ADL400 -01- Installation and operation instruction ADL400 three phase electric meter is designed for three phase energy measurement on low voltage system.The meter meet the related technical requirements of electronic meter in the IEC62053-21IEC62053-22 standards. Note:(■: means standard, □:means optional) General Parameters ADL400 Functions kWh (positive and negative) kvarh (positive and negative) A, B, C phase positive kWh UIPQSPFHz 2~31ST harmonic 12 digits 3 keys kWh Maximum demanded Frozen data on last 48 months, last 90days Date, time Infrared RS485, MODBUS-RTU Description Provide Function Measurement of kWh LCD Display Key programming Pulse output Measurement of electrical parameters Measurement of harmonics Data Communication ■ Electric performance 3×100V3×380V3×57.7/100V3×220/380V <10VA(Single phase) >2MΩ ±0.2% Voltage Nominal voltage Consumption Impedance Accuracy ■ Working environment Working Storing -25~55-40~70Humidity Altitude Temperature ≤95%(No condensation) <2000m Dimension drawings (Unit: mm) NoteThe torque of direct connect should not be greater than 4.0N·mand the torque of connect via CT should not be greater than 2.0N·mFigure 1 direct connect Figure 2 connect via CT 80A6A <1VA ±0.2% 4565Hz ±0.2% Class 0.5s Class 2 ≤0.5s/d 80±20ms 1000imp/kWh,10000imp/kWh RS485 Modbus RTU Current Frequency Clock Active Pulse Communication Energy accuracy Maximum current Consumption Accuracy range accuracy Active energy reactive energy accuracy Width constant Interface Protocol

Upload: others

Post on 17-Mar-2022

5 views

Category:

Documents


0 download

TRANSCRIPT

ADL400

-01- Installation and operation instruction

ADL400 three phase electric meter is designed for three phase

energy measurement on low voltage system.The meter meet the related

technical requirements of electronic meter in the IEC62053-21、

IEC62053-22 standards.

Note:(■: means standard, □:means optional)

General

Parameters

ADL400

Functions

kWh (positive and negative)

kvarh (positive and negative)

A, B, C phase positive kWh

U、IP、Q、S、PF、Hz

2~31ST harmonic

12 digits

3 keys

kWh

Maximum demanded

Frozen data on last 48 months,

last 90days

Date, time

Infrared

RS485, MODBUS-RTU

Description ProvideFunction

Measurement of kWh

LCD Display

Key programming

Pulse output

Measurement of electrical parameters

Measurement of harmonics

Data

Communication

■ Electric performance

3×100V、 3×380V、

3×57.7/100V、 3×220/380V

<10VA(Single phase)

>2MΩ

±0.2%

Voltage

Nominal voltage

Consumption

Impedance

Accuracy

■ Working environment

Working

Storing

-25℃~55℃

-40℃~70℃

Humidity

Altitude

Temperature

≤95%(No condensation)

<2000m

Dimension drawings (Unit: mm)

Note:The torque of direct connect should not be greater than 4.0N·m,and the torque of connect via CT should not be greater than 2.0N·m。

Figure 1 direct connect

Figure 2 connect via CT

80A,6A

<1VA

±0.2%

45~65Hz

±0.2%

Class 0.5s

Class 2

≤0.5s/d

80±20ms

1000imp/kWh,10000imp/kWh

RS485

Modbus RTU

Current

Frequency

Clock

Active Pulse

Communication

Energy

accuracy

Maximum current

Consumption

Accuracy

range

accuracy

Active energy

reactive energy

accuracy

Width

constant

Interface

Protocol

ADL400

Installation and operation instruction

Display examples

Wiring and installing

■ Wiring ■ Installing

ADL400 installing

Total active energy

Voltage of three phase

Current of three phase

power

Note:DIN 35 mm rail installation.

Fig 3 Three phase four lines connect via CT

Ua Ub Uc N Ia* Ia Ib* Ib Ic* Ic

A

B

C

N

Fig 4 Three phase four lines direct connect

L1 L1' L2 L2' L3 L3' N

A

B

C

Fig 5 Three phase three lines connect via CT

Ua Ub Uc Ia* Ia Ib* Ib Ic* IcUn

A

B

C

Fig6 Three phase three lines direct connect

N'L1 L1' L2 L2' L3 L3'

A

B

C

Fig 7 Communication, pulse connection

21 22 17 18

A1 B1 Ep+ Ep-

RS485 Active energy pulse