NHA80945.01 www.schneider-electric.com Altivar Process 900 NHA80945 01/2016 Altivar Process 900 CANopen Manual - VW3A3608, 618, 628 01/2016

Upload: truongkien

Post on 23-Apr-2018

225 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Altivar Process 900

NHA80945 01/2016

NH

A80

945.

01

www.schneider-electric.com

Altivar Process 900 CANopen Manual - VW3A3608, 618, 628

01/2016

Page 2: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

The information provided in this documentation contains general descriptions and/or technical character-istics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein. If you have any suggestions for improvements or amendments or have found errors in this publication, please notify us.

No part of this document may be reproduced in any form or by any means, electronic or mechanical, including photocopying, without express written permission of Schneider Electric.

All pertinent state, regional, and local safety regulations must be observed when installing and using this product. For reasons of safety and to help ensure compliance with documented system data, only the manufacturer should perform repairs to components.

When devices are used for applications with technical safety requirements, the relevant instructions must be followed.

Failure to use Schneider Electric software or approved software with our hardware products may result in injury, harm, or improper operating results.

Failure to observe this information can result in injury or equipment damage.

© 2015 Schneider Electric. All rights reserved.

2 NHA80945 01/2016

Page 3: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Table of Contents

Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5About the Book. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Chapter 1 Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Hardware Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Software Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Chapter 2 Basics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Object Dictionary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Communication Object Identifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Service Data Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Process Data Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Network Management Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Chapter 3 Hardware Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25Hardware Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26Firmware and Description File. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Installation of the Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28Electrical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29Cable Routing Practices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32Accessories Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

Chapter 4 Software Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 354.1 Basic Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

Configuring the Communication Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37[CANopen Address] AdCo. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38[CANopen Baudrate] bdCO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39[CANopen Error] ErCO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

4.2 Profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41Definition of a Profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42Functional Profiles Supported by the Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44CIA402 Operating State Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45Description of Operating States. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48Cmd Register CMd . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49Stop Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50Assigning Control Word Bits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51[CIA402 State Reg] EtA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52Starting Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53Sequence for a Drive Powered by the Power Stage Supply . . . . . . . . . . . . . . . . . . . . . . . . . 54Sequence for a Drive with Separate Control Stage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55Sequence for a Drive with Mains Contactor Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57

4.3 Software Setup with Unity (M340) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59Drive Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60

Chapter 5 Operations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 635.1 Operating States . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64

Configuring Communication Error Response . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 645.2 Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65

Configuring the Control Channel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66Configuration of the Drive for Operation in I/O Profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67Configuration of the Drive for Operation with CiA 402 Profile in Combined Mode . . . . . . . . 68Configuration of the Drive for Operation with CiA 402 Profile in Separate Mode . . . . . . . . . 69

NHA80945 01/2016 3

Page 4: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Chapter 6 Diagnostics and Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71Fieldbus Status LEDs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72Connection for Fieldbus Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75Monitoring of Communication Channel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76Control-Signal Diagnostics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78

Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79

4 NHA80945 01/2016

Page 5: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Safety Information

Important Information

NOTICE

Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, service, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.

PLEASE NOTE

Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.

A qualified person is one who has skills and knowledge related to the construction and operation of electrical equipment and its installation, and has received safety training to recognize and avoid the hazards involved.

Qualification Of Personnel

Only appropriately trained persons who are familiar with and understand the contents of this manual and all other pertinent product documentation are authorized to work on and with this product. In addition, these persons must have received safety training to recognize and avoid hazards involved. These persons must have sufficient technical training, knowledge and experience and be able to foresee and detect potential hazards that may be caused by using the product, by changing the settings and by the mechanical, electrical and electronic equipment of the entire system in which the product is used. All persons working on and with the product must be fully familiar with all applicable standards, directives, and accident prevention regulations when performing such work.

NHA80945 01/2016 5

Page 6: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Intended Use

This product is a drive for three-phase synchronous and asynchronous motors and intended for industrial use according to this manual.The product may only be used in compliance with all applicable safety regulations and directives, the specified requirements and the technical data.Prior to using the product, you must perform a risk assessment in view of the planned application. Based on the results, the appropriate safety measures must be implemented.Since the product is used as a component in an entire system, you must ensure the safety of persons by means of the design of this entire system (for example, machine design). Any use other than the use explicitly permitted is prohibited and can result in hazards. Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.

Product Related Information

Read and understand these instructions before performing any procedure with this drive.

Damaged products or accessories may cause electric shock or unanticipated equipment operation.

DANGERHAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

Only appropriately trained persons who are familiar with and understand the contents of this manual and all other pertinent product documentation and who have received safety training to recognize and avoid hazards involved are authorized to work on and with this drive system. Installation, adjustment, repair and maintenance must be performed by qualified personnel.

The system integrator is responsible for compliance with all local and national electrical code requirements as well as all other applicable regulations with respect to grounding of all equipment.

Many components of the product, including the printed circuit boards, operate with mains voltage. Do not touch. Use only electrically insulated tools.

Do not touch unshielded components or terminals with voltage present. Motors can generate voltage when the shaft is rotated. Prior to performing any type of work on the

drive system, block the motor shaft to prevent rotation. AC voltage can couple voltage to unused conductors in the motor cable. Insulate both ends of unused

conductors of the motor cable. Do not short across the DC bus terminals or the DC bus capacitors or the braking resistor terminals. Before performing work on the drive system: Disconnect all power, including external control power that may be present. Place a Do Not Turn On label on all power switches. Lock all power switches in the open position. Wait 15 minutes to allow the DC bus capacitors to discharge. The DC bus LED is not an indicator

of the absence of DC bus voltage that can exceed 800 Vdc.Measure the voltage on the DC bus between the DC bus terminals (PA/+, PC/-) using a properly rated voltmeter to verify that the voltage is <42 Vdc

If the DC bus capacitors do not discharge properly, contact your local Schneider Electric represen-tative. Do not repair or operate the product.

Install and close all covers before applying voltage.

Failure to follow these instructions will result in death or serious injury.

WARNINGUNEXPECTED MOVEMENT

Drive systems may perform unexpected movements because of incorrect wiring, incorrect settings, incorrect data or other errors. Carefully install the wiring in accordance with the EMC requirements. Do not operate the product with unknown or unsuitable settings or data. Perform a comprehensive commissioning test.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

6 NHA80945 01/2016

Page 7: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Contact your local Schneider Electric sales office if you detect any damage whatsoever.

(1) For USA: Additional information, refer to NEMA ICS 1.1 (latest edition), Safety Guidelines for the Application, Installation, and Maintenance of Solid State Control and to NEMA ICS 7.1 (latest edition), Safety Standards for Construction and Guide for Selection, Installation and Operation of Adjustable-Speed Drive Systems.

DANGERELECTRIC SHOCK OR UNANTICIPATED EQUIPMENT OPERATION

Do not use damaged products or accessories.

Failure to follow these instructions will result in death or serious injury.

WARNINGLOSS OF CONTROL

The designer of any control scheme must consider the potential failure modes of control paths and, for critical control functions, provide a means to achieve a safe state during and after a path failure. Examples of critical control functions are emergency stop, overtravel stop, power outage and restart.

Separate or redundant control paths must be provided for critical control functions. System control paths may include communication links. Consideration must be given to the

implications of unanticipated transmission delays or failures of the link. Observe all accident prevention regulations and local safety guidelines (1). Each implementation of the product must be individually and thoroughly tested for proper operation

before being placed into service.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

NOTICEDESTRUCTION DUE TO INCORRECT MAINS VOLTAGE

Before switching on and configuring the product, verify that it is approved for the mains voltage

Failure to follow these instructions can result in equipment damage.

NHA80945 01/2016 7

Page 8: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

8 NHA80945 01/2016

Page 9: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

About the Book

At a Glance

Document Scope

The purpose of this document is to: Show you how to install the CANopen fieldbus on your drive. Show you how to configure drive to use CANopen for monitoring and control. Provide examples of setup using Unity

NOTE: Read and understand this document and all related documents (see below) before installing,operating, or maintaining your drive.

Validity Note

This documentation is valid for the drive Altivar Process drives.

The technical characteristics of the devices described in this document also appear online. To access this information online:

The characteristics that are presented in this manual should be the same as those characteristics that appear online. In line with our policy of constant improvement, we may revise content over time to improve clarity and accuracy. If you see a difference between the manual and online information, use the online information as your reference.

Step Action

1 Go to the Schneider Electric home page www.schneider-electric.com.

2 In the Search box type the reference of a product or the name of a product range. Do not include blank spaces in the reference or product range. To get information on grouping similar modules, use asterisks (*).

3 If you entered a reference, go to the Product Datasheets search results and click on the reference that interests you.If you entered the name of a product range, go to the Product Ranges search results and click on the product range that interests you.

4 If more than one reference appears in the Products search results, click on the reference that interests you.

5 Depending on the size of your screen, you may need to scroll down to see the data sheet.

6 To save or print a data sheet as a .pdf file, click Download XXX product datasheet.

NHA80945 01/2016 9

Page 10: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Related Documents

Use your tablet or your PC to quickly access detailed and comprehensive information on all our products on www.schneider-electric.com

The internet site provides the information you need for products and solutions The whole catalog for detailed characteristics and selection guides The CAD files to help design your installation, available in over 20 different file formats All software and firmware to maintain your installation up to date A large quantity of White Papers, Environment documents, Application solutions, Specifications... to

gain a better understanding of our electrical systems and equipment or automation And finally all the User Guides related to your drive, listed below:

You can download these technical publications and other technical information from our website at http://download.schneider-electric.com

Title of Documentation Reference Number

Altivar Process ATV900 Getting Started NHA61578 (English), NHA61579 (French), NHA61580 (German), NHA61581 (Spanish), EAV61724 (Italian), NHA61583 (Chinese)

Altivar Process ATV900 Getting Started Annex (SCCR) NHA61584 (English)

Altivar Process ATV930, ATV950 Installation Manual NHA80932 (English), NHA80933 (French), NHA80934 (German), NHA80935 (Spanish), NHA80936 (Italian), NHA80937 (Chinese)

Altivar Process ATV930, ATV950, ATV960, ATV980 Programming Manual

NHA80757 (English), NHA80758 (French), NHA80759 (German), NHA80760 (Spanish), NHA80761 (Italian), NHA80762 (Chinese)

Altivar Process ATV900 Modbus SL manual (Embedded) NHA80939 (English)

Altivar Process ATV900 Ethernet manual (Embedded) NHA80940 (English)

Altivar Process ATV900 PROFIBUS DP manual (VW3A3607) NHA80941 (English)

Altivar Process ATV900 DeviceNet manual (VW3A3609) NHA80942 (English)

Altivar Process ATV900 PROFINET manual (VW3A3627) NHA80943 (English)

Altivar Process ATV900 CANopen manual (VW3A3608, 618, 628) NHA80945 (English)

Altivar Process ATV900 EtherCAT manual - (VW3A3601) NHA80946 (English)

Altivar Process ATV900 Communication Parameters NHA80944 (English)

Altivar Process ATV900 Service Instructions NHA80954 (English)

Altivar Process ATV900 Safety Functions manual NHA80947 (English), NHA80948 (French), NHA80949 (German), NHA80950 (Spanish), NHA80951 (Italian), NHA80953 (Chinese)

Altivar Process Drive Systems – Installation manual NHA37118 (German), NHA37119 (English), NHA37121 (French), NHA37122 (Spanish), NHA37123 (Italian), NHA37124 (Dutch), NHA37126 (Polish), NHA37127 (Portuguese), NHA37128 (Russian), NHA37129 (Turkish), NHA37130 (Chinese)

Altivar Process ATV960 Configuration guide NHA37115 (English), NHA37114(German)

Altivar Process ATV980 Configuration guide NHA37117 (English), NHA37116(German)

10 NHA80945 01/2016

Page 11: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Terminology

The technical terms, terminology, and the corresponding descriptions in this manual normally use the terms or definitions in the relevant standards.

In the area of drive systems this includes, but is not limited to, terms such as error, error message, failure, fault, fault reset, protection, safe state, safety function, warning, warning message, and so on.

Among others, these standards include: IEC 61800 series: Adjustable speed electrical power drive systems IEC 61508 Ed.2 series: Functional safety of electrical/electronic/programmable electronic safety-related EN 954-1 Safety of machinery - Safety related parts of control systems EN ISO 13849-1 & 2 Safety of machinery - Safety related parts of control systems. IEC 61158 series: Industrial communication networks - Fieldbus specifications IEC 61784 series: Industrial communication networks - Profiles IEC 60204-1: Safety of machinery - Electrical equipment of machines – Part 1: General requirements

In addition, the term zone of operation is used in conjunction with the description of specific hazards, and is defined as it is for a hazard zone or danger zone in the EC Machinery Directive (2006/42/EC) and in ISO 12100-1.

Also see the glossary at the end of this manual.

NHA80945 01/2016 11

Page 12: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

12 NHA80945 01/2016

Page 13: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Altivar Process 900

Presentation

NHA80945 01/2016

Presentation

Chapter 1Presentation

What Is in This Chapter?

This chapter contains the following topics:

Topic Page

Hardware Overview 14

Software Overview 15

NHA80945 01/2016 13

Page 14: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Presentation

Hardware Overview

General

The VW3A3608, VW3A3618, VW3A3628 are CANopen modules that can be used in a CANopen industrial fieldbus.

The following figure shows the hardware presentation of these three CANopen modules.

14 NHA80945 01/2016

Page 15: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Presentation

Software Overview

General

CANopen manages communication between the network devices with object dictionaries and objects. A network device can use process data objects (PDO) and service data objects (SDO) to request the object data from the object dictionary of another device and, if permissible, write back modified values.

PDOs (process data objects) for real-time transmission of process data. SDOs (service data object) for read and write access to the object dictionary. Objects for controlling CAN messages: SYNC object (synchronization object) for synchronization of network devices.

EMCY object (emergency object), for signaling errors of a device or its peripherals.

Network management services: NMT services for initialization and network control (NMT: network management).

NMT node guarding for monitoring the network devices.

NMT heartbeat for monitoring the network devices.

NHA80945 01/2016 15

Page 16: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Presentation

16 NHA80945 01/2016

Page 17: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Altivar Process 900

Basics

NHA80945 01/2016

Basics

Chapter 2Basics

What Is in This Chapter?

This chapter contains the following topics:

Topic Page

Object Dictionary 18

Communication Object Identifier 19

Service Data Communication 20

Process Data Communication 21

Network Management Services 22

NHA80945 01/2016 17

Page 18: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Basics

Object Dictionary

Description

Each CANopen device manages an object dictionary which contains the objects for communication.

Index and Subindex

The objects are addressed in the object dictionary via a 16 bit index.

One or more 8 bit subindex entries for each object specify individual data fields in the object. Index and subindex are shown in hexadecimal notation.

The following table provides the index and subindex entries using the example of the object ramps (203C hex):

Description Object Dictionary

The description object dictionary is made of separate chapters: Communication profile area RPDO TPDO Manufacturer specific Application profile (CiA402)

Index Subindex Name Meaning

203C hex 00 hex – Number of entries

203C hex 01 hex ACC Acceleration time

203C hex 02 hex DEC Deceleration time

Index (hex) Object

0000 Unused

0001...001F Static data types

0020...003F Complex data types

0040...005F Unused (Manufacturer-specific complex data types

0060...007F Device profile-specific static data types

0080...009F Device profile-specific complex data types

00A0...0FFF Reserved for further use

1000...1FFF Communication profile area

2000...5FFF ATV9xx specific profile area

6000...9FFF Standardized device profile area

A000...FFFF Reserved for further use

18 NHA80945 01/2016

Page 19: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Basics

Communication Object Identifier

Description

The COB ID (communication object identifier) has 2 tasks as far as controlling communication object is concerned: Bus arbitration: Specification of transmission priorities Identification of communication objects

An 11-bit COB identifier as per the CAN 3.0 A specification is defined for CAN communication; it comprises two parts: Function code, 4 bits Node address (node ID), 7 bits

Function Code

The function code classifies the communication objects. Since the bits of the function code if the COB ID is more significant, the function code also controls the transmission priorities: Objects with a lower function code are transmitted with higher priority. For example, an object with function code A is transmitted prior to an object with function code 3 in the case of simultaneous bus access.

Node Address

Each network device is configured before it can be operated on the network. The device is assigned a unique 7-bit node address (node ID) between 1 (01 hex) and 127 (7F hex). The device address 0 is reserved for broadcast transmissions which are used to send messages to all reachable devices simultaneously.

COB IDs of the Communication Objects

The following table provides the COB IDs of the communication objects with the factory settings.

Communication object Function code Node address, node ID [1...127]

COB ID decimal (hexadecimal)

Service Network Management (NMT) 0 0 0 0 0 0 0 0 0 0 0 0 (0 hex)

Synchronization service (SYNC) 0 0 0 1 0 0 0 0 0 0 0 128 (80 hex)

Emergency service (EMCY) 0 0 0 1 x x x x x x x 128 (80 hex) + node ID

Transmit PDO1 (TPDO1) 0 0 1 1 x x x x x x x 384 (180 hex) + node ID

Receive PDO1 (RPDO1) 0 1 0 0 x x x x x x x 512 (200 hex) + node ID

Transmit PDO2 (TPDO2) 0 1 0 1 x x x x x x x 640 (280 hex) + node ID

Receive PDO2 (RPDO2) 0 1 1 0 x x x x x x x 768 (300 hex) + node ID

Transmit PDO3 (TPDO3) 0 1 1 1 x x x x x x x 896 (380 hex) + node ID

Receive PDO3 (RPDO3) 1 0 0 0 x x x x x x x 1024 (400 hex) + node ID

Transmit SDO (TSDO) 1 0 1 1 x x x x x x x 1408 (580 hex) + node ID

Receive SDO (RSDO) 1 1 0 0 x x x x x x x 1536 (600 hex) + node ID

NMT error control (Node Guarding, Heartbeat)

1 1 1 0 x x x x x x x 1792 (700 hex) + node ID

NHA80945 01/2016 19

Page 20: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Basics

Service Data Communication

Description

Service Data Objects (SDO) can be used to access the entries of an object dictionary using index and subindex. The values of the objects can be read and, if permissible, also written.

Every network device has at least one SDO server to be able to respond to read and write requests from a different device.

The TSDO of a SDO client is used to send the request for data exchange; the RSDO is used to receive.

The data frame of a SDO consists of 8 bytes.

SDOs have a higher COB ID than PDOS, therefore they are transmitted over the can bus at a low priority.

Example of Read Request

This example explains how to read the acceleration (ACC) parameter on an Altivar located at CANopen address 4 (COB ID = 580 hex + Node ID or 600 hex + Node ID). The index / subindex value of this parameter is 203C/02 hex. Values are given in hexadecimal.

Read request: Master → Drive

Read response: Master ← Drive

The value of parameter read is equal to 1000 (03E8 hex), equivalent to an acceleration (ACC) of 100 s, as the unit of this parameter is 0.1 s.

Example of Write Request

This example explains how to write the value 100 s to the acceleration (ACC) parameter on an Altivar located at CANopen address 4 (COB ID = 580 hex + NodeID or 600 hex + Node ID). The index / subindex value of this parameter is 203C/02 hex. Values are give in hexadecimal.

The request code is 2B hex for an item of 2 bytes data length.

Write request: Master → Drive

The request data field indicates the value 03E8 hex as value written is 1000, equivalent to an acceleration (ACC) of 100 s, as the unit of this parameter is 0.1 s.

Write response: Master ← Drive

Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 6

COB ID Request code

Object index Subindex Request data

604 40 3C 20 02 00 00 00 00

Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 6

COB ID Request code

Object index Subindex Request data

584 4B 3C 20 02 E8 03 00 00

Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 6

COB ID Request code

Object index Subindex Request data

604 2B 3C 20 02 E8 03 00 00

Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 6

COB ID Request code

Object index Subindex Request data

584 60 3C 20 02 00 00 00 00

20 NHA80945 01/2016

Page 21: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Basics

Process Data Communication

Description

Process Data Objects (PDO) are used for real-time data exchange of process data such as actual and reference values or the operating state of the device. Transmission is fast because the data is sent without administration data and data transmission acknowledgment from the recipient is not required. Each PDO can be enabled or disabled independently using the bit 31 (valid bit) in subindex 01 hex of the respective communication object.

PDO1 Details

The first PDO is by default compliant with the PDO1 of the Velocity mode of the CiA402. It is asynchronous and contains two data: the control word (6040 hex, CMD) and the target velocity (6042 hex, LFRD) for the output (from Master to Device) and the status word (6041 hex, ETA) and the control effort (6044 hex, RFRD) for the input (from Device to Master).

PDO2 Details

The second PDO set (PDO2) is deactivated by default and can be fully configurable (1 to 4 words of the user choice). It is reserved for adjustments and for additional control and monitoring functions.

PDO3 Details

The third PDO set (PDO3) is reserved. Deactivated by default, it cannot be configured and comprises: RPDO3 (receive), containing four output (from Master to Device) words of the communication scanner

NC1 to NC4 TPDO3 (transmit), containing four input (from Device to Master) words of the communication scanner

NM1 to NM4

Transmission Mode

By default, the three PDOs are asynchronous, although the transmission mode of each PDO can be reconfigured by the user in accordance with requirements: Asynchronous mode (255): The transmit PDO is only sent when the value of its data changes. In this

mode, the inhibit time and event timer can be modified in order to adjust the PDO transmission frequency on the bus.

Cyclic synchronous mode (1…240): The transmit PDO is sent each time a synchronization object (SYNC) is received or when a preconfigured number of synchronization objects (from 1 to 240) is received.

Acyclic synchronous mode (0): The transmit PDO is sent each time the value of its data changes, but only during the synchronous window authorized by the next synchronization object (SYNC).

Synchronization Object

The synchronization object (SYNC) is sent cyclically by the CANopen master. It does not contain data and its frame is limited to its unique COB ID identifier. The purpose of this object is essentially to authorize synchronous communication modes for CANopen slaves.

NHA80945 01/2016 21

Page 22: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Basics

Network Management Services

Description

Network management (NMT) is part of the CANopen communication profile; it is used to initialize the network and the network devices and to start, stop, and monitor the network devices during operation on the network.

NMT services can be divided into two groups: Services for device control, to initialize devices for CANopen communication and to control the behavior

of devices during operation on the network. Services for connection monitoring to check the status of network devices.

Network Management State Machine

The CANopen NMT slave device implements a state machine, which brings automatically after power-on and internal initialization every device in pre-Operational state. In this state the node may be configured and parameterized using SDO, no PDO communication is allowed.

The NMT master device may switch all nodes or a single node to operational state and conversely. In operational state PDO transfer is allowed. By switching a device into the stopped state, it is forced to stop PDO and SDO communication. Furthermore, this state can be used to achieve certain application behavior.

In the operational state, all communication objects are active. Object Dictionary access through SDO is possible.

NMT Message Description

The NMT services for device control are transmitted as unconfirmed messages with COB ID 0. By default, they have the highest priority on the CAN bus.

The following table provides the of command specifier used to manage the NMT state machine.

COB ID Byte 0 Byte 1

0 (000 hex) Command specifier (CS) Node ID(1)

(1) If Node ID is 0, the command specifier is broadcast to all CANopen slaves.

Command specifier (CS) Meaning

1 (01 hex) Start_Remote_Node

2 (02 hex) Stop_Remote_Node

128 (80 hex) Enter_Pre-Operational_State

129 (81 hex) Reset_Node

130 (82 hex) Reset_Communication

22 NHA80945 01/2016

Page 23: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Basics

NMT State Chart

Depending on the communication status of the drive, the following services are available:

In Pre-Operational mode, the master can only perform SDO.

In operation mode, the master can perform SDO and PDO. The device can be controlled only if the user has selected CANopen as the command channel.

In Stop mode, the master cannot perform SDO and PDO.

In the event of a resettable detected error, the drive must be in the Operational NMT state in order that the PDO carrying the control word CMD can reset the drive using the CMD Fault reset bit.

Node Guarding Service

Either the Node Guarding service described here of the Heartbeat service described below can be used for communication monitoring. Only one these two services can be active at any one time. The Node guarding service is deactivated by default on the Altivar.

The master scans the drive at regular intervals (Life Time) by sending "Remote Transmit Requests" (RTR). The "Life Time" is calculated by multiplying the Guard Time by the Life Time Factor.

If, once the Life Time has expired, the drive has not received the RTR: It triggers a Life Guarding error Sends an emergency telegram (EMCY)

Transition Description

(1) On power-up, the node automatically changes to the initialization state

(2) Once initialization is complete, the pre-operational state is activated automatically

(3), (6) Start_Remote_Node

(4), (7) Enter_Pre-Operational_State

(5), (8) Stop_Remote_Node

(9), (10), (11) Reset_Node

(12), (13), (14) Reset_Communication

Initialization Pre-Operational Operational Stopped

PDO X

SDO X X

Synchronization (SYNC) X X

Emergency (EMCY) X X

Bootup Service X X

Network Management (NMT) X X X

NHA80945 01/2016 23

Page 24: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Basics

Node Guarding Frame Description

The drive indicates its NMT state via the "NMT information field, described here:

Bit 6-0 (node state): Current NMT state of the drive: Initialization (00 hex) Stopped (04 hex) Operational (05 hex) Pre-Operational (7 F hex)

Bit 7 (toggle bit): The value of this bit must alternate from one drive response to the other. The value of the toggle bit for the first response following activation of the node Guarding service is 0. This bit can only be reset by sending the Reset_Communication command to the drive. If a response is received with the same toggle bit value as the previous one, the new response is treated as if it had not been received.

Heartbeat Service

If you do not activate the node Guarding service described above, you can use the Heartbeat service to monitor communication with another node that supports this service.

The Heartbeat service is deactivated by default on the Altivar.

Each Heartbeat Producer sends Heartbeat messages at regular intervals (Producer Heartbeat Time).

All Heartbeat Consumer check that they receive these messages in a time less that the Consumer Heartbeat Time.

The Producer Heartbeat Time must be less that the Consumer Heartbeat Time. If the drive has been configured as a consumer and a period equal to the Consumer Heartbeat Time elapses without a Heartbeat message being received, the drive triggers a Heartbeat event and send an emergency telegram (EMCY).

Heartbeat Frame Description

The Heartbeat message sent from the drive contains a Heartbeat Producer state field (byte 0), described here:

Bit 6-0: Heartbeat Producer state: Current NMT state of the drive: Initialization (00 hex) Stopped (04 hex) Operational (05 hex) Pre-Operational (7F hex)

Bit 7 (toggle bit): Reserved: This bit is equal to 0.

Emergency Object

An Emergency object (EMCY) is sent by the drive to other CANopen devices, with a high priority, each time an error is detected or cleared. This is the case in particular for Heartbeat of Life Guard type detected errors. An Emergency object is never repeated.

The error code Errd, and its possible values, is described in the communication parameter file available on www.schneider-electric.com

COB ID Byte 0 Byte 1

1792 (700 hex) + Node ID Bit 7 Bit 6 - 0

Toggle bit Node State

COB ID Byte 0

1792 (700 hex) + Node ID Bit 7 Bit 6 - 0

Reserved Heartbeat Producer State

COB ID Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7

128 (80 hex) + NodeID Error code Errd Error register 0 0 0 0 0

LSB MSB Bit 0 = 0 (no error) or 1 (error)

– – – – –

24 NHA80945 01/2016

Page 25: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Altivar Process 900

Hardware Setup

NHA80945 01/2016

Hardware Setup

Chapter 3Hardware Setup

What Is in This Chapter?

This chapter contains the following topics:

Topic Page

Hardware Presentation 26

Firmware and Description File 27

Installation of the Module 28

Electrical Installation 29

Cable Routing Practices 32

Accessories Presentation 33

NHA80945 01/2016 25

Page 26: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Hardware Setup

Hardware Presentation

CANopen Fieldbus Modules

The following figure shows the VW3A3608 CANopen module with 2 RJ45 connectors:

The following figure shows the VW3A3618 CANopen module with a SubD9 connector:

The following figure shows the VW3A3628 CANopen module with an open style connector:

Item Description Comment

A Port A RJ45 connector

B Port B RJ45 connector

Item Description Comment

− − SubD9 connector

Item Description Comment

− − Open style connector

26 NHA80945 01/2016

Page 27: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Hardware Setup

Firmware and Description File

Compatibility

The associated EDS file is named as the following example:

SEATV9x0_010102E.eds

The files are available on www.schneider-electric.com.

NHA80945 01/2016 27

Page 28: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Hardware Setup

Installation of the Module

Before Starting

Check that the module catalog number marked on the label is the same as that on the delivery note corresponding to the purchase order.

Remove the fieldbus module from its packaging and check that it has not been damaged in transit.

Insertion of the Fieldbus Module

The table provides the procedure for insertion of the CANopen option module in the drive:

1 Slot A

Removal of the Fieldbus Module

The table provides the procedure for removal of the CANopen option module from the drive:

Step Action

1 Ensure that the power is off.

2 Locate the fieldbus module slot (A) on the bottom of the control part.

3 Add the corresponding sticker on the LED front panel of the drive.

4 Insert the module.

5 Check that the module is correctly inserted and locked mechanically in the drive.

Step Action

1 Ensure that the power is off.

2 Press the strip.

3 Remove the module while maintaining the strip pressed,

28 NHA80945 01/2016

Page 29: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Hardware Setup

Electrical Installation

Pin Layout of VW3A3608

The VW3A3608 option module is equipped with 2 RJ45 female sockets for the CANopen connection.

The table provides the pin out details of each RJ45 connector:

NOTE: Both RJ45 are interconnected internally as on the diagram below:

Pin RJ45 signal

1 CAN_H

2 CAN_L

3 CAN_GND

4 Not connected

5 Not connected

6 Not connected

7 Not connected

8 Not connected

NHA80945 01/2016 29

Page 30: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Hardware Setup

Pin Layout of VW3A3618

The VW3A3618 option module is equipped with 1 SubD9 male connector for the CANopen connection.

The table provides the pin out details of the SUB-D 9 connector:

Pin Layout of VW3A3628

The VW3A3628 option module is equipped with 1 open style male connector for the CANopen connection.

The table provides the pin out of the open style connector:

Pin SubD signal

1 Reserved

2 CAN_L

3 CAN_GND

4 Reserved

5 CAN_SHLD

6 CAN_GND

7 CAN_H

8 Reserved

9 Reserved

Pin Signal

1 CAN_GND

2 CAN_L

3 CAN_SHLD

4 CAN_H

5 Reserved

30 NHA80945 01/2016

Page 31: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Hardware Setup

Cable Specification and Maximum Bus Length

The following table describes the maximum length:

The reference potential CAN_GND and the shield connection (connector housing) are galvanically isolated. Keep the galvanic isolation in order to avoid ground loops via the CAN bus. Use equipotential bonding conductors. Use pre-assembled cables to reduce wiring errors. Verify that wiring, cables, and connected interfaces meet the PELV requirements.

Terminating Resistor

Terminating resistors must be placed on both ends of a CAN bus line. A 120 Ohm terminating resistor between CAN_L and CAN_H is used for this purpose.

Baud rate KBit/s Maximum bus length m (ft)

50 1000 (3280)

125 500 (1640)

250 250 (820)

500 100 (328)

1000 20 (65)

NHA80945 01/2016 31

Page 32: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Hardware Setup

Cable Routing Practices

Installation Topology

The following image shows the connection of multiple drives equipped with VW3A3608 CANopen modules.

32 NHA80945 01/2016

Page 33: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Hardware Setup

Accessories Presentation

Introduction

Both ends of a CAN bus line must be terminated. A 120 ohm terminating resistor between CAN_L and CAN_H is used for this purpose. According to the CANopen several solutions are available (See accessories and wear parts).

The following table describes the CANopen accessories for the different bus termination:

Bus termination Accessories

CANopen RJ45 module VW3A3608 CANopen terminating resistor, 120 Ohm, integrated in RJ45 connector

TCSCAR013M120

CANopen open style module VW3A3628 CANopen terminating resistor, 120 ohm, for terminal screw terminal

TCSCAR01NM120

CANopen SubD9 module VW3A3618 CANopen connector, SubD9 (female), with switchable terminating resistor, straight

TSXCANKCDF180T

CANopen cable, 1 m, SubD9 (female) with integrated terminating resistor to RJ45

VW3M3805R01

CANopen cable, 3 m, SubD9 (female) with integrated terminating resistor to RJ45

VW3M3805R030

NHA80945 01/2016 33

Page 34: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Hardware Setup

34 NHA80945 01/2016

Page 35: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Altivar Process 900

Software Setup

NHA80945 01/2016

Software Setup

Chapter 4Software Setup

What Is in This Chapter?

This chapter contains the following sections:

Section Topic Page

4.1 Basic Settings 36

4.2 Profile 41

4.3 Software Setup with Unity (M340) 58

NHA80945 01/2016 35

Page 36: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Software Setup

Basic Settings

Section 4.1Basic Settings

What Is in This Section?

This section contains the following topics:

Topic Page

Configuring the Communication Parameters 37

[CANopen Address] AdCo 38

[CANopen Baudrate] bdCO 39

[CANopen Error] ErCO 40

36 NHA80945 01/2016

Page 37: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Software Setup

Configuring the Communication Parameters

Overview

The parameters are described according to the graphic display terminal. These settings are also possible from commissioning software.

Access

The parameters are accessible in the [Communication] COM, [CANopen] CnO- menu.

NHA80945 01/2016 37

Page 38: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Software Setup

[CANopen Address] AdCo

About This Parameter

This parameter defines the address of the drive on the network. This parameter is taken into account after a power cycle.

Access

This is a read/write parameter.

The parameter number is 6051

Possible Settings

The table presents the parameter settings:

Settings Code Value Description

[OFF][1 to 127]

OFF

1...127

01...127

CANopen address is not assigned.CANopen address is assigned.Factory setting: OFF

38 NHA80945 01/2016

Page 39: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Software Setup

[CANopen Baudrate] bdCO

About This Parameter

This parameter defines the baud rate at which data is transferred. This parameter is taken into account after a power cycle.

Access

This is a read/write parameter.

The parameter number is 6053.

Possible Settings

The table presents the parameter settings:

Settings Code Value Description

[50 kbps][125 kbps][250 kbps][500 kbps][1 Mbps]

50

125

250

500

1M

3852606876

Baud rate is set to 50 Kbps.Baud rate is set to 125 Kbps.Baud rate is set to 250 Kbps.Baud rate is set to 500 Kbps.Baud rate is set to 1 Mbps.Factory setting: 250 Kbps

NHA80945 01/2016 39

Page 40: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Software Setup

[CANopen Error] ErCO

About This Parameter

This parameter indicates the last active CANopen detected error.

Access

This is a read-only Parameter.

The parameter number is 6056.

Possible Settings

The table presents the parameter settings:

Settings Code Value Description

[0][1][2][3][4][5]

0

1

2

3

4

5

012345

No errors detected since the last start of CANopen communication.Bus offNode guarding error requiring a return to the NMT initialization state. CAN overrunHeartbeat error requiring a return to the NMT initialization state.NMT states chart error.

NOTE: If the motor is running, a [CANopen Error] COF is triggered in case of change of NMT state.

40 NHA80945 01/2016

Page 41: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Software Setup

Profile

Section 4.2Profile

What Is in This Section?

This section contains the following topics:

Topic Page

Definition of a Profile 42

Functional Profiles Supported by the Drive 43

Functional Description 44

CIA402 Operating State Diagram 45

Description of Operating States 46

Summary 48

Cmd Register CMd 49

Stop Commands 50

Assigning Control Word Bits 51

[CIA402 State Reg] EtA 52

Starting Sequence 53

Sequence for a Drive Powered by the Power Stage Supply 54

Sequence for a Drive with Separate Control Stage 55

Sequence for a Drive with Mains Contactor Control 57

NHA80945 01/2016 41

Page 42: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Software Setup

Definition of a Profile

Types of Profiles

There are 3 types of profile: Communication profiles Functional profiles Application profiles

Communication Profile

A communication profile describes the characteristics of a bus or network: Cables Connectors Electrical characteristics Access protocol Addressing system Periodic exchange service Messaging service ...

A communication profile is unique to a type of fieldbus (such as Modbus, PROFIBUS DP, and so on) and is used by different types of devices.

Functional Profile

A functional profile describes the behavior of a type of device: Functions Parameters (such as name, format, unit, type, and so on.) Periodic I/O variables State chart ...

A functional profile is common to all members of a device family (such as variable speed drives, encoders, I/O modules, displays, and so on).

They can feature common or similar parts. The standardized (IEC 61800-7) functional profiles of variable speed drives are: CiA402 PROFIDRIVE CIP AC Drive

CiA402 device profile for drives and motion control represents the next stage of this standard development and is now part of the IEC 61800-7 standard.

Application Profile

Application profile defines the services to be provided by the devices on a machine. For example, CiA DSP 417-2 V 1.01 part 2: CANopen application profile for lift control systems - virtual device definitions.

Interchangeability

The aim of communication and functional profiles is to achieve interchangeability of the devices connected via the fieldbus.

42 NHA80945 01/2016

Page 43: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Software Setup

Functional Profiles Supported by the Drive

I/O Profile

Using the I/O profile simplifies PLC programming.

The I/O profile mirrors the use of the terminal strip for control by utilizing 1 bit to control a function.

The I/O profile for the drive can also be used when controlling via a fieldbus.The drive starts up as soon as the run command is sent.15 bits of the control word (bits 1...15) can be assigned to a specific function.

This profile can be developed for simultaneous control of the drive via: The terminals The Modbus control word The CANopen control word Ethernet Modbus TCP embedded The fieldbus module control word

The I/O profile is supported by the drive itself and therefore in turn by all the communication ports (integrated Modbus, CANopen, Ethernet, PROFIBUS DP ,PROFINET, EtherCAT, and DeviceNet fieldbus modules).

CiA402 Profile

The drive only starts up following a command sequence.

The control word is standardized.

5 bits of the control word (bits 11...15) can be assigned to a function.

The CiA402 profile is supported by the drive itself and therefore by all the communication ports (Modbus, CANopen, Ethernet, and PROFIBUS DP, PROFINET, EtherCAT, and DeviceNet).

The drive supports the velocity mode of CiA402 profile.

In the CiA402 profile, there are two modes that are specific to the drive and characterize commands and references value management: Separate [Separate] SEP

Not separate [Not separ.] SIm,

NHA80945 01/2016 43

Page 44: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Software Setup

Functional Description

Introduction

Drive operation involves two main functions, which are illustrated in the diagrams below.

CiA402

The main parameters are shown with their CiA402 name and their CiA402/Drivecom index (the values in brackets are the CANopen addresses of the parameter).

The following figure shows the control diagram for drive operation:

Simplified diagram for speed control in Velocity mode:

Altivar Drive

These diagrams translate as follows for the Altivar drive.

The following figure shows the control diagram for drive operation:

Simplified diagram for speed control in Velocity mode:

44 NHA80945 01/2016

Page 45: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Software Setup

CIA402 Operating State Diagram

State Diagram

After switching on and when an operating mode is started, the product goes through a number of operating states.

The state diagram (state machine) shows the relationships between the operating states and the state transitions. The operating states are internally monitored and influenced by monitoring functions.

The following figure shows the CIA402 state diagram:

NHA80945 01/2016 45

Page 46: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Software Setup

Description of Operating States

Drive Operating State

The operating state of the drive changes depending on whether the control word [Cmd Register] ?CMd, is sent or an event occurs (an error detection, for example).

The drive operating state can be identified by the value of the status word [CIA402 State Reg] EtA.

Operating State Description

1 - Not ready to switch on

Initialization starts. This is a transient state invisible to the communication network.

2 - Switch on disabled The power stage is not ready to switch on.The drive is locked, no power is supplied to the motor.For a separate control stage, it is not necessary to supply the power.For a separate control stage with mains contactor, the contactor is not closed.The configuration and adjustment parameters can be modified.

3 - Ready to switch on The power stage is ready to switch on and awaiting power stage supply mains.For a separate control stage, it is not necessary to supply the power stage, but the system expects it in order to change to state 4 - Switched on.For a separate control stage with mains contactor, the contactor is not closed.The drive is locked, no power is supplied to the motor.The configuration and adjustment parameters can be modified.

4 - Switched on Power stage is switched on.For a separate control stage, the power stage must be supplied.For a separate control stage with mains contactor, the contactor is closed.The drive is locked, no power is supplied to the motor.The power stage of the drive is ready to operate, but voltage has not yet been applied to the output.The adjustment parameters can be modified.If a configuration parameter is modified, the drive returns to the state 2 - Switch on disable .

5 - Operation enabled Power stage is enabled. The drive is in running stateFor a separate control stage, the power stage must be supplied.For a separate control stage with mains contactor, the contactor is closed.The drive is unlocked, power is supplied to the motor.The drive functions are activated and voltage is applied to the motor terminals.If the reference value is zero or the Halt command is applied, no power is supplied to the motor and no torque is applied. To perform [Auto tuning] tUn, the drive must be in state 5 - Operation enabled. The adjustment parameters can be modified.The configuration parameters cannot be modified.

NOTE: The command 4 - Enable operation must be taken into consideration only if the channel is valid. In particular, if the channel is involved in the command and the reference value, transition 4 is possible only after the reference value has been received once.

The reaction of the drive to a Disable operation command depends on the value of the [SwitchOnDisable Stp] dOtd parameter: If the [SwitchOnDisable Stp] dOtd parameter is set to 0, the drive changes

to operating state 4 - Switched on and stops in freewheel stop. If the [SwitchOnDisable Stp] dOtd parameter is set to 1, the drive stops on

ramp and then changes to operating state 4 - Switched on.

46 NHA80945 01/2016

Page 47: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Software Setup

6 - Quick stop active The drive performs a fast stop and remains locked in the operating state 6-Quick stop active. Before restarting the motor, it is required to go to the operating state 2-switch on disabled.During fast stop, the drive is unlocked and power is supplied to the motor.The configuration parameters cannot be modified.The condition for transition 12 to state 2 - Switch on disabled depends on the value of the parameterQuick stop mode (QStd):If the Quick stop mode parameter has the value FST2, the drive stops according to the fast stop ramp and then changes to state 2 - Switch on disabled .If the Quick stop mode parameter has the value FST6, the drive stops according to the fast stop ramp and then remains in state 6 - Quick stop active until: A Disable voltage command is received or The STOP key is pressed or A freewheel stop command via the digital input of the terminal.

7 - Fault reaction active

Transient state during which the drive performs an action corresponding to the selected error response.

8 - Fault Error response terminated. Power stage is disabled.The drive is locked, no power is supplied to the motor.

Operating State Description

NHA80945 01/2016 47

Page 48: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Software Setup

Summary

Device Status Summary

Operating State Power Stage Supply for Separate Control Stage

Power Supplied to Motor

Modification of Configuration Parameters

1 - Not ready to switch on

Not required No Yes

2 - Switch on disabled Not required No Yes

3 - Ready to switch on Not required No Yes

4 - Switched on Required No Yes, return to 2 - Switch on disabled operating state

5 - Operation enabled Required Yes No

6 - Quick stop active Required Yes, during fast stop No

7 - Fault reaction active

Depends on error response configuration

Depends on error response configuration

8 - Fault Not required No Yes

48 NHA80945 01/2016

Page 49: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Software Setup

Cmd Register CMd

Bit Mapping of the Control Word

Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

Fault reset Reserved (=0)

Reserved (=0)

Reserved (=0)

Enable operation

Quick stop Enable voltage

Switch on

0 to 1 transition = Error is reset (after cause of error is no longer active)

1 = Run command

0 = Quick stop active

Authorization to supply AC power

Mains contactor control

Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8

Manufacturer specific assignable

Manufacturer specific assignable

Manufacturer specific assignable

Manufacturer specific assignable

Manufacturer specific

Reserved (=0)

Reserved (=0)

Halt

0 = Forward direction asked 1= Reverse direction asked

Halt

Command State Transition

Final Operating State

Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Example ValueFault

ResetEnable Operation

Quick Stop

Enable Voltage

Switch On

Shutdown 2, 6, 8 3 - Ready to switch on

X X 1 1 0 0006 hex

Switch on 3 4 - Switched on

X X 1 1 1 0007 hex

Enable operation

4 5 - Operation enabled

X 1 1 1 1 000F hex

Disable operation

5 4 - Switched on

X 0 1 1 1 0007 hex

Disable voltage

7, 9, 10, 12 2 - Switch on disabled

X X X 0 X 0000 hex

Quick stop 11 6 - Quick stop active

X X 0 1 X 0002 hex

7, 10 2 - Switch on disabled

Fault reset

15 2 - Switch on disabled

0 → 1 X X X X 0080 hex

X: Value is of no significance for this command.0→1: Command on rising edge.

NHA80945 01/2016 49

Page 50: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Software Setup

Stop Commands

Halt Command

The Halt command enables movement to be interrupted without having to leave the 5 - Operation enabled state. The stop is performed in accordance with the [Type of stop] Stt parameter.

If the Halt command is active, no power is supplied to the motor and no torque is applied.

Regardless of the assignment of the [Type of stop] Stt parameter [Fast stop Assign] FSt, [Ramp stop] rMP, [Freewheel Stop] nSt, or [DC Injection Assign] dCI, the drive remains in the 5 - Operation enabled state.

Fast Stop Command

A Fast Stop command at the terminals or using a bit of the control word assigned to Fast Stop causes a change to the 4 - Switched on

Freewheel Command

A Freewheel Stop command using a digital input of the terminal or a bit of the control word assigned to Freewheel Stop causes a change to operating state 2 - Switch on disabled.

50 NHA80945 01/2016

Page 51: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Software Setup

Assigning Control Word Bits

Function Codes

In the CiA402 profile, fixed assignment of a function input is possible using the following codes:

For example, to assign the DC injection braking to bit13 of CANopen, simply configure the [ DC Injection Assign] dCI parameter with the [C213] C213value.

Bit 11 is assigned by default to the operating direction command [Reverse Assign]?rrS.

Bit CANopen

Bit 11 C211

Bit 12 C212

Bit 13 C213

Bit 14 C214

Bit 15 C215

NHA80945 01/2016 51

Page 52: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Software Setup

[CIA402 State Reg] EtA

Bit Mapping of the Status Word

Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

Warning Switch on disabled

Quick stop Voltage enabled

Fault Operation enabled

Switched on Ready to switch on

A warning is active

Power stage supply disabled

0 = Quick stop is active

Power stage supply present

Error detected

Running Ready 1 = Awaiting power Stage supply

Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8

Manufacturer-specific Direction of rotation

Manufacturer-specific Stop via STOP key

Reserved (=0)

Reserved (=0)

Internal limit active

Target reached

Remote Reserved (=0)

Reference value outside limits

Reference value reached

Command or reference value via fieldbus

Operating State

Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 ETA Masked by

006F H (1)Switch On Disabled

Quick Stop

Voltage Enabled

Fault Operation Enabled

Switched On

Ready to Switch On

1 -Not ready to switch on

0 X X 0 0 0 0 −

2 -Switch on disabled

1 X X 0 0 0 0 0040 hex

3 -Ready to switch on

0 1 X 0 0 0 1 0021 hex

4 -Switched on

0 1 1 0 0 1 1 0023 hex

5 -Operation enabled

0 1 11 0 1 1 1 0027 hex

6 -Quick stop active

0 0 0 1 1 1 0007 hex

7 -Fault reaction active

0 X X 1 1 1 1 −

8 -Fault 0 X X 1 0 0 0 0008 hex(2)...0028 hex

(1) This mask can be used by the PLC program to test the diagram state.(2) detected error following operating state 6 - Quick stop active.X: In this state, the value of the bit can be 0 or 1.

52 NHA80945 01/2016

Page 53: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Software Setup

Starting Sequence

Description

The command sequence in the state diagram depends on how power is being supplied to the drive.

There are 3 possible scenarios:

Power stage supply

Direct Direct Mains contactor controlled by the drive

Control stage supply

Not separate (1) Separate Separate

(1) The power stage supplies the control stage.

NHA80945 01/2016 53

Page 54: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Software Setup

Sequence for a Drive Powered by the Power Stage Supply

Description

Both the power and control stages are powered by the power stage supply.

If power is supplied to the control stage, it has to be supplied to the power stage as well.

The following sequence must be applied:

Step 1

Apply the 2 - Shut down command

Step 2

Check that the drive is in the operating state 3 - Ready to switch on. Then apply the 4 - Enable operation command. The motor can be controlled (send a reference value not equal to zero).

NOTE: It is possible, but not necessary to apply the 3 - Switch on command followed by the 4 - Enable Operation command to switch successively into the operating states 3 - Ready to Switch on, 4 - Switched on and then 5 - Operation Enabled. The 4 - Enable operation command is sufficient.

54 NHA80945 01/2016

Page 55: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Software Setup

Sequence for a Drive with Separate Control Stage

Description

Power is supplied separately to the power and control stages.

If power is supplied to the control stage, it does not have to be supplied to the power stage as well.

The following sequence must be applied:

Step 1

The power stage supply is not necessarily present. Apply the 2 - Shut down command

NHA80945 01/2016 55

Page 56: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Software Setup

Step 2

Check that the drive is in the operating state 3 - Ready to switch on. Check that the power stage supply is present (Voltage enabled of the status word).

Apply the 3 - Switch on command

Step 3

Check that the drive is in the operating state 4 - Switched on. Then apply the 4 - Enable operation command. The motor can be controlled (send a reference value not equal to zero). If the power stage supply is still not present in the operating state 4 - Switched on after a time delay

[Mains V. time out] LCt, the drive triggers an error [Input Contactor] LCF.

Power Stage Supply Terminal Display Status Word

Absent nLP 21 hex

Present rdY 31 hex

56 NHA80945 01/2016

Page 57: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Software Setup

Sequence for a Drive with Mains Contactor Control

Description

Power is supplied separately to the power and control stages.

If power is supplied to the control stage, it does not have to be supplied to the power stage as well. The drive controls the mains contactor.

The following sequence must be applied:

Step 1

The power stage supply is not present as the mains contactor is not being controlled. Apply the 2 - Shutdown command.

Step 2

Check that the drive is in the operating state 3 - Ready to switch on. Apply the 3 - Switch on command, which closes the mains contactor and switch on the power stage

supply.

NHA80945 01/2016 57

Page 58: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Software Setup

Software Setup with Unity (M340)

Section 4.3Software Setup with Unity (M340)

What Is in This Section?

This section contains the following topics:

Topic Page

Introduction 59

Drive Configuration 60

58 NHA80945 01/2016

Page 59: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Software Setup

Introduction

Overview

Here is an example of an application that shows how to control a drive with a M340 PLC equipped with a CANopen port. The operator can control the drive directly from Unity. The version of Unity used here is Unity Pro XL

NHA80945 01/2016 59

Page 60: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Software Setup

Drive Configuration

Factory Setting

Before configuring the drive, it is advised to make a factory setting. Go to: [File management] FMt- menu [Factory settings] FCS- submenu

Then configure [Go to Factory Settings] GFS parameter to OK

Command Configuration

To control the drive with a CANopen fieldbus, it is necessary to select CANopen as command channel active.

Go to: [Complete Settings] CSt-

[Command and Reference] CrP- menu

Then configure [Ref.1 channel] Fr1 parameter to [Ref. Freq-CANopen] Can value

Communication Configuration

Select the CANopen address and the Baud rate in the menu: [Communication] COM-

[Comm parameters] CMP-

[CANopen] CnO-

Then configure [CANopen Address] AdCO parameter to [2] 2. [CANopen Baudrate] bdCO parameter to [125 kbps] 125

The drive must be restarted in order to take into account the CANopen address

EDS Integration

If your Unity software does not contain the drive in the CANopen catalog. You must add the EDS file to the hardware catalog manager installed with Unity.

Once imported, you should see the drive in the Motion & Drive section. The two topics default and PDOsonly are used in the CANopen device configuration screen of Unity to select which objects are mapped and linked to an application variable.

60 NHA80945 01/2016

Page 61: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Software Setup

Default: all the objects described in the EDS have reserved memory in the PLC application. PDOs only: Only the TPDO and RPDO objects are mapped in PLC memory. (The current example uses

this function).

Your hardware catalog manager is now updated and contains the drive. If you import only the EDS file you have only the default choice. You must create new functions in the hardware catalog manager if you need several choices.

NOTE: You cannot reopen the project, if the device which is used in an existing unity project is removed from the hardware catalog manager.

Configuring the Drive in the CANopen Master Project

From the project browser opens the CANopen configuration tool by double-clicking the CANopen drop:

Configuration of the Master

The master configuration consists of: Setting the baud rate Setting the SYNC message period Configuring the memory area which is the image of the whole PDOs handled by the PLC.

NHA80945 01/2016 61

Page 62: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Software Setup

Configuration of the Slave

Add a new device and select the drive in the catalog. The drive was previously added to the catalog by importing the EDS file of the drive.

In the example below, TPDO1 and RPDO1 are selected which provides the basic control command of the drive with the CiA402 velocity mode profile.

PDOs are linked to the %Mw variables, the mapping is automatically generated by Unity according to the index defined in the master configuration panel and to the PDOs and to the slave Node ID.

62 NHA80945 01/2016

Page 63: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Altivar Process 900

Operations

NHA80945 01/2016

Operations

Chapter 5Operations

What Is in This Chapter?

This chapter contains the following sections:

Section Topic Page

5.1 Operating States 64

5.2 Operating Modes 65

NHA80945 01/2016 63

Page 64: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Operations

Operating States

Section 5.1Operating States

Configuring Communication Error Response

Description

The response of the drive in the event of a CANopen communication interruption can be configured. Configuration can be performed using the display terminal from the [Complete settings] CSt-, [Error/Warning handling] CSWM-, [Communication Module] COMO- menu via the [CANopen Error Resp] COL submenu.

The values of the [CANopen Error Resp] COL parameter, which triggers a drive detected error [CANopen Com Interrupt] COF are:

The values of the [CANopen Error Resp]CoL parameter, which does not trigger a transition to the operating state faults are:

The fallback speed can be configured in the [Complete settings] CSt-, [Error/Warning handling] CSWM- menu, [Fallback speed] LFF- submenu, using the [FallbackSpeed] LFF parameter.

Value Meaning

[Freewheel Stop] YES Freewheel stop (factory setting)

[Ramp stop] rMP Stop on ramp

[Fast stop] ?FSt Fast stop

[DC injection] dCI DC injection stop

Value Meaning

[Ignore] nO Detected error ignored

[Per STT] Stt Stop according to configuration of [Type of stop] Stt

[Fallback Speed] LFF Change to fallback speed, maintained as long as the detected error persists and the run command has not been removed

[Speed maintained] rLS The drive maintains the speed at the time the detected error occurred, as long as the detected error persists, and the run command has not been removed

WARNINGLOSS OF CONTROL

If this parameter is set to nO, CANopen communication monitoring is disabled. Only use this setting after a thorough risk assessment in compliance with all regulations and standards

that apply to the device and to the application. Only use this setting for tests during commissioning. Verify that communication monitoring has been re-enabled before completing the commissioning

procedure and performing the final commissioning test.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

64 NHA80945 01/2016

Page 65: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Operations

Operating Modes

Section 5.2Operating Modes

What Is in This Section?

This section contains the following topics:

Topic Page

Configuring the Control Channel 66

Configuration of the Drive for Operation in I/O Profile 67

Configuration of the Drive for Operation with CiA 402 Profile in Combined Mode 68

Configuration of the Drive for Operation with CiA 402 Profile in Separate Mode 69

NHA80945 01/2016 65

Page 66: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Operations

Configuring the Control Channel

Overview

This chapter explains how to configure the drive for operation from communication network through three following examples. I/O mode - a simple command word (based on forward, reverse, and reset binary commands). Combined mode (with native profile CiA 402) - Both reference value and command word come from the

communication network. Separate (with native profile CiA 402) - reference value and command come from separate sources: for

example, the command (in CiA 402) comes from the communication network and the reference value from the HMI.

66 NHA80945 01/2016

Page 67: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Operations

Configuration of the Drive for Operation in I/O Profile

Description

For the I/O profile, here is a simple example, which can be extended with additional features. The command word is made of run forward (bit 0 of CMd), run reverse (bit 1 of CMd), and the function fault reset (bit 7 of CMd).

The settings are the following:

The bits of the command word can now be configured.

In the [Command and Reference] CrP- menu configure:

In the [Error/Warning handling] CSWM- menu, [Fault reset] rSt-?submenu, configure:

[Ref Freq 1 Config] Fr1 [HMI] HMI

[Control Mode] CHCF [I/O profile] IO

[Command switching] CCS Default

[Cmd channel 1] Cd1 [CANopen] CAn

[Reverse Assign] rrS [CD01] Cd01

[Fault Reset Assign] rSF [CD07] Cd07

NHA80945 01/2016 67

Page 68: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Operations

Configuration of the Drive for Operation with CiA 402 Profile in Combined Mode

Description

This section describes how to configure the settings of the drive if it is controlled in CiA 402 mode. The example focuses on the not separate mode. Additional modes are detailed in the drive programming manual.

In the [Complete settings] CSt-? menu, [Command and reference] CrP- submenu: [Ref Freq Channel 1] Fr1: is set on according to the communication source you can choose in the

following table:

[Freq Switch Assign] rFC is set to default value ([Ref Freq 1 Config] Fr1). [Control Mode] CHCF: defines if the drive operates in combined mode (reference and command from

the same channel).

For the current example, [Control Mode] CHCF is adjusted to [Not separ.] SIM as reference and control are originated from the communication network:

Origin of the Control Ref1 Channel Setting

CANopen [CANopen] CAn

Profile Ref1 Channel setting

CiA 402 combined mode [Not separ.] SIM

CiA 402 separate mode [Separate] SEp

I/O profile [I/O profile] IO

68 NHA80945 01/2016

Page 69: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Operations

Configuration of the Drive for Operation with CiA 402 Profile in Separate Mode

Description

Alternate combinations are possible, see the drive programming manual for the list of possible settings.

For example:

The drive is controlled from the communication (CANopen) but the reference value is adjusted on the display terminal. The control word comes from the controller and is written according to CiA 402 profile.

The settings are as shown in the table:

[Ref Freq 1 Config] Fr1 [AI1] AI1

[Control Mode] CHCF [Separate] SEp

[Cmd channel 1] Cd1 [CANopen] CAn

[Freq Switch Assign] rFC Factory setting

NHA80945 01/2016 69

Page 70: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Operations

70 NHA80945 01/2016

Page 71: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Altivar Process 900

Diagnostics and Troubleshooting

NHA80945 01/2016

Diagnostics and Troubleshooting

Chapter 6Diagnostics and Troubleshooting

What Is in This Chapter?

This chapter contains the following topics:

Topic Page

Fieldbus Status LEDs 72

Connection for Fieldbus Mode 75

Monitoring of Communication Channel 76

Control-Signal Diagnostics 78

NHA80945 01/2016 71

Page 72: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Diagnostics and Troubleshooting

Fieldbus Status LEDs

LED Indicators

The following figure describes the LEDs status for the module::

LED Description

CANopen Status

This LED indicates the CANopen status:

Item LED Description

1 CAN_RUN CANopen status

2 CAN_ERR CANopen error

Color & Status Description

OFF The CANopen controller is in OFF state

Green single flash The Altivar 9xx is in STOPPED state

Green blinking The Altivar 9xx is in PRE-OPERATIONAL state

Green ON The Altivar 9xx is in OPERATIONAL state

72 NHA80945 01/2016

Page 73: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Diagnostics and Troubleshooting

Error Status

This LED indicates the CANopen error status:

NMT Chart

The [CANopen NMT state] nMtS parameter (logic address 6057, CANopen index/subindex 201E hex/3A) indicates the NMT chart state. The various possible values are [Boot], [Stopped], [Operation] and [Pre-op] (Pre-operational).

This parameter is accessible in the [Display] MOn- → [Communication map] CMM- → [CANopen map] CnM- menu.

PDO Counter

[Number of RX PDO] nbrp and [Number of TX PDO] nbtp indicate the number of PDOs received and the number of PDOs transmitted by the drive (all PDO sets - PDO1, PDO2, and PDO3 - combined).

The values of the counters are rested to zero once 65535 is reached.

This parameter is accessible in the [Display] MOn- → [Communication map] CMM- → [CANopen map] CnM- menu.

Color & Status Description

OFF No detected error reported

Red single flash Detected error reported by the CANopen controller of the Altivar 9xx (example: too many detected error frames)

Red double flash Detected error due to the occurence of a Node Guarding or a Hearbeat event

Red ON The CANopen controller is in Bus OFF state

NHA80945 01/2016 73

Page 74: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Diagnostics and Troubleshooting

Last CANopen Detected Error

The [Error code] ErCO parameter (index/subindex 201E hex/39) indicates the last active CANopen detected error and maintains its value until the last detected error has been cleared.

This parameter is accessible: in the [Display] MOn- → [Communication map] CMM- → [CANopen map] CnM- menu in the [Communication] COM → [Comm Parameters] CMP → [CANopen] CnO- menu.

The possible values are listed below:

PDO Value Display

The value of parameters mapped in PDOs can be displayed using [PDO1 image] PO1-, [PDO2 image] PO2- and [PDO3 image] PO3- submenus.

These submenus are available in [Display] Mon → [Communication map] CMM → [CANopen map] CnM- menu.

The following figure shows the content of [PDO1 image] PO1- submenu:

NOTE: In each of these screens and for each PDO transmitted or received, only the [Transmit PDOo-o] or [Received PDOo-o] words transmitted and received on the CANopen bus are displayed. This means, for example, PDO2 containing only 4 data bytes (that is, RP21 and RP22), the fields [Received PDO2-3] and [Received PDO2-4] are not displayed.

Display Description

[0] No errors detected since the start of CANopen communication.

[1] Bus off.

[2] Node guarding error requiring a return to the NMT initialization state.

[3] CAN overrun.

[4] Heartbeat error requiring a return to the NMT initialization state.

[5] NMT state chart error

74 NHA80945 01/2016

Page 75: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Diagnostics and Troubleshooting

Connection for Fieldbus Mode

Description

If the product cannot be addressed via the fieldbus, first check the connections. The productmanual contains the technical data of the device and information on network and device installation. Check the following: Power connections to the device. Fieldbus cable and fieldbus wiring. Network connection to the device.

NHA80945 01/2016 75

Page 76: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Diagnostics and Troubleshooting

Monitoring of Communication Channel

Command and Reference Channels

All the drive command and reference parameters are managed on a channel-by-channel basis.

Monitoring of Communication Channels

Communication channels are monitored if they are involved in one of the following parameters: The control word ([Cmd Register] CMd) from the active command channel The control word containing the command switch (bit configured on [Cmd switching] CCS) The control word containing the switch for reference value 1'1B (bit configured on [Ref 1B switching]

rCb) The control word containing the switch for reference value 1'2 (bit configured on [Freq Switch Assign]

rFC) The reference frequency or reference speed ([Ref Frequency] LFr or LFRD: Nominal speed value)

from the active channel for reference value Summing reference frequency or reference speed ([Ref Frequency] LFr or LFRD: Nominal speed

value) 2 (assigned to [Summing Input 2] SA2) Summing reference frequency or reference speed ([Ref Frequency] LFr or LFRD: Nominal speed

value) 3 (assigned to [Summing Input 3] SA3) Subtracting reference frequency or reference speed ([Ref Frequency] LFr or LFRD: Nominal speed

value) 2 (assigned to [Subtract Ref Freq 2] dA2) Subtracting reference frequency or reference speed ([Ref Frequency] LFr or LFRD: Nominal speed

value) 3 (assigned to [Subtract Ref Freq 3] dA3) The reference value given by the PID controller (PISP) The PID controller feedback ([AI Virtual 1] AIU1) The multiplication coefficient of the reference values ([Multiplying coeff.] MFr) 2 (assigned to [Ref

Freq 2 Multiply] MA2) The multiplication coefficient of the reference values ([Multiplying coeff.] MFr) 3 (assigned to [Ref

Freq 3 Multiply] MA3)

As soon as one of these parameters has been written once to a communication channel, it activates monitoring for that channel.

If a communication warning is sent (in accordance with the protocol criteria) by a monitored port or fieldbus module, the drive triggers a communication interruption.

The drive reacts according to the communication interruption configuration (operating state Fault, maintenance, fallback, and so on)

If a communication warning occurs on a channel that is not being monitored, the drive does not trigger a communication interruption.

Parameter Name Parameter Code

Taken Into Account by the Drive

Modbus Serial

CANopen Fieldbus Module Ethernet Embedded

Control word CMd CMd1 CMd2 CMd3 CMd5

Extended control word CMI CMI1 CMI2 CMI3 CMI5

Reference speed (rpm) LFd LFd1 LFd2 LFd3 LFd5

Reference frequency (0.1 Hz)

LFr LFr1 LFr2 LFr3 LFr5

Reference for torque control mode (0.1% of the normal torque))

LTR LTR1 LTR2 LTR3 LTR5

Reference value supplied by PI controller

PISP PIr1 PIr2 PIr3 PIr5

Reference value supplied by analog multiplier function

MFr MFr1 MFr2 MFr3 MFr5

76 NHA80945 01/2016

Page 77: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Diagnostics and Troubleshooting

Enabling of Communication Channels

A communication channel is enabled once all the parameters involved have been written at least one time.The drive is only able to start if all channels involved in command and reference value are enabled.

For example:

A drive in DSP402 profile is connected to an active communication channel.

It is mandatory to write at least 1 time the reference value and the command in order to switch from 4-Switched on to 5-Operation enabled state.

A communication channel is disabled: In the event of a communication warning. In forced local mode.

NOTE: On exiting forced local mode:

The drive copies the run commands, the direction, and the forced local reference value to the active channel (maintained).

Monitoring of the active channels for the command and reference value resumes following a time delay [Time-out forc. local] FLOt.

Drive control only takes effect once the drive has received the reference value and the command from the active channels.

NHA80945 01/2016 77

Page 78: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Diagnostics and Troubleshooting

Control-Signal Diagnostics

Introduction

On the display terminal, the [Display] MON-, [Communication map] CMM- submenu can be used to display control-signal diagnostic information between the drive and the controller: Active command channel [Command Channel] CMdC

Value of the control word [Cmd Register] CMd from the active command channel [Command Channel] CMdC

Active reference frequency channel [Ref Freq Channel] rFCC

Value of the reference frequency [Pre-Ramp Ref Freq] FrH from the active target channel [Ref Freq Channel] rFCC

Value of the operating state word [CIA402 State Reg] EtA

Specific data for all available fieldbus are in dedicated submenus. In the [Command word image] CWI- submenu: control words from all channels In the [Freq. ref. word map] rWI- submenu: reference frequency values produced by all channels

Control Word Display

The [Command Channel] CMdC parameter indicates the active command channel.

The [Cmd Register] CMd parameter indicates the hexadecimal value of the control word (CMD) used to control the drive.

The [Command word image] CWI- submenu ([COM. Module cmd.] CMd3) parameter is used to display the hexadecimal value of the control word from the fieldbus module.

Reference Frequency Display

The [Ref Freq Channel] rFCC parameter indicates the active channel for reference frequency.

The [Ref Frequency] LFr parameter indicates the value (in 0.1 Hz units) of the reference frequency used to control the drive.

The [Freq. ref. word map] rWI- submenu ([Com Module Ref Freq] LFr3 parameter is used to display the value (in 0.1 Hz units) of the reference frequency from the fieldbus.

Operating State Word Display

The [CIA402 State Reg] EtA parameter gives the value of the operating state word (ETA).

The table provides the bit details of ETA parameter:

Bit Description

DRIVECOM Status word

Bit0 = 1 Ready to switch on

Bit1 = 1 Switched on

Bit2 = 1 Operation enabled

Bit3 = 1 Operating state fault

Bit4 = 1 Power stage is switched on

Bit5 = 0 Quick stop

Bit6 = 1 Switch on disabled

Bit7 = 1 Warning

Bit8 = 1 Drivecom reserved

Bit9 = 0 Forced local mode in progress

Bit10 = 1 Reference value reached (steady state)

Bit11 = 1 Reference value exceeded (< LSP or > HSP)

Bit12 Reserved

Bit13 Reserved

Bit14 = 1 Stop imposed via STOP key

Bit15 = 0 Motor rotation in forward direction (or stopped)

78 NHA80945 01/2016

Page 79: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Altivar Process 900

Glossary

NHA80945 01/2016

Glossary

A

AbbreviationsReq. = Required

Opt. = Optional

C

CANController Area Network is an internally standardized serial bus system

COBCommunication Object. A unit of transportation in a CAN network. Data must be sent across a CAN Network inside a COB. There are 2048 different COB's in a CAN network. A COB can contain at most 8 bytes of data.

COB IDEach COB is uniquely identified in a CAN network by a number called the COB Identifier (COB-ID).

D

Display terminalThe display terminal menus are shown in square brackets.

For example: [Communication]

The codes are shown in round brackets.

For example: COM-

Parameter names are displayed on the display terminal in square brackets.

For example: [Fallback Speed]

Parameter codes are displayed in round brackets.

For example: LFF

E

Error Discrepancy between a detected (computed, measured, or signaled) value or condition and the specified or theoretically correct value or condition.

F

Factory settingDefault configuration of the product.

FaultFault is an operating state. If the monitoring functions detect an error, a transition to this operating state is triggered, depending on the error class. A "Fault reset" is required to exit this operating state after the cause of the detected error has been removed. Further information can be found in the pertinent standards such as IEC 61800-7, ODVA Common Industrial Protocol (CIP).

Fault ResetA function used to restore the drive to an operational state after a detected error is cleared by removing the cause of the error so that the error is no longer active.

L

LSBLeast Significant Byte

NHA80945 01/2016 79

Page 80: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Glossary

M

Monitoring functionMonitoring functions acquire a value continuously or cyclically (for example, by measuring) in order to check whether it is within permissible limits. Monitoring functions are used for error detection.

MSBMost Significant Byte

N

NMTNetwork Management. One of the service elements of the application layer in the CAN Reference Model. The NMT serves to configure, initialize, and handle detected errors in a CAN network.

P

ParameterDevice data and values that can be read and set (to a certain extent) by the user.

PDOProcess Data Object

PELVProtective Extra Low Voltage, low voltage with isolation. For more information: IEC 60364-4-41

PLCProgrammable logic controller

Power stageThe power stage controls the motor. The power stage generates current for controlling the motor.

Q

Quick StopThe quick Stop function can be used for fast deceleration of a movement as a response to a detected error or via a command.

R

RPDOReceive PDO

S

SYNCSynchronization Object

T

TPDOTransmit PDO

W

WarningIf the term is used outside the context of safety instructions, a warning alerts to a potential problem that was detected by a monitoring function. A warning does not cause a transition of the operating state.

80 NHA80945 01/2016

Page 81: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure

Glossary

Z

Zone of operationThis term is used in conjunction with the description of specific hazards, and is defined as it is for a hazard zone or danger zone in the EC Machinery Directive (2006/42/EC) and in ISO 12100-1.

NHA80945 01/2016 81

Page 82: Altivar Process 900 NHA80945 01/2016 Altivar … Process 900 CANopen Manual - VW3A3608, 618, 628 ... AdCo ... Read and understand these instructions before performing any procedure