Brief Introduction for Automated Relay Testing
Kamin DaveManager – Marketing & Protection Applications
DOBLE ENGINEERING COMPANY, INDIA
kdave@doble.com
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Protection Relay Testing:
Testing of Generator Protection Relay type SEL300G
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
Under & Over Voltage Protection (27/59)Negative sequence Protection (46)Reverse & Low Forward Power Protection (32)Over Excitation Protection (24)Over & Under Freq. Protection (81O/81U)Under Impedance Protection (21)Loss of Excitation Protection (40G)100% Stator E/F Protection (27TN/64G2)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
Out of Step Protection (78)Voltage Restrained O/C Protection (51VR)Voltage Controlled O/C Protection (51VC)Rotor E/F Protection (64R)Breaker Failure ProtectionGenerator Differential Protection (87D)Ground differential Protection (87N)95% Stator E/F Protection (59GN/64G1)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
Primary & Backup Protection
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
Rotor Earth Fault Protection
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
Characteristic plotted in F6TEST2.21 software for testing
Load Encroachment characteristic plotted
Zone2 Reach
Zone1 Reach
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
Select “D” from List
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
GCB Status Close Input
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
Breaker close input & VT fuse fail input
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
VT fuse fail Status Input
Characteristic selection
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
V/Hz Curve1
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
V/Hz Curve2
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
V/Hz Curve3
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
Selection of Curve
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
Set as a Low Forward Power threshold range
Set as a Reverse Power threshold range
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
Set as Reverse Power function
VT Fuse fail Input
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300GRelay Logic for Reverse Power Function
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
VT fuse fail Status Input
Offset reactance for Zone1
Zone1
Zone2
Offset reactance for Zone2
Directional Angle for Zone2
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
Directional Angle for Zone2
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
Relay Logic for Loss of Excitation Function
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
Enter Setting of NPS Threshold
Enter Time Dial Setting
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300GRelay Logic for Negative Sequence current Function
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
Select function “V”
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
Threshold value
Curve selection “C1”
VT fuse fail status input
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
K = 0.25Normal Inverse Curve
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
Select function “C”
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
Threshold value
Curve selection “C1”
VT fuse fail status input
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
K = 0.2Normal Inverse Curve
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
0-95% SEF
100% SEF
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: SEL300G
Under Freq. function
Under Freq. function
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Test Equipment
• Make : DOBLE
• Model : F6150
Software
• F6TesT Version 2.21-1165
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
F6150 Connections:
CT ConnectionsPT Connections
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
SEL300 Connections:PT ConnectionsCT Connections
Connections of 4th Voltage for 100% SEF
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Testing of Over Excitation Function (24)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
VA
VB
VC
I1
I2
I3
SEL
Test Circuit: Over Excitation Function Test
Source Configurations:3V X 3I
CT Inputs
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
• Inverse Time Curve Test
Tests conducted:
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Use “VFChar” Module for Characteristic Search Test
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Curve3 selection
Enter Time Dial
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Curve3 for Testing
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Expected Curve
Actual Curve from relay
Phasor
Select “ABC” Fault for testing
Relay settings:V/Hz = 1PUCurve = 3Time Dial = 1
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Testing of Reverse Power Function (32)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Reverse Power Protection (32R): Example1
G D Y
GT
GCB
Gen Set
G D Y
GT
GCB
Gen Set
CB1
CB2
CB3
CB4
CB
5
TL Line
TL Line
MW
MW
Healthy Prime-mover
Failed Prime-mover
MVAR
MVAR
E
E
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Reverse Power Protection (32R): Example2
G D Y
GT
GCB
Gen Set
G D Y
GT
GCB
Gen Set
CB1
CB2
CB3
CB4
CB
5
TL Line
TL Line
MW
MW
Healthy Prime-mover
Failed Prime-mover
MVAR
MVAR
E
E
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Reverse Power Protection (32R): Example3
G D Y
GT
GCB
Gen Set
CB1 CB3
CB
5
TL LineMW
Failed Prime-mover
MVAR
E
Active Power Import from Grid sources
Grid
GridMW
MW
MW
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Reverse Power Protection (32R): Example4
GD YTR1
GCB
Gen Set
Failed Prime-mover
MVAR
E
Only Reactive Power Export to Loads
CB1 CB2
D YTR2
CB3 CB4
MC
B5CB6
Load
sLo
ads
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
VA
VB
VC
I1
I2
I3
SEL
Test Circuit: Reverse Power Function Test
Source Configurations:3V X 3I
CT Inputs
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
• Pickup Test
• Time Test
Tests conducted:
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Use “RAMP” Module for Pickup Test
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Pickup Test @ Unity PF:
MW- MW
- MVAR
MVAR
Watts = VA = 952.87W
- MVAR
MVAR
MW- MW
IExpected = 1A
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Pickup Test @ Unity PF:Vn = 110VIn = 5APF = 1 (Unity)PN = (1.7325*0.11*1000*5) = 952.87watts%PSet = 20% of PN
PSet = (952.87 * 20)/(PF*100) = 190.5wattsIExpected = (190.5)/(1.7325*0.11*1000*PF) = 1A
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Enter Expected Value = 1A Enter “Action”details
Pickup
Actual Operating Values
IA@180o
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Pickup Test @ 0.8 lag PF:
MW- MW
- MVAR
MVAR
Watts = 762.3W
- MVAR
MVAR
MW- MW
IExpected = 1.15A
VA = 952.87VA
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Enter Expected Value = 1.15A Enter “Action”details
Pickup
Actual Operating Values
IA@150o
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Pickup Test @ 0.8 lead PF:
MW- MW
- MVAR
MVAR
Watts = 762.3W
- MVAR
MVAR
MW- MW
IExpected = 1.15AVA = 952.87VA
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Enter Expected Value = 1.15A Enter “Action”details
Pickup
Actual Operating Values
IA@210o
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Use “SSIMUL” Module for Time Test
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
TExp = 200ms
TAct = 262ms
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Testing of Loss of Excitation Function (40G)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
VA
VB
VC
IA
IB
IC
SEL
Test Circuit: Field Failure Function Test
Source Configurations:3V & 3I
3V
3I
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
• Characteristic Search Test
• Characteristic Time Test
• RCA (MTA) Test
Tests conducted:
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Use “ZChar” Module for Characteristic Search Test
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Zone1 setting = 20.4Ohms
Zone2 setting = 30.5Ohms
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Show Phasors: fault voltage & current of “ABC” fault
Blue color shows expected characteristic and pink color shows actual tested characteristic
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Click on Oscillograph: Shows, voltage & current waveform of “ABC” fault
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Zone1 setting = 20.4Ohms
Zone2 setting = 30.5OhmsOffset = -3.5 Ohms
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Show Phasors: fault voltage & current of “ABC” fault
Blue color shows expected characteristic and pink color shows actual tested characteristic
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Use “ZTime” Module for Characteristic Time Test
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Show Phasors: fault voltage & current of “ABC” fault
Results Table shows; Zone1 time is 0.1s & Zone2 time is 0.4s
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
SEL300G: Field Failure Function Testing
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
SEL300G: Field Failure Function Testing
LED Indicator operated
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Use “ZMTA” Module for Characteristic MTA (RCA) Test
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Fault type “ABC” selected for testing
Angle Boundary (Theta1)
Angle Boundary (Theta2)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
SEL300G: Field Failure Function Testing
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Testing of Negative Sequence Function (46)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Negative Sequence Protection (46)
Ia
Ic
Ib
Ia
Ic
Ib
IaIc
Ib
+VE Seq. -VE Seq. Zero Seq.
Sequence Components
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
G D Y
GT
GCB
Gen Set
MWMVAR
E
3
46
Operate: I2Measure>I2Set
Sys
MVARMW
F1
Negative Sequence Protection (46)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
G D Y
GT
GCB
Gen Set3
46
Operate: I2Measure>I2Set
F1
Negative Sequence Protection (46)
33
IR @ 0o
IY @ 120O
IB @ 240O
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
I1@0o
I2@120o
I3@240o
SEL
Test Circuit: Negative Phase Seq. Function Testing
Source Configurations:3I
3I
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
• Inverse Time Curve Test
Tests conducted:
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Use “IChar” Module for Characteristic Search Test
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Curve selection
Enter Time Dial
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Inverse Curve for Testing
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Blue color line shows “Expected curve” & Pink color line shows “Actual tested curve”
Phasors shows symmetrical componentsvalue (i.e. I1, I0 & I2)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Testing of Voltage Controlled Over Current Function (51VC)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Voltage Controlled over current function (51VC):
Normally Protection applied for Directly connected Generators where system voltage collapse drastically falls below set value (VSet) during faults.
Voltage Dependent Over Current Protection (51V)
G GCB
D Y
3
51VC Y Y
CB1 3
51
D YCB2 3
51
CB2 3Motpro
MVT
F1
F26.37 MVA11KVPF = 0.8, Xd”=36.4%, Xd’=26%Xd = 231%
1.5MVA, 11KV/0.415KV, %Z = 4.9%
1.5MVA, 11KV/0.415KV, %Z = 4.9%
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
V/Vs
I*/ [I>]
0.2 0.8
0.2
1.0
51V-Voltage Controlled
Vmeasured < VsetIpickup = (k*Iset)T = (0.14*T) / ((Ipickup)0.02-1)
Vmeasured > VsetIpickup = (Iset)T = (0.14*T) / ((Ipickup)0.02-1)
Voltage Dependent Over Current Protection (51V)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
VA
VB
VC
IA
IB
IC
SEL
Test Circuit: Voltage Controlled O/C Function Testing
Source Configurations:3V & 3I
3V
3I
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
• Inverse Time Curve Test
Tests conducted:
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Use “IChar” Module for Characteristic Search Test
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Curve selection
Enter Time Dial
Relay Settings:I> = 0.5*InCurve = C1Time Dial = 1V1 = 50VL-NV2 = 25VL-N
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Characteristic created for testing
Relay Settings:I> = 0.5*InCurve = C1Time Dial = 1V1 = 50VL-NV2 = 25VL-N
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Injected Voltage to relay
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Display Phasors
Blue color shows expected characteristic and pink color shows actual tested characteristic
Right click on check box to enable voltage O/P
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Testing of Voltage Restrained Over Current Function (51VR)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Voltage Restrained over current function (51VR):
Normally Protection is applicable when Generator is connected to system through GT.
Voltage Dependent Over Current Protection (51V)
G GCB3
51VC Y Y
VT
D Y
D YCB1 3
51
D YCB2 3
51
CB2 3
Motpro
M
F1
F2
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
VA
VB
VC
IA
IB
IC
SEL
Test Circuit: Voltage Restrained O/C Function Testing
Source Configurations:3V & 3I
3V
3I
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
V/Vs
I*/ [I>]
0.2 0.8
0.2
1.0
51V-Voltage restrained Vmeasured > Vset2Ipickup = (Iset)
Vmeasured < Vset1Ipickup = (k*Iset)
Vset1 < Vmeasured < Vset2
Slope region
Voltage Dependent Over Current Protection (51V)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
• Inverse Time Curve Test
Tests conducted:
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Use “IChar” Module for Characteristic Search Test
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Curve selection
Enter Time Dial
Relay Settings:I> = 1*InCurve = C1Time Dial = 1V1 = 50VL-NV2 = 25VL-N
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Characteristic created for testing
Relay Settings:I> = 1*InCurve = C1Time Dial = 1V1 = 50VL-NV2 = 25VL-N
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Injected Voltage to relay
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Display Phasors
Blue color shows expected characteristic and pink color shows actual tested characteristic
Right click on check box to enable voltage O/P
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Testing of 0-95% Stator Earth Fault Function (64R1/59GN)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Stator Ground Fault Protection (59GN): Resistor Ground
Maximum Ground Fault Amps = (Line to Neutral Voltage)-------------------------------------
(NGR Resistance)
VLN = 21000/1.7325
100 Ohms, 10s
IFIF PTR = 21000/240V
CTR = 20/1A
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Stator Ground Fault Protection (59GN): Impedance Ground (NGT)
VLN = 21000/1.7325KVPri = 21kVKVSec = 0.240kVKVA = 70KVA R = 0.913 Ohms Full Load current in Primary wdg = 3.33A Ground Fault Impedance = 3640.004 Ohms
IF
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
VA
VB
VC
VN
SEL
Test Circuit: 0-95% SEF Function Testing
Source Configurations:4V
3V
4th V@50Hz
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
• Pickup Test
• Time Test
Tests conducted:
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Use “RAMP” Module for Pickup Test
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
4th Voltage used
Expected value = 5VActual value = 5.3V
Pickup Value = 5V
Action details for Voltage Ramp
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Use “SSIMUL” Module for Time Test
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Ground Fault condition
Display Phasor
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Ground Fault condition
Display Waveforms (Analogue & Digital Channels)
4th Voltage
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Actual trip time = 1s
Relay Output (Open to Close contact)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Testing of 100% Stator Earth Fault Function (64R2/27TN)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Stator Ground Fault Protection (27TN)
3rd HarmonicCurrent circulate
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Stator Ground Fault Protection (27TN): 3RD
Harmonic Under Voltage Method3rd Harmonic Under voltage relay
3rd Harmonic Voltage at Neutral End reduced
3rd Harmonic Voltage at Neutral End reduced
IF
3rd harmonic voltage dropBecause capacitanceIs shorted
IF
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
VA
VB
VC
VN
SEL
Test Circuit: 100% SEF Function Test
Source Configurations:4V
3V
4th V@150Hz
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
• Pickup Test
• Time Test
Tests conducted:
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Use “RAMP” Module for Pickup Test
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
4th Voltage used @ 150Hz Freq.
Expected value = 1VActual value = 1.2V
Pickup Value = 1.2V
Action details for Voltage Ramp
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Use “SSIMUL” Module for Time Test
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Ground Fault condition close to Neutral
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Actual trip time = 0.55s
Relay Output (Open to Close contact)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
SEL300G: 100%SEF Function Testing
LED Indicator operated
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Testing of Under Frequency Function (81UF)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
VA
VB
VC
IA
IB
IC
SEL
Test Circuit: Under Freq. Function Test
Source Configurations:3V & 3I
3V
3I
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
• Pickup Test
• Time Test
Tests conducted:
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Use “RAMP” Module for Pickup Test
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Freq. of Voltage sources
Expected value = 48.5HzActual value = 48.498Hz
Pickup Value = 48.5Hz
Action details for Freq. Ramp
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Use “SSIMUL” Module for Time Test
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Under Frequency condition (48Hz Freq. for Voltage sources)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Actual trip time = 0.33s
Relay Output (Open to Close contact)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Testing of Over Frequency Function (81O/F)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
VA
VB
VC
IA
IB
IC
SEL
Test Circuit: Over Freq. Function Test
Source Configurations:3V & 3I
3V
3I
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
• Pickup Test
• Time Test
Tests conducted:
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Use “RAMP” Module for Pickup Test
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Freq. of Voltage sources
Expected value = 51HzActual value = 51.0002Hz
Pickup Value = 51.0002Hz
Action details for Freq. Ramp
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Use “SSIMUL” Module for Time Test
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Over Frequency condition (51Hz Freq. of Voltage sources)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Actual trip time = 93.9ms
Relay Output (Open to Close contact)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
SEL300G: 100%SEF Function Testing
LED Indicator operated
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Training to L&T Power at Doble Training Center