advantage of iec 61850
DESCRIPTION
Advantage of Iec 61850TRANSCRIPT
-
Track 3: POWER AND SYSTEMS ENGINEERING
International Symposium on Electrical & Electronics Engineering 2007 - Oct 24, 25 2007 - HCM City, Vietnam
-315-
THE ADVANTAGE OF STANDARD IEC61850
IN PROTECTION AND SUBSTATION AUTOMATION SYSTEMS
Assoc. Prof. PhD. Le Kim Hung - Danang University, PhD. Thach Le Khiem - ABB VietNam, and Ivan De Mesmaeker - ABB Switzerland
ABSTRACT
The use of numerical technology in protection and automation has provided multi-functions
equipment, allows the development of new solutions and a higher degree of integration. The paper
give the general functions, advantage and how to use IEC61850 in design, engineering application for
substation protection and control.
1. INTRODUCTION AND ADVANTAGE
OF IEC 61850
The standard IEC61850 - Communication
Networks and Systems is the first and only
global standard that considers all the
communication needs within a substation, it is
covering design aspects, defines guidelines for protection, monitoring, control and automation
This standard also raises interoperability and
free allocation of functions and devices, support all type of architectures protocol and its practical
application for substation automation systems.
IEC 61850 is not only issued, but also ready
to use in many countries. This standard is also
the request strictly by EVN (Electricity in
VietNam) for the substation automation design
in all 500kV and 220kV substation of VietNam
power system.
The advantage of IEC 61850 communication
and protocol:
- Apply the request an open protocol for
protection, monitoring, control at least inside substations.
- This is higher flexibility solution, have the
possibility to make extension without being
dependant on the manufacturer having delivered
the previous parts of the substation equipment.
- Full application and all request for
substation automation, and data interoperability
within the substations.
- Advantage for users: the system
engineering done and documented with the help
of Substation Configuration description
Language (SCL) provided in the IEC 61850-6
can be re-used later when only certain system
components have to be replaced after several
years of operation. By introducing this kind of
global language and established common naming of the function-related signal name, the
substation automation will be complemented by
a hierarchical plant designation scheme in IEC 61850. Since the standard is accepted
worldwide, no difference between the ANSI and
IEC worlds will appear.
2. IMPACT OF IEC 61850 ON
SPECIFICATIONS
The standard has an impact on all activities of field of protection and substation automation,
but the main issues are how to implement this
standard in practice which is to be done by the suppliers, and how to specify protection and
substation automation systems, which is to be
done by the users like utilities. Specifying according to the standard IEC 61850 means that
the entire functionality is split into Logical
Nodes (Fig.1) with their corresponding data, i.e.
with the established common naming of the
function-related signal names. If this is not done
in the specification already, the system
integrator has to do it. Anyway, the people
anywhere in charge of the project execution
(design, engineering, testing, FAT- Factory
Acceptance Test, commissioning, site
-
Track 3: POWER AND SYSTEMS ENGINEERING
International Symposium on Electrical & Electronics Engineering 2007 - Oct 24, 25 2007 - HCM City, Vietnam
-316-
Fig.1 Modelling example of one
feeder in IEC 61850
acceptance test, operation, etc.) will once have to learn this common but simple language. It is
an advantage to, the use of the Standard
Configuration description Language (SCL) has an important advantage: the integrity of data is
warranted by using one single data entry. The
users are recommended to check the signals and
evaluate which ones are really needed
(mandatory (M)/ optional (O)) which the system
designer and integrator take this information
into its design and engineering tool.
- Impacts on the general system design
Based on the specification a solution concept
has to be elaborated. The standard IEC 61850 allows the free allocation of functions. Due to
the split into functional nodes, the system
designer is free to distribute the functions, but has to respect the mentioned constraints as
imposed by the specification. To ensure
seamless interoperability, especially the
distributed functions like breaker failure
protection, busbar protection, station-wide
interlocking, and load shedding have to be designed very carefully. Regarding all the
requirements, only a system integrator with
comprehensive experience will be able to elaborate such an optimized solution exploiting
all benefits of IEC 61850.
- Impacts on the engineering
The informal information from the
specification has to be translated into the formal description using SCL. This work may
be done by the author of the specification or has
to be done latest by the system integrator. The
formal description warrants a high quality of
work, ensures integrity and consistency during
the entire implementation process, from the
general system design to the final
commissioning, facilitating the corresponding
checks in each step of the project execution.
The whole substation automation system is
formally documented in SCL according to IEC 61850. Therefore, the engineering work done
remains memorised and can be reused at any
time for adaptations, extensions and also refurbishment.
- The requested standard and compliance
with IEC 61850
A prerequisite for reasonable project execution is the use of components (IEDs -
Intelligent Electronic Device), which are
proven to be compliant with IEC 61850. The framework for the compliance test is given in
part 10 of the standard (IEC 61850-10) and is
now being detailed by user organizations and test bodies. A test certificate has to be supplied.
The main compliance features are the data
model according to the implemented functions
and the proper running of the needed and
specified services. It shall also be mentioned
that each compliant IED has to be supplied
with a formal data sheet being the SCL
description of its capabilities (ICD - Interface
Control Document files).
3. IEC 61850 FOR SCADA APPLICATION
IN SUBSTATIONS
3.1 Tasks
SCADA - Supervisory control and data
acquisition is one of the basic tasks of a
substation automation system. The tasks of
SCADA are:
-
Track 3: POWER AND SYSTEMS ENGINEERING
International Symposium on Electrical & Electronics Engineering 2007 - Oct 24, 25 2007 - HCM City, Vietnam
-317-
Fig.3 Data model and naming
Local and remote operation of the
switchgear and another equipment.
Acquisition of switchgear information and
measurments.
Handling of events and alarms.
The SCADA application is related to human operation of the network and is performed by a
local or remote operator. The data
communication for this application is directed vertically, i.e. from a higher control level down
to a lower one (commands of any kind from the
operators place) or reverse (binary indications
like breakers or isolators position, measurands
from instrument transformers...) as Figure 2.
3.2 Model (fig.2)
The vertical relationship IEC 61850 is using
the client - server concept. The server is the process or bay level (IEDs), which provides all
data to the client at station or remote level. The
data are provided on request by the server or
automatically by a report from the server issued
if certain conditions are fulfilled. The client is
mostly a computer representing the operators
work place. The client can send commands to
the server for changing data in the server to:
Issue commands for the operation to the
switchgear.
Modify the behavior of the server through
the change of internal data (e.g. change of
parameter sets, analog set-points, enabling or disabling functions).
In a client-server communication, the client controls the data exchange. Therefore, client-
server communication is very flexible in terms
of the data to be transmitted. Compared to a
master slave system, the client-server concept
allows the implementation of multiple clients in
the same system. (e.g. the gateway and the HMI
- Human Machine interface are clients).
IEC 61850 not only specifies the method of the data transfer but also defines the process
data of the servers. For that purpose, IEC 61850
uses an object-oriented approach with Logical Nodes (LN) as core objects. A logical node is a
functional grouping of data and represents the
smallest function, which may be implemented independently in devices. Examples Logical
Node XCBR contains group data of circuit
breaker or Logical Node PTOC is the data of a
timed overcurrent protection.
Logical Nodes have object data, and object-data have data attributes. For example, the
XCBR (Q0_XCBR) has a data called Pos, with
one attribute stVal, which indicates the
position (values according the common double
point indication: off, on, intermediate-state,
bad-state) and another attribute ctlVal for the opening and closing command (values: off, on).
Logical Nodes are grouped in Logical Devices.
Example: Logical Device Tampa_Protection for two zone distance protection Logical Node
PDIS per zone (PDIS1 and PDIS2 in Fig.3).
Logical Devices are implemented in physical
Fig.2 Vertical comminication in the substation
automation system
-
Track 3: POWER AND SYSTEMS ENGINEERING
International Symposium on Electrical & Electronics Engineering 2007 - Oct 24, 25 2007 - HCM City, Vietnam
-318-
Fig.4 Horizontal comminication in the substation
automation system
devices (IEDs). There is some actual information needed not only about the Logical
Nodes and Logical Devices but also about the
complete IED like the status of the common power supply. This information is modeled in
the Logical Node LPHD (see Error! Reference
source not found.3).
3.3 Application
A typical application of SCADA is the
creation of alarm and event lists. With IEC
61850, datasets used together with the report service can be used for that purpose. As an
example, a utility may specify a dataset per IED
that contains all data for the alarm list. The NCC gateway provides the interface from the NCC
(National Control Center) to the substation. It
has two basic tasks:
Protocol and data conversion
Data collection
For the data collection, the NCC gateway is a
client in the IEC 61850 based substation
automation system. The data is typically
collected using the report model. The dataset
used in that case corresponds to the traditional
signal list specifying the information from the
substation to be transmitted to the NCC.
4. IEC 61850 FOR TIME CRITICAL
INFORMATION EXCHANGE
4.1 Tasks
There are several functions in the substation
automation system, which require a time critical
exchange of binary information between
functions located within the same bay or in
different bays. Examples:
Exchange between line protection and
autorecloser.
Exchange between bays for breaker
failure.
Exchange between bays for station
interlocking.
Typically, these functions are not using human interaction and are time critical. They are
time critical because they are safety critical. The
maximal accepted communication delay is in the range of several milliseconds. This information
exchange is a horizontal communication
between devices at the same hierarchical level
(Fig.4).
4.2 Model
As an example, for the information exchange
between the protection function and the breaker failure function, the following logical nodes are
involved:
PTRC (protection trip conditioning)
representing the logic in a protection device
that creates the binary outputs (start and trip
output of e.g. the line protection device).
RBRF representing the protection related
function Breaker Failure function.
The information exchange between these
logical nodes is also modeled as data. The data
is part of the logical node that is the source of
the information exchange. As example, the LN
PTRC has a data Tr with an attribute general
representing the trip output of the protection
device for a general trip. That signal is not only
used to operate the breaker, but it also is used to trigger the breaker failure function.
For the exchange of this type, IEC 61850
introduces a specific information exchange
service called GOOSE (Generic Object Oriented
-
Track 3: POWER AND SYSTEMS ENGINEERING
International Symposium on Electrical & Electronics Engineering 2007 - Oct 24, 25 2007 - HCM City, Vietnam
-319-
Fig.5 Connection between distance protection
and recloser functions
Substation Event) based on the publisher-subscriber concept. The content of a GOOSE
message is defined with a dataset (similar like
for the report model described above). The GOOSE message is sent as a multicast message
over the communication network. That means
that multiple devices can receive the message
and retrieve the information required from the
message. The communication service is not
confirmed; instead, the message is repeated
several times.
In the example of the breaker failure function
a GOOSE message is configured in the protection device that contains at least the data
PTRC.Tr.general. As soon as
PTRC.Tr.general changes its the value to
TRUE, the GOOSE message is sent. The device
performing the breaker failure function is
receiving this message and detects that
PTRC.Tr.general has changed its value to TRUE. Another GOOSE message is sent when
the value changes back to FALSE.
4.3 Application
There are two types of application,
depending if the exchange of information is
between devices inside the bay or between
devices placed in different bays.
Exchange of information inside the bay: A
typical example is the exchange of information between Logical Device Distance Protection
containing instances of LN PDIS, LN PTRC and
the Logical Device Recloser containing the LN RREC in case these both functions are
installed in separate devices as Fig.5.
The LD Distance Protection sends
information to the LD Recloser: start of
starting elements in LN PTRC (PTRC.Str) and
trip in LN PTRC (PTRC.Op). Based on these
information and depending on the settings
(single pole recloser or three pole recloser;
RREC.TrMod) the recloser function
represented by RREC will send information
(RREC.TrBeh) to the LD Distance Protection in order to enable the expected trip
(if one or three phases PTRC.Tr) to the breaker.
The open command to the breaker is issued by the recloser function (RREC.Op).
5. IEC 61850 FOR SUBSTATION
AUTOMATION DESIGN
Substation automation designs have many
steps from the specification up to the
commissioning of a project specific system. SCL was introduced for a comprehensive
description of the complete substation
automation system supporting the goal interoperability of the standard. The description
in SCL allows:
single line diagram,
function allocation to the single line
diagram,
function allocation to devices,
data as being mandatory and optional
according to IEC 61850 (optional if needed or provided),
connection in the communication system,
setting of all configuration parameters as
defined in IEC 61850.
To use IEC 61850 for building the substation
automation, the system designer need:
- ICD files of IEDs
- SSD files of system
-
Track 3: POWER AND SYSTEMS ENGINEERING
International Symposium on Electrical & Electronics Engineering 2007 - Oct 24, 25 2007 - HCM City, Vietnam
-320-
Fig.6 Engineering process using SCL files
The capabilities of an IEC 61850 compliant
device are described in an IED Capability Description (ICD) file. A vendor of devices
claiming conformance to IEC 61850 has not
only to supply paper documentation like a data
sheet but also an ICD file.
The SSD file is used to describe the single line diagram and the allocated functions. The
optional data that need to be supported can also
be described in the SSD file. This replaces the traditional signal list, the elements of a signal
list being the data of LNs. Any system
integration tool needs the SSD file and the ICD files of all devices of the system. The output is
the Substation Configuration Description (SCD)
file. For maintenance and future system
modifications the SCD files have to be archived
as part of the project documentation.
The system configuration tool will take these files written according to SCL and merge these
by the system engineering process to a SCD file.
The formal SCL description will result in a consistent data exchange, allow exchanges
between compliant tools independent from the
supplier and, finally, in a machine-readable
documentation of the data and communication
structure of the SA system. Any extension or update in the future will not start from the
scratch but from the archived SCD file.
6. CONCLUSION
IEC 61850 is efficient standard in building
protection and control automation in the
substation. It provides not only a powerful
method to reach interoperability, but also
supports to cover all aspects related to the
communication, naming, engineering capabilities, conformity, testing... in Substation
Automation Systems, optimized solution
exploiting all benefits for users.
It doesnt mean that all delivered IEC 61850
systems will have the same quality independently of the manufacturer because
architecture remains free as architecture of the
communication system as well as location of the
different functionality as well as the quality of
each protection functions. The first experiences
done by manufacturers and utilities have now to confirm if the expectations are fulfilled and if
some extensions inside the standard will be
needed.
REFERENCES 1. Klaus-Peter Brand, Christoph Brunner, Ivan
De Mesmaeker. How to use IEC 61850 in
protection and automation. Baden and
Zrich, Switzerland, 2005.
2. De Mesmaeker Ivan - CIGRE. Protection and
substation automation systems: handling of
standardisation, integration and information technology. ABB Switzerland, 2006.
3. De Mesmaeker Ivan, Klaus-Peter Brand,
Peter Rietmann, Petra Reinhardt. Practical considerations in applying IEC 61850 for
protection and substation automation
systems. Baden and Zrich, Switzerland,
2005.