Be faster than your competitorTwo men were doing jogging exercise in a forest. Suddenlythey were frightened to hear roar of a lion and soon theyfound him coming after them. One of the men startedrunning fast. “Whatever you do”, said the other man, “youcannot run faster than the lion!”. “May be, but at least I canrun faster than you!” replied the running man, furtheraccelerating his speed.
We cannot be the fastest in the world, but we have to move faster than at least ourcompetitor, otherwise we will be the looser.
Without hard work,no one has been
eversucceeded in the
world yet.
Field Case Study
Digital excitation andcontrol system
DECS-150
OemAutomation solutions
Amtech Electronics (India) Limited conducted seminar, on"Variable Frequency Drives and Energy Conservation" atM/s Mecon Consultants, New Delhi.
Energy savingin Bag filter fan
TRAINING CALENDAR
2018
2018
2018
2018
2018
2018
2018
2018
2018
2019
2019
2019
19-20
22-23
25-26
26-27
22-23
24-25
24-25
21-22
24-25
23-24
22-23
22-23
3
FIELD CASE STUDY
Industry : Carbon maker
Application : Process blower
This case study indicates what happens due to not doing proper wiring as per standard engineering practice.
During commissioning of one Axpert-Eazy VFD, 690 V, 12 Pulse Variable Frequency Drive (VFD) a seriousproblem was reported. VFD was tripping with over current even when motor is running in no load condition.
What was the problem?
The full load current of the Motor was 526 Amps. Customer had taken two 240 SQ MM armored aluminium.cables. Each cable had 3 cores and an armor of stainless steel. Each core from both the cable shorted togetherand connected to VFD at one end and motor at other end. The armor was connected to cable glands at both theends - fixed to VFD panel at one end and motor frame at other end.
As soon as motor was energized on VFD, even at no load, current was about 185 Amps, VFD got trippedimmediately with over current fault, Engineer checked motor insulation, motor cable insulation and VFD, whichwas found OK. After checking everything, it was decided to call an expert.
An expert from senior team of Amtech was consulted. He checked the drive thoroughly and found everythingOK. Trial was taken after removing the motor, keeping only motor cable connected. VFD again tripped with overcurrent. Same observation was found even after connecting any one cable instead of two cables.
Then armor was isolated from the motor ( Very heavy rusting was found at gland connected to motor end) anddrive panel and the drive was started and was found working OK.
Checked the voltage at the cable gland and drive panel earth, it was found to be 180 V , The lamp wasACconnected across these two points, it was glowing, indicating that voltage was not a floating voltage.
Finally it was concluded that this problem occurred due to different earth potentials, because of poor contactwith earth due to rusting.
Separate three & half core cable connected, earth is connected at both the ends, now drive is working ok.
Morale:
Before the drive is started, proper earthing is to be ensured, rather than suspecting VFD.
DOC. NO. CS-268TITLE: ENERGY SAVING IN BAG FILTER FAN
Payback Period Approximately = 6 Months
Industry : ementC
Application : Bag filter fan
Motor rating : AC Induction Motor, 3 Phase-
75kW :
415V :olt
7514RPM :
50Hz :
131A :mp
Previous system : Motor was running on DOLstarter.
Problem observed : 1) High maintenance cost.
.2) Energy losses due to flow control by damper
Present system : kW75 Axpert-Eazy Variable Frequency Drive used.
kW (Consumption) Damper Position
Previous system
(Without drive) : kW % Open52 85
Present system
(With drive ) : kW 100 % Open38
System block diagram :
Merits of new system : 1. Easy & mooth perations o .
2. Energy Saving due to flow control by VFD.
Economical analysis :
�Energy consumption without VFD- P1 = kW52
�Energy consumption with VFD - P2 = kW38
�Energy aving er ay ((P1-P2) 24) = Units.s p d x 336
�Saving er ay @ Rs.4/- Unit = Rs /-p d . 1344
�Saving er ear (Approx. 300 Days) = Rs /-p y . 4,03,200
75 kW, 3-PHASEINDUCTION MOTOR
AXPERT-EAZY
3-PHASE,
415 V,
AC SUPPLY
75 kWBAG FILTER FAN
AMTECH POWER VISION
5
TITLE: Digital excitation and control system DECS-150
Features:
General
A microprocessor based, high performance, digital excitation system ( )DECS-150provides required excitation to the exciter field of a synchronous generator. Thedigital excitation system provides controls, limiters and protection for the generator asoutlined below. The uses PC software to monitor,DECS-150 BESTCOM Plus®control and program the controlled parameters of the excitation system.
Inputs and outputs:
� 63 V DC and 125 V DC @10ADC pulse width modulated (PWM) Output
� 1-phase or 3-phase voltage sensing with nominal inputs of 120 V AC, 240 V AC,480 VAC, and 600 VAC
� 1-phase or 3-phase current sensing with nominal inputs of 1A AC or 5A AC
� Eight (8) fully programmable digital inputs
� Three (3) output contacts, two (2) of which will be fully programmable, capable ofmaking, breaking and carrying 7A
� Single or three phase power input accepting an input of 100 VAC to 277 VAC at 50Hz to 500 Hz from generator line, PMG, or auxiliary winding
Control features:
� with at least ± 0.25% from no load to full loadAutomatic voltage regulator mode
� Integrated manual field current regulator mode
� Integrated var/power factor controller mode
� PIDAdjustments •Auto tuning • Parallel Operation • Reactive droop operation
� Line Drop Compensation
Additional features and functions:
� Automatic voltage matching to the bus voltage when being paralleled
� Bump-less transfer between active and inactive modes of operation
� Integrated power system stabilizer (optional)
� Allow for up to three (3) preposition settings
Limiter functions:
• Over excitation limiting • Under excitation limiting • Stator current limiting • Under frequency
Protection :
• Loss of sensing • Generator over voltage • Generator under voltage • Generator over frequency
• Generator under frequency • Exciter field over voltage • Exciter diode open detection • Exciter diode short detection
• User programmable protection • Syn-check protection • Generator frequency less than 10 Hertz • Configurable protection
PC software:
Set up via PC using BESTCOM Plus software and integrated PLC for customizable logic
Password protection
Communication:
USB type B port (front or rear panel optional) Ethernet: RJ45 jack (rear panel) 10 BASE-T/100BASE-TX (copper)
Diagnostics and event recording
• R • Oscillograph • Sequence of events record up to 1000 timeeal time monitoring
Physical requirements
• HMI Eleven (11) LED indicators will be located on the front of the unit and will indicate the following conditions :
• Manual mode active • Var/PF Active • Loss of generator sensing • OEL Active • UEL Active • Generator over voltage
• Over excitation shutdown • Under frequency active • Exciter field current limit • PSS Active* • Customer Alarm
6
PRODUCT OVERVIEW OEM AUTOMATION SOLUTIONS
INNOVATION AND AMTECHTOTAL AUTOMATION SOLUTIONS
To our customers, AMTECH means one stop, single window solution provider for all the needs ofDynamometer and Test Ring Automation
�Complete packaged automation solutions invarious IPxx rated cabinets
�Automation Solution based on PLC, SCADA,HMI and Instrumentation
�Integration of various communication topologies
�Solution with Controlling, Driving, Visualizing andNetworking
Innovation that keeps you ahead
Amtech, a leading automation solution provider, is one of the most dynamic industrial automation technologycompanies. From being the leading variable frequency drive manufacturer, we have made spectacularachievements in automation industry since our establishment in 1987.
Amtech has rich experience in developing automation solutions for OEMs. Building machines in a world of everchanging products and technologies is a tough business. We partner with leading manufacturers in theautomation industry so that you can rely on us to provide you the best solution for your requirements.
Salient Features
Better - Exceeding expectations
Faster - Quick delivery time and response
Safer - Knowledge and compliance of safety regulations to reduce your risk
Qualitative - We provide top-of-the-line products and services
Efficient - Saving you money and time
Competitive - We want you to be the best in your industry
‘Amtech - Your Trusted Partner for Technology and Service”
With AMTECH, Optimize Your Operations
YOU QUESTION, WE ANSWER
Why 1 HP = 0.746 kW?
1 HP is 550 foot- pounds per second, because in year 1800, James Watt had found out that a horsecan work 550 ft - pound per second.
Now, 1 foot = 0.3048 meters, 1 pound = 4.44822 Newtons.
Hence, 1 HP = 550 x 0.3048 x 4.4822
= 745.69 Newton-meters per second
= 746 Watts.(Approx.) = 0.746 kW
Customer’s Voice
Gandhinagar
Atlanta
GandhinagarAhmedabad
Mumbai
Surat
MuzaffarnagarDelhi(Gurgaon)
Vadodara
Indore
Jamnagar
Udaipur
Kolkata
Nagpur
Pune
Hyderabad
Vapi Raipur
Bhopal
Jamshedpur
JaipurLucknow
Vizag
Bangalore
Chennai
Belgaum
PondicherryTrichy
AurangabadNasik
Chandigarh
Veraval
M. D. Kamath
Paresh Patel
Regional Offices
Contact Person Phone No. (O) Mobile No. E-mail
022-28846083Vrajesh Yadav 09819900501
09108051977
09825042458
mumbai@amtechelectronics.com
bangalore@amtechelectronics.com
delhi@amtechelectronics.com
Mumbai
Bangalore
Chennai
Delhi
T. S. Sridhar 09840618533 09940229955
.
chennai@amtechelectronics.com
Umesh Bhatia 09589344318Indore / Raipur mp@amtechelectronics.com
H.O. and Service Center
Contact Person Phone No. (O) Mobile No. E-mail
Shailesh Patel 09879208780H.O. Gandhinagar sales@amtechelectronics.com079-23289101-102-103
Rajesh Moradiya 09909973780Amtech Service CenterGandhinagar
csd@amtechelectronics.com079-23289101-102-103
G. Sateesh Kumar 09573900222Hyderabad hyderabad@amtechelectronics.com
Kaushik C. 09932820680Kolkata kolkata@amtechelectronics.com
09825042458
09589344318
09573900222
09932820680
09108051977
Pankaj Gulati 09888748620Chandigarh delhi@amtechelectronics.com09888748620
top related