alternator parallel operation

5
Objective: 1. To study the transference of loasd between two alternators running in parrallele, keeping the load,frequency,and voltage constant. 2. To stiudy the variation of voltamperes with respect to alternator excitation, keeping input power , output load, voltage and frequency constant. Theory: The conditions for successful parallel operation of alternator are: 1. The alternators shall have the same frequency 2. The alternators shall have the same alternator induced voltage 3. The alternators shall have the same phase sequence 4. The alternator voltages shall be in phase. The laod output of ther alterantor is governed by the input power from its prime -mover. Variation of excitation gives rise to a change in the kVar ouput; the kW output remins unchanged. Procedure: 1. The alternators are conneted as shown in FIG.1 using two single-phase wattmeters 2. The d.c shunt motors are started and the alternators are brought up to speed. 3. By varying the alternator fields, the terminal voltages are brought up to the rated values(110V). 4. The speeds of the sets are adjusted by means of the motor field rheostat control until thealternators run at rated frequency 5. The synchronising switch is closed in the middle of a dark period of the lamps. ( The alterantors should now be working in parallel, but they should not be delivering any load. Also , if the voltage and speed have been properly adjusted, there should be no interchange odf current between the alternators and the ammeters should read zero. 6. For a particular load output at consatnt frequency and voltage, input ot the d.c machine is varied and the outputs shared by each alternator are noted from the wattmeter readings. Inputs to the d.c side are also noted. 7. A graph is plotted between the input power and the load shared by each machine, as shown in FIG.2 8. Keeping the input power , outputload , terminal voltage an dfrequency constant, the current outut of each alternator is noted for different excitaitons. 9. A graph of output (in VA) versus excitation as shown in FIG.3 is plotted. Observations: Wattmeter constants = Frequency= Voltage = Load Current= LOAD SHARING No. W1 (watts) A1 (amps) Iac1 (amps) Vdc1 (Volts) W2 (watts) A2 (amps) Iac2 (amps) Vdc2 (volts) Voltage = Load current =

Upload: ullahasgar

Post on 26-Mar-2015

130 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: alternator parallel operation

Objective:

1. To study the transference of loasd between two alternators running in parrallele, keeping theload,frequency,and voltage constant.

2. To stiudy the variation of voltamperes with respect to alternator excitation, keeping input power, output load, voltage and frequency constant.

Theory:

The conditions for successful parallel operation of alternator are:1. The alternators shall have the same frequency2. The alternators shall have the same alternator induced voltage3. The alternators shall have the same phase sequence4. The alternator voltages shall be in phase.

The laod output of ther alterantor is governed by the input power from its prime -mover. Variationof excitation gives rise to a change in the kVar ouput; the kW output remins unchanged.

Procedure:

1. The alternators are conneted as shown in FIG.1 using two single-phase wattmeters2. The d.c shunt motors are started and the alternators are brought up to speed.3. By varying the alternator fields, the terminal voltages are brought up to the rated values(110V).4. The speeds of the sets are adjusted by means of the motor field rheostat control until

thealternators run at rated frequency5. The synchronising switch is closed in the middle of a dark period of the lamps. ( The

alterantors should now be working in parallel, but they should not be delivering any load. Also ,if the voltage and speed have been properly adjusted, there should be no interchange odf currentbetween the alternators and the ammeters should read zero.

6. For a particular load output at consatnt frequency and voltage, input ot the d.c machine is variedand the outputs shared by each alternator are noted from the wattmeter readings. Inputs to thed.c side are also noted.

7. A graph is plotted between the input power and the load shared by each machine, as shown inFIG.2

8. Keeping the input power , outputload , terminal voltage an dfrequency constant, the currentoutut of each alternator is noted for different excitaitons.

9. A graph of output (in VA) versus excitation as shown in FIG.3 is plotted.

Observations:

Wattmeter constants = Frequency=

Voltage = Load Current=

LOAD SHARINGNo. W1

(watts)A1(amps)

Iac1(amps)

Vdc1(Volts)

W2(watts)

A2(amps)

Iac2(amps)

Vdc2(volts)

Voltage =Load current =

Page 2: alternator parallel operation

Frequency =W1 =W2 =

Machine I Machine IINo.

If1(amp) Iac1(amp) 1.73VIac1(VA) If2(amp) Iac2(amp) 1.73Viac2(VA)

Results:

Machine I Machine IIS.No.A.C Output,Watts D.C Input ,Watts A.C Output,Watts D.C Input ,Watts

Remark:

Variation of load angle with cahnge in the output load can be observed with a stroboflasharrangement

Page 3: alternator parallel operation

FIG.1 Two D.C motor -alternator sets as follows are used.

Ifpm

Rf1=0-185 ohm

S1 Ra Ia

0-60A Starter A1 F1 F1110 VD.C RSupply Y 0-150V B D.C N

A2 F2 F2 Star-connected alternator 130 V,13.9 A, 3 kVA,50Hz Rf2 =0-35 ohm 1000 rpm

0-6 A D.C L1

R1 W W 110V 10A 0-20A R2FromAlternator 1 N1 N2 0-150 V From Alternator 2 46-54 Hz 46-54 Hz Y1 Y2

B1 B2

0-60A L2 To 3-phase load

L3

MVt

A

A

Vg Vb

A

A

F F

A

A

Page 4: alternator parallel operation

FIG.2

Output Power/Machine (Watts)1000

800 Machine I

600 Machine II

400

200

30 0 500 700 900 1100 1300 1500 1700 Input Power/Machine (Watts)

FIG.3 Load Current I1

Load Current I2

Field MachineII MachineICurrent(Amps)

MachineI Machine II

Volt- amperes

Page 5: alternator parallel operation