Alcatel OmniPCX 4400
SECTION 1
Presentation
Ed.02
-
A L C ET L
Alcatel OmniPCX 4400
Section 1 - Presentation
Section 1 - Presentation
SUMMARY
MI CabinetGeneral information ....................................................................................... 1. 3
1. Overview................................................................................................ 1. 32. Reference to other modules................................................................... 1. 6
Hardware description...................................................................................... 1. 71. Cabinet dimensions ............................................................................... 1. 72. Cherokee PE3657/20 power supply ....................................................... 1. 73. Batteries................................................................................................. 1. 94. Battery alarm......................................................................................... 1. 95. Protective ground .................................................................................. 1.10
M2/M3 CabinetSpecific technical data..................................................................................... 1.11
1. Introduction............................................................................................ 1.112. M2 and M3 cabinet features.................................................................. 1.113. Power supply.......................................................................................... 1.144. Consumption .......................................................................................... 1.145. Interface type......................................................................................... 1.166. Lithium battery based board list ........................................................... 1.187. Installation equipment features ............................................................ 1.198. Electromagnetic compatibility................................................................ 1.239. Safety standards .................................................................................... 1.2310. Network connection ............................................................................. 1.2411. Environment......................................................................................... 1.24
Installation recommendations ........................................................................ 1.251. Introduction............................................................................................ 1.252. Room layout ........................................................................................... 1.263. PABX installation conditions.................................................................. 1.274. Rectifier installation conditions ............................................................. 1.295. Battery installation condition ................................................................ 1.296. Installation thermal constraints ............................................................ 1.307. Recommended equipment ..................................................................... 1.30
MI CabinetCabling diagram ............................................................................................. 1.33
1. Mains connection and distribution in the cabinet ................................. 1.332. 48V distribution in the cabinet .............................................................. 1.343. Modem ................................................................................................... 1.36
Disassembly/Assembly - Power supply ........................................................... 1.37
Ed.02 Ref.3BA19919FRAA 1.1
-
A L C ET L
Alcatel OmniPCX 4400
Section 1 - Presentation
1. Removing the power supply .................................................................. 1.372. Installing the power supply ................................................................... 1.373. Hot replacement of a rectifier module .............................................. 1.38
1.2 Ref.3BA19919FRAA Ed.02
-
A L C ET L
Alcatel OmniPCX 4400
Section 1 - Presentation MI CabinetGeneral information
44A03350000A000AAEN
MI CabinetGeneral informationEdition: 02
1. Overview
1.1. Cabinet description
The MI (Integrated Cabinet) contains an OmniPCX 4400 switch and all the equipment necessary forautonomous operation. It is based on the design of the M3 cabinet.
Figure 1 : External view of the MI cabinet
Frontpanel Rear panel
The MI cabinet contains:
- one (or two) ACT shelves,
- a built-in power supply,
- a backup battery,
Ed.02 Ref.3BA19919FRAA 1.3
-
A L C ET L
Alcatel OmniPCX 4400
MI Cabinet Section 1 - PresentationGeneral information
- a cooling fan shelf,
- a remote maintenance unit (option),
- an external music unit (option),
- a TA to access remote applications (option).
The MI cabinet is designed to accommodate a single PBX. The system is configured according to cus-tomer requirements.
An optional extension cabinet that can accommodate a peripheral shelf may be added. In this case,the terms "standard cabinet" and "extension cabinet" are used.
1.2. Standard MI cabinet
The standard MI cabinet is intended to accommodate a main shelf. Depending on customer require-ments, this main shelf can be an ACT28 or an ACT14.
If is it an ACT14 shelf, a second ACT14 can be added in the same cabinet. This second shelf is aperipheral shelf.
1.3. Extension MI cabinet (option)
The extension MI cabinet is intended to accommodate a peripheral shelf. It does not have a remotemaintenance or external music unit. It has its own power supply, batteries and fan shelf.
Depending on customer requirements, this peripheral shelf can be an ACT28 or an ACT14.
If it is an ACT14 shelf, a second ACT14 can be added in the same cabinet. This second shelf is aperipheral shelf.
1.4. Remote maintenance equipment (option)
Remote maintenance is ensure by an RMA connection. The RMA board provides the function, theCBRMA unit provides the connection and the modem provides transmission.
For more information on the remote maintenance function, see module RMA/SRMA - General infor-mation.
1.4 Ref.3BA19919FRAA Ed.02
-
A L C ET L
Alcatel OmniPCX 4400
Section 1 - Presentation MI CabinetGeneral information
1.5. Internal view of the cabinet
Figure 2 : MI cabinets fitted with ACT28
TA
Fans
Power supply shelf
Main shelf
CBRMA connection unit
Music
Shelf
Fans
Power supply shelf
Pheripheral shelf
Shelf
Extension cabinet(optional)
Batteries Batteries
Standard cabinet
Ed.02 Ref.3BA19919FRAA 1.5
-
A L C ET L
Alcatel OmniPCX 4400
MI Cabinet Section 1 - PresentationGeneral information
2. Reference to other modules
The MI cabinet is described in the following modules:
- Hardware description (see module MI Cabinet - Hardware description),
- Specific technical data (see module M2/M3 cabinet - Specific technical data),
- Installation recommendations (see module M2/M3 cabinet - Installation recommendations),
- Installation Procedure (see module MI Cabinet - Installation procedure),
- Cabling diagram (see module MI Cabinet - Cabling diagram),
- Removing / Installing the power supply (see module MI Cabinet - Disassembly/Assembly - Powersupply),
1.6 Ref.3BA19919FRAA Ed.02
-
A L C ET L
Alcatel OmniPCX 4400
Section 1 - Presentation MI CabinetHardware description
44A03350000A041AAEN
MI CabinetHardware descriptionEdition: 02
1. Cabinet dimensions
Figure 3 : MI cabinet dimensions
1500mm
570mm515
mm
2. Cherokee PE3657/20 power supply
2.1. GeneralPower supply is ensured by a Cherokee PE3657/20 shelf. This power supply converts the 220V/50Hzmains into 48V DC (there is a 110V version).The 48V DC is distributed to the electronic boards via the shelves.The 48V DC is used for the cooling fans.The Cherokee PE3657/20 power supply charges the batteries.Depending on the power requirements of the customers configuration, the power supply shelf is fittedwith:
- 1 or 2 converter boards, if the mains voltage is 220V/50Hz,
- 2 or 4 converter boards, if the mains voltage is 110V/50Hz.
Ed.02 Ref.3BA19919FRAA 1.7
-
A L C ET L
Alcatel OmniPCX 4400
MI Cabinet Section 1 - PresentationHardware description
The Cherokee PE3657/20 power supply also switches over to the backup batteries in the event of amains failure.
2.2. 220 V version
Figure 4 : 220 V power supply shelf
D1
F1MAINS FUSE
FUSIBLE RESEAU
MAINS 230VRESEAU 230V
BATTERY BREAKER
DC OK
CC OK CC OK
II
II
Converter No 1
Converter No 0
Power supply operating LED
Module operating LEDGeneral power supply switch
Switch to isolate batteries Module switch
DISJONCTEUR BATTERIE
DC OK DC OK
1.8 Ref.3BA19919FRAA Ed.02
-
A L C ET L
Alcatel OmniPCX 4400
Section 1 - Presentation MI CabinetHardware description
2.3. 110 V version
Figure 5 : 110 V power supply shelf
D1
F1MAINS FUSE
FUSIBLE RESEAU
MAINS 230VRESEAU 230V
BATTERY BREAKER
DC OK
CC OK CC OK
II
II
Converter No 1
Converter No 0
Power supply operating LED
Module operating LEDGeneral power supply switch
Switch to isolate batteries Module switch
DISJONCTEUR BATTERIE
DC OK DC OK
3. Batteries
The backup batteries supply 48V from 4 12V cells. The batteries are housed in a drawer at the bottomof the cabinet.
Battery life
Depending on customer requirements, there are two types of battery:
- 15Ah providing 4 hour autonomy for a configuration with up to 190 users at 0.25 Erlang
- 38Ah providing 4 hour autonomy for a configuration with up to 500 users at 0.25 Erlang
The 15Ah batteries recharge within 20 hours.
The 38Ah batteries recharge within 22 hours.
4. Battery alarm
When the batteries (with built-in fuse) are almost completely discharged, the voltage drop causes thecabinet to shut down. The PSAL signal triggers shutdown of the system when battery voltage falls belowapproximately 45V. This guarantees a shutdown that damages neither the hardware nor the software.
The PSAL signal is generated by a small board located in the PSAL light. This light is located on thefront panel of the cabinet.
Ed.02 Ref.3BA19919FRAA 1.9
-
A L C ET L
Alcatel OmniPCX 4400
MI Cabinet Section 1 - PresentationHardware description
5. Protective ground
The protective ground must be connected to the MI cabinet by a terminal located on the 48V distributionterminal block.
This terminal enables electrical connection between the ground cable and the metal bracket to whichit is attached.
Electrical continuity is ensured in all metal parts of the MI cabinet by special bolting.
The MI cabinet accepts GN or GG type grounding.
1.10 Ref.3BA19919FRAA Ed.02
-
A L C ET L
Alcatel OmniPCX 4400
Section 1 - Presentation M2/M3 CabinetSpecific technical data
44A03350050A031AAEN
M2/M3 CabinetSpecific technical dataEdition: 02
1. Introduction
This module provides the following information:
- the cabinet features (weight, dimensions, etc.),
- the cabinet power supply,
- the consumption of the different components of the cabinet,
- the interface types (safety level),
- the list of boards requiring a lithium battery (including replacement instructions),
- the equipment features (rectifier, battery, PSAL) used with a complete installation,
- EMCs, safety standards and network connection,
- environment (storage, transportation, etc.).
2. M2 and M3 cabinet features
2.1. Presentation
2.1.1. M2 cabinet
The M2 cabinet is shown in the figure below:
Ed.02 Ref.3BA19919FRAA 1.11
-
A L C ET L
Alcatel OmniPCX 4400
M2/M3 Cabinet Section 1 - PresentationSpecific technical data
Figure 6 : M2 cabinet dimensions
515 mm (20.3 in)570 mm (22.5 in)
740 mm (29.1 in)
The average weight of the M2 cabinet is 70 kg.
2.1.2. M3 cabinet
The M3 cabinet is shown in the figure below:
1.12 Ref.3BA19919FRAA Ed.02
-
A L C ET L
Alcatel OmniPCX 4400
Section 1 - Presentation M2/M3 CabinetSpecific technical data
Figure 7 : M3 cabinet dimensions
515 mm (20.3 in) 570 mm (22.4 in)
1500 mm (59 in)
The average weight of the M3 cabinet is 110 kg.
Ed.02 Ref.3BA19919FRAA 1.13
-
A L C ET L
Alcatel OmniPCX 4400
M2/M3 Cabinet Section 1 - PresentationSpecific technical data
2.2. Cabinet capacities and limitationsM2 and M3 cabinets can support two shelf formats:
SHELVES 6U 12U
Back plane ACT ACT
Boards 14 boards (max.) 28 boards (max.)
3. Power supply
48 V is supplied by a power supply cabinet dedicated to the M2 cabinets.The max. overall consumption is about 1000 W.The PABX operating voltage must be between 45 V and 57 V.
4. Consumption
4.1. Cabinet board and fan consumptionThe cabinet board and fan consumption is given for a theoretical max. traffic of 1 erlang and for 0.25erlang.
Table 1 : Summary table
ACT SHELF BOARDS
- 48 VBOARDS
max. (1 erlang) 0,25 erlang
CPU3 step2 330 mA 330 mA
CPU5 step2 450 mA 450 mA
E&M-4TL 130 mA 130 mA
GPA 285 mA 285 mA
INTOF 160 mA 160 mA
MMS FD and SRMA 170 mA 170 mA
MMS MO and SRMA 355 mA 355 mA
OBCA 30 mA 30 mA
RMA 70 mA 70 mA
UA32 660 mA 491 mA
UA16 354 mA 270 mA
1.14 Ref.3BA19919FRAA Ed.02
-
A L C ET L
Alcatel OmniPCX 4400
Section 1 - Presentation M2/M3 CabinetSpecific technical data
ACT SHELF BOARDS
Z24-2 1204 mA 466 mA
Z12-2 662 mA 293 mA
LIOB 440 mA 440 mA
LIOX 390 mA 390 mA
VPS35 315 mA 315 mA
DID 135 mA 135 mA
LS/GS (NDDI2) 120 mA 120 mA
DPT1 140 mA 140 mA
4635H VOICE MAIL BOARDS
VPM35 360 mA 360 mA
SPA3 375 mA 375 mA
MSBI 194 mA 194 mA
VENTILATOR
Ventilator shelf (5 ventilators) 490 mA 490 mA
4.2. Consumption examples
4.2.1. M2 cabinet
The consumptions calculated below are given for configurations with the following trunks:
Table 2 : PCM trunks
PCM TRUNKS
Configuration type Consumption (48V)
30 trunks, 48 UA, 48 Z 2.1 A
30 trunks, 80 UA, 96 Z 3.6 A
30 trunks, 112 UA, 156 Z 5.7 A
30 trunks, 160 UA, 276 Z 9 A
Ed.02 Ref.3BA19919FRAA 1.15
-
A L C ET L
Alcatel OmniPCX 4400
M2/M3 Cabinet Section 1 - PresentationSpecific technical data
Table 3 : ISDN trunks
ISDN TRUNKS
Configuration type Consumption (48V)
8 T0/S0, 48 UA, 48 Z 2 A
1 T2, 3 T0/S0, 64 UA, 48 Z 2.7 A
2 T2, 6 T0/S0, 80 UA, 96 Z 4.4 A
2 T2, 6 T0/S0, 112 UA, 156 Z 6.8 A
4.2.2. M3 cabinet
The consumptions calculated below are given for configurations with the following trunks:
Table 4 : ISDN trunks
ISDN TRUNKS
Configuration type Consumption (48V)
3 T2, 9 T0/S0, 160 UA, 276 Z 10.7 A
3 T2, 9 T0/S0, 256 UA, 180 Z 10.6 A
4 T2, 12 T0/S0, 224 UA, 396 Z 14.8 A
6 T2, 18 T0/S0, 368 UA, 648 Z 22.5 A
4.3. Set consumption
Set consumption is as follows:
- Z set: 40 mA,
- UA set: 10 mA.
5. Interface type
In order not to lower the level of security, it is necessary to connect circuits of the same type togetherand to make sure that the constraints required for each type of circuit are respected in the means ofconnection.
The interface list is as follows (EN 41-003 and EN 60-950):
BOARD CLASSIFICATION
Z interface (2 wire analog set) Classified TRT (telephone network voltage)
Analog network line interface Classified TRT
1.16 Ref.3BA19919FRAA Ed.02
-
A L C ET L
Alcatel OmniPCX 4400
Section 1 - Presentation M2/M3 CabinetSpecific technical data
BOARD CLASSIFICATION
Tie line of RON/TRON type (E/M) Classified TRT
Tie line of L1 type Classified TRT
Tie line of 50 Hz type Classified TRT
Analog dedicated set interface Classified TBTS (very low safety voltage)
Digital dedicated set interface Classified TBTS
T0/S0 interface Classified TBTS
T1/T2 interface Classified TBTS
Ethernet interface Classified TBTS
Voice mail interface Classified TBTS
On hold music Classified TBTS
V24 interface Classified TBTS
Alarm relay interface Classified TBTS
Floppy disk drive interface Classified TBTS
Inter-shelves link interface Classified TBTS
Supply failure alarm interface Classified TBTS
Paging interface (2 wires) Classified TBTS
48 VDC interface Classified TBTS
Note: dedicated sets connected to the system have a classified TBTS interface.
Board classification
Name Description Reference Safety level
DID Analog direct in dialing 3BA 23181 TNV1
LS/GS Loop Start/GroundStart board
3BA 23171 TNV3
GS Ground Start card(option of LS/GS board)
3BA 23196 TNV3
DPT1 Dual port T1 3BA 23164 TNV1
E&M Analog Tie line trunk 3BA 23191 TNV1
UA 32 ICS 32 interfaces(digital sets)
3BA 53050 SELV
UA 16 ICS 16 interfaces 3BA 53084 SELV
Ed.02 Ref.3BA19919FRAA 1.17
-
A L C ET L
Alcatel OmniPCX 4400
M2/M3 Cabinet Section 1 - PresentationSpecific technical data
Board classification
Z12-2 ONS 12 ports 3BA 53071 TNV2
Z24-2 ONS 24 ports 3BA 53065 TNV2
CPU5 Main processor unit 5 3BA 27038 SELV
PCM2 PCM 2.048 Mbits/sboard
3BA 23064 SELV
PRA2 Primary rate accessboard
3BA 23076 SELV
Nx64 N x 64 Kbits/s board 3BA 23011 SELV
CPU3 Main processor unit 3 3BA 57162 SELV
LIOX Compression 3BA 23145 SELV
LIOB Network compressionwith basic ISDN access
3BA 23138 SELV
INTOF Remote PBX withmetallic and optical
in building connections
3BA 53118 SELV
GPA Signal processingboard without external
connection
3BA 53097 SELV
6. Lithium battery based board list
The following boards require a lithium battery to operate correctly:
Board Battery type
CPU3 Lithium battery (clock module)
VPS35 Lithium battery
VPM35 Lithium battery
GPA Lithium battery (RamCard)
To replace a battery, please comply with the following instructions:
1.18 Ref.3BA19919FRAA Ed.02
-
A L C ET L
Alcatel OmniPCX 4400
Section 1 - Presentation M2/M3 CabinetSpecific technical data
Danger of explosion if the battery is incorrectly replaced. Replace only with thesame or equivalent lithium battery type recommended by the manufacterer.Dispose of used batteries according to the manufacturer's instructions.
Remplacer uniquement avec une batterie au lithium du mme type ou d'untype quivalent recommend par le constructeur. Mettre au rebut les batteriesusages conformment aux instructions du fabricant. Il y a danger d'explosions'il y a remplacement incorrecte de la batterie.
CAUTION
ATTENTION
7. Installation equipment features
7.1. Rectifier
The rectifier must deliver a continuous current whose ripple complies with KAX9516 standard underan on load voltage between 47V and 54V, the intensity being set by the OPS.
Mains and "D curve" circuit breaker ratings are given in the following table:
RATINGRectifier nominal intensity(under 48V) Mains required (AC power
supply)"D curve" circuit breaker
16 A 1.3 kVA 1.8 kVA
25 A 2 kVA 2.8 kVA
40 A 3.2 kVA 4.5 kVA
7.2. Batteries
The two figures below give the battery autonomy:
Ed.02 Ref.3BA19919FRAA 1.19
-
A L C ET L
Alcatel OmniPCX 4400
M2/M3 Cabinet Section 1 - PresentationSpecific technical data
Figure 8 : Battery autonomy
1300
1200
500
0
100
200
300
400
600
700
800
900
1000
1100
1 3 4 5 6 7 82
Pow
er (W
)
Operating range (hours)
15 Ah
24 Ah
38 Ah
50 Ah
Steco batteries:Saphir 150 (15 A/h)Saphir 240 (24 A/h)Saphir 380 (38 A/h)Saphir 500 (50 A/h)
Fulmen batteries:PE 12015 (15 A/h)PE 12024 (24 A/h)PE 12038 (38 A/h)PE 12065 (50 A/h)
1.20 Ref.3BA19919FRAA Ed.02
-
A L C ET L
Alcatel OmniPCX 4400
Section 1 - Presentation M2/M3 CabinetSpecific technical data
Figure 9 : Battery autonomy (continued)
450
400
0
50
100
150
200
250
350
300
14012060 100400 2010 160 18080Operating range (minutes)
Pow
er (W
)
4 Ah
1.2 Ah
7.3. PSAL
When the batteries unload, the supply voltage decreases progressively. The PSAL (Power Supply Alarm)detects the threshold below which the PABX cannot operate. It generates a PSAL signal to the CPU. Onreception of this signal, the CPU shuts the PABX down. The PSAL detects mains recovery and authorizesthe CPU to operate again.
During normal operation, the green indicator light must be lit (PSAL idling).Remark: The PSAL is set ex-factory at 45 V.
Ed.02 Ref.3BA19919FRAA 1.21
-
A L C ET L
Alcatel OmniPCX 4400
M2/M3 Cabinet Section 1 - PresentationSpecific technical data
Figure 10 : Principle
Send PSALSend no PSAL
Rectifier alarm(PSAL)
Led and boardsupervision
48V
to PABXterminal block
The two figures below give the PSAL operating principle:
Figure 11 : Battery unload
54V
49V
47V
45V46V
42V44V
Battery operating range
Battery unloading into the system (1V voltage drop down included)
toleranceThreshold
90''(min.)
shutdown
chargercut off
Normal operation
10' (min.)PSAL
HiZ
V battPSAL INACTIVE
Powersupplyfailure
1.22 Ref.3BA19919FRAA Ed.02
-
A L C ET L
Alcatel OmniPCX 4400
Section 1 - Presentation M2/M3 CabinetSpecific technical data
Figure 12 : Powering up
54V
47V48V
42V
46V
ToleranceThreshold
PSAL
Hi Z
Vbatt PSAL INACTIVE
PSALACTIVATED
Converteractivation
Vbatt
8. Electromagnetic compatibility
The cabinet complies with the following standards:
- EN 55 022 (1987),
- EN 50 082-1 (1992),
- FCC part 68.
9. Safety standards
The cabinet complies with the following standards: IEC 950/EN 60950 (1992) + Amendment N 1+ Amendment N 2 (1993) + Amendment N 3 (1995) + UL1950 ed3 /CAN/CSA C22.2 N 95095ed03 + ED03.
Ed.02 Ref.3BA19919FRAA 1.23
-
A L C ET L
Alcatel OmniPCX 4400
M2/M3 Cabinet Section 1 - PresentationSpecific technical data
10. Network connection
The cabinet complies with FCC part 68 standard.
11. Environment
Storage, transportation and cabinet environment comply with the following standards:
- ETS 300 019 1.1,
- ETS 300 019 1.2,
- ETS 300 019 1.3.
1.24 Ref.3BA19919FRAA Ed.02
-
A L C ET L
Alcatel OmniPCX 4400
Section 1 - Presentation M2/M3 CabinetInstallation recommendations
44A03350050A001AAEN
M2/M3 CabinetInstallation recommendationsEdition: 02
1. Introduction
The PABX needs good environmental conditions to ensure optimum operation.
The purpose of this module is as follows:
- to provide installation recommendations for site components (PABX, rectifier and batteries),
- to provide installation thermal constraints,
- to indicate equipment for site safety.
A room layout is proposed, showing the possible locations for the equipment for a complete installa-tion.
The hardware is specified as follows:
- mobility of equipment: stationary,
- operating condition: continuous,
- protection class: I
- connection type: permanent,
- degree of pollution: 2,
- max. operating temperature: 35 C (95 F) without ventilator; 45 C (113 F) with ventilators.
CAUTION
M2 cabinet must be installed in a restricted access location.
ATTENTION
L'armoire M2 doit tre installe dans un local accsrestreint.
Ed.02 Ref.3BA19919FRAA 1.25
-
A L C ET L
Alcatel OmniPCX 4400
M2/M3 Cabinet Section 1 - PresentationInstallation recommendations
2. Room layout
The room where the PABX is installed must be big enough, clean, well-lit and easily accessible.
The room must be fitted out before the PABX installation. The room must be equipped with at leastfour power sockets.
The roommust be free from dust currents and with a ceiling height of around 2.5m (usual ceiling heightfor offices). Access must be easy for installation and maintenance of the hardware. Room length mustbe sufficient to contain 1 or 2 cabinet add-ons in line with the first cabinet.
A desk must be made available for the technician to facilitate system installation, as well as a filingcabinet for storing the documentation, back-ups and, where appropriate, the maintenance hardwarekit.
The room must not be fitted with a carpet requiring anti-static treatment.
1.26 Ref.3BA19919FRAA Ed.02
-
A L C ET L
Alcatel OmniPCX 4400
Section 1 - Presentation M2/M3 CabinetInstallation recommendations
Figure 13 : Example of room layout
Power supplypanel
Service cabinet
System terminal
Managementterminal
Printer
PABX
Mainframe
700 mm(27.6 in)
510 mm(20.1 in)
1710 mm (67.3 in)
telephone set
700 mm(27.6 in)
3. PABX installation conditions
3.1. EnvironmentThe PABX is designed to work in a well-ventilated office atmosphere. It has ventilation grills.
3.2. TemperatureIn operating conditions the temperature gradient must not exceed 20 C/hour (68 F/hour).
Ed.02 Ref.3BA19919FRAA 1.27
-
A L C ET L
Alcatel OmniPCX 4400
M2/M3 Cabinet Section 1 - PresentationInstallation recommendations
During storage, the temperature must be between -5 C (23 F) and 45 C (113 F). The temperaturegradient must not exceed 10 C/hour (50 F/hour).
During hardware transportation, the temperature must be between -13 F and 140 F. The temperaturegradient must not exceed 20 C/hour (68 F/hour).
3.3. Ventilation - Air conditioning
According to the premises chosen and the installation capacity, choose:
- either forced ventilation to avoid the accumulation of hot air close to the PABX,
- or air conditioning.
This air conditioning can be that of the building in which the room is located but certain precautionsmust be taken, such as:
- when the air conditioning is shut off, this must not produce a high rise in temperature,
- planning automatic restoration after mains recovery.
To overcome these problems, use air conditioning which is specific to the premises and powered by aback-up unit.
To ensure that the PABX operates properly, the main precautions to be taken are:
- choosing premises with the most favorable thermal conditions,
- ventilation and air conditioning on back-up unit,
- automatic ventilation and air conditioning restart as soon as the mains power supply has beenrestored,
- thermal alarm installation. In order to remedy an air conditioning system failure quickly, a devicesignaling an unusual temperature rise is necessary.
3.4. Hygrometry
The degree of hygrometry without condensation must be between 8% and 80%. The hygrometric va-riation must not exceed 30% per hour during operation and during transportation and 10% per hourfor storage.
The absolute hygrometry must be between 1g/m3 and 25g/m3.
3.5. Atmospheric pressure
The atmospheric pressure must be between 70 kPa and 106 KPa.
3.6. Radiation
Only radiation sources respecting the prevailing EMC standards can be located near the PABX (pho-tocopiers, transformers, electrical control panels, etc.).
In all cases, the PABX and sets must not be located in an electromagnetic field greater than 3 V/m.
1.28 Ref.3BA19919FRAA Ed.02
-
A L C ET L
Alcatel OmniPCX 4400
Section 1 - Presentation M2/M3 CabinetInstallation recommendations
3.7. Abnormal voltagesNo source of industrial parasites, whether repeated or accidental, electric or electrostatic, no telephoneor computer distribution line exposed to atmospheric disturbances must interfere with PABX operation.
3.8. LightingThe ambient electrical lighting must be sufficient to allow rapid intervention on the equipment. Inaddition, the rear and front panels of the PABX must be sufficiently lit and also the maintenance desk.In line with office premises, the average lighting level must be about 300 lux at 80cm from floor level.Avoid direct sunlight and prefer incandescent lighting or anti-interference fluorescent tubes. The ligh-ting sources must be powered by the back-up network if it exists.
3.9. Vibrations and shocksThe hard disk and diskette drives are the most sensitive to these two phenomena. The vibrations mustnot exceed 0.02 G with double amplitude less than 25 m. The shocks must be less than 0.1 G.
4. Rectifier installation conditions
Note: This paragraph does not apply to the MI cabinet.The rectifier can be located in a specific room or in the same room as the PABX provided that it meetsthe radiation standards and is at least 3 metres from the PABX, to avoid any radiation.If the rectifier is located in separate premises, these premises must meet the following conditions:
- no dust, acid fumes, corrosive atmosphere, different types of ducts (water, gas, electricity),
- temperature and hygrometry in line with the manufacturers standards,
- the power supply cabinet must be installed as near as possible to the rectifier,
- the distance between the rectifier and the PABX must not be too great to avoid oversizing ofthe power supply cables.
The nature, calibration and type of protection devices, emergency stop devices, conductor cross-sectionand type of canalisation must be defined in accordance with prevailing standards.
5. Battery installation condition
Nota: This paragraph does not apply to the MI cabinet.The batteries must be fitted in:
- a dry and well-ventilated room if they are lead-based or CdNi-based batteries,
- the same room as the PABX if they are sealed batteries.According to the type of battery, check the electrolyte level. If the batteries are delivered dry, fill themup with distilled water. It is essential to comply with the scheduled refill operation specified by themanufacturer.
Ed.02 Ref.3BA19919FRAA 1.29
-
A L C ET L
Alcatel OmniPCX 4400
M2/M3 Cabinet Section 1 - PresentationInstallation recommendations
For information on battery life, see module M2/M3 cabinet - Specific technical data.
6. Installation thermal constraints
IMPORTANT:
Make sure the air vents are not obstructed.
Figure 14 : Example: the M2 cabinet
Outlet
Outlet
Inlet
A room with air conditioning fulfils the conditions for ambient temperature below 35 C (95 F) or fornatural convection.
7. Recommended equipment
It is recommended that the premises be locked and the keys held by a single person.
7.1. Fire detection
It is recommended that the room be equipped with a smoke detection system by ionic analysis.
1.30 Ref.3BA19919FRAA Ed.02
-
A L C ET L
Alcatel OmniPCX 4400
Section 1 - Presentation M2/M3 CabinetInstallation recommendations
7.2. Fire protection
It is recommended that the room be equipped with a protection system using inert gas (systems usingwater projection or mechanical foam must be avoided).
7.3. Temperature alarm
A device for signalling abnormal temperature rise in the room can be of use in responding to airconditioning problems or abnormal conditions quickly.
All these devices are highly recommended given that the PABX and all its peripheral equipment re-present a significant investment and a security equipment.
Ed.02 Ref.3BA19919FRAA 1.31
-
A L C ET L
Alcatel OmniPCX 4400
M2/M3 Cabinet Section 1 - PresentationInstallation recommendations
1.32 Ref.3BA19919FRAA Ed.02
-
A L C ET L
Alcatel OmniPCX 4400
Section 1 - Presentation MI CabinetCabling diagram
44A03350000A051AAEN
MI CabinetCabling diagramEdition: 02
1. Mains connection and distribution in the cabinet
The mains cable, from the customer distribution terminal block, arrives at the power supply terminalblock.
The mains terminal block distributes the mains power to:
- the 48VDC power supply,
- a connection unit that receives the TA and external music power supply connectors.
Ed.02 Ref.3BA19919FRAA 1.33
-
A L C ET L
Alcatel OmniPCX 4400
MI Cabinet Section 1 - PresentationCabling diagram
Figure 15 : Mains distribution in the MI cabinet
Main shelf
UK or Europeantype connector
Mainsinput
clamp
3-wiremains cable
48V terminalblock
GroundPhaseNeutral
TA
External music
CM9 & modem
Detail: mains terminal block
Switch withLED
topower supply
Detail: mains connection unit
2. 48V distribution in the cabinet
The 48V is distributed from the terminal block located at the bottom rear of the cabinet.
The connections are made as follows :
1.34 Ref.3BA19919FRAA Ed.02
-
A L C ET L
Alcatel OmniPCX 4400
Section 1 - Presentation MI CabinetCabling diagram
Figure 16 : 48 V distribution
1
2
3
4
PSAL LED
Protective ground
Blue
Red
2
1
Brown
F4
F5
F2
F3
F1
PSAL
Batt
Entry
PSAL
- A48VLP
A48VP
1
Blue
Red
456
Brown
Battery connectionconnector
-A48VLP
A48VP
2
Blue
Red12
ACT shelf
Power supply shelf
5
Vbatt3
Black
- A48VLP
A48VP
3
Blue
Red
78
Fan shelf
6
8
7
4
3
9
PSAL
- A48VLP
A48VPFilter
Blue
Red
91011Brown
ACT shelf (option)
1011
1 a
- 48V+ 48V
BlueRed
CM9
4
Blue
Red
1312
12
13
Mini-plug
Filter
Connector
Fuse ratings: F1 to F4 : 20A; F5 : 4A; Batt : 20A.
Ed.02 Ref.3BA19919FRAA 1.35
-
A L C ET L
Alcatel OmniPCX 4400
MI Cabinet Section 1 - PresentationCabling diagram
3. Modem
The modem is mounted at the rear of the MI cabinet, above the 48V terminal block. It is supplied bythe DC/DC CM9 converter. This converter is supplied with a 48V input voltage.
Figure 17 : Modem connection
Modem
48V
CM9
9V connection
Attachment plate
Figure 18 : Detailed view of the CM9
1234
123
1
2
IN- 42->56V
IN+ 250 mA max
9V12V
DCACONOFF
Out 3.5V DC500mA max
Out+
Out-
Out 9V/12VAC**/DC4.2W max
Out+
Out-
ON
48V=
9V=
To modem
not usedfrom 48V
terminal block
1.36 Ref.3BA19919FRAA Ed.02
-
A L C ET L
Alcatel OmniPCX 4400
Section 1 - Presentation MI CabinetDisassembly/Assembly - Power supply
44A03350000A920AAEN
MI CabinetDisassembly/AssemblyPower supply
Edition: 02
Warning:Multiple power supply source. This equipment is connected to batteries. Carefullyfollow the instructions below:
1. Removing the power supply
Preliminary steps:
The PBX must be shut down (shutdown procedure completed).
- Open the mains isolating switch (on the electrical panel near the PBX),
- Set the mains power supply switch to the OFF position,
- The "DC OK/AC OK" power supply LEDS must be off,
- Open the battery breaker,
- Wait 2 minutes (for the capacitors to discharge),
- Disconnect the 48V connector at the rear of the power supply unit,
- Unscrew the 4 screws that hold the power supply in place,
- Remove the power supply unit from its housing.
2. Installing the power supply
- Position the power supply unit in its housing,
- Screw the 4 screws that hold the power supply in place,
- Connect the 48V connector to the rear of the power supply unit,
- Connect the mains cable to the mains terminal block,
- Close the mains isolating switch,
- Set the mains power supply switch to the ON position,
- The DC OK/AC OK power supply LEDS must come on,
Ed.02 Ref.3BA19919FRAA 1.37
-
A L C ET L
Alcatel OmniPCX 4400
MI Cabinet Section 1 - PresentationDisassembly/Assembly - Power supply
- Close the battery breaker.
3. Hot replacement of a rectifier module
In most cases, a rectifier can be hot replaced (replaced without cutting off the power supply).
- Open the rectifier switch,
- The rectifier DC OK / AC OK LED must be off,
- Completely remove the 2 attachment screws,
- Gently pull the rectifier forwards (1 or 2 cm),
- Wait 2 minutes (for the capacitors to discharge),
- Remove the rectifier,
- Insert the new rectifier,
- Attach the rectifier with the 2 attachment screws,
- Close the rectifier module switch,
1.38 Ref.3BA19919FRAA Ed.02
tocOverviewCabinet descriptionFigure 1 : External view of the MI cabinetStandard MI cabinetExtension MI cabinet (option)Remote maintenance equipment (option)Internal view of the cabinetFigure 2 : MI cabinets fitted with ACT28
Reference to other modulesCabinet dimensionsFigure 3 : MI cabinet dimensionsCherokee PE3657/20 power supplyGeneral220 V versionFigure 4 : 220 V power supply shelf110 V versionFigure 5 : 110 V power supply shelf
BatteriesBattery alarmProtective groundIntroductionM2 and M3 cabinet featuresPresentationM2 cabinetFigure 6 : M2 cabinet dimensionsM3 cabinetFigure 7 : M3 cabinet dimensions
Cabinet capacities and limitations
Power supplyConsumptionCabinet board and fan consumptionConsumption examplesM2 cabinetM3 cabinet
Set consumption
Interface typeLithium battery based board listInstallation equipment featuresRectifierBatteriesFigure 8 : Battery autonomyFigure 9 : Battery autonomy (continued)PSALFigure 10 : PrincipleFigure 11 : Battery unloadFigure 12 : Powering up
Electromagnetic compatibilitySafety standardsNetwork connectionEnvironmentIntroductionRoom layoutFigure 13 : Example of room layoutPABX installation conditionsEnvironmentTemperatureVentilation - Air conditioningHygrometryAtmospheric pressureRadiationAbnormal voltagesLightingVibrations and shocks
Rectifier installation conditionsBattery installation conditionInstallation thermal constraintsFigure 14 : Example: the M2 cabinetRecommended equipmentFire detectionFire protectionTemperature alarm
Mains connection and distribution in the cabinetFigure 15 : Mains distribution in the MI cabinet 48V distribution in the cabinetFigure 16 : 48 V distributionModemFigure 17 : Modem connectionFigure 18 : Detailed view of the CM9Removing the power supplyInstalling the power supplyHot replacement of a rectifier module