ae303 footing design presentation part 1

Upload: ethan-brotzman

Post on 07-Jul-2018

215 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/18/2019 AE303 Footing Design Presentation Part 1

    1/12

    Footing Design procedure

    Definition

    Footings are structural members used to

    support columns and walls and distribute

    their loads to the soil in such a way that:

    1) The load bearing capacity of the soil is

    not exceeded,

    2) Excessive settlement, differential

    settlement, and rotation are prevented

    3) The footing itself can carry the shears

    and moments applied to it.

    Footing – Bearing Capacity 

    Every soil has a bearing capacity.

    These capacities are either

    assumed “presumptive” or

    calculated by the geotechnical

    engineer. A geotechnical engineer

    typically does soil borings to find

    the subsurface properties. The

    recommendations from this

    investigation are presented in a

    “Soils Report”.

    Soil bearing capacity and settlement areaffected by the type of soil

    (cohesive, cohesionless), the

    density of the soil, and the location

    of the water table.

  • 8/18/2019 AE303 Footing Design Presentation Part 1

    2/12

    Footing – Bearing Capacity 

    Sometimes, especially for small jobs, the structural engineer will elect to use

    presumptive bearing capacities. There are many sources for these, here is

    one example..

    Footing – Bearing Capacity The bearing capacity and settlement characteristics of the soil can be improved by compaction

    and surcharging. This is most useful for shallow foundations (those near the surface).

  • 8/18/2019 AE303 Footing Design Presentation Part 1

    3/12

    Footing – Bearing Capacity 

    The decision as to the type of foundation to use is a decision jointly made by

    the client, the structural engineer, and the geotech. Some risks may be

    taken to avoid costly deep foundation work.

    On Shallow Footings

    On Deep Foundations (Piles)

    Footing – Bearing Capacity All footings are sized (length and width) based on the actual loads and

    the soil’s bearing capacity.

    For example: Assume the load from a column is 40K Dead Load and 60 K

    Live Load, and that the allowable soil bearing capacity is 2.5 K/SqFt.

    Assuming there is no moment, the footing area would have to be:

    100 K / 2.5 Ksf = 40 Sq Ft.

    Based on this area, we could design a footing 6’-4” long by 6’-4” wide,

    or 10’ long by 4’ wide or any other combination of length and width

    that gives a bearing area of 40 Sq.Ft or more.

    The important thing to remember is that the loads were not factored for thisstep. When it comes time to “design” the footing (calculate thickness

    and rebars) we need to factor the loads.

    footingof area

     P actualallowable  ≤q footingof area

     P factoredultimate =q

  • 8/18/2019 AE303 Footing Design Presentation Part 1

    4/12

    Differential Settlement 

    To reduce differential settlement, size all footings

    proportionally to carry the full dead load and an equalpercentage of live load

     Distribution of Soil Pressure

    When the column load P is

    applied on the centroid of the

    footing, a uniform pressure is

    assumed to develop in the soil

    surface below the footing area.

    If a moment is applied, or the

    column is not centered on the

    footing, the soil pressure will not

    be uniform.

    The maximum soil pressure

    must be less than the allowable.

    The minimum soil pressure

    must be greater than zero.

  • 8/18/2019 AE303 Footing Design Presentation Part 1

    5/12

    Footings can have eccentric loads and moments due to errors in

    construction and / or unequal column loads, this is especially true forfootings that carry multiple columns (combined footings).

    Sizing of Footings, for Axial load and Moment

    Strength design requirements

    3^**12 / 1

    2 / * 

     Lb

     L M 

    b*L

    Pq

      factored  factored  factored    +≤

    3^**12 / 1

    2 / *allowable

     Lb

     L M 

    b*L

    Pq   actualactual +≤

    These equations are only valid up to condition c,

    For condition d, two simultaneous equations

    must be solved.

  • 8/18/2019 AE303 Footing Design Presentation Part 1

    6/12

    Types of Footings

     Isolated or single spread

     footings are used to support

    single columns. This is one

    of the most economical

    types of footings and is

    used when columns are

    spaced at relatively long

    distances. A square footing

    is normally the most cost

    effective from a concrete

    and reinforcing bar point of

    view.

    Types of FootingsCombined footings support

    two or more columns.

    Combined footings are used

    when columns are so close

    that single footings would

    overlap. They are also used or

    when one column is located at

    or near a property line. They

    can be rectangular ortrapezoidal in shape.

    The goal is to have the

    center of the footing at the

    centroid of the loads.

  • 8/18/2019 AE303 Footing Design Presentation Part 1

    7/12

    Types of FootingsCombined footings support

    two or more columns. Thegoal is to have the center of

    the footing at the centroid of

    the loads.

    Types of Footings

    Cantilever or strap footings consist of two single footings connected with a

    beam or a strap and support two single columns. The strap reduces

    differential settlement and also adds support for walls.

  • 8/18/2019 AE303 Footing Design Presentation Part 1

    8/12

    Types of Footings

    Wall footings are used to support wallsthat carry loads from upper floors.

    They can also act as part of a retaining

    wall base.

    Types of Footings

     Raft or mat foundation consists of one footing usually placed

    under the entire building area. They are used when soil bearing

    capacity is low, column loads are heavy so that single footings

    cannot be efficiently used. Differential settlement is reduced.

  • 8/18/2019 AE303 Footing Design Presentation Part 1

    9/12

    Types of Footings

     Pile caps are thick footings used to tie a group of piles

    together to support and transmit column loads to the piles.

     Footing Design Considerations

    Once the footings are sized, they must be designed to carry the

    column loads and transmit them to the soil safely while

    satisfying code limitations.

    One and two way shear strength of the concrete

    Moment capacity of the section

    Bearing capacity of columns to the footing

    Dowel requirements

    Development length of bars

  • 8/18/2019 AE303 Footing Design Presentation Part 1

    10/12

     Design for two-way shear

    (  the following examples assume uniform soil pressure )Assume d.

    Determine the shear perimeter b0:

    b0 = 2(c1+d) +2(c2+d) for

    columns of sides c1 and c2.

    1

    2

    3 The shear force Vu acts at a

    section that has a length

    b0 and a depth d; the section is

    subjected to a vertical downward

    load Pu and vertical upward

    pressure qu.( )( ) )consistentunits(keep 21uuu   d cd cqPV    ++−=

     Design for two-way shear

    For two-way shear in footings (and slabs) Vc is the smallest of:

    long side/short side of column concentrated load or

    reaction area

    length of critical perimeter around the column

    where, βc =

    b0 =

    d b f V  0c

    c

    c  4

    2

     

     

     

     +=

     β 

    When β >2 the allowable Vc is reduced.

    d b f 

    b

    d V  0c

    o

    sc  2

     

     

     

     +=

      α 

    d b f V  0cc  4=   αs is 40 for interior, 30 for edgeand 20 for corner column

  • 8/18/2019 AE303 Footing Design Presentation Part 1

    11/12

     Design for two-way shear

    VuV 

    VnVc

     

    Set

    c  =∴

    =

    φ 

    Vc

    V d 

    φ u

    =

    If the required d is not less than or

    equal to the assumed d, pick a larger d

    and repeat the calculations.

    Two way shear will normally control

    for square footings.

     Design for one-way shear

    For footings, the critical section is

    located a distance d from the face

    of the equivalent column.

    If the column is not concrete, the “face”

    location must be calculated. It is half

    way between the edge of the base plate

    and the face of a steel column. It is ¼ of

    “c” inside of a masonry column. (This iscommon for wall footings).

    d b ' f V   2 cc   φ φ    =

  • 8/18/2019 AE303 Footing Design Presentation Part 1

    12/12

     Design for one-way shear

    The ultimate shearing force at section m-m can be

    calculated

     

     

     

     −−=   d 

    c LbqV 

    22

     uu

    If no shear reinforcement is to be

    used, then the minimum value of d

    can be calculated.

    Set Vu = φVc

    b f 

    V d 

     2 c

    u

    φ =