RQCEQ-P
E E D E N 1 0 - 2 0 2
Air Conditioners
Replacement VR V®
Technical Data
RQCEQ-P_EN.pdf 1 2/07/2010 10:39:04
RQCEQ-P
E E D E N 1 0 - 2 0 2
Air Conditioners
Replacement VR V®
Technical Data
RQCEQ-P_EN.pdf 2 2/07/2010 10:39:19
• VRV® Systems • Outdoor Unit 1
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
TABLE OF CONTENTSRQCEQ-P
1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Technical Specifications system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Electrical Specifications system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Technical Specifications module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2 Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Cooling Capacity Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Heating Capacity Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Capacity Correction Factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
5 Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
6 External connection diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56External Connection Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
7 Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58Operation Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
RQCEQ-P_EN.pdf 3 2/07/2010 10:39:19
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
• VRV® Systems • Outdoor Unit2
1 Specifications
Outdoor Uni VRV Systems RQCEQ-P Replacement1-1 Technical Specifications system RQCEQ280PY1 RQCEQ360PY1 RQCEQ460PY1 RQCEQ500PY1 RQCEQ540PY1
System Outdoor unit module 1 RQEQ140P RQEQ180P RQEQ140P RQEQ180POutdoor unit module 2 RQEQ140P RQEQ180P RQEQ140P RQEQ180POutdoor unit module 3 - RQEQ180P
Cooling capacity Nom. kW 28.0 (1) 36.0 (1) 45.0 (1) 50.0 (1) 54.0 (1)Heating capacity Nom. kW 32.0 (2) 40.0 (2) 52.0 (2) 56.0 (2) 60.0 (2)Power input - 50Hz Cooling Nom. kW 7.04 10.3 12.2 13.9 15.5
Heating Nom. kW 8.00 10.7 13.4 14.7 16.1EER 3.98 3.48 3.77 3.61 3.48COP 4.00 3.72 3.89 3.80 3.72Maximum number of connectable indoor units 16 20 26 29 33Capacity range HP 10 13 16 18 20Indoor index connection
Min. 14.0 18.0 23.0 25.0 27.0Max. 36.4 46.2 59.8 65.0 70.2
Casing Colour Ivory white (Munsell code: 5Y7.5/1)Operation range Cooling Standa
rdMin. °CDB -5
Max. °CDB 43Heating Min. °CWB -20
Max. °CWB 15.5Sound pressure level Cooling Nom. dBA 57 61 62 63Refrigerant Type R-410A
Control Electronic expansion valveCircuits Quantity 1
Piping connections Liquid Type Braze connectionOD mm 9.52 12.7 15.9
Gas Type Braze connectionOD mm 22.2 25.4 28.6
Discharge gas Type Braze connectionOD mm 19.1 22.2
Total piping length System Actual m 300Level difference OU - IU Outdoor
unit in highest position
m 50
1-1 Technical Specifications system RQCEQ636PY1 RQCEQ712PY1 RQCEQ744PY1 RQCEQ816PY1 RQCEQ848PY1
System Outdoor unit module 1 RQEQ212P RQEQ140P RQEQ180P RQEQ212POutdoor unit module 2 RQEQ212P RQEQ180P RQEQ212POutdoor unit module 3 RQEQ212P RQEQ180P RQEQ212POutdoor unit module 4 - RQEQ212P
Heating capacity Nom. kW 67.2 (2) 78.4 (2) 80.8 (2) 87.2 (2) 89.6 (2)Power input - 50Hz Heating Nom. kW 17.7 20.7 21.2 23.1 23.6EER 2.90 3.36 3.19 3.01 2.90COP 3.79 3.80 3.81 3.77 3.79Maximum number of connectable indoor units 36 40 43 47 50Capacity range HP 22 24 26 28 30Indoor index connection
Min. 31.8 35.6 37 40.8 42.4Nom. -Max. 82.7 92.6 96.7 106 110
Casing Colour Ivory white (Munsell code: 5Y7.5/1)Operation range Cooling Standar
dMin. °CDB -5
Max. °CDB 43Heating Min. °CWB -20
Max. °CWB 15.5Sound pressure level Cooling Nom. dBA 64 63 64 65 66
RQCEQ-P_EN.pdf 4 2/07/2010 10:39:20
• VRV® Systems • Outdoor Unit 3
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
1 Specifications
Refrigerant Type R-410AControl Electronic expansion valveCircuits Quantity 1
Piping connections Liquid Type Braze connectionOD mm 15.9 19.1
Gas Type Braze connectionOD mm 28.6 34.9
Discharge gas Type Braze connectionOD mm 25.4 28.6
Total piping length System Actual m 300Level difference OU - IU Outdoor
unit in highest position
m 50
1-2 Electrical Specifications system RQCEQ280PY1 RQCEQ360PY1 RQCEQ460PY1 RQCEQ500PY1 RQCEQ540PY1
Current - 50Hz Minimum circuit amps (MCA) A 23.8 34.5 41.0 46.4 51.7Maximum fuse amps (MFA) A 30 40 50 60Total overcurrent amps (TOCA) A 31.2 46.8
Power supply Name Y1Phase 3~Frequency Hz 50Voltage V 400
Voltage range Min. % -10Max. % 10
Notes Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
1-2 Electrical Specifications system RQCEQ636PY1 RQCEQ712PY1 RQCEQ744PY1 RQCEQ816PY1 RQCEQ848PY1
Current - 50Hz Minimum circuit amps (MCA) A 55.5 64.9 66.1 72.7 74.0Maximum fuse amps (MFA) A 70 80 90Total overcurrent amps (TOCA) A 46.8 62.4
Power supply Name Y1Phase 3~Frequency Hz 50Voltage V 400
Voltage range Min. % -10Max. % 10
Notes Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
TOCA means the total value of each OC set.MSC means the maximum current during start up of the compressor
Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.Select wire size based on the larger value of MCA or TOCA
MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
1-1 Technical Specifications system RQCEQ636PY1 RQCEQ712PY1 RQCEQ744PY1 RQCEQ816PY1 RQCEQ848PY1
RQCEQ-P_EN.pdf 5 2/07/2010 10:39:20
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
• VRV® Systems • Outdoor Unit4
1 Specifications
1-3 Technical Specifications module RQEQ140PY1 RQEQ180PY1 RQEQ212PY1
Capacity control % 25 ~ 100 21 ~ 100Casing Colour Ivory white (Munsell code: 5Y7.5/1)Dimensions Unit Height mm 1,680
Width mm 635Depth mm 765
Weight Unit kg 175 179Heat exchanger Type Cross fin coilFan Type Propeller fanOperation range Cooling Standar
dMin. °CDB -5
Max. °CDB 43Heating Min. °CWB -20
Max. °CWB 15Sound power level Cooling Nom. dBA -Sound pressure level Cooling Nom. dBA 54 58 60Compressor Quantity 1
Type Hermetically sealed scroll compressorPiston displacement m³/h 13.34 15.75 16.89Speed rpm 6,300 7,440 7,980Output W 2,800 3,300 3,600Starting method Soft start
Refrigerant Type R-410ACharge kg 10.3 10.6 11.2Control Electronic expansion valveCircuits Quantity 1
Piping connections Liquid Type Braze connectionOD mm 9.52
Gas Type Braze connectionOD mm 15.9 19.1
Discharge gas Type Braze connectionOD mm 12.7 15.9
Defrost method DeicerFan motor Quantity 1
Drive Direct driveOutput W 350
1-4 Electrical Specifications RQEQ140PY1 RQEQ180PY1 RQEQ212PY1
Power supply Name Y1Phase 3~Frequency Hz 50Voltage V 380-415
Voltage range Min. % -10Max. % 10
Notes Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
TOCA means the total value of each OC set.MSC means the maximum current during start up of the compressor
Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.Select wire size based on the larger value of MCA or TOCA
MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
RQCEQ-P_EN.pdf 6 2/07/2010 10:39:20
• VRV® Systems • Outdoor Unit 5
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
2 Electrical data2 - 1 Electrical Data
RQCEQ-P_EN.pdf 7 2/07/2010 10:39:20
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
• VRV® Systems • Outdoor Unit6
3 Options3 - 1 OptionsRQCEQ-P
3D066354
Series VRV III - Q
Model
Option name
RQCEQ280P RQCEQ460P RQCEQ540P RQCEQ712PRQCEQ360P RQCEQ500P RQCEQ636P RQCEQ744P
RQCEQ816PRQCEQ848P
Cool/heater selectorFixing box KJB11ADistributive Refnet header KHRQ23M29H KHRQ23M29Hpiping KHRQ23M64H KHRQ23M64H
KHRQ23M75HRefnet joint KHRQ23M20T KHRQ23M20T
KHRQ23M29T9 KHRQ23M29T9KHRQ23M64T KHRQ23M64T
KHRQ23M75TPipe size reducerOutdoor unit multi BHFP26P36C BHFP26P63C BHFP26P84CConnection piping kit
RQCEQ-P_EN.pdf 8 2/07/2010 10:39:20
• VRV® Systems • Outdoor Unit 7
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
4 Capacity tables4 - 1 Cooling Capacity Tables
RQCEQ-P_EN.pdf 9 2/07/2010 10:39:20
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
• VRV® Systems • Outdoor Unit8
4 Capacity tables4 - 1 Cooling Capacity Tables
RQCEQ-P_EN.pdf 10 2/07/2010 10:39:21
• VRV® Systems • Outdoor Unit 9
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
4 Capacity tables4 - 1 Cooling Capacity Tables
RQCEQ-P_EN.pdf 11 2/07/2010 10:39:21
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
• VRV® Systems • Outdoor Unit10
4 Capacity tables4 - 1 Cooling Capacity Tables
RQCEQ-P_EN.pdf 12 2/07/2010 10:39:21
• VRV® Systems • Outdoor Unit 11
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
4 Capacity tables4 - 1 Cooling Capacity Tables
RQCEQ-P_EN.pdf 13 2/07/2010 10:39:22
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
• VRV® Systems • Outdoor Unit12
4 Capacity tables4 - 1 Cooling Capacity Tables
RQCEQ-P_EN.pdf 14 2/07/2010 10:39:22
• VRV® Systems • Outdoor Unit 13
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
4 Capacity tables4 - 1 Cooling Capacity Tables
RQCEQ-P_EN.pdf 15 2/07/2010 10:39:22
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
• VRV® Systems • Outdoor Unit14
4 Capacity tables4 - 1 Cooling Capacity Tables
RQCEQ-P_EN.pdf 16 2/07/2010 10:39:23
• VRV® Systems • Outdoor Unit 15
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
4 Capacity tables4 - 1 Cooling Capacity Tables
RQCEQ-P_EN.pdf 17 2/07/2010 10:39:23
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
• VRV® Systems • Outdoor Unit16
4 Capacity tables4 - 1 Cooling Capacity Tables
RQCEQ-P_EN.pdf 18 2/07/2010 10:39:23
• VRV® Systems • Outdoor Unit 17
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
4 Capacity tables4 - 1 Cooling Capacity Tables
RQCEQ-P_EN.pdf 19 2/07/2010 10:39:24
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
• VRV® Systems • Outdoor Unit18
4 Capacity tables4 - 1 Cooling Capacity Tables
RQCEQ-P_EN.pdf 20 2/07/2010 10:39:24
• VRV® Systems • Outdoor Unit 19
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
4 Capacity tables4 - 1 Cooling Capacity Tables
RQCEQ-P_EN.pdf 21 2/07/2010 10:39:25
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
• VRV® Systems • Outdoor Unit20
4 Capacity tables4 - 1 Cooling Capacity Tables
RQCEQ-P_EN.pdf 22 2/07/2010 10:39:25
• VRV® Systems • Outdoor Unit 21
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
4 Capacity tables4 - 1 Cooling Capacity Tables
RQCEQ-P_EN.pdf 23 2/07/2010 10:39:25
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
• VRV® Systems • Outdoor Unit22
4 Capacity tables4 - 1 Cooling Capacity Tables
RQCEQ-P_EN.pdf 24 2/07/2010 10:39:26
• VRV® Systems • Outdoor Unit 23
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
4 Capacity tables4 - 1 Cooling Capacity Tables
RQCEQ-P_EN.pdf 25 2/07/2010 10:39:26
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
• VRV® Systems • Outdoor Unit24
4 Capacity tables4 - 1 Cooling Capacity Tables
RQCEQ-P_EN.pdf 26 2/07/2010 10:39:26
• VRV® Systems • Outdoor Unit 25
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
4 Capacity tables4 - 1 Cooling Capacity Tables
RQCEQ-P_EN.pdf 27 2/07/2010 10:39:27
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
• VRV® Systems • Outdoor Unit26
4 Capacity tables4 - 1 Cooling Capacity Tables
RQCEQ-P_EN.pdf 28 2/07/2010 10:39:27
• VRV® Systems • Outdoor Unit 27
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
4 Capacity tables4 - 2 Heating Capacity Tables
RQCEQ-P_EN.pdf 29 2/07/2010 10:39:28
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
• VRV® Systems • Outdoor Unit28
4 Capacity tables4 - 2 Heating Capacity Tables
RQCEQ-P_EN.pdf 30 2/07/2010 10:39:28
• VRV® Systems • Outdoor Unit 29
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
4 Capacity tables4 - 2 Heating Capacity Tables
RQCEQ-P_EN.pdf 31 2/07/2010 10:39:28
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
• VRV® Systems • Outdoor Unit30
4 Capacity tables4 - 2 Heating Capacity Tables
RQCEQ-P_EN.pdf 32 2/07/2010 10:39:29
• VRV® Systems • Outdoor Unit 31
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
4 Capacity tables4 - 2 Heating Capacity Tables
RQCEQ-P_EN.pdf 33 2/07/2010 10:39:29
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
• VRV® Systems • Outdoor Unit32
4 Capacity tables4 - 2 Heating Capacity Tables
RQCEQ-P_EN.pdf 34 2/07/2010 10:39:30
• VRV® Systems • Outdoor Unit 33
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
4 Capacity tables4 - 2 Heating Capacity Tables
RQCEQ-P_EN.pdf 35 2/07/2010 10:39:30
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
• VRV® Systems • Outdoor Unit34
4 Capacity tables4 - 2 Heating Capacity Tables
RQCEQ-P_EN.pdf 36 2/07/2010 10:39:31
• VRV® Systems • Outdoor Unit 35
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
4 Capacity tables4 - 2 Heating Capacity Tables
RQCEQ-P_EN.pdf 37 2/07/2010 10:39:31
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
• VRV® Systems • Outdoor Unit36
4 Capacity tables4 - 2 Heating Capacity Tables
RQCEQ-P_EN.pdf 38 2/07/2010 10:39:31
• VRV® Systems • Outdoor Unit 37
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
4 Capacity tables4 - 2 Heating Capacity Tables
TC: Total Capacity; PI Power Input: kW (Comp. + Outdoor fan motor)Indoor air temp. CDB
Combination(%)
Capacityindex (kW)
Outdoorair temp.
16.0 18.0 20.0 21.0 22.0 24.0TC PI TC PI TC PI TC PI TC PI TC PI
°CDB °CWB kW kW kW kW kW kW kW kW kW kW kW kW130 82.68 -19,8 -20,0 41,2 10,23 41,1 11,09 40,9 11,95 40,8 12,38 40,8 12,80 40,6 13,66
-18,8 -19,0 42,4 10,69 42,3 11,52 42,1 12,36 42,0 12,77 42,0 13,19 41,8 14,02-16,7 -17,0 44,8 11,54 44,7 12,32 44,5 13,10 44,5 13,49 44,4 13,88 44,2 14,67-13,7 -15,0 47,3 12,29 47,1 13,03 47,0 13,77 46,9 14,14 46,8 14,51 46,7 15,25-11,8 -13,0 49,7 12,96 49,5 13,66 49,4 14,36 49,3 14,72 49,2 15,07 49,1 15,77-9,8 -11,0 52,1 13,57 52,0 14,24 51,8 14,90 51,7 15,24 51,7 15,57 51,5 16,24-9,5 -10,0 53,3 13,85 53,2 14,50 53,0 15,15 52,9 15,48 52,9 15,81 52,7 16,46-8,5 -9,1 54,4 14,09 54,3 14,73 54,1 15,37 54,0 15,69 54,0 16,01 53,8 16,65-7,0 -7,6 56,2 14,48 56,1 15,09 55,9 15,71 55,9 16,02 55,8 16,33 55,6 16,94-5,0 -5,6 58,7 14,95 58,5 15,54 58,4 16,13 58,3 16,43 58,2 16,72 58,0 17,31-3,0 -3,7 61,0 15,36 60,8 15,93 60,7 16,50 60,6 16,78 60,5 17,06 60,3 17,630.0 -0,7 64,6 15,95 64,4 16,49 64,3 17,02 64,2 17,29 64,1 17,56 64,0 18,093,0 2,2 68,1 16,46 68,0 16,97 67,8 17,47 67,7 17,73 67,6 17,98 67,5 18,495,0 4,1 70,4 16,77 70,3 17,26 70,1 17,75 70,0 17,99 70,0 18,23 69,8 18,727,0 6,0 72,7 17,05 72,6 17,53 72,4 18,00 72,3 18,24 72,3 18,47 72,1 18,959,0 7,9 75,0 17,32 74,9 17,78 74,7 18,24 74,6 18,47 74,6 18,70 74,4 19,1511,0 9,8 77,3 17,57 77,2 18,02 77,0 18,46 76,9 18,68 76,9 18,91 76,1 19,1013,0 11,8 79,7 17,82 79,6 18,25 79,4 18,68 79,4 18,90 79,3 19,11 76,1 18,3815,0 13,7 82,0 18,05 81,9 18,46 81,7 18,88 81,7 19,09 81,6 19,30 76,1 17,75
120 76.32 -19,8 -20,0 41,0 11,39 40,9 12,18 40,7 12,97 40,7 13,37 40,6 13,76 40,4 14,55-18,8 -19,0 42,2 11,82 42,1 12,58 41,9 13,35 41,9 13,73 41,8 14,12 41,7 14,88-16,7 -17,0 44,6 12,59 44,5 13,32 44,4 14,04 44,3 14,40 44,2 14,76 44,1 15,48-13,7 -15,0 47,1 13,29 46,9 13,97 46,8 14,65 46,7 14,99 46,6 15,34 46,5 16,02-11,8 -13,0 49,5 13,91 49,3 14,56 49,2 15,21 49,1 15,53 49,1 15,85 48,9 16,50-9,8 -11,0 51,9 14,47 51,8 15,09 51,6 15,70 51,6 16,01 51,5 16,32 51,3 16,94-9,5 -10,0 53,1 14,73 53,0 15,33 52,8 15,94 52,8 16,24 52,7 16,54 52,6 17,14-8,5 -9,1 54,2 14,96 54,1 15,55 53,9 16,13 53,9 16,43 53,8 16,72 53,6 17,31-7,0 -7,6 56,0 15,31 55,9 15,88 55,7 16,45 55,7 16,73 55,6 17,02 55,5 17,59-5,0 -5,6 58,5 15,75 58,3 16,29 58,2 16,84 58,1 17,11 58,0 17,38 57,9 17,93-3,0 -3,7 60,8 16,13 60,6 16,65 60,5 17,18 60,4 17,44 60,3 17,70 60,2 18,220.0 -0,7 64,4 16,67 64,2 17,17 64,1 17,66 64,0 17,91 64,0 18,15 63,8 18,653,0 2,2 67,9 17,15 67,8 17,61 67,6 18,08 67,5 18,31 67,5 18,55 67,3 19,015,0 4,1 70,2 17,43 70,1 17,88 69,9 18,33 69,8 18,56 69,8 18,78 69,6 19,237,0 6,0 72,5 17,69 72,4 18,13 72,2 18,57 72,2 18,78 72,1 19,00 70,3 18,729,0 7,9 74,8 17,94 74,7 18,36 74,5 18,79 74,5 19,00 74,4 19,21 70,3 18,0111,0 9,8 77,1 18,17 77,0 18,58 76,8 18,99 76,8 19,20 75,5 18,90 70,3 17,3513,0 11,8 79,5 18,40 79,4 18,80 79,2 19,20 78,0 18,94 75,5 18,19 70,3 16,7115,0 13,7 81,8 18,61 81,7 19,00 80,6 19,02 78,0 18,29 75,5 17,56 70,3 16,14
110 69.96 -19,8 -20,0 40,8 12,55 40,7 13,27 40,5 14,00 40,5 14,36 40,4 14,72 40,3 15,45-18,8 -19,0 42,0 12,94 41,9 13,64 41,8 14,34 41,7 14,69 41,6 15,05 41,5 15,75-16,7 -17,0 44,4 13,65 44,3 14,31 44,2 14,98 44,1 15,31 44,0 15,64 43,9 16,30-13,7 -15,0 46,9 14,29 46,7 14,91 46,6 15,54 46,5 15,85 46,5 16,17 46,3 16,79-11,8 -13,0 49,3 14,86 49,2 15,45 49,0 16,05 49,0 16,34 48,9 16,64 48,8 17,23-9,8 -11,0 51,7 15,37 51,6 15,94 51,4 16,50 51,4 16,79 51,3 17,07 51,2 17,63-9,5 -10,0 52,9 15,61 52,8 16,16 52,7 16,72 52,6 16,99 52,5 17,27 52,4 17,82-8,5 -9,1 54,0 15,82 53,9 16,36 53,7 16,90 53,7 17,17 53,6 17,44 53,5 17,98-7,0 -7,6 55,8 16,14 55,7 16,67 55,6 17,19 55,5 17,45 55,4 17,71 55,3 18,23-5,0 -5,6 58,2 16,54 58,1 17,04 58,0 17,54 57,9 17,79 57,9 18,04 57,7 18,54-3,0 -3,7 60,5 16,89 60,4 17,37 60,3 17,85 60,2 18,09 60,2 18,33 60,0 18,810.0 -0,7 64,2 17,40 64,1 17,85 63,9 18,30 63,9 18,53 63,8 18,75 63,7 19,203,0 2,2 67,7 17,83 67,6 18,26 67,4 18,68 67,4 18,90 67,3 19,11 64,4 18,295,0 4,1 70,0 18,09 69,9 18,50 69,7 18,92 69,7 19,12 69,2 19,12 64,4 17,557,0 6,0 72,3 18,33 72,2 18,73 72,0 19,13 71,5 19,13 69,2 18,36 64,4 16,879,0 7,9 74,6 18,56 74,5 18,95 73,9 19,14 71,5 18,40 69,2 17,67 64,4 16,2411,0 9,8 76,9 18,77 76,8 19,15 73,9 18,43 71,5 17,72 69,2 17,03 64,4 15,6613,0 11,8 79,3 18,99 78,7 19,13 73,9 17,74 71,5 17,07 69,2 16,40 64,4 15,1015,0 13,7 81,6 19,18 78,7 18,46 73,9 17,14 71,5 16,49 69,2 15,85 64,4 14,60
100 63.60 -19,8 -20,0 40,6 13,70 40,5 14,36 40,4 15,02 40,3 15,35 40,2 15,68 40,1 16,34-18,8 -19,0 41,8 14,06 41,7 14,70 41,6 15,34 41,5 15,66 41,4 15,98 41,3 16,61-16,7 -17,0 44,2 14,71 44,1 15,31 44,0 15,91 43,9 16,21 43,9 16,51 43,8 17,12-13,7 -15,0 46,6 15,29 46,5 15,86 46,4 16,43 46,4 16,71 46,3 17,00 46,2 17,56-11,8 -13,0 49,1 15,81 49,0 16,35 48,8 16,89 48,8 17,16 48,7 17,43 48,6 17,97-9,8 -11,0 51,5 16,28 51,4 16,79 51,3 17,30 51,2 17,56 51,1 17,82 51,0 18,33-9,5 -10,0 52,7 16,49 52,6 16,99 52,5 17,50 52,4 17,75 52,4 18,00 52,2 18,50-8,5 -9,1 53,8 16,68 53,7 17,17 53,6 17,66 53,5 17,91 53,4 18,15 53,3 18,65-7,0 -7,6 55,6 16,98 55,5 17,45 55,4 17,93 55,3 18,16 55,3 18,40 55,1 18,88-5,0 -5,6 58,0 17,34 57,9 17,80 57,8 18,25 57,7 18,48 57,7 18,70 57,6 19,16-3,0 -3,7 60,3 17,66 60,2 18,10 60,1 18,53 60,0 18,75 60,0 18,97 58,6 18,730.0 -0,7 64,0 18,12 63,9 18,53 63,7 18,94 63,7 19,14 62,9 18,98 58,6 17,423,0 2,2 67,5 18,51 67,4 18,90 67,2 19,24 65,0 18,50 62,9 17,76 58,6 16,335,0 4,1 69,8 18,75 69,7 19,12 67,2 18,46 65,0 17,75 62,9 17,05 58,6 15,687,0 6,0 72,1 18,97 71,5 19,12 67,2 17,74 65,0 17,06 62,9 16,40 58,6 15,099,0 7,9 74,4 19,18 71,5 18,39 67,2 17,07 65,0 16,43 62,9 15,79 58,6 14,5411,0 9,8 75,8 19,01 71,5 17,72 67,2 16,46 65,0 15,84 62,9 15,23 58,6 14,0413,0 11,8 75,8 18,30 71,5 17,06 67,2 15,86 65,0 15,26 62,9 14,68 58,6 13,5415,0 13,7 75,8 17,67 71,5 16,48 67,2 15,33 65,0 14,76 62,9 14,20 58,6 13,10
RQCEQ636P
NOTES - ANMERKUNGEN - - NOTAS - REMARQUES - NOTE - OPMERKINGEN - - NOTLAR
1. is shown as reference. When selecting the unit models, avoid the Outdoor air tempera-ture range shown by .
dient als Verweis. Vermeiden Sie bei der Auswahl der Gerätemodelle den als marki-
erten Temperaturbereich der Außenluft
H . k ,
se muestra como referencia. Cuando seleccione los modelos de unidad, evite el intervalo
de temperaturas del aire exterior indicado mediante
est montré comme référence.Lors du choix des modèles d'unités, évitez la plage de températures de l'air extérieur illustré par
valori riportati unicamente come riferimento. Nel selezionare i modelli delle unità, non
considerare i valori di temperatura dell'aria esterna indicati con il colore
is als referentie getoond. Wanneer modellen van eenheden worden gekozen, vermijd dan het bereik van buitenluchttemperaturen geïllustreerd door
.
,
referans olarak gösterilmektedir. Ünite modellerini seçerken, belirtilen Dı hava sıcaklı ıaralı ından kaçının
2. The above table shows the average value of conditions which may occur.Die obige Tabelle zeigt den Durchschnittswert der Bedingungen, die auftreten können.
.La tabla de arriba muestra el valor medio de condiciones que pueden ocurrir.
Le tableau ci-dessus donne la valeur moyenne pour des conditions qui peuvent survenir.La tabella in alto mostra il valore delle condizioni medie che si possono riscontrare.
De tabel hierboven geeft de gemiddelde waarde aan van situaties die kunnen voorvallen.,
.
Yukarýdaki tablo meydana gelebilecek koþullarýn ortalama deðerini göstermektedir.
S100071
RQCEQ-P_EN.pdf 39 2/07/2010 10:39:32
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
• VRV® Systems • Outdoor Unit38
4 Capacity tables4 - 2 Heating Capacity Tables
RQCEQ-P_EN.pdf 40 2/07/2010 10:39:32
• VRV® Systems • Outdoor Unit 39
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
4 Capacity tables4 - 2 Heating Capacity Tables
RQCEQ-P_EN.pdf 41 2/07/2010 10:39:33
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
• VRV® Systems • Outdoor Unit40
4 Capacity tables4 - 2 Heating Capacity Tables
RQCEQ-P_EN.pdf 42 2/07/2010 10:39:33
• VRV® Systems • Outdoor Unit 41
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
4 Capacity tables4 - 2 Heating Capacity Tables
RQCEQ-P_EN.pdf 43 2/07/2010 10:39:33
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
• VRV® Systems • Outdoor Unit42
4 Capacity tables4 - 2 Heating Capacity Tables
RQCEQ-P_EN.pdf 44 2/07/2010 10:39:34
• VRV® Systems • Outdoor Unit 43
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
4 Capacity tables4 - 2 Heating Capacity Tables
RQCEQ-P_EN.pdf 45 2/07/2010 10:39:34
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
• VRV® Systems • Outdoor Unit44
4 Capacity tables4 - 2 Heating Capacity Tables
RQCEQ-P_EN.pdf 46 2/07/2010 10:39:35
• VRV® Systems • Outdoor Unit 45
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
4 Capacity tables4 - 2 Heating Capacity Tables
RQCEQ-P_EN.pdf 47 2/07/2010 10:39:35
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
• VRV® Systems • Outdoor Unit46
4 Capacity tables4 - 2 Heating Capacity Tables
RQCEQ-P_EN.pdf 48 2/07/2010 10:39:35
• VRV® Systems • Outdoor Unit 47
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
4 Capacity tables4 - 3 Capacity Correction Factor
RQCEQ-P_EN.pdf 49 2/07/2010 10:39:36
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
• VRV® Systems • Outdoor Unit48
4 Capacity tables4 - 3 Capacity Correction Factor
RQCEQ-P_EN.pdf 50 2/07/2010 10:39:36
• VRV® Systems • Outdoor Unit 49
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
4 Capacity tables4 - 3 Capacity Correction Factor
RQCEQ-P_EN.pdf 51 2/07/2010 10:39:36
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
• VRV® Systems • Outdoor Unit50
4 Capacity tables4 - 3 Capacity Correction Factor
RQCEQ-P_EN.pdf 52 2/07/2010 10:39:36
• VRV® Systems • Outdoor Unit 51
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
4 Capacity tables4 - 3 Capacity Correction Factor
RQCEQ-P_EN.pdf 53 2/07/2010 10:39:37
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
• VRV® Systems • Outdoor Unit52
4 Capacity tables4 - 3 Capacity Correction Factor
RQCEQ-P_EN.pdf 54 2/07/2010 10:39:37
• VRV® Systems • Outdoor Unit 53
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
5 Dimensional drawings5 - 1 Dimensional Drawings
RQCEQ-P_EN.pdf 55 2/07/2010 10:39:37
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
• VRV® Systems • Outdoor Unit54
5 Dimensional drawings5 - 1 Dimensional Drawings
RQCEQ-P_EN.pdf 56 2/07/2010 10:39:37
• VRV® Systems • Outdoor Unit 55
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
5 Dimensional drawings5 - 1 Dimensional Drawings
RQCEQ-P_EN.pdf 57 2/07/2010 10:39:38
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
• VRV® Systems • Outdoor Unit56
6 External connection diagrams6 - 1 External Connection Diagrams
E
RQCEQ-P_EN.pdf 58 2/07/2010 10:39:38
• VRV® Systems • Outdoor Unit 57
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
6 External connection diagrams6 - 1 External Connection Diagrams
RQCEQ-P_EN.pdf 59 2/07/2010 10:39:38
• Outdoor Unit • Replacement VRV® Heat Recovery • RQCEQ-P
• VRV® Systems • Outdoor Unit58
7 Operation range7 - 1 Operation Range
RQCEQ-P_EN.pdf 60 2/07/2010 10:39:39
Naamloze Vennootschap - Zandvoordestraat 300, B-8400 Oostende - Belgium - www.daikin.eu - BE 0412 120 336 - RPR Oostende EE
DE
N1
0-2
02
• C
D •
07
/10
• C
op
yri
gh
t D
aik
in
Th
e p
rese
nt
pu
blic
ati
on
su
pe
rse
de
s E
ED
EN
09
-20
2
Pre
par
ed
in B
elg
ium
by
Lan
no
o (
ww
w.la
nn
oo
pri
nt.
be
), a
com
pan
y w
ho
se c
on
cern
for
the
en
viro
nm
en
t is
se
t in
th
e E
MA
S an
d IS
O 1
40
01
sys
tem
s.
Re
spo
nsi
ble
Ed
ito
r: D
aik
in E
uro
pe
N.V
., Z
an
dv
oo
rde
stra
at
30
0,
B-8
40
0 O
ost
en
de
Daikin products are distributed by:
Daikin’s unique position as a manufacturer of air
conditioning equipment, compressors and refrigerants
has led to its close involvement in environmental issues.
For several years Daikin has had the intention to become
a leader in the provision of products that have limited
impact on the environment. This challenge demands the
eco design and development of a wide range of products
and an energy management system, resulting in energy
conservation and a reduction of waste.
VRV® products are not within the scope of the Eurovent
certification programme.
The present publication is drawn up by way of information only and does not constitute an offer binding
upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this publication to the best of its
knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for
particular purpose of its content and the products and services presented therein. Specifications are subject
to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect
damage, in the broadest sense, arising from or related to the use and/or interpretation of this publication. All
content is copyrighted by Daikin Europe N.V..
RQCEQ-P_EN.pdf 61 2/07/2010 10:39:41