advantage of iec 61850

Upload: joydeepd3232

Post on 31-Oct-2015

28 views

Category:

Documents


0 download

DESCRIPTION

Advantage of Iec 61850

TRANSCRIPT

  • Track 3: POWER AND SYSTEMS ENGINEERING

    International Symposium on Electrical & Electronics Engineering 2007 - Oct 24, 25 2007 - HCM City, Vietnam

    -315-

    THE ADVANTAGE OF STANDARD IEC61850

    IN PROTECTION AND SUBSTATION AUTOMATION SYSTEMS

    Assoc. Prof. PhD. Le Kim Hung - Danang University, PhD. Thach Le Khiem - ABB VietNam, and Ivan De Mesmaeker - ABB Switzerland

    ABSTRACT

    The use of numerical technology in protection and automation has provided multi-functions

    equipment, allows the development of new solutions and a higher degree of integration. The paper

    give the general functions, advantage and how to use IEC61850 in design, engineering application for

    substation protection and control.

    1. INTRODUCTION AND ADVANTAGE

    OF IEC 61850

    The standard IEC61850 - Communication

    Networks and Systems is the first and only

    global standard that considers all the

    communication needs within a substation, it is

    covering design aspects, defines guidelines for protection, monitoring, control and automation

    This standard also raises interoperability and

    free allocation of functions and devices, support all type of architectures protocol and its practical

    application for substation automation systems.

    IEC 61850 is not only issued, but also ready

    to use in many countries. This standard is also

    the request strictly by EVN (Electricity in

    VietNam) for the substation automation design

    in all 500kV and 220kV substation of VietNam

    power system.

    The advantage of IEC 61850 communication

    and protocol:

    - Apply the request an open protocol for

    protection, monitoring, control at least inside substations.

    - This is higher flexibility solution, have the

    possibility to make extension without being

    dependant on the manufacturer having delivered

    the previous parts of the substation equipment.

    - Full application and all request for

    substation automation, and data interoperability

    within the substations.

    - Advantage for users: the system

    engineering done and documented with the help

    of Substation Configuration description

    Language (SCL) provided in the IEC 61850-6

    can be re-used later when only certain system

    components have to be replaced after several

    years of operation. By introducing this kind of

    global language and established common naming of the function-related signal name, the

    substation automation will be complemented by

    a hierarchical plant designation scheme in IEC 61850. Since the standard is accepted

    worldwide, no difference between the ANSI and

    IEC worlds will appear.

    2. IMPACT OF IEC 61850 ON

    SPECIFICATIONS

    The standard has an impact on all activities of field of protection and substation automation,

    but the main issues are how to implement this

    standard in practice which is to be done by the suppliers, and how to specify protection and

    substation automation systems, which is to be

    done by the users like utilities. Specifying according to the standard IEC 61850 means that

    the entire functionality is split into Logical

    Nodes (Fig.1) with their corresponding data, i.e.

    with the established common naming of the

    function-related signal names. If this is not done

    in the specification already, the system

    integrator has to do it. Anyway, the people

    anywhere in charge of the project execution

    (design, engineering, testing, FAT- Factory

    Acceptance Test, commissioning, site

  • Track 3: POWER AND SYSTEMS ENGINEERING

    International Symposium on Electrical & Electronics Engineering 2007 - Oct 24, 25 2007 - HCM City, Vietnam

    -316-

    Fig.1 Modelling example of one

    feeder in IEC 61850

    acceptance test, operation, etc.) will once have to learn this common but simple language. It is

    an advantage to, the use of the Standard

    Configuration description Language (SCL) has an important advantage: the integrity of data is

    warranted by using one single data entry. The

    users are recommended to check the signals and

    evaluate which ones are really needed

    (mandatory (M)/ optional (O)) which the system

    designer and integrator take this information

    into its design and engineering tool.

    - Impacts on the general system design

    Based on the specification a solution concept

    has to be elaborated. The standard IEC 61850 allows the free allocation of functions. Due to

    the split into functional nodes, the system

    designer is free to distribute the functions, but has to respect the mentioned constraints as

    imposed by the specification. To ensure

    seamless interoperability, especially the

    distributed functions like breaker failure

    protection, busbar protection, station-wide

    interlocking, and load shedding have to be designed very carefully. Regarding all the

    requirements, only a system integrator with

    comprehensive experience will be able to elaborate such an optimized solution exploiting

    all benefits of IEC 61850.

    - Impacts on the engineering

    The informal information from the

    specification has to be translated into the formal description using SCL. This work may

    be done by the author of the specification or has

    to be done latest by the system integrator. The

    formal description warrants a high quality of

    work, ensures integrity and consistency during

    the entire implementation process, from the

    general system design to the final

    commissioning, facilitating the corresponding

    checks in each step of the project execution.

    The whole substation automation system is

    formally documented in SCL according to IEC 61850. Therefore, the engineering work done

    remains memorised and can be reused at any

    time for adaptations, extensions and also refurbishment.

    - The requested standard and compliance

    with IEC 61850

    A prerequisite for reasonable project execution is the use of components (IEDs -

    Intelligent Electronic Device), which are

    proven to be compliant with IEC 61850. The framework for the compliance test is given in

    part 10 of the standard (IEC 61850-10) and is

    now being detailed by user organizations and test bodies. A test certificate has to be supplied.

    The main compliance features are the data

    model according to the implemented functions

    and the proper running of the needed and

    specified services. It shall also be mentioned

    that each compliant IED has to be supplied

    with a formal data sheet being the SCL

    description of its capabilities (ICD - Interface

    Control Document files).

    3. IEC 61850 FOR SCADA APPLICATION

    IN SUBSTATIONS

    3.1 Tasks

    SCADA - Supervisory control and data

    acquisition is one of the basic tasks of a

    substation automation system. The tasks of

    SCADA are:

  • Track 3: POWER AND SYSTEMS ENGINEERING

    International Symposium on Electrical & Electronics Engineering 2007 - Oct 24, 25 2007 - HCM City, Vietnam

    -317-

    Fig.3 Data model and naming

    Local and remote operation of the

    switchgear and another equipment.

    Acquisition of switchgear information and

    measurments.

    Handling of events and alarms.

    The SCADA application is related to human operation of the network and is performed by a

    local or remote operator. The data

    communication for this application is directed vertically, i.e. from a higher control level down

    to a lower one (commands of any kind from the

    operators place) or reverse (binary indications

    like breakers or isolators position, measurands

    from instrument transformers...) as Figure 2.

    3.2 Model (fig.2)

    The vertical relationship IEC 61850 is using

    the client - server concept. The server is the process or bay level (IEDs), which provides all

    data to the client at station or remote level. The

    data are provided on request by the server or

    automatically by a report from the server issued

    if certain conditions are fulfilled. The client is

    mostly a computer representing the operators

    work place. The client can send commands to

    the server for changing data in the server to:

    Issue commands for the operation to the

    switchgear.

    Modify the behavior of the server through

    the change of internal data (e.g. change of

    parameter sets, analog set-points, enabling or disabling functions).

    In a client-server communication, the client controls the data exchange. Therefore, client-

    server communication is very flexible in terms

    of the data to be transmitted. Compared to a

    master slave system, the client-server concept

    allows the implementation of multiple clients in

    the same system. (e.g. the gateway and the HMI

    - Human Machine interface are clients).

    IEC 61850 not only specifies the method of the data transfer but also defines the process

    data of the servers. For that purpose, IEC 61850

    uses an object-oriented approach with Logical Nodes (LN) as core objects. A logical node is a

    functional grouping of data and represents the

    smallest function, which may be implemented independently in devices. Examples Logical

    Node XCBR contains group data of circuit

    breaker or Logical Node PTOC is the data of a

    timed overcurrent protection.

    Logical Nodes have object data, and object-data have data attributes. For example, the

    XCBR (Q0_XCBR) has a data called Pos, with

    one attribute stVal, which indicates the

    position (values according the common double

    point indication: off, on, intermediate-state,

    bad-state) and another attribute ctlVal for the opening and closing command (values: off, on).

    Logical Nodes are grouped in Logical Devices.

    Example: Logical Device Tampa_Protection for two zone distance protection Logical Node

    PDIS per zone (PDIS1 and PDIS2 in Fig.3).

    Logical Devices are implemented in physical

    Fig.2 Vertical comminication in the substation

    automation system

  • Track 3: POWER AND SYSTEMS ENGINEERING

    International Symposium on Electrical & Electronics Engineering 2007 - Oct 24, 25 2007 - HCM City, Vietnam

    -318-

    Fig.4 Horizontal comminication in the substation

    automation system

    devices (IEDs). There is some actual information needed not only about the Logical

    Nodes and Logical Devices but also about the

    complete IED like the status of the common power supply. This information is modeled in

    the Logical Node LPHD (see Error! Reference

    source not found.3).

    3.3 Application

    A typical application of SCADA is the

    creation of alarm and event lists. With IEC

    61850, datasets used together with the report service can be used for that purpose. As an

    example, a utility may specify a dataset per IED

    that contains all data for the alarm list. The NCC gateway provides the interface from the NCC

    (National Control Center) to the substation. It

    has two basic tasks:

    Protocol and data conversion

    Data collection

    For the data collection, the NCC gateway is a

    client in the IEC 61850 based substation

    automation system. The data is typically

    collected using the report model. The dataset

    used in that case corresponds to the traditional

    signal list specifying the information from the

    substation to be transmitted to the NCC.

    4. IEC 61850 FOR TIME CRITICAL

    INFORMATION EXCHANGE

    4.1 Tasks

    There are several functions in the substation

    automation system, which require a time critical

    exchange of binary information between

    functions located within the same bay or in

    different bays. Examples:

    Exchange between line protection and

    autorecloser.

    Exchange between bays for breaker

    failure.

    Exchange between bays for station

    interlocking.

    Typically, these functions are not using human interaction and are time critical. They are

    time critical because they are safety critical. The

    maximal accepted communication delay is in the range of several milliseconds. This information

    exchange is a horizontal communication

    between devices at the same hierarchical level

    (Fig.4).

    4.2 Model

    As an example, for the information exchange

    between the protection function and the breaker failure function, the following logical nodes are

    involved:

    PTRC (protection trip conditioning)

    representing the logic in a protection device

    that creates the binary outputs (start and trip

    output of e.g. the line protection device).

    RBRF representing the protection related

    function Breaker Failure function.

    The information exchange between these

    logical nodes is also modeled as data. The data

    is part of the logical node that is the source of

    the information exchange. As example, the LN

    PTRC has a data Tr with an attribute general

    representing the trip output of the protection

    device for a general trip. That signal is not only

    used to operate the breaker, but it also is used to trigger the breaker failure function.

    For the exchange of this type, IEC 61850

    introduces a specific information exchange

    service called GOOSE (Generic Object Oriented

  • Track 3: POWER AND SYSTEMS ENGINEERING

    International Symposium on Electrical & Electronics Engineering 2007 - Oct 24, 25 2007 - HCM City, Vietnam

    -319-

    Fig.5 Connection between distance protection

    and recloser functions

    Substation Event) based on the publisher-subscriber concept. The content of a GOOSE

    message is defined with a dataset (similar like

    for the report model described above). The GOOSE message is sent as a multicast message

    over the communication network. That means

    that multiple devices can receive the message

    and retrieve the information required from the

    message. The communication service is not

    confirmed; instead, the message is repeated

    several times.

    In the example of the breaker failure function

    a GOOSE message is configured in the protection device that contains at least the data

    PTRC.Tr.general. As soon as

    PTRC.Tr.general changes its the value to

    TRUE, the GOOSE message is sent. The device

    performing the breaker failure function is

    receiving this message and detects that

    PTRC.Tr.general has changed its value to TRUE. Another GOOSE message is sent when

    the value changes back to FALSE.

    4.3 Application

    There are two types of application,

    depending if the exchange of information is

    between devices inside the bay or between

    devices placed in different bays.

    Exchange of information inside the bay: A

    typical example is the exchange of information between Logical Device Distance Protection

    containing instances of LN PDIS, LN PTRC and

    the Logical Device Recloser containing the LN RREC in case these both functions are

    installed in separate devices as Fig.5.

    The LD Distance Protection sends

    information to the LD Recloser: start of

    starting elements in LN PTRC (PTRC.Str) and

    trip in LN PTRC (PTRC.Op). Based on these

    information and depending on the settings

    (single pole recloser or three pole recloser;

    RREC.TrMod) the recloser function

    represented by RREC will send information

    (RREC.TrBeh) to the LD Distance Protection in order to enable the expected trip

    (if one or three phases PTRC.Tr) to the breaker.

    The open command to the breaker is issued by the recloser function (RREC.Op).

    5. IEC 61850 FOR SUBSTATION

    AUTOMATION DESIGN

    Substation automation designs have many

    steps from the specification up to the

    commissioning of a project specific system. SCL was introduced for a comprehensive

    description of the complete substation

    automation system supporting the goal interoperability of the standard. The description

    in SCL allows:

    single line diagram,

    function allocation to the single line

    diagram,

    function allocation to devices,

    data as being mandatory and optional

    according to IEC 61850 (optional if needed or provided),

    connection in the communication system,

    setting of all configuration parameters as

    defined in IEC 61850.

    To use IEC 61850 for building the substation

    automation, the system designer need:

    - ICD files of IEDs

    - SSD files of system

  • Track 3: POWER AND SYSTEMS ENGINEERING

    International Symposium on Electrical & Electronics Engineering 2007 - Oct 24, 25 2007 - HCM City, Vietnam

    -320-

    Fig.6 Engineering process using SCL files

    The capabilities of an IEC 61850 compliant

    device are described in an IED Capability Description (ICD) file. A vendor of devices

    claiming conformance to IEC 61850 has not

    only to supply paper documentation like a data

    sheet but also an ICD file.

    The SSD file is used to describe the single line diagram and the allocated functions. The

    optional data that need to be supported can also

    be described in the SSD file. This replaces the traditional signal list, the elements of a signal

    list being the data of LNs. Any system

    integration tool needs the SSD file and the ICD files of all devices of the system. The output is

    the Substation Configuration Description (SCD)

    file. For maintenance and future system

    modifications the SCD files have to be archived

    as part of the project documentation.

    The system configuration tool will take these files written according to SCL and merge these

    by the system engineering process to a SCD file.

    The formal SCL description will result in a consistent data exchange, allow exchanges

    between compliant tools independent from the

    supplier and, finally, in a machine-readable

    documentation of the data and communication

    structure of the SA system. Any extension or update in the future will not start from the

    scratch but from the archived SCD file.

    6. CONCLUSION

    IEC 61850 is efficient standard in building

    protection and control automation in the

    substation. It provides not only a powerful

    method to reach interoperability, but also

    supports to cover all aspects related to the

    communication, naming, engineering capabilities, conformity, testing... in Substation

    Automation Systems, optimized solution

    exploiting all benefits for users.

    It doesnt mean that all delivered IEC 61850

    systems will have the same quality independently of the manufacturer because

    architecture remains free as architecture of the

    communication system as well as location of the

    different functionality as well as the quality of

    each protection functions. The first experiences

    done by manufacturers and utilities have now to confirm if the expectations are fulfilled and if

    some extensions inside the standard will be

    needed.

    REFERENCES 1. Klaus-Peter Brand, Christoph Brunner, Ivan

    De Mesmaeker. How to use IEC 61850 in

    protection and automation. Baden and

    Zrich, Switzerland, 2005.

    2. De Mesmaeker Ivan - CIGRE. Protection and

    substation automation systems: handling of

    standardisation, integration and information technology. ABB Switzerland, 2006.

    3. De Mesmaeker Ivan, Klaus-Peter Brand,

    Peter Rietmann, Petra Reinhardt. Practical considerations in applying IEC 61850 for

    protection and substation automation

    systems. Baden and Zrich, Switzerland,

    2005.