addendum number 2 leitchfield water treatment plant ... · disregard this statement. all special...

38
ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant Leitchfield utilities Commission Bid Opening Date: November 15, 2018 at 2:00 PM local time Date of Addendum: November 8, 2018 Bidders shall conform to the following changes as same shall become binding upon the Contract to be issued in response to the Invitation to Bid. The Contract Documents shall be revised and/or amended as set forth herein: 1. Specification Section 01450 1.3A states Inspection Agency shall be employed by the OWNER. Disregard this statement. All special inspections and material testing shall be done by qualified firm (s) approved by ENGINEER and paid by the CONTRACTOR. 2. Pre-Engineered Metal Building Specification is attached. 3. A revised valve specification Section 13020 is attached. This specification replaces the original 13020. 4. There is no perimeter fencing on the project. Two locking handrail gates are to be provided. See Revised Sheet 5 Attached. 5. Gravel detail attached. 6. Pipe gallery steps are to be poured concrete not steel. 7. Handrail is included in this contract and is not “By Others”. 8. Detail of sidewalk above lower loading bay attached. 9. Final landscaping planting locations to be determined by OWNER. 10. Both loading docks shall be 8” thick poured concrete not asphalt. See Revised Sheet 5 Attached. 11. GAC manufacturer shall supply the header piping and valving for the GAC vessel. See attached drawing to clarify GAC manufacturer scope. 12. Settling Basin Overflow is 24” diameter pipe. Settling basin drain pipe is to be 12” diameter. Sludge System discharge is to be 4” diameter. Combined line from settling basin to lagoon is to be 24” diameter. See revised Sheet 4 and Sheet 9 attached. 13. Existing raw water lines are 36”, 16”, and 10”. Connections to the raw water lines can be made by dry taps or wet taps. 14. Existing high service lines are 16” and 10”. Connections to these lines are by wet tap only. 15. During construction the 16” high service line will be bypassed around the loading docks via the 36” pipe shown on sheet 4. Once construction is complete, the 36” line will be connected to the raw water lines and will switch to raw water service. 16. Excess topsoil and soil can be graded into the water treatment plant property. However, rock shall not be disposed of on the water treatment plant site. The

Upload: others

Post on 27-Apr-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant ... · Disregard this statement. All special inspections and material ... The circuit breaker in MCCB for Transformer T-4 Panel

ADDENDUM NUMBER 2

Leitchfield Water Treatment Plant Leitchfield utilities Commission

Bid Opening Date: November 15, 2018 at 2:00 PM local time Date of Addendum: November 8, 2018 Bidders shall conform to the following changes as same shall become binding upon the Contract to be issued in response to the Invitation to Bid. The Contract Documents shall be revised and/or amended as set forth herein:

1. Specification Section 01450 1.3A states Inspection Agency shall be employed by the OWNER. Disregard this statement. All special inspections and material testing shall be done by qualified firm (s) approved by ENGINEER and paid by the CONTRACTOR.

2. Pre-Engineered Metal Building Specification is attached. 3. A revised valve specification Section 13020 is attached. This specification

replaces the original 13020. 4. There is no perimeter fencing on the project. Two locking handrail gates are to be

provided. See Revised Sheet 5 Attached. 5. Gravel detail attached. 6. Pipe gallery steps are to be poured concrete not steel. 7. Handrail is included in this contract and is not “By Others”. 8. Detail of sidewalk above lower loading bay attached. 9. Final landscaping planting locations to be determined by OWNER. 10. Both loading docks shall be 8” thick poured concrete not asphalt. See Revised

Sheet 5 Attached. 11. GAC manufacturer shall supply the header piping and valving for the GAC

vessel. See attached drawing to clarify GAC manufacturer scope. 12. Settling Basin Overflow is 24” diameter pipe. Settling basin drain pipe is to be

12” diameter. Sludge System discharge is to be 4” diameter. Combined line from settling basin to lagoon is to be 24” diameter. See revised Sheet 4 and Sheet 9 attached.

13. Existing raw water lines are 36”, 16”, and 10”. Connections to the raw water lines can be made by dry taps or wet taps.

14. Existing high service lines are 16” and 10”. Connections to these lines are by wet tap only.

15. During construction the 16” high service line will be bypassed around the loading docks via the 36” pipe shown on sheet 4. Once construction is complete, the 36” line will be connected to the raw water lines and will switch to raw water service.

16. Excess topsoil and soil can be graded into the water treatment plant property. However, rock shall not be disposed of on the water treatment plant site. The

Page 2: ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant ... · Disregard this statement. All special inspections and material ... The circuit breaker in MCCB for Transformer T-4 Panel

CONTRACTOR is responsible for finding suitable location(s) to dispose of the excess material.

17. Disregard the 180 day completion time in the Special Conditions. The contract time is 730 days to substantial completion.

18. Wage rates do not apply to this project. 19. Basement column on 4’-0” x 4’-0” footing shall be 16 inches square reinforced

with 8-#5 bars vertical and #4 ties at 12 inches on-center. 20. Containment around bulk tanks is 4 courses of 8” CMU. Containment around day

tanks shall be 6” concrete curbs. 21. Waterstop specification attached. 22. Stainless steel bolts and nuts for submerged service shall be 316 steel. 23. MCC pre-fabricated building specifications attached. 24. No potassium permanganate saturator is required. 25. Disregard control joint detail on sheet S-1. A construction joint shall be installed

along the basement floor slab parallel to the raw water line creating two large rectangular basement slabs.

26. Provide 6 inches of clean compacted crushed stone under all slabs. 27. Top of pier elevation on the front porch posts shall be 639.33 28. A 6” curb shall be installed around both of the clearwell hatches. 29. Top of retaining wall elevations shall be 640.17, the same elevation as the

finished floor and upper loading dock. 30. A continuous curb shall be installed at the front edge of the parking lot, in front of

all parking spaces. See Revised Sheet 4 31. Curb detail is attached. 32. Exterior stair detail is attached. 33. Flagpole foundation shall be as required by the flagpole manufacturer. The

complete flagpole and foundation is the responsibility of the CONTRACTOR. 34. No blasting on the job per the Special Conditions. 35. Yard piping shall be push joint ductile iron with mechanical joint fittings. 36. Concrete on the first floor of the WTP Building shall be integral color concrete

NOT stained. Owner shall select from colors available. Basement floor and GAC floor will be sealed concrete.

37. Specification Section 03300 (Part 1 2.C): delete reference to Hydrophilic Crystalline Waterproofing.

38. The floor drain from the pump room on sheet 16 shall tie into the 24” backwash drain line.

39. The dollar amount written for Instrumentation, Controls, and Integration is a firm price for using HTI, Inc. Their scope is defined in Specification Section 11505.

40. Disregard Specification Section 11240 2.1 language regarding basis of design and alternates. Sludge collection system shall be by JMS or equal.

41. Contractor shall supply sufficient chemicals to complete all equipment startup. Specific chemicals to be used shall be selected by the owner.

42. Disregard 3. 8” gate valve and 14. lagoon drain vault notes on Sheet 4. 43. The circuit breaker in MCCB for Transformer T-4 Panel PLP shall be 50 A. 44. The feeder to transformer T-4 should be 3 #8+#10 GND, 1”C. 45. The feeder from transformer T-4 to panel PLP should be 4 #2+#8 GND, 1-1/2” C.

Page 3: ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant ... · Disregard this statement. All special inspections and material ... The circuit breaker in MCCB for Transformer T-4 Panel
Page 4: ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant ... · Disregard this statement. All special inspections and material ... The circuit breaker in MCCB for Transformer T-4 Panel

Section 13601 Page 1

Section 13601 – Pre-Engineered Metal Building

1.3.4. Building "Length" is measured from outside to outside of endwall secondary structural member.

1.4. Drawings and Certifications 1.4.1. Drawings: Manufacturer shall furnish complete erection drawings

for the proper identification and assembly of all building components. These drawings shall show anchor bolt settings, transverse cross-sections, sidewall, endwall and roof framing, flashing and sheeting, and accessory installation details.

1.4.2. Certifications: Standard drawings and design analysis shall bear the seal of a registered professional engineer registered in the Commonwealth of Kentucky. Design analysis shall be on file and furnished by manufacturer upon request.

1.4.3. Bills of material requested.

shall be furnished and shall include item weights, if

1. GENERAL

1.1. Scope 1.1.1. These specifications cover the materials and the fabrication of

metal buildings designed, fabricated, and readily erected to be weather tight.

1.1.2. These specifications are an outline of performance to ensure that the CONTRACTOR understands the basis for design, manufacture and application of the entire manufacturer’s metal building system.

1.2. Building Description 1.2.1. A “Traditional Metal Building System” is defined as a building

system that will use either continuous or simple span “Z” purlins for support of the roof covering material.

1.2.2. Gable Symmetrical is a continuous frame building with the ridge in the center of the building, consisting of tapered or straight columns and tapered or straight rafters. The sidewall girts may be continuous (by-passing the columns) or simple span (flush in the column line). The rafters may or may not have interior columns.

1.3. Building Nomenclature 1.3.1. Roof slope is expressed as inches of rise for each 12" of horizontal

run. 1.3.2. Building "Width" is measured from outside to outside of sidewall

secondary structural member (girt). 1.3.3. Building "Eave Height" is a nominal dimension measured from the

finished floor to top flange of eave strut.

2. STRUCTURAL STEEL DESIGN

2.1. General 2.1.1. The building manufacturer shall use standards, specifications,

recommendations, findings and/or interpretations of professionally recognized groups such as AISC, AISI, AAMA, AWS, ASTM, MBMA, Federal Specifications, and unpublished research by MBMA as the basis for establishing design, drafting, fabrication, and quality criteria, practices, and tolerances. For convenience, one or more sources may be referenced in a particular portion of these specifications. In all instances, however, the manufacturer's design, drafting, fabrication and quality criteria, practices, and tolerances shall govern, unless specifically countermanded by the contract documents. All materials shall be designed and fabricated by an AISC - MB category certified manufacturer.

2.1.2. Structural mill sections or welded up plate sections will generally be designed in accordance with the 9th edition of AISC's "Specification for the Design, Fabrication and Erection of Structural Steel for Buildings", ASD method.

2.1.3. Cold-Formed steel structural members will generally be designed in accordance with the latest edition of AISI's "Specifications for the Design of Cold-Formed Steel Structural Members".

2.2. Design Loads 2.2.1. Design loads shall be as specified and set forth in the plans and

specifications, and shall be in accordance with the manufacturer's standard design practices. Design loads may include dead load, roof live loads, wind loads, seismic loads, collateral loads, auxiliary equipment loads, and/or other applied or specified loads.

2.2.2. Dead Load - the actual weight of the building system supported by a given member.

2.2.3. Roof Live Loads - loads produced by maintenance activities, rain, erection activities, and other movable or moving loads but not including wind, snow seismic, crane, or dead loads.

2.2.4. Roof Snow Loads - gravity load induced by the weight of snow or ice on the roof, assumed to act on the horizontal projection of the roof.

2.2.5. Wind Loads - the loads on a structure induced by the forces of wind blowing from any horizontal direction.

2.2.6. Collateral Loads - the weight of any non-moving equipment or material, such as ceilings, electrical or mechanical equipment, sprinkler systems, plumbing, or ceilings.

2.2.7. Auxiliary Loads - dynamic loads induced by cranes, conveyors, or other material handling systems.

2.2.8. Seismic Loads - Loads acting in any direction on a structural system due to the action of an earthquake.

2.2.9. Floor Live Loads - loads induced on a floor system by occupants of a building and their furniture, equipment, etc.

Page 5: ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant ... · Disregard this statement. All special inspections and material ... The circuit breaker in MCCB for Transformer T-4 Panel

Section 13601 Page 2

3. METAL BUILDING SYSTEM BASIC MATERIAL SPECIFICATIONS

3.1. Primary Framing Steel 3.1.1. Steel for hot rolled shapes shall conform to the requirements of

ASTM Specifications A-36 or A992, with minimum yield of 36 or 50 ksi.

3.1.2. Steel for built-up sections shall generally conform to the physical requirements of ASTM A1011, A529, A572 or A36 as applicable, with minimum yield of 55 ksi.

3.1.3. Steel for endwall "C" sections shall conform to the physical requirements of ASTM A1011 Grade 55. Minimum yield shall be 57 ksi.

3.2. Secondary Framing Steel 3.2.1. Steel used to form purlins, girts, and eave struts shall meet the

requirements of ASTM A1011 Grade 55. Minimum yield shall be 57 ksi.

3.3. Roof And Wall Panel Material 3.3.1. Panel material shall be 26 gauge or 24 gauge acrylic coated

Galvalume® or pre-painted Galvalume® as manufactured by Bethlehem Steel Corporation, or equal, conforming to the requirements of ASTM A792 Grade 80 or Grade 50. Minimum yield stress shall be 80 ksi for Grade 80 and 50 ksi for Grade 50.

3.3.2. See Section 5 for additional material used.

3.4. Structural Framing 3.4.1. All framing members shall be shop fabricated for field bolted

assembly. The surfaces of the bolted connections shall be smooth and free from burrs or distortions.

3.4.2. All shop connections shall be in accordance with the manufacturer's standard design practices as specified in Paragraph 2.1.1. Certification of welder qualifications shall be furnished.

Eave Struts: Eave Struts shall be unequal flange cold-formed "C" sections.

3.6.2. Base Angle: A base member will be supplied by which the base of the wall covering may be attached to the perimeter of the slab. This member shall be secured to the concrete slab with ram-sets, expansion bolts, or equivalent anchors as shown on the drawings.

3.7. Bracing 3.7.1. Diagonal Bracing: Diagonal bracing in the roof and sidewalls shall

be used to resist longitudinal loads (wind, crane, seismic, etc.) in the structure. This bracing will be furnished to length and equipped with hillside washers and nuts at each end. It may consist of rods threaded each end or galvanized cable with suitable threaded end anchors. If load requirements so dictate, bracing may be of structural angle and/or pipe, bolted in place.

3.7.2. Flange Braces: The compression flange of all primary framing shall be braced laterally with angles connecting to the webs of purlins or girts so that the flange compressive stress is within allowable limits for any combination of loading.

3.7.3. Special Bracing: When diagonal bracing is not permitted in the sidewall, a rigid frame type portal or fixed base columns will be used. Wind bracing in the roof and/or walls need not be furnished where it can be shown that the diaphragm strength of the roof and/or wall covering is adequate to resist the applied wind forces.

3.8. Roof and Wall Covering 3.8.1. Roof panels shall be standing seam. For standing seam see

Sections 5.2 and 5.3. 3.8.2. Wall panels shall be "PBR”.

3.4.3. All framing members, where necessary,

mark.

shall carry an identifying

3.5. Primary Framing 3.5.1. Rigid Frame: All rigid frames shall be welded built-up "I" sections or

hot-rolled sections. The columns and the rafters may be either uniform depth or tapered. Flanges shall be connected to webs by means of a continuous fillet weld on one side.

3.5.2. Endwall Frames: All endwall roof beams and endwall columns shall be cold-formed "C" sections, mill-rolled sections, or built-up "I" sections depending on design requirements.

3.5.3. Plates, Stiffeners, etc.: All base plates, splice plates, cap plates, and stiffeners shall be factory welded into place on the structural members.

3.5.4. Bolt Holes, etc.: All base plates, splice and flanges shall be shop fabricated to include bolt connection holes. Webs shall be shop fabricated to include bracing holes.

3.5.5. Connections for secondary structural (purlins and girts) shall be ordinary bolted connections, which may include welded clips.

3.5.6. All welding inspection shall be by the manufacturer in accordance with the manufacturer’s AISC – MB category certification. Special inspection by the buyer or owner shall be done in the manufacturer’s facility and shall be noted on the contract documents.

3.6. Secondary Framing 3.6.1. Purlins and Girts: Purlins and girts shall be cold-formed "Z"

sections with stiffened flanges. Flange stiffeners shall be sized to comply with the requirements of the latest edition of AISI. Purlin and girt flanges shall be unequal in width to allow for easier nesting during erection. They shall be pre-punched at the factory to provide for field bolting to the rigid frames. They shall be simple or continuous span as required by design. Connection bolts will install through the purlin webs, not purlin flanges.

5. ROOF AND WALL COVERING 5.1. General. 5.1.1. Standing Seam Roof Panels - see Section 5.2 and 5.3. 5.1.2. "PBR" Panel shall have major ribs 1 1/4" high spaced 12" on

center. In the flat area between the major ribs are two smaller minor ribs. Each panel shall provide 36" net coverage in width. All sidelaps shall be at least one major rib.

5.1.3. Panel Length: All wall panels shall be continuous from sill to roof line and all roof panels shall be continuous from eave to ridge except where lengths become prohibitive for handling purposes. All end laps shall be at least 6" on roof and 4" on walls.

5.1.4. Endwall Edge Cuts: All endwall panels for buildings with 1:12 or less roof slope shall be square cut. All endwall panels for buildings with more than 1:12 roof slope shall be bevel cut by the erector in the field.

Page 6: ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant ... · Disregard this statement. All special inspections and material ... The circuit breaker in MCCB for Transformer T-4 Panel

Section 13601 Page 3

5.2. Standing Seam Roof Panel Type - Ultra-Dek® (Snap Lock) or Double-Lok® (Machine Seamed) 5.2.1. Standing Seam Roof Panels shall be UL-90 rated, roll-formed, 24

5.2.9.3.

tape sealant, furnished in roll form or pre-cut to length. See manual for application. Outside closures shall be manufactured from the same materials as the roof panels.

or 22 gauge acrylic coated Galvalume® or pre-painted Galvalume®. Galvalume® sheet shall have 50% aluminum-zinc alloy–coating with a minimum yield of 50 ksi and conform to ASTM 792-99a. Pre-painted finish shall be a premium Fluoropon¨ coating produced with either Kynar 500® or Hylar 5000® resins and have a full 20 year warranty. Wherever used in this specification, acrylic-coated Galvalume® means Galvalume® with a light acrylic coating such as Galvalume Plus by Bethlehem, Acrylume by National or Galvalume Plus by U.S. Steel. This coating eliminates the need for roll- forming oil and reduces the incidence of field marking by handling or foot traffic.

5.2.2. Panels shall be 24" or 18” wide with 2 minor ribs in between seams. Panel seam shall be 3" high.

5.2.3. One side of the panel shall be female in configuration, which will have factory applied hot-melt mastic (see Sealants And Closures) inside the female seam. The female side will snap over the male side. When using Ultra-Dek® Standing Seam, this procedure will form a self-locking snap system. If choosing Double-Lok® Standing Seam, the male and female seams will be continuously locked together by an electrically powered mechanical seamer, forming a 360-degree Pittsburgh Seam.

5.2.4. The panels shall be factory notched at both ends so that field installation can commence or terminate from either end of the building. Panels cannot start at both ends of the building and work towards each other.

5.2.5. Maximum panel length shall be 45'-0" unless otherwise noted on the purchase order.

5.2.6. Endlaps 5.2.6.1. Endlaps shall have a 16 gauge backup plate. The panel shall have

the eight endlap joint fasteners installed in six pre-punched holes in the flat and in the dimples in the trapezoidal legs.

5.2.6.2. Mastic (see Sealants And Closures) shall be applied between the panels and secured with 1/4" - #14 x 1 1/4 self-drilling fasteners through the panels, and backup plate to form a compression joint.

5.2.6.3. Endlaps and eaves shall be the only places in the roof system where through the roof fasteners can be used inside the building envelope.

5.2.7. Fasteners 5.2.7.1. Eave - 1/4" - #14 x 1 1/4" long life self-drilling with sealing washer. 5.2.7.2. Endlaps - 1/4" - #14 x 1 1/4” long life self-drilling with sealing

washer. 5.2.7.3. Ridge - #14 x 7/8" Lap Tek long life self-drilling with sealing

washer. 5.2.7.4. Clips/to purlin - 1/4" - #14 x 1 1/4" Tek 2 long life self-drilling with

Hex Washer Head and 5/8" O.D. washer. 5.2.7.5. Clips/floating to bar joists - #12-24 x 1 1/4" Tek 4.5 self-drilling with

Washer Head and 5/8" O.D. washer. 5.2.7.6. Long Life fasteners, where exposed, are standard when using an

acrylic coated Galvalume® roof panel. 5.2.8. Clips 5.2.8.1. All clips shall have factory-applied mastic and be designed so that

movement between the panel and the clip does not occur. 5.2.8.2. Ultra-Dek Low fixed clips - shall be 3 3/8" in height providing a 3/8"

clearance for insulation between the panel and the purlin or joist. 5.2.8.3. Ultra-Dek High fixed clips - shall be 4 3/8" in height to

accommodate a thermal spacer for added insulation at the purlins. 5.2.8.4. Ultra-Dek or Double-Lok Low or High floating clips - shall be either

3 3/8" or 4 3/8" in height. Floating clips shall provide a minimum of 2" travel to allow for expansion and contraction.

5.2.9. Sealant And Closures 5.2.9.1. Factory applied sealant used in panel sidelaps shall be a hot melt,

foamable mastic - Q41A.

5.2.9.2. Field applied sealant used at the endlaps, eave, ridge assembly, and gable flashings shall be 100% solids butyl-based elastomeric

Page 7: ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant ... · Disregard this statement. All special inspections and material ... The circuit breaker in MCCB for Transformer T-4 Panel

Section 13601 Page 4

5.2.9.4. Inside closures shall be 18-gauge Galvalume ® or galvanized coated metal.

5.3. Standing Seam Roof Panel Type - BattenLok® (Machine Seamed) and SuperLok®

(Machine Seamed) 5.3.1. Panel Description 5.3.1.1. Standing Seam Roof Panels shall be UL-90 rated, roll-formed, 24

or 22 gauge acrylic coated Galvalume® or pre-painted Galvalume®. Galvalume® sheet shall have 50% aluminum-zinc alloy–coating with a minimum yield of 50 ksi and conform to ASTM 792–99a. Pre-painted finish shall be a premium Fluoropon¨ coating produced with either Kynar 500® or Hylar 5000® resins and have a full 20 year warranty. Wherever used in this specification, acylic-coated Galvalume® means Galvalume®

with a light acrylic coating such as Galvalume Plus by Bethlehem, Acrylume by National or Galvalume Plus by U.S. Steel. This coating eliminates the need for roll- forming oil and reduces the incidence of field marking by handling or foot traffic.

5.3.1.2. Panel profiles shall be 2" inches high x 16" wide. Panel seam is 2" high. All panels shall be striated.

5.3.1.3. One side of the panel shall be female in configuration, which will have factory applied hot-melt mastic (see Sealants And Closures) inside the female seam. The female side will fit over the male side and be continuously locked together by an electrically powered mechanical seamer.

5.3.1.4. Maximum panel length shall be no more than 45'-0" unless otherwise discussed and approved by the manufacturer.

5.3.2. Endlaps 5.3.2.1. Endlaps shall have pre-punched holes in panels and a 16 gauge

backup plate for proper placement of fasteners. 5.3.2.2. Mastic (see Sealants And Closures) shall be applied between the

panels and secured with #14 x 1 1/4" Long Life self-drilling fasteners with sealing washer, through the upper panel, mastic, lower panel and backup plate to form a compression joint.

5.3.2.3. Endlaps and eaves shall be the only places in the roof system where through-the-roof exposed fasteners will be used inside the building envelope.

5.3.3. Fasteners 5.3.3.1. Eave - #12 x 1 1/4" long life self-drilling with sealing washer. 5.3.3.2. Endlaps - #14 x 1 1/4" long life self-drilling with sealing washer. 5.3.3.3. Ridge - #14 x 7/8" Lap Tek long life self-drilling with sealing

washer. 5.3.3.4. Clips to purlin - #12 x 1 1/4" Tek 2 self-drilling with Hex Head

without washer. 5.3.3.5. Clips to bar joists - #12-24 x 1 1/4" Tek 4.5 self-drilling with Hex

Head without washer. 5.3.3.6. Long Life fasteners, where exposed, either self-drilling or self-

tapping, utilizing corrosion resistant head with an extended long life warranty, are standard. These fasteners are recommended for use when using an acrylic coated Galvalume® roof panel.

5.3.3.7. Special applications may require the use of other fastener types than those listed above.

5.3.4. Clips 5.3.4.1. All clips shall have factory-applied mastic. 5.3.4.2. Fixed clips - shall be either 2 3/8" or 3" in height and are to be

used with blanket insulation. 5.3.4.3. Floating clips - shall be either 2 3/8" or 3" in height and are to be

used with blanket insulation. 5.3.5. Sealants And Closures 5.3.5.1. Factory applied sealant used in panel sidelaps shall be a hot

melt, foamable mastic - Q41A. 5.3.5.2. Field applied sealant used at the endlaps, eave, ridge assembly,

and gable flashings shall be 100% solids butyl-based elastomeric tape sealer, furnished in roll form or pre-cut to length.

Page 8: ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant ... · Disregard this statement. All special inspections and material ... The circuit breaker in MCCB for Transformer T-4 Panel

Section 13601 Page 5

5.3.5.3. Outside closures shall be manufactured from the same materials as the roof panels.

6. MISCELLANEOUS MATERIAL SPECIFICATIONS

6.1. Fasteners 6.1.1. Structural Bolts: All bolts used in connections of secondary

framing to primary framing shall be zinc plated ASTM A307 or ASTM A325 as required by design.

6.1.2. Fasteners for Roof Panels: All panels shall be attached to the secondary framing members by means of: a. Option #1: Self-drilling structural screws for roofs shall be

carbon steel #12-14 x 1 1/4" Hex Washer Head, cadmium or zinc plated, with or without painted head, assembled with EPDM washer. These fasteners are applicable for use with fiberglass blanket insulation from 1" to 3" thick.

b. Option #2: Self-drilling structural screws shall be carbon steel #12-14 x 1 1/2" Hex Washer Head, cadmium or zinc plated, with or without painted head, assembled with EPDM washer. These fasteners are applicable for use with fiberglass blanket insulation from 3 1/2" to 6" thick.

c. Option #3: Self-tapping screws shall be #14 x 3/4" type "A" or "AB", zinc plated, painted or plain head assembled with a bonded or separate EPDM washer. These fasteners are applicable for use with fiberglass blanket insulation from 1" to 3" thick. Longer lengths are available. Pre-drilling is required.

d. Option #4: Optional Long Life fastener, in either self-tapping or self-drilling fasteners. Recommended when using acrylic coated Galvalume® panels.

6.1.3. Fasteners for Roof Panel Sidelaps are as follows: a. Option #1: Self-drilling - #14 x 7/8" Lap Tek zinc plated,

painted or plain head assembled with sealing washer. b. Option #2: Above fasteners in a Long Life finish, either in self-

drilling or self-tapping. Corrosion resistant head with a long life extended warranty. These fasteners are recommended when using acrylic coated Galvalume® panels.

c. Option #3: Self-tapping - #14 x 3/4" type "A" or "AB" zinc plated, painted or plain head assembled with sealing washer.

6.1.4. Fasteners for the Standing Seam Roof Panels and clips: See Sections 5.2.7 and 5.3.3.

6.1.5. Fasteners for Wall Panels: All "PBR" Panels shall be attached to the secondary framing members by means of: a. Option #1: Self-drilling fasteners of carbon steel #12 x 1 1/4"

without washers as herein described for fiberglass insulation up to 3" thick and #12 x 1 1/2" for fiberglass insulation 3" to 6" thick.

b. Option #2: Corrosion resistant type Long Life fasteners with sealing washers, either self-tapping or self-drilling, as herein described.

c. Option #3: Self-tapping #14 x 3/4" carbon steel fasteners as herein described. These fasteners are applicable with fiberglass insulation up to 3" thick. #14 x 1-1/2" fasteners are required for 3" to 6" thick insulation. Pre-drilling is required.

6.1.6. Fasteners for Wall Panel Sidelaps: a. Option #1: Self-drilling - #14 x 7/8" carbon steel screws as

herein described. b. Option #2: Corrosion resistant type Long Life fasteners with

sealing washers, either self-drilling or self-tapping, as herein described.

c. Option #3: Self-tapping - #14 x 3/4" carbon steel screws as herein described. Pre-drilling is required.

6.1.7. Blind Rivets: All blind rivets shall be 1/8" diameter, high strength stainless steel pull rivet Type ADH.

6.2. Sealants And Closures 6.2.1. Closure Strips: the corrugations of the roof and wall panels shall be

filled with closures along the eave, ridge rake or base when required for weather tightness. Closures must be ordered separately.

6.2.2. Standing Seam Roof Closures: See Sections 5.2.9 and 5.3.5. 6.2.3. Standing Seam Sealant: See Sections 5.2.9 & 5.3.5. 6.2.4. Caulk: All gutter and downspout joints, rake flashing laps, ridge

flashing laps, doors, windows, and louvers shall be sealed with white, burnished slate, or gray pigmented caulk of Butyl rubber base, or clear silicone.

6.3. Gutter, Flashing And Downspouts 6.3.1. Gutters and Flashing: All standard exterior gutters are 26 gauge

steel with a painted finish in standard colors. Standard rake flashing is 26 gauge steel with painted finish in standard colors.

6.3.2. Downspouts: All downspouts shall be 26 gauge, rectangular in shape, steel with painted finish in standard colors.

6.3.3. Gutters and downspouts shall be sized according to ordinary industry practices to handle rainwater. Special provisions for rainwater over flow, icing, and blocked downspouts should be considered by the builder and owner.

6.4. Flashing And Trim 6.4.1. Flashing at the rake (parallel to roof panels) and high eave shall

not compromise the integrity of the roof system by constricting movement due to thermal expansion and contraction.

6.4.2. All flashing shall be manufactured from Galvalume® steel, whether pre-painted or acrylic coated Galvalume.

6.5. Painting 6.5.1. Structural Painting 6.5.1.1. All uncoated structural steel shall be cleaned of all foreign matter

and loose scale in accordance with SSPC-SP2 and given a one mil coat of red oxide primer. Primer shall be applied by the use of airless handguns or by dip-tank emersion. Primer generally meets or exceeds the performance requirements of Federal Specification TT-P-636D.

6.5.1.2. Light gauge “Z” and “C” section steel members shall be shot blasted and pre-coated with one coat of red oxide primer. Some hand sprayed shop touch-up may be employed.

6.5.1.3. Abrasions caused by handling after painting are to be expected. Primer shall be furnished to touch-up or field painting as specified in the contract documents.

6.6. Painted Steel Panels 6.6.1. Base metal shall be nominal 26 gauge Galvalume® steel. 6.6.2. Prime Coat: The base metal shall be pre-treated and then primed

with an epoxy type primer for superior adhesion and superior resistance to corrosion.

Page 9: ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant ... · Disregard this statement. All special inspections and material ... The circuit breaker in MCCB for Transformer T-4 Panel

Section 13601 Page 6

7. ACCESSORIES 7.1. Personnel Doors 7.1.1. Standard personnel doors shall be of sizes shown on drawings

manufactured from 20 gauge galvanized steel. Door shall have square edges for non-handed installation. Door shall have an embossed finish with a white or bronze prime coat. Doors shall be flush and have vertical mechanical interlocking seams on both hinge and lock edges. Doors shall be provided with top and bottom inverted 16 gauge galvanized steel channels spot-welded within the door. Doors shall be reinforced, stiffened, and sound deadened with resin impregnated kraft fiber honeycomb core with a nominal 1" cell size. Honeycomb core shall completely fill the inside faces of the door and be laminated to the inside faces of the panels by means of moisture resistant, contact type adhesive. Doors shall be reinforced for applicable hardware. Doors shall be solid.

7.1.2. Door frames shall be 16 gauge galvanized steel, pre-painted white. Door jambs shall be constructed for non-hand installation. Door frames shall optional head and jamb flashing and optional weather strip. Door frames shall be provided with 1-1/2 pair of 4-1/2" x 4- 1/2" hinges and reversible ANSI strike plate. Doors and frames shall be reinforced with 7 gauge hinge reinforcements.

7.1.3. Standard cylindrical lever locksets (levers both sides) shall meet ANSI #A156.2, Series 4000, Grade 2. The lockset selected by owner shall be in accordance with all current federal, state and local laws for the type of access required and the nature of use of the building.

7.1.4. Door threshold shall be aluminum, supplied with flat head fasteners and expansion shields for attachment to masonry floor.

7.2. Overhead Door Framing 7.2.1. Overhead door support framing shall be designed to resist

applicable wind loads and shall consist of channel jambs with a structural header at the top of the opening. Twenty-six gauge galvanized steel flashings, color coordinated, shall be provided to conceal panel edges around the opening when requested.

7.3. Gravity Ridge Ventilators 7.3.1. Gravity ridge ventilators shall be manufactured from galvanized

steel and painted white. The ventilator body shall be 26 gauge and the skirt shall match the roof slope. Chain operated damper shall be furnished. Ventilators shall be equipped with standard bird screens and riveted end caps. Ventilators shall be 10' long and have 12” throat.

7.4. Louvers 7.4.1. Louvers shall be as shown on drawings.

7.5. Insulation 7.5.1. Fiberglass Blanket Insulation shall have a density of 0.75 pcf and

shall be available 6” thickness. 7.5.2. Fiberglass insulation facings shall be laminated on one side with

vinyl facing. 8. ERECTION AND INSTALLATION 8.1. Erection and Installation 8.1.1. A qualified erector, using proper tools and equipment shall perform

the erection of the metal building components. Erector shall follow good, sound, safe procedures and guidelines in accordance with any applicable federal, state or local laws.

8.1.2. Erection of the roof system shall be in complete accordance with the Manufacturer's Safety and Erection Manual.

8.1.3. Should the erector need building component weights, these shall be supplied by the manufacturer upon request.

9. BUILDING ANCHORAGE

AND FOUNDATIONS 9.1. Building Anchorage and Foundations 9.1.1. The building anchor bolts shall be designed to resist the maximum

column reactions resulting from the specified combinations of loadings. The manufacturer shall specify the minimum diameter, spacing and projections required to transfer the loads from the column to the anchor bolts. Anchor bolts will be supplied by the contractor and NOT by the manufacturer. Anchor bolt quantity at each base plate shall be in compliance with OSHA Subpart R regulations.

9.1.2. Foundations shall be adequately designed by a registered engineer registered in the Commonwealth of Kentucky to support the building reactions and other loads that may be imposed by the building use. The design shall be based on the specific soil conditions of the building site.

10. The building manufacturer shall furnish complete shop and erection drawings showing anchor bolt settings, sidewall, endwall, and roof framing, transverse cross sections, coverings and flashing details, and accessory installation details to clearly indicate the proper assembly of all building parts. Shop drawings must be prepared, sealed, and signed by a registered engineer registered in the Commonwealth of Kentucky. Design calculations and a letter of certification, signed and sealed by a registered engineer registered in the Commonwealth of Kentucky shall be submitted to Cann-Tech, LLC for the structural framing and roof and wall panels of the metal building.

Page 10: ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant ... · Disregard this statement. All special inspections and material ... The circuit breaker in MCCB for Transformer T-4 Panel

VALVES 13020-1

SECTION 13020 VALVES PART 1 GENERAL 1.01 SCOPE OF WORK Provide all labor, materials, equipment and services required to furnish and install all new valves and rebuild all existing valves as shown on the Drawings and/or specified herein. 1.02 RELATED WORK SPECIFIED ELSEWHERE

A. Yard Piping: Section 02500 B. In Plant Piping: Section 13010 C. Plumbing Valves: Section 15100 D. Plumbing Piping: Section 15410 E. Valves furnished with equipment are included with equipment specifications. F. Operating and Monitoring Systems: Section 13400

1.03 SUBMITTALS

Descriptive literature, catalog cuts, and dimensional prints clearly indicating all dimensions and materials of construction, shall be submitted on all items specified herein to the Engineer for review before ordering. Comply with provisions of Section 01340.

At the time of submission, me Contractor shall, in writing, call Engineer's attention to any deviations that the submittals may have from the requirements of the Engineer's Contract Drawings and Specifications.

PART 2 PRODUCTS 2.01 PLUG VALVES

Plug valves shall be non-lubricated eccentric type with resilient faced plugs and flanged ends faced and drilled ANSI B16.1 125-pound. Valves shall be furnished with corrosion resistant metal seats complying with AWWA C 507-73 Section 7.2; replaceable sleeve type bearings in the upper and lower journals, complying with AWWA C 507-73 Sections 8.1, 8.3, and 8.4; and shaft seals complying wnh AWWA C 507-73 Section 10. Valves shall provide drip-tight shutoff up to the full pressure rating. All plug valves shall be provided with limit stops and rotate 90° from fully opened to fully closed.

All in-plant plug valves shall be manually operated, with worm gear operator handwheel (4" and larger) or lever (3" and smaller). Plug valves located 6 feet or more above the floor shall be furnished with chain wheel operators. Plug valves shall be as manufactured by DeZurik, Keystone, Kennedy Valve, or equal.

Page 11: ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant ... · Disregard this statement. All special inspections and material ... The circuit breaker in MCCB for Transformer T-4 Panel

VALVES 13020-2

2.02 GATE VALVES

Gate valves shall be AWWA C509, resilient seat type, iron body ,non-rising stem, flanged ends, handwheel operated, rated for the working pressure of the line the valve is serving. Gate valves shall be as manufactured by Mueller, M&H, Clow, American Valve & Hydrant, Kennedy Valve, or equal.

2.03 SWING CHECK VALVES (LIQUID SERVICE)

Check valves shall be iron body, bronze mounted, horizontal swing check type, spring loaded suitable for horizontal or vertical service, Kennedy Valve, M&H, Clow or equal.

2.04 AIR VALVES FOR VERTICAL TURBINE PUMPS

Air valves for the high service vertical turbine pumps, shall vent large quantities of air out through the orifice when pump starts, close tight when liquid enters, permit large quantities of air to re-enter through the orifice when pump stops, and prevent vacuum from forming in the pump suction column. The main valve parts shall be a body, cover, baffle, float and seat. The baffle shall shield float from direct impact of air and water to prevent premature float closure. The seat shall slip fit into the fabble or cover and lock in place without any distortion, but remain easily removable. For sizes ½” through 3", the entire float and baffle assembly must be shrouded with a water diffuser to prevent water slamming the float shut. All outlets to be threaded or flanged. The float shall be stainless steel center guided (not free floating) for positive seating and rated 1000 psi non-shock service. The discharge orifice shall be fitted with a DOUBLE-ACTING THROTTLING DEVICE, Patented, to regulate and restrict air venting to establish a pressure loading on the rising suction column of water to eliminate damaging shock to me pump, controls and check valve on pump start. On pump stop, the DOUBLE ACTING THROTTLING DEVICE shall automatically open allowing fall line unrestricted air re-entry to prevent any measure of vacuum to form in the suction column. Valve exterior to be painted with Red Oxide Phenolic Primer Paint as accepted by the FDA for use in contact with Potable Water. Materials of construction shall be certified conforming to following A.S.T.M. specification:

COMPONENT MATERIAL ASTM SPECIFICATION Body, cover Cast iron ASTM A126 Gr. B Baffle, Sizes ½”, 1” & 2” Delrin ASTM D2133 Baffle, Size 3" Cast iron ASTM A48 CL 30 Float Stainless steel ASTM A240 Seat Buna-N Water Diffuser Brass ASTM B 16 Double Acting Throttling Device Patented

Housing Malleable iron ASTM A47 Adj. Screw & Nut Stainless steel ASTM A276 T304 Spring Stainless steel ASTM A313 T316 Plug Teflon AMS3651

Air Valve is to be APCO Series 140DAT Air & Vacuum Valve with Double Acting Throttling Device & Water Diffuser, as manufacturered by Valve & Primer Corporation, Schaumburg, Illinois, U.SA, or equal.

Page 12: ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant ... · Disregard this statement. All special inspections and material ... The circuit breaker in MCCB for Transformer T-4 Panel

VALVES 13020-3

2.05 PLASTIC VALVES

A. Ball Valves:

Plastic ball valves (shut-off valves) shall be Chemtrol TU Series 150 psi threaded true union ball valves as manufactured by Chemtrol Industrial Products NIBCO, Inc., Louisville, Kentucky; Hayward Manufacturing Co., Inc., Elizabeth, New Jersey; or equal, NSF listed for potable water. Valves for PVC shall be manufactured of PVC material and valves for CPVC lines shall be manufactured of CPVC material. Install so indicator arrow is in direction of flow.

B. Check Valves: Plastic check valves shall be threaded Chemtrol B C Series ball check type as manufactured by Chemtrol Industrial Products NIBCO, Inc., Louisville, Kentucky; ball check by Hayward Manufacturing Co., Elizabeth, New Jersey; or equal, NSF listed for potable water. Valves for PVC lines shall be manufactured of PVC material and valves for CPVC lines shall be manufactured of CPVC material. Install so indicator arrow is in direction of flow.

2.06 BUTTERFLY VALVES All butterfly valves shall be of the tight closing, rubber or synthetic rubber seat type with seats securely fastened to valve body. No metal-to-metal seating surfaces will be permitted. Valves shall be bubble tight at the rated pressure in either direction and shall be satisfactory for applications

involving throttling service and/or frequent operation and for applications involving valve operation after long periods of inactivity. The valve discs shall rotate 90° from the full open position to the tight shut position. The valve bodies , themselves shall be of the flanged style, exact where specifically noted on the Drawings. Flanged or ' wafer bodies shall have a retained seat and shall provide tight shutoff up to full valve rating on deadend or isolation service without the use of downstream flange. Valve bodies shall be constructed of cast iron ASTM A-126, Class B, and shall be suitable for use with #125 ANSI flanges. Valves shall meet the full structural requirements of the applicable classes ofAWWA C 504 (Latest Edition). All valves unless indicated on Drawing or Specifications shall be rated for 150 psi. The valve discs shall be cast iron or semi-steel with a welded nickel edge free of ribbing or protrusions which may collect solids. The disc-to-shaft connections shall be via polished 316 SS pins. Sprayed or plated disc are not acceptable. The shafts shall be turned, ground and polished. They shall be 18-8 Type 316 Stainless Steel with diameters per AWWA Spec. C504 (Latest Edition), Class 150B. The shafts shall be of one-piece construction. The shaft seals shall be of Hycar or Hypalon and shall be provided to prevent leakage into the bearing chest areas. The valve bearings shall be Teflon coated, self-lubricating, stainless steel design and construction. The valve seats shall be Neoprene or Hypalon and shall be simultaneously molded, vulcanized and bonded to the valve body. All surfaces of the valve shall be clean, dry and free from grease before painting. The valve surfaces except for disc, seating and finished portions shall be evenly coated at the factory with a suitable rust inhibitive primer. Hydrostatic and leakage tests shall be conducted in strict accordance with AWWA C504 (latest Edition), Section 12. The valves shall be as manufactured by Kennedy Valve, Pratt, Dresser, DeZurik or equal. A. Manually Operated Butterfly Valves

Manually operated valves shall be operated using a cast iron housed handwheel or chain wheel, as required, available in standard weatherproof construction. All units shall have adjustable open and close position stops, with provisions to prevent accidental adjustment changes. The operating shaft shall be supported,

Page 13: ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant ... · Disregard this statement. All special inspections and material ... The circuit breaker in MCCB for Transformer T-4 Panel

VALVES 13020-4

axially and radially, at the input end by permanently lubricated bronze thrust and sleeve bearings.

B. Electric Motor Operators 1. General

Electric motor operators shall be designed to move the valve from fully open to fully closed with operating speeds such that no undue surge or water hammer occurs when electrical power is applied, and hold the valve disc in any intermediate position between fully open to fully closed without creeping or fluttering. Valve, gear, reducer, electric motor operator and accessories shall be furnished complete, ready for installation.

2. Actuator and Gearing

The actuator shall be of worm and gear, single reduction design with provision for input spur or bevel gear assemblies to meet a given rim pull or input torque requirement The input shaft of the manual shall be an extension of the worm shaft, which is a hardened alloy steel. The mating worm gear shall be alloy bronze, accurately cut by bobbing machines. All gearing shall be greased lubricated. Ball or roller bearings shall be used to provide smooth rotation of the worm shaft.

All units shall be provided with a pointer assembly for valve position indication.

All units shall be readily field adaptable to motor operation without disassembly of the manual actuator.

The actuator shall comply with AWWA-C-504-80 specifications.

3. Mechanical Stops

The actuator shall house an adjustable mechanical stop device to prevent travel beyond the valve requirement The stop shall allow valve travel of 90' with a minimum adjust ability of +5\ All stops shall be of steel material.

4. Output Drive

The actuator shall have a removable splined adapter which shall be machined to accept the valve shaft. This adapter material shall be of carbon steel.

5. Electric Actuator

The electric valve actuator shall include the motor, operator unit gearing, limit switch gearing, limit switches, torque switches, stem nut, declutch lever, and auxiliary handwheel, as a self-contained unit. The actuator shall meet AWWA-C-504-80 specifications.

6. Enclosure

The valve actuator motor and all electrical enclosures shall be NEMA 4X, weatherproof, with a 120 volt heater. Unit shall be furnished with a reversing contactor suitable for mounting at any angle. Local control to be provided by a three position selector switch, OPEN-OFF-CLOSE, and a padlockable REMOTE-OFF-LOCAL selector switch. Controls shall be in a remote enclosure separate from me actuator.

7. Motor

The motor shall be specifically designed to operate on 460 volt three phase for valve actuator service and shall be of high starting torque, totally enclosed, nonventilated construction. Motor leads shall be brought into the control compartment or limit switch compartment without external piping or conduit boxes. Motor insulation shall be a minimum NEMA Class B with winding thermostat and a 15 minute rating without exceeding temperature rise.

Page 14: ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant ... · Disregard this statement. All special inspections and material ... The circuit breaker in MCCB for Transformer T-4 Panel

VALVES 13020-5

The motor shall be of sufficient size to open or close the valve against the maximum expected differential pressure within 60 seconds when voltage of the motor terminals is 10 percent above or below nominal voltage. The motor duty rating shall be 15 minutes without exceeding its temperature rating. The motor shall be prelubricated and all bearings shall be of the anti-friction type.

8. Electric Actuator Gearing

The actuator shall be a double reduction unit with the capability of changing the output speed with a relatively fast, simple gear change. The power gearing shall consist of spur or helical gears and worm gearing. The spur or helical gearing and work shall be of hardened alloy steel and the worm gear shall be alloy bronze. All gearing shall be accurately cut with nobbing machines. All power gearing shall be grease lubricated. Ball or roller bearings shall be used throughout.

9. Position Limit Switch

Position limit switches and associated gearing shall be an integral part of the valve actuator. Limit switch gearing shall be of the intermittent type, made of bronze or stainless steel, grease-lubricated, and enclosed in its own gear case to prevent dirt and foreign matter from entering the gear train. Switches shall be adjustable, allowing for trip points from fully open to fully closed positions of valve travel. They shall not be subject to breakage or slippage due to over travel. Limit switches shall be of the heavy duty, open contact type with a rotary wiping action. Each valve actuator shall have a minimum of eight heavy duty contacts with two or four rotor-type switch assemblies. Limit switches shall shut-off the actuator once a desired valve disc location is reached in position seat application. The gear limit switch and torque switch shall carry a standard pilot duty rating as tabulated below:

Voltage 120 A.C.

10. Torque Switch

Each valve actuator shall be equipped with a double torque switch which is responsive to loads encountered in both the opening and closing direction. Each side of the switch shall have a graduated dial and shall be adjustable. A calibration tag shall be mounted near each switch correlating the dial setting with the unit output torque. The torque switch shall operate during the complete valve cycle without the use of auxiliary relays, linkages, latches, or other devices. The torque switch shall be designed to shut off the actuator motor in the event that abnormally high torque is realized in either direction of travel. The torque switch is utilized as a protective device in valve applications requiring position seating.

11. Manual Operation

A handwheel shall be provided for manual operation. The handwheel shall not rotate during motor operation. A fused motor shall not prevent manual operation. When in manual operating position, the unit will remain in this position. The actuator will remain in motor position when the motor is energized. The actuator will remain in motor position until handwheel operation is accomplished by a positive declutching lever which disengages the motor and related gearing mechanically but not electrically. It shall not be possible for the unit to be simultaneously in manual and motor operation.

Page 15: ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant ... · Disregard this statement. All special inspections and material ... The circuit breaker in MCCB for Transformer T-4 Panel

VALVES 13020-6

12. Hammerblow Device

The valve control shall have a built-in lost motion device which allows the motor to reach full speed before imparting a hammerblow to move the valve. This lost motion device allows the load to be shared equally by two lugs cast integrally on the drive sleeve. This feature is not required for modulating services.

13. Electrical Requirements The actuator shall be powered by a clearly defined 460 volt, 3-phase power supply, and all controls shall function on a stated control source and voltage. Electrical controls to be supplied by the actuator manufacturer as indicated in the specifications.

14. Control Valve Operator shall accommodate the following for remote control of On/Off-Open/Closed operation type controls when the valve operator is selected to the Remote position via the local control switch. Open command from remote device via a dry contact closure Close command from remote device via a dry contact closure Full open indication to remote device via a dry contact closure Full closed indication to remote device via a dry contact closure Valve operator fault indication to remote device via a dry contact closure Valve operator in remote position indication to remote device via a dry contact closure Valve Operator shall accommodate the following for remote control of Modulating operation type controls when the valve operator is selected to the Remote position via the local control switch. 4-20mA position demand from remote device 4-20mA position feedback to remote device Full open indication to remote device via a dry contact closure Full closed indication to remote device via a dry contact closure Valve operator fault indication to remote device via a dry contact closure Valve operator in remote position indication to remote device via a dry contact closure

15. Manufacturer Electric motor operators shall be as manufactured by Pratt, Auma, Rotork, Limitorque, or equal.

2.07 MUD VALVES A. Mud valves shall be of the iron body, bronze mounted type with rising stems, flanged ends, extension stem,

2 inch square operating nut, handwheel and open by turning left. B. The frame, yoke, and gate shall be sturdily proportioned for strength and rigidity and be of cast iron

conforming to ASTM specifications A 126 Class B. C. The stem, stem nut, and seats shall be bronze. The stem shall be machined with accurately cut modified

acme threads. D. The gate seat shall be rolled into a dovetailed groove under pressure to make one inseparable unit. The body

(frame) seat ring shall be threaded and screwed into place in the frame. E. Both gate and body seat ring faces shall be machined to a smooth finish. F. Mud valves shall be manufactured by M&H or approved equal.

Page 16: ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant ... · Disregard this statement. All special inspections and material ... The circuit breaker in MCCB for Transformer T-4 Panel

VALVES 13020-7

2.08 CUSHIONED SWING CHECK VALVES - OIL CONTROL SIDE-MOUNTED (FOR BACKWASH PUMPS) The cushioned swing check valve body shall be cast iron per AWWA C508 with integral flanges (not Wafer) and have a centrifugally cast bronze body seal The seat shall be locked in place with stainless lock screws and be field replaceable, without the use of special tools. The pivot shaft shall be one (1) piece hi-strength Type 17-4PH stainless steel, extending thru both sides of the valve body. For control open and three state closing: side mounted hydraulic cylinders shall provide control opening andclosing speeds for the prevention of surge and water hammer. The cylinders must have - two (2) stages of control during the closing cycle and a third stage, by means of a timing valve, to permit instant closure of the disc from fullopen to any degree of closure on pump stop. typically as follows:

1st stage: instant closure to any degree 2nd stage: stage variable slow closure towards final closure 3rd stage: stage variable closure to shut-off

Each stage shall be infinitely, independently adjustable and the oil system self-contained and separate from the main line media. The valve shall control close, while flow reverses in the pipeline during normal pump shut-off or power failure in a time sequence to prevent water hammer. Each stage closure shall be field adjustable. The disc shall have a double device hinge connected to a ductile iron disc arm. The disc arm assembly shall be suspended from the stainless steel shaft. The disc seat shall be Buna-N (replaceable) to provide water-tight shut-off. Materials shall be certified to the following ASTM specifications: COMPONENT MATERIAL ASTM SPECIFICATION Body & Cover Cast Iron ASTM A126,GR. B Disc Cast Iron ASTM A126, Gr.B Disc Arm Ductile Iron ASTM A536 Body Seat Ring Aluminum Bronze ASTM B 148 Disc Seat Buna-N Dashpot Cylinder Steel Per N.F.P.A. Standards Pivot Shaft Stainless Steel Type 17-4PH Exterior Paint Phenolic Primer FDA Approved For Red Oxide Potable Water Contact Valve to be APCO Series 6100 Cushioned Swing Check Valve - Oil control side mounted, as manufactured by Valve & Primer Corporation, Schaumburg, Illinois, or equal.

2.09 VALVE OPERATORS

Valve operators shall be as shown on the plans and specified herein and in Section 13400. Special operators where shown on the plans shall be furnished under this item and Section 13400. Valves shall be positioned to provide for the most convenient position of the actuator possible. Valves located six (6) feet or more from floor level shall be furnished with chain wheel operators or chainlevel operators. Chains shall extend to within four (4) feet off the floor. All NRS floor stands and geared operators shall be indicating type.

2.10 VALVE VAULTS

All buried service valves shall be supplied with a valve vault, as indicated on the Contract Drawings. Valve Vaults shall be reinforced concrete, of the dimensions shown on the Drawings.

Page 17: ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant ... · Disregard this statement. All special inspections and material ... The circuit breaker in MCCB for Transformer T-4 Panel

VALVES 13020-8

PART 3 EXECUTION 3.01 INSTALLATION

All valves shall be installed in accordance with the manufacturer's recommendations.

END OF SECTION

Page 18: ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant ... · Disregard this statement. All special inspections and material ... The circuit breaker in MCCB for Transformer T-4 Panel

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

OHE

OHE

OHE

OHE

OHE

OHE

OHE

OHE

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE

OHE

OHE

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

CL

CL

CL

C

L

C

LC

LC

LC

LC

L

ST

A

TE OF KENTUCK

Y

PR

OFESSIONAL ENGIN

EE

R

MATTHEWBAKER24507

LICENSED

RECORD DRAWINGS

CHECKED BY:

DRAWN BY:

DESIGNED BY:

PROJECT:

SCALE:

SHEET

OF

AS NOTED

MAB

JH

19

5

PROPOSED LANDSCAPING PLANMAB

433 DATE: 10/24/2018

APPR'D DATEDATEREVISIONSDATENO.

S 21°40'49" E 669.95'

S

3

9

°

4

3

'

3

5

"

W

1

3

0

.

0

0

'

S

4

2

°

5

1

'3

3

"

W

1

5

3

.

7

9

'

N

3

0

°3

2

'1

4

" W

3

7

0

.5

6

'

N 23°29'49" W

300.13'

N 1

4°56'5

1" W

99.8

7'

N 68°03'59" E

193.87'

N 21°40'49" W

N 6

8°18

'30

" E

113.99'

N 21°40'49" W 699.95'

N

4

2

°

3

8

'1

3

"

E

5

2

.

9

5

'

S

3

4

°

4

1

'4

9

" E

6

3

5

.2

2

'

S

3

9

°

4

3

'

3

5

"

W

2

1

7

.

2

9

'

BENCH MARK

1/2" REBAR - FLUSH

ELEV. 649.21

32.10'

LAGOON

CLEARWELL

CLEARWELL

FILTER & CONTROL

FLOCCULATORS/

SETTLING BASINS

EXISTING

HOUSE

30 0 15 30 60

SCALE: 1" 30'-0"

L

E

W

I

S

S

C

H

O

O

L

R

O

A

D

3

0

'

R

/

W

G

R

A

V

E

L

R

O

A

D

GRAVEL ROADCEDAR DRIVE 30' R/W

EXISTING WTP

BUILDING

C

E

D

A

R

D

R

IV

E

3

0

' R

/W

GE

NE

RA

TO

R

PLANTING SCHEDULE

SYMBOL PLANT NAME

PLA

NT

TY

PE

HE

IG

HT

SP

RE

AD

NO

. O

F

PLA

NT

S

BUXUS MICROPHYLLA (SCIENTIFIC NAME),

LITTLELEAF BOXWOOD (COMMON NAME)

E

3'

to

4'

3'

to

4'

47

D 4

ACER SACCHARUM (SCIENTIFIC NAME),

SUGAR MAPLE (COMMON NAME)

60'

to

75'

50'

to

60'

ILEX PEDUNCULOSA (SCIENTIFIC NAME),

LONGSTALK HOLLY (COMMON NAME)

E

20'

to

30'

10'

to

15'

3

GRASS GROUND COVER FESCUS OR

BLUEGRASS FAMILY

PAVING, CONCRETE & GRAVEL SCHEDULE

PROPOSED CONCRETE AREAS

(SIDEWALKS, STOOPS, & VEHICLE PADS)

PROPOSED PAVING AREAS

(DRIVEWAYS & PARKING LOTS)

PROPOSED

FLAG POLE

WITH LIGHT

PROPOSED

LAGOON

PROPOSED

CLEARWELL/

GAC BUILDING

PROPOSED

WTP

PROPOSED

SETTLING

BASIN #1

PROPOSED

SETTLING

BASIN #2

PROPOSED

FLOCC. #1

PROPOSED

FLOCC. #2

PROPOSED

MCC BUILDING

PROPOSED GRAVEL AREAS

(DRIVEWAYS & VEHICLE PADS)

PROPOSED LOCKABLE

GATE AT FLOCCULATOR

WALKWAY

PROPOSED LOCKABLE

GATE AT SETTLING

BASIN WALKWAY

ADDENDUM #211/81

U:\C

IT

Y O

F LE

IT

CH

FIE

LD

\433-Leitchfield W

TP

\D

raw

ings\C

ivil\S

HT

02-05.dw

g, 11/8/2018 2:44:49 P

M, A

utoC

AD

P

DF

(G

eneral D

ocum

entation).pc3

AutoCAD SHX Text
WATER TREATMENT PLANT
AutoCAD SHX Text
LEITCHFIELD UTILITIES COMMISSION
AutoCAD SHX Text
GRAYSON COUNTY, KENTUCKY
AutoCAD SHX Text
T
AutoCAD SHX Text
C
AutoCAD SHX Text
Engineers Planners Managers
AutoCAD SHX Text
CANN-TECH, LLC
AutoCAD SHX Text
Phone (502) 859-0907
AutoCAD SHX Text
Fax (502) 859-0668
AutoCAD SHX Text
1100 Glensboro Road
AutoCAD SHX Text
Lawrenceburg, KY 40342
Page 19: ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant ... · Disregard this statement. All special inspections and material ... The circuit breaker in MCCB for Transformer T-4 Panel

SE

E P

LA

NS

F

OR

W

ID

TH

1/4''/1' S

LO

PE

2

:

1

S

L

O

P

E

2

:

1

S

L

O

P

E

2

:

1

S

L

O

P

E

2'' C

RO

WN

8'' M

IN

. D

GA

DITCH LINE

SH

OU

LD

ER

S S

LO

PE

D

FO

R D

RA

IN

AG

E

GR

AV

EL

A

CC

ES

S R

OA

D

SC

AL

E: N

.T

.S

.

Lawrenceburg, KY 40342

1100 Glensboro Road

Fax (502) 859-0668

(502) 859-0907

U:\C

IT

Y O

F LE

IT

CH

FIE

LD

\433-Leitchfield W

TP

\D

raw

ings\C

ivil\S

TA

ND

AR

D_D

ET

AILS

.dw

g, 11/8/2018 2:46:29 P

M, A

utoC

AD

P

DF

(G

eneral D

ocum

entation).pc3

AutoCAD SHX Text
SCALE: AS NOTED
AutoCAD SHX Text
DATE: 11/8/2018
AutoCAD SHX Text
ADDENDUM #2
AutoCAD SHX Text
T
AutoCAD SHX Text
C
AutoCAD SHX Text
Cann-Tech, LLC
AutoCAD SHX Text
GRAVEL ROAD DETAIL
Page 20: ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant ... · Disregard this statement. All special inspections and material ... The circuit breaker in MCCB for Transformer T-4 Panel

6"

AutoCAD SHX Text
POAGE ENGINEERS
AutoCAD SHX Text
OFFICE: (859) 255-9034
AutoCAD SHX Text
& ASSOCIATES, INC.
AutoCAD SHX Text
FAX: (859) 252-3130
AutoCAD SHX Text
LEXINGTON, KENTUCKY 40504
AutoCAD SHX Text
880 Sparta Court Suite 200
AutoCAD SHX Text
BCV
AutoCAD SHX Text
BDS
AutoCAD SHX Text
CHECKED BY
AutoCAD SHX Text
DRAWN BY
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
SA-1
AutoCAD SHX Text
JOB
AutoCAD SHX Text
DATE
AutoCAD SHX Text
P#
AutoCAD SHX Text
OF
AutoCAD SHX Text
3
AutoCAD SHX Text
11/8/2018
AutoCAD SHX Text
18260(433)
AutoCAD SHX Text
WATER TREATMENT PLANT LEITCHFIELD UTILITIES COMMISSION GRAYSON COUNTY, KENTUCKY
AutoCAD SHX Text
WALL BEYOND
AutoCAD SHX Text
#4 BARS @ 8"o.c.
AutoCAD SHX Text
#4 BARS @ 12"o.c.
AutoCAD SHX Text
2-#5 BARS
AutoCAD SHX Text
2-#6 BARS
AutoCAD SHX Text
#4 BARS @ 12"o.c.
AutoCAD SHX Text
12"
AutoCAD SHX Text
1'-4"
AutoCAD SHX Text
8'-0"
AutoCAD SHX Text
SECTION
AutoCAD SHX Text
A
AutoCAD SHX Text
S-16
Page 21: ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant ... · Disregard this statement. All special inspections and material ... The circuit breaker in MCCB for Transformer T-4 Panel

6

8

7

99

14

14 14

18 18

19

20

21

21

21

2119

21 21

21

222222

2625

30

30

3030

739

37

MOP SINK WITH FIVESAMPLE TAPS

FLOW

TIE INTO 24"BACKWASH DRAIN LINE

Page 22: ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant ... · Disregard this statement. All special inspections and material ... The circuit breaker in MCCB for Transformer T-4 Panel

BAFFLEWALL (TYP.)

-4"

17'-8

"1'

-0"

4"8"

18'-8"

ELEV. 612.60

1

SECTIONSCALE: 3/16" = 1'-0"

A15

ruperto
Typewritten Text
Green Pipe is CCC Supply
ruperto
Typewritten Text
Red Pipe is Contractor Supply
Page 23: ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant ... · Disregard this statement. All special inspections and material ... The circuit breaker in MCCB for Transformer T-4 Panel

ST

A

TE OF KENTUCK

Y

PR

OFESSIONAL ENGIN

EE

R

MATTHEWBAKER24507

LICENSED

RECORD DRAWINGS

CHECKED BY:

DRAWN BY:

DESIGNED BY:

PROJECT:

SCALE:

SHEET

OF

AS NOTED

MAB

JH

19

9

SETTLING BASINMAB

433 DATE: 10/24/2018

APPR'D DATEDATEREVISIONSDATENO.

12"x18" OPENING

WITH ST. STL. SLIDE GATE

CENTER

12"x18" OPENING

WITH ST. STL. SLIDE GATE

CENTER

12"x18" OPENING

WITH ST. STL. SLIDE GATE

CENTER

12"x18" OPENING

WITH ST. STL. SLIDE GATE

CENTER

FLO

W

8" PORT

(6 TOTAL)

IN

FLU

EN

T T

RO

UG

H

5'-7

3

16

"5'-7

3

16

"

3'-1"

3'-4

1 2

"3'-4

1 2

"3'-4

1 2

"3'-4

1 2

"

3'-1"

FLOCCULATOR

12"

24" D.I. EFFLUENT

LINE

24" D.I. EFFLUENT

LINE

A

9

A

9

B

9

B

9

1'-6"

56'-0"

1'-6

"28

'-0"

1'-6"

28'-0"

1'-6"

60'-6"

59'-0"

10" 3'-0" 1'-6"

MEGA-VAC

DRIVE

8" PORTS

(6 TOTAL)

ELEV. 637.17

ELEV. 624.67

3'-6"

TOP OF WALL ELEV. 640.67

HANDRAIL

24" D.I. EFFLUENT

LINE INV. ELEV. 636.33

56'-0"

1'-6"

9"

1'-6"

9"

2'-6"

12

"

10''

16"

PLAN

SCALE: 3/16" = 1'-0"

SECTION

SCALE: 3/16" = 1'-0"

A

9

NOTES:

1. TUBE SETTLER SUPPORT SYSTEM SHALL BE DESIGNED PER TUBE

SETTLER MANUFACTURER AND APPROVED BY THE ENGINEER.

2. HANDRAILS, DRIVE UNITS, PLATFORMS, WALKWAYS, ETC, TO BE

PAINTED SAME COLOR AS BUILDING ROOF.

3. SEE STRUCTURAL DRAWINGS FOR STRUCTURAL DETAILS. ALL

STRUCTURAL DIMENSIONS WHERE SHOWN ON THIS SHEET ARE

FOR INFORMATION ONLY. STRUCTURAL SHEETS PREVAIL IN CASE

OF DISCREPANCY.

4. 24" EFFLUENT LINES TO BE TAPPED FOR CL2 AND FOR LEVEL

SENSING EQUIPMENT.

HANDRAIL

28'-0"

1'-6"

9"

16'-0"

SECTION

SCALE: 3/16" = 1'-0"

B

9

28'-0"

WATER LEVEL ELEV. 639.78

MEGA-VAC

MEGA-VAC

DRIVE

MEGA-VAC

7'-0"

9'-0

"

27'-6"

ELEV. 634.33

INV. ELEV. 637.33

CONCRETE

BAFFLE WALL

TUBE SETTLERS

10" PVC

SUBMERGED

ORIFICE

1

10

4'-6"

PIPE COLLAR

AT EFFLUENT

TROUGH

3

10

EFFLUENT

TROUGH

4

10

2'-10

"

10" PVC

SUBMERGED

ORIFICE

1

10

10" PVC

SUBMERGED

ORIFICE

10

EFFLUENT

TROUGH

4

10

TUBE SETTLERS

1

FINISHED GRADE ELEV. 640.00

TOP OF WALL ELEV. 640.67

ELEV. 624.67

MEGA-VAC

TOP OF WALL ELEV. 640.67

FINISHED GRADE ELEV. 640.00

ELEV. 624.67

HANDRAIL

24" D.I. DRAIN

LINE

24" FLARE

OUTLET

24" FLARE

OUTLET

24" D.I. DRAIN

LINE

4" DRAIN

LINE TO

EXISTING

LAGOONS

WATER LEVEL ELEV. 639.78

1'-6"

STEEL SLIDE

GATE

STAINLESS

6"

6"

7"

42"

18'-8"

LADDER

SAFETY

CHAIN

LADDER

HANDRAIL

HANDRAIL

SECTION

SCALE: 3/4" = 1'-0"

2

9

6"2'-1"2'-0"

2'-1" 4'-7"

2

9

1

9

DETAIL

DETAIL

SCALE: 3/4" = 1'-0"

1

9

1" DIA. 11 GA.

TUBING

13/32" HOLES (4)

3" APART

1/4"x2"x2"

STEEL ANGLE

CORRUGATED

RUNG

3/4" ROUND

WITH WALK-THRU

F16W

16 RUNG

MEGA-VAC

10" MUD VALVE

10" 90° M.J.

VALVE

TO EXISTING

LAGOON

12" DRAIN

TO EXISTING

LAGOON

12" DRAIN

TO EXISTING

LAGOON

10" DRAIN

DISCHARGE VALVE

DISCHARGE

PIPING

HANDRAIL

9'-6"

9'-0"

9'-6"

2'-7

3

16

"11

'-1

3

16

"3'-1

3

16

"

10'-0"

5'-0

3

8

"

4

13

16

"

1'-3

7

16

"

1'-9"

3

9

DETAIL

DETAIL

SCALE: 3/4" = 1'-0"

3

9

VALVE

CUT OUT

IN TROUGH

INV. ELEV. 621.00

INV. ELEV. 630.00

ADDENDUM #211/81

U:\C

IT

Y O

F LE

IT

CH

FIE

LD

\433-Leitchfield W

TP

\D

raw

ings\C

ivil\S

HT

09.dw

g, 11/8/2018 2:43:38 P

M, A

utoC

AD

P

DF

(G

eneral D

ocum

entation).pc3

AutoCAD SHX Text
WATER TREATMENT PLANT
AutoCAD SHX Text
LEITCHFIELD UTILITIES COMMISSION
AutoCAD SHX Text
GRAYSON COUNTY, KENTUCKY
AutoCAD SHX Text
T
AutoCAD SHX Text
C
AutoCAD SHX Text
Engineers Planners Managers
AutoCAD SHX Text
CANN-TECH, LLC
AutoCAD SHX Text
Phone (502) 859-0907
AutoCAD SHX Text
Fax (502) 859-0668
AutoCAD SHX Text
1100 Glensboro Road
AutoCAD SHX Text
Lawrenceburg, KY 40342
Page 24: ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant ... · Disregard this statement. All special inspections and material ... The circuit breaker in MCCB for Transformer T-4 Panel

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

OHE

OHE

OHE

OHE

OHE

OHE

OHE

OHE

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE OHE

OHE

OHE

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

O

H

E

W

W

W

W

W

WW

WW

WW

WW

WW

WW

WW

W

WW

W

W

W

W

WW

WW

W

W

W

W

W

WW

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

WW

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

WW

WW

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

S

A

N

S

A

N

S

A

N

S

A

N

S

A

N

S

A

N

S

A

N

S

A

N

S

A

N

S

A

N

S

A

N

S

A

N

S

A

N

S

A

N

S

A

N

S

A

N

SANSAN

SANSAN

SANSAN

SAN SAN

SA

NS

AN

SANSAN

CL

CL

CL

C

L

C

LC

LC

LC

LC

L

W

ST

A

TE OF KENTUCK

Y

PR

OFESSIONAL ENGIN

EE

R

MATTHEWBAKER24507

LICENSED

W

W

W

W

RECORD DRAWINGS

CHECKED BY:

DRAWN BY:

DESIGNED BY:

PROJECT:

SCALE:

SHEET

OF

AS NOTED

MAB

JH

19

4

PROPOSED PIPING PLANMAB

433 DATE: 10/24/2018

APPR'D DATEDATEREVISIONSDATENO.

S 21°40'49" E 669.95'

S

3

9

°

4

3

'

3

5

"

W

1

3

0

.

0

0

'

S

4

2

°

5

1

'3

3

"

W

1

5

3

.

7

9

'

N

3

0

°3

2

'1

4

" W

3

7

0

.5

6

'

N 23°29'49" W

300.13'

N 1

4°56'5

1" W

99.8

7'

N 68°03'59" E

193.87'

N 21°40'49" W

N 6

8°18

'30

" E

113.99'

N 21°40'49" W 699.95'

N

4

2

°

3

8

'1

3

"

E

5

2

.

9

5

'

S

3

4

°

4

1

'4

9

" E

6

3

5

.2

2

'

S

3

9

°

4

3

'

3

5

"

W

2

1

7

.

2

9

'

BENCH MARK

1/2" REBAR - FLUSH

ELEV. 649.21

32.10'

LAGOON

CLEARWELL

CLEARWELL

FILTER & CONTROL

FLOCCULATORS/

SETTLING BASINS

EXISTING

HOUSE

30 0 15 30 60

SCALE: 1" 30'-0"

L

E

W

I

S

S

C

H

O

O

L

R

O

A

D

3

0

'

R

/

W

G

R

A

V

E

L

R

O

A

D

GRAVEL ROAD

CEDAR DRIVE 30' R/W

EXISTING WTP

BUILDING

C

E

D

A

R

D

R

IV

E

3

0

' R

/W

GE

NE

RA

TO

R

PROPOSED

LAGOON

PROPOSED

CLEARWELL/

GAC BUILDING

PROPOSED YARD PIPING

1. 4" DRAIN LINE

2. 12" CLEARWELL OVERFLOW

3. 8" GATE VALVE

4. 12" SETTLING BASIN DRAIN LINE

5. 18" HIGH SERVICE LINE

6. 36" RAW WATER LINE

7. 12" LAGOON OUTFALL LINE (SEE NOTE THIS SHEET)

8. 20" FILTER EFFLUENT

9. 20" BUTTERFLY VALVE

10. 30" RAPID MIX EFFLUENT LINE TO FLOCCULATORS

11. 24" BACKWASH DRAIN LINE

12. 18" BUTTERFLY VALVE

13. HIGH SERVICE METERING VAULT (SEE DETAIL)

14. LAGOON DRAIN VAULT (SEE DETAIL)

15. FIRE HYDRANT

16. CONCRETE HEADWALL AND FLAP VALVE

17. CONCRETE SPLASH PAD (SEE DETAIL)

18. RIP RAP

19. 8" RAW WATER LINE TO RESERVOIR

20. 12" HIGH SERVICE FINISH WATER LINE TO SYSTEM

21. 12" BUTTERFLY VALVE

22. BACK FLOW PREVENTER

23. 24" BUTTERFLY VALVE

24. 30" BUTTERFLY VALVE

25. 36" BUTTERFLY VALVE

26. 6" GATE VALVE

27. 3" GATE VALVE

28. MANHOLE

29. 36" x 18" M.J. REDUCER

30. CONCRETE VAULT WITH PROPELLER METER

31. VAULT WITH METER

32. SANITARY SEWER LINE

33. CLEAN OUT

34. SEPTIC TANK

35. LEACH FIELD

36. 12" LAGOON OUTFALL/DISCHARGE LINE

37. LAGOON OUTFALL VAULT SEE DETAIL

38. FROST PROOF YARD HYDRANT WITH 3/4" CONNECTION

39. 12" GAC BACKWASH/DISCHARGE LINE

40. STEEL PIPE BOLLARDS

41. CONCRETE PAD

42. 6" WATER LINE

43. 3 - 2" CHEMICAL FEED LINES

44. 24" DRAIN LINE

EXISTING YARD PIPING

1. 36" RAW WATER LINE

2. 10" HIGH SERVICE LINE

3. 16" RAW WATER LINE

4. 16" HIGH SERVICE LINE

5. 10" RAW WATER LINE

6. CONTROL WIRE

?

?

2

2

4

44

5

5

6

10

8

8

17

8

15

13

11

17

PROPOSED

WTP

PROPOSED

SETTLING

BASIN #1

PROPOSED

SETTLING

BASIN #2

PROPOSED

FLOCC. #1

PROPOSED

FLOCC. #2

6

23

24

25

26

27

15

44

44

28

28

23

24

6

29

30

31

44

32

32

33

33

33

34

35

GENERAL NOTES:

1. ALL EXISTING UTILITIES SHOWN ARE APPROXIMATE IN LOCATION. THE

CONTRACTOR SHALL VERIFY THE LOCATION OF ALL EXISTING UTILITIES

BEFORE STARTING ON ANY EXCAVATION.

2. ALL YARD PIPING SHALL BE DUCTILE IRON, MECHANICAL JOINT CLASS

350 UNLESS OTHERWISE NOTED

3. ALL YARD PIPING VALVES SHALL BE BUTTERFLY VALVES UNLESS

OTHERWISE NOTED.

4. THE CONTRACTOR SHALL SEE THE PLAN SHEETS FOR VALVE

LOCATIONS ON THE FLOCCULATORS, SETTLING BASINS, CLEARWELL,

AND WET WELL.

5. CONTRACTOR SHALL TIE 12" LAGOON OUTFALL LINE TO EXISTING

LAGOON OUTFALL VAULT.

37

36

PROPOSED

MCC BUILDING

38

30

26

26

38

38

39

DR

AIN

LIN

E

TO

LA

KE

38

40

40

41

38

42

42

42

42

42

43

43

43

43

CW

C

W

CW

6

NOTE:

CONTRACTOR SHALL LOCATE EXISTING

CONTROL WIRE AND CONNECT TO IT AND

RUN NEW LINE TO PROPOSED WATER

TREATMENT PLANT.

SEE CONNECTION

DETAIL THIS SHEET

INSTALL

1-16"x16"x16" TEE

1-18"x16" M.J. REDUCER

2-16" GATE VALVE

1-CONCRETE THRUST BLOCK

INSTALL

1-18"x18"x18" TEE

1-18"x10" M.J. REDUCER

1-10" GATE VALVE

2-CONCRETE THRUST BLOCK

CONNECTION DETAIL

1

1

3

5

3

4

2

2

4

4

U:\C

IT

Y O

F LE

IT

CH

FIE

LD

\433-Leitchfield W

TP

\D

raw

ings\C

ivil\S

HT

02-05.dw

g, 11/8/2018 3:19:45 P

M, A

utoC

AD

P

DF

(G

eneral D

ocum

entation).pc3

AutoCAD SHX Text
WATER TREATMENT PLANT
AutoCAD SHX Text
LEITCHFIELD UTILITIES COMMISSION
AutoCAD SHX Text
GRAYSON COUNTY, KENTUCKY
AutoCAD SHX Text
T
AutoCAD SHX Text
C
AutoCAD SHX Text
Engineers Planners Managers
AutoCAD SHX Text
CANN-TECH, LLC
AutoCAD SHX Text
Phone (502) 859-0907
AutoCAD SHX Text
Fax (502) 859-0668
AutoCAD SHX Text
1100 Glensboro Road
AutoCAD SHX Text
Lawrenceburg, KY 40342
Page 25: ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant ... · Disregard this statement. All special inspections and material ... The circuit breaker in MCCB for Transformer T-4 Panel

Waterstops 03150-1

SECTION 03150 - WATERSTOPS PART 1 GENERAL 1.01 SECTION INCLUDES

A. Provision of waterstops embedded in concrete and spanning control, expansion, and/or construction joints to create a continuous diaphragm to prevent liquid migration.

B. Non-metallic waterstops for use in concrete joints subjected to chlorinated water, seawater, and many waterborne chemicals.

1.02 REFERENCES

A. PVC WATERSTOP

1. Corps of Engineers: CRD-C 572-74

2. American Society for Testing Materials (ASTM)

3. Bureau of Reclamation: C-902

4. Canadian General Standards Board: 41-GP-35M Types 1 & 3

1.03 QUALITY ASSURANCE

A. Waterstop manufacturer shall demonstrate five (5) years minimum continuous, successful experience in production of PVC waterstops.

1.04 DELIVERY, STORAGE, AND HANDLING

A. Store waterstops under tarps to protect from oil, dirt, and sunlight.

PART 2 PRODUCTS 2.01 MATERIALS

A. Provide flexible PVC (polyvinyl chloride) waterstop as manufactured by Sika, profile style number (fill in profile style number).

B. The PVC waterstop shall be extruded from an elastomeric plastic material of which the basic resin is prime virgin polyvinyl chloride. The PVC compound shall not contain any scrapped or reclaimed material or pigment.

C. Performance requirements as follows:

Page 26: ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant ... · Disregard this statement. All special inspections and material ... The circuit breaker in MCCB for Transformer T-4 Panel

Waterstops 03150-2

PROPERTY TEST

METHOD REQUIRED LIMITS

Water absorption ASTM D570 0.15% max Tear Resistance ASTM D624 300 lb/in (52.5 kN/m) min. Ultimate Elongation ASTM D638 350% min. Tensile Strength ASTM D638 2000 psi (13.78 Mpa) min. Low Temperature Brittleness

ASTM D746 No Failure @ -35°F (-37°C)

Stiffness in Flexure ASTM D747 1000 psi (4.82 Mpa) min. Specific Gravity ASTM D792 1.38 max. Hardness, Shore A ASTM D2240 79 ± 3 Tensile Strength after accelerated extraction

CRD-C 572 1600 psi (9.54 Mpa) min.

Elongation after accelerated extraction

CRD-C 572 300% min.

Effect of Alkalies after 7 days: Weight Change Hardness Change

CRD-C 572 Between -0.10% / +0.25% ± 5 points

2.02 ACCESSORIES

A. Provide factory made waterstop fabrications for all changes of direction, intersections, and transitions leaving only straight butt joint splices for the field.

B. Provide grommets, pre-punched holes, or hog rings (installed by others) spaced at 12 inches on center along length of waterstop.

C. Provide Teflon coated thermostatically controlled waterstop welding irons for field butt splices.

PART 3 EXECUTION 3.01 INSTALLATION

A. Field butt splices shall be heat fused welded using a Teflon coated thermostatically controlled waterstop welding iron at approximately 380 degrees F. Follow approved waterstop manufacturer recommendations. Lapping of waterstop, use of adhesives, or solvents shall not be allowed.

B. Center waterstop in joint and secure waterstop in correct position using grommets, pre-punched holes, or hog rings (installed by others) spaced at 12 inches on center along the length of the waterstop and wire tie to adjacent reinforcing steel.

Page 27: ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant ... · Disregard this statement. All special inspections and material ... The circuit breaker in MCCB for Transformer T-4 Panel

Waterstops 03150-3

3.02 FIELD QUALITY CONTROL

A. Waterstop splicing defects which are unacceptable include, but are not limited to the following:

1. Tensile strength less than 80 percent of parent section.

2. Misalignment of centerbulb greater than 1/16 inch.

3. Bond failure at joint deeper than 1/16 inch or 15 percent of material thickness.

4. Misalignment that reduces waterstop cross section more than 15 percent.

5. Visible porosity in the weld.

6. Bubbles or inadequate bonding.

7. Visible signs of splice separation when cooled splice is bent by hand at a sharp angle.

8. Charred or burnt material.

END OF SECTION 03150

Page 28: ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant ... · Disregard this statement. All special inspections and material ... The circuit breaker in MCCB for Transformer T-4 Panel

Prefabricated Building Building Design Specifications:

• Interior walls and ceiling: 10 gauge steel • Exterior walls and roof: 26 gauge PBR panel • Self-Framing Steel Construction • Structural Steel Skid Frame with ¼” floorplate • Undercoating • Roof Slope: Single Slope, ½” per foot • Paint: PSX 700 2 part epoxy • Fire and Weather Resistant Construction

Mechanical:

• Structural PE Stamp: Yes • Design Codes: IBC and NEC. • Structural Welding D1.1/D1.3 • Bolt on lifting eyes bottom frame lift • L/960 Deflection during lifting

Building General Construction Details: Buildings are one of a kind, custom built, walk-in, weather resistant, non-combustible and fully engineered enclosures that include the following standard features: Construction, based on the 2012 IBC, AISC Steel Construction Manual, 13th Edition, and Detailing for Steel Construction, 2nd Edition, consists of a structural steel channel base frame, 1/4” steel floor plate, 10 gauge interior wall panels, ceiling panels and ceiling joists. Steel member joints and seams are connected by fully sealed continuous welds. Building roof is single slope at ½” per foot. Slope direction is based on door location, exterior features and site conditions. Heavy duty removable lifting eyes located at skid (quantity as required per engineering design) will be provided for picking and placing the building with a crane. *Quoted skid deflection is L/240. Insulation: Walls (R-23) and ceiling (R-23) cavities are insulated with custom cut ROXUL ComfortBatt ™ stone wool insulations made from basalt rock and slag. This combination results in a non-combustible product with a melting point of approximately 2150°F (1177°C), which gives it excellent fire resistance properties. ROXUL stone wool is a water repellent yet vapor permeable material. This material has a Flame Spread of 0. The building skid will be insulated with spray applied rigid polyurethane foam in thickness required to achieve an approximate thermal resistance of (R-30). In addition, the building skid will be undercoated with Amercoat 240 Universal Amine Epoxy Coating from PPG to an approximate thickness of 6mils dry. Standard Painting Process: All steel interior surfaces and exposed exterior surfaces are thoroughly cleaned with a phosphatizing acid wash prior to painting. Our high quality Engineered Siloxane Epoxy paint system consists of a coat of PPG’s “Amerlock” primer and PPG’s “PSX-700” coat of paint in the Owner’s choice of our standard colors. PSX 700 is a patented composition that embodies the properties of both high performance epoxy and polyurethane in one coat. This general purpose coating offers “breakthrough” weather resistance and corrosion control. It provides protection and excellent, long lasting appearance in one application, exceeding the gloss and appearance retention of the best polyurethane.

Page 29: ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant ... · Disregard this statement. All special inspections and material ... The circuit breaker in MCCB for Transformer T-4 Panel

Exterior Siding: Exterior walls and roof are covered by preformed 26 gauge PBR panels. The base metal is manufactured from a high strength Galvalume® and coated with Signature® 200 thermoset polyester resin in the owner’s choice of standard colors per attached. Signature® 200 carries a 25-year limited warranty. *Please Note: Additional fees will apply for non-standard siding and/or paint colors.

Doors: • One (1) 4080 Single Door – 14 gauge steel construction, insulated, exterior door with 3 piece x 4-3/4” throat

knockdown frame, panic hardware, 24"x36" safety glass, lockable passage lever, stainless steel hinges, threshold and door sweeps.

• One (1) 3080 Single Door – 14 gauge steel construction, insulated, exterior door with 3 piece x 4-3/4” throat knockdown frame, panic hardware, 24"x36" safety glass, lockable passage lever, stainless steel hinges, threshold and door sweeps.

• Two (2) Entry door switches HVAC:

• Two (2) Bard Manufactured 4T, 480V, 3PH, Wall Mount HVAC Unit with One (1) MC4001-A Lead Lag Controller.

• One (1) Panel Board, 3P4W, 208y/120, 42 slot, 225A w/ main • One (1) 75kva transformer, 480:208Y/120 • Five (5) Lithonia 24W, 48” Interior LED Strip Lights (p/n: MNSLMVM6). • Two (2) Interior Light Switches. • Two (2) Cooper 30W Exterior LED Lights with Integral Photocell Control (p/n: XTOR3A-PC1). • Two (2) Lithonia Emergency Exit Sign/Light Combination Units with Battery Backup (p/n: ECRLED,R). • Four (4) Interior/Exterior 125V, 20A, NEMA 5-20R GFCI Duplex Receptacles.

*Exterior receptacles shall be provided with “in-use” weather proof covers. Grounding:

• Four (4) Stainless Steel Grounding Pads. • Lot – ¼” x 2” Copper Bus Bar (Ground Halo). • -Lot – 24” x 6” NEMA 20B, Aluminum, Cooper B-Line Cable Tray with 9” Rung Spacing.

*This proposal includes single layer cable tray arrangement as shown in provided layout drawing 110954. Additional fees may apply for modification of this configuration.

• Lot – 4/0-1C Bare Copper Cable (Ground). o Ground Halo shall be installed around interior building perimeter near ceiling. 4/0-1C cable shall

connect equipment ground to copper bus bar and terminate at building skid. Miscellaneous:

• One (1) Four zone fire panel • Two (2) manual pull stations • Two (2) smoke detector w/ aux • One (1) Interior strobe/horns • One (1) Exterior strobe/horn • Two (2) 10lb fire extinguisher, CO2

Included Power Cabling:

• 3ea. 500mcm-3C, 600V tray rated cables from ATS to MCCA • 1ea. 500mcm-3C, 600V tray rated cable from ATS to MCCB

Page 30: ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant ... · Disregard this statement. All special inspections and material ... The circuit breaker in MCCB for Transformer T-4 Panel

• 1ea. 2/0-3C, 600V tray rated cable from MCCB to 75kva transformer • 1ea. 4/0-3C, 600V tray rated cable from 75kva transformer • 2ea. #4-3C, 600V tray rated cables from MCC to HVAC • Internal building utilities

Included Control Cabling:

• Two (2) Door entry switches to PLC (coiled on plc side) • Eight (8) Fire alarm panel to PLC terminations (coiled on plc side) • Eight (8) Thermostat panel to PLC terminations (coiled on plc side) • Additional terminations shall be at $25 per termination.

Included Communication Cabling:

• No communication cabling included. Equipment Installed:

• One (1) MCCA (9 sections) • One (1) MCCB (4 sections)

Equipment Procured Installed and Integrated by Others: • PLC panels • PLC terminations from coiled cables

Page 31: ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant ... · Disregard this statement. All special inspections and material ... The circuit breaker in MCCB for Transformer T-4 Panel

EXISTING PAVMENT

SLOPE

DEPTH VARIES

EXISTING

EARTH

6''1''

1/2'' R

18''

STANDARD HEADER CURB

SCALE: N.T.S.

Lawrenceburg, KY 40342

1100 Glensboro Road

Fax (502) 859-0668

(502) 859-0907

U:\C

IT

Y O

F LE

IT

CH

FIE

LD

\433-Leitchfield W

TP

\D

raw

ings\C

ivil\S

TA

ND

AR

D_D

ET

AILS

.dw

g, 11/8/2018 2:46:51 P

M, A

utoC

AD

P

DF

(G

eneral D

ocum

entation).pc3

AutoCAD SHX Text
SCALE: AS NOTED
AutoCAD SHX Text
DATE: 11/8/2018
AutoCAD SHX Text
ADDENDUM #1
AutoCAD SHX Text
T
AutoCAD SHX Text
C
AutoCAD SHX Text
Cann-Tech, LLC
AutoCAD SHX Text
CURB DETAIL
AutoCAD SHX Text
STANDARD HEADER
AutoCAD SHX Text
STANDARD HEADER
Page 32: ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant ... · Disregard this statement. All special inspections and material ... The circuit breaker in MCCB for Transformer T-4 Panel
AutoCAD SHX Text
POAGE ENGINEERS
AutoCAD SHX Text
OFFICE: (859) 255-9034
AutoCAD SHX Text
& ASSOCIATES, INC.
AutoCAD SHX Text
FAX: (859) 252-3130
AutoCAD SHX Text
LEXINGTON, KENTUCKY 40504
AutoCAD SHX Text
880 Sparta Court Suite 200
AutoCAD SHX Text
BCV
AutoCAD SHX Text
BDS
AutoCAD SHX Text
CHECKED BY
AutoCAD SHX Text
DRAWN BY
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
SA-3
AutoCAD SHX Text
JOB
AutoCAD SHX Text
DATE
AutoCAD SHX Text
P#
AutoCAD SHX Text
OF
AutoCAD SHX Text
3
AutoCAD SHX Text
11/8/2018
AutoCAD SHX Text
18260(433)
AutoCAD SHX Text
WATER TREATMENT PLANT LEITCHFIELD UTILITIES COMMISSION GRAYSON COUNTY, KENTUCKY
AutoCAD SHX Text
6"
AutoCAD SHX Text
(2)#4 BARS CONT.
AutoCAD SHX Text
2'-0"
AutoCAD SHX Text
~4" EXP. JT. MAT'L & SEALANT
AutoCAD SHX Text
#3 BARS @ 12"o.c.
AutoCAD SHX Text
#4 NOSING
AutoCAD SHX Text
1" NOSING
AutoCAD SHX Text
#4 BARS @ 12"o.c.
AutoCAD SHX Text
#3 BARS @ 12"o.c.
AutoCAD SHX Text
(4)#4 BARS
AutoCAD SHX Text
SEE ARCH. PLAN FOR TREAD SIZE
AutoCAD SHX Text
SEE ARCH. PLANS FOR RISER
AutoCAD SHX Text
2'-0"
AutoCAD SHX Text
12"
AutoCAD SHX Text
8"
AutoCAD SHX Text
TYPICAL STAIR SECTION
Page 33: ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant ... · Disregard this statement. All special inspections and material ... The circuit breaker in MCCB for Transformer T-4 Panel

SECTION 11376 POSITIVE DISPLACEMENT BLOWERS Part 1 - General 1.1 Manufacturer & Quality Assurance

A. The equipment specified herein is intended to be standard equipment for positive displacement air systems and be supplied by a single OEM to assure uniform quality and compatibility.

B. The supplier shall have experience in providing similar equipment, and shall show proof of

satisfactorily operating installations in the marketplace.

C. The blower packager must be an authorized distributor and packager of the blower being supplied and must be factory authorized to perform warranty service.

1.2 Manufacturer's Field Representation

A. General: The field service representative must be a qualified blower-factory certified technician.

B. Inspection & Start-Up: Upon notification of completion of the aeration system by the

contractor, the blower technician will perform the following duties as applicable: installation inspection & certification, equipment lubrication, control panel parameter setup (if furnished by blower package OEM), initial start-up and corrective adjustments. Site start-up procedures must include equipment soft-foot checks, drivetrain alignment with a laser alignment tool and a minimum one hour run under standard operating conditions.

C. Operator Training: Training to include but not limited to all lubrication locations,

procedures, intervals and allowable lubricants. Drivetrain maintenance, filter servicing, any applicable alarm condition management and special start-up & shut-down procedures.

1.3 Testing

A. A factory blower performance and mechanical acceptance test report from the actual

blower manufacturer shall be supplied for each blower. 1.4 Spare Parts, Lubricants & Special Tools

A. The blower package OEM shall deliver the following parts with the blower package(s). Coupons or certificates for the future delivery or purchase of parts is not acceptable. Coupons or certificates for parts to be included with a maintenance contract is not acceptable.

1. One filter element per blower 2. One v-belt set per blower 3. One case of blower oil

Part 2 – Performance / Components

Page 34: ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant ... · Disregard this statement. All special inspections and material ... The circuit breaker in MCCB for Transformer T-4 Panel

2.1 Design Criteria

Filter Backwash Blower

Quantity 1 Discharge Pressure 5.5 PSIG Motor HP 125 HP Max. Allowable BHP** 90.2 BHP Motor RPM 1800 RPM Air Flow (SCFM) 2510 SCFM Air Flow (ACFM) 2880 ACFM Elevation 493’ASL Inlet Air Temp. 100ºF Blower RPM 1735 RPM Max. Allowable RPM 1800 RPM Blower Model Heliflow 825

**Must include filter & silencer pressure losses. Manufacturer: The blower shall be manufactured by the following and shall be exactly

equal to the model number specified above.

1. Gardner Denver 825 Heliflow Series 2. The blower must be manufactured in the United States. 3. Blower systems shall be fully assembled and tested by Excelsior Blower Systems,

Blandon, PA. 2.2 Rotary Positive Displacement Blower

A. The blower shall be of the horizontal rotary twisted tri-lobe positive displacement type blower. And must provide oil-free air, suitable for heavy-duty continuous industrial service.

B. The Impellers shall be solid 3 lobe helical design to reduce pulsations and noise, with

integral shafting, produced from close grain ductile iron. Impellers shall be machined on all exterior surfaces to a precise contour for operating at close clearances and high efficiency operation. Impellers shall be dynamically balanced to minimize vibration. Blowers with impellers and shafts that are not of the one-piece integral design will not be accepted. Straight, two lobe or straight three lobe impellers are not acceptable.

C. Impeller housing shall be strongly ribbed one-piece design to prevent case distortion when

operating at rated pressures. The housing shall be of high strength cast iron and precision machined for close clearance operation.

D. End plates shall be high strength cast iron with precision machined bearing fits to assure

exact positioning of impellers in the main body housing.

E. Timing gears shall be helical design and machined from high strength alloy steel for precision timing, quiet operation and long life.

Page 35: ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant ... · Disregard this statement. All special inspections and material ... The circuit breaker in MCCB for Transformer T-4 Panel

F. Bearings shall be heavy-duty spherical roller bearings for exact positioning of the impellers, to control thrust and to provide increased overhung load capacity. Bearings must be sized for a minimum B10 life of 50K hours.

G. Lubrication of timing gears and bearings shall be a splash lubrication system. Steel splash

plates shall be directly fastened to the impeller shafts to provide positive oil lubrication at all operating speeds. Grease lubrication is not allowed.

H. Air seals of controlled flow design, shall be piston ring type seals precision fitted to each

impeller shaft to minimize air leakage and maximize efficiency. Oil seals of piston ring and oil flinger design, shall be provided on each internal impeller shaft to prevent leakage from the oil reservoirs. The drive seal shall be a high temperature elastomer lip type seal to

2.3 Electric Motors

A. Constant torque, TEFC (IP55), 1800 RPM, minimum 1.15 S.F., 230/460/3/60, class F insulation, certified for DOL starting and VFD service. Motors shall be as manufactured by Marathon, Baldor, WEG Electric or Toshiba.

B. Motor must meet or exceed Energy Independence and Security Act (EISA 2007) standards

for NEMA premium efficiency.

C. Frame must be cast iron and equipped with cooling fins. The motor feet shall be solid for better mechanical strength and reduced vibration. Aluminum and steel framed motors are not allowed. Skeletonized mounting feet are not allowed.

D. Conduit box must be cast iron and rotatable in 90° increments.

E. Endshields shall be cast iron with fins for better thermal heat dissipation for lower bearing

operating temperatures. They must be equipped with drain holes to expel water that may condense inside the frame in certain environments.

F. VFD operated motors to meet MGI Part 31 rating.

2.4 Blower Package Accessories

A. General: The blower packages shall be fabricated and assembled with the following accessories and shipped complete to the extent feasible for safe shipping.

B. Equipment Base: The base shall be comprised of carbon steel plate and structural steel

shapes and be of sufficient design to support the blower, motor, drivetrain and silencers without undue flexing. The base must be of a heavy duty design to ensure operating vibration levels are within the blower manufacture’s allowable tolerance. The blower and the motor are mounted in the horizontal configuration providing for vertical airflow and horizontally mounted silencers. The silencers may not be welded to the base in any way. All bases must be equipped with sufficient forklift access points. All welding to be per AWS D1.1. All welders must have a current welder qualification test record for AWS D1.1 issued by and AES accredited test facility with a certification no. All welder logs must be up to date. MTRs must be furnished showing that all structural steel products are melted and manufactured in the United States.

Page 36: ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant ... · Disregard this statement. All special inspections and material ... The circuit breaker in MCCB for Transformer T-4 Panel

C. Drive: Provide a v-belt drive assembly consisting of sheaves, quick detachable bushings, v-

belts and slide-tensioning motor base. The sheaves must mount to the blower & motors shafts by use of QD type bushings, Bored to size / direct-shaft-mount sheaves are not allowed. The slide-tensioning base must have dual tensioning screws for ease of face alignment. Single-point tensioning bases will not be considered. Swing type ‘auto’ tensioning by means of the motor mass shall not be allowed. Design the drive assembly with a 1.4 service factor based on the motor nameplate horsepower.

D. Drive Guard: All mechanical power transmission drive components must be equipped with

a steel guard sufficiently designed to protect personnel from accidental contact with moving parts. Guard(s) shall be securely mounted and designed for removal without the use of special tools. All belt drive guards shall be constructed to allow visual inspection of the sheaves and belts without removal. Guards shall be painted safety yellow or safety orange. Plastic guards are not allowed.

E. Filter: Provide each blower with a suitably sized air filter based on the filter manufactures

published airflow capacity levels. Filters to be equipped with a weather hood for outdoor installations. Acceptable manufactures include Universal Silencer, Stoddard, Solberg or approved equal.

F. Intake Silencer: Provide a heavy duty double shell cylindrical noise attenuation unit

constructed of carbon steel sheet, tubing and plate. A chamber-absorptive type silencer is required. The silencer must be multi-chambered for pulse control and shall contain internal packing material for absorption noise control. The silencer must be independently supported but not welded to or integral with the base structure in any way. The silencer must be isolated from the blower connection by a flexible connector / expansion joint and not supported by the blower in anyway. The silencer to be model RIS type as manufactured by Universal Silencer or equal.

G. Discharge Silencer: Provide a heavy duty double shell cylindrical noise attenuation unit

constructed of carbon steel sheet, tubing and plate. A chamber-absorptive type silencer is required. The silencer must be multi-chambered for pulse control and shall contain internal packing material for absorption noise control. The silencer must be independently supported but not welded to or integral with the base structure in any way. The silencer must be isolated from the blower connection by a flexible connector / expansion joint and not supported by the blower in anyway. The silencer to be model SD type as manufactured by Universal Silencer or equal.

The discharge silencer packing material must have a temperature rating equal to or greater

than the blower’s maximum discharge temperature rating.

H. Flexible Connector / Expansion Joints: A flex-conn / expansion joint is required directly at the inlet and discharge of the blower to provide vibration isolation, accommodate thermal expansion and eliminate loading of the blower cylinder. Three piece clamped sleeved type and one piece arch type are both acceptable. Lateral, angular, elongation and compression tolerances must be suitable to accommodate thermal growth and component manufacturing tolerances. The minimum allowable ratings for the inlet is 10 psi, 150°F. The minimum allowable ratings for the discharge is 30 psi, 250°F. Connector joints to be equivalent to Flex-Fab sleeve-type and General Rubber arch-type.

Direct mounting of silencers to the blower without the use of an expansion joint shall not

Page 37: ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant ... · Disregard this statement. All special inspections and material ... The circuit breaker in MCCB for Transformer T-4 Panel

be allowed.

I. Pressure Relief Valve: Provide a weighted type relief valve properly sized to protect the blower from over pressurization. Spring-type valves will not be considered due to set-point unreliability associated with spring-tension life. The valve must be located downstream of the discharge silencer for pulsation protection. Provide valves equal to the Sutorbilt weight-type.

J. Check Valves: Provide a full port dual plate ‘butterfly style’ check valve to be located

downstream of the pressure relief valve. The body shall be steel or cast iron. The internals shall be corrosion resistant aluminum as a minimum. The hinge pin shall be stainless steel and the closure stop pin must be Teflon coated to provide for cushioned contact points. The valve shall be sized based on airflow as per the manufacture’s recommendation to avoid chatter induced fatigue failures. Under-sized and over-sized valves are not permitted. The valve must be suitable for low pressure air. Swing checks, pump valves and valves with external levers, springs or other control mechanisms are not permitted. Provide a valve equivalent to Flexi-Hinge Model 502M, 518, 503 or equal.

K. Discharge Isolation Butterfly Valve: Provide a wafer type, resilient seated, lever operated

butterfly valve for isolating the blower from the system. Furnish valve with cast iron or ductile iron body and a corrosion resistant disc such as stainless steel, Aroxy coated or Nylon coated. The stem shall be stainless steel with a heavy duty Acetal plug bushing. The seat elastomer to be EPDM or Viton. The hand lever must be equipped with position latching plate. Acceptable manufactures are DeZurik, DelVal, Keystone, Bray, Mueller, or approved equal.

L. Discharge Pressure Gauge: Provide 0-15 or 0-30 psi scaled pressure gauge to be stem

mounted or panel mounted connected to the discharge side of the blower. Gauges not connected downstream of the discharge silencer require a pulsation snubber. Stem mounted gauges require a liquid filled case. The case shall be weather tight and be of corrosion resistant material such as stainless steel, aluminum, polysulfone or approved equal. Minimum size is 2-1/2” diameter and minimum accuracy to be +/- 2-1/2% of span per ASME B40.100 Grade 1A. Acceptable manufactures are Wika, Ashcroft or approved equal.

M. Inlet Restriction Gauge: Provide a low vacuum or differential pressure gage to be

connected to the inlet side of the blower, downstream of the filter element. Acceptable ranges are 0-15 to 0-30 Inches H2O scale. Remote mounted and direct stem mounted are acceptable but must be easily viewable without climbing. The case shall be weather tight and be of corrosion resistant material such as stainless steel, aluminum, polysulfone or approved equal. Minimum size is 2-1/2” diameter and minimum accuracy to be +/- 2-1/2% of span per ASME B40.100 Grade Acceptable manufactures are Dwyer, Ashcroft or approved equal.

2.5 Shop Painting

A. Shop Prime Coating: Prime paint all components before assembly with an alkyd primer equivalent to Sherwin Williams Kem-Flash prime. Surface preparation, application and minimum DFT millage to be as per the paint manufactures published recommendation.

B. Shop Finish Coating: Finish paint all components before assembly with an enamel paint

equivalent to Sherwin Williams Sher-Kem paint. Application and minimum DFT millage

Page 38: ADDENDUM NUMBER 2 Leitchfield Water Treatment Plant ... · Disregard this statement. All special inspections and material ... The circuit breaker in MCCB for Transformer T-4 Panel

to be as per the paint manufactures published recommendation. Color to be the OEM’s standard color or owner requested color.

2.7 Sound Reduction Enclosure

A. Each blower assembly shall be furnished with a sound attenuating enclosure suitable for locating outdoors. The enclosure shall be manufactured of 0.063” thick formed aluminum sheet metal panels. The acoustical packing and overall design shall be sufficient to meet a free-field noise requirement of 80 dBA at any horizontal distance of 3 Feet from the exterior surface. The enclosure design shall incorporate a perforated a galvanized steel inner liner to mechanically secure the acoustical foam material and to protect the foam from damage. Painted and powder coated steel enclosures do not offer sufficient weather protection for outdoor installations.

B. The enclosure shall be furnished with latching doors sufficient to view, access, and

otherwise carry out all standard maintenance requirements without enclosure panel disassembly. These activities include but may not be limited to oil drain and fill, grease fitting and plug access, filter service, guard removal and drivetrain replacement and alignment. Lift-out type doors shall not exceed 50lbs.

C. The enclosure must be equipped with a 120/1/60 forced air ventilation system. The air

ventilation fan shall be pre-installed on the enclosure and sized as necessary to keep the assembly at a temperature needed to maintain proper operation as recommended by the assembly manufacturer and must be pre-wired to a thermostat. Blower shaft mounted fans are not acceptable due to hindering maintenance and troubleshooting access at the blower. Also VFD operated turndown speeds result in reduced ventilation airflow.

D. All exposed hardware, latches, hinges, door handles and similar must be highly weather

resistant such as stainless steel, chrome or aluminum.

E. The enclosure must be free standing and not attached or mounted onto the blower package frame in any way. The enclosure will require field assembly and shall be supplied with installation instructions and all fasteners. No special tools shall be required for field assembly.

F. All pipe penetration holes in the enclosure shall be sized to allow for passage of pipe

fittings and/or flanges. Flashing rings shall be provided to seal all pipe penetration holes after final assembly.

END OF SECTION