GRUNDFOS DATA BOOKLET
Selcoperm SESElectrolysis system for 5-45 kg/h Cl2 (equivalent)
Safe and simple production of sodium hypochlorite solution
Ta
ble
of c
on
ten
ts
2
Selcoperm SES
1. General information 3Fundamentals of disinfection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Disinfection with chlorine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3The Selcoperm electrolysis principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Benefits of the electrolysis with Selcoperm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2. Selcoperm Electrolysis System (SES) 5Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3. Design and technical data 7Selcoperm Electrolysis System (SES) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Selcoperm electrolyser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Rectifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11DC cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Degassing and storage tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Brine dosing station . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Chiller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Brine tank. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Acid cleaning station on a trolley . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Acid cleaning station for wall-mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Gas warning system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4. Accessories 20Maintenance kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Handheld conductivity measuring device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Test kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Compact photometer DIT-L . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
5. Grundfos Product Center 21
Ge
ne
ral
info
rma
tio
n
Selcoperm SES 1
1. General information
Fundamentals of disinfectionMany diseases are transmitted by drinking water. Among these diseases are typhus, paratyphoid, cholera and diarrhoea with vomiting, as well as viral infections such as hepatitis and poliomyelitis. Legionella in shower or bathing water can provoke pulmonary diseases.
Compared to the chemical contamination of water, where toxicity values are attained only slowly in general, in a drinking water epidemic infections spread dramatically in the whole supply area. The best prevention of epidemics is to use microbiologically clean non polluted water, preferably deep ground water as drinking water. Unfortunately, in some regions this is not possible for hydrogeological or quantitative reasons. In these regions, surface water is used, which often has to be purified. Pathogens that are possibly encountered, can be removed from the water or killed by adding certain substances to the water, i.e. by disinfecting the water.
Disinfection with chlorineThe most widespread disinfectant used in the treatment of drinking water is chlorine, which can be applied in a variety of ways. History has taught us that, in bacteriological terms, chlorinating water is a quite safe way of disinfecting drinking water. After all, more than 100 years have passed since chlorine was used to disinfect drinking water for the first time. Many years of experience have shown that acute toxicity can be excluded, when chlorination is executed correctly.
Generally, three methods are used for chlorinating drinking and process water:
• Chlorine gas dosing
• Dosing of commercial sodium hypochlorite solution or calcium hypochlorite solution
• Electrolytic sodium hypochlorite generation on site
The third method in particular offers a number of advantages, which are incorporated in the Selcoperm chlorine electrolysis systems.
3
Ge
ne
ral in
form
atio
n
4
Selcoperm SES1
The Selcoperm electrolysis principleWith electrolysis, sodium hypochlorite is produced directly from a solution of common salt using electricity.
Fig. 1 Selcoperm electrolysis principle
The following reactions take place in the electrolysis cell:
2NaCl + 2H2O → 2NaOH + Cl2 + H2
The chlorine (Cl2) produced reacts immediately with the caustic soda solution (NaOH) also formed, resulting in a sodium hypochlorite solution (NaClO):
Cl2 + 2NaOH ↔ NaCl + NaClO + H2O
The sodium hypochlorite solution, which is the disinfectant, has a pH value between 8.5 and 9.5, and a chlorine concentration of 8 g/l. It has a half-life of several months, which makes it ideal for storage in a buffer tank.
After dosing the solution into the water flow, no pH value correction is necessary, as it is often required e.g. in electrolysis according to the membrane principle. The sodium hypochlorite solution reacts in a balance reaction, resulting in hypochlorous acid (HClO), the effective disinfectant:
NaClO + H2O ↔ NaOH + HClO
The resulting hypochlorous acid is the actually effective compound for disinfection of the water. The dissociation of acid to anions is primarily according to an equilibrium dependent on the pH value according to the equation:
HClO + H2O ↔ H3O+ + ClO-
Fig. 2 Dissociation of hypochlorous acid in dependence of the water pH value
The dosing quantity depends on the application as well as the local regulations. In general, the concentration after the injection unit is 0.3 to 2 ppm chlorine equivalent.
Benefits of the electrolysis with Selcoperm• Safe and reliable method of producing sodium
hypochlorite on-site
• Common salt is the base material - it is non-toxic, easy to store and easy to handle
• Only water, common salt and electricity are needed for the electrolysis - low operating costs, world-wide use
• Fresh sodium hypochlorite is always on hand and does not dissociate like commercial sodium hypochlorite solutions
• Low formation of chlorate as a by-product
• Less safety requirements than chlorine-gas-based systems
• Lower pH value than commercial sodium hypochlorite reduces scaling of injection units etc. in hard water areas
• Robust design for easy installation and maintenance
• Long service life, compared with membrane cell electrolysis
ApplicationsTypical disinfection applications for Selcoperm systems are especially in
• drinking water treatment,
• water treatment for industrial processes and cooling towers.
The systems are an excellent alternative to chlorine gas or commercial sodium hypochlorite applications.
Remark: Legislation on the use of disinfectants in water treatment applications is country-specific. Please contact your local Grundfos sales office for further details on the use of our products in your application and area.
TM
06
17
96
30
14
TM
06
17
95
07
15
+-
NaCl
H2
H2O
NaClO solution
Cathode Anode
NaClO
NaOH Cl2
H2O
NaCl
OH-H+
Na+ Cl-
4
100% HClO
80
60
40
20
0
0
20
40
60
80
100
% ClO-
pH
0 °C10 °C30 °CClO-HClO
5 6 7 8 9 10 11
Se
lco
pe
rm E
lec
tro
lys
is S
ys
tem
(S
ES
)
Selcoperm SES 2
2. Selcoperm Electrolysis System (SES)
DescriptionThe Selcoperm electrolysis system is a modular system for the safe production of a 0.8 % sodium hypochlorite solution from a diluted brine solution. The system is suitable for the disinfection of drinking water and industrial process water. The intended use of the Selcoperm system comprises the stationary operation either in continuous or batch processing.
Installation scheme
Fig. 3 Installation scheme of a Selcoperm system
TM
07
00
61
40
17
E
C
H
I
1
12
3
4
5
GD
F
K
I
A
B
ATEX zone 2radius 1-2 m
Pos. Component Description
A Water softener The water softener provides the softened mains water required for the electrolysis.
B Chiller and/or heater To provide the right mains water temperature, an optional chiller or heater can be used.
C Brine tank The brine tank is used for preparation and storage of brine.
D Brine dosing station The brine dosing station doses the required amount of brine into the process.
E Selcoperm electrolyser
The Selcoperm electrolyser comprises:• Electrolysis cells• Hydraulic chamber• Control cabinet• 7" multi-colour touchscreen for operating and monitoring of the whole electrolysis system
F RectifierThe rectifier converts the alternating current (AC) from the power supply into the direct current (DC) needed to run the Selcoperm electrolyser.
GDegassing and storage tank with sensors and degassing fan
In the degassing and storage tank the hydrogen gas is removed from the sodium hypochlorite solution. The degassing and storage tank must be installed as close as possible to the Selcoperm electrolyser. The level inside the tank is monitored by a level sensor. The degassing fan ensures a safe dilution and removal of hydrogen gas. The sodium hypochlorite solution can be dosed directly from the tank to the point of application. It is also possible to pump the sodium hypochlorite solution from the tank into separate storage tanks.
H Gas warning system The gas warning system permanently monitors the concentration of hydrogen gas at the installation location.
I Building ventilationNatural ventilation via ventilation holes or technical ventilation is required at the installation location. Legal requirements and local standards must be observed.
K DC cable set Flexible insulated copper cable for direct current connection between the Selcoperm electroyser and the rectifier.
1 Soft water line
2 Brine line
3Sodium hypochlorite solution line
Besides the sodium hypochlorite solution this line contains hydrogen gas, which is removed in the downstream degassing and storage tank.
4 Exhaust air lineThrough this line the dilution air (99 %) and the hydrogen gas (1 %) are removed from the degassing and storage tank by means of forced ventilation. The exhaust air line has to be directed with a constant upwards incline to a safe discharge point outside the building.
5 Sodium hypochlorite solution line to the point of application
- Drain A drain for maintenance is required on site.
5
Se
lco
pe
rm E
lec
troly
sis
Sy
ste
m (S
ES
)
6
Selcoperm SES2
Functioning and controlSaturated brine from the brine tank (C) is dosed by the brine dosing station (D) into the Selcoperm electrolyser (E), where it is mixed with softened water from the softener (A) in a specified proportion. The resulting diluted brine is led into the electrolysis cells inside the Selcoperm electrolyser (E), where it is converted into sodium hypochlorite and hydrogen by means of direct current (DC) from the rectifier (F). The resulting mixture is led through a line with a slight upwards incline of at least 1 % into the degassing and storage tank (G). The degassing fan at the tank (G) ensures safe dilution and removal of the hydrogen gas to a safe external discharge point. The sodium hypochlorite solution can be dosed directly from the tank (G) to the point of application. It is also possible to pump the sodium hypochlorite solution from the tank (G) into separate storage tanks.
All components and safety functions are monitored and operated via a multi-colour touchscreen at the Selcoperm electrolyser (E).
Safety conceptA reliable safety concept for the operation of the whole system is mandatory, because hydrogen is produced as a by-product in the electrolysis cells.
Before even entering the degassing and storage tank (G), most of the hydrogen is diluted by the degassing fan to 25 % of the lower explosive limit (LEL) and led away into the atmosphere. In the tank the residual hydrogen escapes, is diluted and led away into the atmosphere as well.
The whole Selcoperm electrolysis system is monitored permanently and redundantly. Several sensors at the system, together with hydrogen sensors at the installation location ensure a safety shutdown of the whole system in the event of a failure. Small amounts of hydrogen, which can escape due to a leakage for instance, are led away via the ventilation hole (I) at the highest point of the room. The safety concept is evaluated with technical report by a third-party expert from TÜV SÜD Product Service GmbH. It ensures safe operation without any additional explosion protection at the installation location.
Unique selling points• Unique safety concept, evaluated with technical
report by a third-party expert from TÜV SÜD Product Service GmbH
• No explosion-proof area needed inside the building
• Flow-proportional brine dosing for precise brine concentration
• Standardised modular system
• Outstanding performance data
• Convenient 7" multi-colour touchscreen with self-explanatory menu structure
• Innovative housing design for easy maintenance, flexible installation and safe operation
• Chemically resistant housing material
• High quality standard: Every Selcoperm electrolyser is checked for 100 % performance and tightness at the factory
• Remote maintenance (optional)
De
sig
n a
nd
te
ch
nic
al
da
ta
Selcoperm SES 3
3. Design and technical data
Selcoperm Electrolysis System (SES)The following data apply to the overall Selcoperm electrolysis system and cover all capacity levels.
Water quality specificationThe water supply must conform to the required standard of drinking water given in the specification below. Ask your local water supplier for the specific values.
Salt specificationUse food-grade granular/pellet salt (98.5 % NaCl) according to EN 14805 type 2 with following minimum requirements:
Max. limits of dry salt.
Ambient conditions
* System must be drained. For storage temperatures below +5 °C, the whole system including water softener, lines and external components must not contain any water.
Exposition to direct sunlight can cause changes in colour as well as material deformations and cracks. Don't expose the system to direct sunlight.
ParametersValue (maximum unless stated otherwise)
Colour [mg/l Pt/Co] 20
pH value 6.5 - 10.0
Iron Fe [µg/l] 200
Manganese Mn [µg/l] 20
Fluoride F [mg/l] 2
Turbidity [NTU] 4
Max. particle size [µm] 100
Parameter SymbolMax. mass fraction [mg/kg]
Iron Fe 10.0
Manganese Mn 10.0
Bromide Br 100.0
Calcium Ca 100.0
Magnesium Mg 100.0
Permissible ambient temperatures (min./max.)
Transport* -10 / +50 °C
Storage* +0 / +40 °C
Operation +5 / +40 °C
Operation (rectifier) +10 / +40 °C
Max. relative humidity (non-condensing) 90 %
Max. relative humidity (non-condensing) for rectifier 75 %
Max. altitude above sea level 2000 m
7
De
sig
n a
nd
tec
hn
ica
l da
ta
8
Selcoperm SES3
Selcoperm electrolyserThe Selcoperm electrolyser is the core piece of the Selcoperm electrolysis system.
Fig. 4 Overview components SES-5000 to SES-15000
Fig. 5 Overview components SES-20000 to SES-45000
TM
06
17
98
06
16
TM
06
46
72
06
16
1
2
3
4
11
5
6Z
B
A
V
V
6
1
2
2
3
4
11
5
6
Z
AB
V
V
6
6
De
sig
n a
nd
te
ch
nic
al
da
ta
Selcoperm SES 3
Legend
General data
* System with air-cooled rectifier, excluding optional chiller and heater
Capacity levels, data and product numbers
Connections
Pos. Description
1 Chemically resistant PEHD frame with collecting tray
2 Easily removable powder-coated housing
3Horizontal electrolysis cells with transparent PVC pipe for easy process monitoring and visual electrode check. Several sensors monitor the liquid level and temperature, the voltage and the temperature of all direct-current (DC) connections.
4Lockable hydraulic chamber with shut-off valves and adjustment valves, temperature sensors, flow sensors and leakage sensors, sample valves for brine and sodium hypochlorite solution, and a connection for acid cleaning.
5
Lockable control cabinet with multi-colour touchscreen, emergency stop and main switch. The control cabinet monitors and/or controls the following components and functions:• Rectifier• Brine dosing station• Sensors and valves of the Selcoperm electrolyser• Level sensors and flow sensors of the degassing and storage tank and the sodium hypochlorite solution line• Degassing fans (duty/standby) of the degassing and storage tank• Potential-free contact for start/stop signal for optional transfer pumps to transfer the sodium hypochlorite solution from the degassing tank to
separate storage tanks• Gas warning system• Several potential-free alarm contacts• Acid cleaning station• Remote maintenance (optional)
6 Top or bottom connection for direct current cables from the rectifier
11
7" multi-colour touchscreen for operating and monitoring of the whole electrolysis system. Selectable languages are English, German, Spanish, French, Chinese, Turkish and Russian.The system can be operated in two operation modes:• automatic mode• service modeThe system can also be remotely controlled and monitored via PROFINET.
A Soft water inlet
B Brine inlet
V NaClO solution outlet
Z Drain outlet
Sodium hypochlorite concentration 8 - 8.5 g/l
Salt consumption 3 - 3.5 kg NaCl per kg of Cl2 (equivalent)
Power consumption (DC/AC)* 4.2 - 4.6 / 5.0 - 5.4 kWh per kg of Cl2 (equivalent)
Soft water consumption 125 litres per kg of Cl2 (equivalent)
Soft water inlet pressure 3-5 bar (depending on the capacity level)
Soft water temperature 10-20 °C (for higher or lower temperatures an external chiller or heater is required)
Soft water quality for operation Drinking water quality, softened to: 1 °dH / 17.8 ppm CaCO3 and less
Max. pressure inside electrolyser, NaClO solution line and degassing and storage tank
1 bar
SES typeCapacity level Cl2
(equivalent)[g/h]
Max. power rating of built-in control cabinet
[kW]
Total soft water flow[l/h]
Weight[kg] Product
numberEmpty Filled
SES-5000 5000 1.5 633 660 685 98720672
SES-7500 7500 1.5 944 680 715 98720676
SES-10000 10000 1.5 1266 720 770 98720678
SES-15000 15000 3 1887 780 845 98720681
SES-20000 20000 3 2532 1170 1270 98720705
SES-30000 30000 5.2 3776 1250 1380 98720707
SES-45000 45000 5.2 5660 1350 1550 98720722
Pos. Description SES-5000 SES-7500 SES-10000 SES-15000 SES-20000 SES-30000 SES-45000
A Soft water inlet DN 25 DN 25 DN 25 DN 25 DN 40 DN 40 DN 40
B Brine inlet DN 20 DN 20 DN 20 DN 20 DN 25 DN 25 DN 25
4 Acid cleaning inlet and outlet DN 20 DN 20 DN 20 DN 20 DN 20 DN 20 DN 20
V NaClO solution outlet DN 50 DN 50 DN 50 DN 65 DN 100 DN 100 DN 100
Z Drain outlet DN 25 DN 25 DN 25 DN 25 DN 25 DN 25 DN 25
9
De
sig
n a
nd
tec
hn
ica
l da
ta
10
Selcoperm SES3
Built-in control cabinet
Dimensions and space requirements
Fig. 6 Dimensions and space requirements. Dimensions in mm.
Supply voltage: 380-415 V, 50-60 Hz (3 phases + N + PE)
Enclosure class: IP54
Electrical safety class: I
Pollution degree: 2
TM
06
17
99
06
16
2060 1060 1200 2800
53004060
2250
3200
3560
1500
15001000
1000
1000
1000
1000
1000
2250
SES-5000, SES-7500, SES-10000, SES-15000 SES-20000, SES-30000, SES-45000
De
sig
n a
nd
te
ch
nic
al
da
ta
Selcoperm SES 3
RectifierThe rectifier converts the alternating current from the power supply into the direct current needed to run the Selcoperm electrolyser. In case of a failure, the rectifier shuts down. The communication between the Selcoperm electrolyser and the rectifier is designed redundantly (Profinet and hardwired) for the safety shutdown functions.
Technical data for air-cooled rectifier
Fig. 7 Air-cooled rectifier
Water-cooled rectifiers are available on request
DC cableFlexible insulated copper cable for direct current connection between the Selcoperm electroyser and the rectifier. The standard cable length must not exceed 10 m. Longer cables are available on request.
The cable required depends on the type of the Selcoperm electroyser.
Enclosure class: IP20
Max. relative humidity (non-condensing): 75 %
Permissible ambient temperature for operation (min. / max.):
+10 / +40 °C
TM
06
38
74
111
5
SES typeDimensions
L x W x H[mm]
Weight[t]
DCcurrent
[A]
Power loss[kW]
Air flow[m³/h]
Input voltage50 Hz
3 phases + PE[VAC]
Current per phase
[A]
Product number
SES-5000 900 x 875 x 2500 0.8 1 x 800 4 1300
380 56.8 98844338
400 54.0 98844339
415 52.0 98844340
SES-7500 900 x 875 x 2500 0.8 1 x 800 4.5 1300
380 80.8 98844344
400 76.8 98844345
415 74.0 98844346
SES-10000 900 x 875 x 2500 0.9 1 x 800 5.01 2600
380 106.7 98844350
400 101.3 98844351
415 97.7 98844352
SES-15000 900 x 875 x 2500 1 1 x 800 5.67 2600
380 154.8 98844356
400 147.1 98844357
415 141.8 98844358
SES-20000 1200 x 875 x 2500 1.7 2 x 800 10.03 3900
380 213.5 98844362
400 202.8 98844363
415 195.5 98844364
SES-30000 1800 x 875 x 2500 2 2 x 800 11.33 3900
380 309.8 98844368
400 294.3 98844369
415 283.7 98844370
SES-45000 2700 x 875 x 2500 3 3 x 800 17 5200
380 464.6 98844374
400 441.4 98844375
415 425.4 98844376
SES typeLength
[m]Cable cross-section
[mm2]Product number
SES-5000SES-7500SES-10000SES-15000
45 240 99366691
SES-20000SES-30000
90 240 99366728
SES-45000 135 240 99366739
11
De
sig
n a
nd
tec
hn
ica
l da
ta
12
Selcoperm SES3
Degassing and storage tankThe degassing and storage tank is a mandatory component of the Selcoperm electrolysis system. In systems with several electrolysers, one tank for each electrolyser must be installed.
The volume of the tank depends on the capacity level of the Selcoperm electrolyser. Engineered degassing and storage tanks are available on request (e.g. larger volumes than indicated in the table).
The sodium hypochlorite solution can be dosed directly from the tank to the point of application. In this case, the volume of the tank must be selected according to the demand of sodium hypochlorite solution of the individual application. It is also possible to pump the sodium hypochlorite solution from the degassing and storage tank into separate storage tanks. Separate storage tanks and transfer pumps are available on request.
One degassing fan is installed on the tank by default. To avoid a system shutdown due to a defective fan, an additional standby fan can be ordered.
Installation set
A special installation set is pre-installed at the degassing and storage tank. The use of this installation set is mandatory to ensure the compliance with the certified safety concept of the Selcoperm electrolysis system.
Fig. 8 Degassing and storage tank 1.5 m3
Components
A collecting tray is not within the scope of delivery.
TM
07
03
41
49
17
1 3 42
9
5/6107
11
12
8
Pos. DescriptionPart of
installation set
1 NaClO solution inlet
2 Air inlet
3 Exhaust air outlet
4 Inspection opening
5/6 NaClO solution outlet or Drain
7 Level sensor connection
8 Overflow switch connection
9 Degassing fan yes
10 Level sensor yes
11 Calibration pipe
12 Overflow switch yes
-Air flow sensor for exhaust air line with connection flange
yes
-Leakage sensor(for installation with collecting tray)
yes
- T-piece with NaClO solution line level switch yes
De
sig
n a
nd
te
ch
nic
al
da
ta
Selcoperm SES 3
Technical data
Connections
* Outer pipe diameter
SES typeVolume
[m3]Diameter
[mm]
Height (with additional
standby fan)[mm]
Air flow [m3/h]
Product number
Tank with one fanTank with additional
standby fan
SES-5000 1 1000 2100 (2500) 300 99380533 99382924
SES-7500 1.5 1000 2300 (2700) 450 99380855 99382988
SES-10000 2 1300 2200 (2600) 600 99380939 99383004
SES-15000 3 1600 2400 (2900) 900 99381000 99383090
SES-20000 4 1800 2400 (2900) 1200 99381676 99383118
SES-30000 6 2000 2700 (3200) 1800 99381749 99383232
SES-45000 9 2200 3200 (3900) 2700 99382350 99383263
Pos. Description SES 5000 SES 7500 SES 10000 SES 15000 SES 20000 SES 30000 SES 45000
1 NaClO solution inlet (loose flange) DN 80 DN 80 DN 80 DN 100DN 125 d125*
DN 125 d125*
DN 125 d125*
2 Air inlet (socket flange) DN 150 DN 150 DN 150 DN 200 DN 200 DN 200 DN 300
3 Exhaust air outlet (socket flange)DN 125 d125* DN 150 DN 150 DN 200 DN 250 DN 300 DN 300
4 Inspection opening (blank flange) DN 150 DN 150 DN 300 DN 300 DN 300 DN 400 DN 400
5, 6NaClO solution outlet or Drain (union, DN80 flange)
DN 32 DN 32 DN 50 DN 50 DN 50 DN 80 DN 80
7 Level sensor connection (thread) 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"
8 Overflow switch connection (solid flange) DN 25 DN 25 DN 25 DN 25 DN 25 DN 25 DN 25
13
De
sig
n a
nd
tec
hn
ica
l da
ta
14
Selcoperm SES3
Brine dosing stationThe brine is dosed with digital dosing pumps. To ensure reliable brine dosing, the dosing station comprises a duty pump and a standby pump. Pulsation dampers ensure low pulsation. As the counterpressure of the Selcoperm electrolyser is too low, the brine dosing station contains a pressure loading valve.
The dosing station is controlled via the touchscreen on the Selcoperm electrolyser. A Flow Monitor is installed on each pump to monitor the dosing process. Errors in the dosing process are displayed on the touchscreen of the Selcoperm electrolyser.
Fig. 9 Brine dosing station
Components
Technical dataThe Selcoperm electrolyser provides the brine dosing station with the supply voltage of 230 V, 50/60 Hz, and the control current of 4-20 mA.
TM
07
00
97
411
7
1 2
3
4
5
Pos. Description
1 Dosing cabinet with sliding doors
2 Pressure pulsation damper
3 Pressure loading valve PLV
4Digital dosing pumps (duty/standby) with flow monitoring function
5Suction pulsation damper with scale for calibration and manual vacuum pump for priming
SES typeDosing capacity
[l/h]Pump type Length [mm]
Height [mm]
Width [mm]
Weight [kg]
Product Number
SES-5000 63 DDA 200-4
1950 1750 400 200 98865559SES-7500 94 DDA 200-4
SES-10000 126 DDA 200-4
SES-15000 187 DDA 200-4
SES-20000 252 DME 375-10 2450 1800 500 250 99155579
SES-30000 376 DME 940-42450 1800 500 270 98865561
SES-45000 560 DME 940-4
De
sig
n a
nd
te
ch
nic
al
da
ta
Selcoperm SES 3
Water softenerThe water softener provides the softened mains water required for the electrolysis.
The water softener is equipped with a dual head and two cylinders to ensure a constant soft-water supply even during regeneration. A stand-alone brine tank provides the brine needed for regeneration. An installation set for piping, a bypass valve and a filter with manual backwash function are delivered with each water softener.
The water softener can be ordered pre-assembled on a skid or without skid.
Fig. 10 Water softener
Technical data
TM
06
18
03
02
15
Supply voltage: 230 V, 50/60 Hz
Operating pressure: 2-8 bar
Power consumption: 10 VA
SES typeSoft water
flow[l/h]
Cylinders Brine tankWater
inlet/outlet
Product numbersoftener, filter and bypass
Diameter[mm]
Height[mm]
Volume[l]
Diameter[mm]
Height[mm]
pre-assembled on skid
without skid
SES-5000 570 2 x 208 1310 150 500 810 DN 25 98865562 98865569
SES-7500 850 2 x 208 1310 150 500 810 DN 25 98865563 98865570
SES-10000 1140 2 x 208 1310 150 500 810 DN 25 98865564 98865571
SES-15000 1700 2 x 208 1310 150 500 810 DN 25 98865565 98865572
SES-20000 2280 2 x 257 1530 210 570 880 DN 25 98865566 98865573
SES-30000 3400 2 x 334 1790 300 700 870 DN 25 98865567 98865574
SES-45000 5100 2 x 369 1840 500 780 1100 DN 40 98865568 98865575
15
De
sig
n a
nd
tec
hn
ica
l da
ta
16
Selcoperm SES3
ChillerIf the required soft water temperature cannot be met, a chiller can be used to cool the soft water down. The chiller is placed between the water softener and the Selcoperm electrolyser. The softened water entering the chiller must comply with the recommended soft water quality (see page 7). The chiller is designed to run 24 hours a day, controlled via a local control panel.
Fig. 11 Chiller
Technical data
* The values apply to the operating point, the maximum values are higher.
TM
06
18
00
05
15
Supply voltage: 400 V, 50/60 Hz (3 phases + PE), 380 V and 415 V are available on request
Max. water temperature inlet: 30 °C
Water temperature outlet: 15 °C
Flow[l/h]
Capacity level Cl2
(equivalent)[g/h]
Ambient temperature range: 10-40 °C (type OLB), 5-45 °C (type cBoxX, Arctic)
TypeCooling capacity
[kW]
Power consumption
[kW]*
Current consumption
[A]*
Length[mm]
Width[mm]
Height[mm]
Weight[kg]
Product number
600 5000 vBoxX15 10.0 6.2 11.4 800 1000 1500 340 98865576
900 7500 vBoxX24 20.0 13.7 17.3 810 1270 1500 340 98865577
1200 10000 cBoxX 30 23.0 9.2 17.6 1240 830 2030 540 98865578
1800 15000 cBoxX 50 38.0 15.0 27.4 1240 830 2030 550 98865579
2400 20000 cBoxX 60 44.0 19.1 35.8 1240 830 2030 620 98865580
3600 30000 cBoxX 90 63.1 27.2 44.7 1840 830 2030 700 98865581
5100 45000 cBoxX 160 112.5 46.3 82.9 2665 1200 2030 1200 98865582
10200 2 x 45000 2 x cBoxX 160 2 x 112.5 2 x 46.3 2 x 82.9 2 x 2665 2 x 1200 2 x 2030 2 x 1200 98865583
20400 4 x 45000 Arctic 350 345.0 162.6 280.3 6500 2220 2200 4500 98865584
40800 8 x 45000 2 x Arctic 350 2 x 345.0 2 x 162.6 2 x 280.3 2 x 6500 2 x 2220 2 x 2200 2 x 4500 98865585
Flow[l/h]
Capacity level Cl2
(equivalent)[g/h]
Ambient temperature range: 10-50 °C (type OLB), 5-50 °C (type cBoxX, Arctic)
TypeCooling capacity
[kW]
Power consumption
[kW]*
Current consumption
[A]*
Length[mm]
Width[mm]
Height[mm]
Weight[kg]
Product number
600 5000 vBoxX 30 19.3 9.2 13.3 1240 830 2030 540 98865586
900 7500 vBoxX 30 19.3 13.7 17.6 1240 830 1500 340 98865587
1200 10000 cBoxX 40 25.7 12.0 21.9 1240 830 2030 540 98865588
1800 15000 cBoxX 50 31.6 17.5 31.5 1240 830 2030 550 98865589
2400 20000 cBoxX 70 43.0 20.8 35.9 1840 830 2030 650 98865590
3600 30000 cBoxX 100 63.4 31.0 53.3 1840 830 2030 720 98865591
5100 45000 cBoxX 180 110.0 52.3 89.9 3965 1200 2030 1300 98865592
10200 2 x 45000 2 x cBoxX 160 2 x 95.3 2 x 46.3 2 x 82.9 2 x 2665 2 x 1200 2 x 2030 2 x 1100 98865593
20400 4 x 45000 Arctic 380 345.0 230.4 375.9 7500 2220 2200 5000 98865594
40800 8 x 45000 2 x Arctic 380 2 x 345.0 2 x 230.4 2 x 375.9 2 x 7500 2 x 2220 2 x 2200 2 x 5000 98865595
De
sig
n a
nd
te
ch
nic
al
da
ta
Selcoperm SES 3
HeaterIf the required soft water temperature cannot be met, a heater can be used to warm the soft water up. The heater is placed between the water softener and the Selcoperm electrolyser. The softened water entering the heater must comply with the recommended soft water quality (see page 7). The device is designed to run 24 hours a day, controlled via a local control panel.
Fig. 12 Heater
Technical data
* The installation set comprises two temperature sensors Pt100 with T-piece, and three bypass valves with valve position indicator
Calculation of heating capacity
The required heating capacity can be calculated individually as follows:
Required heating capacity [kW] ≥ Water flow [m3/h] * Temperature difference to achieve [K] * 1.16
Brine tankThe brine tank is used for preparation and storage of brine.
• Material: Polyethylene
• With water inlet valve
• Gravel bed is not included (gravel bed height depends on salt type)
• Optional overflow switch is available on request
Other sizes, separate storage tanks and transfer pumps as well as gravel are available on request.
TM
06
18
08
05
15
Supply voltage: 400 V, 50/60 Hz (3 phases + PE)
Min. water temperature inlet: 3 °C
Water temperature outlet: 15 °C
Flow[l/h]
Capacity level Cl2 (equivalent)
[g/h]
Heating capacity
[kW]Type
Power consumption
[kVA]Flange
Fuse rating
[A]
Weight[kg]
Product number
HeaterControl panel
HeaterControl panel
Installation set*
600 5000 8 HF/SE-10 10.5 DN 25 20 45 40 98865596 98865606
98865616900 7500 13 HF/SE-15 16 DN 25 35 46 50 98865597 98865607
1200 10000 17 HF/SE-20 21 DN 25 50 47 70 98865598 98865608
1800 15000 25 HF/SE-30 31.5 DN 50 63 63 70 98865599 98865609
988656172400 20000 34 HF/SE-40 42 DN 50 80 73 70 98865600 98865610
3600 30000 50 HF/SE-60 63 DN 50 2 x 63 78 80 98865601 98865611
5100 45000 71 HF/SE-95 100 DN 80 2 x 100 135 100 98865602 9886561298865618
10200 2 x 45000 142 HF/SE-175 184 DN 80 4 x 100 195 150 98865603 98865613
20400 4 x 45000 285 HF/SE-345 363 DN 100 6 x 125 320 250 98865604 9886561498865619
40800 8 x 45000 570 HF/SE-560 588 DN 100 8 x 125 495 400 98865605 98865615
Salt capacity [kg]
Diameter[m]
Height[m]
Inlet Outlet
Gravel (4-8 mm) required for a gravel bed height of 200-400
mm[m3]
Product number
2300 1.8 1.3 DN 25 DN 32 0.5 - 1 99380223
3800 2.3 1.3 DN 25 DN 32 0.8 - 1.6 99380183
17
De
sig
n a
nd
tec
hn
ica
l da
ta
18
Selcoperm SES3
Acid cleaning station on a trolleyThe Selcoperm electrolyser provides the acid cleaning station with the supply voltage by means of a special plug. The acid cleaning station is controlled via the touchscreen on the Selcoperm electrolyser.
The acid cleaning station is pre-assembled on a trolley for acid cleaning of the electrodes.
Features• 300-litre acid tank with collecting tray
• DMX 460-4 dosing pump with single-phase motor (230 V, 50 Hz)
• Equipment for hydraulic and electrical connection to the Selcoperm electrolyser
Overview
Fig. 13 Acid cleaning station on a trolley
Acid cleaning station for wall-mountingThe acid cleaning station is pre-assembled and ready for mounting on a wall.
Features• With foot valve and 10 m hose for the connection to
the Selcoperm electrolysis system and an external acid tank
• Without tank, trolley and collecting tray
Overview
Fig. 14 Acid cleaning station - wall mounted
DescriptionProduct number
Acid cleaning station on a trolley 98865693
TM
06
96
45
26
17
Pos. Description
1 Collecting tray
2 Trolley
3 Acid tank, 300 l
4 Return flow line
5 Special plug for connection to Selcoperm electrolyser
6 3-way ball valve
7 Dosing pump
8 Connection to Selcoperm electrolyser with manual valve
9 3-way ball valve
10 Drain valve
11 Pressure relief valve
3
4
2
1
11
9
10
8
7
6
5
DescriptionProduct number
Acid cleaning station for wall-mounting 99398520
TM
07
08
19
06
18
Pos. Description
4 Return flow line
5 Special plug for connection to Selcoperm electrolyser
6 3-way ball valve
7 Dosing pump
8 Connection to Selcoperm electrolyser with manual valve
9 3-way ball valve
11 Pressure relief valve
11
9
5
6
7
8
4
De
sig
n a
nd
te
ch
nic
al
da
ta
Selcoperm SES 3
Gas warning systemAs a part of the safety concept, a gas warning system for hydrogen gas (H2) must be installed at the installation location.
A self-contained gas warning system with at least two sensors for each Selcoperm electrolyser must be used. The gas warning system has to provide two potential-free output contacts, which are directly connected to the Selcoperm electrolyser to shut down the whole system in case of gas leakage. The contact type of the output contact must be NC (normally closed) to ensure the safety shutdown even in case of wire breakage.
Grundfos provides a suitable gas warning system meeting all these requirements. It provides the information needed at a glance via a comprehensive display and LEDs showing the status with different colours. The system can operate stand-alone or interface with alarm devices and control systems using several outputs.
Fig. 15 Gas warning system and sensor
Features• Wall-mounted IP65 control panel with simultaneous
display of up to four gas sensors. Ambient temperature up to 55 °C.
• Sensors selectable with local calibration directly on the sensor or with remote calibration module
• Output connection for one or two audible or visual alarms, 5 A, 24 VDC
• Potential-free contacts rated 5 A, 250 VAC (non-inductive) for Alarm 1, Alarm 2 and Fault
• 8 output relays, configurable to different alarms
• Optionally extendable with further relay modules
• Operates with 24 VDC external power supply as a standard. Optional internal power module for use with 110-240 VAC, 50/60 Hz, 2 A can be supplied. A local UPS (Uninterruptible Power Supply) has to be provided.
• Multi-language PC software to set parameters
* Local legislation may restrict shipping
TM
06
18
05
13
15
DescriptionProduct number
4-channel gas warning controller 99393814
Internal power module 110-240 VAC, 50/60 Hz, 2 A 98865624
PC software with adapter cable 98865625
Hydrogen sensor, range 0-100 % LEL, local calibration 98865626
Hydrogen sensor, range 0-100 % LEL, remote calibration 98865627
Calibration gas 2 %, bottle with regulating valve* 98865629
Combined horn and light alarm, 24 VDC 98037506
19
Ac
ce
ss
orie
s
20
Selcoperm SES4
4. Accessories
Maintenance kitsThese maintenance kits comprise the diaphragm and valve parts for the maintenance of the brine pumps in the brine dosing station. One kit is required for each pump.
Handheld conductivity measuring device
Features
• Long-living 2-pole graphite measuring cell
• Display alternatives: TDS, salinity and temperature
• Automatic temperature compensation
• Low current consumption
• Adjustable
Fig. 16 Handheld conductivity measuring device
Technical data
Order data
Test kitTest kit for SES, comprising:
• Measuring cylinder
• Total hardness test for titrimetric determination of the water hardness
• Thermometer
• Spindle for specific gravity measurement
• Titration set for measurement of the chlorine concentration in the sodium hypochlorite solution
• Operating instructions
Fig. 17 Test kit
Compact photometer DIT-L• For quick determination of the concentration of
chlorine, chlorine dioxide or ozone as well as the pH in water.
• For details, please see the DIT-L data booklet.
Fig. 18 DIT-L photometer
Description SES type Pump typeProduct number
Maintenance kit for brine pump
SES-5000
DDA 200-4 99151342SES-7500
SES-10000
SES-15000
SES-20000 DME 375-10 96520380
SES-30000DME 940-4 96520391
SES-45000
TM
06
46
74
08
16
Measuring ranges
Conductivity 0.0 ... 100.0 mS/cm
Temperature -5.0 ... +100 °C
Accuracy
Conductivity, TDS, salinity± 0.5 % of reading± 0.5 % full scale
Temperature ± 0.3 K
Power supply
Battery (included) 9 V battery, type IEC 6F22
Power consumption < 1.5 mA
DescriptionProduct number
Handheld conductivity measuring device 98842506
TM
06
46
75
08
16
DescriptionProduct number
Test kit 98842487
TM
06
18
07
30
14
Parameter Measuring range
Chlorine 0.01 - 6 mg/l
Chlorine dioxide 0.02 - 11 mg/l
Ozone 0.02 - 2 mg/l
pH value 6.5 - 8.4 pH
Gru
nd
fos
Pro
du
ct
Ce
nte
r
21
Selcoperm SES 5
5. Grundfos Product Center
All the information you need in one place Downloads
Performance curves, technical specifications, pictures, dimensional drawings, motor curves, wiring diagrams, spare parts, service kits, 3D drawings, documents, system parts. The Product Center displays any recent and saved items - including complete projects - right on the main page.
On the product pages, you can download installation and operating instructions, data booklets, service instructions, etc. in PDF format.
"SIZING" enables you to size a pump based on entered data and selection choices.
Online search and sizing tool to help you make the right choice.
http://product-selection.grundfos.com
"REPLACEMENT" enables you to find a replacement product. Search results will include information on the following:
• the lowest purchase price• the lowest energy consumption• the lowest total life cycle cost.
"CATALOGUE" gives you access to the Grundfos product catalogue.
"LIQUIDS" enables you to find pumps designed for aggressive, flammable or other special liquids.
22
23
GRUNDFOS A/S DK-8850 Bjerringbro . DenmarkTelephone: +45 87 50 14 00www.grundfos.com
98721404 0218
ECM: 1212914 Th
e n
am
e G
run
dfo
s, t
he
Gru
nd
fos
log
o,
an
d b
e t
hin
k i
nn
ov
ate
are
re
gis
tere
d t
rad
em
ark
s o
wn
ed
by
Gru
nd
fos
Ho
ldin
g A
/S o
r G
run
dfo
s A
/S,
De
nm
ark
. A
ll ri
gh
ts r
ese
rve
d w
orl
dw
ide
.©
Co
pyr
igh
t G
run
dfo
s H
old
ing
A/S
top related