Instrumentation and control
Instrumentation and control system is designed for minimum local manning and operator attention.
The basic need of the instrumentation us for safeoperation and efficient functioning of the plant.
This can be achieved by installing optimum number measurement, indicating, transmitting and controllinginstruments for all required parameters of the plants(e.g. pressure, level, temperature, flow etc.)
-
8/3/2019 08. Control & Instrumentation
3/41
3
BASIC COMPONENTS OF ACONTROL SYSTEM
S ensor Also often called as Primary Element.Acquires information about the status of the process variables.Typical examples:RTD/thermocouples (for temperature measurements),
Capacitance type cells (for liquid level /draft /pressuremeasurements), etc.
Controller The Brain or Heart Of the control system (the decision maker).
It is the hardware element with Built-in capacity for performing theonly task requiring some forms of Intelligence.Typical examples:Electronic controllers, digital computers used as controller.
-
8/3/2019 08. Control & Instrumentation
4/41
4
BASIC COMPONENTS OF ACONTROL SYSTEM
Transmitter S econdary Element.Responsible of passing the information acquired by the sensor tocontroller and sending the controller decision to the final controlelement.Measurement and control signals may be transmitted or aselectrical signals.Typical examples:Electrical transmitters.
Final control elementHave the task of actually implementing the control commandissued by the controller on the process.Typical examples:Control valve, variable speed motors, electric motors etc.
-
8/3/2019 08. Control & Instrumentation
5/41
5
BASIC COMPONENTS OF ACONTROL SYSTEM
The importance of these components is that they performthe three basic operations that must be present in everycontrol system:1. Measurement:Measuring the variable to be controlled is usually done by
the combination of sensor and transmitter.2 . Decision:Based on the measurements and the set point, thecontroller must then decide what to do to maintain thevariable at its desired value.3 . Action:
As the result of the controller's decision, the system mustthen take an action. This is usually accomplished by thefinal control element.
-
8/3/2019 08. Control & Instrumentation
6/41
6
CONTROL SYSTEM
I/O CARDS
PROCESSOR
I/O CARDS
OPERATOR STATIONS
ENGG
STATION
-
8/3/2019 08. Control & Instrumentation
7/41
7
Basic Parameters
Measurement & Control of followingParameters are essential for Instrumentation
PressureTemperatureFlowLevel
-
8/3/2019 08. Control & Instrumentation
8/41
8
TAPPING POINT S
GASES
STEAMGASES
LIQUIDS
-
8/3/2019 08. Control & Instrumentation
9/41
9
PressurePressure measurements are one of the most common measurements
required in the boiler .These range from very low -1 500 mmwcDraft to very high steam pressure 1 50 kg/cm 2 .That includedifferent type of media like steam ,water, fuel oil, air, gas eachwith varying degree of accuracy and reliability.Pressure varies depending on altitude above sea level, weather pressure fronts and other conditions. The measure of pressure is,therefore, relative and pressure measurements are stated aseither gauge or absolute. A gauge pressure device will indicatezero pressure when bled down to atmospheric pressure (i.e.,gauge pressure is referenced to atmospheric pressure). Gaugepressure is denoted by a (g) at the end of the pressure unit [e.g.,kPa (g)].Absolute pressure includes the effect of atmospheric pressure
with the gauge pressure. It is denoted by an (a) at the end of thepressure unit [e.g., kPa (a)]. An absolute pressure indicator wouldindicate atmospheric pressure when completely vented down toatmosphere - it would not indicate scale zero.Absolute Pressure = Gauge Pressure + Atmospheric PressureThe majority of pressure measurements in a plant are gauge.
-
8/3/2019 08. Control & Instrumentation
10/41
10
Pressure
-
8/3/2019 08. Control & Instrumentation
11/41
11
Pressure
Pressure measuring devicesThe common pressure measuring devicesused in IJT boilers areDiaphragm, capsule gauges for lowpressure measurementBourdon tube gauges for medium and highpressureS mart type Pressure Transmitter withrequired range
-
8/3/2019 08. Control & Instrumentation
12/41
12
Pressure
-
8/3/2019 08. Control & Instrumentation
13/41
13
Pressure
Installation:Pressure Gauges are installed on site usingaccessories as follows:S yphonsS unbber S eal2 way manifoldThese are protective devices for pressuremeasuring instrument from surges & pulsations.These devices used as per applicationrequirement
-
8/3/2019 08. Control & Instrumentation
14/41
14
Pressure Gauges (Normal Installation)
-
8/3/2019 08. Control & Instrumentation
15/41
15
Pressure Gauges along with S yphon
-
8/3/2019 08. Control & Instrumentation
16/41
16
Pressure Gauges along with S unbber:
-
8/3/2019 08. Control & Instrumentation
17/41
17
Pressure Transmitter (Normal Installation)
-
8/3/2019 08. Control & Instrumentation
18/41
18
Temperature Measurement
Temperature is measured by following:Temperature Gauge:
1. Mercury inS
teel type2 . Bi-Metallic3 . Gas Filled
Temperature S ensors:1. RTD2 . Thermocouple
-
8/3/2019 08. Control & Instrumentation
19/41
19
Temperature Measurement
Installation:Temperature Gauges / S ensors are
installed on site using thermowell.
It is a protective devices for temperature
measuring instrument from damages.
-
8/3/2019 08. Control & Instrumentation
20/41
20
Temperature Gauge / ELEMENT(Normal Installation)
-
8/3/2019 08. Control & Instrumentation
21/41
21
Temperature Transmitter (Normal Installation)
-
8/3/2019 08. Control & Instrumentation
22/41
-
8/3/2019 08. Control & Instrumentation
23/41
23
Flow Measurement
Installation:Flow sensors are installed in line of the fluid to create DP &hook-ed up with transmitter for measuring DifferentialPressure, which corresponds to flow:
Q = K1* (P/T ) * D P W here,DP = differential pressure across the flow elementP = Main Steam Pressure
T = Main steam temperatureK1 = ConstantQ = Compensated flow
-
8/3/2019 08. Control & Instrumentation
24/41
24
Flow Transmitter (S TEAM)
-
8/3/2019 08. Control & Instrumentation
25/41
25
Flow Transmitter (AIR)
-
8/3/2019 08. Control & Instrumentation
26/41
26
Drum Level
STEAM
W ATER
H: Drum Center to CenterDistance
h: Height of water insidepressurized drum
HP LP
CondensatePot withconstant Headas a wet Leg
D1 = W ater Density Inside DrumD2 = W ater Density in Leg
HP LP = (P+hD1g) (P+HD2g)Diff. Pr., P= hD1g HD2g = hD1 HD2( W here P,h and H are measured in mm of water)(D1 & D2 are in gm/cc)Hence, h = P + HD2
D1
-
8/3/2019 08. Control & Instrumentation
27/41
27
Drum Level
D rum Level Control MethodS ingle ElementThree Element
Shrink &
Swell EffectS hrink : When S team Flow Decreases
Drum Level DecreasesS well : When S team Flow Increases
Drum Level Increases
Basic ElementsDrum LevelS team FlowFeed Water Flow
-
8/3/2019 08. Control & Instrumentation
28/41
28
Drum Level
-
8/3/2019 08. Control & Instrumentation
29/41
29
Transmitter
Typical Basic Operation of Transmitter
Sensing Element + Transducer =Transmitter unit
SENSINGELEMENT INDICATION TRANSDUCER
-
8/3/2019 08. Control & Instrumentation
30/41
30
Transmitter
Transmitters are generally use is of 2 wire type.This is the most widely used method for transmitter connections .There are three basic
elements in this loop, namely Power S
upply ,transmitter and the receiving instrument .Theyare connected in series and the transmitter actsas a current regulator in the series circuit . Thecurrent in the series circuit changes with respectto change in process parameter. This simplifiescabling and reduces erection and cable cost.
-
8/3/2019 08. Control & Instrumentation
31/41
3 1
Transmitter
Normal Pressure Transmitter
-
8/3/2019 08. Control & Instrumentation
32/41
32
Transmitter
Differential Pressure Transmitter
-
8/3/2019 08. Control & Instrumentation
33/41
33
TROUBLE S HOOTING OFTRAN S MITTER
I. POTENTIAL SOURCELOOP WIRING
II . HIGH OUTPUTPOTENTIAL S OURCE :1.PRIMARY ELEMENT2 .IMPUL S E PIPING3 .TRAN S MITTER ELECTRONIC S4 .S EN S ING ELEMENT
-
8/3/2019 08. Control & Instrumentation
34/41
34
TROUBLE S HOOTING OFTRAN S MITTER
III . LOW OUTPUT OR NO OUTPUTPOTENTIAL S OURCE :
1. PRIMARY ELEMENT2 . LOOP WIRING3 . IMPUL S E PIPING
4 . S EN S ING ELEMENT
-
8/3/2019 08. Control & Instrumentation
35/41
35
TROUBLE S HOOTING OFTRAN S MITTER
IV .TRANSMITTER D OES NOTCHARACTERIZE PROPERLY
POTENTIAL S OURCE :1.PRE SS URE S OURCE /CORRECTION2 .mA METER3 .POWER S UPPLY4 . TRAN S MITTER ELECTRONIC S5 . S EN S ING ELEMENT
-
8/3/2019 08. Control & Instrumentation
36/41
36
Control Valve
Being the Final Control Element in a system is not aneasy job.To start with, Control Valves are blamed for any and all
problems that crop up in the process.Control Valve are subjected to corrosion, high velocity,cavitations, flashing liquids, cryogenic temperatures,abrasion, high temperatures and thermal shock.Control Valve are expected not only to throttle alongthrough all this, but most likely, you are also being askedto act as a block valve and shut off tight .
-
8/3/2019 08. Control & Instrumentation
37/41
37
Control Valve Classification
Rotary Motion
Linear Motion
Butterfly
Eccentric Plug
Ball
Swing Through
Lined
EccentricSegmented
Full
V-Notch
Globe
Diaphragm
Pinch or Clamp
Globe
Angle
3-Way
Single Seated
Double Seated
Split body
Control
Valve
-
8/3/2019 08. Control & Instrumentation
38/41
38
Control Valve Flow Characteristics
-
8/3/2019 08. Control & Instrumentation
39/41
39
Control ValveLeakage Classifications
Class I:Identical to Class II, III, and IV in construction and design intent, but noactual shop test is made.
Class II:Intended for double-port or balanced singe-port valves with a metal pistonring seal and metal-to-metal seats. Air or water at 45 to 60 psig is the testfluid. Allowable leakage is 0 .5% of the rated full open capacity.
Class III:Intended for the same types of valves as in Class II.
Allowable leakage is limited to 0 .1 % of rated valve capacity.
Class IV:Intended for single-port and balanced single-port valves with extra-tightpiston seals and metal-to-metal seats. Leakage rate is limited to 0 .0 1% of rated valve capacity.
-
8/3/2019 08. Control & Instrumentation
40/41
40
Control ValveLeakage Classifications
Class V:Intended for the same types of valves as Class IV.The test fluid is water at 1 00 psig or operating pressure.Leakage allowed is limited to 5 X 10 ml per minute per
inch of orifice diameter per psi differential.Class VI:Intended for resilient-seating valves.The test fluid is air or nitrogen. Pressure is the lesser of 50 psig or operating pressure.The leakage limit depends on valve size and rangesfrom 0 .1 5 to 6 .75 ml per minute for valve sizes 1through 8 inches.
-
8/3/2019 08. Control & Instrumentation
41/41
4 1
Basic Control Loops in BOILER
Pre ssu re Cont rolF W h ead er p ressu reF u rnac e D raftCombustion Cont rol (M ain St em Pre ssu re)Soot Blow er
D e-aerato r
Leve l cont rolD rum Leve l
o Singl e El em ento Th ree El em ent
D e-aerato rCBD
Te mp eratu re Cont rolSup er H eat ed St eam