Number Alarm Cause: Heat pump operation: Action: Type 1 Sensor fault BT1 Sensor not connected/defective Calculated flow temperature is set to min calculated flow temperature Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 2 Sensor fault BT2 Sensor not connected/defective (heating medium return) Addition blocked. GM is calculated with "condensor out" sensor. Even if "condensor out" sensor is missing, heating is blocked. VVM 500: 1. Using BT 3 if its available. 2. If BT 3 is not avaialable, BT63 will be used. Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 3 Sensor fault BT3 Sensor not connected/defective (heating medium return) Compressor is blocked when hot water loading. VVM 500: Let the heating medium pump go according to the speed that is chosen in the menu 5.1.19= constantly Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 6 Sensor fault BT6 Sensor not connected/defective (hot water, controlling) VVM 500: Using BT54 Automatic reset Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 7 Sensor fault BT7 Sensor not connected/defective (hot water peak) Automatic reset Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 8 Alarm overzicht November 2018

Upload: lyanh

Post on 04-May-2019

228 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Alarm overzicht - nibe.eu · Automatic reset Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 32 Sensor fault BS1 Air flow is out of range of

Number Alarm Cause: Heat pump operation: Action: Type

1 Sensor faultBT1

Sensor notconnected/defective

Calculated flowtemperature is set to mincalculated flowtemperature

Proposal: Check thesensor and itsconnections. See alsothe electrical wiringdiagram.

2 Sensor faultBT2

Sensor notconnected/defective(heating mediumreturn)

Addition blocked. GM iscalculated with"condensor out" sensor.Even if "condensor out"sensor is missing, heatingis blocked.

VVM 500: 1. Using BT 3 ifits available. 2. If BT 3 isnot avaialable, BT63 willbe used.

Proposal: Check thesensor and itsconnections. See alsothe electrical wiringdiagram.

3 Sensor faultBT3

Sensor notconnected/defective(heating mediumreturn)

Compressor is blockedwhen hot water loading.

VVM 500: Let the heatingmedium pump goaccording to the speedthat is chosen in themenu 5.1.19= constantly

Proposal: Check thesensor and itsconnections. See alsothe electrical wiringdiagram.

6 Sensor faultBT6

Sensor notconnected/defective(hot water,controlling)

VVM 500: UsingBT54

Automatic reset Proposal: Check thesensor and itsconnections. See alsothe electrical wiringdiagram.

7 Sensor faultBT7

Sensor notconnected/defective(hot water peak)

Automatic reset Proposal: Check thesensor and itsconnections. See alsothe electrical wiringdiagram.

8

Alarm overzicht November 2018

Page 2: Alarm overzicht - nibe.eu · Automatic reset Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 32 Sensor fault BS1 Air flow is out of range of

10 Sensor fault:BT10

Sensor notconnected/defective(brine in)

GP2 switches to manualspeed if auto-control isselected. Automaticallyresets when the sensorhas been runningcorrectly in 60 sec. GP2returns to auto-controlled operation.

Proposal:- Check the sensor andits connections.

11 Sensor faultBT11

Sensor notconnected/defective(condensor out)

Compressor blocked Proposal: Check thesensor and itsconnections. See alsothe electrical wiringdiagram.

12 Sensor faultBT12

Sensor notconnected/defective(condensor return)

Supply sensor (BT2) isused for controlling maxcondensor outtemperature for thecompressor. If supplysensor is also missing;blocked heating modeand blocked compressorin HW mode.

Proposal: Check thesensor and itsconnections. See alsothe electrical wiringdiagram.

16 Sensor faultBT16

Sensor notconnected/defective(evaporator)

Automatic reset Proposal: Check thesensor and its settings.See also the electricalwiring diagram.

20 Ground source:Sensor faultAZ1-BT20Exhaust air:Sensor faultBT20

Sensor notconnected/defective(exhaust air)

Ground source: Pump(AZ1-GP2) in FLM isblocked.Exhaust air: Automaticreset

Proposal: Check thesensor and itsconnections. See alsothe electrical wiringdiagram.

21 Ground source:Sensor faultAZ1-BT21Exhaust air:Sensor faultBT21

Sensor notconnected/defective(extract air)

Grounde source: Pump(AZ1-GP2) in FLM isblocked.Exhaust air: Automaticreset

Proposal: Check thesensor and itsconnections. See alsothe electrical wiringdiagram.

22 Sensor faultDEW-BT6

Sensor notconnected/defective(hot water sensor,controlling in extrawater heater)

25 Sensor faultBT25

Sensor notconnected/defective(heat mediumreturn external)

External additive blocked Proposal: Check thesensor and itsconnections. See alsothe fault-tracingschedule for thecurrent product.

26 Sensor faultAZ1-BT26

Sensor notconnected/defective(brine, collector in)

Pump (AZ1-GP2) in FLM isblocked.

Proposal: Check thesensor and itsconnections. See alsothe fault-tracingschedule for thecurrent product.

Page 3: Alarm overzicht - nibe.eu · Automatic reset Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 32 Sensor fault BS1 Air flow is out of range of

27 Sensor faultBP8

Sensor notconnected/defective(low pressuresensor)

Compressor blocked Proposal: Check thesensor and itsconnections.

28 Sensor faultBT71

Sensor notconnected/defective(external heatingmedium return)

No action. Togehter withalarm 25; heat is blocked.

Proposal: Check thesensor and itsconnections.

29 Sensor faultBT29

Sensor notconnected/defective(compressor oiltemperature)

Compressor blocked Proposal: Check thesensor and itsconnections.

31 Sensor faultBT63

Sensor notconnected/defective(heating mediumsupply afterimmersion heater)

VVM 500: Blockinginternal electricaddition

Automatic reset Proposal: Check thesensor and itsconnections. See alsothe electrical wiringdiagram.

32 Sensor faultBS1

Air flow is out ofrange of the airvelocity sensor

Automatic reset.Compressor blocked.

Check that the filter isinstalled. Check thefan speed.

33 Sensor faultEP30-BT53

Sensor notconnected/defective(solar collectors)

Solar additive blocked. Proposal: Check thesenors and itsconnections. See alsothe electrical wiringdiagram.

34 Sensor faultEP30-BT53

Sensor notconnected/defective(solar panel)

Solar additive blocked Proposal: Check thesensor and itsconnections. See alsothe electrical wiringdiagram.

35 Sensor faultEM1-BT52

Sensor notconnected/defective(boilertemperature)

Shunt closes. Burnershuts down.

Proposal: Check thesensor and itsconnections. See alsothe electrical wiringdiagram.

36 Sensor faultEP21-BT2

Sensor notconnected/defective(supply sensor,heating system 2)

Control on return sensor(EP21-BT3)

Proposal: Check thesensor and itsconnections. See alsothe electrical wiringdiagram.

37 Sensor faultEP22-BT2

Sensor notconnected/defective(supply sensor,heating system 3)

Control on return sensor(EP22-BT3)

Proposal: Check thesensor and itsconnections. See alsothe electrical wiringdiagram.

38 Sensor faultEP23-BT2

Sensor notconnected/defective(supply sensor,heating system 4)

Control on return sensor(EP23-BT3).

Proposal: Check thesensor and itsconnections. See alsothe electric wiringdiagram.

Page 4: Alarm overzicht - nibe.eu · Automatic reset Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 32 Sensor fault BS1 Air flow is out of range of

39 Sensor faultEQ1-BT64

Sensor notconnected/defective(brine, supply)

Brine blocked, brineshunt closes.

Proposal: Check thesensor and itsconnections. See alsothe electric wiringdiagram.

40 Compressorphase1 missing

Compressor phaseis missing or hasbeen below 160V inmore than 30 min.

Compressor blocked Proposal: Check thephase. Reset thephase.

41 Compressorphase 2 missing

Compressor phaseis missing or hasbeen below 160V inmore than 30 min.

Compressor blocked Proposal: Check thephase. Reset thephase.

42 Compressorphase 3 missing

Compressor phaseis missing or hasbeen below 160V inmore than 30 min.

Compressor blocked Proposal: Check thephase. Reset thephase.

43 Faulty phasesequence

Phases ar connectedin wrong sequence

Compressor blocked Proposal: Reconnectthe phase sequenceon incomingelectricity.

44 Overheatedsoftstart

Fuses for the softstart card aredefective

Compressor blocked. - Defective fuse- Defective soft startcardAlso read: TDI Alarm44 F1345 2013-12-18

45 Motor protectionon single phase(Norway) hasprobably beentriggered.

50 High pressurealarm

The high pressureswitch hastriggeredrepeatedly

Compressor blocked.Manual reset.

Bad circulation in theheating mediumcircuit.Proposal:- Bleed heat pumpand climate system- Check the heatingmedium pump- Open any radiatorthermostats- Check that theparticle filter is notblocked- Check that thepressure switch iscorrectly connectedFault in coolingcircuit:- Call a qualifiedrefrigerationtechnician

51 Low pressurealarm

F1145: Lowpressure sensor hasbeen below its cut-off value. Others:

Compressor blocked.Manual reset.

Proposal:Groundsource: Checkthe brine flow andbrine frost protection

Page 5: Alarm overzicht - nibe.eu · Automatic reset Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 32 Sensor fault BS1 Air flow is out of range of

The low pressureswitch hastriggered.

point. See also theelectric wiringdiagram. Exhaust air: -Check ventilation flowand exhaust airtemperature. - Checkthat the pressureswitch is correctlyconnected - Check thedefrost function andthe sensors thatcontrol it.

52 Temperaturelimiter

Temperaturelimiter has tripped

Immersion heaterblocked. Manual reset.

Proposal:- Check if air insystem.- Check if heatingmedium flow iscorrect.- Manual reset of thetemerature limiter.See also the electricwiring diagram.

53 Level switch Level switchbrine /pressureswitch hastriggered

The compressor andbrine pump are blocked.

Proposal: Check andseal any leaks in thecollector circuit.

54 The motorprotection breakerhas triggered.

Proposal: Check thecabling connections ofthe compressor.Manual reset.

55 Hot gas alarm Comperssor hasbeen stoppedbecause the hot gastemperatureexceeded its limits.

Compressor blocked.Manual reset.

Proposal:Ground source: Call aqualified refrigerationtechnician.Exhaust air: See alarmnumber 50, Highpressure alarm.

56 Incorrect serialnumber

Serial number doesnot exist

Compressor stopped andrelay deactivated

Proposal: Check theserial number

57 Incorrectfirmware

Serial number andfirmware do notmatch.

Compressor blocked andrelay deactivates.

Proposal: Make surethat the firmware isdesigned for theproduct and serialnumber.

58 Pressure switch High- or lowpressure switchhave triggered.

Compressor blocked. Bad circulation inheating medium orcollector circuit.Proposal:- Bleed heat pump,climate system andcollector circuit- Check the brinefreezing point- Check the heatingmedium and brinepump- Open any radiator

Page 6: Alarm overzicht - nibe.eu · Automatic reset Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 32 Sensor fault BS1 Air flow is out of range of

thermostats- Check that theparticle filter is notblocked- Check that thepressure switch iscorrectly connectedFault in coolingcircuit:- Call a qualifiedrefrigerationtechnician

60 Low HTF out The temperature ofthe outgoing brinegoes below the setmin- temperatureand the alarm isselected.

Compressor blocked. Proposal:Bad circulation in thebrine circuit- Check the brinepump- Check that the brineis bled. Minimum limitis usually changedonly at groundwaterinstallations and opensystems.

63 Low air flowToo low air flow atair flow sensor BS1

Compressor blocked Check the air filter ,fan speed and air flow

64 Low exhaust airtemperature

Exhaust airtemperature hasbeen below 16° Cand not risen above17° C within 60minutes.

Compressor blocked,automatic reset.Resets when the exhaustair temperature has beenabove 17° C in 60minutes.

For firmware versionbefore 1770 - select"auxiliary operation".For firmware versionfrom 1770 onwards-the machine switchesto auxiliary operationmode automatically.

65 Highcondensationwater level

Alarm fromexternal levelmonitor

Compressor blocked - Check the outflowfrom externalcondensation watercontainer

66 Highcondensationwater level

Alarm from levelmonitor incondensation watercontainer

Compressor blocked - Check that the waterhas a free flow fromthe container- Empty watercontainer

67 AntifreezeprotectionSupply air

Supply airtemperature (BT22)is below 5° C .

Fans stops andcompressor is blocked.Any blocking ofimmersion heaterrepeals.

Suggestions:

- Bleed the supply airbattery (QM 21).

- Check the watertemperature and theflow to the heatingbattery.

69 Not affected

Page 7: Alarm overzicht - nibe.eu · Automatic reset Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 32 Sensor fault BS1 Air flow is out of range of

Non-calibratedair flow sensor

The air flow sensorhas not beencalibrated

Perform a ventilationadj u stment and setthe real air flow inmenu 5.1.5.1

70 Perm. com.error inputcard

No communicationwith the input card

Calculated flow is set tomin. flow. Manual reset.

Proposal: Check thecommunicationcircuits connections onthe input card anddisplay card.

71 Perm. com.error base card

No communicationwith the base card(AA2 at AA26).

Compressor blocked.Manual reset.

Proposal: Check thecommunicationcircuits connections onthe base-, input- anddisplay card.

72 Perm. com.error softstartcard

No communicationwith the softstartcard.

Compressor blocked. Proposal: Check thecommunicationcircuits connections onsoftstart card andbase card.

73 Perm. com.error heatingsystem 2

No communicationwith the accessorycard.

Accessory blocked. Proposal:- Check the powersupply leading to theaccessory card.- Check thecommunication cablesleading to theaccessory card.- Check the setting ofthe dipswitch.

74 Perm. com.error heatingsystem 3

No communiationwith the accessorycard.

Accessory blocked. Proposal:- Check the powersupply leading to theaccessory card.- Check thecommunication cablesleading to theaccessory card.- Check the setting ofthe dipswitch.

75 Perm. com.error base card No communication

with the base card(AA26).

Compressor blocked.Manual reset.

Check thecommunication circitsconnections on htebase-, input- anddisplay card.

76 Perm. com.error heatingsystem 4

No communicationwith the accessorycard.

Accessory blocked. Proposal:- Check the powersupply leading to theaccessory card.- Check thecommunication cablesleading to theaccessory card.- Check the setting ofthe dipswitch.

77 Accessory blocked.

Page 8: Alarm overzicht - nibe.eu · Automatic reset Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 32 Sensor fault BS1 Air flow is out of range of

Perm. com.error additivewith shunt

No communicationwith the accessorycard.

Proposal:- Check the powersupply leading to theaccessory card.- Check thecommunication cablesleading to theaccessory card.- Check the setting ofthe dipswitch.

78 Perm. com.error pool

No communicationwith the accessorycard.

Accessory blocked. Proposal:- Check the powersupply leading to theaccessory card.- Check thecommunication cablesleading to theaccessory card.- Check the setting ofthe dipswitch.

79 Perm. com.error FLM

Permanentcommunicationfault with theaccessory card forFLM.Communicationcables to the cardare incorrect orincorrectlyinstalled.Fault in thecommunicationcircuits in theaccessory-, input- ordisplay card.Incorrect address onthe dipswitch.

Accessory blocked. Check the cables andcards.

83 Unsuccessfuldefrosting F 1

10 :

Defrost discontinued.Compressor stopped.

P r op o sal

86 Perm. com.error SAM 40

No communicationwith the accessorycard for SAM 40

- Check the powersupply to theaccessory card.- Check the setting of

Page 9: Alarm overzicht - nibe.eu · Automatic reset Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 32 Sensor fault BS1 Air flow is out of range of

which is activatedin menu 5.2.

the dipswitch.- Check thecommunication cablesleading to theaccessory card.

87 Perm. com.error stepcontrolledadditive

Permanentcommunicationfault with theaccessory card withstep controlledadditive.

Accessory blocked. Proposal: Check thecables and cards.

88 Perm. com.error Solar

Permanentcommunicationfault with theaccessory card forSolar.Communicationcables to the cardare incorrect orincorrectlyinstalled.Fault in thecommunicationcircuits in theaccessory-, input- ordisplay card.Incorrect address onthe dipswitch.

Accessory blocked. Proposal: Check thecables and cards.

89 Perm. com.error HPAC

Permanentcommunicationfault with theaccessory card forHPAC.Communicationcables to the cardare incorrect orincorrectlyinstalled. Fault inthe communicationcircuits in theaccessory-, input- ordisplay card.Incorrect address onthe dipswitch.

Accessory blocked. Proposal: Check thecables and cards.

90 Perm. com.faultgroundwaterpump

Permanentcommunicationfault with theaccessory card forgroundwaterpump.Communicationcables to the cardare incorrect orincorrectlyinstalled.Fault in thecommunicationcircuits in theaccessory-, input- ordisplay card.

Accessory blocked. Proposal: Check thecables and cards.

Page 10: Alarm overzicht - nibe.eu · Automatic reset Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 32 Sensor fault BS1 Air flow is out of range of

Incorrect address onthe dipswitch.

91 Perm. com.error HWC

Permanentcommunicationfault with theaccessory card forhot watercirculation.Communicationcables to the cardare incorrect orincorrectlyinstalled.Fault in thecommunicationcircuits in theaccessory-, input- ordisplay card.Incorrect address onthe dipswitch.

Accessory blocked. Proposal: Check thecables and cards.

92 Perm. com.error DEW Permanent

communicationfault with theaccessory card forDEW.Communicationcables to the cardare incorrect orincorrectlyinstalled.Fault in thecommunicationcircuits in theaccessory-, input- ordisplay card.Incorrect address onthe dipswitch.

Accessory blocked. Proposal: Check thecables and cards.

93 Perm. com.error 2-pipescooling

Permanentcommunicationfault with theaccessory card for2-pipes cooling.Communicationcables to the cardare incorrect orincorrectlyinstalled.Fault in thecommunicationcircuits in theaccessory-, input- ordisplay card.Incorrect address onthe dipswitch.

Accessory blocked. Proposal: Check thecables and cards.

94 Perm. com.error PCD4

Permanentcommunicationfault with the

Accessory blocked. Proposal: Check thecables and cards.

Page 11: Alarm overzicht - nibe.eu · Automatic reset Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 32 Sensor fault BS1 Air flow is out of range of

accessory card for4-pipes passivecooling.Communicationcables to the cardare incorrect orincorrectlyinstalled.Fault in thecommunicationcircuits in theaccessory-, input- ordisplay card.Incorrect address onthe dipswitch.

95 Perm. Com.Error

Permanentcommunicationfault with

Accessory blocked. Proposal: Check cablesand cards.

96 Perm. Com.Room unit,zone 1

Permanentcommunicationfault with roomunit, zone 1.

Room unit blocked. Proposal: Checkcommunicationcables.

97 Perm. Com.Room unit,zone 2

Permanentcommunicationfault with roomunit, zone 2

Room unit blocked. Proposal: Checkcommunicationcables.

98 Perm. Com.room unit,zone 3

Permanentcommunicationfault with roomunit, zone 3

Room unit blocked. Proposal: Checkcommunication cables

99 Perm. Com.room unit,zone 4

Permanentcommunicationfault with roomunit, zone 4.

Room unit blocked Proposal: Checkcommunicationcables.

100 Perm. Com.error inverter

Permanentcommunicationfault with theinverter

Compressor blocked Propposal:- Check the powersupply leading toinverter andcommunicationcables.

101 Sensor faultBT1

Sensor temporarilymissing

Proposal: Check anysensors andconnections

102 Sensor faultBT2

Sensor temporarilymissing

Proposal: Check anysensors andconnections

103 Sensor faultBT3

Sensor temporarilymissing

Proposal: Check anysensors andconnections

104 Sensor faultBT4

Sensor temporarilymissing

Proposal: Check anysensors andconnections

105

Page 12: Alarm overzicht - nibe.eu · Automatic reset Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 32 Sensor fault BS1 Air flow is out of range of

Sensor faultBT5

Sensor temporarilymissing

Proposal: Check anysensors andconnections

106 Sensor faultBT6

Sensor temporarilymissing

Proposal: Check anysensors andconnections

107 Sensro faultBT7

Sensor temporarilymissing

Proposal: Check anysensors connections

108 Sensor faultBT8

Sensor temporarilymissing

Proposal: Check anysensors andconnections

109 Sensor faultBT9

Sensor temporarilymissing

Proposal: Check anysensors andconnections

110 Sensor faultBT10

Sensor temporarilymissing

Proposal: Check anysensors andconnections

111 Sensor faultBT11

Sensor temporarilymissing

Proposal: Check anysensors andconnections

112 Sensor faultBT12

Sensor temporarilymissing

Proposal: Check anysensors andconnections

113 Sensor faultBT13

Sensor temporarilymissing

Proposal: Check anysensors andconnections

114 Sensor faultBT14

Sensor temporarilymissing

Proposal: Check anysensors andconnections

115 Sensor faultBT15

Sensor temporarilymissing

Proposal: Check anysensors andconnections

116 Sensor faultBT16

Sensor temporarilymissing

Proposal: Check anysensors andconnections

117 Sensor faultBT17

Sensor temporarilymissing

Proposal: Check anysensors andconnections

118 Sensor faultBT18

Sensor temporarilymissing

Proposal: Check anysensors andconnections

119 Sensor faultBT19

Sensor temporarilymissing

Proposal: Check anysensors andconnections

120 Sensor faultBT20

Sensor temporarilymissing

Proposal: Check anysensors andconnections

140

Page 13: Alarm overzicht - nibe.eu · Automatic reset Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 32 Sensor fault BS1 Air flow is out of range of

Compressorphase 1 missing

Compressor phase 1has been brieflymissing

Proposal: No actionneeded. Possibly checkcompressor phase.

141 Compressorphase 2 missing

Compressor phase 2has been brieflymissing

Proposal: No actionneeded. Possibly checkcompressor phase.

142 Compressorphase 3 missing

Compressor phase 3has been brieflymissing

Proposal: No actionneeded. Possibly checkcompressor phase.

145 Temporarygeneral phasefault

Temporary problemwith thecommunicationfrom the base cardto the motorprotection

Proposal: Checkcables/cards

150 High condensorout

Condensor out hasreached maxpermittedtemperature

Automatic reset

155 Hot gas alarm The Hot gas (BT14)has temporarillybeen over 135° C

Compressor stopped.Automatically reset whenthe hot gas is below 90°C.

Proposal:- Contact a qualifiedservice technician.

158 Low defrosttemperature The temperature at

the defrost (BT76) isbelow -25° C .

Defrostdiscontinued. Compressorstopped.

Proposal:- Check the defrostfunction- Check the defrostsensor (BT76)- Check solenoid valve

159 Highevaporatortemperature

The evaporatortemperature (BT16)has exceeded

Compressorstopped. Defrostdiscontinued.

Proposal:- Check the defrostfunction- Check theevaporator sensor(BT16)- Check solenoid valve

160 Low HTFout Brine out hasreached set mintemperature

Automatic reset

161 High HTFin Brine in hasreached set maxtemperature

Automatic reset

162 High condensorout

Condensor out hasreached maxpermittedtemperature

Automatic reset

163 High condensorin Condensor exceeds

max temperatureAutomatic reset

Page 14: Alarm overzicht - nibe.eu · Automatic reset Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 32 Sensor fault BS1 Air flow is out of range of

164 Low exhaust airtemperature

See alarm 64 Automatic reset whenthe temperature exceeds17° C below X minutes

166 Electricalanode incorrect

Fault in theelectrical anode

Proposal:- Check the electricanode, circuit boardat the electric anodeand the cables to theelectric anode.

170 Com. errorinput card

Communicationwith the input cardis temporarilymissing

Proposal: Check anycables/cards

171 Com. errorbase card

Communicationwith the base cardis temporarilymissing

Proposal: Check anycables/cards

172 Com. errorsoftstart card

Communicationwith the softstartcard is temporarilymissing

Proposal: Check anycables/cards

173 Com. errorheating system2

Communicationwith accessory cardfor climate system 2temporarily missing

Proposal: Check anycables/cards

174 Com. errorheating system3

Communicationwith accessory cardfor climate system 3temporarily missing

Proposal: Check anycables/cards

175 Start-up ofsoftstart card

The softstart card isstarted up. Takesapprox 20 sec

Proposal: Check anycables/cards

176 Com. errorheating system4

Communicationwith accessory cardfor climate system 4temporarily missing

Proposal: Check anycables/cards

177 Com. erroraddition withmixing valve

Communicationwith accessory cardfor mixing valvecontrolledadditional heattemporarily missing

Proposal: Check anyconnections, cablesand cards.

178 Com. errorpool

Communicationwith accessory cardfor pooltemporarily missing

Proposal: Check anycables/cards

179 Com. error FLM Communicationwith accessory FLMis temporarilymissing

Proposal: Check anycables/cards

180 Freeze prot Freeze protectionactive. Occurs if the

Permits room heating

Page 15: Alarm overzicht - nibe.eu · Automatic reset Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 32 Sensor fault BS1 Air flow is out of range of

outdoortemperature isbelow 3 degreesand no heating ispermitted.

181 Failed periodicincrease

Periodic increasedid not reach thestop temperaturewithin 5 hours

182 Load monitoractivated

One or more powersteps cannot beactivated becausethe current in atleast one phase istoo high

Proposal: Check thephase load. It mayrequire a larger mainfuse.

183 Defrosting Defrosting inprogress

No action

184 Filter alarm Air filter needscleaning

Proposal: Clean the airfilter and restart theheat pump.

185 Anti-freezesupply air

Supply airtemperature (BT22)or the returntemperature fromthe heating battery(BT69) is below

Fans stopped andcompressor blocked. Anyblockage of theimmersion heater islifted.

- Check the watertemperature and theflow to the heatingbattery.

187 Com. error stepcontrolledadditional heat

Temporarycommunicationfault with accessorycard with stepcontrolledadditional heat

Proposal: Check anycables/cards

188 Com. faultsolar

Temporarycommunicationfault with accessorycard with solar

Proposal: Check anycables/cards

189 Com. errorHPAC

Temporarycomunication faultwith accessory cardwith HPAC

Proposal: Check anycables/cards

190 Com. errorground waterpump

Temporarycommunicationfault with accessorycard with groundwater pump

Proposal: Check anycables/cards

191 Com. errorHWC

Temporarycommunicationfault with accessorycard with hot watercirculation

Proposal: Check anycables/cards

192 Com. error 2pipe cooling

Temporarycommunicationfault with accessory

Proposal: Check anycables/cards

Page 16: Alarm overzicht - nibe.eu · Automatic reset Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 32 Sensor fault BS1 Air flow is out of range of

card with 2 pipecooling

193 Com. ErrorDEW

Temporarycommunicationfault with accessorycard DEW

Proposal: Check anycables/cards

194 Com. ErrorPCD4

Temporarycommunicationfault with accessorycard with 4 pipecooling

Proposal: Check anycables/cards

195 Com. errorFJ V M

Temporarycommunicationfault with

Proposal: Check anycables/cards

196 Com. room unitzone 1

Temporarycommunicationfault with roomunit zone 1

Proposal: Check anycables/cards

197 Com. room unitzone 2

Temporarycommunicationfault with roomunit zone 2

Proposal: Check anycables/cards

198 Com. room unitzone 3

Temporarycommunicationfault with roomunit zone 3

Proposal: Check anycables/cards

199 Com. room unitzone 4

Temporarycommunicationfault with roomunit zone 4

Proposal: Check anycables/cards

200 Com. errorinverter

201 Inverter alarm Inverter indicatesalarm

See chapterTroubleshooting inthe Service manualSEM NIBE F750 forfault specification.Alarm code stands inalarm log in F750 inbrackets.

202 Inverter fault Inverter indicatesalarm

See chapterTroubleshooting inthe Service manual:SEM NIBE F750 forfault specification.Alarm code stands inalarm log in F750 inbrackets.

203 Inverter errortype I

Permanent inveterfault type I

See alarm tab menu 6for error code. SeechapterTroubleshooting inthe Service manual:

Page 17: Alarm overzicht - nibe.eu · Automatic reset Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 32 Sensor fault BS1 Air flow is out of range of

SEM NIBE F750 forfault specification.

204 Inverter errortype II

Permanent inverterfault type II

See alarm tab menu 6for error code. SeechapterTroubleshooting inthe Service manual:SEM NIBE F750 forfault specification.

205 Inverter errortype III

Permanent inverterfault type III

See alarm tab menu 6for error code. SeechapterTroubleshooting inthe Service manual:SEM NIBE F750 forfault specification.

206 Perm. com.error HW-comfort

No communicationwith accessory cardfor 15 sec

Proposal:- Check the powersupply leading to theaccessory card.- Check thecommunication cablesleading to theaccessory card.- Check the setting ofthe dipswitch.

207 Com. error HW-comfort

No communicationwith the accessory

Proposal: Check anycables/cards

208 Com. error Acc-EB1

No communicationwith accessory cardfor 15 sec

VVM 500:- Check thecommunication cables- Check the dip switchsettings

209 Com. errorACC-EPxx

3 communicationfaults in a row withthe accessory card

Blocking addition

213 Inverter errortype I

Temporary inverterfault

Inverter blocked. If thealarm is active more than1h the alarm will passover to alarm 203(Permanent inverter faulttype II)

214 Inverter errortype II

Temporary inverterfault type II

Compressor blocked. Ifthe alarm is active morethan 1h or if the alarm isactivated 3 times in 2h,the alarm will pass overto alarm 204 (permanentinverter fault type II)

215 Inverter errortype III

Temporary Inverterfault type III

Compressor blocked. Ifthe alarm is active morethan 1h or if the alarm isactivated 3 times in 2h,the alarm will pass over

Page 18: Alarm overzicht - nibe.eu · Automatic reset Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 32 Sensor fault BS1 Air flow is out of range of

to alarm 204 (permanentinverter fault type II)

216 Inverter alarmtype II Incorrect inverter Manual reset in menu.

Compressor blocked.Suggestion:

- Upgrade firmware toat least version:

F1155,F1255

v7740R4

F2120 v431

F750 v7679R4

F730 v7696R6

- Replace the inverter

220 High pressurealarm

Heat pump(selected outdoorunit) sending faultmessage to thecontroller

Compressor blocked See troubleshootingfor selected outdoorunit.

221 Low pressurealarm

Heat pump(selected outdoorunit) sending faultmessage to thecontroller

Comperssor blocked. See troubleshootingfor selected outdoorunit.

222 Motorprotectionalarm

Heat pump(selected outdoorunit) sending faultmessage to thecontroller

Compressor blocked See troubleshootingfor selected outdoorunit.

223 Communicationalarm

Heat pump(selected outdoorunit) sending faultmessage to thecontroller

Compressor blocked See troubleshootingfor the selectedoutdoor unit.Read more in: TDI20141023

224 Fan error Heat pump(selected outdoorunit) sending afault message tothe controller

Compressor blocked See troubleshootingfor the selectedoutdoor unit.

225 Flow/ return Heat pump(selected outdoorunit) sending faultmessage to thecontroller

Compressor blocked See troubleshootingfor the selectedoutdoor unit.

227 Sensor fault Heat pump(selected outdoorunit) sending faultmessage to thecontroller

Compressor blocked See troubleshootingfor the selectedoutdoor unit.

228 Defrost fault Heat pump(selected outdoor

Compressor blocked

Page 19: Alarm overzicht - nibe.eu · Automatic reset Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 32 Sensor fault BS1 Air flow is out of range of

unit) sending faultmessage to thecontroller

See troubleshootingfor the selectedoutdoor unit.

229 Shortoperationtimes forcompressor

Compressor hasstopped three timesin a row, short timeafter start

Compressor blocked - Open thermostaticvalves to ensurecirculation in theheating system- Bleed the climatesystem and heat pump- Check the filter inthe climate systemand possibleventilation- Check the start- andstop temperature forhot water charging- Check the heatingmedium pump- Check the coolingcircuit

230 Hot gas alarm Heat pump(selected outdoorunit) sending faultmessage to thecontroller

Compressor blocked See troubleshootingfor the selectedoutdoor unit.

231 Phase sequenceerror

Heat pump(selected outdoorunit) sending faultmessage to thecontroller

Compressor blocked See troubleshootingfor the selectedoutdoor unit.

232 Lowevaporation

Heat pump(selected outdoorunit) sending faultmessage to thecontroller

Compressor blocked See troubleshootingfor the selectedoutdoor unit.

236 Sensor faultAZ2-BT20

Sensor notconnected/defective(exhaust air)

Circulation pump (AZ1-GP2) in FLM blocked

Proposal: Check sensorand its connections

237 Sensor faultAZ2-BT21

Sensor notconnected/defective(exhaust)

Circulation pump (AZ1-GP2) in FLM blocked

Proposal: Check sensorand its connections

238 Sensor faultAZ2-BT26

Sensor notconnected/defective(brine collector in)

Circulation pump (AZ1-GP2) in FLM blocked

Proposal: Check sensorand its connections

239 Sensor faultAZ3-BT20

Sensor notconnected/defective(exhaust)

240 Sensor faultAZ3-BT21

Sensor notconnected/defective(exhaust)

Circulation pump (AZ1-GP2) in FLM blocked

Proposal: Check anysensor and itsconnections

241 Sensor faultAZ3-BT26

Sensor notconnected/defective(brine collector in)

Circulation pump (AZ1-GP2) in FLM blocked

Proposal: Check sensorand its connections

Page 20: Alarm overzicht - nibe.eu · Automatic reset Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 32 Sensor fault BS1 Air flow is out of range of

242 Sensor faultAZ4-BT20

Sensor notconnected/defective(exhaust)

Circulation pump (AZ1-GP2) in FLM blocked

Proposal: Check sensorand its connections

243 Sensor faultAZ4-BT21

Sensor notconnected/defective(exhaust)

Circulation pump (AZ1-GP2) in FLM blocked

Proposal: Check sensorand its connections

244 Sensor faultAZ4-BT26

Sensor notconnected/defective(brine collector in)

Circulation pump (AZ1-GP2) in FLM blocked

Proposal: Check sensorand its connections

245 Com. error FLM2

No communicationtemporarily withthe accessory FLM 2

Accessory blocked Proposal:- Check fuses, powersupply leading to theaccessory card.- Check thecommunication cablesleading to theaccessory card.- Check the setting ofthe dipswitch.

246 Com. error FLM3

No communicationtemporarily withaccessory FLM3

Accessory blocked Proposal:- Check fuses, powersupply leading to theaccessory card.- Check thecommunication cablesleading to theaccessory card.- Check the setting ofthe dipswitch.

247 Com. error FLM4

No communicationtemporarily withthe accessory FLM4

Accessory blocked Proposal:- Check fuses, powersupply leading to theaccessory card.- Check thecommunication cablesleading to theaccessory card.- Check the setting ofthe dipswitch.

248 Communicationfault No connection

between thedisplay unit and thebase card

Compressor and chargingpump stopped

- Checkt thecommunication cablebetween the displayunit and the base card

250 Com.error ACC-SMS 40

No communicationtemporarily withaccessory card

Accessory blocked See troubleshootingIHB SMS 40

251 Com. error ACCModbus 40

No communicationtemporarily withaccessory card

Accessory blocked See troubleshootingIHB SMS 40

252 Com.error slave No communicationtemporarily withslave heat pump

Compressor in slaveblocked

Proposal: Check slavesettings in menu 5.2.2,communication cablesand its connections.

Page 21: Alarm overzicht - nibe.eu · Automatic reset Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 32 Sensor fault BS1 Air flow is out of range of

Read more in: TDI20141023

253 Sensor faultQZ1-BT70

Sensor notconnected/defective(hot water flow)

Mixing valve closes Proposal: Check sensorand its connections

255 Motorprotectionalarm, brinepump

Motor protoectionon the brine pumptriggered

Current comperssorblocked. Automatic reset.

Bad circulation inbrine circuit:- check the brinepump- vent the brinesystem- check the particlefilter so its notclogged- check the brinepump cables andconnections with theheat pump

257 Com. errorACS45

No communicationtemporarily withaccessory card

Accessory blocked Proposal:- Check fuses, powersupply leading to theaccessory card.- Check thecommunication cablesleading to theaccessory card.- Check the setting ofthe dipswitch.

258 Sensor faultEQ1-BT57

Sensor notconnected/defective(Cooling brine)

Proposal: Check sensorand its connections

259 Sensor faultEQ1-BT75

Sensor notconnected/defective(cooling flow heatpump)

Proposal: Check sensorand its connections

261 This alarm wasgenerated bythe heat pump

Temperaturedeviation on theheat exchangersensor (Tho-R1/R2)five times within 60minutes orcontinuously in 60minutes

Compressor blocked Proposal:- Defect sensor- Insufficient aircirculation- The heat exchangeris clogged- Defect control cardEB101- Too large amount ofrefrigerant

262 This alarm wasgenerated bythe heat pump

Overheat powertransistor

Compressor blocked 15V power to theinverters PCB isunstable.

263 This alarm wasgenerated bythe heat pump

Incorrect voltageout from theinverter

Compressor blocked Proposal:- Disruption onincoming power- Service valve closed- Not enoughrefrigerant amount- Compressor fault- Defect circuit board

Page 22: Alarm overzicht - nibe.eu · Automatic reset Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 32 Sensor fault BS1 Air flow is out of range of

for the inverter inEB101

264 This alarm wasgenerated bythe heat pump

Communicationbetween circuitboard for theinverter and controlcard is interupted

Compressor blocked Proposal:- Disruption on theconnection betweencards- Defect circuit boardfor the inverter inEB101- Defect control cardEB101

265 This alarm wasgenerated bythe heat pump

Continuous erroron power transistorduring 15 minutes

Compressor blocked Proposal:- Defect fan motor- Defect circuit boardfor the inverter inEB101

266 This alarm wasgenerated bythe heat pump

Low refrigerantamount

Compressor blocked Proposal:- Service valve closed- Loose contact onsensor (BT15, BT3)- Defect sensors (BT15,BT3)- Too low refrigerantamount

267 This alarm wasgenerated bythe heat pump

Inverter fault, bootfailure

Compressor blocked Proposal:- Defect circuit boardfor the inverter inEB101- Defect control cardEB101- Compressor fault

268 This alarm wasgenerated bythe heat pump

Overcurrent,inverter A/F module

Compressor blocked - Sudden powerfailure

270 Compressorpreheater isactive

Preheat Compressor is inpreheat mode untilBT29> B P8

270 PreheatingPreheat of thecompressor is active

Compressor is blocked.Automatic reset.

271 Cold outdoorair EB 101

EB 101 sendingmessage to thecontroller

Compressor blocked

272 Hot outdoor air EB 101 sendingmessage to thecontroller

Compressor blocked

273 HW-start andHW-stop havebeen reset tofactory settings

Adj u stment ofhotwater-settingsbecause of shortoperation time

HW-start and HW-stopfor economy and normalhave been reset tofactory settings

274 Compressorphaseoverloaded

Load monitor hascaused thecompressor not to

Page 23: Alarm overzicht - nibe.eu · Automatic reset Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 32 Sensor fault BS1 Air flow is out of range of

operate withdesired power.

275 Compressorphaseoverloadedlongtime

Load monitor hascaused thecompressor not tooperate withdesired power.

277 This alarm wasgenerated bythe heat pump

Sensor fault MHIexchanger

Compressor blocked Proposal:- Sensor fault heatexchanger F2040,THO-R1(BT16)/THO-R2EB101- Defect control card

278 This alarm wasgenerated bythe heat pump

Sensor fault MHIambient air

Compressor blocked Proposal:- Sensor fault outdoortemperature sensorTho-A(BT28) EB101- Defect control cardEB101

279 This alarm wasgenerated bythe heat pump

Sensor fault MHIdischarge

Compressor blocked Proposal:- Sensor fault hotgasBT14 (Tho-D) EB101- Defect control cardEB101

280 This alarm wasgenerated bythe heat pump

Sensor fault MHIsuction

Compressor blocked Proposal:- Sensor fault suctiongas BT17 (Tho-S)EB101- Defect control cardEB101

281 This alarm wasgenerated bythe heat pump

Sensor fault MHI LP Compressor blocked Proposal:- Sensor fault lowpressure sensor BP2(LTP) EB101- Defect control cardEB101- Error in refrigerantcircuit EB101

282 Comm.errorACC.-EQ1

Threecommunicationerror in a row hasoccurred towardsthe accessory cardACS 310

Accessory blocked.Temporarycommunication fault.

283 Comm. ErrorAcc.-EQ1

Permanentcommunicationerror ACS310

Accessory blocked Proposal:- Checkcommunication cables- Check dipswitchsettings

290 Fan alarmThe speed signal(tachometer signal)from the fanindicates that thefan speed is zero.

- Compressor stopped.- Immersion heaterstopped.- Defrost stopped.

Check the fan, cablesand connections andthe base card.

Page 24: Alarm overzicht - nibe.eu · Automatic reset Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 32 Sensor fault BS1 Air flow is out of range of

291 Charge pumpalarm The speed signal

(tachometer signal)from the chargepump indicates thatthe charge pumpspeed is zero.

- Compressor stopped.- Immersion heaterstopped.- Defrost stopped.

Check the chargepump, cables andconnections and thebase card.

294 Not compatibleheatpump The alarm occurs if

the outdoor unittoward VVM320 isnot a F2030-7,F2030-9, F2040-8,F2040-12.Faulty settings ofthe dip switches onthe circuit board.

HW blocked. Unit cannotbe restarted after powersupply was off.

Check the connectionsof the outdoor unitand dip switchsettings.Read more in: TDI20141023 , TDI20140813

299 Wrong versionPCA Base

Firmware versionon the base card(AA2) is too low forinvertercommunication.

Compressor blocked.Reset when the correctversion is detected.

Proposal:- Change base card(AA2)

301 Com. errorslave 1 No communication

temporarily withslave heat pump(EB101)

Slave compressor blocked Proposal: Check slavesettings in menu 5.2.2,communication cablesand its connections.Read more in: TDI20141023

302 Com. errorslave 2

No communicationtemporarily withslave heat pump(EB102)

Slave compressor blocked Proposal: Check slavesettings in menu 5.2.2,communication cablesand its connections

303 Com. errorslave 3

No communicationtemporarily withslave heat pump(EB103)

Slave compressor blocked Proposal: Check slavesettings in menu 5.2.2,communication cablesand its connections

304 Com. errorslave 4

No communicationtemporarily withslave heat pump(EB104)

Slave compressor blocked Proposal: Check slavesettings in menu 5.2.2,communication cablesand its connections

305 Com. errorslave 5

No communicationtemporarily withslave heat pump(EB105)

Slave compressor blocked Proposal: Check slavesettings in menu 5.2.2,communication cablesand its connections

306 Com.error slave6

No communicationtemporarily withslave heat pump(EB106)

Slave compressor blocked Proposal: Check slavesettings in menu 5.2.2,communication cablesand its connections

307 Com. errorslave 7

No communicationtemporarily withslave heat pump(EB107)

Slave compressor blocked Proposal: Check slavesettings in menu 5.2.2,communication cablesand its connections

Page 25: Alarm overzicht - nibe.eu · Automatic reset Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 32 Sensor fault BS1 Air flow is out of range of

308 Com. errorslave 8

No communicationtemporarily withslave heat pump(EB108)

Slave compressor blocked Proposal: Check slavesettings in menu 5.2.2,communication cablesand its connections

325 Temperaturelimiter alarmfor defrostelement

Temperaturelimiter FD3 hastripped

Heatpump changes topassive defrost

- Check the filter andair flow

- The alarm can bereset in the alarmmenu but will returnwhen the defrostelement tries toconnect until thetemperature limiter isreset.

- Temperature limitershall be reset andfunction tested by aninstaller or servicetechnician

326 Fault in EB16Active defrostinghas failed threetimes in a row

Heat pump merges topassive defrost

- Check the filter andair flow- Checkt thecalibration of airspeed sensor BS1 inmenu 5.1.5.1- Checht thedefrosting elementEB16

340 Anti-freezesupply air

Supply airtemperature (BT22)is below 11° C .

HW load blocked.Returns automaticallywhen the supply airtemperature exceeds16°

- Bleed the supply airbattery.- Check the watertemperature and theflow to the heatingbattery.- If repeated alarms;verify that circulatedwater volume issufficient.

351 Uncertainsensor accuracy

Uncertain sensoraccuracy on thebrine sensors BT10and BT11. Thedifference is morethan 2K betweenthem at calibration.

GP2 switches to manualspeed if auto control isselected. Manual reset ofauto control in menu5.1.9

Proposal:- Check sensorsBT10and BT11 and their

352 Uncertainsensor accuracy

Uncertain sensoraccuracy on the HMsensors BT2 andBT3. The differenceis more than 2Kbetween them atcalibration.

GP1 switches to manualspeed if auto control isselected. Manual reset ofauto control in menu5.1.11

Proposal:- Check the sensorsBT2 and BT3 and theirconnections.

353 Uncertainsensor accuracy

Uncertain sensoraccuracy on the HM

GP1 switches to manualspeed if auto control is

Proposal:- Check the sensors

Page 26: Alarm overzicht - nibe.eu · Automatic reset Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 32 Sensor fault BS1 Air flow is out of range of

sensors BT3 andBT12. Thedifference is morethan 2K betweenthem at calibration.

selected. Manual reset ofauto control in menu5.1.11

BT3 and BT12 andtheir connections.

354 Slave EB101 Delta BT3-BT12 islarger than 2K aftercalibration

Changes from auto tomanual circulation pumpspeed. Uncertain sensoraccuracy.

355 Slave EB101 Delta BT3-BT63 islarger than 2K aftercalibration

Changes from auto tomanual circulation pumpspeed. Uncertain sensoraccuracy.

356 Failed sensorcalibration

Sensor calibrationdiffers more than2K between BT3and BT63

GP1 will go over tomanual operation

Check the flow in theheating system is notdisturbed by air orclosed ventilators.Restart the display.

372 Perm. com.error pool 2 No communication

with the accessorycard.

Accessory blocked. Proposal:- Check the powersupply leading to theaccessory card.- Check thecommunication cablesleading to theaccessory card.- Check the setting ofthe dipswitch.

403 Sensor fault onEB101

Sensor faultdetected on EB101of the COM-interface MHI-EMMY

- Compressor blocked- If GP12 or GP1 isregulated by sensorEB101-BT3, they willswich to the manually setspeed.

Proposal:- Check thetemperature sensorand its connections.See also the wiringdiagram.

404 Sensor fault onEB101

Sensor faultdetected on EB101of the COM-interface MHI-EMMY

- Compressor blocked Proposal:- Check thetemperature sensorsand its connections.See also the wiringdiagram.

412 Sensor fault onEB101-BT12

Sensor faultdetected on EB101of the COM-interface MHI-EMMY

- Compressor blocked- If GP12 or GP1 isregulated by sensorEB101-BT3, they willswich to the manually setspeed.

Proposal:- Check thetemperature sensorand its connections.See also the wiringdiagram.

415 Sensor fault onEB101-BT15

Sensor faultdetected on EB101of the COM-interface MHI-EMMY

Compressor blocked Proposal:- Check thetemperature sensorand its connections.See also the wiringdiagram.

420 Inverter alarmtype II

Compressor stopped.Automatic reset 60 sec.

Proposal:- Check the main fuse

Page 27: Alarm overzicht - nibe.eu · Automatic reset Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 32 Sensor fault BS1 Air flow is out of range of

A temporarycommunicationalarm has occured.

after the inverter fault isreset. The compressorwill make a new attemptto start according tonormal start routine.

and the group fusesand their connections- Check thecommunication cableto the inverter and itsconnections.- If the alarm occursagain; contact aservice technician.

421 Inverter alarmtype II

A temporarycommunicationalarm has occured 3times within 2hours or has beencontinuously for 1h.

Compressor blocked.Manual reset in menu.

Proposal:- Check the main fuseand the group fusesand their connections.- Check thecommunication cableto the inverter and itsconnections- Do a restart of theheat pump by turningit off through theoperating switch- If the alarm occursagain; contact aservice technician.

422 Inverter alarmtype II

A temporary alarmon the externalinput of theinverter hasoccured

Compressor stopped.Automatic reset 60 sec.after the inverter fault isreset. The compressorwill make a new attemptto start according tonormal start routine.

Proposal:- Check the main fuseand the group fusesand its connections- If the fault occursagain; contact aservice technician

423 Inverter alarmtype II

A temporary alarmon the externalinput of theinverter hasoccurred 3 timeswithin 2 hours orthe input has beencontinuouslybroken for 1 hour.

Compressor blocked.Manual reset in menu.

Proposal:- Check thecommunication cableon the external inputof the inverter- Check the main fuseand the group fuses- Restart the heatpump by turning it offthrough the operationswitch- If the fault occursagain; contact aservice technician

425 Triggeredpressure switch High pressure

switch or lowpressure switch istriggered.

Compressor blocked Bad circulation inheating system or lackofrefrigerant/problem inrefrigerant circuit.

Suggestions:

- Vent the heatpumpand heatingsystem.

- Open all thermostatson the radiators.

- Check and cleanfilters/strainers.

Page 28: Alarm overzicht - nibe.eu · Automatic reset Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 32 Sensor fault BS1 Air flow is out of range of

- Check thechargepump.

- Check thatpressureswitches arecorrect wired.

Problem in refrigerantcircuit:

- Call a certifiedrefrigerationtechnician.

426 Inverter alarmtype III

A temporarily faultin the inverter hasoccur.

Automatically reset 30minutes after theinverter fault iscorrected. Compressorstopped.

Proposal:- Check the main fuseand the group fusesand their connections.- Restart the heatpump through thepower switch to breakthe power.- If the alarm occursagain; contact aservice technician.

427 Inverter alarmtype III

A temporaryinternal fault in theinverter hasoccurred 3 timeswithin 2 hours orcontinuously in 1hour.

Compressor blocked.Manual reset in menu.

Proposal:- Check the main fuseand the group fusesand their connections.- Restart the heatpump through thepower switch to brekthe power.- If the alarm occursagain; contact aservice technician.

428 Inverter alarmtype III A temporary

internal fault in theinverter hasoccurred.

Compressor stopped.Automatic reset 60 sec.after the inverter alarmhas been corrected.

Proposal:- Check the main fuseand the group fusesand their connections.- Restart the heatpump through thepower switch to breakthe power.- If the alarm occursagain; contact aservice technician.

1 phase inverter:Check thecondensator

429 Inverter alarmtype II A temporary

internal fault in theinverter hasoccurred 3 timeswithin 2 hours orcontinuously in 1hour.

Compressor blocked.Reset manually in menu.

Proposal:- Check the main fuseand the group fusesand their connections.- Restart the heatpump through thepower switch to breakthe power.- If the alarm occurs

Page 29: Alarm overzicht - nibe.eu · Automatic reset Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 32 Sensor fault BS1 Air flow is out of range of

again; contact aservice technician.

1 phase inverter:Check thecondensator

430 Inverter alarmtype I

Phase voltage tothe inverter hastemporarily beentoo high.

Automatic reset 60 sec.after the fault iscorrected. Compressorstopped.

Proposal:- Check the main fuseand the group fusesand their connections.- If the alarm occursagain; contact aservice technician.

431 Inverter alarmtype I

Phase voltage tothe inverter hastemporarily beentoo high more than1 hour.

Reset manually in menu.Compressor blocked.

Proposal:- Check the main fuseand the group fusesand their connections.- If the alarm occursagain; contact aservice technician.

432 Inverter alarmtype I

Phase voltage tothe inverter hastemporarily beentoo low.

Automatic reset 60 sec.after the fault iscorrected.

Proposal:- Check the main fuseand the group fusesand their connections.- If the alarm occursagain; contact aservice technician.

433 Inverter alarmtype I

Phase voltage tothe inverter hasbeen too low,below 180V inmore than 1 hour.

Compressor blocked.Reset manually in menu.

Proposal:- Check the main fuseand the group fusesand their connections.- If the alarm occursagain; contact aservice technician.

434 Inverter alarmtype I

A compressor phasehas temporarilybeen missing.

Compressor stopped.Automatic reset 60sec.

Proposal:- Check the main fuseand the group fusesand their connections.- If the alarm occursagain; contact aservice technician.

435 Inverter alarmtype I

A compressor phasecontinuouslymissing to theinverter for anhour.

Compressor blocked.Reset manually in menu.

Proposal:- Check the main fuseand the group fusesand their connections.- If the alarm occursagain; contact aservice technician.

436 Inverter alarmtype II

A temporaryinternal fault in theinverter hasoccurred.

Compressor stopped.Automatic reset 60 sec.after the inverter fault.

Proposal:- Check the main fuseand the group fusesand their connections.- Restart the heatpump through thepower switch to breakthe power.- If the alarm occurs

Page 30: Alarm overzicht - nibe.eu · Automatic reset Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 32 Sensor fault BS1 Air flow is out of range of

again; contact aservice technician.

437 Inverter alarmtype II

A temporaryinverter fault in theinverter hasoccurred 3 timeswithin 2 hours orcontinuously in 1hour.

Compressor blocked.Manual reset in menu.

Proposal:- Check the main fuseand the group fusesand their connections.- Restart the heatpump through thepower switch to breakthe power.- If the alarm occursagain; contact aservice technician.

438 Inverter alarmtype II The inverter has

temporary reachthe maximumoperatingtemperaturebecause of poorcooling

Compressor stopped.Automatic reset 60 sec.after the inverter fault iscorrected.

Poor circulation in HMcircuit. Proposal:- Bleed the heat pumpand the climatesystem.- Check the particlefilter, so it is notclogged.- Openradiators/under floorheating thermostats.

439 Inverter alarmtype II The inverter has

temporary reachedmaximumoperatingtemperaturebecause of poorcooling 3 timeswithin 2 hours orbeen missingcontinuously in 1hour.

Compressor blocked.Reset manually in menu.

Poor circulation in HMcircuit. Proposal:- Bleed the heat pumpand the climatesystem.- Check the particlefilter, so it is notclogged.- Openradiators/under floorheating thermostats.- If the alarm occursagain; contact aservice technician.

440 Inverter alarmtype II

Max "power in" hastemporary been toohigh.

Compressor stopped.Automatic reset 60 sec.after the inverter fault iscorrected.

Proposal:- Check the main fuseand the group fusesand their connections.- If the alarm occursagain; contact aservice technician.

441 Inverter alarmtype II

Max "power in" hastemporary been toohigh 3 times within2 hours or beenmissingcontinuously for anhour.

Compressor blocked.Reset manually in menu.

Proposal:- Check the main fuseand the group fusesand their connections.- If the alarm occursagain; contact aservice technician.

442 Inverter alarmtype II Inverter has

temporary reachedmax operating

Compressor stopped.Automatic reset 60 sec.

Poor circulation in HMcircuit.Proposal:

Page 31: Alarm overzicht - nibe.eu · Automatic reset Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 32 Sensor fault BS1 Air flow is out of range of

temperaturebecause of poorcooling.

after the inverter fault iscorrected.

- Bleed the heat pumpand the climatesystem.- Check the particlefilter, so it is notclogged.- Openradiators/under floorheating thermostats.

443 Inverter alarmtype II Inverter has

temporary reachedmax operatingtemperaturebecause of poorcooling 3 timeswithin 2 hours orbeen missingcontinuously in anhour.

Compressor blocked.Manual reset in menu.

Poor circulation in HMcircuit. Proposal:- Bleed the heat pumpand the climatesystem.- Check the particlefilter, so it is notclogged.- Openradiators/under floorheating thermostats.- If the alarm occursagain; contact aservice technician.

444 Inverter alarmtype II

A temporaryinternal fault hasoccurred in theinverter.

Compressor stopped.Automatic reset 60 sec.after the inverter fault iscorrected.

Proposal:- Check the main fuseand the group fusesand their connections.- Restart the heatpump through thepower switch to breakthe power.- If the alarm occursagain; contact aservice technician.

445 Inverter alarmtype II

A temporaryinverter fault hasoccurred 3 timeswithin 2 hours orcontinuously in 1hour.

Compressor blocked.Manual reset in menu.

Proposal:- Check the main fuseand the group fusesand their connections.- Restart the heatpump through thepower switch to breakthe power.- If the alarm occursagain; contact aservice technician.

446 Inverter alarmtype II

A compressor phasehas temporarilybeen missing.

Compressor stopped.Automatic reset 60 sec.after the phase has beenreset.

- Check the main fuseand the group fusesand their connections.- If the fault occursagain; contact aservice technician.

447 Inverter alarmtype II

A phase hastemporarily beenmissing 3 timeswithin 2 hours orbeen missing

Compressor blocked.Manual reset in menu.

- Check the main fuseand the group fusesand their connections.- If the fault occursagain; contact aservice technician.

Page 32: Alarm overzicht - nibe.eu · Automatic reset Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 32 Sensor fault BS1 Air flow is out of range of

continuously for 1hour.

448 Inverter alarmtype II

The compressor hastemporarily beenoperating withlower speed thanallowed minimumspeed.

Compressor stopped.Automatic reset 60 sec.after the inverter fault iscorrected.

- Check the main fuseand the group fusesand their connections.- If the fault occursagain; contact aservice technician.

449 Inverter alarmtype II

The compressor hastemporarily beenoperating withlower speed thanallowed minimumspeed, 3 timeswithin 2 hours orbeen missingcontinuously for 1hour.

Compressor blocked.Manual reset is possiblewhen the alarm hasdisappeared.

- Check the main fuseand the group fusesand their connections.- If the fault occursagain; contact aservice technician.

450 Inverter alarmtype III

Not used function(false alarm)

- Check the main fuseand the group fusesand their connections.- Restart the heatpump through thepower switch to breakthe power.- If the alarm occursagain; contact aservice technician.

451 Inverter alarmtype III

Not used function(false alarm)

- Check the main fuseand the group fusesand their connections.- Restart the heatpump through thepower switch to breakthe power.- If the alarm occursagain; contact aservice technician.

452 Inverter alarmtype II

Power out frominverter tocompressor hastemporarily beentoo high.

Compressor stopped.Automatic reset 60 sec.after the inverter fault iscorrected.

- Check the main fuseand the group fusesand their connections.- If the fault occursagain; contact aservice technician.

453 Inverter alarmtype II

Power out frominverter tocompressor hastemporarily beentoo high 3 timeswithin 2 hours orbeen missingcontinuously in 1hour.

Compressor blocked.Manual reset in menu.

- Check the main fuseand the group fusesand their connections.- If the fault occursagain; contact aservice technician.

454 Inverter alarmtype II

Temporary too highoutput from theinverter hasoccurred.

Compressor stopped.Automatic reset 60 sec.after the inverter hasoccurred.

- Check the main fuseand the group fusesand their connections.- If the fault occurs

Page 33: Alarm overzicht - nibe.eu · Automatic reset Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 32 Sensor fault BS1 Air flow is out of range of

again; contact aservice technician.

455 Inverter alarmtype II

Temporary too highoutput from theinverter hasoccurred 3 timeswithin 2 hours orbeen missingcontinuously in 1hour.

Compressor blocked.Manual reset in menu.

- Check the main fuseand the group fusesand their connections.- If the fault occursagain; contact aservice technician.

460 Inverter alarmtype II

(Only 1-phase) Toohigh "power in" toinverter hastemporarilyoccurred. Candepend on lowincomming power(> 1 98 VAC)

Compressor stopped.Automatic reset 60 sec.after the inverter fault iscorrected.

- Check the main fuseand the group fusesand their connections.- If the fault occursagain; contact aservice technician.

461 Inverter alarmtype II

(Only 1-phase) Toohigh "power in" toinverter hastemporarilyoccurred 3 timeswithin 2 hours orbeen missingcontinuously in 1hour. Can dependon low incommingpower (> 1 98

Compressor blocked.Manual reset in menu.

- Check the main fuseand the group fusesand their connections.- If the fault occursagain; contact aservice technician.

468 Inverter alarmtype III

Not used function(false alarm)

Proposal:- Check the main fuseand the group fusesand their connections.- Restart the heatpump through thepower switch to breakthe power.- If the alarm occursagain; contact aservice technician.

469 Inverter alarmtype III

Not used function(false alarm)

Proposal:- Check the main fuseand the group fusesand their connections.- Restart the heatpump through thepower switch to breakthe power.- If the alarm occursagain; contact aservice technician.

470 Inverter alarmtype III

Not used function(false alarm)

Proposal:- Check the main fuseand the group fusesand their connections.- Restart the heatpump through thepower switch to break

Page 34: Alarm overzicht - nibe.eu · Automatic reset Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 32 Sensor fault BS1 Air flow is out of range of

the power.- If the alarm occursagain; contact aservice technician.

471 Inverter alarmtype III

Not used function(false alarm)

Proposal:- Check the main fuseand the group fusesand their connections.- Restart the heatpump through thepower switch to breakthe power.- If the alarm occursagain; contact aservice technician.

472 Inverter alarmtype III

Not used function(false alarm)

Proposal:- Check the main fuseand the group fusesand their connections.- Restart the heatpump through thepower switch to breakthe power.- If the alarm occursagain; contact aservice technician.

473 Inverter alarmtype III

Not used function(false alarm)

Proposal:- Check the main fuseand the group fusesand their connections.- Restart the heatpump through thepower switch to breakthe power.- If the alarm occursagain; contact aservice technician.

474 Inverter alarmtype III

Not used function(false alarm)

Proposal:- Check the main fuseand the group fusesand their connections.- Restart the heatpump through thepower switch to breakthe power.- If the alarm occursagain; contact aservice technician.

475 Inverter alarmtype III

Not used function(false alarm)

Proposal:- Check the main fuseand the group fusesand their connections.- Restart the heatpump through thepower switch to breakthe power.- If the alarm occursagain; contact aservice technician.

Page 35: Alarm overzicht - nibe.eu · Automatic reset Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 32 Sensor fault BS1 Air flow is out of range of

476 Inverter alarmtype III

Not used function(false alarm)

Proposal:- Check the main fuseand the group fusesand their connections.- Restart the heatpump through thepower switch to breakthe power.- If the alarm occursagain; contact aservice technician.

477 Inverter alarmtype III

Not used function(false alarm)

Proposal:- Check the main fuseand the group fusesand their connections.- Restart the heatpump through thepower switch to breakthe power.- If the alarm occursagain; contact aservice technician.

478 Inverter alarmtype III

Not used function(false alarm)

Proposal:- Check the main fuseand the group fusesand their connections.- Restart the heatpump through thepower switch to breakthe power.- If the alarm occursagain; contact aservice technician.

479 Inverter alarmtype III

Not used function(false alarm)

Proposal:- Check the main fuseand the group fusesand their connections.- Restart the heatpump through thepower switch to breakthe power.- If the alarm occursagain; contact aservice technician.

480 Not used function(false alarm)

Proposal:- Check the main fuseand the group fusesand their connections.- Restart the heatpump through thepower switch to breakthe power.- If the alarm occursagain; contact aservice technician.

481 Inverter alarmtype III

Not used function(false alarm)

Proposal:- Check the main fuseand the group fusesand their connections.

Page 36: Alarm overzicht - nibe.eu · Automatic reset Proposal: Check the sensor and its connections. See also the electrical wiring diagram. 32 Sensor fault BS1 Air flow is out of range of

- Restart the heatpump through thepower switch to breakthe power.- If the alarm occursagain; contact aservice technician.

995 External alarm An alarm accordingto chosen on theAUX - entrance.

Only information.A u tomatic resetw h enclosing the entrance is

- Check possibleexternal connectionfunction.

996 Blocked External additionheat blockedthrough AUX -

Automatic reset whenclosing over the entranceis broken. Additionalheat blocked.

997 Compressorblocked External

compressor blockedthrough AUX -

Automatic reset whenclosing over the entranceis broken. Compressorblocked.

998