13/32)10(13/32)
60
IndustryLeaderIndustryLeader
11 (14/32
")11 (14
/32)
Example of 6-people lift.
-
The Strength of City Multi
F eatures and Benefits
Increased Pipe Lengths
New Fan DesignLow Noise Levels
City Multi VRF systems led the introduction of larger single fan rotors some ten years ago, achieving substantially lower noise levels over multiple designs. Continuing the development in the areas of blade shape and weight, Mitsubishi Electric have managed to achieve even higher performance and lower noise levels. To reduce noise levels further and comply with inner city residential noise regulations, all outdoor units include Night Set-back mode. This function works by lowering the fan speed and compressor frequency proportionally with reduction in demand.
Total system pipe lengths of up to 300m(984ft) and furthest pipe lengths of 150m(492ft) make the City Multi Y series system one of the most flexible VRF systems in the market
New inverter driven outdoor fan motor
The compressor compartment is sealed by metal panels to attain a low noise level in all directions.
Newly designed refrigerant circuit (low pressure loss)
Highly efficient R410A Scroll compressor
R410A R22Y Series
Total Pipe Length 300(984) 240(787)
Furthest Piping Length 150(492) 120(393)
LowNoise LowNoise
Low NoiseLow Noise
Furthest piping length 175m[574ft] (equivalent length) (actual length 150m[492ft])
between indoor units top-bottom differential15m[49ft]
Outdoor unit
Indoor unit
Top-bottom differential 50m[164ft]
Y Series
Page 15 Page 16
NewImprovedFigures
NewImprovedFigures
m(ft)
-
The Strength of New City MultiR410A Pipe Sizing
The new models have a smaller foot print and service space requirement than the R22 models.
Operating range in cooling is from an outdoor temperature of -5C[23F], while that in heating has expanded to an outdoor temperature of -20C[-4F]
Heating Operation RangeAt low ambient temperature the guaranteed operating range in heating is now lowered to -20C[68F]
Blue Fin TreatmentThe anti-corrosion Blue Fin treatment of the heat exchanger is especially effective in urban environments where the build up of traffic pollutions can damage the aluminum fins reducing the capacity and life expectancy of the unit. All City Multi R410A outdoor units have been treated in this fashion.
As R410A has a higher specific heat capacity than R22, the pipework is smaller. This means the pipe itself is cheaper, easier to install and therefore less riser space is required within the building.
Conventional
Conventional CITY MULTI
Gaspiping
28.58(1-1/8)
Liquidpiping12.7(1/2)
mm(in.)
Gaspiping22.2(7/8)
Liquidpiping9.52(3/8)
8-14HP systems1.21m2
16/18HP systems1.84m2
50%reduction
-20C[-4F] -10C[14F] 0C[32F] 10C[50F] 20C[68F] 30C[86F] 40C[104F]
In cooling mode
Outdoor temperature(dry bulb temperature)
Outdoor temperature(wet bulb temperature)-20C[-4F]
15.5C[60F]
In heating mode
-5C[-23F]
43C[109F]
Effective Use of Space
Page 17 Page 18
18HP
1.84m2 2.77m2
Based on 10HP model
760(29-29/32)
300(11-26/32)
450(17-23/32)
920 (36-7/32)
1510(59-14/32)
760(29-29/32)
300(11-26/32)
450(17-23/32)
1220 (48-1/32)
1510(59-14/32)
760(29-29/32)
300(11-26/32)
450(17-23/32)
1220 (48-1/32)
1510(59-14/32)
1990 (117-23/32)
840(33-1/18)
100(3-30/32)
450(17-23/32)
mm (in.)
mm (in.)
-
Page 19 Page 20
Remote Controller
Remote Controller
Individual Remote Controller
Centralized Remote Controller
The need for control is paramount in order to optimise the performance of any air conditioning system and minimise its running costs. Mitsubishi Electric offer a wide range of control options designedto do just this.
Operating an air conditioning system without the right control can prove costly. It's therefore important to ensure that every system is correctly specified to the degree of control it requires. Mitsubishi Electric have a wide range of controls available 'off-the-shelf' and where needed, individual control systems can be specifically designed to suit.
Good controls will benefit any application, largeor small. Air conditioning products need toreact to a variety of factors: different room sizes, usage and staff levels; changes in the climate; electronic equipment and lighting ...the list goes on. So whatever the application, optimum control of air conditioning systems is essential and will result in a constant, comfortable environment, which inturn is both energy and cost efficient.
A degree of differenceWhen an air conditioning system is not properly controlled,it will not run as efficiently as it should. For every degree that the system deviates from the required temperature,energy costs can rise by up to 5%. Specify one of the many control options from Mitsubishi Electric to ensure air conditioning works as intended, whilst giving the optimum amount of control.
The simpler, the betterWith the array of comprehensive control systems available from Mitsubishi Electric,it becomes simple to design and install air conditioning systems. From a simple hand heldcontroller to a G50 system - you are in control.
The importance of control
-
Page 21 Page 22
: Each group / Batched : Each group : Block (City Multi indoor unit only) : Batched handling (for maintenance): Batched only : Not available : Not used : G-50A license registration possible.
*3: Interlock setting from local remote controller. *4: From schedule setting *5: When PAC-YT32PTA is connected.*2: Installation possible at Initial setting tool.*1: For group operation, cross-over wring is required between indoor unit.
Integrated Communications Control with Mitsubishi's Unique Transmission Network (M-NET)
Local remote controller System controller
Remote controllerSimpleremote
controller
Wirelessremote
controller
Systemremote
controllerCentralized controller
ON/OFFremote
controller
Start / Stop
Operation mode
Temperature setting
Permit / Prohibit direction
Fan speed
Air flow direction
ON/OFF
Error flashing
Error content
Filter sign
Operating hour
Operation mode
Set temperature
Indoor temperature (intake) Permit / Prohibit
Fan speed
Air flow direction
Weekly
Annual (Designated day setting)One day
Times of stops / Starts per day
Times of stops / Starts per week
Auto off timer
Minimum setting unit (minutes)Error history
Daily / Monthly reports
Electricity charges
Set temperature range limit
Auto lock
Ventilation (group / interlocked)Group setting
Block setting
Revision of electricity charges
Start / Stop
Fan speed
Ventilation mode
Status
Fan speed
Ventilation mode
Ope
ratio
nM
onito
ring
Sche
dulin
gR
ecor
ding
Oth
ers
Cont
rol a
ndm
an
age
men
tVe
ntilat
ion(gr
oup / in
terloc
ked)
Venti
lation
(group
/ inter
locked
)
Ope
ratio
nM
onito
ring
PAR-21MAA
1G/16units 1G/16units 1G/16units 1G/16units 16/5050/50 2000G/2000unitsGB-50A browser50G/50units
PAR-F27MEA PAC-SE/YT51CRA PAR-FL32MAPAR-FA32MA PAC-YT40ANRAPAC-SF44SRA GB-50A
GB-50A browser50G/50units
GB-50A TG-2000A
Model
No. of units controllable(Groups (G) / units)
12
84
/
/
/
/
/
/
/
1
/
/
/
/
/
/
/
12
84
1
3/321/21
/
/
/
/
/
/
10
1/1
/
10
1/1
10
8
56
1
/1*
*2
Scheduletimer
50G/50U
PAC-YT34STA
16
112
5
/
*4
*4
*4
*2
*2
*2
/
/
/
/
/
/
/
12
84
1
*2
*2
*2
*2
/
//
/
*3
/
/
/
/
/
/
*5
Groupremote
controller
8G/16units
PAC-SC30GRA
/48
/
/
/
/
/
/
/
*5
*5
/30
*5*5
*5
*5
/336*5
Remote ControllerRemote Controller
System Controller
MELANSMALANS has a large line-up, including local remote controllers, timers, grouping controllers, central controllers, and centralized integrated software, PLC and its software, as well as BMS interface hardware and software etc. The combination of the MELANS products can fulfill the requirements of small-scaled control system, middle-scaled control system up to 2000 indoor units, and/or large-scaled opening system affiliated to a BMS system. Moreover, with central controller G-50A/GB-50A, PC browser and long distance remote control (monitoring and operating) via net-work is possible and easy.
C entralized Remote ControllerI ndividual Remote Controller
LMAP02 BACnetTM interface softwarePAC-YG31CDA
Interface
MITSUBISHI ELECTRIC's CITYMULTI can be easily connected to the building management system through BACnetTM.
LON WORKSTM transmission line
BACnetTM transmission line
Ethernet Integrated centralized control software TG-2000A
M-N
ET
MITSUBISHI ELECTRIC's Air-conditionaer Network System (MELANS) leads air conditioner management a PC browser and Network era.
System Remote Controller
ScheduleTimer
All of the local remote controllers feature liquid crystal and LED displays and easy to operate.
RemoteController
SimpleRemoteController
WirelessRemote Controller
PAR-F27MEA
PAR-FA32MAPAC-SE51CRAPAC-YT51CRA
PAR-FL32MA
PAR-21MAA
OUTDOOR UNITY :PUHY
INDOOR UNITPLFY-VAMPLFY-VLMDPMFY-VBMPEFY-VMRPEFY-VMSPDFY-VMPEFY-VML
PEFY-VMHPCFY-VGMPKFY-VAM / VGM / VFM PFFY-VLEMPFFY-VLRMFresh Air Intake type
A ir-Conditioning Control System
This is a specialized air condi-tioning management system, in which up to 2000 indoor units can be centrally controlled.
ON/OFFRemote Controller
PAC-YT40ANRAPAC-SF44SRA PAC-YT34STA
G-50A GB-50A
GroupRemote Controller
PAC-SC30GRA
-
Page 23 Page 24
Remote ControllerRemote Controller
Control SystemsIndividual Control Systems
MA remote controller
Non-polarized2-wire
Non-polarized2-wire
MA remote controller
Example of system configuration
M-NET
Wired MA remote controller PAR-21MAA
New display-Larger,easier-to-see characters Dot matrix liquid crystal screen displays complete operating status.
Digital display lets you set temperature in 1C/F increments. Weekly Timer: up to 8 ON/OFF/Temperature Settings can be
made per day. The time can be set in 1-minute increments. Equipped with a thermostat sensor in the remote controller
that makes possible more comfortable room temperature con-trol.
Enables you to select cool/heat/fan operation mode with the indoor remote controller of your choice without using the cool/heat selector.
Ability to limit the set temperature (upper and lower tempera-ture can be set.)
Ability to restrict setting changes (either all changes or all ex-cept ON/OFF)
Constantly monitors for malfunctions in the system, and is equipped with a self-diagnosis function that lets you know by error code immediately when a malfunction occurs.
Dimensions: 100 x 120 x19 mm
Various control systems can be offered with indoor unit remote controller.
Lossnay
Remotecontroller
Remotecontroller
Outdoor unit
Cooling/Heating mode switch control
Remotecontroller
Remotecontroller
Remotecontroller
Remotecontroller
Remotecontroller
Remotecontroller
Cooling/Heating mode of the outdoor unit can be switched with the remote controller for indoor unit.
Two-remote-controllercontrolBy connecting with two re-mote controllers, an outdoor unit can be controlled freely either from the one in the room or from the one in the control room. (Last setting override) Group control is possible by using two remote controllers.
Remote controlRemote controller wiring can be extended up to 200m, which makes it possible for the indoor unit remote controllers to be instal-led at one place without being separated.
Interlocking controlTotal enthalpy heat exchanger (Lossnay) can be operated and controlled with in-door unit remote controller. Cleaning time for an air wash unit is displayed on the controller when the unit is connected.
Group controlA remote controller can control up to 16 indoor units at the same time.(Automatic address setting)
Dot liquid crystal display Display example [Operation mode]
Display example [Cool mode]
ON/OFF TEMP.
F F
TIME SUN
WEEKLYSIMPLE
AUTO OFF
[Japanese]
[Russian][English]
[Itarian]
[German]
[Chinese]
[Spanish]
[French]
Various information is displayed and conveyed clearly, enabling more accurate operation of the air conditioner.
Dot Liquid Crystal Display (LCD)The dot liquid crystal display enables quick under-standing of the operation state.
Multi-language DisplayIn addition to English, contents can be displayed in sev-en other languages.This function makes the remote controller very useful in fa-cilities where foreigners are present.
Multi Language Display Example
-
Page 25 Page 26
PAC-SE51CRA
PAR-FL32MA PAR-FA32MA
Simple remote controller PAC-SE51CRA(M-NET) / PAC-YT51CRA(MA)
Wireless remote controller PAR-FL32MA / PAR-FA32MA
Remote ControllerRemote Controller
Wired ME remote controller PAR-F27MEA
Example of system configuration
Example of system configuration
Example of system configuration
This remote control requires that wiring is connected to only one outdoor unit.
Group operation with multiple outdoor units is possible. Grouping can be changed freely, which makes dividing rooms for tenant easier.
Daily timerRepeated ON / OFF timer every day.
Auto OFF timer0:30, 1:00, 1:30, 2:00...4:00 one touch timer.
Function lockAll functions or all functions except ON / OFF can be selected.
Limit setting of room temperature. Dimensions:130 x 120 x 19 mm
No need to configure addresses for group operation. Lit LED keeps you informed of operation - blinking even
gives you the error code via the number of blinks. Can be used with the MA remote controller.
*When used in group configurations, wiring between indoor units is required.
*Combining ME remote controller and/or LOSSNAY remote-controller in a group is not possible.
Optional LCD temperature setting and display in 1C /1F unit.
Dimensions:153 x 57 x 18 mm
Control: START/STOP, room temperature and fan speed The only wiring required is cross-over wiring based on
two-wire signal lines. Room temperature sensors are built-in. LCD temperature setting and display in 1C /1F unit. Can operate all types of indoor units
*Since this system has no operation mode switching, test op-eration, self-diagnosis or interlock setting functions, it should always be used in conjunction with the PAR-21MAA or other centralized controller.
*Combining ME remote controller and/or LOSSNAY remotecontroller in a group is not possible.
Dimensions:120 x 70 x 41 mm
Control SystemsIndividual Control Systems
ME R/C ME R/C
UP
Central controller
Power supply unit
SimpleMA R/C
SimpleMA R/C
Signal receiving unit
Signal receiving unit
Non-polarized2-wire
Non-polarized2-wire
Non-polarized2-wire
Wireless remote controller
Wireless remote controller
Signal receiving unit
Wireless remote controller
-
Page 27 Page 28
CentralizedRemote Controller
System exampleSystem example
Systemremote
controller
R / C : Remote Comtroller R / C : Remote Comtroller
PZ-52SFPZ-52SF
LOSSNAY
Power supplyunit
LOSSNAYLOSSNAY
PAR-21MAA PAR-21MAA
UP
Systemremote
controller
Schedule timer
Power supplyunit
Simple PAC-SE51CRA
PAR-F27MEA
PAR-21MAA
LOSSNAY UP
System remote controller PAC-SF44SRA Schedule timer PAC-YT34STA
Remote ControllerRemote Controller
FUNCTIONUNITS
ON/OFF
MODE SELECTION
TEMPERATURE SETTING
FAN SPEED SETTINGS
AIR FLOW DIRECTION
PERMIT/PROHIBIT FUNCTION
INDOOR RETURN AIR TEMPERATURE
ERROR INDICATION
VENTILATION INTERLOCK
EXTERNAL INPUT
EXTERNAL OUTPUT
DESCRIPTION PAC-SF44SRA50 units/50 groupMax No.Units
Run and stop operationSwitches between Cool/Dry/Auto/Fan/Heat.Operation Mode will vary depending on the indoor unit. Auto mode is available with only R2 and WR2 systemsSets the groups temperature control.Cool/Dry:19-30CHeat:17-28CAuto:19-28C4 speed - Lo-Mi1-Mi2-Hi2 speed - Lo-HiAir Flow angles:100-80-60-40 and auto swingRun/Stop,Temperature Setting,Mode Selection and Filter Reset functions can be prohibited via a higher level system controllerMeasures the intake temperature of the master unit within the group Displays a 4 digit code and the affected unit addressAllows the group to be interlocked with a heat recovery Lossnay unitHardwired connections available
Hardwired connections available
One system controller is available for use when you need to control up to fifty indoor units from one location. The PAC-SF44SRA also has hardwired connection available (On/Off input, fire alarm input, run output, fault output).
Mitsubishi Electric controllers are complimented by a weekly programmable timer, being able to control up to fifty indoor units. The PAC-YT34STA also has hardwired connection available (On/Off input, fire alarm input, run output, fault output).
System ControllerFUNCTIONUNITS
ON/OFF
MODE SELECTION
TEMPERATURE SETTING
CURRENT TIME
ERROR INDICATION
EXTERNAL INPUT
EXTERNAL OUTPUT
DESCRIPTION PAC-YT34STA50 units/50 groupMax No.Units
Run and stop operationSwitches between Cool/Dry/Auto/Fan/Heat.Operation Mode will vary depending on the indoor unit. Auto mode is available with only R2 and WR2 systemsSets the groups temperature control.Cool/Dry:19-30CHeat:17-28CAuto:19-28CSet the timeDisplays a 4 digit code and the affected unit addressHardwired connections available
Hardwired connections available
Programmable Timer
Displays
On/Off/Fire AlarmOn/Off/Faults
Operation Operation Displays
On/Off/Fire AlarmOn/Off/Faults
Dimensions:130 x 120 x 19 mm
Dimensions:130 x 120 x 19 mm
-
System example
Page 29 Page 30
ON/OFFremote
controller
LOSSNAY
PZ-52SF
PAC-YT51CRA
PAR-F27MEA
PAR-21MAA
ON/OFF remote controller PAC-YT40ANRA Group remote controller PAC-SC30GRA
Remote ControllerRemote Controller
CentralizedRemote Controller
System exampleConnect to the centralized transmission line
R/C:Remote Controller
UP
Power supply unit
Group remotecontroller
PAR-21MAA PAR-21MAA
Connect to the indoor/outdoor transmission line
Group remotecontroller
PAR-21MAA PAR-21MAAR/C:Remote Controller
FUNCTIONON/OFFOPERATION MODE SWITCHINGTEMPERATURE SETTINGFAN SPEED SETTINGAIR FLOW DIRECTION SETTINGMANUAL OPERATION PROHIBIT/PERMIT(ON/OFF, OPERATION MODE, SETTING TEMPERATURE, FILTER RESET)SPECIFIC MODE OPERATION PROHIBIT(COOLING PROHIBIT, HEATING PROHIBIT, COOLING/HEATING PROHIBIT)ROOM TEMPERATURE DISPLAY
ERROR DISPLAY
SCHEDULE OPERATIONVENTILATION OPERATION(INDEPENDENT)
VENTILATION OPERATION(INTERLOCKED)
EXTERNAL OUTPUT(ERROR OUTPUT, OPERATION OUTPUT)
CONNECTION POSITION
DESCRIPTIONRun and stop operation for the air conditioner unitsNot availableNot availableNot availableNot available
Compatible only with external input.
Not available
Not availableLED flashes during failure.(The error code can be confirmed by removing the cover.)Not availableGroup operation of only LOSSNAY units possible.*Only ON/OFF of group.The LOSSNAY will run in interlock with the operation of indoor unit.*The fan rate and mode cannot be changed. The LED will turn ON only during operation after interlocking."ON/OFF" and "error/normal" are output with the level signal.*The optional output cable is required.
Indoor/outdoor transmission line: ConnectableCentral system transmission line: Connectable (Power supply unit (PAC-SC50KUA) is needed.)
OPERATIONS DISPLAY
Just press a switch to start. All of the units can be started stopped by pressing the main switch, and each unit in the group can be started stopped with individual switched.
Up to 8 groups can be operated (maximum of 16 units/. Just by pressing RAC-SC30GRA switches, groups can be started and stopped as a batch.
Dimensions:130 x 120 x 19 mm
Dimensions:130 x 120 x 19 mm
FUNCTIONUNITS
ON/OFF
MODESELECTION
TEMPERATURE SETTING
FAN SPEED SETTINGS
AIR FLOW DIRECTION
PERMIT/PROHIBIT FUNCTION
INDOOR RETURN AIR TEMPERATURE
ERROR INDICATION
VENTILATION INTERLOCK
DESCRIPTIONMax No.Units
Run and stop operationSwitches betweenCool/Dry/Auto/Fan/Heat.Operation Mode will vary depending on theindoor unit. Auto mode is available with only R2 and WR2 systemsSets the groups temperaturecontrol.Cool/Dry:19-30CHeat:17-28CAuto:19-28C4 speed - Lo-Mi1-Mi2-Hi2 speed - Lo-HiAir Flow angles: 100-80-60-40 and auto swingRun/Stop,Temperature Setting,Mode Selectionand Filter Reset functions can be prohibitedvia a higher level system controllerMeasures the intake temperature of themaster unit within the groupDisplays a 4 digit code and the affectedunit addressAllows the group to be interlocked with a heatrecovery Lossnay unit
PAC-SC30GRA
OPERATIONS16 units/ 8 group
DISPLAY
-
Page 31 Page 32
Remote ControllerRemote Controller
System Structure
Public telephoneline
Router
Ethernet City Multi
M-NET
Remote monitoring via aWeb browser
Web browser
City Multi
M-NET
Provider
Provider
Operation
Example of display icons (air conditioner icons)
Stop
Occurrence of abnormality
Operation/Occurrence of a filter sign
In timer operation
Lossnay on
Under energy-saving control
Up to 50 units of packaged air conditioners can free-ly be monitored and operated! Furthermore, it has enabled the Monitoring and Op-eration Via a Web Browser on a Personal Computer connected to it using a LAN or telephone line!
First in the industryWith Web Server Functions!
* Microsoft is a trademark or trademark of Microsoft corporation.
Simple and FlexibleThis new generation controller is suitable for small to large systems with simple to complex functions available.
Web BrowserEnables monitoring and operation of air conditioning units us-ing a PC with Microsoft Internet Explorer.
Remote AccessAllows users to remotely monitor and operate the air condi-tioning units using a PC connected to a telephone line.
Auto AlarmIn the case of any malfunction, necessary information will be sent to a mobile phone and/or personal computer by e-mail.
Easy to UpgradeVarious new functions will be introduced gradually and can easily be down loaded into any existing G-50A/GB-50A.
Example: Energy MonitoringDemand ControlAnnual Schedule
G-50A (with display)
GB-50A
Central controller G-50A/GB-50A
FUNCTION
G50 Centralised Controller
G50 Software OptionsG50 - Saving EnergyG50 - Peak CutG50 - Personal WebG50 - BacNet
Energy Saving CapabilityPeak Cut ControlVirtual Remote ControllersBacnet interface
DESCRIPTION
Up to 50 indoor units can be connectedRun and Stop operation for a single groupSwitches between Cool/Dry/Auto/Fan/Heat.Operation Mode will vary depending on the indoor unit.Auto modeis available with only R2 and WR2 systemsSets the groups temperature control.Cool/Dry:19-30C,Heat:17-28C,Auto:19-28C4 speed:Lo-Mi1-Mi2-Hi,2 speed:Lo-HiAir Flow angles:100-80-60-40 and auto swingMaximum of 3 time sequences with 3 Start/Stop times per day for all groups can be allocatedIndividual prohibit operations for each remote controller function (Run/Stop, Temperature Setting,Mode Selection and Filter Reset) can be activatedDisplays the measured intake temperature from each group
Displays a 4 digit code and the affected unit address.An error log is held showing the last 64 date stamped alarmsAllows each unit within the group to operate in test modeAllows the group to be interlocked with a heat recovery Lossnay unitReduce the setpoint band of each individual unit (exp.23C to 25C)Automatically switch heat pump outdoor unit to cooling or heating mode depending on the requirementsCommission the G50 from the web pagesTwo types of login available (Administrator & Guest).Administrator able to allow specific function access to guestHardwired connections are available for : Inputs: Level Signal-Batch Start/Stop,Batch Emergency Stop
Pulse Signal-Batch Start/Stop,Enable/Disable Local R/COutputs: Start/Stop Status,Error/Normal Status
PAC-SC50KUA
G50 -Web MonitorG50 - Email G50 - ScheduleG50 - Change
Control and Monitor the G50 via Internet Explorer 5 or 6Enable E-mail activation on fault conditionsWeekly / Annual Scheduling and Night Set BackEnergy Charge
MAX No.OFINDOOR UNITSON/OFFMODE SELECTION
TEMPERATURE SETTINGFAN SPEED SETTINGAIR FLOW DIRECTIONTIMER OPERATIONPERMIT/PROHIBIT FUNCTION
INDOOR RETURN AIR TEMPERATUREERROR INDICATIONTEST RUN FUNCTIONVENTILATION INTERLOCKWEB SETPOINTLIMITWEB AUTOCHANGEOVERWEB INITIALSETTINGWEB LOGINEXTERNAL INPUT/OUTPUT
POWER SUPPLY UNIT
CentralizedRemote Controller
Power supply unit PAC-SC50KUA
UP
POWER RATING
MODEL
WEIGHTSERIAL No.
2.11kg
POWER SUPPLY UNIT
MITSUBISHI ELECTRIC CORPORATION
PAC-SC50KUA
Power supply unit PAC-SC50KUA
UP
POWER RATING
MODEL
WEIGHTSERIAL No.
2.11kg
POWER SUPPLY UNIT
MITSUBISHI ELECTRIC CORPORATION
PAC-SC50KUA
-
Page 33 Page 34
Integrated centralized control software TG-2000A
123
4
5
678
Charge license
Web monitorlicense
Schedulelicense
Input G-50A12VDC
M-NET
Example of Basic System Configuration. Main features of TG-2000A
Power supply unit PAC-SC50KUA
3-phase 208/230V(3-wire)
RS-232CRS-485
Indoor unit system watt-hour meter
Outdoor unit system watt-hour meter
Uninterruptive power supply (UPS)
Integrated centralized controlsoftware installation
Central controller personal computerTG-2000A
Indoor unit watt-hour meter
Single-phase 208/230V
Single-phase 208/230V
power sourceIndoor unit system
watt-hour meter
Outdoor unit system watt-hour meter
PLC (with electric amount count software)
Uninterruptible power supply (UPS)
Integrated centralized controlsoftware installation
Central control personal computerTG-2000A
Indoor unit watt-hour meter
Converter
Compatible with TG-2000A Ver. 4.10 and higher * The electric amount count software or separately procured parts must be used with the designated PLC.
The TG-2000A can realize the following functions using the G-50A/GB-50A option (license).* Operation/monitor* Annual/weekly schedule* Charge* Energy saving *1* Peak cut *1*1: Compatible with TG-2000A Ver. 4.10 and higher,
G-50A Ver. 2.51 or later.
UP
POWER RATING
MODEL
WEIGHTSERIAL No.
2.11kg
POWER SUPPLY UNIT
MITSUBISHI ELECTRIC CORPORATION
PAC-SC50KUA
Remote ControllerRemote Controller
CentralizedRemote Controller
Up to 2000 indoor units (40 G-50A/GB-50A units) can be operated and monitored simultaneously.The air-conditioner layout can be displayed on the screen, making control and operation easier.The annual and weekly schedules can be set. Two schedules, such as the summer master and winter master, can be saved in the weekly schedule.Air-conditioning charges can be calculated based on the multiple air-conditioner usage results. The power apportionment percentage data and apportioned power rate can be calculated for each indoor unit using the power apportionment function, and can be output as a CSV format file. * Power apportionment charging is not possible with the old model, A control or K control.
Charging without WHM : The user manually inputs the power rate to calculate the air-conditioning charges. (Using a tool)
RS-485 WHM charging : The RS-485 WHM value is automatically tabulated to calculate theair-conditioning charges.
PLC + pulse WHM charging : The pulse output WHM value is automatically tabulated by the PLC to calculate the air-conditioning charges.
Energy saving operation is possible using the "ON/OFF", "set temperature change", "fan operation changeover" and "performance save operation (60% to 90%)" functions.Energy saving operation matching the amount of power in use is possible by using the PLC's electric amount count software.Night set-back operation is possible with schedule settings. *1*4General equipment can be operated and monitored. *2General equipment can be schedule-controlled when using PAC-YG21CDA with PLC.For details of PLC refer to Installation Manual of PAC-YG21CDA. *3
*1: Compatible with TG-2000A Ver. 4.10 and higher, G-50A Ver. 2.51 and higher.*2: Compatible with TG-2000A Ver. 4.30 and higher, G-50A Ver. 2.51 and higher.*3: Compatible with TG-2000A Ver. 4.60 and higher, G-50A Ver. 2.70 and higher.*4: With Night Set-Back function,the CITY MULTI system can run at heating mode with target temperature set
to 12C/54Funder schedule control. This function can protect the room from dropping down to extremelylow temperature at mid-night.
-
Page 35 Page 36
M-NET
Example of System ConfigurationSystem design made simple through integration ofvarious devices into a total control configuration.
Outdoor unit
M-NET LON WORKS(78kdps)
208-230V60Hz
Remotecontroller
Indoor units
Remotecontroller
Indoor units
Remotecontroller
Indoor units
Remotecontroller
Indoor units
Remotecontroller
Lighting
SecurityCenter control device
CITY MULTI System
Outdoor unit
Indoor unitsMax. 50 indoor units
LON WORKSThe building management system is connected to the CITY MULTI air conditioning system using LON WORKS , which is widely used on field networks, allowing for an open network and savings in construction to face.
LON WORKSProtocol converterbetween LON WORKSand M-NET
LONWORKS (LMAP02) BACnet TM interface(PAC-YG31CDA)
Example of Basic System Configuration.
LAN
G-50A
Centralmonitor
BMS
TG-2000A(Optional)
Web Browser(Optional)
BACnet interface softwarePAC-YG31CDA
G-50A
M-NET
M-NET
PAC-SC50KUAPower supply unit
WHMWHM
TM
TMBACnet
LON, LON WORKS and the Echelon logo are trademarks of Echelon Corporation registered in the United States and other countries.
CITY MULTI can easily combine into a Building Management System (BMS) via the LonWorksTM and M-NET adapter LMAP02. LonWorksTM is an opened transmission protocol widely used at BMS, and related equipment control.CITY MULTI is therefore compatible with large-scaled BMS management via LonWorksTM.
One LM ADAPTER unit can connect up to 50 Groups/50 indoor units.Using a single LONWORKS adapter (LM ADAPTER), you can connect up to a maximum of 50 indoor units.
MITSUBISHI ELECTRIC's CITYMULTI can be easily connect to the building management system through BACnetTM. BACnetTM is the appropriate transmission method and used in many of the backbone networks and also it is easy to combine with other equipment corresponding to BACnetTM.
One BACnetTM interface software manages up to 500 Groups/500 Indoor units. (10 G-50A/GB-50A units).
Remote ControllerRemote Controller
FUNCTION NETWORK VARIABLE NETWORK VARIABLE
Run/StopCooling/Drying/Heating/Auto/FanCooling 19-30C,Heating 17-28C,Auto 19-28CLo-Mi1-Mi2-HiOn/Off,Mode,SetpointNormal/Reset
Run/StopCooling/Drying/Heating/Auto/FanCooling 19-30C,Heating 17-28C,Auto 19-28CLo-Mi1-Mi2-HiOn/Off,Mode,Setpoint4 Character code - Indicates all unit alarms-
-
-
ON/OFFMODE OPERATIONSETPOINT ADJUSTMENTFAN SPEED CONTROLPERMIT / PROHIBITFILTER DIRTY RESET
ON/OFFMODE OPERATIONSETPOINT ADJUSTMENTFAN SPEED CONTROLPERMIT / PROHIBITFAULT CODEFILTER SIGNROOM TEMPERATURETHERMO
LONWORKS INTERFACE
Control
Monitoring
FUNCTION NETWORK VARIABLE NETWORK VARIABLE
Run/StopCooling/Drying/Heating/Auto/FanCooling 19-30C,Heating 17-28C,Auto 19-28CLo-Mi1-Mi2-HiOn/Off,Mode,SetpointNormal/Reset
Run/StopCooling/Drying/Heating/Auto/FanCooling 19-30C,Heating 17-28C,Auto 19-28CLo-Mi1-Mi2-HiOn/Off,Mode,SetpointHorizontal - 60-80-100 swing4 Character code - Indicates all unit alarms-
-
ON/OFFMODE OPERATIONSETPOINT ADJUSTMENTFAN SPEED CONTROLPERMIT / PROHIBITFILTER DIRTY RESET
ON/OFFMODE OPERATIONSETPOINT ADJUSTMENTFAN SPEED CONTROLPERMIT / PROHIBITAIRFLOW DIRECTIONFAULT CODEFILTER SIGNROOM TEMPERATURE
BACnet INTERFACE
Control
Monitoring
-
Page 37 Page 38
Indoor unit
I ndoor unit
Ceiling cassette type 4-way airflow Ceiling cassette type 2-way airflow Ceiling cassette type 1-way airflow Ceiling concealed typeCeiling suspended typeWall mounted typeFloor standing type
Ceiling cassette (4way air flow)
Ceiling concealed
Ceiling cassette (2way air flow)
Ceiling cassette (1way air flow)
Ceiling suspended
Wall mounted
Floor standing
PKFY-P VAM-EPKFY-P VGM-EPKFY-P VFM-E
PFFY-P VLEM-E
PDFY-P VM-E
PEFY-P VMR-E-L/R
PLFY-P VAM-E
PFFY-P VLRM-E
Model
CapacityP20 P25 P32 P40 P50
2.2kW 2.8kW 3.6kW 4.5kW 5.6kW
Model
CapacityP63 P80 P100 P125
7.1kW 9.0kW 11.2kW 14.0kW
Model
CapacityP20 P25 P32 P40 P50
2.2kW 2.8kW 3.6kW 4.5kW 5.6kW
Model
CapacityP63 P71 P80 P100 P125
7.1kW 8.0kW 9.0kW 11.2kW 14.0kW
Model
CapacityP20 P25 P32 P40 P50 P63 P71
2.2kW 2.8kW 3.6kW 4.5kW 5.6kW 7.1kW 8.0kW
Model
CapacityP80 P100 P125 P140 P200 P250
9.0kW 11.2kW 14.0kW 16.0kW 22.4kW 28.0kW
Model
CapacityP20 P25 P32 P40 P50 P63 P100
2.2kW 2.8kW 3.6kW 4.5kW 5.6kW 7.1kW 11.2kW
Model
CapacityP20 P25 P32 P40 P50 P63
2.2kW 2.8kW 3.6kW 4.5kW 5.6kW 7.1kW
Model
CapacityP20 P25 P32 P40
2.2kW 2.8kW 3.6kW 4.5kW
Model
CapacityP80 P140 P200 P250
9.0kW 16.0kW 22.4kW 28.0kW
Model
CapacityP40 P63 P100 P125
4.5kW 7.1kW 11.2kW 14.0kW
OA Processing Units
PEFY-P VML-E
PEFY-P VMH-EPEFY-P VMS-E
PEFY-P VMH-E-F
PLFY-P VLMD-E
PMFY-P VBM-E
PCFY-P VGM-E
Fresh Air Intake
Page39 - Page40 Page55 - Page56
Page41 - Page42 Page57 - Page58
Page43 - Page44 Page59 - Page60
Page45 - Page54 Page61 - Page62
-
Page 39 Page 40
SpecificationsIndoor unit
4-, 3-, or 2-way outlet selection
Fixed airflow direction per vane
Motorfor the vane
*Optional air outlet shutter plate is necessary for two-or three-way airflow settings. The noise level may increase during two- or three-way airflow setup.
72 airflow patterns
850mm(33-1/2in.)
INDOOR UNITCeiling cassette type4-way airflow
The new power cassette VAM offers 72 different airflow patterns, making it ideal for applications with ceilings up to 4.2 m(13-13/16ft) in height.
Drain water pipe lifted to 850mm(33-1/2in.)
The 72 different airflow patterns provide the best solution for varying room layouts and air-conditioning requirements. For ex-tra versatility, you can also select from two-, three- or four-way outlets. What's more, the addition of separate motors to the in-dividual vanes enables manual control that-together with re-mote control vane settings-make possible highly customized and flexible airflow patterns.
First in the industry to offer 72 airflow patterns
Easy Installation
Superb Features
Specifications according to ceiling height and number of vents
4-way3-way2-way
Power Cassette VAMStandard High ceiling 1 High ceiling 2
3.23.64.0
3.64.04.2
4.24.2---
4.2(13-13/16)
4-way high ceiling 2
3.6(11-13/16)
m (ft)
3-way standard
3.2(10-1/2)
4-way standard
The airflow of the VAM power cassette is powerful enough to warm atrium-type ceilings up to 4.2 m(13-13/16ft) in height.
Wide-flow air outlet delivers a comforting breeze
Outstanding Specifications
Specifications
Note:
PLFY-P32VAM-E PLFY-P40VAM-E PLFY-P50VAM-E PLFY-P63VAM-E
3.612,300
3.73,1504.0
3,40013,6000.120.120.590.59
4.515,400
4.74,0005.0
4,30017,100
5.619,100
5.85,0006.3
5,40021,500
7.124,200
7.36,3008.0
6,90027,3000.160.160.780.78
Power source
Cooling capacity
Heating capacity
Powerconsumption
Current
External finish(Munsel No.)Dimension H W D
Net weightHeat exchanger
Fan
Motor
Air filter
Refrigerantpipe diameter
Drain pipe diameterNoise level (Lo-Mid2-Mid1-Hi) 3 4
Type
Airflow rate(Low-Mid2-Mid1-High) External static pressureTypeOutput
Gas(Flare)Liquid(Flare)
0.140.140.680.68
22 (49)
Turbo fan11-12-13-14 12-13-14-16
12.7 (1/2)
14-15-16-18
Single phase induction motor
6.35 (1/4) 9.52 (3/8)O.D. 32 (1-1/4)
27-28-29-31 27-28-30-32 28-29-31-33
12.7 (1/2) / 15.88 (5/8)(Compatible)
6.35 (1/4) / 9.52 (3/8)(Compatible)
258 840 84010-3/16 33-1/8 33-1/8 11-3/4 33-1/8 33-1/8
kWBTU/h
kWkcal/h
kWkcal/hBTU/h
kWkWAA
mm
in.kg(lbs.)
m3/minL/scfmPa
kW
mm(in.)
mm(in.)mm(in.)dB(A)
1122111
3
3
3
PLFY-P80VAM-E PLFY-P100VAM-E PLFY-P125VAM-E
9.030,700
9.38,00010.0
8,60034,1000.180.180.860.86
11.238,20011.6
10,00012.5
10,80042,7000.300.301.431.43
14.047,800
14.512,500
16.013,80054,600
0.340.341.641.64
Panel : 0.70Y 8.59/0.97
24 (53)Cross fin (Aluminum plate fin and copper tube)
16-18-20-22
15.88(5/8)
0
0.070 0.120PP Honeycomb
30-32-35-37
32 (71)
19-22-25-27 21-24-27-29183-200-217-233388-424-459-494
200-217-233-267424-459-494-565
233-250-267-300494-530-565-636
267-300-333-367565-636-706-777
317-367-417-450671-777-883-953
350-400-450-483742-848-953-1024
33-36-39-41 35-38-41-43
15.88 (5/8) / 19.05 (3/4) (Compatible)
298 (30) 840 (950) 840 (950)
~ 220-240V 50Hz / ~ 220-230V 60Hz
CoolingHeatingCoolingHeating
1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.Cooling : Indoor 27C(80.6F)DB/19C(66.2F)WB,Outdoor 35C(95F)DBHeating : Indoor 20C(68F)DB,Outdoor 7C(44.6F)DB/6C(42.8F)WB
2 Cooling capacity indicates the maximum value at operation under the following conditionCooling : Indoor 27C(80.6F)DB/19.5C(67.1F)WB,Outdoor 35C(95F)DB.Heating : Indoor 21C(69.8F)DB,Outdoor 7C(44.6F)DB/6C(42.8F)WB
3 External dimension/ net weight are shown in , and airflow rate/noise level are in (low-middle2-middle1-high).4 It is measured in anechoic room.
-
Page 41 Page 42
Specifications
Specifications
Note:
INDOOR UNITCeiling cassette type2-way airflow
Fresh air can be taken in to the main unit directly (optional ac-cessories needed.
The drain can be positioned anywhere up to 600mm(23-5/8in.) from the ceiling's surface, providing greater freedom with long cross-piping and allowing more versatility with piping layouts.
Equipped with drain water lift-up mechanism as standard
Terminal block on outside of main unit makes wiring easier
Newly designed decorative panel with air flow switching and swing functions as a standard feature
Compact unit and low noise level attained! Fresh air directly taken in
The slimline body is highly suitable for installation in narrow ceiling spaces and for replacing obsolete air-conditioning equipment in older buildings. The main unit is only 290mm(11-7/16in.) height.
Slim body - only 290mm(11-7/16in.) height
Ceiling surface
Drain heightmax. 593(23-3/8)
Main unit height - 290(11-7/16)
593
(11-7/16in.)
Slim body of 290mm(11-7/16in.) height.
1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.Cooling : Indoor 27C(80.6F)DB/19C(66.2F)WB,Outdoor 35C(95F)DBHeating : Indoor 20C(68F)DB,Outdoor 7C(44.6F)DB/6C(42.8F)WB
2 Cooling capacity indicates the maximum value at operation under the following condition.Cooling : Indoor 27C(80.6F)DB/19.5C(97.1F)WB,Outdoor 35C(95F)DB Heating : Indoor 21C(69.8F)DB,Outdoor 7C(44.6F)DB/6C(42.8F)WB
3 The figure in < > indicates panel's
4 It is measured in anechoic room.
mm (in.)
Indoor unit
PLFY-P20VLMD-E PLFY-P25VLMD-E PLFY-P32VLMD-E PLFY-P40VLMD-E~ 220-240V 50Hz / ~ 220-230V 60Hz
Unit: Galvanizing Decoration Panel: ABS (0.7Y 8.59/0.97) Service Panel: Galvanizing (0.7Y 8.59/0.97)290 776 634
11-7/16 30-9/16 2523 (51)
Cross finTurbo fan 1
0Single phase induction motor
0.015PP honeycomb fabric (long life filter)
12.7 (1/2)6.35 (1/4)
O.D.32 (1-1/4)
6.5-8.0-9.5108-133-158230-283-335
7.0-8.5-10.5117-142-175247-300-371
24 (53)
2.27,5002.3
2,0002.5
2,2008,500
0.072 / 0.0750.065 / 0.0690.36 / 0.370.30 / 0.32
2.89,6002.9
2,5003.2
2,80010,900
0.072 / 0.0750.065 / 0.0690.36 / 0.370.30 / 0.32
3.612,300
3.73,1504.0
3,40013,600
0.072 / 0.0750.065 / 0.0690.36 / 0.370.30 / 0.32
4.515,400
4.74,000
5.04,30017,100
0.081 / 0.0850.074 / 0.079
0.40 / 0.420.34 / 0.37
27-30-3328-31-34
29-33-3630-34-37
kWBTU/h
kWkcal/h
kWkcal/hBTU/h
kWkWAA
mm
in.kg(lbs.)
m3/minL/scfmPa
kW
mm(in.)mm(in.)mm(in.)dB(A)dB(A)
1122111
3
3
CoolingHeatingCoolingHeating
Type
Airflow rate (Lo-Mid-Hi)External static pressureTypeOutput
Gas(Flare)Liquid(Flare)
4220V,240V230V
kWBTU/h
kWkcal/h
kWkcal/hBTU/h
kWkWAA
mm
in.kg(lbs.)
m3/minL/scfmPa
kW
mm(in.)
mm(in.)mm(in.)dB(A)dB(A)
1122111
3
3
CoolingHeatingCoolingHeating
TypeAirflow rate(P50~P100:Lo-Mid-Hi)(P125:Lo-Mid2-Mid1-Hi)External static pressureTypeOutput
Gas(Flare)Liquid(Flare)
4220V,240V230V
PLFY-P63VLMD-E PLFY-P80VLMD-E PLFY-P100VLMD-E PLFY-P125VLMD-E~ 220-240V 50Hz / ~ 220-230V 60Hz
Unit: Galvanizing Decoration Panel: ABS (0.7Y 8.59 / 0.97) Service Panel: Galvanizing (0.7Y 8.59 / 0.97)
Turbo fan 1 Turbo fan 2
15.88 (5/8)
9.52 (3/8)
10.0-13.0-15.5167-217-258353-459-547
17.5-21.0-25.0292-350-417618-742-883
0.030 (at 240V)
15.5-18.5-22.0258-308-367547-653-777
0Single phase induction motor
0.020 (at 240V)0.020
7.124,200
7.36,3008.0
6,90027,300
0.101 / 0.1050.094 / 0.0990.49 / 0.510.43 / 0.46
28 (62)
9.030,700
9.38,00010.0
8,60034,100
0.147 / 0.1560.140 / 0.1500.72 / 0.740.66 / 0.69
44 (98)Cross fin
11.238,20011.6
10,00012.5
10,80042,700
0.157 / 0.1860.150 / 0.1800.75 / 0.880.69 / 0.83
47 (104)
14.047,800
14.512,500
16.013,80054,600
0.28 / 0.280.27 / 0.271.35 / 1.351.33 / 1.33
290 1,708 60611-7/16 67-1/4 23-7/8< 28>
56 (124)
Sirocco fan 424.0-27.0-30.0-33.0
400-450-500-550848-953-1,059-1,165
0.078 2 (at 240V)Synthetic fiber unwoven
cloth filter (long life)
O.D.32 (1-1/4)33-36-3934-37-40
PLFY-P50VLMD-E
PP honeycomb fabric (long life filter)
5.619,100
5.85,0006.3
5,40021,500
0.082 / 0.0860.075 / 0.0800.41 / 0.430.35 / 0.38
27 (60)
31-34-3732-35-38
32-37-3933-38-40
40-42-44-46(Lo-Mid2-Mid1-Hi)
15.88 (5/8)12.7 (1/2)
6.35 (1/4)
36-39-4237-41-43
290 946 63411-7/16 37-1/4 25< 28>
290 1,446 63411-7/16 56-15/16 25< 28>
9.0-11.0-12.5150-183-208318-388-441
Power source
Cooling capacity
Heating capacity
Powerconsumption
Current
External finish
Dimension H W D
Net weightHeat exchanger
Fan
Motor
Air filterRefrigerantpipe diameterDrain pipe diameterNoise level(Lo-Mid-Hi)
Power source
Cooling capacity
Heating capacity
Powerconsumption
Current
External finish
Dimension H W D
Net weightHeat exchanger
Fan
Motor
Air filter
Refrigerantpipe diameter
Drain pipe diameterNoise level(Lo-Mid-Hi)
-
Page 43 Page 44
Specifications
Specifications
Note:
1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.Cooling : Indoor 27C(80.6F)DB/19C(66.2F)WB,Outdoor 35C(95F)DBHeating : Indoor 20C(68F)DB,Outdoor 7C(44.6F)DB/6C(42.8F)WB
2 Cooling capacity indicates the maximum value at operation under the following condition.Cooling : Indoor 27C(80.6F)DB/19.5C(67.1F)WB,Outdoor 35C(95F)DBHeating : Indoor 21C(69.8F)DB,Outdoor 7C(44.6F)DB/6C(42.8F)WB
3 External dimension / net weight are shown in , and airflow rate/noise level are in (low-middle2-middle1-high).4 It is measured in anechoic room.
mm (in.)
198(7-13/16)PMFY-VBM
230(9-11/16)
max.402
(15-7/8)max.600
(23-5/8)
Compact and lightweight body perfect for limited ceiling space applications.
Unit body size has been standardized for all models at 854mm for easier installa-tion. Body weight is only 14kg for the main unit and 3kg for the panel, making this unit one of the lightest in the industry.
Compact size for smooth installation and maintenance
Newly developed airflow control technolo-gy reduces noise level to only 27dB (P20VBM) for industry-leading quiet oper-ation.
Quiet operation
The drain can be positioned anywhere up to 600mm(23-5/8in.) from the ceiling's surface.Drain lift-up mechanism
INDOOR UNITCeiling cassette type1-way airflow
Indoor unit
Power source
Cooling capacity
Heating capacity
Powerconsumption
Current
External finishDimension H W DNet weightHeat exchanger
Fan
Motor
Air filterRefrigerantpipe diameterDrain pipe diameterNoise level (Lo-Mid2-Mid1-Hi)
0.0440.0440.210.21
Panel : 0.98Y8.99/0.63230 812 395 (9-1/16 32 15-9/16)
14 (31)Cross fin (Aluminum plate fin and copper tube)
Line flow fan 17.3-8.0-8.6-9.3
122-133-143-155258-283-304-328
0Single phase induction motor
0.028PP Honeycomb fabric
12.7 (1/2)6.35 (1/4)
O.D. 25 (1) 32-34-36-37
4.515,400
4.74,000
5.04,30017,1000.0540.0540.260.26
7.7-8.7-9.7-10.7128-145-162-178272-307-343-378
33-35-37-39
kWBTU/h
kWkcal/h
kWkcal/hBTU/h
kWkWAA
mm(in.)kg(lbs.)
m3/minL/scfmPa
kW
mm(in.)mm(in.)mm(in.)dB(A)
Type
Airflow rate(Low-Mid2-Mid1-High)External staticpressureTypeOutput
CoolingHeatingCoolingHeating
1122111
3
3
3
4
Gas(Flare)Liquid(Flare)
2.89,6002.9
2,5003.2
2,80010,900
2.27,5002.3
2,0002.5
2,2008,5000.0420.0420.200.20
3.612,300
3.73,1504.0
3,40013,600
~ 220-240V 50Hz / ~ 220V 60Hz
6.5-7.2-8.0-8.7108-120-133-145230-254-283-307
27-30-33-35
PMFY-P25VBM-E PMFY-P32VBM-E PMFY-P40VBM-EPMFY-P20VBM-E
-
Page 45 Page 46
Specifications
INDOOR UNITCeiling concealedtype
Prepared a contact for a card key. Its possible to operate / stop by taking a card key in and out.
Realizing the low level noise that is NC21 around a bed and N22 around a desk when the high notch.It contributes to create a quiet indoor environment.*Outlet is elbow-constructed using a glass wool duct.The noise level is changed by the room size or the setting con-dition of the unit.
Operable by card key switch Ultra low noise
Energy-saving by prevention of forgetting the switch off
Enables to install for symmetric design room
Both of Left piping / Right piping, control box, are available.It's selectable for layout of each room.Plus easy maintenance from the access door in the prefabrica-ted bath.*Seen from an anterior view, the pipe and control box are on the right side of R type.
Compact & Simple operation remote controller is available.*This remote controller can operate only start / stop, indoor tem-perature control and wind speed control. Centralized remote controller must be used together.Enables a prevention to forget the switch in a vacant room off by the centralized remote controller like G-50.
Problem solver for residential hotels, museums, libraries, or hospitals where low noise is especially a must!
Noise measurement pointNoise measurement pointNoise measurement pointCard KeySwitchCard KeySwitch
InletInlet
Noise measurement pointNoise measurement pointNoise measurement point
*According to the data measured in Mitsubishi Electric laboratory
Indoor unit
Specifications
Note:
1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.Cooling : Indoor 27C (81F) DB/19C (66F) WB, Outdoor 35C (95F) DBHeating : Indoor 20C (68F) DB, Outdoor 7C (45F) DB/6C (43F) WB
2 Cooling capacity indicates the maximum value at operation under the following condition.Cooling : Indoor 27C (80.6F) DB/19.5C (67.1F) WB,Outdoor 35C (95F) DB Heating : Indoor 21C (69.8F) DB,Outdoor 7C (44.6F) DB/6C (42.8F) WB
3 The external static pressure is set to 100Pa (at 220V) / 150Pa (at 230, 240V) at factory shipment.4 Measured in anechoic room. Noise levels of the unit with a rear air inlet. (Noise levels are higher than the unit with a bottom air inlet.)
Static Presure5Pa
Width640mm
25-6/32in.
Ultra Low Noise
Piping connectionL modelR model
0.018 0.023
Power source
Cooling capacity
Heating capacity
Powerconsumption
Current
External finish
Dimension H W D
Net weightHeat exchanger
Fan
Motor
Air filter
Refrigerantpipe diameter
Drain pipe diameter
Noise level (Lo-Mid-Hi)
4
Gas(Flare)Liquid(Flare)
220V230V240V
TypeAirflow rate(Lo-Mid2-Mid1-Hi)External staticpressureTypeOutput
CoolingHeatingCoolingHeating
kWBTU/h
kWkcal/h
kWkcal/hBTU/h
kWkWAA
mm
in.kg(lbs.)
m3/min
Pa
kW
mm(in.)
mm(in.)mm(in.)
dB(A)
1122111
3
3
1-phase 220/230/240V 50Hz 220/230V 60Hz2.8
9,6002.9
2,5003.2
2,80010,900
0.06 / 0.060.06 / 0.060.29 / 0.290.29 / 0.29Galvanized
292 640 580-
18 (40)Cross fin (Aluminum fin and copper tube)
Sirocco fan 1
PEFY-P20VMR-E-L PEFY-P25VMR-E-L PEFY-P32VMR-E-L
2.27,5002.3
2,0002.5
2,2008,500
0.06 / 0.060.06 / 0.060.29 / 0.290.29 / 0.29
3.612,300
3.73,150
4.03,40013,600
0.07 / 0.080.07 / 0.080.34 / 0.380.34 / 0.38
5
1-phase induction motor
PP Honeycomb fabric (washable)6.35 (1/4)
12.7(1/2)O.D. 26 (1)
4.8-5.8-7.9 4.8-5.8-9.3
20-25-3021-26-3222-27-30
20-25-3321-26-3522-27-33
0.018 0.023
Power source
Cooling capacity
Heating capacity
Powerconsumption
Current
External finish
Dimension H W D
Net weightHeat exchanger
Fan
Motor
Air filter
Refrigerantpipe diameter
Drain pipe diameter
Noise level (Lo-Mid-Hi)
4
Gas(Flare)Liquid(Flare)
220V230V240V
TypeAirflow rate(Lo-Mid2-Mid1-Hi)External staticpressureTypeOutput
CoolingHeatingCoolingHeating
kWBTU/h
kWkcal/h
kWkcal/hBTU/h
kWkWAA
mm
in.kg(lbs.)
m3/min
Pa
kW
mm(in.)
mm(in.)mm(in.)
dB(A)
1122111
3
3
1-phase 220/230/240 V 50Hz 220/230V 60Hz2.8
9,6002.9
2,5003.2
2,80010,900
0.06 / 0.060.06 / 0.060.29 / 0.290.29 / 0.29Galvanized
292 640 580-
18 (40)Cross fin (Aluminum fin and copper tube)
Sirocco fan 1
PEFY-P20VMR-E-R PEFY-P25VMR-E-R PEFY-P32VMR-E-R
2.27,5002.3
2,0002.5
2,2008,500
0.06 / 0.060.06 / 0.060.29 / 0.290.29 / 0.29
3.612,300
3.73,150
4.03,40013,600
0.07 / 0.080.07 / 0.080.34 / 0.380.34 / 0.38
5
1-phase induction motor
PP Honeycomb fabric (washable)6.35 (1/4)
12.7 (1/2) O.D. 26(1)
4.8-5.8-7.9 4.8-5.8-9.3
20-25-3021-26-3222-27-30
20-25-3321-26-3522-27-33
-
Page 47 Page 48
Specifications
Specifications
Note:
1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.Cooling : Indoor : 27CD.B./19CW.B. (81FD.B. / 66FW.B.) Outdoor : 35CD.B. (95FD.B. )Heating : Indoor : 20CD.B. (68FD.B.) Outdoor : 7CD.B. / 6CW.B. (45FD.B. / 43FW.B.)
Pipe length : 7.5m (24-9/16ft) Height difference : 0m (0ft) 2 Cooling Indoor: 27C(80.6F)DB/19.5C(67.1F)WB, Outdoor: 35C(95F)DB
Heating Indoor: 21C(69.8F)DB, Outdoor: 7C(44.6F)DB/6C(42.8F)WB3 The external static pressure is set to 15 Pa at factory shipment.
Increased design flexibility for the places where low noise operation is especially needed from an ultra thin body.
Changeable static pressure(4 stage 5-15-35-50Pa)
Can be installed easily in tight spaces, such as ceiling cavities or drop-ceilings.
Ultra low height unit with 200mm (7-28/32in.) high
INDOOR UNITCeiling concealedtype
Changeable air flow rate (3 stage low-middle-high)
Drain lift-up pump is attached as standard.
Filter is attached as standard.
Reduced noise thanks to the use of newly designed centrifugal fan and coil
dB(A)Noise level table (Standard static pressure)
Mor
e th
an 2
0mm
Mor
e th
an 2
0mm
Make the access door at the appointed position properlyfor service maintenance.
Ceiling surface Access door
P20272522
Capacity P25272522
P32302825
Noise Level HighMidLow
Fan Speed
Indoor unit
Static Presure5~50Pa
Height200mm
7-28/32in.
Width900mm
35-14/32in.Low Noise
0.080.39
2.27,5002.3
2,0002.5
2,2008,500
0.060.28
0.080.39
0.060.28
0.090.44
0.070.33
0.110.53
0.090.42
0.130.63
0.110.52
0.140.68
0.120.57
kWBTU/h
kWkcal/h
kWkcal/hBTU/h
kWA
Pa
kWm3/min
mm
In. kg
mm(in.)mm(in.)mm(in.)dB
Power source
Cooling capacity
Heating capacity
Power input Current
Fan 3
External finish External dimension H W D Net weight
Drain piping diameter Noise level (Lo-Mid-Hi) (mesured in anechoic room) Air filter Heat exchanger
Type Quantity External static press Motor type Motor output Airflow rate(Lo-Mid-Hi)
Liquid Gas
1-phase 220-240V 50Hz 1-phase 220-230V 60Hz
5-15-35-50DC brushless motor
0.096
Galvanized200 900 700
7-7/8 35-7/16 27-9/16
O.D. 32 (1-1/4)
PP Honeycomb fabric (washable)Cross fin (Aluminium fin and copper tube)
3.612,300
3.73,1504.0
3,40013,600
Sirocco fan 3
7.5-8.5-10
25-28-30
6.35 (1/4) Brazed12.7 (1/2) Brazed
2.89,6002.9
2,5003.2
2,80010,900
23 24
4.55.04.7
4,0005.0
4,30017,100
8-9.5-11
28-30-33
5.66.35.8
5,0006.3
5,40021,500
9.5-11-13
6.35 (1/4) Brazed12.7 (1/2) Brazed
30-32-35
6-7-8
22-25-27
7.18.07.3
6,3008.0
6,90027,300
Sirocco fan 4
12-14-16.5
200 1100 7007-7/8 43-5/16 27-9/16
289.52 (3/8) Brazed15.88 (5/8) Brazed
30-33-36
PEFY-P20VMS-E PEFY-P25VMS-E PEFY-P32VMS-E PEFY-P50VMS-EPEFY-P40VMS-E PEFY-P63VMS-E
1122111
Refrigerant piping diameter
-
Page 49 Page 50
Specifications
Specifications
Note:
Cooling/heating capacity indicates the maximum value at operation under the following condition.
1 Cooling Indoor: 27C(80.6F)DB/19C(66.2F)WB, Outdoor: 35C(95F)DBHeating Indoor: 20C(68F)DB, Outdoor: 7C(44.6F)DB/6C(42.8F)WB
2 Cooling Indoor: 27C(80.6F)DB/19.5C(67.1F)WB, Outdoor: 35C(95F)DBHeating Indoor: 21C(69.8F)DB, Outdoor: 7C(44.6F)DB/6C(42.8F)WB
3 The external static pressure is set to 50Pa at factory shipment.
4 The value for Models 20-80 are that at the external static pressure of 100Pa, while the value for Models 100-125 are that at the external static pressure of 130Pa.
5 The figure in ( ) indicates noise level at 240V/50Hz.6 It is measured in anechoic room.
Long room
L-shaped roomsRoom with fixed ceiling fixtures
Max.600
(23-5/8)
110-300
(4-3/8~11-13/16)
mm (in.)
Maintenance panelwith air intake Maintenance panel
with air intake
Canvas duct forbottom section
A rear intake canalso be used
Maintenance panelMaintenance panel
Square duct flange Rear intake filter box
A bottom intake canalso be used
Rear intake filter box
System ceiling
Square duct flange
Blower unit(With auto-vanes)
Maintenancepanel withair intake
INDOOR UNITCeiling Concealed Type
Achieving creative air conditioning design through a rich array of system materials.
Multiple installation patterns for assorted applications and locationsAir outlet side compatible with a variety of ducts (optional)
Slim 295mm main unit with optional drain up mechanism ensures
up to 600 mm(23-5/8in.) of lift
Adjustable setting of external static pressure to meet system configuration
and installation conditions
Static pressure settings can be increased to adjust to all kinds of ducts as well as functional upgrade option (high perfor-mance filter etc). An increase from the standard 50Pa to 130 Pa is possible to cope with various layout configurations.*For P100~P125
Flexible installation for a variety of layouts
Indoor unit
Max.416(16-7/16)
184(16-7/16)
Bottom intake (using canvas duct)
Ceiling chamber system (1)
Hanging ceiling installation
Bottom intake (directly attached to panel)
All-duct system
Ceiling chamber system (2)
Static Presure30~100(130)Pa
Gas(Flare)Liquid(Flare)
TypeAirflow rate(Lo-Mid2-Mid1-Hi)External staticpressureTypeOutput
CoolingHeatingCoolingHeating
kWBTU/h
kWkcal/h
kWBTU/h
kWkcal/h
kWkWAA
mm
in.kg(lbs)
m3/min
Pa
kW
mm(in.)
mm(in.)mm(in.)dB(A)
Power source
Cooling capacity
Heating capacity
Power consumption(50/60Hz)Current
External finish
Dimension H W D
Net weightHeat exchanger
Fan
Motor
Air filter
Refrigerantpipe diameter
Drain pipe diameterNoise level (Lo-Mid2-Mid1-Hi) 6
0.13 / 0.150.13 / 0.150.60 / 0.710.60 / 0.71
295 960 73511-5/8 37-13/16 28-15/16
Sirocco fan 2
10.0-11.0-12.5-14.0
34-36-37-39
2.27,5002.3
2,0002.5
8,5002.6
2,250
2.89,6002.9
2,5003.2
10,9003.3
2,8000.11 / 0.120.11 / 0.120.53 / 0.580.53 / 0.58
295 710 73511-5/8 28 28-15/16
Sirocco fan 1
6.0-6.5-7.5-8.5
28-30-33-36
25.5 (57)
12.7 (1/2)
6.35 (1/4)
12.7 (1/2)
6.35 (1/4)
~ 220-240V 50Hz / ~ 220V 60Hz3.6
12,3003.7
3,1504.0
13,6004.1
3,550
Galvanizing
27 (60)Cross fin (Aluminum plate fin and copper tube)
30 / 50 / 100
Single phase induction motor0.075 (at 240V)
Synthethic fiber unwoven cloth filter (long life)
O.D. 32 (1-1/4)
5.619,100
5.85,000
6.321,500
6.55,600
34 (75)
4.515,400
4.74,0005.0
17,1005.2
4,500
32 (71)
11221122
3
45
Gas(Flare)Liquid(Flare)
TypeAirflow rate(Lo-Mid2-Mid1-Hi)External staticpressureTypeOutput
CoolingHeatingCoolingHeating
kWBTU/h
kWkcal/h
kWBTU/h
kWkcal/h
kWkWAA
mm
in.kg(lbs)
m3/min
Pa
kW
mm(in.)
mm(in.)mm(in.)dB(A)
Power source
Cooling capacity
Heating capacity
Powerconsumption
Current
External finish
Dimension H W D
Net weightHeat exchanger
Fan
Motor
Air filter
Refrigerantpipe diameter
Drain pipe diameterNoise level (Lo-Mid2-Mid1-Hi) 6
7.124,200
7.36,3008.0
27,3008.3
7,1000.14 / 0.170.14 / 0.170.68 / 0.820.68 / 0.82
12.5-14.0-16.0-18.0
30-34-36-39
8.027,300
8.37,1009.0
30,7009.3
8,0000.15 / 0.180.15 / 0.180.72 / 0.880.72 / 0.88
295 1,160 73511-5/8 45-11/16 28-15/16
39 (86)
13.5-15.5-17.5-19.5
30 / 50 / 100
0.078 (at 240V)
15.88 (5/8)
32-35-37-40
~ 220-240V 50Hz / ~ 220V 60Hz9.0
30,7009.3
8,00010.0
34,10010.5
9,0000.17 / 0.210.17 / 0.210.82 / 1.010.82 / 1.01Galvanizing
Cross fin (Aluminum plate fin and copper tube)Sirocco fan 2
14.5-16.5-18.5-21.0
Single phase induction motor
Synthethic fiber unwoven cloth filter (long life)
9.52 (3/8)O.D. 32 (1-1/4)
34-37-40-42
14.047,800
14.512,500
16.054,600
16.314,000
0.33-0.38 / 0.390.33-0.38 / 0.391.55-1.63 / 1.841.55-1.63 / 1.84
24.0-34.0(Lo-Hi)
0.190 (at 240V)
40-45 (42-46) 5
11.238,20011.6
10,00012.5
42,70013.0
11,2000.27-0.31 / 0.290.27-0.31 / 0.291.28-1.34 / 1.361.28-1.34 / 1.36
19.5-28.0(Lo-Hi)
0.140 (at 240V)
34-42 (37-44) 5
335 1,510 77513-1/4 59-1/2 30-9/16
52 (115)
50 / 100 / 130
15.88 (5/8)
11221122
3
4
PDFY-P20VM-E PDFY-P25VM-E PDFY-P32VM-E PDFY-P40VM-E PDFY-P50VM-E
PDFY-P63VM-E PDFY-P71VM-E PDFY-P80VM-E PDFY-P100VM-E PDFY-P125VM-E
-
Page 51 Page 52
Specifications
Specifications
Note: In the case of bottom inlet, the operating noise is louder than in the case of rear inlet.
Hole pitch
Access door
20/25/32 Model
100(3-15/16) or more
225(8-7/8)
30(1-3/16)
mm (in.)
20(13/16) or more
Service space:500(19-11/16) or more
245(9-11/16)+Drain covering configurationheight
P20362925
Capacity P25362925
P32402925
NoiseLevel
dB(A)Noise level table
HighMidLow
FanSpeed
Increased design flexibility for hotel and residential use from an thin body.
Reduced noise thanks to the use of newly designed centrifugal fan
Drainage lines may be connected on either the right or left side.
Low static pressure (5Pa) meets an application requiring direct air flow
Changeable air flow rate (3 stage low-middle-high)
Flexible installation by rear or bottom return air inlet.
Perfect for use in hotels and other places where line placement is a problem.
Filter is attached as standard.
Can be installed easily in tight spaces, such as ceiling cavities or drop-ceilings.Notes: Drain lift-up pump not applicable.
Low height unit with 225mm(8-7/8in.) high
Indoor unit
Note:
Cooling/heating capacity indicates the maximum value at operation under the following condition.
1 Cooling/heating capacity indicates the maximum value at operation under the following condition.Cooling Indoor: 27C(80.6F)DB/19C(66.2F)WB, Outdoor: 35C(95F)DBHeating Indoor: 20C(68F)DB, Outdoor: 7C(44.6F)DB/6C(42.8F)WB
2 Cooling capacity indicates the maximum value at operation under the following condition.Cooling Indoor: 27C(80.6F)DB/19.5C(67.1F)WB, Outdoor: 35C(95F)DBHeating Indoor: 21C(69.8F)DB, Outdoor: 7C(44.6F)DB/6C(42.8F)WB
3 The external static pressure is set to 100Pa (at 220V) /150Pa (at 230, 240V) at factory shipment. 4 The value are that at 240V.
5 It is measured in anechoic room.
Static Presure5Pa
Width720mm
28-11/32in.
Power source
Cooling capacity
Heating capacity
Power consumption(50/60Hz)Current
External finish
Dimension H W D
Net weightHeat exchanger
Fan
Motor
Air filter
Refrigerantpipe diameter
Drain pipe diameterNoise level (Lo-Mid-Hi) 5
Gas(Brazing)Liquid(Brazing)
Type
Airflow rate(Lo-Mid-Hi)External static pressureTypeOutput
CoolingHeatingCoolingHeating
kWBTU/h
kWkcal/h
kWkcal/hBTU/h
kWkWAA
mm
in.kg(lbs.)
m3/minL/scfmPa
kW
mm(in.)
mm(in.)
dB(A)
1122111
PEFY-P20VML-E PEFY-P25VML-E PEFY-P32VML-E
2.27,5002.3
2,0002.5
2,2008,500
~ 220-240V 50Hz / 60Hz2.8
9,6002.9
2,5003.2
2,80010,900
Galvanizing225 720 550
8-7/8 28-3/8 21-11/1618 (40)
Cross fin (Aluminum plate fin and copper tube)Sirocco fan 1
5Single phase induction motor
PP Honeycomb fabric (washable)12.7 (1/2)
6.35 (1/4)R1 (External thread)
0.05 / 0.060.05 / 0.060.24 / 0.280.24 / 0.28
3.612,300
3.73,150
4.03,40013,600
0.07 / 0.090.07 / 0.090.32 / 0.420.32 / 0.42
4.8-5.8-9.580-97-158
170-205-335
0.032
25-29-40
0.023
25-29-36
4.8-5.8-7.980-97-132
170-205-279
-
Page 53 Page 54
Specifications
Specifications
Note:
Capacity P503427
P633832
P71
3932
P8041
35
P10042
34
P125
42
34
P14042
34
NoiseLevel
dB(A)Noise level table (Standard static pressure 220V)
High
Low
P403427
Externalstatic
pressure(Pa)
220V230/240V
380V400/415V
P40 P50 P63 P71
50/100/200100/150/200
110/220130/260
P80 P100 P125 P140 P200 P250
MAX.550
(21-11/16)
222(8-3/4)
328(12-15/16)
Increased design flexibility from sufficient external static pressure allow authentic duct air- conditioning with an elegant interior layout.
Maximum external static pressure 200Pa
Reduced noise thanks to the use ofnewly designed centrifugal fan
The additional external static pressure capacity provides flexibility for duct extension, branching and air outlet configuration.
Drain up mechanism (option) ensures up to 550mm (21-11/16in.) of lift
The introduction of an upper drain mechanism allows the drain con-nection to be raised as high as 550mm(21-11/16in.), allowing more freedom in piping layout design and reducing horizontal piping re-quirements.
All maintenance to the unit, includ-ing fan inspection and fan motor removal, can be conducted from the inspection opening on one side.
One-side maintenance
FanSpeed
Indoor unit
Cooling/heating capacity indicates the maximum value at operation under the following condition.1 Cooling Indoor: 27C(80.6F)DB/19C(66.2F)WB, Outdoor: 35C(95F)DB
Heating Indoor: 20C(68F)DB, Outdoor: 7C(44.6F)DB/6C(42.8F)WB2 Cooling Indoor: 27C(80.6F)DB/19.5C(67.1F)WB, Outdoor: 35C(95F)DB
Heating Indoor: 21C(69.8F)DB, Outdoor: 7C(44.6F)DB/6C(42.8F)WB3 The external static pressure is set to 100Pa (at 220V) /150Pa (at 230, 240V) at factory shipment. 4 The value are that at 240V.5 The external static pressure is set to 220Pa (at 380V) /260Pa (at 400, 415V) at factory shipment.6 The value are that at 415V.7 It is measured in anechoic room.4 The value are that at 240V.5 The external static pressure is set to 220Pa (at 380V) /260Pa (at 400, 415V) at factory shipment.6 The value are that at 415V.7 It is measured in anechoic room.
mm (in.)
Static Presure100~200(260)Pa
Power source
Cooling capacity
Heating capacity
Power consumption(50/60Hz)Current
External finish
Dimension H W D
Net weightHeat exchanger
Fan
Motor
Air filter (option)
Refrigerantpipe diameter
Drain pipe diameterNoise level (Lo-Hi) 5
Gas(Brazing)Liquid(Brazing)
220V230,240V
220V230,240V
Type
Airflow rate(Lo-Hi)External staticpressure 3TypeOutput
CoolingHeatingCoolingHeating
kWBTU/h
kWkcal/h
kWkcal/hBTU/h
kWkWAA
mm
in.kg(lbs.)
m3/minL/scfmPaPa
kW
mm(in.)
mm(in.)mm(in.)dB(A)dB(A)
1122111
4
PEFY-P40VMH-E PEFY-P50VMH-E PEFY-P63VMH-E PEFY-P71VMH-E PEFY-P80VMH-E PEFY-P100VMH-E PEFY-P125VMH-E PEFY-P140VMH-E
4.515,400
4.74,0005.0
4,30017,100
44 (98)
12.7 (1/2)
6.35 (1/4)
5.619,100
5.85,0006.3
5,40021,500
380 750 90015 29-9/16 35-7/16
12.7 (1/2)
6.35(1/4)
7.124,200
7.36,3008.0
6,90027,300
0.24 / 0.300.24 / 0.301.12 / 1.381.12 / 1.38
Sirocco fan 113.5-19.0225-317477-671
0.12
32-3836-41
8.027,300
8.37,1009.0
7,70030,700
0.26 / 0.330.26 / 0.331.20 / 1.511.20 / 1.51
15.5-22.0258-367547-777
0.14
15.88 (5/8)
32-3935-41
9.030,700
9.38,00010.0
8,60034,100
0.32 / 0.400.32 / 0.401.47 / 1.831.47 / 1.83
18.0-25.0300-417636-883
0.18
35-4138-43
11.238,20011.6
10,00012.5
10,80042,700
14.047,800
14.512,500
16.013,80054,600
380 1,200 90015 47-1/4 35-7/16
70 (155)
Sirocco fan 2
0.26
15.88 (5/8)
34-4238-44
16.054,600
16.314,000
18.014,00061,400
0.48 / 0.590.48 / 0.592.35 / 2.702.35 / 2.70
28.0-40.0467-667989-1413
0.48 / 0.580.48 / 0.582.34 / 2.662.34 / 2.66
26.5-38.0442-633
936-1342
O.D. 32 (1-1/4)
Galvanizing380 1,000 900
15 39-3/8 35-7/1650 (111)
Cross fin (Aluminum plate fin and copper tube)
50 / 100 /200100 / 150 / 200
Single phase induction motor
Synthethic fiber unwoven cloth filter (long life)
0.19 / 0.230.19 / 0.230.88 / 1.060.88 / 1.06
10.0-14.0167-233353-494
0.08
27-3431-37
45 (100)
O.D. 32 (1-1/4)9.52 (3/8)
kWBTU/h
kWkcal/h
kWkcal/hBTU/h
kWkWAA
mm
in.kg(lbs.)
m3/minL/scfmPaPa
kW
mm(in.)
mm(in.)mm(in.)dB(A)dB(A)
PEFY-P200VMH-E PEFY-P250VMH-E
~ 220-240V 50Hz / 60Hz
Power source
Cooling capacity