CODES AND STANDARDS
CONSTRUCTION TYPE ‐
USE GROUP CLASSIFICATION ‐
CODE DATA
AREA CALCULATIONS GROSS SQUARE FEET
FIREPROOFING SCHEDULEHOURSFIRE RESISTANCE RATINGS U.L. # OR OTHER
PINNACLE ARCHITECTSPROJECT ARCHITECTS210 N. SAINT CLAIR STREET DAYTON, OHIO 45402
HEAPY ENGINEERINGMECHANICAL ELECTIRICAL CONSULTANTS1400 WEST DOROTHY LANE DAYTON, OHIO 45409
EQUIP equipment
perimeterPERIM
janitorJAN
SVGC suspended vinyl gypsum ceiling
basementBSMTgalvanizedGALV
CPT carpet
glassGL
gypsum boardGYP.BD.
CY cubic yardCTC center to center
general contractor
gypsum board ceilinggypsum board soffit
gypsum board bulkhead
GCGBSGBCGBBcrash rail
CRBCR
ceramic tilecourse(s,ing)
CTCRS
coved resilient base
futureFUT
footingFTG
FA fasten, fastener
existingEXIST
CONST construction
CLS closure
CL centerline of
CH channel
gage, gaugeGA
caulk(ing)CLK
CLO closet
BUL bulletinBUR built-up roof
framefireproof(ing)
FRFP
ceramic mosaic tile
clear
CMT
CLR
furred(ing)
feet or foot
FUR
FT
continuousconcrete
CONTCONCCOL
contractorCORRCONTR
corridor
column
FRT fire retardant
concrete masonry unitCMU
each wayEW
exterior
EXP
EXT
exhaustEXHexpansion
face brickFBFDFE
fire extinguisher cabinetfinish floor elevationFFE
FFLFGL
FEC
cabinetcarpet basecubicle curtaincubicle curtain trackcubic feet
foundation
FHCFINFLRFND
face of concreteface of masonry
FOCFOM
contr. furnished, contr. installedcorner guard
chamfercircumferencecontrol joint
ceiling
contract limit line
floor drainfire extinguisher
finish floor linefiberglassfire hose cabinetfinish(ed)floor(ing)
CABCBCCCCTCFCFCICG
CHAMCIRCCJ
CLG
CLL
rough openingRO
mouldingMLD
marker boardMRKBD
movableMOV
ROWRUB
right of wayrubber
masonry openingMO
mount(ed),(ing)metal
MP
MTMTL
multi-paint
windowwood
weight
waterproof(ing)waterstopwainscot
welded wire meshwall to wall
WINWD
WTWSCT
WPWS
WWMWTW
quantityQTY
PTN partition
mediumMED
LTWT lightweight
LTG lightinglightlow point
LTLP
LAM laminated
KO knock out
polyvinyl chloridePVC
PTD paper towel dispenser
LVR louver
PLPG
plastic laminateplate glass
plaster
PNLPLWDPLSTRPLC
pounds per square footPSFPRPP
panel
pairpush plate
plywood
plastic laminate clad
QTQTR RD
quarry tilequarter round
PSI pounds per square inch
jointJT
radius
reference
RADRDREFREINF
requiredresilient
revision
REQ'DRESILRETREV
roof drain
reinforcing
return
reflectedRFLRM
riserR
room
kitchen
kick plate
length, long
lavatory
KIT
KPL
L
LAVLBL
linear footlong leg horizontallong leg vertical
level
masonry
lintel
LFLLHLLV
LVL
MAS
LTL
label
mechanical
manufacturer
maximum
miscellaneousminimum
MAXMECH
MFR
MISCMIN
MAT material
TMPRD tempered
TEL telephonetop of curb
temporarytongue and groovethick(ness)
top of pavement
top of slab
tread
toilet paper dispenser
TC
TEMPT>HK
TP
TSTTSL
T
TPD
typicaltop of wall
verticalvinyl composition tilevapor barrier
west, width, wide
vinyl wall coveringveneer
TWTYP
VERTVCTVB
W
VWCVNR
top of steel
water closetwood base
WCWB
EIFS ext. insulation & finish sys.
BC bottom of curb
ASPH asphalt
depth, deepD
detaildemolitiondouble
DETDEMODBL
dimensiondiagonaldiameter
DIMDIAGDIA
drinking fountainDF
anchor bolt
door openingDODN
drawer
downspoutdoor
DWRDWGDSDR
acousticaladdendumadjustableabove finish flooralternatealuminumanodized
above
drawing
down
expansion bolteacheast
EBEAE
electric(al)elevationexpansion joint
each face
ELECELEJ
EF
access panelarchitectural
boardbumper guardbituminous
equalelevator
EQELEV
blockingbench mark
bearing platebearingbrick
bottom
building
both sides
ABABVACOUSADDADJAFFALTALUMANODAPARCH
BDBGBITUMBLDGBLKGBMBOTBPLBRGBRKBS
pre-formed composite metal panel
owner furnished, owner installedowner furnished, contr. installed
NC no ceiling
PCMPPCC pre-cast concrete
MTLFUR metal furringMUL mullion
HT heighthigh pointHP
GMU glazed masonry units
ounceOZ
NOMNO
nominalnumber
on centerOCOA
outside diameter
OHOFOIOFCIOD
overhead
overall
openingOPG
P
OPP
particle boardPBDpaint
opposite
gravelgrab bargrade
hardboard
height, high
grout
GRVLGRBGR
HDBD
H
GT
hardwood
hollow core
heating, ventilating, air-conditioninghorizontal
hollow metalHDWDHDW
HC
HVACHORZ
HM
interiorinsulationinclude(d),(ing)
invertINTINSULINCL
INV
inside diameterID
hardware
not to scaleNTS
millwork
north
not in contract
MWK
N
NIC
sanitary napkin dispenserSND
STRUC structural
STD standardSTLSTOR storage
steel
SSTL stainless steelSS solid surfacingSQ square
SGC suspended gypsum ceiling
suspendedsheet vinyl
SUSPSV
southsuspended acoustical ceilingsanitary
SSACSAN
soap dispenserSCHSDSEC
solid coreSCschedule
section
sheetsimilar
space
SHTSIM
SP
specialSPECSPLSPM
square foot
specification
single-ply membrane
SF
PROJECT TITLE:
ABBREVIATIONS:
SYMBOLS LEGEND:
PROJECT TEAM:
DRAWING INDEX:
VICINITY MAP:
AIR HANDLER UNIT #8405 W. GRAND AVE. DAYTON, OHIO 45405
AUGUST 11, 2018
unit dimensionunderwriters laboratoriesunfinishedunless noted otherwise
UDULUNFUNO
N
verify in fieldVIF
AREA OF WORK
GRAVEL
NOTE REFERENCE
LINTEL TYPE
METAL
BRICK
CONCRETE
CEILING HEIGHT
CONCRETE MASONRY UNIT
REFERENCE DRAWING NUMBERDETAIL NUMBER
COLUMN REFERENCE
TEST BORING WALL TYPE
DOOR NUMBER
WINDOW NUMBER
L‐1
PLASTIC LAMINATE
SHIM
WOOD, FRAMING
WOOD, FINISH
PLYWOOD
LOUVER TYPE
ELEVATION LETTER
REFERENCE DRAWING NUMBER
REFERENCE DRAWING NUMBERSECTION NUMBER
EXISTING POINT ELEVATION
NEW CONTOUR
NEW POINT ELEVATION
EXISTING CONTOUR
INSULATION, BATT
INSULATION, RIGID
GRID LINES
CARD READER
ELEVATION
MTL STUD
EARTH
GYPSUM BOARD/PLASTER
SET NO. SEALfield verifyFV
GLBLK glass block
gypsum wall boardGWB
gypsum boardGB
ROOM NUMBERROOM NAMEWAITING
107
3 REVISION NUMBER& TYPE
SHELL & MEYER ASSOCIATES, INC.STRUCTURAL ENGINEERING CONSULTANTS2202 S. PATTERSON BLVD. DAYTON, OHIO 45409
O
MICHAEL
7744TAYLOR
T.
OTSTA
OE FIH
EST
E
I
GR
T
H IRDRE A C
C
TE
S0‐1S1‐0S1‐1
STRUCTURAL NOTESPARTIAL THIRD FLOOR PLANPARTIAL ROOF FRAMING PLAN
STRUCTURAL
A3‐1
A3‐2
PARTIAL THIRD FLOOR DEMOLITION & PARTIAL FOURTHFLOOR NEW WORK PLANTHIRD FLOOR CEILING DEMO & NEW WORK PLAN ‐SECTIONS / DETAILS
ARCHITECTURAL
PLUMBING LEGEND AND INDEXPARTIAL PLANS ‐ PLUMBING NEW WORK
D.P001D.P201
PLUMBING
D.H001D.H201D.H501
MECHANICAL LEGEND, NOTES & INDEXPARTIAL THIRD FLOOR AND ROOF PLANAHU SCHEDULES AND DETAILS
MECHANICAL
ELECTRICAL LEGEND, SCHEDULES & INDEXELECTRICAL SINGLE LINE DIAGRAMPARTIAL THIRD FLOOR ‐ ELECTRICAL PLANSPARTIAL FOURTH FLOOR ‐ ELECTRICAL PLANS
D.E001D.E002D.E103D.E104
ELECTRICAL
COVER
�������������������� ����������������������
����������������� �������������
���������������� ��� ������ ������������������������� ����!� ��"��������#�������������� ����$� ��%��������������������������� ���&� ��%���������������� ����'� ��%�
�������� ��������������(������������ ����������)��������*� � ��� �����������#������ � ������������������������������� �������+,- �%�.���������������� �//0-�1������������������������������������������������
��������*���������*������������������ ����������������������*��%�%��������������-��
�����2��)������ ��������������������� $� ��%3��������������������������� &� ��%�33
�� ��%���������� � ������������������������� 4&� ��%�/3
4�� ��%��3����������������*� ���������-�����-������*������������������������������ 5�$!$6$78$ ������-����9:;$���%�-�<
�������*����������������*��������������������������� (%��
���������������������� �&� ��%�.�3����*��������������� ��2�������������������������������
��������������������%� ��������������������������"�������������������������������
�����������������2���������������=���%�������������������������������������������������������1����������������2�������1��������%������������������������*�����1������������������1�������������������"%�%3%���������2�������������������������������������������������������>��������*���������������������������������������������������>��������������������������*�����"��� �-/-�������������������������%
�%� ��������������������*������#�������������������������*������������������*���������������������������������������%
(%� ����������������������������������=�������������������������������������������������������%��������������������������*�������2�������������������������������������������������������������������������������������������������������������������������)%
"%� ������������������������������������������������������%�����������������������������������������*���*����������������2����������������������������������������������������������������������������)����������������������������������%���������������������������*�����2���*�����������������������������������������������*������������%������������������*������������������%
3%� �����+���*�������������%�������������������������������������������2���������2�������������������������������������)%
����������������
����������������������
���������������� ��������� ������������������������������������������������ ��3�������������������������5�����������������< �%� ��������������/��%"��������������������������������������%� ������������������������������������)���������5�<(%� �����3�������������������������������+�3����"%� ������������������- USED ���������������������������/��%?3%� �����������- ���������/��%?������/��%�(
(�������� �3���"�������� �3���
�������������������%� �������������������������������������0�������������������
�������������%�%� ������������������������������������-��������������������
�����������������������������*��������������*��������%(%� CONCRETE SUBSTRATE - �%�%�%����(,"1����%�����0��0�����������������
��->������������������-�*������������*����������-(�.�%������������������0-/�(,"1%�
"%� REINFORCING INTO CONCRETE - �%�%�%����������-���3����(����#*�������-(.�"%�������������������������������""@��������������%�%�%
3%� GROUTED CONCRETE MASONRY ������������������������%�.1�������������������������- �%�%�%����(,"1����%�����)�)������(�����������-����-�(.3%������������������0-"�(,"1%
/%� GROUTED CONCRETE MASONRY �����������������*����������������������- �%�%�%����(,"1����%�����)�)�����>����������������-����-(�3/%������������������0-/��,"1%
�%� UNGROUTED CONCRETE MASONRY - ���������������*-����������*������-����-�/.�%���%�%�%����������������������,�1����%�����0��-�0����������*��������������@��0-"1����������������%�������������������*�>�����������������������%
�����3�- �������������������
�%� ��������������������������������������������������������������������������������������������������������������,���(/�-����������(�(-������������������"����������������1����������������������1%
�%� �����������������������������������������������������*���������������������������%������������������������������������2����%
(%� ����������������������������������������������������������������������������������� ��������������
������������������������������??���3��)� ��������������������������������������3����6%���3��)� ������������������������3����6%����"/�)� �����������������������������������������,������(/��(/�)�
"%� �������������������������������������������������������33"��(/�)��A����������)��������������.������%
3%� ��������������������������������������(,"1����%������������������-�.3����������,���������������-##����������%����������*����������������������*�����������������������FACTORED �����������������������������������������������������������������LOAD AND RESISTANCE FACTOR DESIGN���%�%�%����3,�/1����)���������������������������������������������1�������������������������1����%�%�%��������������������%
/%� �������������������������������������,"���������������������2�������%��
�%� �������������������������������������������������*��#������������������������������������)�����������������������������������-������������>��������������������������3(%
.%� ������������������������������������>�����������������������������������������������������������������������/@"@3,�/1��������*������%�%�%�������������������*�����>������������������������������������%
?%� ��������� ���������,�����������������������3��B���������������%�����������=������������������������������������������������%���������������������������������������%�����������������*�������������������������������������������%����������,���������������������������B��������������������������������=������������������������������������������������%���������������������������������������%�����������������*�������������������������������������������%
�����3�- �������������������������������
�%� ���������������������������������������������������������������������������������������1��������������������������������������������-����������������������������1�������-���%
�%� ������������������������������������������������������������������������(�������������*�������������������� �3"�CD;&���/��9%���������������������E �3��)���������3�����A�"(�CD;&���.��9%���������������������E �((�)���������((��
(%� �������������������������>�����������������������������2����������������/3(%�����?������2�������������������������)����������/�����������������������������������������%
"%� ��������������������������3%� �����������������������������#������������������#�����"0-�1�����
�������%���2�����������=�������������%����������������������������������������������������*�������%��������������������������������*����������������������������������������������������������������0���2�������%
+ASSOCIATES INCSHELL MEYER2202 S Patterson blvdDayton, OH 45409.1930ph.937.298.4631 [email protected]
STRUCTURAL ENGINEERS
�$9FE��6GH$8'��G%����.-�3�((
Kettering Health Network
Grandview Medical Center
KEY PLAN:
REVISIONS:
NOTES:
Date
Checked By
Drawn By
Job No. Sheet No.
No. Date Description
III%FD7798;$968JD'$8'&%8G����� �?(�%����%�����������������# �?(�%����%�".?(
�����%��%���������������*���������
AREA�OF�WORK
�-�
��������������
�-��-�.
���
=��
Air�Handler�Unit�#8
405 W. GRAND AVE. DAYTON, OHIO 45405
�"?-/�%.
���������� ��������������������������������
�������
�������
������
������
�����
�����
�����
�����
������
������
������
������
����� �����
����
�������
����
�������
�������
�������
�������
�������
�������
������
�������
������
������
�������
�������
�������
�������
��������
��������
��������
����� �
��������� ������� �����������
�����
���
�
����������
����������
���������
�����
����
�
�������
�������
�������
�������
�������
�������
�������
�������
�������
�������
�������
�������
�������
�������
������
��������
��������
��������
��������
��������
��������
��������
��������
��������
��������
��������
���������������
�������
�������
�������
�������
�������
�������
�������
��������
��������
������
�������
�������
�����
�� ��
�
����� ��������
�� ��
�
����� ���
����� ���
�����
����
� �����
���
����� �
�����
���
�����
���
�����
���
�����
���
�����
���
�����
���
��������
�����
���
�!��"�����#��"�$��%$
$%���"&
�
�
$%��'���#"����!���$(��!)�"�!����%�"%���%$���$(!!�("�%���*��!�����!%��
���+�*��!�����(��("�%"����*�#���!����&
��,���
�*��
,����*
�-�
�,����
��+*�
,����*
�,����
*�,�
���*
�,����
*�,�
���*
�,����
*�,�
���*
,������+*
�,����* ��,����* ��,����* ��,�������+�* �,������+�* ��,����* �,����* ��,����* ��,����* �,����*
��,���
�*��
,����*
�,����
**
��,���
���+�*
���+�*
�,����
��+*
,����
���+*
��,����* ��,����* ��,�������+�* �,������+�* �,������+�* ��,������+�* ��,������+*
�,����
**
�* ��,�������+�*
�,����
*��
,����*
�,����
�*
��,����* ��,����* ��,�����+*
�,������+�*
��,���
���+�*
,����
��+�*
�,����
��+*
�,����
*
��������+����� %$��')(��!� $�#("���$%."��"��� !%%$�%)"���
+ASSOCIATES INCSHELL MEYER2202 S Patterson blvdDayton, OH 45409.1930ph.937.298.4631 [email protected]
STRUCTURAL ENGINEERS
�/�01�)234/56�"3�����������
Kettering Health Network
Grandview Medical Center
KEY PLAN:
REVISIONS:
NOTES:
Date
Checked By
Drawn By
Job No. Sheet No.
No. Date Description
777�0899�5:/�25;86/56<�53)�%"�=������������������������ ��=������������
����"�������!�($���$�������'�%">�%�(%�
AREA�OF�WORK
��+��*�?��,��*
����
)�$�(�!���($�� !%%$ $�#("��)!�"�
������
���
� $
Air�Handler�Unit�#8
405 W. GRAND AVE. DAYTON, OHIO 45405
�������
��+��*�?��,��*�"�� !%%$��"����$�� !%%$�
�������
�������
������
������
�����
�����
�����
�����
������
������
������
������
�����
�����
�������
�������
�������
�������
�������
������
�������
������
������
�������
�������
�������
��������
��������
��������
��������
��������
����� �
�������
�������
���������
���������
�����������
�����������
���������
�����
���
�����
���
�����
���
�����
���
����� �
��������
�����
���
�����
���
�����
���
���
�!��"�#��!�$"�����
%�������&'���!"" ����(�� ��!�!�)" �$�" �����������*'�� �+
+��� �!�$"���&"+�"!���!&$$�� �!& ,�"+$,����+"!����'"*����"%�#�!'-������'����'���"%�#�!'-�+��������'����'��#"��")�#�!#�&+���*��./��!�,�"!��!"*+�!���!
!���"�#��!�$"�����
+���!"" ��!�&+�$"���&"+�"!���!&$$�� �!& ,�"+$,����+"!���'"*���#"��")�#�!'-������'����'��#"��")�#�!#�&+���*��./��!�,�"!��!"*+��!���!
� �
+����"!���!&$$����"$�''���'���/'���
+�����+�!�&$
�'���
�'���
�'���
�'���
�
#� #
�
����������
�����
�����
������#��
������0�
������0�
������0�
������0�
������0�
������0�
������0�
������0�
������0�
����0�
����0�
���������
����0�
������0�
������0�
������0�
������0�
������0�
������
������
������
������#����
������0�
������0�
������0�������0�
������0�
������0�
������0�
������0�
������0�
������0�
����������
�����
����
�����
�����
����#��
������0�
������0�
������0�
������0�
������0�
������0�
������0�
�����
�����
� �
��������/��������
������������������������������������������
�������/� ������� �������/��
�������/� �������� �������/��
�������/�
��������
��������/����������
���/���'$�#���&'�&+�"+������)���$����(
������� �������� �������� ����������/�� ��������/�� �������� ������� �������� �������� �������
��������
��������
�������
����������/��
���/��
��������/�
��������/�
�������� �������� ����������/�� ��������/�� ��������/�� ���������/�� ���������/�
�������
�
�� ����������/��
�������
��������
��������
�������� �������� ��������/�
��������/��
���������/��
�������/��
��������/�
�������
$�����/�
$�����/�
'���'���/'���
�'���
�'���
'���
'����!
��
+���!"" ��!�&+�$"���&"+�"!���!&$$��'���'���/'���
'����!
��
������0�������0�
������
������0�
������0�
��������/�
��������
��/��
�������
$�����/�
$�����/�
��&'���������$�#�!�� $""!
���������
��123�� 43456��57 8995
���������
�*��0"&'�
+����*���%�+��!��&"+
+���$�����/��
+���$�����/�� �!�&��$
+�������$���/�����/���/��� !")�+��!�'��#"��")�%�+�$�%"&+���"�+��� �!�&��$��+�$�'
�� ��
+�������$���/�����/���/��� !")�+��!�'��#"��")�%�+�$�%"&+���"�+��� �!�&��$��+�$�'
'�&)��'�+�����
�/ ���/�
�/ ���/��,%�
��&'���������$�#�!�� $""!
���������
+����*���%�+��!��&"+
������0"&'�
+���������
�''�����/�������$"+�
%$��/����������./�����/����&��#"$�'
+���$�����/��
�,%�
'�&)��*��0"&'���'�+�����
�!"*���'�+�����
�/ ���/��,%�
�/ ���/��,%�
�� ��
+"��:���*���+��!���$���$$���&'�&+��0"&'��#!&��&+��
�
�
$����!�&+�&����'�!& �&+��%����!+
&+�&����'��!& �&+��!��
'���%$�+� "!$"���&"+
��%�'� �
���%�'� �
����� &+�&����'��!& �&+��!��
�!& ����'+"��$"��&+���"+�&�&"+'���!"" � !�)&+��%$�+� "!$"���&"+'��+��$"��&+�'
#
��%�'� �
���%�'� �
������
�
��%�'� �
��%�'� �
�����
��&'���������$�#�!�� $""!
���������
�������
��������
��������/��
��������/��
�������
���/�
��/� ���/�
%$��/������������./�����/����&���'��&+$�''�'���$��&$�&�(�&(�#"$���;���%�+'&"+��+��"!'����/����)#��&+�"������"+��'$�#�
%&%�����/���'�����������9�<��)������$ �
�/��,%�
%&%�����/���'���
�������
�/��
���/�
���/����/��
+"��*'���,%���������#��)�'%$&��
%$��/���������������+��!���
%$��/���������������+��!���
%$��/�������������./�����/����&���#"$�'
���/��
����
�����/��
��
�/�+�'�/ �'�
�/���'&��'
������
)�)#�! '&;�
%!" &��� �!�&��$�$�����/�����$���"�0"&'��%�!�����&$�0�
$��
$��$��$��
$��
$��
$��
���
#�#
%$�+����
%$�+�#�#
�+�$�� !�)��""!���./�)����
%$�+� &��+���'�
'���$����(
$�� $�����/��
$�� $�����/��
��������"%%����+�
�����#�#
��������
'���$����(�'*%%"!�����"%�+&+�' $""!����(��&����"+�!����'$�# '��$�:�+�''���
������+�$�+"��!�=����& $�''����+���
+"��':�����$$���$�'��/��� &$$������%"*!��"+�!����'$�#���!"*��� "!�����"%+�'��$�''����+��������%!" &�����>���%"*!�'�"%� "!�"%+�'�������!����!����+�����������(��"�#�� �'��+����"� !�)�����&+�!��'���"$�#��(��&)��& � &!�%!"" &+������&'�!�=���
'���%$�+
�/��"$�#��(����)���
)������"+�!�"%+���#,
$�''����+���
������+�$�+"��!�=����&
$"�����$���+��!�0"&'��%�+�$�%"&+�'��+����$���"�+��� �!�&��$�$�����/�
��&'���������$�#�!�� $""!
���������
�������
��������
%$��/������������./�����/����&���'��&+$�''�'���$���!*�#"$�'
%&%�����/���'�����������9�<��)������$ �
�/��,%�
%&%�����/���'���
+���������
��������/��
��������/��
�������
���/��
�������
��/�
�!"*���'�+�����
��&'���������$�#�!�� $""!
���������
�/����'���!�%$����./�����/����&���#"$�'
+���������
�/�
�/�
�!"*���'�+�����
����
�/���%$���./��/�������/�����%�"+�'�!��'�������9�<�
����������'$�# +����"+�!����&+ &$$
���� "!��$$��"+��+�!������+�/"!���+��!�$"��'��!����!���������+����?��+��$"������)"!�����+���� !")���%�+�$�����%"&+�-�'�!*���+�$�'�)*'��#��&+'��$$����"��&!������������$"����"�����"%%"'&���%�+�$�%"&+�-��'�'�"�+�������&'�����&$��%%$&�'��"��$$ 0"&'�'��&����"+��+�!���������$"��'������������?��#�+������(��$&)&��&'�����'*)�" ��$$������"+��+�!�����$"��'�#�����+��+,�%�&!�" �#�!�0"&'������%�+�$�%"&+�'�����!�&+ "!�&+��!�=*&!���&+����&�&"+��"��$$�'��+��!��'�0�&������'%��& &���&"+'�
@��
@��
�"+��+�!����$"��
��+��!$"��
'���$�0"&'���,%� )&+����#�!�&+ "!�&+�
(�'65162���� ����� $���/������/����/���
$��'65162���� ����� $���/������/����/���
���!����#)�)#�!�"+�����'&���" �0"&'�'� &�$����$���"��"%A�#"��")���"!�'�'�'�"�+
%�+�$�%��
0"&'��!�&+ "!�&+������&$ "!��"+��+�!�����"!���+��!�$"��' '��$�:�+�'0�
�/ �
�"%�A#"��")�,%�����%&���
+ASSOCIATES INCSHELL MEYER2202 S Patterson blvdDayton, OH 45409.1930ph.937.298.4631 [email protected]
STRUCTURAL ENGINEERS
�6�BC�%59D6<3�+9�����������
Kettering Health Network
Grandview Medical Center
KEY PLAN:
REVISIONS:
NOTES:
Date
Checked By
Drawn By
Job No. Sheet No.
No. Date Description
...�B1EE�<86�5<F136<32�<9%�"+�:������������������������ ��:������������
����+��'����$�&!�'�!�������,�"+-�"�&"�
AREA�OF�WORK
�2�1E71<�367
'���
%�!�&�$�!"" � !�)&+�%$�+'
������
���
0 !
Air�Handler�Unit�#8
405 W. GRAND AVE. DAYTON, OHIO 45405
�����'�
��/����G�������!�� $""!��+������� $""!�
��/���G������
'����
��/���G������
'����
�&���!""
�&��
�!""
��/���G������
'����
��/���G������
'����
��/���G������
'����
��/���G������
'����
��/���G������
'����
��/���G������
'���
ALUMINUM ADATHRESHOLD SET INA FULL BED OFMASTIC
NEW 3'‐8" WIDE BY6'‐5" TALLINSULATED HOLLOWMETAL ROOFACCESS PANEL
NEW HOLLOWMETAL DOORFRAME SET INTOEXISTING OPENINGFROM WINDOWREMOVAL
NEW ROOF TOPUNIT #8 ‐ REFER TOMECHANICAL FORADDITIONALINFORMATION ANDDETAILS
ADHERED PVCMEMBRANE WALKWAY PADS FROMNEW ACCESS DOORTO NEW ROOF TOPUNIT AS SHOWN
3'‐6" TALL METALGUARD RAILATTACHED OFPARAPET WALL ‐FLASH AS REQUIREDTO CREATE AWEATHER TIGHTSYSTEM
RELOCATEDEXISTING VENTTHRU ROOF ‐ REFERTO MECHANICALFOR ADDITIONALINFORMATION ANDDETAILS
EXISTING RELOCATEDROOF DRAIN ‐ REFERTO MECHANICAL FORADDITIONALINFORMATION ANDDETAILS
4424HOLDING 14
4423HOLDING 13
4421HOLDING 12
4425TLT.
A3‐25
3'‐2
3 8"2'‐6"
2'‐10"
2'‐6"
23'‐1018" 4'‐0"
3" 3'‐6" 3"
13'‐8"
11'‐0
"
SLOPE
1 4" / 1'‐0"
SLOPE 14" / 1'‐0" SLOPE 14" / 1'‐0"
SLOPE
1 4" / 1'‐0"
SLOPE
1 4" / 1'‐0"
SLOPE
1 4" / 1'‐0"
SLOPE
1 4" / 1'‐0"
13'‐8"
SLOPE 14" / 1'‐0"
SLOPE 14" / 1'‐0"
1'‐9"
SLOPE
1 4" / 1'‐0"
NEW AIR HANDLINGUNIT #8 ‐ REFER TO PMEDRAWINGS FORADDITIONALINFORMATION ANDDETAILS
DIMENSIONS SHOWNARE TO METAL DUCT(TYP.) ‐ REFER TOSTRUCTURAL AND PMEDRAWINGS FORADDITIONALINFORMATION ANDDETAILS
SLOPE 14" / 1'‐0"(TYP.)
PREFABRICATEDALUMINUM STAIRSYSTEM WITHHANDRAILS
PREFABRICATEDALUMINUM STAIRSYSTEM WITHHANDRAILS
PREFABRICATEDALUMINUM STAIR
SYSTEM WITHHANDRAILS
13'‐3
3 8"
NEW INSULATED PREFABRICATED ROOFCURB (HEIGHT TO MATCH CURBSUPPORTING AIR HANDLING UNIT) RUNCOUNTER FLASHING (ROOF MEMBRANE)OUT FROM CURB 1'‐0" AND UP CURB 1'‐0" ‐RUN NEW ROOF MEMBRANE UP AND OVERNEW ROOF CURB
ENCLOSURE TO BE CONSTRUCTED FROMINSULATED ALUMINUM EXTERIOR PANELS ‐INSULATION TO BE 1" CLOSED CELL ‐ALUMINUM PANEL TO BE 16 GA ‐ PITCH CAPFROM UNIT TO REAR WALL ‐ ALLDIMENSIONS ARE TO BE VERIFIED IN THEFIELD. PAINT TO MATCH THE REST OFSURROUNDING ELCLOSURES
SLOPE
NEW HVAC PIPINGSHALL PENETRATE ROOF
AND RUNHORIZONTALLY TO NEW
AHU#8 UNIT BELOWENCLOSURE
EXISTING EXTERIORWALL ASSEMBLY TOREMAIN
EXISTING WINDOWUNIT TO BE REMOVEDWITH ALLATTACHMENTHARDWARE ‐ PREPARE FOR NEW DOORFRAME TO BEINSTALLED
PORTION OF EXISTINGEXTERIOR WALLASSEMBLY TO BEREMOVED
EXISTING FIXTURE TOBE REMOVED REPAIRSURROUNDING AREATO MATCH ADJACENT
3'‐8" (VIF)
4424HOLDING 14
4423HOLDING 13
4421HOLDING 12
425LT.
REMOVE EXISTING PVC ROOF MEMBRANE AND RIGIDINSULATION DOWN TO EXISTING CONCRETE DECK.REMOVE ALL FLASHING AROUND ROOF PENETRATIONS(REFER TO PLUMBING, ELECTRICAL AND MECHANICALDRAWINGS FOR ADDITIONAL DETAILS) RELOCATE ROOFDRAINS AS NOTED. PATCH OR REPAIR EXISTINGCONCRETE AND METAL ROOF DECKING AFTER REMOVALOR RELOCATION. PREP FOR NEW TAPERED INSULATIONAND NEW FULLY ADHERED PVC ROOF MEMBRANE
O
MICHAEL
7744TAYLOR
T.
OTSTA
OE FIH
EST
E
I
GR
T
H IRDRE A C
C
TE
PARTIAL FOURTH FLOOR AND ROOF PLAN NEW WORK PLANPARTIAL FOURTH FLOOR AND ROOF PLAN DEMOLITION PLAN
EXISTING EXTERIORWALL ASSEMBLY TOREMAIN
EXISTING WINDOWUNIT TO BE REMOVEDWITH ALLATTACHMENTHARDWARE ‐ PREPARE FOR NEW DOORFRAME TO BEINSTALLED
PORTION OF EXISTINGEXTERIOR WALLASSEMBLY TO BEREMOVED
EXISTING FIXTURE TOBE REMOVED REPAIRSURROUNDING AREATO MATCH ADJACENT
3'‐8" (VIF)
4424HOLDING 14
4423HOLDING 13
2AN
4425TLT.
3'‐8" (VIF)
ALUMINUM ADATHRESHOLD SET INA FULL BED OFMASTIC
NEW 3'‐8" WIDE BY6'‐5" TALLINSULATED HOLLOWMETAL ROOFACCESS PANEL
NEW HOLLOWMETAL DOORFRAME SET INTOEXISTING OPENINGFROM WINDOWREMOVAL
4424HOLDING 14
SLOPE 14" / 1'‐0"
PREFABRICATEDALUMINUM STAIRSYSTEM WITHHANDRAILS
NEW HVAC PIPINGSHALL PENETRATE ROOF
AND RUNHORIZONTALLY TO NEW
AHU#8 UNIT BELOWENCLOSURE
THRU WALL FLASHING
STEEL ANGLE LINTEL
BACKER ROD WITHSEALANT AROUND
EXTERIOR PERIMETER OFDOOR FRAME
HOLLOW METAL DOORFRAME
INSULATED METAL ROOFACCESS DOOR
EXISTING BRICK VENEER
ADA THRESHOLD SETFULL BED OF MASTIC
METAL FLASHING
NEW TERMINATION BARWITH SEALANT
WELD NEW PIECE OFPVC MEMBRANE ON
TOP OF EXISTING WALLFLASHING AND EXTEND
NEW PVC ROOFMEMBRANE UP WALLAND UNDER NEW ADA
THRESHOLD
NEW FRT WOODBLOCKING
EXISTING STEEL ANGLELINTEL
ADHERE NEW 58"GYPSUM WALL BOARDAND RETURN TOEXISTING MASONRYWALL
EXISTING SUSPENDEDCEILING SYSTEM TOREMAIN ‐ REMOVE ONLYENOUGH SUSPENDEDCEILING SYSTEM TOPERFORM REQUIREDWORK ‐ REPLACEEXISTING BACK TOCREATE UNDISTURBEDAPPEARANCE
CAULK AROUNDINTERIOR PERIMETER OFDOOR FRAME
PREFABRICATED ALUM.HAND RAIL AND STAIRS
ALUMINUM ADATHRESHOLD SET IN AFULL BED MASTIC
GROUT CORES FULL
8'‐4" (VER
IFY IN FIELD
)
8'‐0" (VER
IFY IN FIELD
)
FOURTH FLOOR
ROOF
THIRD FLOOR ROOF
1'‐6"
53 8"53 8"
53 8"2"
4'‐6
3 4"
11"
11"
11"
4'‐6
3 4"
53 8"53 8"
53 8"2"
1'‐6"
4'‐014"
11"
11"
8'‐0" (VER
IFY IN FIELD
)
THIRD FLOOR
THIRD FLOOR ROOF
1 2"1'‐5
3 8"1'‐31 2"
1'‐31 2"
4'‐0"
738"
8"
1 12" Ø GALVANIZEDSTEEL RAILING SYSTEM
MOUNTING PLATE ‐REFER TO STRUCTURALFOR ADDITIONALINFORMATION ANDDETAILS
LEVELING GROUT ASREQUIRED
EXTERIOR ROOF ACCESS HARDWARE
1 EA. 3'‐0" x 6'‐5" x 1 34" INSULATEDPAINTED HOLLOW METAL DOORAND PAINTED HOLLOW METALFRAME. PROVIDE THE FOLLOWINGHARDWARE SET:
1 12 PR NRP BALL BEARING HEAVYDUTY HINGES1 EA. ADA LEVER MORTISE LOCKSET(STORE FRONT FUNCTION) SARGENTTO MATCH EXISTING HOSPITALLOCKS1 EA. ADA CUSH CLOSER WITH HOLDOPEN OPTION1 EA. WALL STOP1 EA. THERMALLY BROKENTHRESHOLD1 EA. SET OF WEATHER STRIPPINGINCLUDING SILL SWEEP1EA. INTERIOR SIGH (BY OWNER)"FOR STAFF USE ONLY"
8" M
IN.
PVC PREFABRICATEDVENT STACK FLASHING
IF LEAD FLASHING ISEXIST. ON THE PIPE ITMUST BE REMOVED
BEFORE PVC FLASHINGIS INSTALLED.
PIPE FLASHING DETAIL
NEW VENT STACK ‐ TO REPLACEEXISTING
CONTINUOUS SEALANT
STAINLESS STEEL CLAMPINGRING, POSITIONED 14" FROM TOPON THE STACK FLASHING
HEAT WELD JOINT
SINGLE PLY PVC MEMBRANE ASSPECIFIED
4" RIGID INSULATION / MIN.R‐24.2
EXISTING 2" POURED GYPSUMOVER 10" CONCRETE SLAB.MEMBRANE FLASHINGATTACHMENT ‐ MIN. 18"O.C. & A MIN. OF 1PLATE FASTENER PERFLASHING.
14'‐5
"
22'‐2"
SAW CUT EXISTING PLASTER CEILING (APPROX.320 SF.) AND REMOVE FOR THE INSTALLATION OFSTRUCTURAL STEEL SUPPORT AND HVACEQUIPMENT ‐ DO NOT CUT THE STEEL BAR JOISTABOVE
EXISTING PLASTER CEILING ASSEMBLY TOREMAIN
14'‐5
"
22'‐2"EXISTING PLASTER CEILING ASSEMBLY TOREMAIN
ADD NEW HORIZONTAL 2 HOURSHAFT WALL ASSEMBLY(NER‐258) TO BOTTOM OFEXISTING STRUCTURE AND FIRECAULK AROUND PERIMETER TOEXISTING PLASTER EDGES. FIREPROOF NEW STEEL BEAMSWHERE EXPOSED WITH 1 12 HOURFIRE RATED FIREPROOFING
O
MICHAEL
7744TAYLOR
T.
OTSTA
OE FIH
EST
E
I
GR
T
H IRDRE A C
C
TE
PARTIAL FOURTH FLOOR DEMO PLAN
PARTIAL FOURTH FLOOR NEW WORK PLAN
SECTION THRU NEW ACCESS DOORSECTION THRU NEW GURAD RAIL
PARTIAL THIRD FLOOR CEILING DEMOLITION PLAN
PARTIAL THIRD FLOOR CEILING NEW WORK PLAN
A1
P1 P1OR
A1
OH1
2
1P2
BP2
GENERAL FLOOR PLAN NOTES
RISER OR STACK NUMBER
DETAIL: B = DETAIL DESIGNATION P2 = SHEET W HERE DETAIL IS LOCATED
FIRE SUPPRESSION HAZARD CLASSIFICATION AND HAZARD CLASSIFICATION GROUP
SECTION: 1 = SECTION DESIGNATION P2 = SHEET W HERE DETAIL IS LOCATED
EQUIPMENT REFERENCE. LETTER DESIGNATION VARIES. REFER TO SCHEDULES.
EQUIPMENT, DEVICE, OR PLUMBING FIXTURE MARK. LETTER DESIGNATIONS REFER TO SCHEDULES.
CONNECT TO EXISTING
PLAN NOTE. APPLIES ONLY TO THE SHEET W HICH IT IS SHOW N UNLESS NOTED OTHERW ISE.
DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.
"UP TO" SYMBOL (ITEM ON FLOOR ABOVE)
10" 10"
ELEV: 8' - 0"ELEV: 8' - 0"
TOE: 3' - 0"
BOE: 0' - 6"
APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO TOP OR BOTTOM OF EQUIPMENT, UNLESS NOTED OTHERW ISE
APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO CENTERLINE OF PIPE, UNLESS NOTED OTHERW ISE
FIRE SUPPRESSION SYMBOLSDOUBLE LINE SINGLE LINE
CONCEALED PENDENT SPRINKLER
FS
PIV
S
FIRE HYDRANT
FLOW SW ITCH
GATE VALVE OS&Y
INSTITUTIONAL PENDENT SPRINKLER
PENDENT SPRINKLER
POST INDICATOR VALVE
RECESSED PENDENT SPRINKLER
SIDE W ALL SPRINKLER
SUPERVISED VALVE
UPRIGHT SPRINKLER
PIPING SYMBOLSDOUBLE LINE SINGLE LINE
BOTTOM CONNECTION (45°)
BRANCH TEE CONNECTION (NOTE: BULLHEAD TEE'S ARE NOT PERMITTED)
DIRECTION OF PITCH
DROP
ELBOW DOW N
ELBOW UP
EXISTING PIPE TO BE REMOVED
EXISTING PIPE TO REMAIN
FLOW DIRECTION DESIGNATION
PUMP
RISE
TOP CONNECTION (45°)
TOP CONNECTION (90°)
BOTTOM CONNECTION (90°)
DD
RR
PLUMBING AND FIRE SUPPRESSION PIPING DESIGNATIONS
DOMESTIC COLD W ATER
DOMESTIC HOT W ATER
DOMESTIC HOT W ATER RETURN
EXISTING PIPE TO REMAIN
EXISTING PIPE TO BE REMOVED
HOT W ATER PIPE (140 DEGS. F.)
HOT W ATER PIPE (180 DEGS. F.)
HOT W ATER RETURN PIPE (140 DEGS. F.)
HOT W ATER RETURN PIPE (180 DEGS. F.)
ARGON PIPE
COMPRESSED AIR PIPE
MEDICAL CARBON DIOXIDE PIPE
COMBINATION FIRE SUPPRESSION AND DOMESTIC W ATER SERVICE
DIESEL FUEL PIPE
SPRINKLER PIPE (DRY)
FIRE SUPPRESSION (STANDPIPE / SPRINKLER MAIN)
FIRE SERVICE
FUEL OIL FLOW LINE
FUEL OIL GAUGE LINE
FUEL OIL RETURN LINE
FUEL OIL SUPPLY LINE
NATURAL GAS PIPE
GARAGE DRAINAGE PIPE
GAS SERVICE
HYDROGEN PIPE
HELIUM PIPE
MEDICAL INSTRUMENT AIR PIPE
KITCHEN W ASTE PIPE
LABORATORY COMPRESSED AIR PIPE
LABORATORY VENT PIPE
LABORATORY VACUUM PIPE
LABORATORY W ASTE PIPE
MEDICAL NITROGEN PIPE
MEDICAL COMPRESSED AIR PIPE
MEDICAL-SURGICAL VACUUM PIPE
GASOLINE PIPE (NON-LEAD)
MEDICAL NITROUS OXIDE PIPE
NON-POTABLE
MEDICAL OXYGEN PIPE
(OVERFLOW ) SECONDARY STORM DRAINAGE PIPE
PROPANE GAS PIPE
PUMP DISCHARGE PIPE
PRE-ACTION / DELUGE SPRINKLER PIPE
PURE W ATER PIPE
SPRINKLER PIPE (W ET)
SANITARY DRAINAGE PIPE
SOFT COLD W ATER
SPRINKLER DRAIN PIPE
STORM DRAINAGE PIPE
FUEL TANK VENT PIPE
TRAP PRIMER DISCHARGE PIPE
TEMPERED W ATER PIPE
SANITARY SEW ER VENT
W ASTE ANESTHESIA GAS DISPOSAL PIPE
W ATER SERVICE
140
LV
180
140R
180R
AR
CA
CO2
CW S
DF
DS
F
FS
FOF
FOG
FOR
FOS
G
GD
GS
H2
HE
IA
IV
IW
LA
LV
LW
N2
MA
MV
NG
NO
NPW
O2
OD
P
PD
PS
PW
S
SAN
SCW
SD
STM
T
TP
TW
V
W AGD
W S
INDIRECT VENT PIPE
INDIRECT W ASTE PIPE
K
3
3
CHECK VALVE
T
P
FOBFOT
SHUTOFF VALVE (REFER TO SPECIFICATIONS FOR REQUIRED TYPE BASED ON APPLICATIONS)
CONCENTRIC PIPE REDUCER
ECCENTRIC PIPE REDUCER
PRESSURE GAUGE
TEMPERATURE GAUGE OR THERMOMETER
UNION
CLEANOUT
STRAINER
STRAINER W ITH A BLOW DOW N VALVE AND HOSE CONNECTION
DRAIN VALVE W ITH HOSE END CONNECTION
AUTOMATIC FLOW CONTROLLER W ITH P/T PLUG IN AND OUT
EXPANSION JOINT
PRESSURE REGULATING VALVE
SAFETY RELIEF VALVE. PIPE DISCHARGE AIR GAPPED TO FLOOR DRAIN UNLESS NOTED OTHERW ISE.
PRESSURE AND TEMPERATURE TEST PLUG
TRAP PRIMER
VACUUM GAUGE W ITH STOP
CLEANOUT TO GRADE OR FINISHED FLOOR
END CAP
MIXING FAUCET
PLUG
HOSE BIB
W ALL HYDRANT
PLUG VALVE
SHUTOFF VALVE AND BOX
SHUTOFF VALVE ON RISER
V
VB
TP
CO
COMBINATION SHUTOFF AND BALANCING VALVE (REFER TO SPECIFICATIONS FOR REQUIRED TYPE BASED ON APPLICATIONS)
BALL VALVE
BUTTERFLY VALVE
GATE VALVE
VALVES AND FITTINGSDOUBLE LINE SINGLE LINE
SOLENOID VALVES
P/T PRESSURE AND TEMPERATURE SAFETY RELIEF VALVE. PIPE DISCHARGE AIR GAPPED TO FLOOR DRAIN UNLESS NOTED OTHERW ISE.
FIRE DEPARTMENT VALVE
W ATER METERM
ACID VENT PIPEAV
ACID W ASTE PIPEAW
ABBREVIATIONS
AAP - AREA ALARM PANEL (MEDICAL GAS)AC - AIR COMPRESSOR OR AIR CONDITIONERACC - ACCESSACCU - AIR COOLED CONDENSING UNITAD - ACCESS DOOR OR AREA DRAINADB - ACID DILUTION BASINADJ - ADJUSTABLEAFF - ABOVE FINISHED FLOORAFG - ABOVE FINISHED GRADEALT - ALTERNATEAP - ACCESS PANELAPPROX - APPROXIMATEAR - AIR RECEIVER OR ARGONARCH - ARCHITECT OR ARCHITECTURALASSY - ASSEMBLYAV - ACID VENTAW - ACID W ASTE
BDD - BACK DRAFT DAMPERBFP - BACKFLOW PREVENTERBLDG - BUILDINGBOB - BOTTOM OF BEAMBOD - BOTTOM OF DUCTBOE - BOTTOM OF EQUIPMENTBOF - BOTTOM OF FOOTINGBOG - BOTTOM OF GRILLEBOP - BOTTOM OF PIPEBOT - BOTTOMBT - BATHTUBBTU - BRITISH THERMAL UNITBTUH - BRITISH THERMAL UNIT PER HOURBTW N - BETW EEN
CA - COMPRESSED AIRCB - CATCH BASINCBD - COUNTER BALANCED BACKDRAFT DAMPERCFCI - CONTRACTOR FURNISHED CONTRACTOR
INSTALLEDCFM - CUBIC FEET PER MINUTECHS - CHILLED W ATER SUPPLYCHR - CHILLED W ATER RETURNCI - CAST IRONCK - CLINICAL SINKCLG - CEILINGCMU - CONCRETE MASONRY UNITCO - CLEAN OUTCO2 - MEDICAL CARBON DIOXIDECONN - CONNECT OR CONNECTIONCONTR - CONTRACTORCORR - CORRIDORCS - CLINICAL SINK OR COLD SOFT W ATERCTR - CENTERCU - COPPERCW - COLD W ATERCW S - COMBINATION W ATER SERVICE
OR CONDENSER W ATER SUPPLYCW R - CONDENSER W ATER RETURN
D - DEPTH OR DRAIN LINEDD - DECK DRAINDET - DETAILDF - DRINKING FOUNTAIN OR W ATER COOLER
OR DIESEL FUELDFU - DRAINAGE FIXTURE UNITDI - DEIONIZED W ATERDIA - DIAMETERDIM - DIMENSIONDN - DOW NDS - DOW N SPOUT OR SPRINKLER (DRY)DT - PERFORATED DRAIN TILEDW G - DRAW ING
EA - EACHEC - ELECTRICAL CONTRACTOR (DIVISION 26)EEW - EMERGENCY EYE W ASHEJ - EXPANSION JOINTELEC - ELECTRICALELEV - ELEVATOREQ - EQUALEQUIP - EQUIPMENTET - EXPANSION TANKETR - EXISTING TO REMAINES - EMERGENCY SHOW EREQS - EQUIPMENT SUPPLIEREW C - ELECTRICAL W ATER COOLEREXH - EXHAUST AIREXP - EXPANSIONEXT - EXTERIOREX - EXISTING
F - FIRE SUPPRESSION (STANDPIPE/SPRINKLER MAIN)FCE - FIRE CONTROL EQUIPMENTFCO - FLOOR CLEANOUTFD - FLOOR DRAINFDC - FIRE DEPARTMENT CONNECTIONFDV - FIRE DEPARTMENT VALVEFF - FINISHED FLOOR ELEVATIONFHC - FIRE HOSE CABINETFLR - FLOORFM - FORCE MAINFOB - FLAT ON BOTTOM
FOF - FUEL OIL FLOWFOG - FUEL OIL GAUGEFOR - FUEL OIL RETURNFOS - FUEL OIL SUPPLYFOT - FLAT ON TOPFPM - FEET PER MINUTEFR - FIRE RISERFS - FLOOR SINK OR FIRE SERVICEFSC - FIRE SUPPRESSION CONTRACTOR (DIVISION 21)FT - FEETFTG - FOOTING
G - GAS OR NATURAL GASGA - GAUGEGAL - GALLONGALV - GALVANIZEDGC - GENERAL TRADES CONTRACTORGD - GARAGE DRAINAGEGPM - GALLONS PER MINUTEGS - GAS SERVICEGW - GREASE W ASTE
H2 - HYDROGENHB - HOSE BIBBHC - HVAC CONTRACTOR (DIVISION 23)HD - HUB DRAINHE - HELIUMHG - REFRIGERANT HOT GASHP - HORSEPOW ER OR HIGH POINTHPC - HIGH PRESSURE CONDENSATE RETURNHPS - HIGH PRESSURE STEAM SUPPLYHPW - HIGH PURITY W ATERHPW R - HIGH PURITY W ATER RETURNHR - HOSE REELHT - HEAT TRACEHTR - HEATERHVAC - HEATING, VENTILATING, AND AIR CONDITIONINGHW - HOT W ATERHW R - HEATING HOT W ATER RETURNHW S - HEATING HOT W ATER SUPPLY
IA - MEDICAL INSTRUMENT AIRID - INSIDE DIAMETERINV - INVERT ELEVATIONIN - INCHESIV - INDIRECT VENTIW - INDIRECT W ASTE
JS - JANITOR SINK
K - KITCHEN W ASTEKEC - KITCHEN EQUIPMENT CONTRACTOR
L - LENGTHLA - LABORATORY COMPRESSED AIRLAV - LAVATORYLBS - POUNDSLCW - LABORATORY COLD W ATERLEC - LABORATORY EQUIPMENT CONTRACTORLHW - LABORATORY HOT W ATERLHW R - LABORATORY HOT W ATER RETURNLPC - LOW PRESSURE CONDENSATE RETURNLPS - LOW PRESSURE STEAM SUPPLYLV - LABORATORY VACUUM OR LABORATORY VENTLW - LABORATORY W ASTE
MA - MEDICAL COMPRESSED AIRMAP - MASTER ALARM PANEL (MEDICAL GAS)MAX - MAXIMUMMB - MOP BASINMC - MECHANICAL CONTRACTOR (DIVISION 23)MEZZ - MEZZANINEMFR - MANUFACTURERMH - MANHOLEMIN - MINIMUM OR MINUTEMISC - MISCELLANEOUSMTD - MOUNTEDMTG - MOUNTINGMPC - MEDIUM PRESSURE CONDENSATE RETURNMPS - MEDIUM PRESSURE STEAM SUPPLYMU - W ATER MAKE-UPMV - MEDICAL SURGICAL VACUUM
N2 - MEDICAL NITROGENN/C - NORMALLY CLOSEDNG - GASOLINE (NON-LEAD)NIC - NOT IN CONTRACTN/O - NORMALLY OPENNO - MEDICAL NITROUS OXIDENOM - NOMINALNPW - NON-POTABLE W ATERNPT - NATIONAL PIPE THREADNTS - NOT TO SCALE
02 - MEDICAL OXYGENOA - OUTDOOR AIROD - OUTSIDE DIAMETER OR OVERFLOW DRAINOFCI - OW NER FURNISHED CONTRACTOR
INSTALLEDOFOI - OW NER FURNISHED OW NER INSTALLED
P - PROPANE GASPC - PLUMBING CONTRACTOR (DIVISION 22)
OR PUMPED CONDENSATE RETURNPD - PUMP DISCHARGE OR PARAPET DRAINPIV - POST INDICATOR VALVEPLBG - PLUMBINGPS - PRE-ACTION/DELUGE SPRINKLER PRESS - PRESSUREPRV - PRESSURE REGULATING VALVEPSF - POUNDS PER SQUARE FOOTPSI - POUNDS PER SQUARE INCHPSV - PRESSURE SUSTAINING VALVEPSIG - POUNDS PER SQUARE INCH GAUGEPW - PURE W ATER
RA - RETURN AIRRAD - RADIUSRCP - REINFORCED CONCRETE PIPERD - ROOF DRAINREC - RECESSEDREQD - REQUIREDRI - ROUGH INRL - REFRIGERANT LIQUIDROS - REVERSE OSMOSIS W ATER SUPPLYROR - REVERSE OSMOSIS W ATER RETURNRPM - REVOLUTIONS PER MINUTERS - REFRIGERANT SUCTIONRV - RELIEF VALVE
S - SPRINKLER (W ET)SA - SHOCK ARRESTOR OR SUPPLY AIRSAN - SANITARY OR SANITARY DRAINSCH - SCHEDULESCW - SOFT COLD W ATERSD - SPRINKLER DRAIN OR SUBSOIL DRAINSH - SHOW ERSHT - SHEETSK - SINKSPEC - SPECIFICATIONSSQ - SQUARESR - SUPPLY RISERSS - SANITARY STACK (SOIL OR W ASTE) OR
STAINLESS STEELSTD - STANDARDSTM - STORM OR STORM DRAINAGESTRUC - STRUCTURAL OR STRUCTURESUC - SITE UTILITY CONTRACTOR
T - FUEL TANK VENTTD - TRENCH DRAINTEMP - TEMPERATURETOB - TOP OF BEAMTOD - TOP OF DUCTTOE - TOP OF EQUIPMENTTOF - TOP OF FOOTINGTOJ - TOP OF JOISTTOP - TOP OF PIPETOS - TOP OF SLAB OR TOP OF STEELTF - TRAP FILLERTP - TRAP PRIMER OR TRAP PRIMER DISCHARGETW - TEMPERED W ATERTYP - TYPICAL
UR - URINALUNO - UNLESS NOTED OTHERW ISE
V - VENT OR SANITARY SEW ER VENTVAC - VACUUMVC - VACUUM CLEANINGVCV - VACUUM CLEANING VALVEVE - VACUUM EXHAUSTVEL - VELOCITYVIB - VALVE IN BOXVOL - VOLUMEVP - VACUUM PUMPVS - VENT STACKVTR - VENT THROUGH ROOFVR - VENT RISER
W / - W ITHW /0 - W ITHOUTW - W ASTEW AGD - W ASTE ANESTHESIA GAS DISPOSALW C - W ATER CLOSETW CO - W ALL CLEANOUTW H - W ALL HYDRANT OR W ATER HEATERW IV - W ALL INDICATOR VALVEW S - W ATER SERVICE
YCO - YARD CLEANOUT
ZVC - ZONE VALVE CABINET
PIPE RISER
NOTE: ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT TO MODIFICATIONS ON OTHER DRAWINGS.
ALL SYMBOLS OR ABBREVIATIONS MIGHT NOTNECESSARILY BE USED ON THIS PROJECT.
GENERAL NOTES
A ALL PIPING IS ABOVE THE CEILING (AT THE UNDERSIDE OF STRUCTURE IN EXPOSED STRUCTURE AREAS), UNLESS OTHERW ISE NOTED.
B REFER TO DETAILS AND DIAGRAMS FOR PIPING, PIPE SIZES AND PIPELINE DEVICES NOT INDICATED ON THE FLOOR PLAN.
C ABOVE CEILING UTILITY SPACE IS LIMITED. COORDINATION W ITH ALL TRADES IS CRITICAL, PRIOR TO INSTALLATION OF ANY W ORK.
D LOCATIONS AND SIZES OF EXISTING PIPING HAVE BEEN DETERMINED FROM A REVIEW OF EXISTING DRAW INGS AND/OR SITE INSPECTION, W HERE POSSIBLE. FIELD VERIFICATION OF EXACT LOCATIONS, ELEVATIONS, INVERTS, SIZES, DIRECTION OF FLOW , ETC. SHALL BE REQUIRED PRIOR TO BEGINNING NEW W ORK.
E ALL PIPING SHALL BE REMOVED BACK TO ACTIVE MAINS AND CAPPED, OR REMOVED BACK TO POINTS OF CONNECTION IN NEW W ORK. DOMESTIC W ATER PIPING SHALL BE REMOVED BACK TO W ITHIN 2 PIPE DIAMETERS OF ACTIVE BRANCH/MAIN. NO DEADLEGS SHALL REMAIN. INACCESSIBLE PIPING, W HERE SO NOTED, TO BE ABANDONED SHALL BE DISCONNECTED FROM ACTIVE SYSTEMS AND CAPPED OR PLUGGED IN CONCEALED LOCATIONS. ALL ABANDONEDPIPING SHALL BE CAPPED AT INLET AND OUTLET.
F NEW CONNECTIONS TO EXISTING PIPING SHALL BE W ITH THE SAME SIZE AS THE EXISTING PIPING, UNLESS OTHERW ISE NOTED.
G ALL REMOVED MATERIAL AND EQUIPMENT, SO DESIGNATED BY THE OW NER, SHALL BE TURNED OVER AND PLACED W HERE DIRECTED. ALL MATERIAL AND EQUIPMENT, W HICH THE OW NER DOES NOT W ISH TO RETAIN, SHALL BECOME THE PROPERTY OF THE CONTRACTOR RESPONSIBLE FOR THE REMOVAL.
H REFER TO THE ARCHITECTURAL PLANS FOR PROJECT PHASING REQUIREMENTS.
I ANNULAR SPACE OF PIPE, CONDUIT AND OTHER SIMILAR PENETRATIONS OF FIRE RATED ASSEMBLIES SHALL BE FIRESTOPPED. IN ADDITION, PENETRATIONS THRU RATED FLOORS SHALL ALSO BE FIRESTOPPED TO RETARD PASSAGE OF FIRE ANDSMOKE. REFER TO SPECIFICATIONS. REFER TO ARCHITECTURAL DRAW ING(S) FOR CONSTRUCTION, LAYOUT AND FIRE RATINGS OF FLOORS, W ALLS, PARTITIONS AND OTHER BUILDING ELEMENTS. REFER TO ARCHITECTURAL DRAW INGS FOR PENETRATION DETAILS.
FD1
FD1
FD1
CO
4" - SAN
2" - V
3"VTR
4" - SAN
4"
���������
����
��� ���
����
����������
��������
� !�� " ������� "
� " ���� ��#��$%�$ �
���������
������������� ��������������
��� �
�� ������������ �
���"%$����&�����$����#"� ' (����)*+"�,,,"�---+���.�/�)*+"�,,,"�01)*,-2��"��"�����������������3��(���0402,
Heapy Project No. 2018-05176.01
�����������
������
����� ���
12" = 1'-0"
D.P001
PLUMBING LEGEND,NOTES, DIAGRAM AND
SHEET INDEX
07/27/18
WSM
DPB
SHEET LIST - PLUMBING - AHU 8
Sheet Number Sheet NameD.P001 PLUMBING LEGEND, NOTES, DIAGRAM AND SHEET INDEXD.P201 PARTIAL PLANS - PLUMBING NEW WORK
SCALE: NONE
SANITARY WASTE AND VENT DIAGRAM1
1 2018.08.17 PERMIT SET
����
�����
��
CO
BFP
BFP
1971
1948
9 10 12 13
D
E
G
F
FD1 FD1
FD1CLEAN STEAM GENERATOR
RO TANK
RO SYSTEM
W ATER SOFTENER
CARBON FILTER
TO DRAIN COOLER
0.75"
0.5"
0.5"
0.5"
0.5"
0.5"
4D.P201
ETR VS
VTRVR
4" - STM
VTR
RD1
ETR 4" DS DN
14 15
1
2
5
0.75" - NPW6
7
120.75"
0.75"
2.5"
- DC
W2"
- DH
W0.
75" -
DHW
R0.
75" -
O2
1" -
MV
0.75
" - M
A 0.5"
- NO
V
V
4" -
STM
7
9
3
11
11
11
10
12 13
D
E
G
H
F
R 25' - 0"
RELIEF
OA
14 15
3" VTR
RELOCATED 4" VTR
RD1
3
4
8
10
AHU-8
ETR RD
10 12 13
E
G
F
FD1 FD1
FD1CO VR
4" - SAN
4" SS UP 4" SS DN
11
CARBON FILTERMARLO #ACA-10G-1120V/1PH
N/C
DCW
DHW
THERMOSTATIC MIXING VALVE (SET TO 77 DEG. F)
TO DRAIN TO DRAIN
W ATER SOFTENER W / BRINE TANKMARLO #MAT-15M-3/4120V/1PH
N/CNPW NPW
REVERSE OSMOSIS SYSTEMMARLO #MRO-500120V/1PH
RO W ATER
75 GALLON RO TANK AS MANUFACTURED BY ACE ROTOMOLD
N/C
TO DRAIN
S
1" MANUAL BLOW DOW N
TO DRAINDRAIN COOLER
0.5" - DCW
LEVEL CONTROLLER W / SIGHT GLASS
0.5" - NPW (TEMPERED)
CLEAN STEAM GENERATOR IS INCLUDED IN BASE BID. INSTALL PER MANUFACTURER'S RECOMMENDATIONS (PROVIDED BY DIV 23)
PROVIDE DIELECTRIC UNION AT THIS LOCATION (BY DIV 22). ALL PIPING DOW NSTREAM AND ASSOCIATED W ITH CLEAN STEAM SYSTEM IS TO BE STAINLESS STEEL (UNLESS NOTED OTHERW ISE)
REFER TO PLUMBING
DRAW INGS FOR CONTINUATION OF
PIPING
NOTE: ALL DASHED EQUIPMENT IS PROVIDED BY DIV 23 AS AN ADD ALTERNATE. DASHED PIPING W ILL BE PROVIDED BY DIV 22 AS AN ADD ALTERNATE.
BASE BID PIPING
4" THICK HOUSEKEEPING PAD
REFER TO MECHANICAL DRAW INGS FOR CONTINUATION
HPC
HPS (70#)
LPS (15#)
2" 1.25"
3"
ALL LPS PIPING AND FITTINGS TO BE STAINLESS STEEL
0.75" NPW TO ROOF HYDRANT
HPS
(70#
)
LPS
(15#
)
HPC
� �������
������
�������
����
����������
��������
!"��!# �������!#
�!# ���� ��$��%&�%!�
���������
������������� ��������������
��� �
�� ������������ �
���#&%����'�����%����$#�!(�)�����*+,#�---#�...,���/���*+,#�---#�01*+-.2��#���#����������������3��)���0402-
Heapy Project No. 2018-05176.01
�����������
������
����� ���
As indicated
D.P201
PARTIAL PLANS -PLUMBING NEW WORK
07/27/18
WSM
DPB
SCALE: 1/4" = 1'-0"
PARTIAL THIRD FLOOR - ENLARGED PLAN - NEW WORK1
SCALE: 3/16" = 1'-0"
PARTIAL ROOF PLAN2
SCALE: 1/4" = 1'-0"
PARTIAL SECOND FLOOR PLAN - NEW WORK3
SCALE: 12" = 1'-0"
CLEAN SYSTEM - RO SYSTEM DETAIL4
1 DISCONNECT AND REMOVE EXISTING VENTPIPING SERVING DEMOLISHED VENT THROUGHROOF ABOVE. REROUTE VENT PIPING TO NEWVENT THROUGH ROOF.
2 MODIFY EXISTING DOWNSPOUT AS REQUIRED TOACCOMMODATE RELOCATED ROOF DRAIN.
3 DISCONNECT AND REMOVE EXISTING ROOFDRAIN.
4 DISCONNECT AND REMOVE EXISTING VENT THRUROOF. REMOVE PIPING BACK TO POINT OFRECONNECTION.
5 0.75" DCW UP TO ROOF HYDRANT IN RTUVESTIBULE ABOVE. COORDINATE EXACTLOCATION AND INSTALLATION REQUIREMENTSWITH HC.
6 EXTEND 0.75" NON-POTABLE WATER FROM DRAINCOOLER FEED. REFER TO DETAIL 4/D.P201.
7 COORDINATE EXACT ROUTING AT JOB SITE.8 ROOF HYDRANT, JR SMITH #5904, IN RTU
VESTIBULE. COORDINATE EXACT LOCATION ANDINSTALLATION REQUIREMENTS WITH HC.
9 PROVIDE EXPANSION LOOP, EQUAL TOMETRAFLEX "METRALOOP", AT BUILDINGEXPANSION JOINT.
10 PROVIDE NEW ROOF DRAIN, ZURN ZC100-DE ORAPPROVED EQUAL.
11 REMOVE AND REPLACE EXISTING CEILING ASREQUIRED TO ACCOMMODATE NEW PIPING.
12 MODIFY EXISTING SPRINKLER PIPING IN THISAREA AS REQUIRED TO ACCOMMODATE NEWDUCTWORK. ADD NEW SPRINKLERS ASREQUIRED FOR 48" OR WIDER DUCTWORK. NEWPIPING AND SPRINKLERS TO MATCH EXISTING.COORDINATE EXACT REQUIEMENTS WITH HC.
1 2018.08.17 PERMIT SET
NOTE: ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT TO MODIFICATIONS ON OTHER DRAWINGS.
ALL SYMBOLS OR ABBREVIATIONS MIGHT NOT NECESSARILY BE USED ON THIS PROJECT.
ABBREVIATIONS
AC - AIR COMPRESSOR OR AIR CONDITIONERACCU - AIR COOLED CONDENSING UNITAD - ACCESS DOOR OR AREA DRAINADJ - ADJUSTABLEAFF - ABOVE FINISHED FLOORAFG - ABOVE FINISHED GRADEAFMS - AIR FLOW MEASURING STATIONALT - ALTERNATEAP - ACCESS PANELAPPROX - APPROXIMATEARCH - ARCHITECT OR ARCHITECTURALASSY - ASSEMBLYATC - AUTOMATIC TEMPERATURE CONTROL
BDD - BACK DRAFT DAMPERBFP - BACKFLOW PREVENTERBLDG - BUILDINGBOB - BOTTOM OF BEAMBOD - BOTTOM OF DUCTBOE - BOTTOM OF EQUIPMENTBOF - BOTTOM OF FOOTINGBOG - BOTTOM OF GRILLEBOP - BOTTOM OF PIPEBOT - BOTTOMBTU - BRITISH THERMAL UNITBTUH - BRITISH THERMAL UNIT PER HOUR
CBD - COUNTER BALANCED BACKDRAFT DAMPERCFCI - CONTRACTOR FURNISHED CONTRACTOR
INSTALLEDCFM - CUBIC FEET PER MINUTECHS - CHILLED W ATER SUPPLYCHR - CHILLED W ATER RETURNCHGR - CHILLED W ATER GLYCOL SOLUTION RETURNCHGS - CHILLED W ATER GLYCOL SOLUTION SUPPLYCLG - CEILINGCMU - CONCRETE MASONRY UNITCO - CLEAN OUTCO2 - CARBON DIOXIDECONN - CONNECT OR CONNECTIONCONTR - CONTRACTORCTR - CENTERCU - COPPERCW - COLD W ATERCW R - CONDENSER W ATER RETURNCW S - CONDENSER W ATER SUPPLY
D - DRAIN LINEDB - DRY BULBDDC - DIRECT DIGITAL CONTROLSDI - DEIONIZED W ATERDIA - DIAMETERDIM - DIMENSIONDN - DOW NDW G - DRAW ING
EA - EACH OR EXHAUST AIREAT - ENTERING AIR TEMPERATUREEC - ELECTRICAL CONTRACTOR (DIVISION 26)EJ - EXPANSION JOINTELEC - ELECTRICALELEV - ELEVATOREQUIP - EQUIPMENTET - EXPANSION TANKETR - EXISTING TO REMAINEQS - EQUIPMENT SUPPLIEREW T - ENTERING W ATER TEMPERATUREEXH - EXHAUSTEXP - EXPANSIONEXT - EXTERIOREX - EXISTING
FD - FLOOR DRAINFF - FINISHED FLOOR ELEVATIONFLR - FLOORFOB - FLAT ON BOTTOMFOF - FUEL OIL FLOWFOG - FUEL OIL GAUGEFOR - FUEL OIL RETURNFOS - FUEL OIL SUPPLYFOT - FLAT ON TOPFPM - FEET PER MINUTEFSC - FIRE SUPPRESSION CONTRACTOR (DIVISION 21)FT - FEETFTG - FOOTING
G - GAS OR NATURAL GASGA - GAUGEGAL - GALLONGALV - GALVANIZEDGC - GENERAL TRADES CONTRACTORGPM - GALLONS PER MINUTE
HB - HOSE BIBBHC - HVAC CONTRACTOR (DIVISION 23)HD - HUB DRAINHG - REFRIGERANT HOT GASHP - HORSEPOW ERHPC - HIGH PRESSURE CONDENSATE RETURNHPS - HIGH PRESSURE STEAM SUPPLYHR - HOURHT - HEAT TRACEHTR - HEATERHVAC - HEATING, VENTILATING, AND AIR CONDITIONINGHW - HOT W ATERHW R - HEATING HOT W ATER RETURNHW S - HEATING HOT W ATER SUPPLY
ID - INSIDE DIAMETERINV - INVERT ELEVATIONIN - INCHES
KEC - KITCHEN EQUIPMENT CONTRACTOR
L - LENGTHLAT - LEAVING AIR TEMPERATURELAV - LAVATORYLBS - POUNDSLPC - LOW PRESSURE CONDENSATE RETURNLPS - LOW PRESSURE STEAM SUPPLYLW T - LEAVING W ATER TEMPERATURE
MAX - MAXIMUMMDD - MOTORIZED DAMPERMEZZ - MEZZANINEMFR - MANUFACTURERMH - MANHOLEMIN - MINIMUM OR MINUTEMISC - MISCELLANEOUSMTD - MOUNTEDMTG - MOUNTINGMPC - MEDIUM PRESSURE CONDENSATE
RETURNMPS - MEDIUM PRESSURE STEAM SUPPLYMU - W ATER MAKE-UP
N/C - NORMALLY CLOSEDNIC - NOT IN CONTRACTN/O - NORMALLY OPENNOM - NOMINALNPT - NATIONAL PIPE THREADNTS - NOT TO SCALE
OA - OUTDOOR AIROBD - OPPOSED BLADE DAMPEROD - OUTSIDE DIAMETEROFCI - OW NER FURNISHED CONTRACTOR
INSTALLEDOFOI - OW NER FURNISHED OW NER INSTALLED
P - PROPANE GASPC - PLUMBING CONTRACTOR (DIVISION 22)
OR PUMPED CONDENSATE RETURNPLBG - PLUMBINGPRESS - PRESSUREPRV - PRESSURE REGULATING VALVEPSF - POUNDS PER SQUARE FOOTPSI - POUNDS PER SQUARE INCHPSIG - POUNDS PER SQUARE INCH GAUGE
RA - RETURN AIRRAD - RADIUSRCP - REFLECTED CEILING PLANRD - ROOF DRAINREC - RECESSEDREQD - REQUIREDRI - ROUGH INRL - REFRIGERANT LIQUIDROS - REVERSE OSMOSIS W ATER SUPPLYROR - REVERSE OSMOSIS W ATER RETURNRPM - REVOLUTIONS PER MINUTERS - REFRIGERANT SUCTION
S - SPRINKLER (W ET)SA - SUPPLY AIRSAN - SANITARY OR SANITARY DRAINSCH - SCHEDULESCW - SOFT COLD W ATERSHT - SHEETSPEC - SPECIFICATIONSSQ - SQUARESR - SUPPLY RISERSRV - SAFETY RELIEF VALVESS - STAINLESS STEELSTD - STANDARDSTM - STORM OR STORM DRAINAGESTRUC - STRUCTURAL OR STRUCTURESUC - SITE UTILITY CONTRACTOR
TEMP - TEMPERATURETOB - TOP OF BEAMTOD - TOP OF DUCTTOE - TOP OF EQUIPMENTTOF - TOP OF FOOTINGTOJ - TOP OF JOISTTOP - TOP OF PIPETOS - TOP OF SLAB OR TOP OF STEELTYP - TYPICAL
UNO - UNLESS NOTED OTHERW ISE
V - VENTVAC - VACUUMVEL - VELOCITYVIB - VALVE IN BOXVOL - VOLUMEVTR - VENT THROUGH ROOFVR - VENT RISER
W / - W ITHW /0 - W ITHOUTW B - W ET BULBW CO - W ALL CLEANOUT
GENERAL FLOOR PLAN NOTESPLAN NOTE. APPLIES ONLY TO THE SHEET W HICH IT IS SHOW N UNLESS NOTED OTHERW ISE.
DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.
3
3
A1 EQUIPMENT, DEVICE, OR PLUMBING FIXTURE MARK. LETTER DESIGNATIONS REFER TO SCHEDULES.
H1 H1OR EQUIPMENT REFERENCE. LETTER DESIGNATION VARIES. REFER TO SCHEDULES.
2
1H2
BH2
RISER OR STACK NUMBER
DETAIL: B = DETAIL DESIGNATION H2 = SHEET W HERE DETAIL IS LOCATED
SECTION: 1 = SECTION DESIGNATION H2 = SHEET W HERE DETAIL IS LOCATED
A1 "UP TO" SYMBOL (ITEM ON FLOOR ABOVE)
APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO TOP OR BOTTOM OF EQUIPMENT, UNLESS NOTED OTHERW ISE
10"
ELEV: 8' - 0"ELEV: 8' - 0"
TOD: 8' - 10"
BOD: 7' - 2"
20x20
20x20
APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO TOP OR BOTTOM OF DUCTW ORK, UNLESS NOTED OTHERW ISE
APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO CENTERLINE OF PIPE, UNLESS NOTED OTHERW ISE
DL-1
UC-X DOOR UNDERCUT. X = HEIGHT OF UNDERCUT IN INCHES; 0.75 INCH UNDERCUT IF NO HEIGHT IS NOTED. COORDINATE W ITH GC.
DOOR LOUVER. 1 = SQUARE FEET OF LOUVER.
CONNECT TO EXISTING
HVAC PIPING DESIGNATIONSCHILLED W ATER SUPPLY PIPECHS
CONDENSER W ATER SUPPLY PIPECW S
CONDENSER W ATER RETURN PIPECW R
DRAIN LINE. PITCH IN DIRECTION INDICATEDD
HEATING HOT W ATER SUPPLY PIPEHW S
HEATING HOT W ATER RETURN PIPEHW R
W ATER MAKE-UP PIPEMU
VENT PIPEV
REFRIGERANT LIQUID LINERL
REFRIGERANT SUCTION LINERS
EXPANSION TANK PIPEET
REFRIGERANT HOT GAS LINEHG
LOW PRESSURE CONDENSATE RETURN PIPELPC
LOW PRESSURE STEAM SUPPLY PIPELPS
MEDIUM PRESSURE CONDENSATE RETURN PIPEMPC
MEDIUM PRESSURE STEAM SUPPLY PIPEMPS
PUMPED CONDENSATE RETURN PIPEPC
HIGH PRESSURE CONDENSATE RETURN PIPEHPC
HIGH PRESSURE STEAM SUPPLY PIPEHPS
STEAM SUPPLY PIPE - NUMBER INDICATES P.S.I.G.10
MISC SYMBOLS
DUCTWORK SYMBOLS
ROUND BRANCH DUCTW ORKCONICALFITTING
ACOUSTICFITTING
ACOUSTICFITTING
ADAD
D
R R
D
RECTANGULAR BRANCH DUCTW ORK
SQUARE TEE W ITH TURNING VANES
NOTE: ALL SQUARE ELBOW S IN RECTANGULAR AND ROUND / OVAL DUCTW ORK SHALL BE PROVIDED W ITH TURNING VANES. REFER TO SPECIFICATIONS FOR ADDITIONAL DETAILS.
EXISTING DUCTW ORK TO REMOVED
RETURN AIR, RELIEF AIR, OR TRANSFER AIR DUCTW ORK. (UP AND DOW N) RADIUSED OR SQUARE W ITH TURNING VANES.SUPPLY AIR OR OUTDOOR AIR DUCTW ORK.(UP AND DOW N) RADIUSED OR SQUARE W ITH TURNING VANES.EXHAUST AIR DUCTW ORK. (UP AND DOW N) RADIUSED OR SQUARE W ITH TURNING VANES.RECTANGULAR AND ROUND / OVAL DUCTW ORK RISE / DROP W ITH 90° RADIUSED OR SQUARE ELBOW S AND TURNING VANES.
RADIUS ELBOW
90° SQUARE ELBOW (W ITH TURNING VANES)NOTE: ALL SQUARE ELBOW S IN RECTANGULAR AND ROUND DUCTW ORK SHALL BE PROVIDED W ITH TURNING VANES.
ACCESS DOOR OR PANEL
DUCTW ORK RISE IN DIRECTION OF AIR FLOW
DUCTW ORK DROP IN DIRECTION OF AIR FLOW
DUCTW ORK W ITH ACOUSTICAL LINER. LISTED DUCT SIZES ARE INSIDE CLEAR DIMENSIONS.
RECTANGULAR ROUND / OVAL
FLEXIBLE DUCTW ORK
FLEXIBLE CONNECTION
DUCTW ORK CONSTRUCTED OF SPECIAL MATERIAL AS NOTED
DIRECTION OF PITCH
RECTANGULAR DUCTW ORK DIMENSIONS(W x H), SYSTEM ABBREVIATION26x20 SA
ROUND DUCTW ORK DIMENSIONS (DIA), SYSTEM ABBREVIATION
26ø SA
OVAL DUCTW ORK DIMENSIONS (W x H), SYSTEM ABBREVIATION26x20 OV SA
DUCTWORK DEVICE SYMBOLS
W ALL OR DUCTW ORK MOUNTED AIR DEVICE. SG1 = DESIGNATION (REFER TO AIR DEVICE SCHEDULE). 20x12 = DUCT CONNECTION SIZE (IN INCHES).300 = REQUIRED CFM. 9'-0" = MOUNTING HEIGHT FROM FLOOR TO BOTTOM OF GRILLE.
A310ø300
MANUAL BALANCING VALVE DAMPER W ITH LOCKING DEVICE
BDD = BACK DRAFT DAMPERCBD = COUNTER-BALANCED BACK DRAFT DAMPER
SD = SMOKE DAMPERFS = COMBINATION FIRE - SMOKE DAMPERMDD = MOTORIZED DAMPERAFMS = AIR FLOW MEASURING STATION
DUCT MOUNTED SMOKE DETECTOR. COORDINATE LOCATION.
HUMIDITY SENSOR - DUCT MOUNTED
SG120x12
300BOG: 9'-0"
XXX
A-D
XX
H
SD
SP
AIR DEVICE. A3 = DESIGNATION (REFER TO FLOOR PLANS AND AIR DEVICE SCHEDULE FOR VARIOUS DESIGNATIONS).10ø = NECK SIZE (IN INCHES). 300 = REQUIRED CFM. ALL AIR DEVICE DISCHARGE 4-W AY UNLESS NOTED W ITH FLOW ARROW S. AIR DEVICE SHOW N IS 2-W AY SIDE THROW . METHOD OF IDENTIFICATION ALSO APPLIES TO OTHER CEILING MOUNTED AIR DEVICES.
FIRE DAMPERA = TYPE (REFER TO FLOOR PLANS FOR VARIOUS TYPES)D OR S = DYNAMIC OR STATIC
STATIC PRESSURE SENSOR - DUCT MOUNTED
CCARBON DIOXIDE SENSOR - DUCT MOUNTED
STEMPERATURE SENSOR - DUCT MOUNTED
CHECK VALVE
T
P
FOBFOT
SHUTOFF VALVE (REFER TO SPECIFICATIONS FOR REQUIRED TYPE BASED ON APPLICATIONS)
CONCENTRIC PIPE REDUCER
ECCENTRIC PIPE REDUCER
PRESSURE GAUGE
TEMPERATURE GAUGE OR THERMOMETER
COMBINATION SHUTOFF AND BALANCING VALVE (REFER TO SPECIFICATIONS FOR REQUIRED TYPE BASED ON APPLICATIONS)
VALVES AND FITTINGSSINGLE LINE
10"
TOE: 3' - 0"
BOE: 0' - 6"
CHILLED W ATER GLYCOL SOLUTION RETURN PIPECHGR
CHILLED W ATER GLYCOL SOLUTION SUPPLY PIPECHGS
CHILLED W ATER RETURN PIPECHR
SQUARE THROAT / RADIUS HEEL FITTINGS NOT ACCEPTABLE
PIPING SYMBOLSDOUBLE LINE SINGLE LINE
BOTTOM CONNECTION (45°)
BRANCH TEE CONNECTION (NOTE: BULLHEAD TEE'S ARE NOT PERMITTED)
DIRECTION OF PITCH
DROP
ELBOW DOW N
ELBOW UP
EXISTING PIPE TO BE REMOVED
EXISTING PIPE TO REMAIN
FLOW DIRECTION DESIGNATION
PUMP
RISE
TOP CONNECTION (45°)
TOP CONNECTION (90°)
BOTTOM CONNECTION (90°)
DD
RR
PIPE RISER
RADIUS'D BRANCH
RADIUS'D TEE
EXISTING DUCTW ORK TO REMAIN
UNLESS NOTED OTHERW ISE ON DRAW INGS, 15° MAX FOR DIVERGING, 30° MAX FOR CONVERGING TRANSITION
EMERGENCY SHUTOFF STATION. 46" MOUNTING HEIGHT UNLESS NOTED OTHERW ISE.
SPACE TEMPERATURE SENSOR / THERMOSTAT. W HEN W ALL MOUNTED, MOUNTING HEIGHT 46" TO MEET ADA REQUIREMENTS. W HEN MOUNTED NEXT TO W ALL SW ITCH COORDINATE W ITH ARCHITECT.
T
DPDIFFERENTIAL PRESSURE SENSOR. W HEN W ALL MOUNTED, MOUNTING HEIGHT 46" TO MEET ADA REQUIREMENTS. W HEN MOUNTED NEXT TO W ALL SW ITCH COORDINATE W ITH ARCHITECT.
H HUMIDITY SENSOR. W HEN W ALL MOUNTED, MOUNTING HEIGHT 46" TO MEET ADA REQUIREMENTS. W HEN MOUNTED NEXT TO W ALL SW ITCH COORDINATE W ITH ARCHITECT.
CARBON DIOXIDE SENSOR. W HEN W ALL MOUNTED, MOUNTING HEIGHT 46" TO MEET ADA REQUIREMENTS. W HEN MOUNTED NEXT TO W ALL SW ITCH COORDINATE W ITH ARCHITECT.
C
COCARBON MONOXIDE SENSOR. W HEN W ALL MOUNTED, MOUNTING HEIGHT 46" TO MEET ADA REQUIREMENTS. W HEN MOUNTED NEXT TO W ALL SW ITCH COORDINATE W ITH ARCHITECT.
TEMPERATURE SENSOR. W HEN W ALL MOUNTED, MOUNTING HEIGHT 46" TO MEET ADA REQUIREMENTS. W HEN MOUNTED NEXT TO W ALL SW ITCH COORDINATE W ITH ARCHITECT.
S
S TEMPERATURE SENSOR MOUNTED IN CEILING PLENUM.
STATIC PRESSURE SENSOR.SP
STRAINER W ITH A BLOW DOW N VALVE AND HOSE CONNECTION
DRAIN VALVE W ITH HOSE END CONNECTION
AUTOMATIC FLOW CONTROLLER W ITH P/T PLUG IN AND OUT
EXPANSION JOINT
MANUAL AIR VENT
AUTOMATIC AIR VENT
PRESSURE REDUCING VALVE
2 PORT AUTOMATIC CONTROL VALVE
3 PORT AUTOMATIC CONTROL VALVE
QUICK OPENING MANUAL VALVE
VACUUM BREAKER
NEEDLE VALVE
PRESSURE AND TEMPERATURE TEST PLUG
VACUUM GAUGE W ITH STOP
END CAP
GLOBE VALVE
SHUTOFF VALVE AND BOX
SHUTOFF VALVE ON RISER
A
M
M
N
V
VB
SOLENOID VALVES
SAFETY RELIEF VALVE. FOR HYDRONIC SYSTEMS PIPE DISCHARGE AIR GAPPED TO FLOOR DRAIN UNLESS NOTED OTHERW ISE. FOR STEAM SYSTEMS PIPE DISCHARGE TO OUTDOORS.
W ATER METERM
PRESSURE GAUGE W ITH COCK AND SIPHON LOOP
BI-M ETALIC STEAM TRAP AND DRIP ASSEM BLY
THERMODYNAMIC STEAM TRAP AND DRIP ASSEMBLY
INVERTED BUCKET STEAM TRAP AND DRIP ASSEMBLY
FLOAT AND THERMOSTATIC STEAM TRAP AND DRIP ASSEMBLY
THERM OSTATIC STEAM TRAP AND DRIP ASSEM BLY
BM
TD
IB
FT
TS
FLOW M ETERF
UNION
CLEANOUT
STRAINER
AUTOMATIC PRESSURE INDEPENDENT CONTROL VALVE
M
���������
����
��� ���
����
����������
��������
� !�� " ������� "
� " ���� ��#��$%�$ �
���������
������������� ��������������
��� �
�� ������������ �
���"%$����&�����$����#"� ' (����)*+"�,,,"�---+���.�/�)*+"�,,,"�01)*,-2��"��"�����������������3��(���0402,
Heapy Project No. 2018-05176.01
�����������
������
����� ���
12" = 1'-0"
D.H001
MECHANICAL LEGENDAND SHEET INDEX
July 27, 2018
HPB
MRM
PH D - SHEET LIST - MECHANICAL
Sheet Number Sheet NameD.H001 MECHANICAL LEGEND AND SHEET INDEXD.H201 PARTIAL THIRD FLOOR AND ROOF PLAND.H501 HVAC SCHEDULES AND DETAILSD.H701 HVAC CONTROLSD.H702 HVAC CONTROLS
2018.04.18 BPA DEMOLITION
1 2018.08.24 CONSTRUCTIONDOCUMENTS
SD
SD
SD
���� �� �
10 12 13
G
F
3403
MECHANICALROOM #10
3410CORRIDOR
3433
BREAKROOM
3434
LOCKERROOM
3431
JAN.CLOSET
RA
20x1
4 EA
38x2
4 RA
42x2
4 RA
28ø SA 52x24 SA
48x3
0 RA42x24 RA
CHS
CHS CH
R
LPSLPC
HPCHPS
CHSHWRHWS
CHS
CHRCHS
CHR
LPC
LPS
HWRHWS
HPS
HPC
38x1
4 RA
2.5"
LPCLPS
12
13
13
14
17
18
TYP.19
15
16
23
3"
3"
21
24
14 15
2"
1.25"
2"
2.5" 1.5"
FS
14x12 EA
FS
29
42x14 RA
6"6"
4"4"
28
27
2"
1.25"
CHSCHR
CHS
CHR
1.25"1.25"
13
1"4"4"
FS
42x24 RA
14
FS
10 12 13
E
G
F
AHU-8
3403
MECHANICALROOM #10
3410CORRIDOR
3433
BREAKROOM
3434
LOCKERROOM
3431
JAN.CLOSET
RA
RA
14x1
2 EA
24ø
39x8
120x34
9
9
9
8
11
10
12
14 15
22
(E)EF-12
10 12 13
D
E
G
H
F
3
1
AH-8
2
5
4
RELIEF
OA
.
6
7
EF-8
HWS
HWR
CHS
CHR
2.5"2.5"
4"4"
RL
RS
20
RS RL
14 15
H-2
HWS
HWR
CHS
CHR
LPS
LPC
1.5"
1"
25
26
14
10x16 EA
10x1
6 EA
2.5"2.5"
4"4"
2"
DD
30
���������
����
��� ���
����
����������
��������
� !�� " ������� "
� " ���� ��#��$%�$ �
���������
������������� ��������������
��� �
�� ������������ �
���"%$����&�����$����#"� ' (����)*+"�,,,"�---+���.�/�)*+"�,,,"�01)*,-2��"��"�����������������3��(���0402,
Heapy Project No. 2018-05176.01
�����������
������
����� ���
As indicated
D.H201
PARTIAL THIRD FLOORAND ROOF PLAN
July 5, 2018
HPB
MRM
GENERAL NOTESA. ALL ROOF W ORK IS TO BE COORDINATED W ITH THE GENERAL CONTRACTOR.
B. ALL NEW LPS PIPING DOW NSTREAM OF CLEAN STEAM GENERATOR IS TO BE STAINLESS STEEL.
C. ALL EXTERIOR DUCTW ORK IS TO BE INSULATED, W RAPPED, AND SUPPORTED AS REQUIRED IN THE SPECIFICATIONS.
D. ALL EXTERIOR W ATER PIPING IS TO BE PROVIDED W ITH HEAT TRACE. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
PLAN NOTES1. NEW AH SAT ON SEISMIC CURB - REFER TO DETAILS ON SHEET D.H501 FOR ADDITIONAL
INSTALLATION REQUIREMENTS.
2. 8'-0" W IDE SERVICE CORRIDOR. REFER TO AH DETAILS ON SHEET D.H501 FOR ADDITIONAL AH INSTALLATION AND COIL PIPING REQUIREMENTS.
3. ENSURE THAT NEW OUTDOOR AIR INTAKE OPENING ON AH IS A MINIMUM OF 25'-0" AW AY FROM ALL EXHAUST AND VENT SOURCES.
4. EXISTING EXHAUST FAN IS TO BE REMOVED. EXISTING ROOF PENETRATION IS TO BE PATCHED TO MATCH EXISTING FINISHES.
5. EXISTING EXHAUST FAN IS TO BE REPLACED. EXISTING ROOF PENETRATION AND CURB TO BE REUSED W ITH NEW EXHAUST FAN. PROVIDE CURB ADAPTER AS REQUIRED.
6. EXISTING CONDENSING UNIT SERVING IT ROOM ON GROUND FLOOR IS TO BE RELOCATED TO AVOID CONFLICT W ITH NEW DUCTW ORK SHOW N. COORDINATE SHUTDOW N W ITH OW NER PRIOR TO RELOCATION. COORDINATE NEW AH UNIT LOCATION AND ASSOCIATED DUCTW ORK W ITH EXISTING LINE SET AND ADJUST LINES AS NECESSARY. REPLACE ALL EXISTING PIPE SUPPORTS W ITH NEW SIMILAR TO PORTABLE PIPE HANGERS ROOF PIPE SUPPORTS.
7. ABANDONED ROOF SUPPORTS ARE TO BE REMOVED. PATCH ROOF TO MATCH EXISTING FINISH AS REQUIRED.
8. EXISTING STEAM PRV STATION AND ASSOCIATED PIPING MAY BE REMOVED AND IS BEING REPLACED BY CLEAN STEAM SYSTEM. REFER TO DETAILS FOR NEW W ORK REQUIREMENTS. COORDINATE REMOVAL OR SALVAGE W ITH OW NER - STATION MAY BE LEFT IN PLACE FOR BACK-UP.
9. REMOVE EXISTING DUCT TO POINT INDICATED. REFER TO NEW W ORK VIEW THIS SHEET FOR RE-USE REQUIREMENTS.
10. EXISTING OA INTAKE DUCTW ORK AND ASSOCIATED LOUVER ARE TO BE COMPLETELY REMOVED. EXISTING LOUVER IS TO BE SALVAGED AND REINSTALLED. PROVIDE BLANK-OFF PANEL BEHIND LOUVER W ITH 4" RIGID INSULATION BOARD.
11. EXISTING AH IS TO BE COMPLETELY REMOVED, ALONG W ITH ALL MECHANICAL, ELECTRICAL, CONTROLS, AND SUPPORT CONNECTIONS. COORDINATE REMOVAL W ITH ELECTRICAL CONTRACTOR. EXISTING HOUSEKEEPING PAD IS TO BE DEMOLISHED.
12. EXISTING EXPANSION TANKS ARE TO REMAIN.
13. DUCT MOUNTED SMOKE DETECTOR - COORDINATE INSTALLATION W ITH ELECTRICAL CONTRACTOR.
14. NEW 48x30 RA AND 42x30 SA DUCTW ORK UP / DOW N FROM ROOF ABOVE - REFER TO ADJACENT VIEW FOR CONTINUATION.
15. NEW PIPING UP / DOW N SERVING AH ON ROOF - REFER TO ADJACENT VIEW FOR CONTINUATION.
16. 32x22 SA DUCT CONNECTION CAPPED FOR FUTURE. PROVIDE MANUAL VOLUME DAMPER AT TAKE-OFF.
17. PROVIDE CAPPED 1" LPS AND 0.75" LPC CONNECTIONS W ITH VALVES FOR FUTURE 3400 W ING HUMIDIFIER CONNECTIONS.
18. NEW CLEAN STEAM GENERATOR. CEMLINE MODEL CSG, CAPABLE OF PRODUCING 555#/HR OF LPS-15PSI FROM 720 #/HR OF HPS-65 PSI. PROVIDE W ITH 4" HOUSEKEEPING PAD. REFER TO DETAIL ON SHEET D.P201 FOR ADDITIONAL INSTALLATION REQUIREMENTS.
SCALE: 1/4" = 1'-0"
PARTIAL THIRD FLOOR - ENLARGED PLAN - NEW WORK2
SCALE: 1/4" = 1'-0"
PARTIAL THIRD FLOOR - ENLARGED PLAN - REMOVALS1
SCALE: 3/16" = 1'-0"
PARTIAL FOURTH FLOOR - DEMOLITION AND NEW WORK PLAN3
19. RO SYSTEM COMPONENTS SHOW N ARE TO BE PROVIDED AS ALTERNATE #1 - REFER TO DETAIL ON PLUMBING SHEET D.P201 FOR ADDITIONAL EQUIPMENT AND INSTALLATION INFORMATION.NEW LOCATION OF EXISTING CONDENSING UNIT. EXTEND LINESETS TO NEW LOCATION. CONFIRM REVISED PIPE LENGTHS W ITH MANUFACTURER AND PROVIDE ANY REFRIGERATION PIPING ACCESSORIES REQUIRED. PROVIDE PORTABLE PIPE HANGERS ROOF SUPPORTS FOR ALL NEW ROOFTOP PIPING. PROVIDE CONDENSING UNIT W ITH NEW EQUIPMENT RAILS FOR MOUNTING - COORDINATE ROOF FLASHING W ITH GENERAL CONTRACTOR.
20. NEW LOCATION OF EXISTING CONDENSING UNIT. EXTEND UNESETS TO NEW LOCATION. CONFIRM REVISED PIPE LENGTHS W ITH MANUFACTURER AND PROVIDE ANY REFRIGERANT PIPING ACCESSORIES REQUIRED. PROVIDE PORTABLE PIPE HANGERS ROOF SUPPORTS FOR ALL NEW ROOFTOP PIPING. PROVIDE CONDENSING UNIT W ITH NEW EQUIPMENT RAILS FOR MOUNTING - COORDINATE ROOF FLASHING W ITH GENERAL CONTRACTOR.
21. INSTALL ALL DUCTW ORK IN THIS AREA AS HIGH AS POSSIBLE.
22. EXISTING VFD TO BE REMOVED. COORDINATE W ITH ELECTRICAL CONTRACTOR.
23. EXISTING 1.25" CHS/R DOW N TO SECOND FLOOR CT ROOM AC UNIT.
24. EXISTING 2.5" CHS/R DOW N TO MRI BELOW .
25. NEW PIPING UP FROM BELOW ROUTED ABOVE THE ROOF LINE OVER TO NEW AIR HANDLING UNIT SERVICE CORRIDOR. PIPING IS TO BE SUPPORTED ACROSS THE ROOF AND ENCLOSED W ITHIN AN ALUMINUM HOUSING THAT IS SAT ON AN EQUIPMENT CURB CAPABLE OF BEING FLASHED INTO THE EXISTING ROOF SYSTEM. REFER TO ARCHITECTURAL AND STRUCTURAL PLANS FOR ADDITIONAL INFORMATION. EXISTING W ATER PIPING W ITHIN ENCLOSURE IS TO BE HEAT TRACED - COORDINATE INSTALLATION W ITH EC. ENCLOSURE IS TO BE PAINTED (COLOR PER OW NER) - COORDINATE W ITH GENERAL CONTRACTOR.
26. RETURN AIR INLET PLENUM TO NEW AH TO BE FULL SIZE OF FACTORY OPENING AND A MINIMUM OF 3'-0" DEEP.
27. PROVIDE 1.25" DRAIN CONNECTION W ITH BALL VALVE AND THREADED DUST CAP IN PIPING AT LOCATION INDICATED FOR DRAIN DOW N PURPOSES. COORDINATE TYPE OF DRAIN HOSE CONNECTION W ITH OW NER PRIOR TO INSTALLATION.
28. PROVIDE 4" CHS/R TAPS AT LOCATION SHOW N FOR FUTURE CONNECTION W ITH BLIND FLANGES AND SHUT-OFF VALVES.
29. TEMPORARY 48X24 DUCT INTERCONNECT FOR UNIT START-UP PURPOSES. REMOVE AND CAP AT MAINS ONCE NO LONGER REQUIRED. REPAIR INSULATION AS REQUIRED.
30. 2" COMMON DRAIN PIPE FOR COLLECTION OF ALL SECTION DRAINS DURING UNIT W ASHDOW N. PROVIDE THREADED CAP AT EACH END OF PIPNIG FOR EITHER SPILLING TO ROOF DRAIN OR CLEANOUT PURPOSES.
HVAC UNIT
1. AHU BASE.
2. INSULATED SEISMIC ROOF CURB.CURB SHALL BE BE A MINIMUM OF12" ABOVE THE ROOF SURFACE.
3. IN-CURB ACOUSTICAL TREATMENTHUSHCORE DS-30 DECK SYSTEM OREQUAL. (PROVIDED BY AND INSTALLED BY MECHANICAL CONTRACTOR)
4. CAULK AT ALL ROOF CURB PERIMETERW ITH HUSH SEALANT ACOUSTICAL GRADEOR EQUAL.
5. FIELD INSTALLED ROOF CANT STRIPBY ROOFING CONTRACTOR.
NOTES
25REFER TO
ARCHITECTURAL DRAW INGS FOR ROOF
CONSTRUCTION INFORMATION
ROOFING
1
34
DETAIL NOTES1. END INLET RETURN AIR OPENING (FACTORY BELLMOUTH OPENING 74"X42"). PROVIDE
FLEXIBLE DUCT CONNECTOR AT POINT OF UNIT CONNECTION.
2. LED MARINE LIGHT.
3. 2" PLEATED + 4" MERV-14 PRE-FILTER RACK.
4. DESICCANT W HEEL. (TYPE 3 DESICCANT)
5. RETURN / RELIEF FAN ARRAY W ITH FAN ISOLATION DAMPERS. (3x2 ARRAY)
6. FAN MOTOR REMOVAL RAIL. MATCHING RAIL TO BE PROVIDED W ITHIN SERVICE VESTIBULE FOR TRANSFER OF FAN ONCE CLEAR OF UNIT DOOR.
7. SERVICE VESTIBULE (8'-0" W IDTH).
8. INTERNAL DUCT OPENING TO BE COVERED W ITH GRATING TO ACCOMMODATE MAINTENANCE ACCESS REQUIREMENTS.
9. M IXING BOX SECTION W ITH OA / RA DAMPERS AND INTAKE W EATHER HOOD.
10. SERVICE VESTIBULE ENTRY DOOR.
11. HOT W ATER PRE-HEAT COILS. (QTY: 1)
12. SUPPLY FAN ARRAY W ITH FAN ISOLATION DAMPERS. (3x2 ARRAY)
13. W ALL-MOUNTED VFD W ITH BYPASS. (ONE PER FAN) BASIS OF DESIGN: YASKAW A ROUTE NO PIPING ABOVE VFD'S.
14. CHILLED W ATER PRIMARY COOLING COIL (QTY: 2)
15. UVGI DISINFECTION SYSTEM ARRAY. (REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION)
16. CHILLED W ATER SECONDARY COOLING COIL. (QTY: 2)
17. UVGI DISINFECTION SYSTEM W ITH PCO AIR CLEANING MESH. (REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION)
18. FINAL FILTER SECTION.
19. STEAM HUMIDIFIER (SUPPLIED BY HUMIDIFIER VENDOR.)
20. SUPPLY AIR OPENING. (FACTORY BELLMOUTH OPENING 74"x42"). PROVIDE FLEXIBLE DUCT CONNECTOR AT POINT OF UNIT CONNECTION.
21. 6" BASE RAIL.
22. 4" THICK UNIT CASING. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
23. RELIEF AIR OPENING W ITH W EATHER HOOD.
24. PROVIDE DUCT TRANSITION FROM SIZE OF FACTORY OPENING TO DUCT SIZE INDICATED ON FLOOR PLANS.
25. SEISMIC ROOF CURB - REFER TO ADJACENT DETAIL THIS SHEET AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.
26. ELECTRIC UNIT HEATER (PROVIDED BY AH VENDOR).
27. SERVICE VESTIBULE LIGHT SW ITCH.
28. CONVENIENCE OUTLET.
29. HOSE BIBB FOR MAINTENANCE PURPOSES - REFER TO PLUMBING DRAW INGS FOR ADDITIONAL INFORMATION.
30. COORDINATE OPENINGS THROUGH AHU CASING W ITH MANUFACTURER OR MANUFACTURER TO PROVIDE PIPING PENETRATION PORTALS FOR 4" CHS/R, 2.5" HW S/R, 1.5" LPS, AND 1" LPC PIPING.
31. PROVIDE 18x18 OPENING IN RELIEF AIR PLENUM W ITH MOTORIZED DAMPER. DAMPER TO BE NORMALLY CLOSED AND SHALL MODULATE OPEN AS NEEDED ONCE TEMPERATURE IN VESTIBULE RISES ABOVE 75°F (ADJ.)
32. DDC TEMPERATURE SENSOR FOR CONTROL OF SERVICE VESTIBULE RELIEF DAMPER.
33. 18x18 OPENING IN EXTERIOR W ALL OF SERVICE VESTIBULE W ITH LOUVER AND BIRDSCREEN. PROVIDE GRAVITY BACK DRAFT DAMPER ON INTERIOR OF OPENING THAT IS NORMALLY CLOSED. DAMPER IS TO BE ORIENTED TO RECEIVE PRESSURE FROM VESTIBULE. MOUNT LOUVER AT 48" AFF TO BOTTOM.
34. MOTORIZED W HEEL BYPASS DAMPER.
35. PROVIDE GRID OF UNISTRUT SUPPORTS AT UNDERSIDE OF AHU CASING FOR SUPPORT OF PIPING AS SHOW N.
36. COIL PULL CLEARANCE AND SERVICE VESTIBULE ACCESS PLUG.
37. MAINTAIN MINIMUM OF 42" CLEAR FROM FACE OF UNIT TO PIPING/CONDUIT MAINS ROUTED UP HIGH W ITHIN SERVICE VESTIBULE. RACK/STACK PIPING AS REQUIRED TO ACCOMMODATE - COORDINATE INSTALL W ITH ELECTRICAL CONTRACTOR.
DETAIL GENERAL NOTESA. REFER TO SPECIFICATIONS FOR ADDITIONAL UNIT AND COMPONENT CONSTRUCTION
REQUIREMENTS, OPTIONS, AND MATERIAL SELECTIONS.
B. PIPING SHOW N IS FOR REFERENCE ONLY.
UPPER SECTION
ELEVATION
LOW ER SECTION
5
23
9
3 11 4 12
26
7 35
65 113
344 12 6
2231
28
25 19 18 17 16 34 21 28 15 14
30
1310
32 13
TYP.
TYP.
$ T
7
19 18 17 15 1416 4
8
10
$$ 27
27$
1
1
2 TYP.
36 36
33
20
20
24
24
24
24
29
36
3737
3737
MOTOR - 480V - 3 PHASE UNLESS NOTED OTHERW ISE.
PR
E-H
EA
TIN
G C
OIL
LEAV. AIR
FACE AREA (S.F.)
HOUSING
PRESS. DROP IN. W .G. CLEAN
PR
E-F
ILT
ER
SENSIBLE M BH
TOTAL M BH
ENT. AIR DB/W B
LEAV. AIR DB/W B
AUTO. VALVE Cv & TYPE
MAX. W ATER P.D.- FT.
MAX. AIR P.D.- INCHES W .G.
TYPE
PR
IMA
RY
CO
OLI
NG
CO
IL
STEAM PRESSURE (TO AH)
CAPACITY; LBS./HR.
GPM
MAXIMUM FACE VELOCITY
AUTO. VALVE Cv & TYPE
MAX. W ATER P.D.- FT.
MAX. AIR P.D. INCHES W .G.
HU
MID
IFIE
R
COOLING COIL CAPACITY BASED ON 42° ENT. W ATER
HEATING COIL CAPACITY BASED ON 180° ENT. W ATER
VARIABLE SPEED DRIVE (QTY.)
W HEEL DIA.
CAPACITY M BH
MOTOR (MIN. H.P.)
MAXIMUM FACE VELOCITY
TOTAL/EXT. S.P.-INCHES W .G.
ENT. AIR
SU
PP
LY F
AN
CFM PER FAN
GENERAL NOTES
UNIT LOCATION
AREA SERVED
UNIT NUMBER
UNIT CONFIGURATION
ALL CAPACITIES BASED ON W ATER
ITEMS IN PARENTHESIS ( ) INDICATES QUANTITIES REQUIRED.
AIR HANDLING UNIT (OFCI)
FACE AREA
HOUSING
PRESS. DROP IN. W .G. CLEAN
AIR BLENDER
FIN
AL
FIL
TE
R
TYPE
CFM PER FAN
TOTAL / EXT. S.P. - INCHES W .G.
W HEEL DIA.
MOTOR (MIN. HP)
VARIABLE SPEED DRIVE (QTY.)
RE
TU
RN
FA
N
NOTES:
TOTAL MOTOR B.H.P.
MOTOR B.H.P.
SEISMIC RATED ROOF CURB
DESIGN SUPPLY CFM
TOTAL RETURN CFM
PRESS. DROP IN. W .G. DIRTY
PRESS. DROP IN. W .G. DIRTY
CONNECTED SUPPLY CFM
SET MIN. OUTDOOR AIR CFM
CONNECTED RETURN CFM
NUMBER OF FANS
CONNECTION SIZE (QTY. COILS)
GPM
CONNECTION SIZE (QTY. COILS)
NUMBER OF FANS
SE
CO
ND
AR
Y C
OO
LIN
G C
OIL
SENSIBLE M BH
TOTAL M BH
MAX. AIR P.D. IN W .G.
CFM
CROSS-LEAKAGE CFMENTERING AIR TEMPERATURE
DE
SIC
CA
NT
WH
EE
L
ENTERING AIR MOISTURE (REGEN)
LEAVING AIR TEMPERATURE
AT FINAL FILTER LEAVING AIR
CAPACITY LB/HRMOISTURE, GR/LBM
GR/LBM
DB / W B (PROCESS INLET)
DB / W B (PROCESS OUTLET)
ENTERING AIR TEMPERATURE
LEAVING AIR TEMPERATURE
DB / W B (REGEN INLET)
DB / W B (REGEN OUTLET)
AH-8
MAX ROW S/FPF
MAX ROW S/FPF
2 SUPPLY FAN MOTORS SHALL BE DESIGNED TO PROVIDE N+1
MAXIMUM FACE VELOCITY
ENT. AIR DB/W B
LEAV. AIR DB/W B
MAX. W ATER P.D.- FT.
MAX. AIR P.D.- INCHES W .G.
GPM
CONNECTION SIZE (QTY. COILS)
MAX ROW S/FPF
DESIGN OA CONDITIONS: 100°F DB/ 82°F W B,SUMMER, -10°F W INTER.
SILENCERS
261.9
52.2
0.51
62.0 / 50.0
47.0 / 42.9
12.9
2.0"
8 / 120
1,454
2"
16,000
71.2 / 63.4
50.2
48.5 / 48.4
76.0 / 64.5
53.2 / 47.3
-
39.9
BLOW -THRU
16,000
CATH LABS
1971 BLDG. - ROOF
7.5 (6)
3,500
6
15.0"
8.5" / 3.5"
38.8
17,508
500
881.9
538
504.5
146.5
1.0"
75.2 / 66.2
48.50 / 48.40
17.06
-
3"
10 / 142
2" PLEATED 30% 4" MERV 14
15"
8.7" / 3.0"
5.0 (6)
YES
3,200
16,000
12" CART - 90-951 EFF
FRONT
16,000
3,200
6
NO
FRONT
1.2
0.661
28.00
1.0
19.785
0.785
28.0
NO
3 PROVIDE ONE VFD W ITH BYPASS PER FAN.
607.3
45.0
80.0
.09
9.5
40.5
16,000
1 / 132
2.0"
502
261.9
AIR HANDLER TYPE CUSTOM OUTDOOR
YES (6) 3
YES (6) 3
AIRFLOW (MIN/MAX CFM)
4 ONE PIPING CONNECTION SERVES TW O COILS AT THIS
2
2
ECONOMIZER DAMPER YES
MAX. ECONOM IZER CFM 16,000
5 HEATING COIL AND COOLING COILS ARE ONLY SIZED FOR DESIGN MAXIM UM MINIMUM OUTDOOR AIR. COILS ARE TO BE STAGGERED W ITHIN UNIT FOR EASE OF MAINTENANCE.
1 REFER TO HUMIDIFIER SCHEDULE FOR PERFORMANCE REQUIREMENTS.
REDUNDANCY. TOTAL AIRFLOW AND STATIC PRESSURE SHALL BE ACHIEVED W ITH ONE FAN ON STAND-BY.
CONNECTION SIZE.
(PLANT SETPOINT IS 42° F) 5
15.0
AUTO. VALVE Cv & TYPE -
UV LIGHTS YES
UV LIGHTS YES
4
4
4
PHOTOCATALYTIC OXIDATION AIR CLEANER YES
GE
NE
RA
L
UNIT W EIGHT 30,000
UPPER SECTION DIMENSIONS (L" x W " x H") 385" x 217" x 70"
LED MARINE LIGHTS YES
MOTOR REMOVAL RAILS YES
SERVICE VESTIBULE / W IDTH YES / 8'-0"
LOW ER SECTION DIM ENSIONS (L" x W " x H")
OVERALL UNIT DIMENSIONS (L" x W " x H")
385" x 217" x 63"
385" x 217" x 133"
(3400 W ING)
-
1
FACTORY CUT DUCT OPENINGS YES
NOTES1. AIR HANDLING UNIT/CASING.2. HUMIDIFIER SUPPORTS PER AHU AND HUMIDIFIER MANUFACTURER'S
INSTRUCTIONS.3. BLANKED OFF AREAS. 100% OF AIR FLOW MUST PASS THRU THE HUMIDIFIER
GRID. BLANK OFFS SHALL BE MIN. 18 GA, SAME MATERIAL AS AHU LINER.4. AHU BASE RAIL AND CURB.5. DRIP LEG AND TRAP ASSEMBLY. REFER TO TYPICAL STEAM DRIP ASSEMBLY
DETAIL.6. MOUNT STEAM SIDE STRAINER SUCH THAT STRAINER IS ON ITS SIDE IN A
HORIZONTAL POSITION.7. LINE SIZE AUTOMATIC 2-POSITION CONTROL VALVE FOR SEASONAL OR SAFETY
SHUTOFF.8. AUTOMATIC MODULATING CONTROL VALVE.9. STEAM DISTRIBUTORS. VERTICAL SHOW N, HORIZONTAL SIMILAR. SPACING,
QUANTITIES, ETC... PER EQUIPMENT DATA.10. INCREASE INSTALLATION DIMENSIONS IF REQUIRED BY HUMIDIFIER
MANUFACTURER.11. FULL SIZE DIRT LEG, BUT MINIMUM 0.75" SIZE, W ITH DRAIN VALVE AND HOSE
CONNECTION.12. F&T STEAM TRAP, SIZED BY EQUIPMENT MANUFACTURER, 0.75" M INIMUM.13. DO NOT LIFT CONDENSATE RETURN PIPING.14. SECOND CONDENSATE RETURN CONNECTION W HEN REQUIRED BY HUMIDIFIER
MANUFACTURER. PIPE INDEPENDENTLY SAME AS ONE SHOW N, TRAP DISCHARGE TO CONDENSATE RETURN MAIN.
15. FROM SECOND TRAP DISCHARGE W HEN REQUIRED.16. SLEEVE AND FOAM AIR TIGHT ALL PIPING PENETRATIONS. PROVIDE STAINLESS
STEEL ESCUTCHEONS FOR NEAT APPEARANCE.
5
6 7 8
16
3
3
31410
1
9
3
1612
13
15
114
2
4" M
IN14
" MIN
20" M
IN
FT
STEAMSUPPLY MAIN
CONDENSATERETURN MAIN
FLOOR
LOW PRESSURECONDENSATE RETURN MAIN
M M
FOBSUPPLY HEADER
CONDENSATE HEADER
1. STEAM MAIN (30 PSIG AND BELOW ).2. F. & T. STEAM TRAP, 0.75" SIZE UNLESS NOTED
OTHERW ISE.3. COLLECTING POCKET AND DIRT LEG SAME SIZE AS MAIN.4. LENGTH FROM INVERT OF MAIN TO DRAIN PIPE, 1.5 x
MAIN DIAMETER, 8" M INIMUM.5. CONDENSATE RETURN, FULL SIZE OF TRAP DISCHARGE,
0.75" MINIMUM.6. 0.75" DRAIN VALVE W ITH HOSE CONNECTION.7. 0.75" TEST VALVE AND DRAIN W ITH HOSE CONNECTION.
NOTES
52
1
4
3 6 7
FT
4" M
IN.
.
1. AUTOMATIC TW O-PORT CONTROL VALVE. NORMALLY OPEN THRU COIL.
2. 0.5" DRAIN VALVE.3. PIPE REDUCER IF COIL CONNECTION
DIFFERS FROM PIPE SIZE.4. LEAVE W IDE OPEN UNLESS NEEDED TO
EVENLY DISTRIBUTE FLOW THRU COILS OR TO BALANCE PUMP GPM.
5. COIL RECIRCULATING PUMP. PUMP BOD: B&G e90, SIZE 2AAC, 120/1 W ITH A 0.5 HP MOTOR. SUPPORT FROM SERVICE VESTIBULE UTILIZING VIBRATION ISOLATING HANGERS AND SEISMIC RESTRAINTS (IMP FACTOR 1.5.)COORDINATE INSTALLATION W ITH EC.
A. ALL PIPING SHALL BE FULL SIZE OF MAIN RUN-OUT PIPING UNLESS NOTED OTHERW ISE. BRANCH PIPING TO EACH COIL ONE SIZE SMALLER THAN MAIN RUN-OUT PIPING, BUT NO SMALLER THAN COIL CONNECTION SIZE.
B. REFER TO AIR HANDLING UNIT SCHEDULE FOR AUTOMATIC CONTROL VALVE SIZE.
HWS
HWR
A IR
FLOW
5
34
3
1
2
AIR
FLOW
M
NOTES
GENERAL NOTES
1. AUTOMATIC THREE-PORT CONTROL VALVE. NORMALLY CLOSED THRU COIL.
2. 0.5" DRAIN VALVE.3. PIPE REDUCER IF COIL CONNECTION DIFFERS FROM PIPE SIZE.4. DRAIN PAN.5. DRAIN PIPE, SAME SIZE AS PAN CONNECTION, W ITH DEEP SEAL
TRAP. REFER TO CONDENSATE DRAIN PIPING DETAIL.6. W ITH AUTOMATIC CONTROL VALVE IN FULL BYPASS, SET
BALANCING VALVE TO MATCH PRESSURE DROP THRU COIL.7. LEAVE W IDE OPEN UNLESS NEEDED TO EVENLY DISTRIBUTE
FLOW THRU COILS.
A. ALL PIPING SHALL BE FULL SIZE OF MAIN RUN-OUT PIPING UNLESS NOTED OTHERW ISE. BRANCH PIPING TO EACH COIL ONE SIZE SMALLER THAN MAIN RUN-OUT PIPING, BUT NO SMALLER THAN COIL CONNECTION SIZE.
B. REFER TO AIR HANDLING UNIT SCHEDULE FOR AUTOMATIC CONTROL VALVE SIZE. VERIFY VALVE PORTING AND CONNECT PIPING TO PROPER PORTS, PER MANUFACTURER'S RECOMMENDATIONS.
C. SECONDARY CHILLED W ATER COIL TO BE PROVIDED W ITH A 2-W AY CONTROL VALVE (NO BYPASS).
CHR
CHS
A IR
FLOW
AIR
FLOW
M
D
1
3
7
6
73
2
4
5
NOTES
GENERAL NOTES
BLOW -THRU UNIT
1. DRAIN PIPE, SAME SIZE AS UNIT DRAIN PAN CONNECTION.2. VERIFY REQUIRED HEIGHT FOR DRAIN PIPE AND TRAP
INSTALLATION. PROVIDE ADDITIONAL BEAMS OR BACK-TO-BACK CHANNELS UNDER UNIT, IF REQUIRED, TO ATTAIN REQUIRED HEIGHT.
3. TEE W ITH CLEANOUT PLUG.4. 1" CENTERLINE-TO-CENTERLINE DIMENSION.5. CENTERLINE-TO-CENTERLINE DIMENSION NOT LESS THAN
SUPPLY FAN T.S.P. (INCH W .G.) + 1/2 INCH.6. AH CURB.
NOTES
2
FLOOR DRAIN
1
3
4
5
.
..
6
A.H. UNIT
���������
����
��� ���
����
����������
��������
� !�� " ������� "
� " ���� ��#��$%�$ �
���������
������������� ��������������
��� �
�� ������������ �
���"%$����&�����$����#"� ' (����)*+"�,,,"�---+���.�/�)*+"�,,,"�01)*,-2��"��"�����������������3��(���0402,
Heapy Project No. 2018-05176.01
�����������
������
����� ���
As indicated
D.H501
HVAC SCHEDULES ANDDETAILS
July 5, 2018
HPB
MRM
SCALE: NONE
AHU - ROOF CURB DETAIL1
SCALE: NONE
AH-8 SCHEMATIC DETAIL2
NOTES:1. SEASONAL SHUT-OFF VALVE SHALL BE LINE-SIZE-2-POSITION TYPE.2. MODULATING CONTROL VALVE FURNISHED WITH HUMIDIFIER.
3. SIZES ARE APPROXIMATE, FIELD VERIFY EXACT DIMENSIONS.4. HUMIDIFIER TO BE RATED FOR USE WITH 'CLEAN STEAM' (RO SOURCEWATER) SYSTEM. PROVIDE ALL REQUIRED ACCESSORIES ANDCOMPONENTS AS STAINLESS STEEL.
GENERAL NOTES:A. STEAM SERVICE TO HUMIDIFIER IS 10.0 PSIG SATURATED STEAM.B. PROVIDE F&T TRAP(S) PER DETAILS.
C. WHEN APPLICABLE, REFER TO SPECIFICATIONS FOR SEISMIC RESTRAINT REQUIREMENTS.
STEAM HUMIDIFIERS
MA
RK
DESCRIPTION SERVICE SP
AC
E C
ON
DIT
ION
S (
DB
/RH
)
PERFORMANCE DIMENSIONS MISC.SEISMIC
RESTRAINTS BASIS OF DESIGN
SE
E N
OT
E
EN
TE
RIN
G A
IR T
EM
PE
RA
TU
RE
DB
/WB
(°F
)
LE
AV
ING
AIR
TE
MP
ER
AT
UR
E D
B/W
B (
°F)
CF
M
LB
S /
HR
MIN
. NU
MB
ER
OF
DIS
TR
IBU
TIO
N T
UB
ES
MA
X. D
ISP
ER
SIO
N D
IST
AN
CE
DU
CT
/ C
AS
ING
WID
TH
(S
EE
NO
TE
3)
DU
CT
/ C
AS
ING
HE
IGH
T (
SE
E N
OT
E 3
)
ST
EA
M S
ER
VIC
E P
IPE
SIZ
E
CO
ND
EN
SA
TE
RE
TU
RN
PIP
E S
IZE
AIR
FLO
W P
RO
OF
HIG
H D
UC
T R
H C
UT
-OU
T
MO
DU
LAT
ING
CO
NT
RO
L V
ALV
E (
NO
TE
2)
SE
AS
ON
AL
SH
UT
-OF
F V
ALV
E (
NO
TE
1)
RE
QU
IRE
D
IMP
OR
TA
NC
E F
AC
TO
R
MANUFACTURER MODELH-2 UNIT HUMIDIFIER AH-8 68.0 / 50.0 54.5 / 37.0 56.0 / 51.9 16,000 170 20 24" 116" 48" 1.5" 1" � � � � � 1.5 DRI-STEEM XV 1,2,3,4
NOTES:1. PROVIDE WITH CURB ADAPTER AND INTEGRAL DISCONNECT.
GENERAL NOTES:A. ALL FANS SHALL BE A.M.C.A. 211 AND 311 PERFORMANCE CERTIFIED AND SHALL BEAR THE A.M.C.A. LABEL.B. SONES VALUES BASED ON A.M.C.A. 301 MEASURED AT 5 FT.C. MOTOR HORSEPOWERS LISTED SHALL BE CONSIDERED MINIMUM.
E. ROOF & WALL OPENINGS ARE APPROX. VERIFY SIZE & COORDINATE.F. COORDINATE STEEL FRAMING AROUND ROOF OPENING WHERE REQUIRED FOR DECK SUPPORT, AND WALL LINTELS FOR WALL OPENINGS.
G. WHEN APPLICABLE, REFER TO SPECIFICATIONS FOR VIBRATION ISOLATOR TYPES AND SEISMIC RESTRAINT REQUIREMENTS.H. VFD'S SHALL BE CONSTRUCTED AND LABELED FOR REQUIRED SCCR (SHORT CIRCUIT CURRENT RATING). COORDINATE WITH DIVISION 26.
FANS
MA
RK
TY
PE
(R
EF
ER
TO
SP
EC
S)
DESCRIPTION SERVICE CO
NN
EC
TE
D C
FM
FA
N C
FM
ST
AT
IC P
RE
SS
UR
E (
IN. W
.C.)
AP
PR
OX
. WH
EE
L D
IAM
ET
ER
MA
XIM
UM
SO
NE
S
MOTOR
VA
RIA
BLE
FR
EQ
UE
NC
Y D
RIV
E
AP
PR
OX
. RO
OF
/WA
LL O
PE
NIN
G
AP
PR
OX
. WE
IGH
T (
LBS
.)
VIB
RA
TIO
N IS
OLA
TO
R T
YP
E
SEISMICRESTRAINTS BASIS OF DESIGN
SE
E N
OT
E
HO
RS
EP
OW
ER
VO
LTA
GE
- P
HA
SE
ELE
CT
RO
NIC
ALL
Y C
OM
MU
TA
TE
D
RE
QU
IRE
D
IMP
OR
TA
NC
E F
AC
TO
R
MANUFACTURER MODELEF-8 D2 DOWNBLAST CENTRIFUGAL 3400 WING EA 1,460 1600 0.75 - 13.6 0.75 480 - - 15" x 15" 48 INTERNAL � 1.5 GREENHECK G-133-VG 1
SCALE: NONE
AHU STEAM INJECTION HUMIDIFIER4
SCALE: NONE
30 PSIG AND LOWER STEAM DRIP ASSEMBLY5
SCALE: NONE
A.H. UNIT HOT WATER COILS6
SCALE: NONE
A.H. UNIT CHILLED WATER COILS7
SCALE: NONE
AIR HANDLING UNIT DRAIN PIPING8
AI
AO
BI
BO
PI
OAT
MAT
RAT
SAT
CCAT
HCAT
OAHY
RAH
SAH
NC
NO
L
H
C
XX-01
LEGEND-AUTOMATIC TEMPERATURE CONTROLS
CONTROL POINT - SEE POINTS SCHEDULE
ANALOG INPUT
ANALOG OUTPUT
BINARY INPUT
BINARY OUTPUT
PULSED INPUT
OUTSIDE AIR TEMPERATURE
MIXED AIR TEMPERATURE
RETURN AIR TEMPERATURE
SUPPLY AIR TEMPERATURE
COOLING COIL LEAVING AIR TEMPERATURE
HEATING COIL LEAVING AIR TEMPERATURE
OUTSIDE AIR HUMIDITY
RETURN AIR HUMIDITY
SUPPLY AIR HUMIDITY
NORMALLY CLOSED (CLOSES ON LOSS OF POW ER)
NORMALLY OPEN (OPENS ON LOSS OF POW ER)
LOW
HIGH
COMMON
2-W AY AUTOMATIC 2-POSITION CONTROL VALVE
3-W AY AUTOMATIC 2-POSITION CONTROL VALVE
2-W AY AUTOMATIC MODULATING CONTROL VALVE
3-W AY AUTOMATIC MODULATING CONTROL VALVE
DIFFERENTIAL PRESSURE SENSOR
DIFFERENTIAL PRESSURE SW ITCH
CARBON DIOXIDE SENSOR
CARBON MONOXIDE SENSOR
CURRENT SENSOR TRANSMITTER
ELECTRONIC TO PNEUMATIC TRANSDUCER
FLOW METER TRANSMITTER
HUMIDITY SENSOR
LEVEL CONTROLLER
LEVEL TRANSMITTER
PRESSURE SENSOR
STATIC PRESSURE SENSOR
TEMPERATURE SENSOR
W ATER FLOW SENSOR
W ATER LEVEL SENSOR
CURRENT SW ITCH
END SW ITCH
FLOW SW ITCH
HUMIDISTAT
OCCUPANCY SENSOR
PRESSURE SW ITCH, HIGH LIMIT
PRESSURE SW ITCH, LOW LIMIT
TEMPERATURE LOW LIMIT (FREEZE STAT)
ROOM THERMOSTAT
W ATER LEVEL SW ITCH
EMERGENCY SHUT-OFF STATION
AIR FLOW MEASURING STATION
VARIABLE FREQUENCY DRIVE (ADJUSTABLE FREQUENCY MOTOR CONTROLLER)
MOTOR STARTER
CONTACTOR
LOCAL TEMPERATURE CONTROL PANEL
PRESSURE SAFETY - HIGH
PRESSURE SAFETY - LOW
SMOKE DETECTOR
DAMPER OR VALVE ACTUATOR - MODULATING
DAMPER OR VALVE ACTUATOR - 2-POSITION
RELAY
UVGI LIGHT
PUMP
FAN
COOLING COIL
HEATING COIL
HUMIDIFIER
FILTER
ENERGY RECOVERY W HEEL
OPPOSED BLADE CONTROL DAMPER
PARALLEL BLADE CONTROL DAMPER
SMOKE DAMPER
MIN OA / ECON DAMPER
DX COIL
W ALL MOUNTED DEVICE
DUCT INSERTION DEVICE
PIPE INSERTION OR IMMERSION DEVICE W ITH W ELL
AVERAGING SENSOR OR DEVICE
OUTDOOR SENSOR OR DEVICE, SHIELDED
FAN ARRAY, "X" FANS VERTICAL x "Y" FANS HORIZONTAL
GENERAL NOTES-AUTOMATIC TEMPERATURE CONTROLSA A COMPLETE SYSTEM OF AUTOMATIC TEMPERATURE CONTROLS SHALL BE INSTALLED AS REQUIRED TO ACCOMPLISH THE SEQUENCE OF CONTROL FOR VARIOUS ITEMS OF EQUIPMENT AND SYSTEMS DESCRIBED HEREINAFTER. THE SYSTEM SHALL BE A DIRECT DIGITAL CONTROL SYSTEM UTILIZING ELECTRIC OR PNEUMATIC ACTUATION AS DEFINED IN THE SPECIFICATIONS.
B THE CONTROL DIAGRAMS AND INFORMATION CONTAINED W ITHIN ARE TO SHOW DESIGN INTENT. IT IS THE CONTROL SYSTEM SUPPLIERS RESPONSIBILITY TO DEVELOP DETAILED AND COMPLETE CONTROL DIAGRAMS AND SHOP DRAW INGS TO ACCOMPLISH THE SPECIFIED SEQUENCES.
C THE POINTS LIST IS SHOW N AS AN AID TO THE CONTRACTOR INDICATING THE MINIMUM POINTS REQUIRED FOR CONTROL, AND MONITORING. ALL INPUT AND OUTPUT POINTS, AND THEIR REQUIRED INTERFACE AND ACCESSORY HARDW ARE, SHALL BE PROVIDED FOR A COMPLETE AND FUNCTIONAL CONTROL SYSTEM. IF OR W HEN ADDITIONAL POINTS ARE REQUIRED TO ACCOMPLISH THE SEQUENCES OF CONTROL SPECIFIED, THESE POINTS, ALONG W ITH ADDITIONAL DIRECT DIGITAL CONTROL PANE(S) (IF REQUIRED), SHALL ALSO BE PROVIDED.
D BULB W ELLS FOR TEMPERATURE SENSING AS INDICATED SHALL BE PROVIDED BY THE HVAC CONTRACT. PIPING W ORK SHALL INCLUDE PROPERLY SIZED W ELDOLET OR THREADOLET FITTINGS PLACED AS DIRECTED BY THE CONTROL SYSTEM SUPPLIER.
E ELECTRICAL W ORK INCLUDES A POW ER SOURCE TO THE MOTOR STARTERS. PROVIDE ALL HVAC POW ER SOURCES REQUIRED BEYOND THESE STARTERS OR BEYOND SOURCES EXPLICITLY SHOW N ON THE ELECTRICAL DRAW INGS. THIS SHALL INCLUDE BUT NOT BE LIMITED TO W IRING, CONDUIT, TRANSFORMERS, RELAYS AND FUSES.
M
M
M
M
DPHL
DPH
L
C
CO
CS
EPT
FM
H
LC
LT
P
SP
T
WF
WL
CS
ES
FS
H
OS
HLP
LLP
TLL
T
WL
LEGEND-AUTOMATIC TEMPERATURE CONTROLS
AFMS
VFD
MS
CON
TCP
SD
M
M
SD
X
X
X
X
X
X
X
X
X
X
R
M M
MINECON
R
UV
3 x 1X x Y
PSH
PSL
���������
����
��� ���
����
����������
��������
� !�� " ������� "
� " ���� ��#��$%�$ �
���������
������������� ��������������
��� �
�� ������������ �
���"%$����&�����$����#"� ' (����)*+"�,,,"�---+���.�/�)*+"�,,,"�01)*,-2��"��"�����������������3��(���0402,
Heapy Project No. 2018-05176.01
�����������
������
����� ���
12" = 1'-0"
D.H701
HVAC CONTROLS
08/09/18
IAS
MRM
SCALE: NONE
HVAC CONTROLS LEGEND1
AIR HANDLING UNIT AH-8 ATC DIAGRAMSCALE: NONE
T
AH-46SUPPLY AIR
TEMPERATURE
AH-47
SAFETY SHUTDOW N
PSH SP
AH-49
DUCT STATIC PRESSURE
SUPPLY AIR
SUPPLY FAN
AH-27
AIR FLOW STATION
VFD
AH-29START/STOP
AH-30
DRIVE SPEEDAH-31
FAN FAULT
AH-28
FAN STATUS
COOLING COIL
AH-33
DRAIN PAN OVERFLOW
T
AH-26
H.C.L.A.T.
AH-25FREEZE-
STAT
PRE-HEAT COIL
AH-20
MIXED AIR TEMPERATURE
PRE- FILTER
AH-19
FILTER STATUS
DPHL
AH-34
RETURN AIR DAMPER
AH-52
BUILDING DIFFERENTIAL STATIC PRESSURE
DPHL TO THE
OUTDOORS
REFERENCE TO ROOM #
T T
LL
AFMS
RELIEF AIR (TO OUTSIDE)
RELIEF AIR DAMPER
AH-14
RELIEF AIR TEMPERATURE
T
AH-13
RELIEF AIR DAMPER
RETURN FAN
AH-08
AIR FLOW STATION
AFMS
VFD AH-09
FAN STATUSAH-10
START/STOP
AH-11
DRIVE SPEEDAH-12
FAN FAULT
OUTSIDE AIR
AH-17
AIR FLOW STATION
OUTSIDE AIR DAMPER
AFMS
AIR HANDLING UNIT AH-8 POINTS LIST SCHEDULE
POINT NO.
TYPE
NOTES
POINT NAME
ALARM
RETU
RN A
IR T
EMPE
RAT
URE
RET
URN
AIR
HUM
IDIT
Y
RETU
RN A
IR S
MO
KE D
ETEC
TIO
N
PRES
SURE
SAF
ETY
SHUT
-DO
WN
MIX
ED A
IR T
EMPE
RAT
URE
HO
T W
TR C
OIL
RET
UR
N W
ATER
TE
MPE
RAT
UR
E
SUPP
LY F
AN S
TATU
S
SUPP
LY F
AN S
TART
/STO
P
SUPP
LY F
AN F
AULT
PRIM
ARY
CH
ILLE
D W
ATER
CO
IL
CO
NTR
OL
VALV
E
DRA
IN P
AN O
VERF
LOW
SUPP
LY F
AN -
AIR
FLO
W
MEA
SUR
ING
STA
TIO
N
HOT
WAT
ER C
OIL
PU
MP
STAT
US
HO
T W
ATER
CO
IL P
UM
P ST
ART/
STO
P
FREE
ZE-S
TAT
PREH
EAT
CO
IL-L
EAVI
NG
AIR
TE
MPE
RAT
UR
E
ENER
GY
WHE
EL S
TATU
S
ENER
GY
WHE
EL S
TART
/STO
P
RELI
EF A
IR D
AMPE
R
UVG
I SYS
TEM
-CC
PHO
TOC
ATAL
YTIC
OXI
DAT
ION
(P
CO
) AIR
CLE
ANER
NOTES:1. CURRENT SENSOR.2. COORDINATE W ITH VFD SUPPLIER.3. COORDINATE SMOKE DETECTION ALARM SIGNAL FROM FIRE ALARM SYSTEM. SMOKE DETECTOR BY DIV 26/284. IN ADDITION TO BEING A (BI) SAFETIES SHALL BE W IRED INTO THE FAN STARTERS/VFD(S) STARTER CIRCUIT SUCH THAT THE SAFETY SHALL FUNCTION W HETHER THE SELECTOR SW ITCH IS IN THE "HAND" OR "AUTOMATIC" POSITION.5. COORDINATE INTER-FACE CARD W ITH VFD SUPPLIER. FACILITY CONTROLS SYSTEM: EMCOR (AUTOMATED LOGIC).
RETU
RN A
IR F
ILTE
R ST
ATUS
OUT
SID
E AI
R D
AMPE
R
RET
URN
AIR
DAM
PER
OU
TSID
E AI
R -
AIR
FLO
W
MEA
SUR
ING
STA
TIO
N
WH
EEL
SUPP
LY L
EAVI
NG
AIR
TE
MPE
RAT
UR
E
PRE
FILT
ER S
TATU
S
AH-01 AH-02 AH-03 AH-04 AH-05 AH-07 AH-08 AH-09 AH-10 AH-11 AH-12 AH-13 AH-14 AH-15 AH-16 AH-17 AH-18 AH-19 AH-20 AH-21 AH-27AH-23 AH-24 AH-25 AH-26AH-22 AH-28 AH-29 AH-30 AH-31 AH-32 AH-33 AH-34 AH-35 AH-36 AH-49AH-38 AH-39 AH-40 AH-41 AH-42
AI
HIG
H/LO
W
AIAI
HIG
H/LO
W
A I
HIG
H/LO
W
BI
4
BI
ON
TRIP
3,4
BI
LOW
PR
ESS.
SY
STEM
ALA
RM
4
B0
2
ON
TRIP
2
AO BI
ON
TRIP
4
AI
HIG
H/LO
W
ON
FAIL
URE
BI
1
BO BI AI AI
HIG
H/LO
W
BI
1
B0 BOBI
ADJU
STAB
LE
HIG
H P
RES
S.
A0 A0
HIG
H/LO
W
AIAI
HIG
H/L
OW
B I
ADJU
STAB
LE
HIG
H P
RES
S.
RET
UR
N F
AN -
AIR
FLO
W
MEA
SUR
ING
STA
TIO
N
AI
HIG
H/L
OW
RET
URN
FAN
STA
TUS
ON
FAIL
URE
BI
1
RET
URN
FAN
STAR
T/ST
OP
RETU
RN
FAN
DRI
VE S
PEED
RETU
RN F
AN F
AULT
BO
2
AO BI
ON
TRIP
2
WH
EEL
LEAV
ING
RET
UR
N A
IR
TEM
PER
ATU
RE
A I
HIG
H/LO
W
A I
HIG
H/LO
W
RELI
EF A
IR T
EMPE
RATU
RE
AH-43
BO
H
L
WL
L
H
AH-44
HUMIDIFIER
M
AH-45
HUMIDIFIER CONTROL VALVE
HUMIDIFIER ISOLATION VALVE
M
AH-44
UV
HOT W ATER CONTROL
VALVE
M
AH-32
CHILLED W ATER CONTROL VALVE
MT
MSAH-23
PUMP STATUS
AH-24
HOT W ATER PUMP START/STOP
AH-21
AH-22
RETURN W ATER TEMPERATURE
2 2
AH-45 AH-46 AH-47
WH
EEL
ENT
RET
UR
N A
IR
TEM
PER
ATU
RE
AI
HIG
H/LO
W
FINAL FILTER
AH-43
FILTER STATUS
DPHL
AH-41
UV
AH-51
RETURN FAN VFD INTER-FACE
AH-50SUPPLY FAN VFD
INTER-FACE
AH-48
M
M
M
LOCATE W HERE SHOW N ON PLANS3 x 1
W HEEL ENTERING TEMPERATURE
AH-35
T
W HEEL LEAVING TEMPERATURE
AH-38
TCOOLING
COIL
AH-40
DRAIN PAN OVERFLOW
WL
M
AH-39
CHILLED W ATER CONTROL VALVE
PCO
CATALYTIC AIR CLEANER
RETURN AIR
3 x 1
AH-36
W HEEL START/STOP
MS
AH-37
W HEEL STATUS
PSL
SAFETY SHUT-DOW N
AH-04
FIRE ALARM SMOKE
DETECTION
AH-03
H
RETURN AIR HUMIDITY
AH-02
T
AH-01
RETURN AIR TEMPERATURE
RETURN AIR FILTER
AH-05
FILTER STATUS
DP HL
H
L
SD
W HEEL LEAVING TEMPERATURE
AH-07
T
W HEEL ENTERING TEMPERATURE
AH-06
T
AH-16
AHU-16
AH-15
OUTSIDE AIR TEMPERATURE
T
AH-42
H
DISCHARGE HUMIDITY
AH-48HL
AH-06
AO
OUT
SIDE
AIR
TEM
PER
ATUR
E
AI
HIG
H/L
OW
HO
T W
ATER
CO
IL C
ON
TRO
L VA
LVE
AO
AH-51 AH-52
ON
TRIP
HIG
H/LO
W
ON
FAIL
URE
B I
1
SUPP
LY F
AN D
RIV
E SP
EED
A0
2
UVG
I SYS
TEM
-C
C
BO
WH
EEL
SUPP
LY E
NTE
RIN
G A
IR
TEM
PER
ATU
RE
ON
FAIL
URE
AH-37
HIG
H/LO
W
SEC
ON
DAR
Y C
HIL
LED
WAT
ER C
OIL
C
ON
TRO
L VA
LVE
A0
DRAI
N P
AN O
VERF
LOW
BI
4
ON
TRIP
FINA
L FI
LTER
STA
TUS
BI
ADJU
STAB
LE
HIG
H P
RES
S.
HUM
IDIF
IER
ISO
LATI
ON
VAL
VE
BO
HUM
IDIF
IER
CONT
ROL
VALV
E
AO
SUPP
LY A
IR T
EMPE
RATU
RE
AI
HIG
H/LO
W
PRES
SURE
SAF
ETY
SHU
T-DO
WN
BI
HIG
H P
RES
S.
SYST
EM A
LAR
M
4
DIS
CH
ARG
E H
UM
IDIT
Y SE
NSO
R
(DU
CT
MO
UN
TED
)
AI
HIG
H/LO
W
DUC
T ST
ATIC
PRE
SSU
RE
AI
HIG
H/L
OW
INTER-FACE
SUPP
LY F
AN V
FD IN
TER
FACE
5
AH-50
INTER-FACE
RET
URN
FAN
VFD
INTE
RFAC
E
5
BUIL
DIN
G D
IFFE
REN
TIAL
STA
TIC
PR
ESSU
RE
AI
HIG
H/LO
W
3 x 1
(1) VFD PER FAN (TYP OF BOTH
ARRAYS)
3 x 1
���������
����
��� ���
����
����������
��������
� !�� " ������� "
� " ���� ��#��$%�$ �
���������
������������� ��������������
��� �
�� ������������ �
���"%$����&�����$����#"� ' (����)*+"�,,,"�---+���.�/�)*+"�,,,"�01)*,-2��"��"�����������������3��(���0402,
Heapy Project No. 2018-05176.01
�����������
������
����� ���
12" = 1'-0"
D.H702
HVAC CONTROLS
08/09/18
IAS
MRM
SCALE: NONE
AIR HANDLING UNIT #8 CONTROL DIAGRAM1
4
3
UP 8R
ELECTRICAL SYMBOLS
EXISTING OUTLET OR DEVICE TO REMAIN. MAINTAIN EXISTING CIRCUITING.
DASH SYMBOL INDICATES PARTICULAR OUTLET OR DEVICE TO BE REMOVED AND CIRCUITRY MADE CONTINUOUS W HERE REQUIRED.
ELECTRICAL CONNECTION.
20A-125V HOSPITAL GRADE DUPLEX RECEPTACLE, NEMA 5-20R (18" MH UNLESS NOTED OTHERW ISE).
20A-125V HOSPITAL GRADE SINGLE RECEPTACLE, NEMA 5-20R (18" MH UNLESS NOTED OTHERW ISE).
HOSPITAL GRADE SPECIAL PURPOSE RECEPTACLE. REFER TO NOTE ON PLAN.
20A-125V HOSPITAL GRADE DOUBLE DUPLEX RECEPTACLE. NEMA 5-20R, (18" MH UNLESS NOTED OTHERW ISE) TW O GANG ASSEMBLY.
20A-125V HOSPITAL GRADE DUPLEX RECEPTACLE, NEMA 5-20R, W ITH GROUND FAULT CIRCUIT INTERRUPTER (18" MH UNLESS NOTED OTHERW ISE).20A-125V W EATHERPROOF HOSPITAL GRADE DUPLEX RECEPTACLE, NEMA 5-20R (HORIZONTAL 18" MH UNLESS NOTED OTHERW ISE) W ITH TAYMAC #10310 STANDARD COVER, VERTICAL MOUNT.20A-125V W EATHERPROOF HOSPITAL GRADE DUPLEX RECEPTACLE, NEMA 5-20R W ITH GROUND FAULT CIRCUIT INTERRUPTER (18" MH UNLESS NOTED OTHERW ISE), W ITH TAYMAC #20310 STANDARD COVER, VERTICAL MOUNT.
JUNCTION BOX. SQUARE DEVICE INDICATES A CONNECTION TO CRITICAL POW ER.
MULTI-OUTLET RECEPTACLES ASSEMBLY, NEMA 5-15R (SINGLE OUTLETS ON 18" CENTERS) (46" MH UNLESS NOTED OTHERW ISE).
DISCONNECT SW ITCH.
MOTOR STARTER.
COMBINATION MOTOR STARTER AND DISCONNECT SW ITCH.
ELECTRIC MOTOR.
ELECTRICAL PANEL OR SW ITCHBOARD PER DRAW INGS.
GF
WP
WP/GF
J
20A-125V HOSPITAL GRADE DUPLEX RECEPTACLE, NEMA 5-20R (46" MH UNLESS NOTED OTHERW ISE).
ABBREVIATIONS
ATS - AUTOMATIC TRANSFER SW ITCH
CORR - CORRIDOR
D - DEPTHDIA - DIAMETERDIM - DIMENSIONDIV - DIVISIONDN - DOW NDW G - DRAW ING
EC - ELECTRICAL CONTRACTOR (DIVISION 26)ELEC - ELECTRICALEM - EMERGENCYEQUIP - EQUIPMENTE - EXISTING TO REMAINE/R - EXISTING TO BE RELOCATED
GC - GENERAL CONTRACTORGF - GROUND FAULT CIRCUIT INTERRUPTERGFCI - GROUND FAULT CIRCUIT INTERRUPTER
HC - HVAC CONTRACTOR (DIVISION 23)HP - HORSE POW ERHVAC - HEATING, VENTILATING, AND AIR CONDITIONING
MTD - MOUNTED
PC - PLUMBING CONTRACTOR (DIVISION 22)PLBG - PLUMBINGPR - PRINTER
S - SURFACE MOUNTEDSPEC - SPECIFICATIONSSQ - SQUARE
TYP - TYPICAL
VFD - VARIABLE FREQUENCY DRIVE
W P - W EATHERPROOF
1
E2
B
E2DETAIL: B = DETAIL DESIGNATION
E2 = SHEET W HERE DETAIL IS LOCATED
SECTION: 1 = SECTION DESIGNATION E2 = SHEET W HERE SECTION IS LOCATED
PLAN NOTE. APPLIES ONLY TO THE SHEET W HICH IT IS SHOW N.
DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.
GENERAL FLOOR PLAN NOTES
EACH ARROW HEAD REPRESENTS ONE COMPLETE CIRCUIT; "X" DENOTES PANEL NAME; NUMBER(S) DENOTES CIRCUIT(S).
X - 1,2
3
3
LUMINAIRE SYMBOLSLIGHTING FIXTURE. CAPITAL LETTER DENOTES FIXTURE TYPE, LOW ER CASE LETTER DENOTES SW ITCHING ARRANGEMENT.
LIGHTING FIXTURE ON CRITICAL CIRCUIT.
EXIT LIGHTING FIXTURE, ARROW S AS INDICATED.
Aa
3
3
NOTE:• ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT
TO MODIFICATIONS ON OTHER DRAWINGS.• ALL SYMBOLS OR ABBREVIATIONS MIGHT NOT
NECESSARILY BE USED ON THIS PROJECT.
LIGHTING FIXTURE ON LIFE SAFETY AND NIGHT LIGHT.
SQUARE DEVICE INDICATES A CONNECTION TO CRITICAL POW ER. SPECIFICATION IS SAME AS RESPECTIVE ROUND DEVICE.
J
7 9 10
D
E
G
H
J
DP5
DP2DP3
(#1)
DP5(#2)
DP5(#4)
DP5(#3)
DP4 (#2) (#1)
(#1)
DP3(#2)
DP3(#3)
DP3(#4)
DP2(#4)
DP2(#3)
DP2(#2)
(#1)
DP4
US1 US2
DP1DP1 (#2) (#1)
ATS1
800ABPS
O.U.SW BD
EM1
PRIM
ARY
SWIT
CHG
EAR
#2
DP15
E60LS
MCC6
T11
NL2
NL1
8
F
1
2
���������
����
��� ���
����
����������
��������
� !�� " ������� "
� " ���� ��#��$%�$ �
���������
������������� ��������������
��� �
�� ������������ �
���"%$����&�����$����#"� ' (����)*+"�,,,"�---+���.�/�)*+"�,,,"�01)*,-2��"��"�����������������3��(���0402,
Heapy Project No. 2018-05176.01
�����������
������
����� ���
As indicated
D.E001
ELECTRICAL LEGEND,SCHEDULES AND SHEET
INDEX
July 5, 2018
KMU
LLC
PHD - SHEET LIST - ELECTRICAL
Sheet Number Sheet NameD.E001 ELECTRICAL LEGEND, SCHEDULES AND SHEET INDEXD.E002 ELECTRICAL SINGLE LINE DIAGRAMD.E103 PARTIAL THIRD FLOOR - ELECTRICAL PLANSD.E104 PARTIAL FOURTH FLOOR - ELECTRICAL PLANS
NOTES:1.
LUMINAIRES
MARK
LAMPSV
OLT
AG
E
LO
AD
(V
A)
MANUFACTURER CATALOG NO. DESCRIPTIONOTHER ACCEPTABLE
MANUFACTURERS
MOUNTING
SE
E N
OT
E
TY
PE
CA
TA
LOG
NO
.
COLOR
S-SURFACER-RECESSEDSM-STEM MTDWM-WALL MTDC-CHAIN MTD
UC-UNDER CABCS-CEIL SURFACE
NOTES:1. COMBINATION VFD/DISCONNECT FURNISHED BY HC, INSTALLED BY EC.
MOTORS, STARTERS, DISCONNECTS & CONTROLS
MARK
MOTOR STARTER DISCONNECT MEANS CONTROL FEEDER
SE
E N
OT
E
NAMEPLATE
CHARACTERISTICS LOCATION
NE
MA
SIZ
E
TYPE LOCATION
FU
RN
ISH
ED
BY
TYPE LOCATION
FU
RN
ISH
ED
BY
INT
ER
LOC
K W
ITH
MO
TO
R N
O. B
Y E
.C.
MA
NU
AL
AT
ST
AR
TE
R
INT
EG
RA
L W
ITH
EQ
UIP
ME
NT
FU
RN
ISH
ED
BY
SE
E N
OT
E
NU
MB
ER
OF
CO
ND
UC
TO
RS
WIR
E S
IZE
GR
OU
ND
SIZ
E
CO
ND
UIT
SIZ
E
HO
RS
EP
OW
ER
(H
P)
LO
AD
(kV
A)
120
V-1
PH
208
V-1
PH
208
V-3
PH
277
V-1
PH
480
V-1
PH
480
V-3
PH
RO
OM
NU
MB
ER
ROOM NAME MA
NU
AL
MA
GN
ET
IC
BU
ILT
-IN
MO
TO
R O
/L
2-S
PE
ED
VF
D
SE
E N
OT
E
NE
AR
MO
TO
R
MO
TO
R C
ON
T C
EN
TE
R
EQ
UIP
CO
NT
PA
NE
L
RO
OM
NU
MB
ER
SE
E N
OT
E
DIS
C S
WIT
CH
MA
NU
AL
ST
AR
TE
R
RE
CE
PT
AC
LE
FE
ED
ER
SW
OR
BR
EA
KE
R
NE
MA
TY
PE
DIS
C S
IZE
FU
SE
SIZ
E
NE
AR
MO
TO
R
MO
TO
R C
ON
T C
EN
TE
R
EQ
UIP
CO
NT
PA
NE
L
PA
NE
LBO
AR
D
SE
E N
OT
E
AHU8-RF AHU8 RETURN FAN (6) 5 6.32 � - ROOF � � HC � � HC HC 3 12 12 0.75 1AHU8-SF AHU8 SUPPLY FAN (6) 7.5 9.15 � - ROOF � � HC � � HC HC 3 12 12 0.75 1
P-1 AH8 HOT WTR RECIRC PUMP 1/2 1.18 � - AH9 VESTIBULE 0 � � EC � � EC HC 2 12 12 0.75
SCALE: 3/16" = 1'-0"
PARTIAL GROUND FLOOR - ELECTRICAL PLAN2
1 LOCATION OF SPARE 200A FUSIBLE SWITCH.
2 APPROXIMATE LOCATION OF SHAFT FROMGROUND FLOOR TO LEVEL 3. UTILIZE SPARE2" CONDUIT INSTALLED UNDER PREVIOUSPHASE.
7.95 kVA 7.6 kVA (21 A)TOTAL CONNECTED ESTIMATED DEMAND
Notes:
Total Load: 3.07 kVA 2.85 kVA 2.05 kVA23 Space -- -- 0.0 kVA 0.0 kVA -- -- Space 2421 Space -- -- 0.0 kVA 0.0 kVA -- -- Space 2219 Space -- -- 0.0 kVA 0.0 kVA -- -- Space 2017 Space -- -- 0.0 kVA 0.0 kVA -- -- Space 1815 CONTROLS 20 A 1 0.1 kVA 0.2 kVA 1 20 A CDQ 1613 AHU8 HEAT TRACE 20 A 1 1.0 kVA 0.0 kVA 1 20 A Spare 1411 AHU8 HEAT TRACE 20 A 1 1.0 kVA 0.0 kVA 1 20 A Spare 129 AHU8 HEAT TRACE 20 A 1 1.0 kVA 0.0 kVA 1 20 A Spare 107 AHU8 HEAT TRACE 20 A 1 1.0 kVA 0.0 kVA 1 20 A Spare 85 Lighting 20 A 1 0.1 kVA 1.0 kVA 1 20 A AH8 UV LTG 63 UV LIGHT 20 A 1 0.4 kVA 1.2 kVA 1 20 A P-1 41 Lighting 20 A 1 0.4 kVA 0.7 kVA 1 20 A REC 2
CKT Circuit Description Trip PolesA B C
Poles Trip Circuit Description CKT
Voltage: 120/208 Wye-3PH-4W Mains Rating: 100 ASupply From: E87-CB Enclosure: Type 1 Mains Type: MLO
Location: AH8 VEST. - Mounting: Surface A.I.C. Rating: 10,000Panel: E234-CB
95.78 kVA 72.32 kVA (87 A)TOTAL CONNECTED ESTIMATED DEMAND
Notes:
Total Load: 31.93 kVA 31.93 kVA 31.93 kVA53 Space -- -- 0.0 kVA 0.0 kVA -- -- Space 5451 Space -- -- 0.0 kVA 0.0 kVA -- -- Space 5249 Space -- -- 0.0 kVA 0.0 kVA -- -- Space 5047 Space -- -- 0.0 kVA 0.0 kVA -- -- Space 4845 Space -- -- 0.0 kVA 0.0 kVA -- -- Space 4643 Space -- -- 0.0 kVA 0.0 kVA -- -- Space 4441 -- -- -- 0.0 kVA 1.0 kVA -- -- -- 4239 -- -- -- 0.0 kVA 1.0 kVA -- -- -- 4037 Spare 20 A 3 0.0 kVA 1.0 kVA 3 20 A AHU8 UNIT HEATER 3835 -- -- -- 3.0 kVA 2.1 kVA -- -- -- 3633 -- -- -- 3.0 kVA 2.1 kVA -- -- -- 3431 AHU8 SUPPLY FAN 20 A 3 3.0 kVA 2.1 kVA 3 20 A AHU8 RETURN FAN 3229 -- -- -- 3.0 kVA 2.1 kVA -- -- -- 3027 -- -- -- 3.0 kVA 2.1 kVA -- -- -- 2825 AHU8 SUPPLY FAN 20 A 3 3.0 kVA 2.1 kVA 3 20 A AHU8 RETURN FAN 2623 -- -- -- 3.0 kVA 2.1 kVA -- -- -- 2421 -- -- -- 3.0 kVA 2.1 kVA -- -- -- 2219 AHU8 SUPPLY FAN 20 A 3 3.0 kVA 2.1 kVA 3 20 A AHU8 RETURN FAN 2017 -- -- -- 3.0 kVA 2.1 kVA -- -- -- 1815 -- -- -- 3.0 kVA 2.1 kVA -- -- -- 1613 AHU8 SUPPLY FAN 20 A 3 3.0 kVA 2.1 kVA 3 20 A AHU8 RETURN FAN 1411 -- -- -- 3.0 kVA 2.1 kVA -- -- -- 129 -- -- -- 3.0 kVA 2.1 kVA -- -- -- 107 AHU8 SUPPLY FAN 20 A 3 3.0 kVA 2.1 kVA 3 20 A AHU8 RETURN FAN 85 -- -- -- 3.0 kVA 2.1 kVA -- -- -- 63 -- -- -- 3.0 kVA 2.1 kVA -- -- -- 41 AHU8 SUPPLY FAN 20 A 3 3.0 kVA 2.1 kVA 3 20 A AHU8 RETURN FAN 2
CKT Circuit Description Trip PolesA B C
Poles Trip Circuit Description CKT
Voltage: 480 Delta-3PH-3W Mains Rating: 200 ASupply From: DP4 Enclosure: Type 1 Mains Type: DSL
Location: MECH. - Mounting: Surface A.I.C. Rating: 14,000Panel: E233-EB
1 2018.08.24 CONSTRUCTIONDOCUMENTS
NE
NONE
E234-CB
E233-EB
60/3P
SB (NEW)
E44-LS(NEW)
60/260/260/3
125/3P
E195-CB
200A/3P (200A)
CATHLABUPS
N191 N192
MA
EPLABUPS
MA
80/3PCB
80/3PCB
125/3P STCB2
125/3P STCB2E184-CB E185-CB E186-CB
N80
E85-CB
SB
E187-CB
SINGLE-LINE DIAGRAM
N
100A/3PMANUALTRANS.
PDU1A PDU1B
480�208Y/120V75KVA
SONETPDU1-LS
�
HV3
LIFE SAFETY
B3
A2
C3A3
1"C
ELEV. ELEV.
ELEV. ELEV.
ELEV. ELEV.
EM43
SECTION #1
EM51ELEC.SHOP
EM1
EM53EM53A
EM41
EM52
SPAC
E FO
R20
0A S
WIT
CH
SECTION #2
1200AMAIN
CATSCANLEIBERT
AC
SPAR
E10
0SP
ARE
100
SPAR
E10
0
200
200
SPAR
E20
0
200
EM55
EM42
EM50
EM5
EM3 EM4 EM2
'66 BLDG.
SECTION #3
EM6
SPAR
E20
0SP
ARE
200
SPAR
E20
0SP
ARE
200
SPAC
E20
0
SPAC
E20
0
SECTION #4 SECTION #1
OLD MATERNITY A.C.
BOILER
SECTION #2
200
SPAR
E10
0
SPAR
E10
0
100
SPAR
E10
0SP
ARE
100
ROOM
OLD AH #1
EMER
.
NO
RM
.
O.U. BLDG.
OLD
SPAC
E20
0
P3
EMX1
SECTION #1 SECTION #2
SPAR
E60
SPAR
E20
0
SPAR
E20
0
SPAR
E40
0
P2CATHLAB
SPAR
E60
P4
TO WESTPARKING
LOT LIGHTS
SPAR
E30
P5
SPAR
E
CHILLERRM. 21
SPAR
E20
0
800
SPAR
E20
0
200A
MED AIRPUMP
PACKAGE #2
100A
MED VACPUMP
PACKAGE #2
800 800 1600
SECT. #1 SECTION #2
TO O.U. BLDG.
200A
SPA
CE
200A
SPA
CE
EM9SHORT
EM9A
STAY
1� 200ATELE.
FRAMEROOM
NUCLEARMEDICINE
ELEC.SHOPCAGE
PLUMB.SHOPHALL
SECTION #1 SECTION #2 SECTION #3 SECTION #4
1600
200
HALLNEARRM. 5
200
HG
200
AAG(AG)
E
SPAC
E
200
AA12300
2-10
0ASP
ACE
200
GG12300EAST
HH12300
WEST
200
BG
200
CG
200
DG
400
GG
2-10
0ASP
ACE
2-10
0ASP
ACE
SPAR
E10
0SP
ARE
100
SPAR
E20
0
200
200
NG
200
2-10
0ASP
ACE
2-10
0ASP
ACE
SPAR
E10
0SP
ARE
100
200
NL1
200
NL2
SITE
200
PG
LIGHTING
LPN-150
NUCLEARMEDICINE
COMM. RM.PHARMACY
T16
200
R1
2-10
0ASP
ACE
SECTION #4 SECTION #3 SECTION #2 SECTION #1
2-10
0ASP
ACE
SPAR
E10
0SP
ARE
100
"N62"(BB)
200
TRANSFERFOR PHONE
SWITCH
200
MG
200
FG
F1
200
200
SPAC
E
SPAR
E20
0
B1
200
C1
200
D1
E1
200
200
KG
400
'66 BLDG.NUCLEAR
200
200
TG
SPAR
E20
0
400
SPAR
E20
0
200
200
EG
200
SG
400
JG
TO LS SECT. 2
TO TS14
TO SC1
SPAR
E
SPAC
E
SPAC
E
SPAC
E
SPAC
E
SPAC
E
1600 800 800SPACESPACE
J1J1A
SHORTSTAY
TVROOM
SHORTSTAY
CATHLAB
3600'66
EM44B
CATHLAB
TO TS13
SPAR
E
SPAR
E
SPAR
E
SPAR
E
MORGUE
EM44A
RADIOLOGYCLOSET
QI
RAD.
RAD.CLOSET
BLDG.
K12300
D24600
LAB KITCH.
KITCH.STEAMROOM
LOBBYELEV. #7THERAPY
PHYS.
MED.NUC.
HALLRADIOLOGYTHERAPY
PHYS.
HIMS COMM. ROOM
D1ADOCTOR'S
READING RM.
PHARM.
HALLNEARPBX
PHONESWITCH
REGULATOR
GGELEV. OLD LAB KIT.
MAILROOMWALL
#3 & 4LOBBY
KIT.KIT.
MANHOLE #__
����
EMER
.
����
RADIOLOGYQI
TO DP18SECT. 3
SHEET E-5
3600
A15600
TO ELEV. #10SEE SHEET E-6
B16600
EM13
'66 BLDG.EM13A
'66 BLDG.EM13B
LABHALLOLDMAIL
ROOM
RAD.HALL
2300
CHEM.LAB
QIRAD.
RAD.CLOSET
MORGUE
PENTHOUSEPANEL
ELEV. #8
SHEET E-4
SHEET E-4
SHEET E-4
SHEET E-4
#3 #4
#5 #6
#7 #8
TAG
12-
93 R
EMO
VED
CHILLER 3RM. 3
SPACESPACE
TO PSC-2
N177
N178
CB X-RAY CATHLAB
ANGIO
AB
DP6
LABELED C23/60
2/60
E133EB
B506E148CB
B521E146CB
1342E131CB
2432E103CB
2407E102CB
3548E87CB
4542E75CB
4545E75ACB
2430E100CB
1518E132CB
2316E109CB
EM422316
E109CB
E128CB
2435E101CB
E127CB
B415E147CB
1616E129CB
3617E78CB
4645E71CB
6600E68CB
6642N66
B522E145EB
3403
CTFEEDER
B503E139EB
2407E104EB
7601
3618N76
3419N83
5642N69
B400
N14
3CB
N14
2
B424E140
1725E124
N136B524
N1171342N110
2316N105
2314N107
N106
N111N112
N113 N115N116
CAPPEDOFF IN
BOILER RM.
B521
N138N137
1616N121
2317N125
1335N120 1313
N114
2606N88
N89 N90
N91A
N91
N92
4653N123B
N70N72 N74 N73
3618N77
N79
2311N123A
N119
N1231631 N122
1728
J1
N62B408
N961500 N95
1500
N1181725
2332N94
2407N93
2314N108
2437N18L
E59CB E182CB
E61CB E67CB
B522
E63CB E64CB
3621E44ALS
2432E44BLS
1342E43LS
B522E60LS
TO SHEEE-4E60LS
CAGE
OLD HIMSDICTATION
SPAR
E
TRANSFORMER
NEED'S #
�����PENTHOUSE
N-P
PANEL C2VASCULAR LAB
HALL 3618
6500
7603 7603
TO TS-23
60/3
(40)
100/
3
100/
3
EM44CLS
60A/2P(40A)
60A/2P(50A)
WP60/3
30A/2P(25A)
480V10KVA 60A/3P PMS240/120V
EXISTING PULL BOX
NOTE: DARK LINE WEIGHT REPRESENTS NEW WORK.
"MTS2-LS"
100
"MTS1-LS"
UPSBYPASS
PBXUPS
EM43MORGUE
TO "LS"
E128ACB(LAB)
N96A N95A
EM6A FGA
SHAFTDAMPERS
ELEV.MACHINERM
ELEV.COND.UNIT
A/C
20A/2P(20A)
T31000 KVA12,470V TO480V - 3PH - 3W
T21500 KVA12,470V TO280Y/120V - 3PH - 4W
T12000KVA12,470V TO480V - 3PH - 3W
T11KVA
V TOV - 3PH - 3W
400/3
(400A)
400/3(250A)
400/3(300A)
480� TO480/277V500 KVA 6.69%
TRANSFORMERTAP
TS-1
200/3(200A)
EMX1
EMP1
E82EB
200/3(200A)
E84-CB (EM8)
E
E87-CB
E
1525
1500
�
XXX
HV2
� �
XXX
U1
UG
U3
C2
C1
HV1
XXX
TO PSC-2 TO PSC-2
1725
2315
1400
1427
1518
1725
1725
2435
2435
1616
2529
2517
2517
4653
4542
4504
4542
3419
DP3 ()1600A - 208Y/120V-3PH-4W
DP2 ()1600A - 208Y/120V-3PH-4W
DP1 ()1000A - 480V-3PH-4W
DP16 ()A - 480V-3PH-3W
DP4 ()800A - 480V-3PH-3W
DP5 ()800A - 208Y/120V-3PH-4W
DP15 ('71 BLDG. BASEMENT,OFFICE NEAR ROOM 5)A - 480V-3PH-3W
DP6 (RM 3403)800A - 208Y/120V-3PH-4W
US2 ()3000A - 208Y/120V-3PH-4W
US3 ()1600A - 480V-3PH-3W
US1 ()2000A - 480V-3PH-3W
SEVENTH
SIXTH SIXTH
FIFTH FIFTH
FOURTH FOURTH
THIRD THIRD
SECOND SECOND
FIRST FIRST
BSMNT BSMNT
ROOF
SCALE:
1
2
3
4
���������
����
��� ���
����
����������
��������
� !�� " ������� "
� " ���� ��#��$%�$ �
���������
������������� ��������������
��� �
�� ������������ �
���"%$����&�����$����#"� ' (����)*+"�,,,"�---+���.�/�)*+"�,,,"�01)*,-2��"��"�����������������3��(���0402,
Heapy Project No. 2018-05176.01
�����������
������
����� ���
3/32" = 1'-0"
D.E002
ELECTRICAL SINGLE LINEDIAGRAM
July 5, 2018
KMU
LLC
1 PROVIDE NEW 60A/3P BREAKER.
2 4-#6, 1-#10 GRD. IN 1.25" CONDUIT.
3 UTILIZE SPARE 200A FUSIBLE SWITCH ANDPROVIDE NEW 200A FUSING (LPS-RK).
4 3-#3/0, 1-#6 GRD. IN 2" CONDUIT.
����
�����
�
�
�
�
T
T
T
46 46
����
�����
�
�
�
�
T
T
T
46 46
7 9 10 12 13
D
E
G
8
F
AHU-8E87A
-CB
E87-
CB
N80A
E44-
LSN80
E195
-CB
DP-6
EMP1
2
3
14 15
7 9 10 12 13
D
E
G
8
F
1
E233-EB
E87A
-CB
E87-
CB
E44-
LS
N80A N8
0
E195
-CB
DP-6
EMP1
14 15
-MECH.
4
� �������
������
�������
����
����������
��������
!"��!# �������!#
�!# ���� ��$��%&�%!�
���������
������������� ��������������
��� �
�� ������������ �
���#&%����'�����%����$#�!(�)�����*+,#�---#�...,���/���*+,#�---#�01*+-.2��#���#����������������3��)���0402-
Heapy Project No. 2018-05176.01
�����������
������
����� ���
3/16" = 1'-0"
D.E103
PARTIAL THIRD FLOOR -ELECTRICAL PLANS
July 5, 2018
KMU
LLC
SCALE: 3/16" = 1'-0"
PARTIAL THIRD FLOOR - ELECTRICAL DEMOLITION PLAN1
SCALE: 3/16" = 1'-0"
PARTIAL THIRD FLOOR - ELECTRICAL DEMOLITION PLAN2
1 APPROXIMATE LOCATION OF SHAFT FROMGROUND FLOOR TO LEVEL 3. UTILIZE SPARE2" CONDUIT INSTALLED UNDER PREVIOUSPHASE.
2 EXISTING VFD'S REMOVED BY HC. EC SHALLDISCONNECT AND REMOVE CIRCUITS BACKTO SOURCE (EMP1).
3 EXISTING AHU-8 SHALL BE REMOVED BY HC.EC SHALL DISCONNECT AND REMOVE ALLASSOCIATE ELECTRICAL AND FIRE ALARMCONNECTIONS.
4 COORDINATE EXACT LOCATION OF PANELWITH OWNER.
DN
3
4
DN
DN
3
4
DN
J
GF
J
S
S
AP
J
J
J
J
WP/GF
P
WP/GF
WP/GF
J
7 9 10 12 13
D
E
G
8
F
2
19
14 15
14
7 9 10 12
D
E
G
F
7
8
412
9
W P
5
6
9
13
TYP.5
10
11
10
13
1
E233
-EB
- 8,1
0,12
E233
-EB
- 14,
16,1
8
AHU8-RF AHU8-RF
E234-CB
E234-CB - 5
E234-CB - 1E234-CB - 1
E234-CB - 1
E234-CB - 1
E234-CB - 1
E234-CB - 2
E234-CB - 16
E234-CB - 6
E234-CB - 1
E234-CB - 1
E234-CB - 3
E233
-EB
- 2,4
,6
AHU8-RF
E233
-EB
- 26,
28,3
0
E233
-EB
- 32,
34,3
6
AHU8-RF AHU8-RF
E233
-EB
- 20,
22,2
4
AHU8-RF
3
E233-EB - 38,40,42
14 15
-AH8 VEST.
17
17
18
EF-8
14
E234-CB - 4P-1
19
E233
-EB
- 7,9
,11
E233
-EB
- 13,
15,1
7
AHU8-SF AHU8-SF
E233
-EB
- 1,3
,5
AHU8-SF
E233
-EB
- 25,
27,2
9
E233
-EB
- 31,
33,3
5
AHU8-SF AHU8-SF
E233
-EB
- 19,
21,2
3
AHU8-SF
20 E234-CB - 7
20 E234-CB - 9
20 E234-CB - 11
20 E234-CB - 13
16 1
E234-CB - 3
11
11
E234-CB - 2
E234-CB - 2E234-CB - 2
E234-CB - 15
21
E234-CB - 1
E234-CB - 1
E234-CB - 1
E234-CB - 1
22
5E234-CB - 5
a
a
a
b
b
b
b
c c
c
AH-8
c
c
c
c
8
���������
����
��� ���
����
����������
��������
� !�� " ������� "
� " ���� ��#��$%�$ �
���������
������������� ��������������
��� �
�� ������������ �
���"%$����&�����$����#"� ' (����)*+"�,,,"�---+���.�/�)*+"�,,,"�01)*,-2��"��"�����������������3��(���0402,
Heapy Project No. 2018-05176.01
�����������
������
����� ���
3/16" = 1'-0"
D.E104
PARTIAL FOURTH FLOOR- ELECTRICAL PLANS
July 5, 2018
KMU
LLC
NOTES1 MAKE ELECTRICAL CONNECTION TO UV LIGHT
CONTROL PANEL, SWITCH, STARTER.
2 EXISTING EXHAUST FAN SHALL BE REMOVED BYHC. EC SHALL DISCONNECT AND REMOVECIRCUIT BACK TO SOURCE.
3 8'-0" WIDE SERVICE VESTIBULE.
4 PROVIDE SWITCH WITH PILOT LIGHT FOR AHUEXTERIOR LIGHTING.
5 JELLY JAR LUMINAIRE FURNISHED BY AHUMANUFACTURER, INSTALLED BY EC.
6 UNIT HEATER, DISCONNECT ANDINTERCONNECTING WIRING PROVIDED BY AHUMANUFACTURER. EC SHALL PROVIDE SINGLEPOINT CONNECTION TO LINE SIDE OFDISCONNECT.
7 FACTORY INSTALLED SUPPLY FAN ARRAYVARIABLE SPEED DRIVES. PROVIDE SINGLE POINTCONNECTION TO LINE SIDE OF EACH VFD.INTERCONNECTING WIRING BETWEEN VFD ANDMOTOR SHALL BE DONE BY THE AHUMANUFACTURER.
8 FACTORY INSTALLED RETURN FAN ARRAYVARIABLE SPEED DRIVES. PROVIDE SINGLE POINTCONNECTION TO LINE SIDE OF EACH VFD.INTERCONNECTING WIRING BETWEEN VFD ANDMOTOR SHALL BE FACTORY INSTALLED.
9 AHU SHALL BE SHIPPED IN 3 PIECES AND SHALLBE CONNECTED IN THE FIELD. EC SHALLCONNECT ALL INTERNAL CIRCUITS. UTILIZELIQUID TIGHT CONDUIT. COORDINATE WITH HC.
10 PROVIDE CONNECTION TO AHU8 INTERIORLIGHTING CIRCUIT.
11 CONVENIENCE RECEPTACLE PROVIDED BY AHUMANUFACTURER. EC SHALL PROVIDE CIRCUIT.
12 PROVIDE 120V CONTROL CIRCUIT TO NEW DDCPANEL.
13 SERVICE VESTIBULE LIGHT SWITCH PROVIDED BYAHU MANUFACTURER.
14 EXISTING CONDENSING UNIT FOR DATA CLOSETSHALL BE RELOCATED BY HC. EC SHALLDISCONNECT AND EXTEND CIRCUIT TO NEWLOCATION. MATCH EXISTING CONDUCTOR SIZES.
16 ROOF PENETRATIONS FOR CONDUIT SHALL BEMINIMUM 6'-8" AWAY FROM THE FACE OF THECOLUMNS. REBAR SHALL NOT BE CUT. XRAY SLABTO AVOID REBAR. COORDINATE WITHSTRUCTURAL ENGINEER.
17 PROVIDE SPEAKER WIRING IN CONDUITCONNECTED TO PUBLIC ADDRESS SYSTEMBELOW. COORDINATE WITH OWNER.
18 PROVIDE RACEWAY FROM ABOVE CEILING ONLEVEL 4 FOR WIRELESS ACCESS POINT ASSHOWN. NETWORK CABLING AND HARDWARE BYOWNER.
19 EXISTING EXHAUST FAN SHALL BE REPLACED BYHC. EC SHALL DISCONNECT EXISTING EXHAUSTFAN AND PROVIDE CONNECTION TO NEWEXHAUST FAN. EXISTING STARTER SHALL BEUTILIZED. PROVIDE NEW NEMA 3R DISCONNECTNEAR EXHAUST FAN.
20 PROVIDE 120V CONNECTION TO HEAT TRACE.COORDINATE WITH HC.
21 PROVIDE POWER CONNECTION FOR HUMIDIFIERCONTROLLER, FURNISHED BY AHUMANUFACTURER.
22 AHU MAUFACTURER PROVIDED CDQ CONTROLS,EC TO PROVIDE POWER CONNECTION.
SCALE: 3/16" = 1'-0"
PARTIAL FOURTH FLOOR - ELECTRICAL DEMOLITION PLAN1
SCALE: 3/16" = 1'-0"
PARTIAL FOURTH FLOOR - ELECTRICAL NEW WORK PLAN2