1. overview
Post on 13-Dec-2015
5 Views
Preview:
DESCRIPTION
TRANSCRIPT
WASCO SALES GAS METERING SYSTEM
Emerson Proprietary2
System OverviewSystem Overview
The Metering system is sub-divided into 2 major sub-systems. These are:
1.) Field Mounted Metering Streams Which includes 3 no. USM with upstream meter tube & PT, TT & 2 no. of GC.
2.) Control System ( Flow Computer installed in Control Panel) with Supervisory System
Emerson Proprietary3
System OverviewSystem Overview
Emerson Proprietary4
System OverviewSystem Overview
Emerson Proprietary5
System OverviewSystem Overview
Emerson Proprietary6
System OverviewSystem OverviewField Mounted Metering System
The proposed Sales gas metering system upgrade is intended to replace the existing 3 Orifice metering streams for measurement of Natural Gas With Daniel Ultrasonic Meter. Major components in the system are
1.) Ultrasonic flow meters with upstream meter tube for each stream.
2.) Temperature Transmitter with RTD in Thermo well for each stream.
3.) Pressure transmitter for each Stream
4.) Junction box.
5.) Gas Chromatograph -2No.
Emerson Proprietary7
System OverviewSystem OverviewControl System with SCADA
Major components are
1.) Control Panel (1800 mm (H) * 800 mm (W) * 600 mm (D) – 1no.
2.) Flow Computer (FloBoss S600+) - 2no.(Duty –Standby)
3.) Laser Printer - 2no.
4.) Ethernet Switches. - 2no.
5.) Supervisory Computer – 1no.
Emerson Proprietary8
System OverviewSystem Overview
Emerson Proprietary9
System Overview - ComponentsSystem Overview - Components
Ultrasonic flow MeterDaniel 3400 Gas Ultrasonic Flow Meter is designed to accurately measure Gas products in accordance with International standard.
Meter Performance Flow calibrated accuracy is ±0.1% of reading relative to lab over entire flow calibration range (Qmin-Qmax) Accuracy is ±0.3% including lab uncertainty Repeatability is ±0.05% of reading for 5 to 100 fps Meter meets or exceeds AGA 9 (2007) performance specifications
Emerson Proprietary10
System Overview - ComponentsSystem Overview - Components
Temperature Transmitter The Temperature Transmitter ismounted on each stream as per hook up diagram for measurement of line temperature. The Measurement elements is Pt 100 in accordance to IEC 60751 tolerance class A. The RTD’s are 4 wire. Signal from RTD is connected to the remote mounted Temperature transmitter. The O/p of Temperature Transmitter is 2 wire 4 - 20 mA HART.
Pressure TransmitterThe Pressure transmitters will be mounted on each stream a for measurement of in line pressure. The Inline pressure is used for pressure compensation of the flow. Transmitter Output: 4 -20 mA, HART Compliant.Two-valve integral pressure manifold is used with 3051 transmitters. The first valve provides instrument isolation. The second valve allows venting, draining, or calibration through the test port. The Manifold is available with 1/2–14 NPT male process connections.
Emerson Proprietary11
System Overview - ComponentsSystem Overview - ComponentsGas Chromatograph.Two No. of Gas Chromatographs shall be installed near the inlet header with 3 sided shelter. Both the GC shall take the gas sample from common sample probe installed on 1”nozzle on inlet header. There are three major parts of GC. Sample Probe. Sample Conditioning System. Gas Chromatograph Analyzer.
Sample handling has two basic functions: To supply the analyzer with a sample representative of actual process. The sample as analyzed must be essentially the same as the process. To provide calibration gases as a reference so the system can calibrate itself.
Extractive sampling is often complex. The sample is gathered by a probe at Take-off and transported to shelter for conditioning and analysis. Sample conditioning removes particulates and moisture without altering the sample's chemistry or concentration. A probe filter blocks particulates from entering the system. .
Emerson Proprietary12
System Overview - ComponentsSystem Overview - ComponentsGas Chromatograph Analyzer.The Model 700XA is a high-speed gas chromatograph (GC) system that is engineered to meet specific field application requirements based on typical natural gas stream composition and anticipated concentration of the selected components. In its standard configuration, the Model 700 can handle up to four streams: typically, three for sample and one for calibration. The Model 700 system consists of below major parts:
Analyzer assemblyThe analyzer assembly includes airless oven, the columns, TCDs/TCDs, a preamplifier, power supply, stream switching valves, analytical valves and solenoidsController AssemblyThe electronics assembly includes the electronics and ports necessary for signal processing, instrument control, data storage, personal computer (PC) interface, and telecommunications. This assembly allows the user to use MON2020 to control the GC.
Emerson Proprietary13
System Overview - ComponentsSystem Overview - Components
Control Panel
The Metering Control Panel shall be placed in the Control cabin (Safe area). One Enclosures of size 1800 (H) x 800 (W) x 600 (D) shall be used to house the Flow computer (Floboss S600+) The Flow computer cabinet shall be equipped with Surge protectors, MCB’s, TB’s etc. An Instrument earth (IE), Shield earth (IS) and Power earth (PE) shall be provided in the cabinet.
For more details pls. Refer 97151018-3-050 Control Panel GA drawing and 97151018-3-051Interconnecting Diagram
Emerson Proprietary14
System Overview - ComponentsSystem Overview - ComponentsEmerson Floboss S600+ Flow Computer Flow computer is used for computation of corrected flow with pressure & temperature compensation &reporting . It has dedicated IO card as per types of inputs.
The FloBoss S600+ Flow Computer is a panel-mount flow computer designed specifically to measure hydrocarbon liquid and gas where versatility and accuracy matter. The standard features of the S600+ make it ideal for fiscal measurement, custody transfer, batch loading, and meter proving applications.
The S600+ allows to configure multi-stream, multi-station applications, enabling simultaneous measurement of meter liquids and gasses.
The S600+ is designed for use either as a stand-alone flow computer or as a system component. The intelligent I/O modules fit both gas and liquid applications and typically support two dual-pulsed streams and a header. Adding I/O modules (up to a maximum of three) allows to configure up to six dual-pulsed streams or up to 10 single-pulsed streams and two headers.
Emerson Proprietary15
System Overview - ComponentsSystem Overview - ComponentsSCADAOne machine of HP Make are provided which acts as a SCADA computer. This computer are referred as Metering Supervisory Computers which communicates with Flow Computers on Ethernet through Cisco switches. SCADA software with license of 300 Tags is installed on the supervisory Computer. SCADA software acts as the primary interface for metering supervision, entry and display of data.
The supervisory computer shall have as a minimum the following facilities: Alphanumeric display of all data, control requests. Process data Flow Meter & GC diagnostic data Trends Keyboard for data entry commands, etc.; Alarm indication & acceptance facility. Reports. The supervisory computer, as a minimum, performs the following functions and where necessary, display the relevant data: Form a database of selected alarms, measured and calculated variables, obtained via the data bus from the stream measurement flow computers.
Emerson Proprietary16
System Overview System Overview
Metering Operation PhilosophyAll Metering Streams are installed with inlet & outlet manual isolation valves. These valves shall be fully opened when particular stream is required to be online & can be remained close when stream to be isolated. Also for each stream drain & vent valves are provided.
Emerson Proprietary17
System Overview System Overview SCADA SYSTEMNetwork/InterfaceCommunication between the flow computer and supervisory system shall be realized via Ethernet connection. The protocol that shall be used for the communication is Modbus TCP/IPThe scheme is a graphical representation of the network how it shall be connected.
Emerson Proprietary18
System Overview System Overview SecuritiesThere are three types of Securities for SCADA operation1. Administrator: By accessing this level (Login), user have full rights for configuration, modification, Set Point change, acknowledge alarms.2. Engineer: By accessing this level (Login), user have rights for Set point change & acknowledge alarms etc. User cannot do the configuration, modification.3. Operator: By accessing this level (Login), user have limited access like acknowledge alarms & monitoring the data on SCADA. User cannot do configuration, modification, Set point Change.
Graphics The SCADA application is divided in to various graphics representing the complete skid. The graphics available in the application are the following: Skid Overview System Architecture Trending graphic Skid Alarms graphic Reports
Emerson Proprietary19
System Overview System Overview
Hands-On: Familiarization with the Metering Skid and Components
Emerson Proprietary20