Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Brief Introduction for Automated Testing of LFDC101/102 Relay

Kamin DaveManager – Marketing & Protection Applications

South Asia & Middle EastDOBLE ENGINEERING COMPANY, INDIA

kdave@doble.com

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Protection Relay Testing:

Testing of LFDC101/102Relay by using F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: LFDC101/102

High speed directional comparison protection using signaling channel

Distance Zone Backup

Switch On to Fault Protection

Voltage Transformer supervision

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: LFDC101/102

Operating time of Directional comparison unit is 12 to 15ms

Operating time of Distance zone (Backup) is adjustable

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: LFDC101/102

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: LFDC101/102

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: LFDC101/102

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: LFDC101/102

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: LFDC101/102

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: LFDC101/102

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: LFDC101/102

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: Measuring Principle

RA RBCommunication(Signaling betn two relays)

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: Measuring Principle

Carrier scheme supervised by Mho elementIf there is fault in Line & fault impedance falls under preset value then Both relays will send carrier signals to each otherScheme is normally applied as a primary protection for short line length (<5km)

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: Measuring Principle

F1 External fault (F1) in Forward direction

IA = - IBIA + IB = 0

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: Measuring Principle

F1

External fault (F1) in Forward direction

IA

IB

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: Measuring Principle

F1

External fault (F1) in Forward direction

ZA

ZB

ZF

ZF

Forward Direction

Reverse Direction

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: Measuring Principle

F1 External fault (F1) in Reverse direction

Both currents are zero in Radial feeder IA = 0IB = 0

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: Measuring Principle

External fault (F1) in Reverse direction

ZA ZB

ZFZF

Reverse Direction

S1 S2

RA RB

F1

IA IB

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: Measuring Principle

F1 Internal fault (F1) in Forward direction

IA

IB

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: Measuring Principle

F1 Internal fault (F1) in Forward direction

ZA

ZBZF

ZF

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: Measuring Principle

ZA

ZB ZF

ZF

RF

RF

Kn = 0.75

Internal Fault: Fault measurement for Phase to Ground faults

Kn = 0.75

R in Ohms

X in Ohms

R in Ohms

X in Ohms

RA

RB

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: Measuring Principle

Internal fault (F1) in Forwarddirection& fault feeding is from End A

F1 F2

Internal fault (F2) in Forwarddirection& fault feeding is from End B

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: Measuring Principle

Internal fault (F1) in Forward direction & Fault feeding is from source “S1”

ZA ZB

ZFZF

S1RA RBF1

RC RDZC ZD

ZF

ZF

Relay “RC” will operate on Back Zone

IA IB

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: Measuring Principle

ZA

ZB ZF

ZF

Relay Operating time faster (12 to 15ms) when carrier signal receive & impedance falls under preset value during internal faults

R in Ohms

X in Ohms

R in Ohms

X in Ohms

RA

RB

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: Measuring Principle

ZA

ZB ZF

ZF

Relay Operating time based on time delay set in relay when carrier signal NOT receive & impedance falls under preset value during internal faults

R in Ohms

X in Ohms

R in Ohms

X in Ohms

RA

RB

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

LFDC Relay for Line1

LFDC Relay for Line2

220KV GETCO S/S

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

220KV GACL S/S

LFDC Relay for Line1

LFDC Relay for Line2

PLCC Cabinet

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Communication through PLCCPLCC: Power Line Carrier Communication (PLCC) is used to communicate devices between substations.The Audio frequency is carried out by a carrier frequency and the range of carrier frequency is 24kHz to 500kHzWave trap: It is an inductor of rating in mili henry. It is connected in series with the power transmission line. It blocks the high frequency carrier waves (24kHz to 500kHz) and let Power waves (50Hz – 60Hz) to pass through.

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Communication through PLCCCoupling Capacitor: It provides low impedance path for carrier energy to H.V. line and blocks the power frequency circuit by being a high impedance path.HF Cable: It is used to carry to signal from PLCC cabinet to switchyard

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Communication through PLCCPLCC Cabinet: It indoor equipment. It is divided in two parts;

TransmitterReceiver

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Communication through PLCCWave trap or Line trap

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Carrier send Carrier receive

Carrier receive Carrier send

Communication through PLCC

Exchange SignalsBoth are thinking same

Scheme Stable on External Faults

220KV GETCO S/S 220KV GACL S/S

F1RA RB

Delta V = 0Delta I = 0IA - IB = Delta IIA = IB VA - VB = Delta VVA = VB

IA IB

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Carrier send Carrier receive

Carrier receive Carrier send

Communication through PLCC

Scheme Operates on Internal Faults

220KV GETCO S/S 220KV GACL S/S

F1RA RB

Delta V = ?Delta I = ?IA - IB = Delta IIA not equal to IBVA - VB = Delta VVA not equal to VB

Exchange SignalsBut both are thinking in different

IA IB

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Carrier send Carrier receive

Carrier NOT receive Carrier send

Communication through PLCC

Scheme Operates on Internal Faults

220KV GETCO S/S 220KV GACL S/S

F1RA RB

Delta V = ?Delta I = ?IA - IB = Delta IIA not equal to IBVA - VB = Delta VVA not equal to VB

No Exchange of SignalsBut both are thinking in different

IA IB

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Communication through PLCC

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Communication through PLCC

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: LFDC101/102

Relay Settings:Location: GETCO and GACL Ends, DahejLine length: 1.5kmLine voltage: 220kV (Line1)• Z = 0.2 Ohms• tZ = 0.2s• Line Angle = 78 Deg.• Kn = 0.75

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Test Equipment

• Make : DOBLE

• Model : F6150

Software

• F6TesT Version 2.19-1065

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

VA

VB

VC

I1

I2

I3

Relay

Test Circuit:

Source Configurations:3V X 3I

CT Inputs

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

• Zone Time Test during carrier signal received from other end

• Zone Time Test (Distance Zone Backup)

• Zone Characteristic Test

• SOTF Test

• Stability Test of scheme

Test Conducted:

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Zone Time Test during Carrier signal received

from other end

Use “ZTime” Module

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Location Level

Right click on Mouse & click on “Append” and create new Location

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Level

Right click on Mouse & click on “Append” and create new Relay

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Parameters

Click on “Add” button & select “Impedance” function

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Click here & then click on “New Zone” button

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select “MHO” & enter relay settings

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Click on “Yes”

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Characteristic created for Ph-N fault

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Characteristic created for Ph-Ph & 3-Ph faults

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Click on “Yes”

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Right Click on “Mouse” & Click on “Append” to create new Test plan

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Right click on “Mouse” & click on “Append” to create new test module for testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select “Z-Time” Module from list

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Press on “OK” & Create New Test Definition

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select characteristic from list

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Enter Test current (i.e. 2.3A)

Select Test Method

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select Trigger (i.e. Open to Close)

Enter Prefault duration & Max. fault duration

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Click Test points in R-X Plane for “Ph-Ph” fault

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Right Click on check box

Green/Red Points areActual Points have been tested

Blue color shows;Expected characteristic

Line Angle

Relay operated in 12 to 13ms

Carrier signal received from other end on E19 & E20terminals of Relay

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Display shows relay tripped on DIR (A-N fault)

Time Test: Directional Comparison

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Zone Time Test (Distance Zone Backup)

Use “ZTime” Module

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Right Click on check box

Green/Red Points areActual Points have been tested

Blue color shows;Expected characteristic

Line Angle

Relay operated in 250 to 260ms

Carrier signal NOT received from other end on E19 & E20 terminals of Relay

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Right Click on check box

Green/Red Points areActual Points have been tested

Blue color shows;Expected characteristic

Line Angle

Relay operated in 250 to 260ms

Carrier signal NOT received from other end on E19 & E20 terminals of Relay

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Display shows relay tripped on Z (T) (BC fault)

Time Test: Distance Backup Zone

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Characteristic Test

Use “ZChar” Module

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Right click on “Mouse” & Press on “Append”& Create new Test Module

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select “Z-Char” Module from list

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Double click on “Characteristic Test”

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Press on “OK” & Create New Test Definition

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select characteristic from list

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select Test Method

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Enter Test current (i.e. 2.3A)

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select Trigger (i.e. Open to Close)

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Enter Angle Boundary for test (Say; start from 0 to 180 Degree)

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Enter Angle Boundary for test (Say; start from 0 to 180 Degree)

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Green Points (white lines) areActual Points have been tested

Blue color shows;Expected characteristic

Line Angle

Right Click on check box

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Right Click on check box

Green Points (white lines) areActual Points have been tested

Blue color shows;Expected characteristic

Line Angle

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

SOTF Test

Use “SSIMUL” Module

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select SSIMUL Module from list

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

State1 set for SOTF

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Operating time recorded 47ms

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Scheme Testing

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Comm Channel

Protectionunder test

GPS Synch: End to End Testing

Test PUTT/POTT Schemes

1pps Signal 1pps SignalF6910+F6885+F6895 Option

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Communication through PLCC

Counter for Carrier send signals

Counter for Carrier receive signals

Both end relays tripped on 13ms

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

F6TEST2.21-1157 Advance Line Version

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery