Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets

Upload: others

Post on 26-Mar-2020

22 views

Category:

Documents


5 download

TRANSCRIPT

Page 1: Advancements in online partial discharge monitoring and ... · Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets. Abstract: For

Advancements in online partial

discharge monitoring and assessment

of MV through EHV Substation assets

Page 2: Advancements in online partial discharge monitoring and ... · Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets. Abstract: For

Abstract:For decades it has been recognized that partial discharge assessment is an excellent method for determining asset health.

• On line non-invasive techniques for monitoring and surveying have been proven to provide the necessary level of detail for condition assessment without impacting system operation.

• Techniques exist now to test assets from 3KV to 500KV and beyond. Metal clad switchgear and busswork, GIS switchgear and busses, air insulated assets (insulators, arrestors, bushings, etc.), as well as paper insulated and extruded cables can all be tested on-line without an outage.

This presentation will give a brief overview of the causes and effects of partial discharge and then examine the various technologies available for finding it on-line.

Examples of field success stories will also be given.

Page 3: Advancements in online partial discharge monitoring and ... · Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets. Abstract: For

Topics for Today

Who is EA Technology

Causes and effects of Partial Discharge

Sensing Technologies

Transient Earth Voltage

Ultrasonic Reception

Radio Frequency Current Transformers

Ultra High Frequency Radio Detection

Recent Advancements in Detection

Page 4: Advancements in online partial discharge monitoring and ... · Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets. Abstract: For

• Provide products and services for measuring, monitoring and managing physical assets for electric utilities

• Consulting on a wide range of power system issues

• Produce inspection and maintenance standards and procedures

• Forensic failure investigation services

• Major patron of the Institute of Asset Management

• Instrumental in PAS 55 and ISO 55000 development

• EATLLC – US Subsidiary in NJ

Page 5: Advancements in online partial discharge monitoring and ... · Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets. Abstract: For

Partial Discharge - A flashover of part of the insulation system due to a localized electric field greater than the dielectric withstand capability of that part where the overall insulation system remains capable of withstanding the applied electrical field.

Void

GroundConductor

V withstand of C2 < applied field V withstand of C1&C3 > applied field

What is Partial Discharge (PD)?

5

One effect of this flashover is a high frequency current pulse that travels through the capacitance of the insulation (C1 & C3)

HF CurrentPulse

C1 C2 C3

Page 6: Advancements in online partial discharge monitoring and ... · Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets. Abstract: For

Products of Partial Discharge

6

Partial discharge breakdown of insulation produces:

Light, Heat, Smell, Sound, Electromagnetic Waves, and an

HF Electric Current

+

Water

Nitric

AcidElectric

TEV

Page 7: Advancements in online partial discharge monitoring and ... · Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets. Abstract: For

Partial Discharge (PD)

Where can it occur

- Any insulation (Air, Oil, Solid, GIS)

- Wide range of voltages (>4KV)

- Any age equipment

- Types of equipment

- Metal clad circuit breakers / switchboards

- Bus ducts (Segregated phase, ISO Phase, GIS)

- Cables

- Overheard insulators

Page 8: Advancements in online partial discharge monitoring and ... · Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets. Abstract: For

Types of PD

Page 9: Advancements in online partial discharge monitoring and ... · Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets. Abstract: For

Practical Non-Intrusive PD

Detection Methods

Internal discharge activity

• Transient Earth Voltage (TEV) Detection

• RFCT Detection of Current Pulse

• UHF Detection of EMI

Surface discharge activity

• Ultrasonic Detection

• TEV Detection - high amplitude surface discharge

• RFCT Detection of Current Pulse

• UHF Detection of EMI

Page 10: Advancements in online partial discharge monitoring and ... · Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets. Abstract: For

Internal Partial Discharge Effect 1

(current pulse - TEV)

10

HV BUSBAR

PARTIAL DISCHARGEJOINT/GASKET

HV BUSBAR

HIGH FREQUENCY PULSE TO METALWORK VIA

CAPACITANCE OF INSULATOR

TEV RESULTS DUE TO IMPEDANCE OF GROUNDING

At HF, PD currents are constrained to

Flow in a thin layer on the surface of

Conductor.

Skin depth in mild steel at 100MHz

0.5um

UltraTEV

PULSE TRAVELS VIA SKIN EFFECT

Page 11: Advancements in online partial discharge monitoring and ... · Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets. Abstract: For

HV BUSBAR

EM WAVEEM WAVE

PARTIAL DISCHARGEJOINT/GASKET

HV BUSBAR

Internal Partial Discharge Effect 2

(EM Wave)

11

PULSE TRAVELS VIA SKIN EFFECT

TEV RESULTS DUE TO IMPEDANCE OF GROUNDING

This effect is usually less than the current pulse unless the PD is

phase to phase!

UltraTEV

Page 12: Advancements in online partial discharge monitoring and ... · Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets. Abstract: For

TEV from PD

EMI from PD

Corona

PD Hawk

PD Spectrum (Simplified)

• Partial Discharge

causes a

broadband EMI

emission

(approx. 3-3000

MHz)

• Corona causes a

smaller band EMI

emission (30-400

MHz)

• TEV caused by

capacitive currents

are typically in the

3-80 MHz band

Partial Discharge Frequency Spectrum

Page 13: Advancements in online partial discharge monitoring and ... · Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets. Abstract: For

13

Probable Internal

No Internal Significant

Discharging

PossibleSurface Discharging

ProbableBackgroundInterference

Probable Floating Metal

Bad Conn

Partial Discharge TEV Interpretation

Page 14: Advancements in online partial discharge monitoring and ... · Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets. Abstract: For

Partial Discharge damage found

through TEV sensing

Channel cutthrough resin by discharge

Page 15: Advancements in online partial discharge monitoring and ... · Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets. Abstract: For

Surface Discharge Detection

Through Ultrasonic Sensing

• In severe cases, audible sound may be present

• Less severe deterioration may be detected

using ultrasonic detecting instruments

• Sound spectrum in the 40kHz range

• Characteristic sound more important than

absolute level

Page 16: Advancements in online partial discharge monitoring and ... · Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets. Abstract: For

Cracks / contaminated

surface

Carbonized tracking

Discharge noise can be picked up

with Ultrasonic detector via gap

Measurement relies on an

air path from source to

sensor

Types of access

Cable box vents

CB Bushings / HV spouts

Gaps around panel joints

Bolt holes

Contact probe

Designed to work though cabinet

metalwork, no direct air path needed

Surface Discharge

Page 17: Advancements in online partial discharge monitoring and ... · Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets. Abstract: For

Environmental Factors

• Moisture in air will play a significant role in whether discharge is active

• When monitoring ultrasonically the environmental conditions (%RH and Temperature) should also be monitored

0

10

20

30

40

50

60

70

80

90

100

29/03/2005

00:00

03/04/2005

00:00

08/04/2005

00:00

13/04/2005

00:00

18/04/2005

00:00

23/04/2005

00:00

28/04/2005

00:00

03/05/2005

00:00

08/05/2005

00:00

13/05/2005

00:00

Date

%R

H, T

emp

erat

ure

0

1

2

3

4

5

6

7

8

9

10

Lev

el o

f U

ltra

son

ic A

ctiv

ity

°C %RH Ultrasonic

Page 18: Advancements in online partial discharge monitoring and ... · Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets. Abstract: For

Surface Discharge Activity Detected

by Ultrasonic Sensing

Page 19: Advancements in online partial discharge monitoring and ... · Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets. Abstract: For

Tracking due to PD on a panelboard

Page 20: Advancements in online partial discharge monitoring and ... · Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets. Abstract: For

PD Current Pulse Detection using an

RFCTHow Does It Work?

Earth Ground

Phase Reference

Void (PD Site)

Reflected PD Current Pulse

Initial Pulse Reflected Pulse

Distance from RFCT to PD site can be derived from knowing the time between the pulses and the length of the cable

Far end of cable

MeasuringDevice

Page 21: Advancements in online partial discharge monitoring and ... · Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets. Abstract: For

Cable Termination Screen Failure

Found through RFCT sensing

Page 22: Advancements in online partial discharge monitoring and ... · Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets. Abstract: For

Utility Field Results of RFCT Sensing

They classified their results into Green, Amber, & Red

• Green is a test where no partial discharge was found.

• Amber is a test result where some levels of PD were detected.

• Red means that PD levels indicating significant degradation were detected.

UK utility Electricity North West Limited (ENWL) shared the results of a two year evaluation of RFCT based Cable PD detection that involved the online condition assessment of 191 33KV MV cables on their network over a two year period.

Over the course of two years, they experienced the following failure rates:• Red - 41.2%• Amber - 21.7%• Green – 1.9%

Page 23: Advancements in online partial discharge monitoring and ... · Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets. Abstract: For

Internal Partial Discharge Overhead

insulator (EM Wave)

23

EM Wave

PD Hawk

Page 24: Advancements in online partial discharge monitoring and ... · Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets. Abstract: For

Example of Internal PD Found in Outdoor Switchyard

• Internal Partial Discharge in a 12KV Medium Voltage Cable

Phase Resolved Plot Showing Internal Partial Discharge

12KV Medium Voltage Cable

1800

Page 25: Advancements in online partial discharge monitoring and ... · Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets. Abstract: For

Example of Surface PD Found in Outdoor Switchyard

• Surface Partial Discharge in a 66KV Circuit Breaker

66KV Circuit Breaker

1800

Phase Resolved Plot Showing Surface Partial Discharge

Page 26: Advancements in online partial discharge monitoring and ... · Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets. Abstract: For

Re-cap of Non-Intrusive PD Detection Methods

• Metal Clad Switchgear / Busses / Air Cooled Transformers

• Internal discharge – Transient Earth Voltage

• Surface Discharge – Ultrasonic

• Medium, High, and Extra High Voltage Cables

• Internal discharge – RFCT Detection

• Surface Discharge (Terminations) - Ultrasonic

• Air Insulated Switchgear

• Internal discharge – UHF Detection of EMI

• Surface Discharge – Ultrasonic & UHF Detection

• GIS switchgear

• Internal discharge – UHF Detection

Page 27: Advancements in online partial discharge monitoring and ... · Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets. Abstract: For

Recent Advancements in Online - PD Detection

• Phase resolved plots for TEV, Ultrasonic, RFCT, UHF

• Helps discern desired signal from noise

• Waveform plots for TEV, Ultrasonic, RFCT, UHF

• Helps discern desired signal from noise

Page 28: Advancements in online partial discharge monitoring and ... · Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets. Abstract: For

• Automatic PD Detection Algorithms

• Assist user, reduce mis-readings

• NFC (Near Field Communications) Tags

• Eliminate data entry and reduce possible mistakes

Recent Advancements in Online - PD Detection

Page 29: Advancements in online partial discharge monitoring and ... · Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets. Abstract: For

• Full time non-invasive monitoring

• Monitor cables, metal clad switchgear, GIS Switchgear

• On-board storage and report generation with WiFi / USB / HTML

• Promotes standardized test reports and sharing of data

Recent Advancements in Online - PD Detection

Page 30: Advancements in online partial discharge monitoring and ... · Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets. Abstract: For