En-1 AIR CONDITIONER OPTIONAL PARTS External connect kit PART NO. 9319446004 INSTALLATION MANUAL For authorized service personnel only. 1. SAFETY PRECAUTIONS WARNING This mark indicates procedures which, if improperly performed, might lead to the death or serious injury of the user. When installing each wire, please thoroughly read this manual. Before installation be sure that all sources of power have been shut off. There is a danger of electric shock. For input/output, use the voltage as described in the signal specifications. Using voltage of other specifications may result in malfunction and erroneous operation of the airconditioner. CAUTION This mark indicates procedures which, if improperly performed, might possibly result in personal harm to the user, or damage to property. Do not pull on the connectors with too much force. 2. ABOUT THE UNIT 2. 1. Main Unit & Accessories • The following installation parts are supplied. Use them as required. Name and Shape Q’ty Application Installation manual 1 This manual Wire (External input): Orange / Yellow 1 For connect to External device for input. Wire (External output): Blue / Purple 1 For connect to External device for operation status output. Wire (External output): Red / White 1 For connect to External device for error status output. Binder clamp 1 For fixing the binder. Binder 1 For fixing the wires. Screw 1 For fixing the binder clamp. 3. SETTING 3. 1. External Input 3. 1. 1. Control Input (Operation/Stop or Forced stop) • The air conditioner can be remotely operated by means of the following on-site work. "Operation/Stop" mode or "Forced stop" mode can be selected with function setting of indoor unit. Circuit diagram example Indoor unit PC board of communication kit Connector Orange Yellow Connected unit Ex.) Switch 10m * Signal Field supply * Make the distance from the PC board to the connected unit within 10m. Contact capacity : 24VDC or more, 10mA or more. ● When function setting is "Operation/Stop" mode Input signal Indoor unit OFF Stop ON Operation ● When function setting is "Forced stop" mode Indoor unit Input signal Command Remote controller Remote control operation invalidity Normal Stop OFF Forced stop Operation ON ON ON ON NOTE • Operation mode, temperature, and airflow cannot be set by external input. Use the remote controller to set. • If the air conditioner is activated by external input, it will operate in the settings before stop. To change the settings, use the remote controller.

Upload: others

Post on 30-Mar-2020

19 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: AIR CONDITIONER 3. SETTING 3. 1. External Input ...IM) UTY-XWZXZ5.… · AIR CONDITIONER OPTIONAL PARTS External connect kit PART NO. 9319446004 INSTALLATION MANUAL For authorized

En-1

AIR CONDITIONEROPTIONAL PARTSExternal connect kit

PART NO. 9319446004

INSTALLATION MANUALFor authorized service personnel only.

1. SAFETY PRECAUTIONS

WARNING This mark indicates procedures which, if improperly performed, might lead to the death or serious injury of the user.

When installing each wire, please thoroughly read this manual.

Before installation be sure that all sources of power have been shut off. There is a danger of electric shock.

For input/output, use the voltage as described in the signal specifications. Using voltage of other specifications may result in malfunction and erroneous operation of the airconditioner.

CAUTIONThis mark indicates procedures which, if improperly performed, might possibly result in personal harm to the user, or damage to property.

Do not pull on the connectors with too much force.

2. ABOUT THE UNIT

2. 1. Main Unit & Accessories

• The following installation parts are supplied. Use them as required.

Name and Shape Q’ty Application

Installation manual

1

This manual

Wire (External input): Orange / Yellow

1

For connect to External device for input.

Wire (External output): Blue / Purple

1

For connect to External device for operation status output.

Wire (External output): Red / White

1

For connect to External device for error status output.

Binder clamp

1

For fixing the binder.

Binder

1

For fixing the wires.

Screw

1

For fixing the binder clamp.

3. SETTING

3. 1. External Input

3. 1. 1. Control Input (Operation/Stop or Forced stop)

• The air conditioner can be remotely operated by means of the following on-site work. "Operation/Stop" mode or "Forced stop" mode can be selected with function setting of indoor unit.

Circuit diagram example

Indoor unitPC board of

communication kit

Connector

Orange

Yellow

Connected unit

Ex.) Switch

10m *

Signal

Field supply

* Make the distance from the PC board to the connected unit within 10m.Contact capacity : 24VDC or more, 10mA or more.

● When function setting is "Operation/Stop" mode

Input signal

Indoor unit

OFF

Stop

ON

Operation

● When function setting is "Forced stop" mode

Indoor unit

Input signal

Command

Remote controller

Remote control operation invalidity

Normal

Stop

OFF

Forced stop

Operation

ON

ON ON ON

NOTE• Operation mode, temperature, and airflow cannot be set by external input. Use the

remote controller to set.

• If the air conditioner is activated by external input, it will operate in the settings before stop. To change the settings, use the remote controller.

9319446004_UTY-XWZXZ5_IM.indd 1 2011/03/18 19:21:03

Page 2: AIR CONDITIONER 3. SETTING 3. 1. External Input ...IM) UTY-XWZXZ5.… · AIR CONDITIONER OPTIONAL PARTS External connect kit PART NO. 9319446004 INSTALLATION MANUAL For authorized

En-2

3. 2. External Output

3. 2. 1. Operation Status Output

• An air conditioner operation status signal can be output.

Circuit diagram example

Indoor unitPC board of

communication kit

ConnectorBlue

Purple

Connected unit

Ex.) Relay unit~24V DC Ex.) Display

Relay Power supply

10m *

Signal

Field supply

* Make the distance from the PC board to the connected unit within 10m. Relay spec. : Max.24V DC, 10mA to less than 500mA.

Indoor unit

Output signal

Stop

OFF

Operation

ON

NOTE

• Only operation and stop signals will be output. Use the remote controller to check the operation mode, temperature, and airflow.

3. 2. 2. Error Status Output

• An air conditioner condition normal/error status signal can be output.

Circuit diagram example

Indoor unitPC board of

communication kit

ConnectorRed

White

Connected unit

Ex.) Relay unit~24V DC Ex.) Display

Relay Power supply

10m *

Signal

Field supply

* Make the distance from the PC board to the connected unit within 10m. Relay spec. : Max.24V DC, 10mA to less than 500mA

Error status

Output signal

Normal

OFF

Error

ON

NOTE

• Only error signals will be output. Check the error information on the display area of the main unit.

4. CONNECTING TO INDOOR UNIT

• Connect the connector to the board of the air-conditioner. To connect to the air-conditioner, refer to the installation manual of the air-conditioner.

• Connect the tip of the wire to the external equipment. If necessary, extend it with locally procured wire.

• Ensure that the connecting part is insulated for protection.

9319446004_UTY-XWZXZ5_IM.indd 2 2011/03/18 19:21:03