Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Brief Introduction for Automated Relay Testing

Kamin DaveManager – Marketing & Protection Applications

DOBLE ENGINEERING COMPANY, INDIA

kdave@doble.com

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Protection Relay Testing:

Testing of Generator Protection Relay type SEL300G

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Under & Over Voltage Protection (27/59)Negative sequence Protection (46)Reverse & Low Forward Power Protection (32)Over Excitation Protection (24)Over & Under Freq. Protection (81O/81U)Under Impedance Protection (21)Loss of Excitation Protection (40G)100% Stator E/F Protection (27TN/64G2)

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Out of Step Protection (78)Voltage Restrained O/C Protection (51VR)Voltage Controlled O/C Protection (51VC)Rotor E/F Protection (64R)Breaker Failure ProtectionGenerator Differential Protection (87D)Ground differential Protection (87N)95% Stator E/F Protection (59GN/64G1)

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Primary & Backup Protection

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Rotor Earth Fault Protection

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Characteristic plotted in F6TEST2.21 software for testing

Load Encroachment characteristic plotted

Zone2 Reach

Zone1 Reach

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Select “D” from List

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

GCB Status Close Input

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Breaker close input & VT fuse fail input

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

VT fuse fail Status Input

Characteristic selection

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

V/Hz Curve1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

V/Hz Curve2

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

V/Hz Curve3

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Selection of Curve

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Set as a Low Forward Power threshold range

Set as a Reverse Power threshold range

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Set as Reverse Power function

VT Fuse fail Input

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300GRelay Logic for Reverse Power Function

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

VT fuse fail Status Input

Offset reactance for Zone1

Zone1

Zone2

Offset reactance for Zone2

Directional Angle for Zone2

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Directional Angle for Zone2

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Relay Logic for Loss of Excitation Function

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Enter Setting of NPS Threshold

Enter Time Dial Setting

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300GRelay Logic for Negative Sequence current Function

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Select function “V”

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Threshold value

Curve selection “C1”

VT fuse fail status input

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

K = 0.25Normal Inverse Curve

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Select function “C”

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Threshold value

Curve selection “C1”

VT fuse fail status input

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

K = 0.2Normal Inverse Curve

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

0-95% SEF

100% SEF

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Under Freq. function

Under Freq. function

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Test Equipment

• Make : DOBLE

• Model : F6150

Software

• F6TesT Version 2.21-1165

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

F6150 Connections:

CT ConnectionsPT Connections

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

SEL300 Connections:PT ConnectionsCT Connections

Connections of 4th Voltage for 100% SEF

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Testing of Over Excitation Function (24)

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

VA

VB

VC

I1

I2

I3

SEL

Test Circuit: Over Excitation Function Test

Source Configurations:3V X 3I

CT Inputs

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

• Inverse Time Curve Test

Tests conducted:

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Use “VFChar” Module for Characteristic Search Test

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Curve3 selection

Enter Time Dial

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Curve3 for Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Expected Curve

Actual Curve from relay

Phasor

Select “ABC” Fault for testing

Relay settings:V/Hz = 1PUCurve = 3Time Dial = 1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Testing of Reverse Power Function (32)

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Reverse Power Protection (32R): Example1

G D Y

GT

GCB

Gen Set

G D Y

GT

GCB

Gen Set

CB1

CB2

CB3

CB4

CB

5

TL Line

TL Line

MW

MW

Healthy Prime-mover

Failed Prime-mover

MVAR

MVAR

E

E

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Reverse Power Protection (32R): Example2

G D Y

GT

GCB

Gen Set

G D Y

GT

GCB

Gen Set

CB1

CB2

CB3

CB4

CB

5

TL Line

TL Line

MW

MW

Healthy Prime-mover

Failed Prime-mover

MVAR

MVAR

E

E

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Reverse Power Protection (32R): Example3

G D Y

GT

GCB

Gen Set

CB1 CB3

CB

5

TL LineMW

Failed Prime-mover

MVAR

E

Active Power Import from Grid sources

Grid

GridMW

MW

MW

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Reverse Power Protection (32R): Example4

GD YTR1

GCB

Gen Set

Failed Prime-mover

MVAR

E

Only Reactive Power Export to Loads

CB1 CB2

D YTR2

CB3 CB4

MC

B5CB6

Load

sLo

ads

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

VA

VB

VC

I1

I2

I3

SEL

Test Circuit: Reverse Power Function Test

Source Configurations:3V X 3I

CT Inputs

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

• Pickup Test

• Time Test

Tests conducted:

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Use “RAMP” Module for Pickup Test

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Pickup Test @ Unity PF:

MW- MW

- MVAR

MVAR

Watts = VA = 952.87W

- MVAR

MVAR

MW- MW

IExpected = 1A

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Pickup Test @ Unity PF:Vn = 110VIn = 5APF = 1 (Unity)PN = (1.7325*0.11*1000*5) = 952.87watts%PSet = 20% of PN

PSet = (952.87 * 20)/(PF*100) = 190.5wattsIExpected = (190.5)/(1.7325*0.11*1000*PF) = 1A

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Enter Expected Value = 1A Enter “Action”details

Pickup

Actual Operating Values

IA@180o

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Pickup Test @ 0.8 lag PF:

MW- MW

- MVAR

MVAR

Watts = 762.3W

- MVAR

MVAR

MW- MW

IExpected = 1.15A

VA = 952.87VA

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Enter Expected Value = 1.15A Enter “Action”details

Pickup

Actual Operating Values

IA@150o

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Pickup Test @ 0.8 lead PF:

MW- MW

- MVAR

MVAR

Watts = 762.3W

- MVAR

MVAR

MW- MW

IExpected = 1.15AVA = 952.87VA

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Enter Expected Value = 1.15A Enter “Action”details

Pickup

Actual Operating Values

IA@210o

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Use “SSIMUL” Module for Time Test

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

TExp = 200ms

TAct = 262ms

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Testing of Loss of Excitation Function (40G)

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

VA

VB

VC

IA

IB

IC

SEL

Test Circuit: Field Failure Function Test

Source Configurations:3V & 3I

3V

3I

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

• Characteristic Search Test

• Characteristic Time Test

• RCA (MTA) Test

Tests conducted:

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Use “ZChar” Module for Characteristic Search Test

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Zone1 setting = 20.4Ohms

Zone2 setting = 30.5Ohms

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Show Phasors: fault voltage & current of “ABC” fault

Blue color shows expected characteristic and pink color shows actual tested characteristic

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Click on Oscillograph: Shows, voltage & current waveform of “ABC” fault

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Zone1 setting = 20.4Ohms

Zone2 setting = 30.5OhmsOffset = -3.5 Ohms

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Show Phasors: fault voltage & current of “ABC” fault

Blue color shows expected characteristic and pink color shows actual tested characteristic

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Use “ZTime” Module for Characteristic Time Test

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Show Phasors: fault voltage & current of “ABC” fault

Results Table shows; Zone1 time is 0.1s & Zone2 time is 0.4s

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

SEL300G: Field Failure Function Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

SEL300G: Field Failure Function Testing

LED Indicator operated

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Use “ZMTA” Module for Characteristic MTA (RCA) Test

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Fault type “ABC” selected for testing

Angle Boundary (Theta1)

Angle Boundary (Theta2)

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

SEL300G: Field Failure Function Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Testing of Negative Sequence Function (46)

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Negative Sequence Protection (46)

Ia

Ic

Ib

Ia

Ic

Ib

IaIc

Ib

+VE Seq. -VE Seq. Zero Seq.

Sequence Components

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

G D Y

GT

GCB

Gen Set

MWMVAR

E

3

46

Operate: I2Measure>I2Set

Sys

MVARMW

F1

Negative Sequence Protection (46)

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

G D Y

GT

GCB

Gen Set3

46

Operate: I2Measure>I2Set

F1

Negative Sequence Protection (46)

33

IR @ 0o

IY @ 120O

IB @ 240O

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

I1@0o

I2@120o

I3@240o

SEL

Test Circuit: Negative Phase Seq. Function Testing

Source Configurations:3I

3I

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

• Inverse Time Curve Test

Tests conducted:

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Use “IChar” Module for Characteristic Search Test

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Curve selection

Enter Time Dial

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Inverse Curve for Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Blue color line shows “Expected curve” & Pink color line shows “Actual tested curve”

Phasors shows symmetrical componentsvalue (i.e. I1, I0 & I2)

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Testing of Voltage Controlled Over Current Function (51VC)

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Voltage Controlled over current function (51VC):

Normally Protection applied for Directly connected Generators where system voltage collapse drastically falls below set value (VSet) during faults.

Voltage Dependent Over Current Protection (51V)

G GCB

D Y

3

51VC Y Y

CB1 3

51

D YCB2 3

51

CB2 3Motpro

MVT

F1

F26.37 MVA11KVPF = 0.8, Xd”=36.4%, Xd’=26%Xd = 231%

1.5MVA, 11KV/0.415KV, %Z = 4.9%

1.5MVA, 11KV/0.415KV, %Z = 4.9%

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

V/Vs

I*/ [I>]

0.2 0.8

0.2

1.0

51V-Voltage Controlled

Vmeasured < VsetIpickup = (k*Iset)T = (0.14*T) / ((Ipickup)0.02-1)

Vmeasured > VsetIpickup = (Iset)T = (0.14*T) / ((Ipickup)0.02-1)

Voltage Dependent Over Current Protection (51V)

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

VA

VB

VC

IA

IB

IC

SEL

Test Circuit: Voltage Controlled O/C Function Testing

Source Configurations:3V & 3I

3V

3I

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

• Inverse Time Curve Test

Tests conducted:

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Use “IChar” Module for Characteristic Search Test

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Curve selection

Enter Time Dial

Relay Settings:I> = 0.5*InCurve = C1Time Dial = 1V1 = 50VL-NV2 = 25VL-N

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Characteristic created for testing

Relay Settings:I> = 0.5*InCurve = C1Time Dial = 1V1 = 50VL-NV2 = 25VL-N

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Injected Voltage to relay

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Display Phasors

Blue color shows expected characteristic and pink color shows actual tested characteristic

Right click on check box to enable voltage O/P

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Testing of Voltage Restrained Over Current Function (51VR)

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Voltage Restrained over current function (51VR):

Normally Protection is applicable when Generator is connected to system through GT.

Voltage Dependent Over Current Protection (51V)

G GCB3

51VC Y Y

VT

D Y

D YCB1 3

51

D YCB2 3

51

CB2 3

Motpro

M

F1

F2

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

VA

VB

VC

IA

IB

IC

SEL

Test Circuit: Voltage Restrained O/C Function Testing

Source Configurations:3V & 3I

3V

3I

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

V/Vs

I*/ [I>]

0.2 0.8

0.2

1.0

51V-Voltage restrained Vmeasured > Vset2Ipickup = (Iset)

Vmeasured < Vset1Ipickup = (k*Iset)

Vset1 < Vmeasured < Vset2

Slope region

Voltage Dependent Over Current Protection (51V)

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

• Inverse Time Curve Test

Tests conducted:

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Use “IChar” Module for Characteristic Search Test

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Curve selection

Enter Time Dial

Relay Settings:I> = 1*InCurve = C1Time Dial = 1V1 = 50VL-NV2 = 25VL-N

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Characteristic created for testing

Relay Settings:I> = 1*InCurve = C1Time Dial = 1V1 = 50VL-NV2 = 25VL-N

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Injected Voltage to relay

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Display Phasors

Blue color shows expected characteristic and pink color shows actual tested characteristic

Right click on check box to enable voltage O/P

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Testing of 0-95% Stator Earth Fault Function (64R1/59GN)

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Stator Ground Fault Protection (59GN): Resistor Ground

Maximum Ground Fault Amps = (Line to Neutral Voltage)-------------------------------------

(NGR Resistance)

VLN = 21000/1.7325

100 Ohms, 10s

IFIF PTR = 21000/240V

CTR = 20/1A

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Stator Ground Fault Protection (59GN): Impedance Ground (NGT)

VLN = 21000/1.7325KVPri = 21kVKVSec = 0.240kVKVA = 70KVA R = 0.913 Ohms Full Load current in Primary wdg = 3.33A Ground Fault Impedance = 3640.004 Ohms

IF

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

VA

VB

VC

VN

SEL

Test Circuit: 0-95% SEF Function Testing

Source Configurations:4V

3V

4th V@50Hz

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

• Pickup Test

• Time Test

Tests conducted:

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Use “RAMP” Module for Pickup Test

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

4th Voltage used

Expected value = 5VActual value = 5.3V

Pickup Value = 5V

Action details for Voltage Ramp

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Use “SSIMUL” Module for Time Test

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Ground Fault condition

Display Phasor

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Ground Fault condition

Display Waveforms (Analogue & Digital Channels)

4th Voltage

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Actual trip time = 1s

Relay Output (Open to Close contact)

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Testing of 100% Stator Earth Fault Function (64R2/27TN)

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Stator Ground Fault Protection (27TN)

3rd HarmonicCurrent circulate

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Stator Ground Fault Protection (27TN): 3RD

Harmonic Under Voltage Method3rd Harmonic Under voltage relay

3rd Harmonic Voltage at Neutral End reduced

3rd Harmonic Voltage at Neutral End reduced

IF

3rd harmonic voltage dropBecause capacitanceIs shorted

IF

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

VA

VB

VC

VN

SEL

Test Circuit: 100% SEF Function Test

Source Configurations:4V

3V

4th V@150Hz

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

• Pickup Test

• Time Test

Tests conducted:

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Use “RAMP” Module for Pickup Test

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

4th Voltage used @ 150Hz Freq.

Expected value = 1VActual value = 1.2V

Pickup Value = 1.2V

Action details for Voltage Ramp

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Use “SSIMUL” Module for Time Test

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Ground Fault condition close to Neutral

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Actual trip time = 0.55s

Relay Output (Open to Close contact)

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

SEL300G: 100%SEF Function Testing

LED Indicator operated

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Testing of Under Frequency Function (81UF)

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

VA

VB

VC

IA

IB

IC

SEL

Test Circuit: Under Freq. Function Test

Source Configurations:3V & 3I

3V

3I

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

• Pickup Test

• Time Test

Tests conducted:

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Use “RAMP” Module for Pickup Test

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Freq. of Voltage sources

Expected value = 48.5HzActual value = 48.498Hz

Pickup Value = 48.5Hz

Action details for Freq. Ramp

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Use “SSIMUL” Module for Time Test

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Under Frequency condition (48Hz Freq. for Voltage sources)

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Actual trip time = 0.33s

Relay Output (Open to Close contact)

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Testing of Over Frequency Function (81O/F)

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

VA

VB

VC

IA

IB

IC

SEL

Test Circuit: Over Freq. Function Test

Source Configurations:3V & 3I

3V

3I

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

• Pickup Test

• Time Test

Tests conducted:

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Use “RAMP” Module for Pickup Test

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Freq. of Voltage sources

Expected value = 51HzActual value = 51.0002Hz

Pickup Value = 51.0002Hz

Action details for Freq. Ramp

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Use “SSIMUL” Module for Time Test

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Over Frequency condition (51Hz Freq. of Voltage sources)

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Actual trip time = 93.9ms

Relay Output (Open to Close contact)

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

SEL300G: 100%SEF Function Testing

LED Indicator operated

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Training to L&T Power at Doble Training Center