case study-iii - class 4 examclass4exam.com/books/12. case study-ii… · ppt file · web view ·...
Post on 22-May-2018
216 Views
Preview:
TRANSCRIPT
CASE STUDY-IIIBOILER TUBE FAILURE
The IncidentBoiler Make: MIURADate: March 26, 2010Place: At sea Initial Indication: Frequent water being taken
into hotwell indicating Boiler High Water Consumption and Boiler Feed pump running frequently
Boiler Furnace checked through peephole, found slight water accumulation inside the furnace
Confirmation: Boiler burner and swirler unit removed, found
few tubes on Stbd aft leaking and steam leaking in the form of a jet
Action: Main Engine and Boiler stopped, 6 Nos. leaky
tubes plugged by ship staff
Repeat of the Incident Date: April 11, 2010 Place: At Port Initial Indication: Frequent water being taken into hot well indicating Boiler High Water Consumption and Boiler Feed pump running frequently Boiler Furnace checked through peephole, found slight water accumulation inside the furnace Confirmation: Boiler burner and swirler unit removed. Found 3 major tube leakages and 27 minor tube leakages and steam leaking in the form of a jet Action: Boiler stopped. 30 Nos. leaky tubes plugged by ship staff
Immediate Causes Identified ROOT CAUSE: Failure to monitor Boiler water conditionINDIRECT CAUSES:Failure to take proper rounds in Engine RoomFailure in daily monitoring of Cascade tank water quality, Failure in daily Monitoring of Observation tank on Deck Failure to test Cargo tank heating Coil at Regular intervals
Design problemsCascade tank was not fitted with Oil Detecting Sensor or Salinity Sensor to warn operatorsPoor material of Plate heaters --- Cracking of plate damages boiler water very fast & by the time, Duty Engineer realizes, Oily Water enters BoilerMiura Boiler load might reach 100% at High Combustion ModeBurner has O-rings which require renewal every year Leaky Burner can cause Violent Combustion – leading to tube burn out
Operational & Maintenance Problems
Lack of interest to protect MachineryLack of motivation and complacency
by ship staffUn-Controlled Dumping of excess
Steam in Drain Cooler – leading to tube leakage
Burner never pressure tested “OR” Replaced every Year
Cargo Tank Heating Coil not tested at regular interval
Solutions Attached problem did not happen over-night but over long period of time Daily Visual Check & Testing of Cascade
tank Water, observation tank and gauge glass will give indication
Beyond Doubt, C/E or none of the Duty Engrs or Oilers took regular thorough Rounds of Machinery Space C/E to witness Boiler water test once every week Please maintain firing of Boiler at Low Combustion mode, which is good enough for fulfilling Steam requirement onboard including cargo heating Replacement of Burner every year on exchange basis
Burst water wall tubes in the furnace
Burst wall tubes and plugged tubes with color changed
Horizontal cracks were located in the water tubes of low area
Top view of the water tubes in the furnace room
Deposits in the burst tubes internally (Near bottom tube plate)
Water tubes internal viewing
Take care of your Boilers well!