acwc-sd - · pdf fileacwc-sd • screw . type • • • air-cooled packaged...

24
••••••••••••••••••••• ••••••••••••••••••••••••••••• ! ACWC-SD Screw Type Air-Cooled Packaged Chillers Installation, Operation, and Maintenance Manual DESCRIPTION TABLE OF CONTENTS Inspection & Handling Location and Mounting Wiring Chiller Piping Start-Up Maintenance Slide Valve Unloading System Low Ambient Operation Control Settings Unit Operating Limitations Sequence of Operation Safety Controls, Field Wiring, Star Delta Start Control Wiring Diagrams ACWC 40 thru 70 ACWC 90 thru 135 ACWC 145 thru 200 ACWC 215 thru 265 Power Wiring Diagrams ACWC 40 thru 70 ACWC 90 thru 135 ACWC 145 thru 200 ACWC 215 thru 265 Electrical Data Cooler Pressure Drops Unit Loading/Suspension Points Troubleshooting Guide Causes & Prevention of Freeze-Up Start-up Check List Operating Data Maintenance Form No. 6184 PAGE NO. 2 2 2 2 2&3 3 4 5 5 5 6 & 7 7 8 & 9 10 & 11 12 & 13 14 & 15 16 16 17 17 18 & 19 20 21 22 22 23 24 24 DUNHAM-BUSH USA

Upload: dodat

Post on 16-Feb-2018

228 views

Category:

Documents


6 download

TRANSCRIPT

Page 1: ACWC-SD - · PDF fileACWC-SD • Screw . Type • • • Air-Cooled Packaged Chillers •• Installation, Operation, and •• • Maintenance Manual • • • •• DESCRIPTION

bullbullbullbullbull

bullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbull

bullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbullbull

bullbull

bullbull

bullbullbullbull

bullbull bull bullbull

bull ACWC-SD

bull Screw Typebullbullbull Air-Cooled Packaged Chillers bullbull Installation Operation and bullbull Maintenance Manualbullbullbullbullbullbull DESCRIPTION

TABLE OF CONTENTS

Inspection amp Handling

bull Location and Mounting Wiring Chiller Pipingbullbull Start-Up

bull Maintenance

bull Slide Valve Unloading System Low Ambient Operation Control Settings Unit Operating Limitations Sequence of Operation

bull Safety Controls Field Wiring Star Delta Startbull Control Wiring Diagramsbull ACWC 40 thru 70 ACWC 90 thru 135 ACWC 145 thru 200 ACWC 215 thru 265 Power Wiring Diagrams ACWC 40 thru 70 ACWC 90 thru 135 ACWC 145 thru 200 ACWC 215 thru 265 Electrical Data Cooler Pressure Drops Unit LoadingSuspension Points Troubleshooting Guide Causes amp Prevention of Freeze-Up bull Start-up Check Listbull Operating Data Maintenance

bullbullbullForm No 6184

PAGE NO 2 2 2 2

2 amp 3 3 4 5 5 5

6 amp 7 7

8 amp 9 10 amp 11 12 amp 13 14 amp 15

16 16 17 17

18 amp 19 20 21 22 22 23 24 24

DUNHAM-BUSH USA

INSPECTION amp HANDLING CHILLER PIPING

When unit is received it is the responsibility of the contractor to inspect the unit for shipping damage at time of off loading and make note of damage on carriers freight bill

ACWC units are factory mounted on (2) carbon steel angle beams Sizes 45 thru 90 have three lifting holes per side Sizes 110 thru 215 have four lifting holes per side and sizes 240 thru 265 have five lifting holes per side to facilitate lifting

Spreader bars must be used between rigging lines to prevent damage to the unit Rollers may be used under the skids to facilitate moving the unit a short distance

Models ACWC-40DF thru 22DC are factory mounted on two permanent angle beam carbon steel skids A minimum of four 2 78 lifting eyes are provided in the skids to allow rigging Physical damage to the unit after acceptance is not the responsibility of the factory

LOCATION amp MOUNTING

Model ACWC Air Cooled Packaged Water Chillers are designed for outdoor application and may be mounted on roof or at ground level Air lIow through the condenser is vertical and the unit may be located adjacent to outside of building or on roof without regard for prevailing wind direction

Since these units are air cooled the flow of air to and from the condenser coil must not be impeded There must be no obstruction above the unit that would tend to dellect discharge air downward where it could be recirculated back to the inlet of the unit The required overhead air space should be a minimum of eight feet Ductwork must not be applied to the fan outlets

The unit must be installed with sufficient clearance for air entrance to the condenser coil and for servicing access The unit should be located no closer than four feet from any wall or other obstruction Clearance must be provided at either end of the unit to permit removal of tubes from the chiller

Unit must be set on a solid and level foundation

On roof installations the unit should be mounted on support beams which span load-bearing walls to prevent excessive vibration

On ground level installations the unit should be mounted on a substantial base that will not settle A one-piece concrete slab with footings extended below the frost line is recommended A space should be left between the slab and the building to prevent the transmission of sound and vibration

Vibration mounts may be used for roof-mounted units or other locations where noise might be objectionable

WIRING

A unit wiring diagram showing the required power supply characteristics and all factory supplied wiring details are provided with unit Separate field supplied disconnects must be installed for the power and control circuits and should be within the sight of the unit

Separate 115-volt power source must be field supplied to provide power for control and heater circuits if optional control circuit transformer is not provided All electrical connections should be periodically tightened

The chiller inlet (return) water pipe should be connected to the water connection closest to the control panel end of the unit and the outlet (supply) water pipe connected to the water connection on the opposite end of the cooler(s)

A flow switch must be installed in a straight horizontal section of the chilled water piping This is to be field installed

Gauges should be installed in the piping to and from the chiller to measure the pressure drop and to insure the proper (GPM) flow rate in accordance with submittal data A strainer should be installed in the piping on the inlet side of the chiller and vibration eliminators should be employed on both the inlet and outlet pipes Air vents should be located at all high points in the piping system Vents should be located to be accessible to servicing Drain connections should be provided at all low points to permit complete drainage of chiller and piping system

The chilled water piping should be insulated to reduce heat pickup and to prevent condensation If the system is for year-round operation or if it will not be drained in the winter the chilled water piping should be protected against freezing by electric heating cable or other suitable means

Upon completion of chiller piping start the system water pump and purge air from the system Air purging should be done from the high points in the water circuit Purging of the chiller barrel may be accomplished through the vent pipe located on the top of the chiller compartment Failure to purge air from the water circuit will result in inadequate water flow and may cause the unit to cutout

STARTmiddotUP Refer to start test and check list included with this manual

2

CAUTION

The discharge line valve must be open before starting the compressor Liquid line valves must also be open for sustained operation

All compressors are solid mounted on isopads therefore compressor hold-down bolts must not be loosened Loosening these bolts will cause excessive vibration of the compressor and may result in refrigerant line breakage Prior to start-up check all compressor hold-down bolts for tightness

MAINTENANCE

CONDENSER Units are equipped with direct drive fans that have inherently protected motors with permanently lubricated bearings

The air inlet of the condenser coil should be kept clean through a regular maintenance program

COMPRESSOR

1 OIL LEVEL - The oil level in the compressor(s) should be checked periodically with the compressor either running or stopped If the oil level is below one-half (12) the sight glass oil must be added

2 RECOMMENDED OIL -- The unit 4 factory-charged with DB SR-30 refrigeration 01

Do not add any other type of oil to this factory charge

Do not operate compressor If 011 level Is below one-half (12) sight glass

If the oil level is below the minimum specified above and DB SR-30 is not on hand you may drain the entire factory oil charge then refill with SUNISO 4GS refrigeration oil The factory (DB) oil is of the synthetic type and will not mix with SUNISO 4GS Do not attempt to operate the screw compressor with any oil other than these two specified above

It is suggested that a gallon or mom of DB SR-30 oil be obtained and kept on hand at the job site The substitution of SUNISO 4GS oil as outlined above will result in a 2 to 491 capacity loss and no reduction in input KW

PROCEDURE FOR ADDING OIL

Install temporary jumper wire around LPcontrol contacts of circuit to be serviced Manually close liquid line service valve Lower return water T-STAT (T1) setting to start compressor Run compressor until minimum positive pressure reading on suction service gauge (Do not run compressor in vacuum) Place the system onoff switch in the off position Close the line valve in the discharge line between compressor amp condenser Equalized pressure should now be a minimum of refrigerant vapor Reopen discharge line valve Remove jumper wire from pressure control Open liquid line service valve

3 COMPRESSOR REPAIRS (internal) - Contact factory or an authorized DB Service Agency if a compressor malfunction is suspected

4 COMPRESSOR REPAIRS (External) - Proper operation of unloaded ban loading and unloading is controlled by solenoid valves UL-1 UL-2 and UL-3 Any of these three (3) solenoid valves may be repaired or replaced in the field as required

5 Standard oil acid test kit is not compatible with synthetic oil See DB color chart for oil condition

HIGHPRESSURE PORT

SIGHT GLASS I

CRANKCASE HEATER

3

SLIDE VALVE UNLOADING SYSTEM

The Rotary screw compressor capacity control system for infinite modulation consists of a slide valve and hydraulic pistoncylinder operator intemal to the compressor plus three hydraulic solenoid valves (UL-1 UL-2 amp UL-3)

The slide valve forms a portion of the chamber wall in which the rotors turn thus its position with respect to the rotors determines the effective rotor length and thereby the percent of full load capacity

Upon compressor start-up UL-3 is opened This allows oil pressure to act upon the hydraulic piston holding it in the fully unloaded position After 30 seconds during which time full oil flow is established to all bearings surfaces UL-3 is closed At this point the temperature controller is free to open and close UL-1 or UL-2 in response to the supply water temperature

The slide valve will move to the left (loading) by force of discharge pressure whenever UL-1 opens to permit flow to the oil return (low

Load

centJ

Screw Rotor

Slide Valve

Unload

~ Oil Pressure

Oil Pressure Lines

Hydraulic Piston

pressure) line The slide valve will move to the right (unloading) whenever UL-2 opens the oil supply (high pressure) line since the force of the oil exceeds that of the discharge gas

The temperature controller sends a series of power (energizing) pulses to the appropriate solenoid to adjust to load conditions The further the supply water temperature is from the controller set point the longer is the duration of the pulses The series of pulses will continue until the controller is satisfied As the water temperature approaches the set point the pulses become quite brief to prevent overshooting the set point

This method of compressor unloading in conjunction with supply water sensing minimizes actionreaction lag time and overshoot resulting in an exceptionally precise and stable control of supply water temperature

Oil Oil Return Supply

The following table lists solenoid valve position for all three operating modes

UL-1 UL-2 UL-3 Starting Close Close Open Loadinq Open Close Close Unloading Close Open Close

4

LOW AMBIENT OPERATION

Due to the wide range of applications it is sometimes necessary to operate the Air Cooled Packaged Water Chillers at ambients below summer conditions Without proper control when ambients drop below 60degF the pressure differential between the condenser and the evaporator is below the level to insure proper thermal expansion valve operation As a result the unit may cycle off Two types of system control are available allowing the units to operate at the ambients indicated

FAN CYCLING MEDIUM AMBIENT CONTROL TO 30degF

(STANDARD EQUIPMENT-FACTORY INSTALLED)

A fan cycling control is standard on all Air Cooled Packaged Water Chillers to provide proper operating head pressures in ambient conditions to 30degF

This is an automatic operation in which the condenser fans are cycled on and off as required in response to head pressure This arrangement provides positive start-up control down to +30degF by delaying the condenser fan operation until a predetermined head pressure is obtained

LOW AMBIENT CONTROL TO OdegF

In conjunction with the standard fan cycling feature all compressors are enclosed in individual housings This housing assures adequate compressor oil temperature for lubrication A five minute time delay relay provides a bypass around the low pressure control to prevent nuisance trip-out during cold start up

COOLER FREEZE PROTECTION-LOW AMBIENT

Cooler freeze protection is a major concern with air cooled chillers To protect against freeze-up a heater cable is provided as standard which protects the cooler to -12degF However there is no freeze protection in the event of power failure or heater cable burnout so the following should be considered for additional protection

1 Drain the cooler and chilled water piping if the chiller is not to be operated over the winter months Drain connections are provided on the coolers

2 Add ethylene glycol to the chilled water system Freeze point should be approximately 10degFbelow minimum design ambient temperature See Page 11 for Glycol Performance

The cooler heater is wired to the control panel and is operational from the factory offered control transformer or field supplied control power

COOLER FREEZE PROTECTION-oPERATION

The ACWC-SD chiller is provided with a temperature sensing freezstat (38deg set point) and a field installed flow switch shutting off the compressors on loss of water flow is also required

Optional low pressure or hot gas bypass freeze protection is also available on the ACWC-SD If these options have not been purchased it is extremely important to guarantee proper chiller water gpm as well as double checking the temperature sensing freezstat calibration

ACWC-SD CONTROL SETTINGS

CUT-INCUT-OUT (PSIG)

UNIT FLP1 FLP2 FLP3 FLP4 FLP5 FLP6 FLP7 FLP8 FLP9 FLP10 FLP11 FLP12 FLP13 FLP14 ISM 44-55 280170 295180

70 260160 275175 2901215

90 260160 275175 2901215 260160 275175 2901215

110-135 260160 2751175 2851210 2951235 2601160 275175 285210 2951235

145-160 280170 2951180 260160 275175 2901215 260160 275175 2901215

185-200 280170 295180 260160 275175 2951235 2951235 260160 275175 285210 2951235 215 260160 275175 2901215 260160 2901215 2901215 260160 275175 290215 260160 275175 290215

240 260160 260160 275175 275175 2901215 2901215 260160 260160 275175 275175 2851210 2851210 295235 2951235

265 260160 260160 275175 275175 2851210 2851210 295235 2951235 260160 260160 275175 275175 285210 2851210 2951235

TEMPERATURE ACTUATED LEGEND FACTORY SETTING

Chiller Low Water Temperature Thermostat T2 Cut-Out 3rF Chiller Heater Thermostat

I(Non-Adiustable) Included With CBH1 Heater

Cut-In Cut-Out

40degF 45degF

Oil Temperature Safety Control (Adjustable) Manual Reset

OTS 1 OTS 2 OTS3

Cut-Out 240degF

Capacity Control Thermostat (Adj) Mode Control Position T1 Dial Set At 44degF

UNIT OPERATING LIMITATIONS

1 Maximum ambient air to condenser is 110degF (60 Hertz operation) 2 Maximum allowable cooler water pressure is 150 PSIG 3 Maximum allowable water temperature to cooler is 75degF 4 Units must not have leaving water temperatures of 42degF or lower unless used with a glycol solution

5

KEY TO WIRING DIAGRAM INDEXING SYSTEM

The wiring diagrams and sequence instructions on the following pages have been devised to simplify the understanding and tracing of circuit theory The following key shows how the indexing system can be used

12 Line number on wiring diagram

[12] Line number in text

(R5) Component identification symbol in text (Relay 5)

[E] Normally open contact - line number location

[E] Normally closed contact - line number location

Holding coil - line number location

amp Note number

SEQUENCE OF OPERATION (TYPICAL) MODELS ACWC 90-135 SO

The following sequence of operation is typical for all ACWC SD Models Refer to the wiring diagram furnished with the unit for specific information ( ) Control Identification Symbol [ ] Circuit Line Number

Important Notel With all the control circuit switches (SW1-SW3) in the off position and the staging thermostat (T1) to its highest temperature Terminals 2 and 4 on the Terminal Board (TER5) must have 115 volts supshyplied for a minimum of 24 hours to energize the compressor crankshycase heaters (CCH1 2) [6 8]

Preliminary Sequence Close the main power disconnect switch Check to see that the red indicating light on the phase loss monitor (PLM 1) is lit (Note There will be two phase loss monitors (PLM1) and (PLM2) on dual power block models) This light must be on to indicate proper phase rotation for the compressors If the light is not on disconnect the main power and reverse any two phase legs at the Main Incoming Power Terminal Block (WARNING DO NOT REVERSE THE LEADS ON THE PHASE LOSS MONITOR FOR THIS WILL ALLOW THE COMPRESSORS TO RUN BACKWARDS CAUSING SEVERE DAMAGE AND WILL VOID THE COMPRESSOR WARRANTY)

The crankcase heater relay contacts (R3) [6] and (R4) [8] are closed and are supplying power to the compressor crankcase heaters Power is also supplied to the chiller barrel heater (CBH1) [13) the optional receiver heaters (RH1 2 [1011] and the optional convenience outlet (CO) [14]

Control power goes through the control panel circuit breaker (CB1) [8] and field supplied remote time clock [36] Check to make sure time clock contacts close during occupied modes

Start up the chilled water pump The water flow is confirmed when the water flow switch completes the electrical circuit across Terminals 15 and 16 [38] on Terminal Board (TER5) Terminals 17 [47] and 18 [49] provide an interlock for the water pump starter(s) when either compressor is in operation Set the thermostat (T1) to the desired leaving water temperature (eg 44degF) Set point adjustment is acshycomplished directly on the control

Place the three (3) control circuit switches (SW1-SW3) in the On position thus energizing the balance of the control circuit [23] [33] [36] The system will be in the Time-In mode for five minutes before the first compressor will start

The low ambient lockout thermostat (LAT1) [38] and temperature freezestat (T2) [38] must also be satisfied to allow compressor operashytion

Stage 1 Starting Upon demand for cooling thefirst stepof the staging thermostat (T1) will be to close energizing relays (R1) [61] time delay (TD1) [60] and the optional time delay (TD3) [62] If all the safety controls and switches are closed (see Safety Controls section for more detail) the control

circuit for Compressor No1 will energize allowing the compressor to start Relay (R5) [20] will energize closing the normally open (NO) set of contacts [23] which energize the liquid line solenoid valve (SOL1) [23] Another set of NO contacts on (R5) [20) provide a series intershylock with all the safety and operating controls which will lock out the compressor if any safety trips during normal operation (See Note 6 on Wire Diagram) The last set of NO contacts on (R5) [48) provides an interlock circuit for the water circuiting pump(s)

The fan contactor (C13) [23] will also close supplying power to the side of the fan cycling pressure controls (See Power Wiring Diagram)

Note The fan motors are controlled by their own fan cycling controls and will cut in at different factory set head pressures

Time Delay (TD1) [601) has two (2) sets of contacts the first set of (TD1) [19] normally closed (NC) contacts provide a 30 second jumper around the low pressure control (LP1) [20] to prevent short cycling during start-up The second set of (TD1) [24) contacts in the NC posishytion power the unloader solenoid (UL3-1) [24] which hold the comshypressor in the full unload position for 30 seconds After (TD1) [60] times out (30 seconds) the contacts for the unloader solenoid (UL3-1) open and the NO set close which energize the relay (R3) [25]

Stage 1 Modulation Upon energizing relay (R3) [25) the crankcase heater (CCH 1) [6] is de-energized and the NO contacts of relay (R3) [45 48] are closed allowing the thermostat (T1) to energize the load solenoid (UL1-1) [45) and the unload solenoid (UL2-1) [481] upon demand The opshytional time delay (TD3) [62] is used to bypass low pressure control (LP1) [20] for five minutes for low ambient starts

Stage 2 Starting Subsequent to the start of Compressor No1 an approximate five minute time delay is incorporated into the microprocessor After this time delay and a further call for cooling the second step of the stagshying thermostat (T1) will close This will energize relay (R2) [58] time delay (TD2) [57] and the optional time delay (TD4) [59] If all the safety controls and switches are closed (see Safety Control section for more details) the control circuit for Compressor No2 will energize allowing the compressor to start Relay (R6) [3D] will energize allowshying the liquid line solenoid valve (SOL2) [331] to energize Relay (R6) [3D]will also interlock the water pump starters and the safety controls the same as Compressor No 1 circuit

The fan contactor (C14) [33] will close supplying power to the line side of the fan cycling pressure controls (See Power Wiring Diagram)

Time delay (TD2) will provide a 30 second jumper around the low pressure control (LP2) [30] and will energize the full unload solenoid (UL 3-2) [34] for 30 seconds then energize relay (R4) [35]

Upon energizing relay (R4) [35] the crankcase heater (CCH2) [8] is de-energized and the NO contacts of relay (R4) [46 49) are closed allowing the thermostat (T1) to energize the load solenoid (UL2-1) [46] and the unload solenoid (UL2-2) [49] upon demand

6

SHUTDOWN SEQUENCE

Stage 2 Shutdown Stage 1 Shutdown

After both compressors have unloaded fully and the leaving water temperature is still lower than the setpoint the second step of the thermostat (T1) will open and de-energize relay (R2) [58] providing an approximate five minute time delay again integral with the microshyprocessor has expired subsequent to the start of Compressor No2 This will close the liquid line solenoid (SOL2) [33] and turn off Comshypressor No2 Compressor No 1 will load and unload as required Compressor No2 will not be able to restart for five minutes due to integral time delays

SAFETY CONTROLS

The unit is protected by the following safety controls

1 High Pressure (HP) 2 Low Pressure (LP) (automatic reset) 3 High Discharge Temperature (OTS) 4 Compressor Solid State Module (CSTM) 5 Low Water Temperature (T2) 6 Low Ambient Thermostat (LAT) 7 Compressor Starter Overloads (OLH) (optional) 8 Phase Loss Monitor (PLM) 9 Control Circuit Breaker (CB1)

If any of these devices should open due to abnormal conditions the compressor(s) will automatically stop All controls must be manually reset except low ambient thermostat (LAT) and phase loss monitor (PLM) The individual compressor safeties (HP LP OTS and CSTM) contacts are found on Lines 20 (CTT1) or Line 30 (CTT1) The other safeties listed above are discussed in the preliminary sequence section

If the leaving water temperature is still lower than the setpoint the first step of the thermostat (T1) will open and de-energize relay(RI) [61]This will close the liquid line solenoid (SOL 1) [23] and turn off Compressor NO1 as long as it has run for approximately three minutes Compresshysor NO1 will not be able to restart for five minutes

FIELD CONTROL WIRING

In addition to 3 phase power (and optional 115 volt control) wiring described above the following control interlock wiring is recommended The as built control schematic provided with the unit provides detailed information Typical control schematics are as shown on pages 8-15

1) Alarm Circuit -Terminals 6-13 (2 per compressor circuit) can be used to trigger remote failure lights or alarm bells in the event of a refrigeration failure

2) Time Clock - All unit on-off control should be done through terminals 15 and 16 An open contact shuts down the unit Time clock night shut down and energy management shut down should all be done from these terminals and contacts should be applied in series

3) Flow Switch - The flow switch contacts should be installed between terminals 15 and 16 and be in series with time clock contacts

4) Chilled Water Pump - The control of the chilled water pump must be worked out by the system designer It is necessary for the pump to be on during any compressor operation and terminals 17 and 18 should be used to energize the pump starter However it is likely that the pump should remain on throughout all occupied operation or even at night for freeze protection Terminals 17 and 18 should not be the sole means of controlling pump operation

STARmiddotDELTA STARTING OPEN TRANSITION (OPTIONAL)

Typical For All Compressors On initial call for cooling staging relay (R1) holding coil will energize The (R1) contacts 7-4 close energizing star contactor (S1) and the five second transition timer (TD5) Transition contactor (S1) power contacts close tying the center legs of the compressor motor windings together into Star (WYE) configuration At the same time (S1) NC (Normally Closed) auxiliary contacts open preventing (C2) from closing (S1) NO (Normally Open) auxiliary contacts then close energizing contactor (C1) The (C1) power contacts close applying power to the

compressor winding (C1) NO (Normally Open) auxiliary contacts close locking (C1) in the energized position The compressor operates in the Star mode until (TD5) transition timer times out (five seconds) at which time contacts NC open and de-energize (S1) Star contactor (S1) NC auxiliary contacts close (TD5) timer NO contacts close energizing compressor contactor (C2) power contacts close thereby completing the Delta wiring configuration Compressor contactor (C2) NC auxiliary contacts open preventing (S1) star contactor from energizing until the next starting sequence

7

--

exgt

LE

GE

ND

m

rrbullbull

saN

OI

IlIG

CI-

Z

CO

HT

AC

TQ

ftmiddot (

0

[5

10

1t5

el

) C

ON

TA

ClO

middot A

NS

(C

UlT

middot pound

AM

III

bull C

ON

TO

L

(C

UlT

C

UtC

UIT

Ulaquo

III

H

IAT

EIt

I C

HllL

rU

lU

[AT

III

CU

Ne(

ASE

H

un

co

U

OIl

ll

SOL

ID

TA

U

MO

OU

Lt

H

US

UII

lI[

con

RO

L

LOW

Abullbull

IN

T

[

twO

fI

lO

W

nul

tt C

ON

TIIlI

OL

OIL

TU

II

r

UIIl

I(

SA

HA

S[

0

1$

M

ON

t T

O

lllE

LA

Tmiddot

tTA

GIH

O

1t[

LU

-U

CIT

Y ~OL

bull

CI

l

tC5

I H

el

C

Ubullbull

e

lHI

CC

HI

esr

P

I L

UI

VI

enst

P

LU

11

0)

(L

AY

middot tN

Uft

LO

CK

(

L[N

OIO

middot L

lOU

IO L

INI

SWIT

CN

CO

W

UD

C

C

UIT

S

SWIT

CH

ST

EN

fH(

MO

ST

AT

middot S

[OU

[Ne

EIt

TH

UM

OS

Tn

-L

OW

n

llI

IUU

[

TtIt

WIN

AL

10amp

1110

cu

no

wE

It

UN

I J

SO

LI

w

10

Tl T[l

Il

S

Tl

Ufl

Ul

10

0

-

CT

OII

I

WIl

WO

T

lM[

HU

T c

alli

CO

NTbull

bull L

OW

Ipound

n

LO

CC 0

1

TO

T

IllS

I

ond

tlt

UN

Lo

ao

t

OL

(NO

ID bull

(O

M

no

ll

Ul

ImiddotZ

~(

tU

IIL

T

IIS

VI

O

I

_

-~

OIO

HA

l

ell

C

UtC

Ul

[

amp1

(( -

(cri

VE

lli K

uru

en

C

IAC

Uff

A

UK

(jII

f bull

CO

[

I(

C(

OV

TL

lT

CI

I (O

NU

OL

If

Jll

AIr

IS

HO

UA

W

(fIA

S

LL

Tl

LO

AO

LI

T

(III

WO

STA

T

0

middot

5

O

(III

LO

AO

fU

UIS

LImiddot

H

OT

L

IGH

TS

H

IUC

IIY

[1II

H

[AU

IIIS

~ jllf

M1

III[

Cll

[

H

[U

t

US

UII

ll[

CO

NT

IIO

LS

~tCt

JVII

l N

(AU

III

14

(0

1

T

O)

TO

wI

DtL

AY

amp L

OW

U

tu

LO

CK

ou

r rt

(

O(L

IN

SlT

IO

C

OH

TA

(TO

Il

(O~USO

C

OH

O

lll

bull iT

A

OlL

C

Ol

CO

MV

[Nf

epound

o

un

n

Ctft

CU

lT I

DE

TA

IL

A

SlA

M

DE

LTA

ST

AR

T

O -~

OA

~ 5~U

Z

OI

Cl

U

I 14

(I

amp

~

NC

f

cl

AU

I

51

ZtA

LU

TOO C

21

NO

~~

bullbull

N

WHT

I---

I

l I J

II

A

CN

lCU

lT

If

OOHAI~

l

~i1

WH

It[

-

OI

ON

AL

r---

----

---

-I

Q

WT

I lt

raquo

I I L

JI

bull bull

I I

0

II

-

lJ

_ Ij

lf

I

cal

II

iOO

w

shy

) C

it

~

WTI~AL

r --------------------------------

Iamp

I

_l

[0

0

I

OO

CM

lL

00

LO

II

cu

U

II

bullL

~J

It

_U

I

TH

u

I

HT

I~

r-~~

~ --

-I=

=~==

=~I

11

2

N

~~~

~--

----

----

=~

I

-lt

l

= I

en

co

o J

rO~

2

~L

----------

-

-oS

f

I

r--shy

J

on

T

O)

vI

Q~~A

J T

Ot

L-

ll~_

f

1

II

CU

H ~

~OI

L1

-i

r---

----

-

~

10

rc

I

bullbull

lf

OIS

ti

l W

I H

Z

01

11

1

-J

o

u

L

shy

0bull

-

0 T

1

111

A -

bull 0

[0

HT

I

ll II

rgt ---

-ij

---

ITl~ll

t

1amp

I

1t

D

MIN

I[D

11

~

ill HTAILmiddot~

O

LM

I 01

1

OL

HJ

III0

1l~

tM

Ow

N

CI

amp

tt

I w

lO

OIO

HL

---

__

J

O ~

~Ll

~

tB1

It

CI)

n

IS

-1

M

k

V

Io

Jmiddot

r---

1

we

14

-4

I

Mill

I

CO

MPR

ESS

OR

C

IRC

UIT

I

Til

bull ~

r-

so li

e II

It

S

tON

L

N

O

fll

II

If

II

~

s~

o

oc

gt

(I)

r in

n

100

00U

lz

--I

~o

e

0

r ce

cn

shy0

0

Z

Ggt

bullbull bullbull bullbull bullbull bullbull bullbull

r~T~-

ICt

MQ

Teuro

CO

MT

It01

I T

IM C

lot

ll

~---

Cl

ll

(O

41

(

flO

W

5Wlf

CH

~

I

Olt

CO

NT

AC

TO

C

OIL

S C

I-I

bull C

tS

AN

D S

t sn

N

OW

IIt

Dll

QU

0

1 C

OM

UC

TI

I

111

114

0

(

U

II

NO

f T

O I

(

C

uNO

IO

ON

UtI

se

CO

HO

UI

li

D(

1

A

ND

1

n

WP

(IU

ult

l S

(NIC

tf1

I

LO

CU

ID

1M bullbullU

O

UT

UT

r-

----

shybullbull

0

11

UO

V

HA

Il

LO

IS

raquoON

TO

S

TE

lurN

AU

bull

AN

D

0111

IIC

O(

I A

ND

A

U(

Cfl

YpoundL

Y

So

C

rt

TO

0

0 M

AN

UA

L a

ll H

TO

tNT

AN

D

~10l

IA

NO

M

TII

UC

TtO

NS

II

rCO

tNO

m

IMIT

AL

CO

H

laquo

0

U

TI

I It

4

Ishy

C

OW

III

ISO

R

MO

DU

LES

dC

NO

MmiddotA

U

VA

TC

I

D

U

1111

WIL

L A

LSO

LO

C_ O

UT

(

let

Umiddot

I C

AL

L

WH

IM

IAI

TY

flit

TH

[I(

CO

Nmiddot

I

OL

I CA

Jrf I

I II

EM

T

IT T

Uft

I1

tW

ITC

H bullbull

0

VO

NIN

IL

f PO

C

Obullbull

bull

I w

UII

II

I

C

IL

Llf

i I

ITA

f[1

II

ItV

N

IWIT

ti r

raquo7

~Slt~1

~~~~( 1~~~~tlDOO

CO

N

CT

O

WU

UH

O 0f

II C

OW

bullbullbullbull

~~1

II

bull

LL

TI

lIT

AT

0

N

O 1

0 O

CA

TID

1

1 I

I IIl

ETU

IIPt

W4T

P

LU

WHE

N u

TI

It N

OT

lU

u

rD

ttl

III I

ICO

Ma-

aU

0 11

nM

H

u

l

UN

I()1

II M

UST

HA

V(

SH

llL

DID

C

AU

I

LO

Me

T

II

no O

R

ItUM

WT

M

ItO

WI

L

IAH

to u

ri N

T I

T H

-

ITbullbull

O

N

ft

0

-

011

II~T

K

ITI

GU

ION

An

ON

S

o H

O-

ON

G C

OI

-W

it

11

N(

NO

6 N

c

CO

NU

ClI

W

If

lIN

( N

O

o N

0

CO

NT

AC

TS

WIt

K

liN

t N

O

6 N

OT

t I

TH

L

Nt

NO

Y S

UI

-I

IS

5_

1

~

~

no

~ I

I I_

VLOA

Or- I

I ~~

vumiddot

S1 so

CO

Hit

so

0

amp

g A

SI ~

I

1

7100-

I -I

I 01

10

OH

0

10

f T

AN

I V

I

] CM

NG

( av

rlt

10

0 O

K__

ST

AG

(

COD

lJ-

L7

00

~It

A

lIT

00]

VL

I fi

ll

14

1

10A

O

f

_ III

rC

OH

O

In o

y

00bull

00

10 ~

0

10

CO

Ol

C

bull

] 4

U

rr

COL~

bull Jo

un

J

W bull

C~P

OJ [

ou

-t

urO

NT

01

CO

l0

1

N

Omiddot

~ ]

(jCO~_

0

)

un

ll

n ~

T

I 11

I1

III _~

n

~

amp

7

10

II

01

u II 17

II

0

II

01

IS

-I

-lt

sE

o

0 c

raquo

CD

r iii

0

~O

U

lZ

+-1

~

tI

t

0

r QE

CIJ

-c

tl

Z

Ggt

lt0

bullbull bullbull

bullbull

bullbullbullbull

~

o

tUN

oa

lllO

_--

-

shyC

t-4

CII

C

cn

bull

tlN

I

CC

HImiddot

t

csnu

middota

--1

LA

T

loP

a

01

11

-1

111

111

IIImiddota

It

4

IOL

IS

IW

Imiddot

I

I T

I n flbull

bull

TO

middot I

st

U

LImiddot

a

Oft

lo

tL

LtG

EN

D

CO

NlA

CT

IM ~

CO

lllf

lllt

UtO

JII

CO

NT

AC

TO

CII

CU

fT

IIIC

AICC

III

CO

NTJ

IIOL

CIC

UIT

U

NImiddot

HU

TI

eNU

LlII

I

Il

I

AU

It

C

NlaquoC

AU

NC

An

C

O

UIO

10

LIO

T

AU

N

t U

SU

I C

O T

OO

L LO

W

eT

fM

llltM

OT

AT

L

OW

Hl

III

UII

I C

Oft

TJl

OL

OU

n

ru

ulltl

A

nT

T

HA

-

0bullbull M

OH

IfOIt

fl

lLA

Y I

AO

INI

MU

C

AN

cn

CO

fTltO

Ibull

ItIL

A

INT

ILO

CIC

OL

EN

OtD

Ll

OU

ID L

INt

Cc

ulT

MOO

ULIE

C

NIC

CA

SE

ItS

C

(

OM

II

IOII

(lI

IieLf

W

I eM

-

UIE

R

TH

III

OIT

6Tmiddot S

lOU

lC

U

MC

ot

LOW

TlM

e

U1

T

lER

bullbull

L l

OA

JIIO

middotCU

lTo

tJ

II W

UU

Nt

TI

M

AL

IO

D

oC

0It

1 U

IIN

t T

IMe

OC

LU

middotCA

II C

ONT

a

LOW

IU

t L

OCK

OUT

NPD

WIU

UN

LOA

Olil

t 1

0L

(NO

I0

C

O

III

OIl

lI

cn

CIJ

tCU

IT

UII

lEIt

ft

EC

poundIV

E H

IAI

C

Ol

(C

UIT

1I

IUIIl

I1II

CO

NY

(NIE

NC

E

OU

TU

T

CU

I C

ON

nlo

0

1

AN

$ M

ill1

1

HO

YIll

MU

II

lLT

I l

OA

O

LlI

lIIT

T

H(

O

ITA

T

OL

O

VC

LO

AO

MIA

nl

L1

lI1

~HAII

LO

IS

MO

NIT

O

L

Imiddot J

~fOT

L

IOH

TS

1

1

IC

IIV

E

HE

UE

ItM

lIC

tmiddotl

rC

IIV

E

MU

TlI

t l

tIIS

UIl

l(

CO

NT

ItO

LI

T

lmiddot1

C

CC

lvllt

N

EA

fllt

T

lW

OS

TA

lI

TO

Jmiddot 4

T

INe

H

LA

Y

LOW

In

vlt

l LO

C

OU

T

1O

t-1

ft

lll

D

UA

Tmiddot

TA

SIT

ION

C

ON

TAC

TO

Ill

$middot

1

CO

C

O

(

lIO

C

ON

TA

CT

O

T

A

Dn

u

CO

WC

tllltN

CI

ount

T

DE1AIL~

ST

AR

D

EL

TA

S

TA

RT

r

2

~f

10

t10

II

amp

II

11

II

)

1IllI

1IU

--shy

OW

E

IV

-

utv

lO

f

I I Ibull

A

UR

C

IlltC

UIT

C

IRC

UIT

ALA

NlC

UfT

C

lflC

UIT

I I

I

~li

IT

I

Ot

ON

AL

il------~---l

-

tL

J --

--

C

it

prIlgjf~

II

ell

I

I

IfB

I

t

---------~~-------

__

~

L_ -

7 -

-r--

et

r

I

II10

-I

CII

-lt

PL

1amp

I I

II b

I

L _

__

J

II 3

2I

oo

II

Qraquo

~

IS

lI

(

)r-

t-_

_ o

J_

_

O

TIO

L

I ~~

--~-

I

I CD

oL

__

__

__

__

__

CO

I- f

_

JI I

t degz

OI

OIl

lAL

r-

---

IS

r

-l

0

I

I

+10$

IL

KS

I T

e

0 Lr

I J

II

T

ITI

lOL

l 1

40

bull (C

IS)

TO

bullbull

lD

A-

~ -

r--

-~l

)~II

I

~G

__

_~L_J

0

O

HA

I

~ -

-Ill

-

---

-10-

--

~E

II

cn

-C~

II

Z

0

G)

Il

l~

r- I W

lllltO

WH

IN

JU

L1

l0

I I

I

OL

M

OL

MI

OL

I ~ro

o

jo

o

Jt

JI

L

OT

10N

AI

II

0

(01

0 CO

MPR

ESS

OR

C

IRC

UIT

~

27

III

gt

0

IIA

IO

amp1

)amp

1

1

II

~

I rA

I

TA~

D

ELTA

STA~T

CONP~E~)

CU

lT 2

~

f

bull ]

A

U

4 ]I

IUft

middotJI

Mon

tUPlOI

NT

lOA

Ot-

-O

I

01

0

]

(N

GI

011

1

00

CT

AN

)

40

00

HN

a

_N

I

J00

I -

It IC

y

TO

I

I I

I

~

oiiO

NA

t

I bull bull

wi

i

lOa

r~TT~-

I M

OT

I C

ON

sr

0

llItt

(

co

ce

OZ

UK

1

11

_JO

I I

)--11

--

- ---

-

IJI

LD

~

I

A

CK

lS

C

UK

I

IL

UO

A

TO

O

WH

IT

1

L

OW

SW

ITC

HJl

AL

D

00

IZ

I

f

1It-

-

rl__ u-

poundL

J f

aT

ION

AL

TI

WfI

OO

f

~

ff

I

Dill

C

ON

TAC

TOIlI

C

OtL

S (1

middot4

(IS

middot14

A

ND

II-

I

01

1In

N

O

Wl

0

51

11

~

CO

NT

AC

TS

I

fH

IO

Uti

IS

N

OT

TO

IE

al

llauN

DIO

O

N H

I Sr

CO

NO

AIl

lf

StO

l

f

I

TI

AN

D

TI

TI

U

I

IIN

OII

t

0middot

f1L

OC

AT

IO

IN n

lll

GU

lUT

r-

----

shy~

(I

G

lIt

no

v

HA

I

LO

SS M

ON

IO

nf

1Na

bull

AN

D

ON

rc

I(

CO

M(

f A

IrfD

I

lItU

rC

TIY

(U

00

-

5

E

[CO

OIO

lItc

rlll

TO

0

0

AN

UA

L

t

OIN

T A

Na

f

oo

IlU

COfrt

TO

I U

ND

IN

Stt

UC

TIO

trl

r

co

rNH

D

01 11

raquoIN

ITIA

L

CO

NT

lIIiO

L

fII

I0 I

UT

IS

a

jshy

orshy

10bull

CO

M1

II1t1

Ol

MO

GU

LI

I N(

tN-a

UT

OM

AT

lC

I 1I

lfla

n

flS

bullbull

11

A

LSO

ampO

eMmiddotO

UT

luer

llt

middot I

no

C

AL

Y

WH

IM A

N

IUIT

T T

IIII

P

T

MU

I C

ON

egoo

IT

flO

LI

CA

l

ItU

I1 I

T

TU

NIN

G W

ITC

M

0

~r=

0 I

lIO

Wlf

lIT

A

L

fOtt

CO

lI

tbullbull

w

ITC

H_

I

on

WO

Nlf

lIT

JII

IL

POllt

COW

bull

I In

degz

r+-i

~~

t

u ~o

1 ~rI~~

~~

~~TtIc~~I~D

1

SW

lTC

HI ~

C

OIfT

AC

TcU

t W

lItN

t C

OM

bullbull

H

To

lIL

b

l

0t~~1

0

1

CO

tfC

TO

H

I

lIt

C

ltbull

IIT

C

~r-

bull

WM

IH

-

2

N

OT

1V

l

rD

wllI

I[ to

IlIC

OM

n

I W

I

It

I

fjC

Ofl

P

tE

CJ)shy

t W

IN L

UI N

OT

SU

PL

ID

W

IIIIC

O

J

lleo

W

ti

l

LU

KT

IT

10- A

ND

10ft

II

v

C~

LO

CA

TU

I II

1t

11V

MI

_T

at

I

z10

I

T

lNH

A

TU

RC

S

lNS

OIt

MU

tT

ve

IL

OID

C

IL

C

()

11II

L

AT

I

AT

10

_

A

U

IIIT

I0middot

PCA

LOW M

I_ lO

TI

I bullbull

n

II

DES

IGN

ATI

ON

S

II

CO

NT

IlID

t I

NO

-o

MO

LD

INfl

C

OIL

It L

tNI

NO

0

Q

N

C

CO

NU

ClI

W

ITH

UN

I N

O

01]

0 co

O

f

11

~

I

ILK

n

e

s IA

UL

It

ibull

o O

CO

NTA

CTS

w

nw L

INI

NO

01

fA

0

~

fItO

TI

LI

I N

O

v

A

II

~ ~ bull i middots

~

~~ - ~

~

1- I J I J I I I I I I I I I I I I I I L __ J

I

a bull bull a bull bull

I I I

_J

r------~

=~I = ~ ~ bull ~ I I

~

as coe ruq SV~ siapow ~NI~IM lO~lN03lV3ldAl

i 4

_

a

~FirI1 u~III - I I

~ 1I

00000 -

I=II~I~~~~raquoIIIItIII~ampI~

as ooz nJ4l sv ~ siapow ~NI~IM lO~lNOgt TVgtldAl

bullbull bullbull

bullbull

~

jgt

lpoundIt

ND

II

co

----

----

----

----

----

----

----

----

-

r-~-middot--=-~~

~

bull a

~

at~04

5

---

~1I

A

~n

bullbullmiddot-shy

wo

_-

bull

lIt

C-

I C

Cf

aC

TO

Ic

ow

n

CC

eM

ca

~C

M

OD

IAI

CI

T-

CO

IITA

CT

oa

bullbull

CMCU

rT I

ItIM

IA

co-l

to

c-c

VIT

C

I

rr

c

AfE

bull r~----Ef1

POW

I

III

IQ

W

Q

tIL

UT

I1I

U__~

J

COt

I

LD

W M

lMtr

f nc

IIO

ff

0

N

LO

W

C

OIIT

INM

I I

CO

M

US

ON

C

NC

UIT

II

II

-~

_T

shy

C

O

NU

SO

II

CIN

CU

IT Z

II

D[TA~

-

ST

AN

D(~TA

IT

AII

T

0

u III

r

amp

II

-~

If

10

MA

MI

eN

talI

Tco_

~

STA

N D[~TA

ST

AII

T

~

CIS

-I

LA

~ 1-4

nmiddot

00

-

-II

1t1S

-1 aw

o fI

fl

U- I -~ Ci

Pi=

i

t

shy

~

iii

i

iii=

ii

-

-shyiii

ClL

n

TU

U

LOt

e

bull It

lLA

Yn

C

AM

Im

CIII

IID

L bull

CU

_C

Abull

fl

lUY

_f

tMO

ea

UY

middotIO

CI

lO

Ll

t

NIU

_L

N

CO

WU

UO

ItC

U

llT

l bullbull 0

1middot

lit

TMC

MI0

8TA

T tc

_lt

CIl

it

11

II

_

middotLO

W

TII

IfN

T

UIlI

C

nll

-

D-C

UlT

QIIU

tW

n-T

PII

IU

LIO

MI-

AC

TC

Ntf

Wi

MI

II

II

tY

middotCM

OO

C

LOW

HIe U

(O

Uf

lIl_

L

OA

M

1OtI

1tO

lD

CO

OA

CM

UtT

1M

C

lIY

Dl

NC

Afi

ll ea

-tU

lT 1

ItUbullbull

lI

oo

ww

lItt

lffc

e O

Un

n

cT

IlG

I

Ie-

~U

IIIC

CIV

P

1T

1lt

C

bullbull

Off

AT

tw

ebullbull

ampOW

IC

IUT

~-

4ti

iT

~

co

ww

O

UfU

T

DITA~

A

ITA

A

OEL

TA

IT

AJI

IT

co

rn~

e

I

1amp

ItmiddotI

~ bull

I I

I

I r

~

bull Iamp

II

I ~

I-

oJ

II I

IrIf

I I I I

s~

o

-I I

ltDc

() raquo

L 10

V

i

()

~O

to

U

lZr0

t2

llJ

IL

C6

J=

_J

~-1

f

II

c 0

II

N

ge

cno

c-

II

Z

Ggt

If IO

IC

IIY

II

IIR

III

IJt

T H

llII

A

Il C

Olaquof

U

TMIbull

~LDM

fI

lAR

PM

Iamp L

Oll

lTV

ii

iLii

Uii

ii

~

U3

I iL

iii=

i

Uii

u

i

O

(no)

T

bull II

1

IOA~

bullr

~ I

[gtO(]O

~ i I Ii i 2 ~ ~ ~ i a bull il 2 ~

iiibullbullbull

~ I ~ I I I ~~ =l ~ iI I ~ I I I It I 1111 amp ~~

as ooz nJ4l SP~ SlapoUII ~NI~IM 10U1NOl lVlldAl

-------

---

TYPICAL POWER WIRING Models 45 thru 70 SC

----

rYl31I01 I

-Ii --ti-

_ I ~_-

~ lniJ -

LIIbullbullbullbull PC _ amp-II _--- ~

TYPICAL POWER WIRING Models 90 thru 135 SC

- --- _ Tt

~rfh c~

tP ~

_III ~

I r-- ~- IIlJ

bull - MIl Mf __ bull Ie_~--~ _shy- shy16

---

----------

TYPICAL POWER WIRING Models 145 thru 200 SC

_ --1a1 IIUrI

middotrFti~v_ bull I

i~i ~~ TaII IIOMLI ~tN T 100 WTIOII 011 lilOOCL a

~ t1

tI bullbullbull

L

i I r-~

I r

~ ~ ~ III

2 ~ ~ ~l

- ~IlD I hJOHr eo teO acshyt CmiddotClM ~ CIKUr1 --

TYPICAL POWER WIRING Models 215 thru 265 SC

ItUU 1D Wll1U1I fIa -rMI

rt-h I -au 11 1_ i r~ rt-f

-i rn f1 ft fi i- llil bullbull c~ I bull c =

~~~ ~i~-~

~~m

~~~CI1 R~~ ~ ~~ ~llAi4I

luv~ bull ~uf LL~~-

~Mfl l~t IrMiA

a I III nII I bull it d

~-t--J I Lll-l~j ~nL4111 WlJj== lit-

I bullbullbull I

UGEND

~

~l OJ

- c~

~~~---

~)~middotI

I

L _~~~ L _I__~_J I ~ (11_1 ~ H~ CUlTMIt tffC_) Ll N

-r_ 0 1ItCIIIl0AI lllQUlllCo as -0- bull bullbull fI PC 110 lNJCllII a Olil1100pound1 II 111 el 1101 ItCOU_ 011 IIOOIL140

I 011 CI-( H[ (0110 (fMCun ubullbull --- l(lD IMbullbull Ntlf 110 e414-7

--CTOttbullbull

2

17

ELECTRICAL DATA Model Volts Type COMPRESSOR FAN MOTORS MIN CIRCUIT RECOMMENDED MAXIMUM ACWC 60 Hz of Qty RLA Starting FLA LRA AMPACITY WIRESIZE FUSESIZE

SC 3 Ph Start HP Ea Curro Ea Ea Ea Circ1 Circ2 Circ1 Circ2 Circ1 eire 2

208230 XL 1788 1040 (4) 70 (4) 380 252 - 250 - 400 -45 208230 YO (1) 50 1788 347 (4) 70 (4) 380 252 - 250 - 400 -

460 XL 737 422 (4) 35 (4) 190 106 - 2 - 175 -460 YO 737 141 (4) 35 (4) 190 106 - 2 - 175 -

208230 XL 2051 1228 (4) 70 (4) 380 284 - 300 - 450 -55 208230 YO (1) 60 2051 409 (4) 70 (4) 380 284 - 300 - 450 -

460 XL 904 485 (4) 35 (4) 190 127 - 1 - 200 -460 YO 904 162 (4) 35 (4) 190 127 - 1 - 200 -

208230 XL 2083 1415 (6) 70 (6) 380 302 350 500 -70 208230 YO (1) 75 2083 472 (6) 70 (6) 380 302 350 500 -

460 XL 974 539 (6) 35 (6) 190 143 0 225 -460 YO 974 180 (6) 35 (6 190 143 0 225 -208 XL 1788 1040 (6) 70 (6) 380 266 224 300 0000 400 400 208 YO 1788 347 (6) 70 (6) 380 266 224 300 0000 400

90 230 XL (2) 50 1788 1040 (6) 70 (6) 380 266 224 400 I300 0000 400 400 230 YO 1788 347 (6) 70 (6) 380 266 224 300 0000 400 400 460 XL 737 422 (6) 35 (6) 190 187 - 000 - 250 460 YO 737 141 (6) 35 (6) 190 187 - =1000 - 250 208 XL 2051 1228 (8) 70 (8) 380 312 256 400 300 250 208 YO 2051 409 (8) 70 (8) 380 312 256 400 300 500

110 230 XL (2) 60 2051 1228 (8) 70 (8) 380 312 256 g I350 300 SOO 450 230 YO 2051 409 (8) 70 (8) 380 312 256 350 300 500 450 460 XL 914 485 (8) 35 (8) 190 231 - 0000 - 300 460 YO 904 162 (8) 35 (8) 190 231 - 0000 - 300 -

208 XL (1) 60 2051 1228 (8) 70 (8) 380 312 260 400 300 500 450(1) 75 2083 1415

208 YO (1) 60 2051 409 (8) 70 (8) 380 312 260 400 300 500 450(1) 75 2083 472

230 XL (1) 60 2051 1228 (8) 70 (8) 380 312 260 350 300 500 450(1) 75 2083 165125

230 YO (1) 60 2051 409 (8) 70 (8) 380 02 260 350 300 500 450 (1) 75 2083 472

460 XL (1) 60 904 485 (8) 35 (8) 190 240 - 250 - 300 -(1 75 974 539

460 YO (1) 60 904 162 (8) 35 (8) 190 240 - 250 - 300 -(1) 75 974 180

208 XL 2083 1415 (8) 70 (8) 380 316 260 400 300 500 450 208 YO 2083 472 (8) 70 (8) 380 316 260 400 300 500 450

135 230 XL (2) 75 2083 1415 (8) 70 (8) 380 316 260 400 300 500 450 I 230 YO 2083 472 (8) 70 (8) 380 316 260 400 300 500 450

460 XL 974 539 (8) 35 (8) 190 247 - 250 - 300 -460 YO 974 180 (8i 35 (8) 190 247 - 250 - 300 -

208 XL (2) SO 1788 1040 (10) 70 (10) 380 326 402 400 0000 500 500(1) 60 2051 1228

208 YO (2) 50 1788 347 (10) 70 (10) 380 326 402 400 0000 500 500(1 60 2051 409

230 XL (2) 50 1788 1040 (10) 70 (10) 380 326 402 400 0000 500 500 145 (1) 60 2011 1228

230 YO (2) 50 1788 347 (10) 70 (10) 380 326 402 400 0000 500 500(1) 60 2051 409

460 XL (2) 50 737 422 (10) 35 (10) 190 295 - 350 350 --(1) 60 904 485

460 YO (2) SO 731 141 10 (35) (10)190 295 - 350 350- -(1)60 904 162

208 XL 2051 1228 (10) 70 (10) 380 326 462 400 (2)250 500 600 208 YO 2051 409 (10) 70 (10) 380 326 462 400 (2)250 500 600

160 230 XL (3) 60 2051 1228 (10) 70 (10) 380 326 462 400 (2)250 500 230 YO 2051 409 (10) 70 (10) 380 326 462 600400 (2)250 500 600 460 XL 904 485 (10) 35 (10) 190 329 - 400 - 400 460 YO 904 167 (10) 35 (10) 190 329 - 400 - 400 - I

NOTES 1 XL Across the LineYOStarDelta 2 RLA Rated LoadAmps(ratedin accordance withARI Standard 590) LRA LockedRotorAmps 3 Wire Size Amps equal125of the ratedloadampsfor the largestmotorin thecircuitplus100of the ratedloadampsfor all othermotorsin the circuit per

NEC 4 Wire size based on copperconductorswith75C insulation perNECTable310-16 Terminal block lugs are sizedaccordingly Use of oversize wiringmay

not lit in terminal blocks 5 Maximumfuse size is basedon 175to 225of the ratedloadampsfor the largestmotorin the circuitplus 100of the rated loadampsfora othermotors

in the circuit per NEC VOLTAGE TOLERANCES 208V-230V min 187VMax 253V

480V Min414V Max506V

I

18

ELECTRICAL DATA Volts Type COMPRESSORModel FAN MOTORS MINCIRCUIT RECOMMENDED MAXIMUM 60 Hz of Oty RLA Starting FLAACWC LRA AMPACITY WIRESIZE FUSE SIZE 3 Ph Start Curro EaSC HP Ea Ea Ea Cire1 Cire2 Cire1 Cire2 Cire1 Cire2 208 XL 2051(1) 60 1228 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 1415 208 YO (1) 60 2051 409 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 472 230 XL (1) 60 2051 1228 (12)70 (12) 380 341 469 500 (2) 250 500 600

12 75 2083 1415185 230 YO (1) 60 2051 409 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 472 460 XL 485 (12) 35 (1) 60 904 (12) 190 352 500 400- - -

(2) 75 974 539 460 YO (1) 60 904 162 (12) 5(12)19 352 500 400- - -

(2) 75 974 180 208 XL 2083 1415 (12) 70 (12) 380 345 469 500 500(2) 250 600

472208 YO 2083 (12) 70 345(12) 380 469 500 (2) 250 500 600 230 XL (3) 75 2083 1415 (12) 70 345(12) 380 469 500 (2) 250 500 600200 230 YO 2083 472 (12) 70 (12) 190 345 469 500 500(2) 250 600 460 XL 539974 (12) 35 (12) 190 359 - 450500 - -

180 1(12) 35 460 YO 974 (12) 190 359 450 -500- -2051 1228208 XL (12) 70 504(12) 380 504 (2) 250 (2) 250 700 700

208 YO 2051 409 (12) 70 (12) 380 504 504 (2) 250 700(2) 250 700 (4) 60 2051 1228 (12) 70 230 XL (12) 380 504 504 (2) 250 (2) 250 700 700215

YO 2051 409230 (12) 70 (12) 380 504 504 (2) 250 (2) 250 700 700 460 904 485 (12) 35 XL (12) 190 225 225 0000 0000 300 300

(12) 35 460 YO 904 162 (12) 190 300225 225 0000 0000 300 2051 1228208 XL (2) 60 (14) 70 (14) 380 504 525 (2250 700 700(2)300

(2) 75 2083 1415 2051 409 (14) 70 700 700208 YO (2) 60 (14) 380 504 525 (2) 250 (2)300

(2) 75 2083 472240 700XL (2) 60 2051 1228 (14) 70 (14) 380 504 525 (2)250 (2)300 700230

(2) 75 2083 1415 2011230 YO (2) 60 409 (14) 70 (14) 380 504 525 (2) 250 (2)300 700 700

(2) 75 2083 472 300460 XL (2) 60 904 485 (14) 35 (14) 190 225 248 0000 250 300

12 75 974 539 904 162 250 300 300460 YO (2) 60 (14) 35 (14) 190 225 248 410

(2) 75 974 180 2083 1415 (2)300 700 700XL (16) 70 (16) 380 525 525 (2)300208 2083 1415 (2)300 700 700208 YO (16) 70 525 525 (2)300(16) 380

700 7002083 1415 (16) 70 (2300230 XL (16) 380 525 525 (2300 700 700(2300(4) 75 2083 472 (16) 70 (16) 380 525 525 (2300230 XL265

300250 300974 539 (16) 35 248 248 250XL (16) 380 460 (16) 35 300 300974 (16 380 248 250 250YO 539 248460

NOTES 1 XL Across the Line YO Star Delta 2 RLA Rated Load Amps (rated in accordance with ARI Standard 590) LRA Locked Rotor Amps 3 Wire Size Amps equal 125 of the rated load amps for the largest motor in the circuit plus 100 of the rated load amps for all other motors in the circuit per

NEC 4 Wire size based on copper conductors with 75degG insulation per NEG Table 310-16 Terminal block lugs are sized accordingly Use of oversize wiring may

not fit in terminal blocks 5 Maximum fuse size is based on 175 to 225 of the rated load amps for the largest motor in the circuit plus 100 of the rated load amps for a other motors

in the circuit per NEG VOLTAGE TOLERANCES 208V-230V min 187V Max 253V

480V Min414V Max506V

19

0

(Wd~) 3lV~ M011 ~31VM

006 009 00 OOt OOl OS L 00 L os 0 Ot

V D m (I) (I)

c D m c D o V

- m m -t o

~

~ m D-

aoao 3~nSS3~d ~3100~

APPLICATION DATA

POINT LOADING

ArMi I 1 5 1

ACWC 45 THRU 10 SC

COMPRESSOR CONDENSER SECTION SECTION

_ 2 4 bull 1

bull CA

J

Model Dimensions Size A B C D 45 91 - - -55 91 - - -70 145 - - -90 145 - - -110 60 40 160 -125 60 40 160 -135 60 40 160 -145 138 74 107 -160 13830 74 107 -185 138 129 107 -200 138 129 107 -215 106 82 106 80 240 106 82 134 107 265 133 110 134 107

1310

1310

~

1

1310

2

ACwe 110 THRU 200 Ie

COMPREIlOfl CONDENSER SECTION IECnoN

4 -

5Imiddot

ACWC 2t5 THRU 215 SC

Model Loadlnu (LBS) Size 1amp2 3amp4 5amp6 7amp8 9 amp10 45 585 765 550 - -55 705 810 635 - -70 660 890 700 - -90 1025 1500 1175 - -110 1195 635 1525 995 -125 1255 690 1835 1115 -135 1255 665 1880 1105 -145 1330 2380 2160 1450 -160 1330 2440 2280 1515 -185 1235 2575 2980 1360 -200 1275 2635 3020 1380 -215 1010 2270 2590 2240 840 240 1115 2550 2870 2715 1125 265 1380 2980 3515 2750 1175

11

II i middot 2 4 lIf 11 to L

21

TROUBLESHOOTING GUIDE

CHILLER UNIT WILL NOT START POSSIBLE CAUSE REMEDY 1 Power off 1 Check main disconnect switch

2 Main line open 2 Check main fuses

3 Incorrect wiring 3 Check the wiring diagram

4 Loose terminals 4 Tiqhten all terminals

5 Control circuit open 5 Check phase loss monitor flow switch circuit breakers temperature control low ambient thermostat low temperature thermostat remote switch etc

6 Time delay 6 Wait

COMPRESSOR HUMS BUT DOES NOT START

POSSIBLE CAUSE REMEDY

1 Low voltage 1a Check at service and unit for loss

b Consult power company

COMPRESSOR CUTS OUT ON LOW PRESSURE SAFETY CONTROL POSSIBLE CAUSE REMEDY 1 Refrigerant shortage 1 Check for leaks -- add refrigerant 2 Restriction in liquid line 2a Plugged strainer - dean or replace

b Liquid line valve partially closed - open valves fully c Expansion valve clogged or inoperative - clean or replace as

required d Solenoid valve partially open - clean or replace as required

3 Low water flow thru cooler 3 Check water flow thru cooler and correct as required

COMPRESSOR CYCLES ON HIGH PRESSURE CONTROL POSSIBLE CAUSE REMEDY 1 Compressor discharge valve partially closed 1 Open valve fully 2 Non-condensible gases in system 2 Operate condenser fans with compressors off If condenser

pressure exceeds saturated pressure corresponding to condenser entering air temperature then purge air from discharge line

3 Overcharge of R-22 3 Purge system while in operation until head pressure reaches a normal level

4 Dirty condenser 4 Clean the condenser 5 Compressor discharge check valve not operating properly 5 Replace if necessary 6 Fans not running 6 Check pressure control setting

CAUSES AND PREVENTION OF FREEZE-UP CAUSES PREVENTION 1 Improper charging 1 Charge per manufacturers recommendation

2 Improperly set safety time delay 2 Check the safety time delay low pressure control for proper setting at the beginning of each season

3 Improper chilled water circulation 3 Use an ample sized cleanable strainer in the chilled water circuit Make certain the strainer is clean to insure full flow and velocity of

chilled water It may sometimes be necessary to treat the water to prevent formation of deposits

4 Not draining for winter shutdown 4 When the system is shut down for the winter remove the drain

plugs and drain the cooler Blowout any remaining water with air

5 Improper pump shutdown 5 Make sure chiller barrel heater is working and flow switch is installed per wiring diagrams

6 Low ambient during air conditioning season 6 Make sure chiller barrel heater is working

NOTE If the ambient temperature is below 32degF freezing can be completely prevented by one of two methods

1 Drain all water from the equipment 2 Add antifreeze to the water

22

START-UP CHECK LIST

Unit Model No

Setting unit

Wiring

Piping

Alignment

Before Start-Up

After Start-Up

Yes No a Vibration isolator used

b Spring isolator adjusted for equal height c If rubber-in-shear isolators are used is unit leveled by shimming

a Power wiring complete

b Control wiring complete c Electric service adequate for load

d Power source voltage correct for motor(s) used

e Motor circuit has proper size fusetrons f System wired per diagram

g All lead connections tight h Wiring complies with local codes i Flow switch operation

a Piping complies with applicable codes b External piping independently supported c Chilled water lines insulated

a All belts adjusted and checked for tension b All pulleys checked and adjusted for proper pitch tightness and

alignment

a Open compressor discharge service valve b Open liquid valve(s) c Open suction and discharge valves to pressure gauges (if supplied) d Check rotation of all fan motors e Start auxiliary equipment (pumps fans etc) f Is crankcase heater operating Operate 24 hours prior to unit startup g Check the compressor oil level through the crankcase sight glass The oil

level should be to the top of the glass If the level is low add oil in accordance with the directions in the maintenance instruction

h Check all control settings as specified in Table 1 I Air purged from chilled water system

a Check high pressure control b Check oil temperature safety switch c Check and adjust low pressure or temperature freeze control d Check and adjust operating thermostat e Check and adjust low pressure operating control f Check and adjust expansion valve superheat g Check and adjust capacity control thermostat

23

OPERATING DATA CHILLER Voltage L-1 L-2 L-3 _ Pressure Gauge Readings 1 Suction psig 1 Discharge psig 2 Suction psig 2 Discharge _ psig 3 Suction psig 3 Discharge psig 4 Suction psig 4 Discharge _ psig High pressure switch setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-in) psig psig (Out) 4 (Cut-In) psig psig (Out) Checked Setting - Yes - No (each circuit) Low Pressure Switch Setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-In) psig psig (Out) 4 (Cut-in) psig psig (Out) Checked Setting -Yes -No (each circuit) 1 Oil Temperature Safety Switch Cut Out 2 Oil Temperature Safety Switch Cut Out 3 Oil Temperature Safety Switch Cut Out 4 Oil Temperature Safety Switch Cut Out If Star-Delta start time delay is seconds Temperature of air entering condenser F Temperature of air leaving condenser of Temperature of chilled water entering chiller OF Temperature of water (chilled) leaving chiller F Chilled water pressure entering chiller psig Chilled water pressure leaving chiller psig

MAINTENANCE Good maintenance practice will prolong the chiller life and will reduce the Ask of system breakdown and expensive service calls

A weekly check of the ACWC-SD unit requires only a few minutes and will prove beneficial in insuring long trouble free operation

WEEKLY CHECKS- with unit in operation for at least four hours 1) Check compressor oil level - At least above 12 of sight glass 2) Record suction and discharge pressures

Typical Condition R22 Ambient 95degF Return water 55degF Leaving water 45degF Suction 62 psig Discharge 270 psig

3) Record ambient temperature 4) Check liquid sight glass

Make sure liquid is clear - no bubbles 5) Check that all fans are running 6) Check entering face of condenser coil for cleanliness 7) Record voltage at unit

All of the above can be performed by building maintenance personnel If oil levels are low or any of the above checked items are questionable consult a qualified serviceman

At least once a year a qualified serviceman should check unit oil levels superheat and control operation

DUNHAM-BUSH USA

P l) bull 130 xUtUC t01 Bmgess RO~ Harrisonburg VA 22801 Phone (540) 434-0711 FAX (540) 434-~ 2118

wvvwdunham-bushcom Form No 6184

Page 2: ACWC-SD - · PDF fileACWC-SD • Screw . Type • • • Air-Cooled Packaged Chillers •• Installation, Operation, and •• • Maintenance Manual • • • •• DESCRIPTION

INSPECTION amp HANDLING CHILLER PIPING

When unit is received it is the responsibility of the contractor to inspect the unit for shipping damage at time of off loading and make note of damage on carriers freight bill

ACWC units are factory mounted on (2) carbon steel angle beams Sizes 45 thru 90 have three lifting holes per side Sizes 110 thru 215 have four lifting holes per side and sizes 240 thru 265 have five lifting holes per side to facilitate lifting

Spreader bars must be used between rigging lines to prevent damage to the unit Rollers may be used under the skids to facilitate moving the unit a short distance

Models ACWC-40DF thru 22DC are factory mounted on two permanent angle beam carbon steel skids A minimum of four 2 78 lifting eyes are provided in the skids to allow rigging Physical damage to the unit after acceptance is not the responsibility of the factory

LOCATION amp MOUNTING

Model ACWC Air Cooled Packaged Water Chillers are designed for outdoor application and may be mounted on roof or at ground level Air lIow through the condenser is vertical and the unit may be located adjacent to outside of building or on roof without regard for prevailing wind direction

Since these units are air cooled the flow of air to and from the condenser coil must not be impeded There must be no obstruction above the unit that would tend to dellect discharge air downward where it could be recirculated back to the inlet of the unit The required overhead air space should be a minimum of eight feet Ductwork must not be applied to the fan outlets

The unit must be installed with sufficient clearance for air entrance to the condenser coil and for servicing access The unit should be located no closer than four feet from any wall or other obstruction Clearance must be provided at either end of the unit to permit removal of tubes from the chiller

Unit must be set on a solid and level foundation

On roof installations the unit should be mounted on support beams which span load-bearing walls to prevent excessive vibration

On ground level installations the unit should be mounted on a substantial base that will not settle A one-piece concrete slab with footings extended below the frost line is recommended A space should be left between the slab and the building to prevent the transmission of sound and vibration

Vibration mounts may be used for roof-mounted units or other locations where noise might be objectionable

WIRING

A unit wiring diagram showing the required power supply characteristics and all factory supplied wiring details are provided with unit Separate field supplied disconnects must be installed for the power and control circuits and should be within the sight of the unit

Separate 115-volt power source must be field supplied to provide power for control and heater circuits if optional control circuit transformer is not provided All electrical connections should be periodically tightened

The chiller inlet (return) water pipe should be connected to the water connection closest to the control panel end of the unit and the outlet (supply) water pipe connected to the water connection on the opposite end of the cooler(s)

A flow switch must be installed in a straight horizontal section of the chilled water piping This is to be field installed

Gauges should be installed in the piping to and from the chiller to measure the pressure drop and to insure the proper (GPM) flow rate in accordance with submittal data A strainer should be installed in the piping on the inlet side of the chiller and vibration eliminators should be employed on both the inlet and outlet pipes Air vents should be located at all high points in the piping system Vents should be located to be accessible to servicing Drain connections should be provided at all low points to permit complete drainage of chiller and piping system

The chilled water piping should be insulated to reduce heat pickup and to prevent condensation If the system is for year-round operation or if it will not be drained in the winter the chilled water piping should be protected against freezing by electric heating cable or other suitable means

Upon completion of chiller piping start the system water pump and purge air from the system Air purging should be done from the high points in the water circuit Purging of the chiller barrel may be accomplished through the vent pipe located on the top of the chiller compartment Failure to purge air from the water circuit will result in inadequate water flow and may cause the unit to cutout

STARTmiddotUP Refer to start test and check list included with this manual

2

CAUTION

The discharge line valve must be open before starting the compressor Liquid line valves must also be open for sustained operation

All compressors are solid mounted on isopads therefore compressor hold-down bolts must not be loosened Loosening these bolts will cause excessive vibration of the compressor and may result in refrigerant line breakage Prior to start-up check all compressor hold-down bolts for tightness

MAINTENANCE

CONDENSER Units are equipped with direct drive fans that have inherently protected motors with permanently lubricated bearings

The air inlet of the condenser coil should be kept clean through a regular maintenance program

COMPRESSOR

1 OIL LEVEL - The oil level in the compressor(s) should be checked periodically with the compressor either running or stopped If the oil level is below one-half (12) the sight glass oil must be added

2 RECOMMENDED OIL -- The unit 4 factory-charged with DB SR-30 refrigeration 01

Do not add any other type of oil to this factory charge

Do not operate compressor If 011 level Is below one-half (12) sight glass

If the oil level is below the minimum specified above and DB SR-30 is not on hand you may drain the entire factory oil charge then refill with SUNISO 4GS refrigeration oil The factory (DB) oil is of the synthetic type and will not mix with SUNISO 4GS Do not attempt to operate the screw compressor with any oil other than these two specified above

It is suggested that a gallon or mom of DB SR-30 oil be obtained and kept on hand at the job site The substitution of SUNISO 4GS oil as outlined above will result in a 2 to 491 capacity loss and no reduction in input KW

PROCEDURE FOR ADDING OIL

Install temporary jumper wire around LPcontrol contacts of circuit to be serviced Manually close liquid line service valve Lower return water T-STAT (T1) setting to start compressor Run compressor until minimum positive pressure reading on suction service gauge (Do not run compressor in vacuum) Place the system onoff switch in the off position Close the line valve in the discharge line between compressor amp condenser Equalized pressure should now be a minimum of refrigerant vapor Reopen discharge line valve Remove jumper wire from pressure control Open liquid line service valve

3 COMPRESSOR REPAIRS (internal) - Contact factory or an authorized DB Service Agency if a compressor malfunction is suspected

4 COMPRESSOR REPAIRS (External) - Proper operation of unloaded ban loading and unloading is controlled by solenoid valves UL-1 UL-2 and UL-3 Any of these three (3) solenoid valves may be repaired or replaced in the field as required

5 Standard oil acid test kit is not compatible with synthetic oil See DB color chart for oil condition

HIGHPRESSURE PORT

SIGHT GLASS I

CRANKCASE HEATER

3

SLIDE VALVE UNLOADING SYSTEM

The Rotary screw compressor capacity control system for infinite modulation consists of a slide valve and hydraulic pistoncylinder operator intemal to the compressor plus three hydraulic solenoid valves (UL-1 UL-2 amp UL-3)

The slide valve forms a portion of the chamber wall in which the rotors turn thus its position with respect to the rotors determines the effective rotor length and thereby the percent of full load capacity

Upon compressor start-up UL-3 is opened This allows oil pressure to act upon the hydraulic piston holding it in the fully unloaded position After 30 seconds during which time full oil flow is established to all bearings surfaces UL-3 is closed At this point the temperature controller is free to open and close UL-1 or UL-2 in response to the supply water temperature

The slide valve will move to the left (loading) by force of discharge pressure whenever UL-1 opens to permit flow to the oil return (low

Load

centJ

Screw Rotor

Slide Valve

Unload

~ Oil Pressure

Oil Pressure Lines

Hydraulic Piston

pressure) line The slide valve will move to the right (unloading) whenever UL-2 opens the oil supply (high pressure) line since the force of the oil exceeds that of the discharge gas

The temperature controller sends a series of power (energizing) pulses to the appropriate solenoid to adjust to load conditions The further the supply water temperature is from the controller set point the longer is the duration of the pulses The series of pulses will continue until the controller is satisfied As the water temperature approaches the set point the pulses become quite brief to prevent overshooting the set point

This method of compressor unloading in conjunction with supply water sensing minimizes actionreaction lag time and overshoot resulting in an exceptionally precise and stable control of supply water temperature

Oil Oil Return Supply

The following table lists solenoid valve position for all three operating modes

UL-1 UL-2 UL-3 Starting Close Close Open Loadinq Open Close Close Unloading Close Open Close

4

LOW AMBIENT OPERATION

Due to the wide range of applications it is sometimes necessary to operate the Air Cooled Packaged Water Chillers at ambients below summer conditions Without proper control when ambients drop below 60degF the pressure differential between the condenser and the evaporator is below the level to insure proper thermal expansion valve operation As a result the unit may cycle off Two types of system control are available allowing the units to operate at the ambients indicated

FAN CYCLING MEDIUM AMBIENT CONTROL TO 30degF

(STANDARD EQUIPMENT-FACTORY INSTALLED)

A fan cycling control is standard on all Air Cooled Packaged Water Chillers to provide proper operating head pressures in ambient conditions to 30degF

This is an automatic operation in which the condenser fans are cycled on and off as required in response to head pressure This arrangement provides positive start-up control down to +30degF by delaying the condenser fan operation until a predetermined head pressure is obtained

LOW AMBIENT CONTROL TO OdegF

In conjunction with the standard fan cycling feature all compressors are enclosed in individual housings This housing assures adequate compressor oil temperature for lubrication A five minute time delay relay provides a bypass around the low pressure control to prevent nuisance trip-out during cold start up

COOLER FREEZE PROTECTION-LOW AMBIENT

Cooler freeze protection is a major concern with air cooled chillers To protect against freeze-up a heater cable is provided as standard which protects the cooler to -12degF However there is no freeze protection in the event of power failure or heater cable burnout so the following should be considered for additional protection

1 Drain the cooler and chilled water piping if the chiller is not to be operated over the winter months Drain connections are provided on the coolers

2 Add ethylene glycol to the chilled water system Freeze point should be approximately 10degFbelow minimum design ambient temperature See Page 11 for Glycol Performance

The cooler heater is wired to the control panel and is operational from the factory offered control transformer or field supplied control power

COOLER FREEZE PROTECTION-oPERATION

The ACWC-SD chiller is provided with a temperature sensing freezstat (38deg set point) and a field installed flow switch shutting off the compressors on loss of water flow is also required

Optional low pressure or hot gas bypass freeze protection is also available on the ACWC-SD If these options have not been purchased it is extremely important to guarantee proper chiller water gpm as well as double checking the temperature sensing freezstat calibration

ACWC-SD CONTROL SETTINGS

CUT-INCUT-OUT (PSIG)

UNIT FLP1 FLP2 FLP3 FLP4 FLP5 FLP6 FLP7 FLP8 FLP9 FLP10 FLP11 FLP12 FLP13 FLP14 ISM 44-55 280170 295180

70 260160 275175 2901215

90 260160 275175 2901215 260160 275175 2901215

110-135 260160 2751175 2851210 2951235 2601160 275175 285210 2951235

145-160 280170 2951180 260160 275175 2901215 260160 275175 2901215

185-200 280170 295180 260160 275175 2951235 2951235 260160 275175 285210 2951235 215 260160 275175 2901215 260160 2901215 2901215 260160 275175 290215 260160 275175 290215

240 260160 260160 275175 275175 2901215 2901215 260160 260160 275175 275175 2851210 2851210 295235 2951235

265 260160 260160 275175 275175 2851210 2851210 295235 2951235 260160 260160 275175 275175 285210 2851210 2951235

TEMPERATURE ACTUATED LEGEND FACTORY SETTING

Chiller Low Water Temperature Thermostat T2 Cut-Out 3rF Chiller Heater Thermostat

I(Non-Adiustable) Included With CBH1 Heater

Cut-In Cut-Out

40degF 45degF

Oil Temperature Safety Control (Adjustable) Manual Reset

OTS 1 OTS 2 OTS3

Cut-Out 240degF

Capacity Control Thermostat (Adj) Mode Control Position T1 Dial Set At 44degF

UNIT OPERATING LIMITATIONS

1 Maximum ambient air to condenser is 110degF (60 Hertz operation) 2 Maximum allowable cooler water pressure is 150 PSIG 3 Maximum allowable water temperature to cooler is 75degF 4 Units must not have leaving water temperatures of 42degF or lower unless used with a glycol solution

5

KEY TO WIRING DIAGRAM INDEXING SYSTEM

The wiring diagrams and sequence instructions on the following pages have been devised to simplify the understanding and tracing of circuit theory The following key shows how the indexing system can be used

12 Line number on wiring diagram

[12] Line number in text

(R5) Component identification symbol in text (Relay 5)

[E] Normally open contact - line number location

[E] Normally closed contact - line number location

Holding coil - line number location

amp Note number

SEQUENCE OF OPERATION (TYPICAL) MODELS ACWC 90-135 SO

The following sequence of operation is typical for all ACWC SD Models Refer to the wiring diagram furnished with the unit for specific information ( ) Control Identification Symbol [ ] Circuit Line Number

Important Notel With all the control circuit switches (SW1-SW3) in the off position and the staging thermostat (T1) to its highest temperature Terminals 2 and 4 on the Terminal Board (TER5) must have 115 volts supshyplied for a minimum of 24 hours to energize the compressor crankshycase heaters (CCH1 2) [6 8]

Preliminary Sequence Close the main power disconnect switch Check to see that the red indicating light on the phase loss monitor (PLM 1) is lit (Note There will be two phase loss monitors (PLM1) and (PLM2) on dual power block models) This light must be on to indicate proper phase rotation for the compressors If the light is not on disconnect the main power and reverse any two phase legs at the Main Incoming Power Terminal Block (WARNING DO NOT REVERSE THE LEADS ON THE PHASE LOSS MONITOR FOR THIS WILL ALLOW THE COMPRESSORS TO RUN BACKWARDS CAUSING SEVERE DAMAGE AND WILL VOID THE COMPRESSOR WARRANTY)

The crankcase heater relay contacts (R3) [6] and (R4) [8] are closed and are supplying power to the compressor crankcase heaters Power is also supplied to the chiller barrel heater (CBH1) [13) the optional receiver heaters (RH1 2 [1011] and the optional convenience outlet (CO) [14]

Control power goes through the control panel circuit breaker (CB1) [8] and field supplied remote time clock [36] Check to make sure time clock contacts close during occupied modes

Start up the chilled water pump The water flow is confirmed when the water flow switch completes the electrical circuit across Terminals 15 and 16 [38] on Terminal Board (TER5) Terminals 17 [47] and 18 [49] provide an interlock for the water pump starter(s) when either compressor is in operation Set the thermostat (T1) to the desired leaving water temperature (eg 44degF) Set point adjustment is acshycomplished directly on the control

Place the three (3) control circuit switches (SW1-SW3) in the On position thus energizing the balance of the control circuit [23] [33] [36] The system will be in the Time-In mode for five minutes before the first compressor will start

The low ambient lockout thermostat (LAT1) [38] and temperature freezestat (T2) [38] must also be satisfied to allow compressor operashytion

Stage 1 Starting Upon demand for cooling thefirst stepof the staging thermostat (T1) will be to close energizing relays (R1) [61] time delay (TD1) [60] and the optional time delay (TD3) [62] If all the safety controls and switches are closed (see Safety Controls section for more detail) the control

circuit for Compressor No1 will energize allowing the compressor to start Relay (R5) [20] will energize closing the normally open (NO) set of contacts [23] which energize the liquid line solenoid valve (SOL1) [23] Another set of NO contacts on (R5) [20) provide a series intershylock with all the safety and operating controls which will lock out the compressor if any safety trips during normal operation (See Note 6 on Wire Diagram) The last set of NO contacts on (R5) [48) provides an interlock circuit for the water circuiting pump(s)

The fan contactor (C13) [23] will also close supplying power to the side of the fan cycling pressure controls (See Power Wiring Diagram)

Note The fan motors are controlled by their own fan cycling controls and will cut in at different factory set head pressures

Time Delay (TD1) [601) has two (2) sets of contacts the first set of (TD1) [19] normally closed (NC) contacts provide a 30 second jumper around the low pressure control (LP1) [20] to prevent short cycling during start-up The second set of (TD1) [24) contacts in the NC posishytion power the unloader solenoid (UL3-1) [24] which hold the comshypressor in the full unload position for 30 seconds After (TD1) [60] times out (30 seconds) the contacts for the unloader solenoid (UL3-1) open and the NO set close which energize the relay (R3) [25]

Stage 1 Modulation Upon energizing relay (R3) [25) the crankcase heater (CCH 1) [6] is de-energized and the NO contacts of relay (R3) [45 48] are closed allowing the thermostat (T1) to energize the load solenoid (UL1-1) [45) and the unload solenoid (UL2-1) [481] upon demand The opshytional time delay (TD3) [62] is used to bypass low pressure control (LP1) [20] for five minutes for low ambient starts

Stage 2 Starting Subsequent to the start of Compressor No1 an approximate five minute time delay is incorporated into the microprocessor After this time delay and a further call for cooling the second step of the stagshying thermostat (T1) will close This will energize relay (R2) [58] time delay (TD2) [57] and the optional time delay (TD4) [59] If all the safety controls and switches are closed (see Safety Control section for more details) the control circuit for Compressor No2 will energize allowing the compressor to start Relay (R6) [3D] will energize allowshying the liquid line solenoid valve (SOL2) [331] to energize Relay (R6) [3D]will also interlock the water pump starters and the safety controls the same as Compressor No 1 circuit

The fan contactor (C14) [33] will close supplying power to the line side of the fan cycling pressure controls (See Power Wiring Diagram)

Time delay (TD2) will provide a 30 second jumper around the low pressure control (LP2) [30] and will energize the full unload solenoid (UL 3-2) [34] for 30 seconds then energize relay (R4) [35]

Upon energizing relay (R4) [35] the crankcase heater (CCH2) [8] is de-energized and the NO contacts of relay (R4) [46 49) are closed allowing the thermostat (T1) to energize the load solenoid (UL2-1) [46] and the unload solenoid (UL2-2) [49] upon demand

6

SHUTDOWN SEQUENCE

Stage 2 Shutdown Stage 1 Shutdown

After both compressors have unloaded fully and the leaving water temperature is still lower than the setpoint the second step of the thermostat (T1) will open and de-energize relay (R2) [58] providing an approximate five minute time delay again integral with the microshyprocessor has expired subsequent to the start of Compressor No2 This will close the liquid line solenoid (SOL2) [33] and turn off Comshypressor No2 Compressor No 1 will load and unload as required Compressor No2 will not be able to restart for five minutes due to integral time delays

SAFETY CONTROLS

The unit is protected by the following safety controls

1 High Pressure (HP) 2 Low Pressure (LP) (automatic reset) 3 High Discharge Temperature (OTS) 4 Compressor Solid State Module (CSTM) 5 Low Water Temperature (T2) 6 Low Ambient Thermostat (LAT) 7 Compressor Starter Overloads (OLH) (optional) 8 Phase Loss Monitor (PLM) 9 Control Circuit Breaker (CB1)

If any of these devices should open due to abnormal conditions the compressor(s) will automatically stop All controls must be manually reset except low ambient thermostat (LAT) and phase loss monitor (PLM) The individual compressor safeties (HP LP OTS and CSTM) contacts are found on Lines 20 (CTT1) or Line 30 (CTT1) The other safeties listed above are discussed in the preliminary sequence section

If the leaving water temperature is still lower than the setpoint the first step of the thermostat (T1) will open and de-energize relay(RI) [61]This will close the liquid line solenoid (SOL 1) [23] and turn off Compressor NO1 as long as it has run for approximately three minutes Compresshysor NO1 will not be able to restart for five minutes

FIELD CONTROL WIRING

In addition to 3 phase power (and optional 115 volt control) wiring described above the following control interlock wiring is recommended The as built control schematic provided with the unit provides detailed information Typical control schematics are as shown on pages 8-15

1) Alarm Circuit -Terminals 6-13 (2 per compressor circuit) can be used to trigger remote failure lights or alarm bells in the event of a refrigeration failure

2) Time Clock - All unit on-off control should be done through terminals 15 and 16 An open contact shuts down the unit Time clock night shut down and energy management shut down should all be done from these terminals and contacts should be applied in series

3) Flow Switch - The flow switch contacts should be installed between terminals 15 and 16 and be in series with time clock contacts

4) Chilled Water Pump - The control of the chilled water pump must be worked out by the system designer It is necessary for the pump to be on during any compressor operation and terminals 17 and 18 should be used to energize the pump starter However it is likely that the pump should remain on throughout all occupied operation or even at night for freeze protection Terminals 17 and 18 should not be the sole means of controlling pump operation

STARmiddotDELTA STARTING OPEN TRANSITION (OPTIONAL)

Typical For All Compressors On initial call for cooling staging relay (R1) holding coil will energize The (R1) contacts 7-4 close energizing star contactor (S1) and the five second transition timer (TD5) Transition contactor (S1) power contacts close tying the center legs of the compressor motor windings together into Star (WYE) configuration At the same time (S1) NC (Normally Closed) auxiliary contacts open preventing (C2) from closing (S1) NO (Normally Open) auxiliary contacts then close energizing contactor (C1) The (C1) power contacts close applying power to the

compressor winding (C1) NO (Normally Open) auxiliary contacts close locking (C1) in the energized position The compressor operates in the Star mode until (TD5) transition timer times out (five seconds) at which time contacts NC open and de-energize (S1) Star contactor (S1) NC auxiliary contacts close (TD5) timer NO contacts close energizing compressor contactor (C2) power contacts close thereby completing the Delta wiring configuration Compressor contactor (C2) NC auxiliary contacts open preventing (S1) star contactor from energizing until the next starting sequence

7

--

exgt

LE

GE

ND

m

rrbullbull

saN

OI

IlIG

CI-

Z

CO

HT

AC

TQ

ftmiddot (

0

[5

10

1t5

el

) C

ON

TA

ClO

middot A

NS

(C

UlT

middot pound

AM

III

bull C

ON

TO

L

(C

UlT

C

UtC

UIT

Ulaquo

III

H

IAT

EIt

I C

HllL

rU

lU

[AT

III

CU

Ne(

ASE

H

un

co

U

OIl

ll

SOL

ID

TA

U

MO

OU

Lt

H

US

UII

lI[

con

RO

L

LOW

Abullbull

IN

T

[

twO

fI

lO

W

nul

tt C

ON

TIIlI

OL

OIL

TU

II

r

UIIl

I(

SA

HA

S[

0

1$

M

ON

t T

O

lllE

LA

Tmiddot

tTA

GIH

O

1t[

LU

-U

CIT

Y ~OL

bull

CI

l

tC5

I H

el

C

Ubullbull

e

lHI

CC

HI

esr

P

I L

UI

VI

enst

P

LU

11

0)

(L

AY

middot tN

Uft

LO

CK

(

L[N

OIO

middot L

lOU

IO L

INI

SWIT

CN

CO

W

UD

C

C

UIT

S

SWIT

CH

ST

EN

fH(

MO

ST

AT

middot S

[OU

[Ne

EIt

TH

UM

OS

Tn

-L

OW

n

llI

IUU

[

TtIt

WIN

AL

10amp

1110

cu

no

wE

It

UN

I J

SO

LI

w

10

Tl T[l

Il

S

Tl

Ufl

Ul

10

0

-

CT

OII

I

WIl

WO

T

lM[

HU

T c

alli

CO

NTbull

bull L

OW

Ipound

n

LO

CC 0

1

TO

T

IllS

I

ond

tlt

UN

Lo

ao

t

OL

(NO

ID bull

(O

M

no

ll

Ul

ImiddotZ

~(

tU

IIL

T

IIS

VI

O

I

_

-~

OIO

HA

l

ell

C

UtC

Ul

[

amp1

(( -

(cri

VE

lli K

uru

en

C

IAC

Uff

A

UK

(jII

f bull

CO

[

I(

C(

OV

TL

lT

CI

I (O

NU

OL

If

Jll

AIr

IS

HO

UA

W

(fIA

S

LL

Tl

LO

AO

LI

T

(III

WO

STA

T

0

middot

5

O

(III

LO

AO

fU

UIS

LImiddot

H

OT

L

IGH

TS

H

IUC

IIY

[1II

H

[AU

IIIS

~ jllf

M1

III[

Cll

[

H

[U

t

US

UII

ll[

CO

NT

IIO

LS

~tCt

JVII

l N

(AU

III

14

(0

1

T

O)

TO

wI

DtL

AY

amp L

OW

U

tu

LO

CK

ou

r rt

(

O(L

IN

SlT

IO

C

OH

TA

(TO

Il

(O~USO

C

OH

O

lll

bull iT

A

OlL

C

Ol

CO

MV

[Nf

epound

o

un

n

Ctft

CU

lT I

DE

TA

IL

A

SlA

M

DE

LTA

ST

AR

T

O -~

OA

~ 5~U

Z

OI

Cl

U

I 14

(I

amp

~

NC

f

cl

AU

I

51

ZtA

LU

TOO C

21

NO

~~

bullbull

N

WHT

I---

I

l I J

II

A

CN

lCU

lT

If

OOHAI~

l

~i1

WH

It[

-

OI

ON

AL

r---

----

---

-I

Q

WT

I lt

raquo

I I L

JI

bull bull

I I

0

II

-

lJ

_ Ij

lf

I

cal

II

iOO

w

shy

) C

it

~

WTI~AL

r --------------------------------

Iamp

I

_l

[0

0

I

OO

CM

lL

00

LO

II

cu

U

II

bullL

~J

It

_U

I

TH

u

I

HT

I~

r-~~

~ --

-I=

=~==

=~I

11

2

N

~~~

~--

----

----

=~

I

-lt

l

= I

en

co

o J

rO~

2

~L

----------

-

-oS

f

I

r--shy

J

on

T

O)

vI

Q~~A

J T

Ot

L-

ll~_

f

1

II

CU

H ~

~OI

L1

-i

r---

----

-

~

10

rc

I

bullbull

lf

OIS

ti

l W

I H

Z

01

11

1

-J

o

u

L

shy

0bull

-

0 T

1

111

A -

bull 0

[0

HT

I

ll II

rgt ---

-ij

---

ITl~ll

t

1amp

I

1t

D

MIN

I[D

11

~

ill HTAILmiddot~

O

LM

I 01

1

OL

HJ

III0

1l~

tM

Ow

N

CI

amp

tt

I w

lO

OIO

HL

---

__

J

O ~

~Ll

~

tB1

It

CI)

n

IS

-1

M

k

V

Io

Jmiddot

r---

1

we

14

-4

I

Mill

I

CO

MPR

ESS

OR

C

IRC

UIT

I

Til

bull ~

r-

so li

e II

It

S

tON

L

N

O

fll

II

If

II

~

s~

o

oc

gt

(I)

r in

n

100

00U

lz

--I

~o

e

0

r ce

cn

shy0

0

Z

Ggt

bullbull bullbull bullbull bullbull bullbull bullbull

r~T~-

ICt

MQ

Teuro

CO

MT

It01

I T

IM C

lot

ll

~---

Cl

ll

(O

41

(

flO

W

5Wlf

CH

~

I

Olt

CO

NT

AC

TO

C

OIL

S C

I-I

bull C

tS

AN

D S

t sn

N

OW

IIt

Dll

QU

0

1 C

OM

UC

TI

I

111

114

0

(

U

II

NO

f T

O I

(

C

uNO

IO

ON

UtI

se

CO

HO

UI

li

D(

1

A

ND

1

n

WP

(IU

ult

l S

(NIC

tf1

I

LO

CU

ID

1M bullbullU

O

UT

UT

r-

----

shybullbull

0

11

UO

V

HA

Il

LO

IS

raquoON

TO

S

TE

lurN

AU

bull

AN

D

0111

IIC

O(

I A

ND

A

U(

Cfl

YpoundL

Y

So

C

rt

TO

0

0 M

AN

UA

L a

ll H

TO

tNT

AN

D

~10l

IA

NO

M

TII

UC

TtO

NS

II

rCO

tNO

m

IMIT

AL

CO

H

laquo

0

U

TI

I It

4

Ishy

C

OW

III

ISO

R

MO

DU

LES

dC

NO

MmiddotA

U

VA

TC

I

D

U

1111

WIL

L A

LSO

LO

C_ O

UT

(

let

Umiddot

I C

AL

L

WH

IM

IAI

TY

flit

TH

[I(

CO

Nmiddot

I

OL

I CA

Jrf I

I II

EM

T

IT T

Uft

I1

tW

ITC

H bullbull

0

VO

NIN

IL

f PO

C

Obullbull

bull

I w

UII

II

I

C

IL

Llf

i I

ITA

f[1

II

ItV

N

IWIT

ti r

raquo7

~Slt~1

~~~~( 1~~~~tlDOO

CO

N

CT

O

WU

UH

O 0f

II C

OW

bullbullbullbull

~~1

II

bull

LL

TI

lIT

AT

0

N

O 1

0 O

CA

TID

1

1 I

I IIl

ETU

IIPt

W4T

P

LU

WHE

N u

TI

It N

OT

lU

u

rD

ttl

III I

ICO

Ma-

aU

0 11

nM

H

u

l

UN

I()1

II M

UST

HA

V(

SH

llL

DID

C

AU

I

LO

Me

T

II

no O

R

ItUM

WT

M

ItO

WI

L

IAH

to u

ri N

T I

T H

-

ITbullbull

O

N

ft

0

-

011

II~T

K

ITI

GU

ION

An

ON

S

o H

O-

ON

G C

OI

-W

it

11

N(

NO

6 N

c

CO

NU

ClI

W

If

lIN

( N

O

o N

0

CO

NT

AC

TS

WIt

K

liN

t N

O

6 N

OT

t I

TH

L

Nt

NO

Y S

UI

-I

IS

5_

1

~

~

no

~ I

I I_

VLOA

Or- I

I ~~

vumiddot

S1 so

CO

Hit

so

0

amp

g A

SI ~

I

1

7100-

I -I

I 01

10

OH

0

10

f T

AN

I V

I

] CM

NG

( av

rlt

10

0 O

K__

ST

AG

(

COD

lJ-

L7

00

~It

A

lIT

00]

VL

I fi

ll

14

1

10A

O

f

_ III

rC

OH

O

In o

y

00bull

00

10 ~

0

10

CO

Ol

C

bull

] 4

U

rr

COL~

bull Jo

un

J

W bull

C~P

OJ [

ou

-t

urO

NT

01

CO

l0

1

N

Omiddot

~ ]

(jCO~_

0

)

un

ll

n ~

T

I 11

I1

III _~

n

~

amp

7

10

II

01

u II 17

II

0

II

01

IS

-I

-lt

sE

o

0 c

raquo

CD

r iii

0

~O

U

lZ

+-1

~

tI

t

0

r QE

CIJ

-c

tl

Z

Ggt

lt0

bullbull bullbull

bullbull

bullbullbullbull

~

o

tUN

oa

lllO

_--

-

shyC

t-4

CII

C

cn

bull

tlN

I

CC

HImiddot

t

csnu

middota

--1

LA

T

loP

a

01

11

-1

111

111

IIImiddota

It

4

IOL

IS

IW

Imiddot

I

I T

I n flbull

bull

TO

middot I

st

U

LImiddot

a

Oft

lo

tL

LtG

EN

D

CO

NlA

CT

IM ~

CO

lllf

lllt

UtO

JII

CO

NT

AC

TO

CII

CU

fT

IIIC

AICC

III

CO

NTJ

IIOL

CIC

UIT

U

NImiddot

HU

TI

eNU

LlII

I

Il

I

AU

It

C

NlaquoC

AU

NC

An

C

O

UIO

10

LIO

T

AU

N

t U

SU

I C

O T

OO

L LO

W

eT

fM

llltM

OT

AT

L

OW

Hl

III

UII

I C

Oft

TJl

OL

OU

n

ru

ulltl

A

nT

T

HA

-

0bullbull M

OH

IfOIt

fl

lLA

Y I

AO

INI

MU

C

AN

cn

CO

fTltO

Ibull

ItIL

A

INT

ILO

CIC

OL

EN

OtD

Ll

OU

ID L

INt

Cc

ulT

MOO

ULIE

C

NIC

CA

SE

ItS

C

(

OM

II

IOII

(lI

IieLf

W

I eM

-

UIE

R

TH

III

OIT

6Tmiddot S

lOU

lC

U

MC

ot

LOW

TlM

e

U1

T

lER

bullbull

L l

OA

JIIO

middotCU

lTo

tJ

II W

UU

Nt

TI

M

AL

IO

D

oC

0It

1 U

IIN

t T

IMe

OC

LU

middotCA

II C

ONT

a

LOW

IU

t L

OCK

OUT

NPD

WIU

UN

LOA

Olil

t 1

0L

(NO

I0

C

O

III

OIl

lI

cn

CIJ

tCU

IT

UII

lEIt

ft

EC

poundIV

E H

IAI

C

Ol

(C

UIT

1I

IUIIl

I1II

CO

NY

(NIE

NC

E

OU

TU

T

CU

I C

ON

nlo

0

1

AN

$ M

ill1

1

HO

YIll

MU

II

lLT

I l

OA

O

LlI

lIIT

T

H(

O

ITA

T

OL

O

VC

LO

AO

MIA

nl

L1

lI1

~HAII

LO

IS

MO

NIT

O

L

Imiddot J

~fOT

L

IOH

TS

1

1

IC

IIV

E

HE

UE

ItM

lIC

tmiddotl

rC

IIV

E

MU

TlI

t l

tIIS

UIl

l(

CO

NT

ItO

LI

T

lmiddot1

C

CC

lvllt

N

EA

fllt

T

lW

OS

TA

lI

TO

Jmiddot 4

T

INe

H

LA

Y

LOW

In

vlt

l LO

C

OU

T

1O

t-1

ft

lll

D

UA

Tmiddot

TA

SIT

ION

C

ON

TAC

TO

Ill

$middot

1

CO

C

O

(

lIO

C

ON

TA

CT

O

T

A

Dn

u

CO

WC

tllltN

CI

ount

T

DE1AIL~

ST

AR

D

EL

TA

S

TA

RT

r

2

~f

10

t10

II

amp

II

11

II

)

1IllI

1IU

--shy

OW

E

IV

-

utv

lO

f

I I Ibull

A

UR

C

IlltC

UIT

C

IRC

UIT

ALA

NlC

UfT

C

lflC

UIT

I I

I

~li

IT

I

Ot

ON

AL

il------~---l

-

tL

J --

--

C

it

prIlgjf~

II

ell

I

I

IfB

I

t

---------~~-------

__

~

L_ -

7 -

-r--

et

r

I

II10

-I

CII

-lt

PL

1amp

I I

II b

I

L _

__

J

II 3

2I

oo

II

Qraquo

~

IS

lI

(

)r-

t-_

_ o

J_

_

O

TIO

L

I ~~

--~-

I

I CD

oL

__

__

__

__

__

CO

I- f

_

JI I

t degz

OI

OIl

lAL

r-

---

IS

r

-l

0

I

I

+10$

IL

KS

I T

e

0 Lr

I J

II

T

ITI

lOL

l 1

40

bull (C

IS)

TO

bullbull

lD

A-

~ -

r--

-~l

)~II

I

~G

__

_~L_J

0

O

HA

I

~ -

-Ill

-

---

-10-

--

~E

II

cn

-C~

II

Z

0

G)

Il

l~

r- I W

lllltO

WH

IN

JU

L1

l0

I I

I

OL

M

OL

MI

OL

I ~ro

o

jo

o

Jt

JI

L

OT

10N

AI

II

0

(01

0 CO

MPR

ESS

OR

C

IRC

UIT

~

27

III

gt

0

IIA

IO

amp1

)amp

1

1

II

~

I rA

I

TA~

D

ELTA

STA~T

CONP~E~)

CU

lT 2

~

f

bull ]

A

U

4 ]I

IUft

middotJI

Mon

tUPlOI

NT

lOA

Ot-

-O

I

01

0

]

(N

GI

011

1

00

CT

AN

)

40

00

HN

a

_N

I

J00

I -

It IC

y

TO

I

I I

I

~

oiiO

NA

t

I bull bull

wi

i

lOa

r~TT~-

I M

OT

I C

ON

sr

0

llItt

(

co

ce

OZ

UK

1

11

_JO

I I

)--11

--

- ---

-

IJI

LD

~

I

A

CK

lS

C

UK

I

IL

UO

A

TO

O

WH

IT

1

L

OW

SW

ITC

HJl

AL

D

00

IZ

I

f

1It-

-

rl__ u-

poundL

J f

aT

ION

AL

TI

WfI

OO

f

~

ff

I

Dill

C

ON

TAC

TOIlI

C

OtL

S (1

middot4

(IS

middot14

A

ND

II-

I

01

1In

N

O

Wl

0

51

11

~

CO

NT

AC

TS

I

fH

IO

Uti

IS

N

OT

TO

IE

al

llauN

DIO

O

N H

I Sr

CO

NO

AIl

lf

StO

l

f

I

TI

AN

D

TI

TI

U

I

IIN

OII

t

0middot

f1L

OC

AT

IO

IN n

lll

GU

lUT

r-

----

shy~

(I

G

lIt

no

v

HA

I

LO

SS M

ON

IO

nf

1Na

bull

AN

D

ON

rc

I(

CO

M(

f A

IrfD

I

lItU

rC

TIY

(U

00

-

5

E

[CO

OIO

lItc

rlll

TO

0

0

AN

UA

L

t

OIN

T A

Na

f

oo

IlU

COfrt

TO

I U

ND

IN

Stt

UC

TIO

trl

r

co

rNH

D

01 11

raquoIN

ITIA

L

CO

NT

lIIiO

L

fII

I0 I

UT

IS

a

jshy

orshy

10bull

CO

M1

II1t1

Ol

MO

GU

LI

I N(

tN-a

UT

OM

AT

lC

I 1I

lfla

n

flS

bullbull

11

A

LSO

ampO

eMmiddotO

UT

luer

llt

middot I

no

C

AL

Y

WH

IM A

N

IUIT

T T

IIII

P

T

MU

I C

ON

egoo

IT

flO

LI

CA

l

ItU

I1 I

T

TU

NIN

G W

ITC

M

0

~r=

0 I

lIO

Wlf

lIT

A

L

fOtt

CO

lI

tbullbull

w

ITC

H_

I

on

WO

Nlf

lIT

JII

IL

POllt

COW

bull

I In

degz

r+-i

~~

t

u ~o

1 ~rI~~

~~

~~TtIc~~I~D

1

SW

lTC

HI ~

C

OIfT

AC

TcU

t W

lItN

t C

OM

bullbull

H

To

lIL

b

l

0t~~1

0

1

CO

tfC

TO

H

I

lIt

C

ltbull

IIT

C

~r-

bull

WM

IH

-

2

N

OT

1V

l

rD

wllI

I[ to

IlIC

OM

n

I W

I

It

I

fjC

Ofl

P

tE

CJ)shy

t W

IN L

UI N

OT

SU

PL

ID

W

IIIIC

O

J

lleo

W

ti

l

LU

KT

IT

10- A

ND

10ft

II

v

C~

LO

CA

TU

I II

1t

11V

MI

_T

at

I

z10

I

T

lNH

A

TU

RC

S

lNS

OIt

MU

tT

ve

IL

OID

C

IL

C

()

11II

L

AT

I

AT

10

_

A

U

IIIT

I0middot

PCA

LOW M

I_ lO

TI

I bullbull

n

II

DES

IGN

ATI

ON

S

II

CO

NT

IlID

t I

NO

-o

MO

LD

INfl

C

OIL

It L

tNI

NO

0

Q

N

C

CO

NU

ClI

W

ITH

UN

I N

O

01]

0 co

O

f

11

~

I

ILK

n

e

s IA

UL

It

ibull

o O

CO

NTA

CTS

w

nw L

INI

NO

01

fA

0

~

fItO

TI

LI

I N

O

v

A

II

~ ~ bull i middots

~

~~ - ~

~

1- I J I J I I I I I I I I I I I I I I L __ J

I

a bull bull a bull bull

I I I

_J

r------~

=~I = ~ ~ bull ~ I I

~

as coe ruq SV~ siapow ~NI~IM lO~lN03lV3ldAl

i 4

_

a

~FirI1 u~III - I I

~ 1I

00000 -

I=II~I~~~~raquoIIIItIII~ampI~

as ooz nJ4l sv ~ siapow ~NI~IM lO~lNOgt TVgtldAl

bullbull bullbull

bullbull

~

jgt

lpoundIt

ND

II

co

----

----

----

----

----

----

----

----

-

r-~-middot--=-~~

~

bull a

~

at~04

5

---

~1I

A

~n

bullbullmiddot-shy

wo

_-

bull

lIt

C-

I C

Cf

aC

TO

Ic

ow

n

CC

eM

ca

~C

M

OD

IAI

CI

T-

CO

IITA

CT

oa

bullbull

CMCU

rT I

ItIM

IA

co-l

to

c-c

VIT

C

I

rr

c

AfE

bull r~----Ef1

POW

I

III

IQ

W

Q

tIL

UT

I1I

U__~

J

COt

I

LD

W M

lMtr

f nc

IIO

ff

0

N

LO

W

C

OIIT

INM

I I

CO

M

US

ON

C

NC

UIT

II

II

-~

_T

shy

C

O

NU

SO

II

CIN

CU

IT Z

II

D[TA~

-

ST

AN

D(~TA

IT

AII

T

0

u III

r

amp

II

-~

If

10

MA

MI

eN

talI

Tco_

~

STA

N D[~TA

ST

AII

T

~

CIS

-I

LA

~ 1-4

nmiddot

00

-

-II

1t1S

-1 aw

o fI

fl

U- I -~ Ci

Pi=

i

t

shy

~

iii

i

iii=

ii

-

-shyiii

ClL

n

TU

U

LOt

e

bull It

lLA

Yn

C

AM

Im

CIII

IID

L bull

CU

_C

Abull

fl

lUY

_f

tMO

ea

UY

middotIO

CI

lO

Ll

t

NIU

_L

N

CO

WU

UO

ItC

U

llT

l bullbull 0

1middot

lit

TMC

MI0

8TA

T tc

_lt

CIl

it

11

II

_

middotLO

W

TII

IfN

T

UIlI

C

nll

-

D-C

UlT

QIIU

tW

n-T

PII

IU

LIO

MI-

AC

TC

Ntf

Wi

MI

II

II

tY

middotCM

OO

C

LOW

HIe U

(O

Uf

lIl_

L

OA

M

1OtI

1tO

lD

CO

OA

CM

UtT

1M

C

lIY

Dl

NC

Afi

ll ea

-tU

lT 1

ItUbullbull

lI

oo

ww

lItt

lffc

e O

Un

n

cT

IlG

I

Ie-

~U

IIIC

CIV

P

1T

1lt

C

bullbull

Off

AT

tw

ebullbull

ampOW

IC

IUT

~-

4ti

iT

~

co

ww

O

UfU

T

DITA~

A

ITA

A

OEL

TA

IT

AJI

IT

co

rn~

e

I

1amp

ItmiddotI

~ bull

I I

I

I r

~

bull Iamp

II

I ~

I-

oJ

II I

IrIf

I I I I

s~

o

-I I

ltDc

() raquo

L 10

V

i

()

~O

to

U

lZr0

t2

llJ

IL

C6

J=

_J

~-1

f

II

c 0

II

N

ge

cno

c-

II

Z

Ggt

If IO

IC

IIY

II

IIR

III

IJt

T H

llII

A

Il C

Olaquof

U

TMIbull

~LDM

fI

lAR

PM

Iamp L

Oll

lTV

ii

iLii

Uii

ii

~

U3

I iL

iii=

i

Uii

u

i

O

(no)

T

bull II

1

IOA~

bullr

~ I

[gtO(]O

~ i I Ii i 2 ~ ~ ~ i a bull il 2 ~

iiibullbullbull

~ I ~ I I I ~~ =l ~ iI I ~ I I I It I 1111 amp ~~

as ooz nJ4l SP~ SlapoUII ~NI~IM 10U1NOl lVlldAl

-------

---

TYPICAL POWER WIRING Models 45 thru 70 SC

----

rYl31I01 I

-Ii --ti-

_ I ~_-

~ lniJ -

LIIbullbullbullbull PC _ amp-II _--- ~

TYPICAL POWER WIRING Models 90 thru 135 SC

- --- _ Tt

~rfh c~

tP ~

_III ~

I r-- ~- IIlJ

bull - MIl Mf __ bull Ie_~--~ _shy- shy16

---

----------

TYPICAL POWER WIRING Models 145 thru 200 SC

_ --1a1 IIUrI

middotrFti~v_ bull I

i~i ~~ TaII IIOMLI ~tN T 100 WTIOII 011 lilOOCL a

~ t1

tI bullbullbull

L

i I r-~

I r

~ ~ ~ III

2 ~ ~ ~l

- ~IlD I hJOHr eo teO acshyt CmiddotClM ~ CIKUr1 --

TYPICAL POWER WIRING Models 215 thru 265 SC

ItUU 1D Wll1U1I fIa -rMI

rt-h I -au 11 1_ i r~ rt-f

-i rn f1 ft fi i- llil bullbull c~ I bull c =

~~~ ~i~-~

~~m

~~~CI1 R~~ ~ ~~ ~llAi4I

luv~ bull ~uf LL~~-

~Mfl l~t IrMiA

a I III nII I bull it d

~-t--J I Lll-l~j ~nL4111 WlJj== lit-

I bullbullbull I

UGEND

~

~l OJ

- c~

~~~---

~)~middotI

I

L _~~~ L _I__~_J I ~ (11_1 ~ H~ CUlTMIt tffC_) Ll N

-r_ 0 1ItCIIIl0AI lllQUlllCo as -0- bull bullbull fI PC 110 lNJCllII a Olil1100pound1 II 111 el 1101 ItCOU_ 011 IIOOIL140

I 011 CI-( H[ (0110 (fMCun ubullbull --- l(lD IMbullbull Ntlf 110 e414-7

--CTOttbullbull

2

17

ELECTRICAL DATA Model Volts Type COMPRESSOR FAN MOTORS MIN CIRCUIT RECOMMENDED MAXIMUM ACWC 60 Hz of Qty RLA Starting FLA LRA AMPACITY WIRESIZE FUSESIZE

SC 3 Ph Start HP Ea Curro Ea Ea Ea Circ1 Circ2 Circ1 Circ2 Circ1 eire 2

208230 XL 1788 1040 (4) 70 (4) 380 252 - 250 - 400 -45 208230 YO (1) 50 1788 347 (4) 70 (4) 380 252 - 250 - 400 -

460 XL 737 422 (4) 35 (4) 190 106 - 2 - 175 -460 YO 737 141 (4) 35 (4) 190 106 - 2 - 175 -

208230 XL 2051 1228 (4) 70 (4) 380 284 - 300 - 450 -55 208230 YO (1) 60 2051 409 (4) 70 (4) 380 284 - 300 - 450 -

460 XL 904 485 (4) 35 (4) 190 127 - 1 - 200 -460 YO 904 162 (4) 35 (4) 190 127 - 1 - 200 -

208230 XL 2083 1415 (6) 70 (6) 380 302 350 500 -70 208230 YO (1) 75 2083 472 (6) 70 (6) 380 302 350 500 -

460 XL 974 539 (6) 35 (6) 190 143 0 225 -460 YO 974 180 (6) 35 (6 190 143 0 225 -208 XL 1788 1040 (6) 70 (6) 380 266 224 300 0000 400 400 208 YO 1788 347 (6) 70 (6) 380 266 224 300 0000 400

90 230 XL (2) 50 1788 1040 (6) 70 (6) 380 266 224 400 I300 0000 400 400 230 YO 1788 347 (6) 70 (6) 380 266 224 300 0000 400 400 460 XL 737 422 (6) 35 (6) 190 187 - 000 - 250 460 YO 737 141 (6) 35 (6) 190 187 - =1000 - 250 208 XL 2051 1228 (8) 70 (8) 380 312 256 400 300 250 208 YO 2051 409 (8) 70 (8) 380 312 256 400 300 500

110 230 XL (2) 60 2051 1228 (8) 70 (8) 380 312 256 g I350 300 SOO 450 230 YO 2051 409 (8) 70 (8) 380 312 256 350 300 500 450 460 XL 914 485 (8) 35 (8) 190 231 - 0000 - 300 460 YO 904 162 (8) 35 (8) 190 231 - 0000 - 300 -

208 XL (1) 60 2051 1228 (8) 70 (8) 380 312 260 400 300 500 450(1) 75 2083 1415

208 YO (1) 60 2051 409 (8) 70 (8) 380 312 260 400 300 500 450(1) 75 2083 472

230 XL (1) 60 2051 1228 (8) 70 (8) 380 312 260 350 300 500 450(1) 75 2083 165125

230 YO (1) 60 2051 409 (8) 70 (8) 380 02 260 350 300 500 450 (1) 75 2083 472

460 XL (1) 60 904 485 (8) 35 (8) 190 240 - 250 - 300 -(1 75 974 539

460 YO (1) 60 904 162 (8) 35 (8) 190 240 - 250 - 300 -(1) 75 974 180

208 XL 2083 1415 (8) 70 (8) 380 316 260 400 300 500 450 208 YO 2083 472 (8) 70 (8) 380 316 260 400 300 500 450

135 230 XL (2) 75 2083 1415 (8) 70 (8) 380 316 260 400 300 500 450 I 230 YO 2083 472 (8) 70 (8) 380 316 260 400 300 500 450

460 XL 974 539 (8) 35 (8) 190 247 - 250 - 300 -460 YO 974 180 (8i 35 (8) 190 247 - 250 - 300 -

208 XL (2) SO 1788 1040 (10) 70 (10) 380 326 402 400 0000 500 500(1) 60 2051 1228

208 YO (2) 50 1788 347 (10) 70 (10) 380 326 402 400 0000 500 500(1 60 2051 409

230 XL (2) 50 1788 1040 (10) 70 (10) 380 326 402 400 0000 500 500 145 (1) 60 2011 1228

230 YO (2) 50 1788 347 (10) 70 (10) 380 326 402 400 0000 500 500(1) 60 2051 409

460 XL (2) 50 737 422 (10) 35 (10) 190 295 - 350 350 --(1) 60 904 485

460 YO (2) SO 731 141 10 (35) (10)190 295 - 350 350- -(1)60 904 162

208 XL 2051 1228 (10) 70 (10) 380 326 462 400 (2)250 500 600 208 YO 2051 409 (10) 70 (10) 380 326 462 400 (2)250 500 600

160 230 XL (3) 60 2051 1228 (10) 70 (10) 380 326 462 400 (2)250 500 230 YO 2051 409 (10) 70 (10) 380 326 462 600400 (2)250 500 600 460 XL 904 485 (10) 35 (10) 190 329 - 400 - 400 460 YO 904 167 (10) 35 (10) 190 329 - 400 - 400 - I

NOTES 1 XL Across the LineYOStarDelta 2 RLA Rated LoadAmps(ratedin accordance withARI Standard 590) LRA LockedRotorAmps 3 Wire Size Amps equal125of the ratedloadampsfor the largestmotorin thecircuitplus100of the ratedloadampsfor all othermotorsin the circuit per

NEC 4 Wire size based on copperconductorswith75C insulation perNECTable310-16 Terminal block lugs are sizedaccordingly Use of oversize wiringmay

not lit in terminal blocks 5 Maximumfuse size is basedon 175to 225of the ratedloadampsfor the largestmotorin the circuitplus 100of the rated loadampsfora othermotors

in the circuit per NEC VOLTAGE TOLERANCES 208V-230V min 187VMax 253V

480V Min414V Max506V

I

18

ELECTRICAL DATA Volts Type COMPRESSORModel FAN MOTORS MINCIRCUIT RECOMMENDED MAXIMUM 60 Hz of Oty RLA Starting FLAACWC LRA AMPACITY WIRESIZE FUSE SIZE 3 Ph Start Curro EaSC HP Ea Ea Ea Cire1 Cire2 Cire1 Cire2 Cire1 Cire2 208 XL 2051(1) 60 1228 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 1415 208 YO (1) 60 2051 409 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 472 230 XL (1) 60 2051 1228 (12)70 (12) 380 341 469 500 (2) 250 500 600

12 75 2083 1415185 230 YO (1) 60 2051 409 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 472 460 XL 485 (12) 35 (1) 60 904 (12) 190 352 500 400- - -

(2) 75 974 539 460 YO (1) 60 904 162 (12) 5(12)19 352 500 400- - -

(2) 75 974 180 208 XL 2083 1415 (12) 70 (12) 380 345 469 500 500(2) 250 600

472208 YO 2083 (12) 70 345(12) 380 469 500 (2) 250 500 600 230 XL (3) 75 2083 1415 (12) 70 345(12) 380 469 500 (2) 250 500 600200 230 YO 2083 472 (12) 70 (12) 190 345 469 500 500(2) 250 600 460 XL 539974 (12) 35 (12) 190 359 - 450500 - -

180 1(12) 35 460 YO 974 (12) 190 359 450 -500- -2051 1228208 XL (12) 70 504(12) 380 504 (2) 250 (2) 250 700 700

208 YO 2051 409 (12) 70 (12) 380 504 504 (2) 250 700(2) 250 700 (4) 60 2051 1228 (12) 70 230 XL (12) 380 504 504 (2) 250 (2) 250 700 700215

YO 2051 409230 (12) 70 (12) 380 504 504 (2) 250 (2) 250 700 700 460 904 485 (12) 35 XL (12) 190 225 225 0000 0000 300 300

(12) 35 460 YO 904 162 (12) 190 300225 225 0000 0000 300 2051 1228208 XL (2) 60 (14) 70 (14) 380 504 525 (2250 700 700(2)300

(2) 75 2083 1415 2051 409 (14) 70 700 700208 YO (2) 60 (14) 380 504 525 (2) 250 (2)300

(2) 75 2083 472240 700XL (2) 60 2051 1228 (14) 70 (14) 380 504 525 (2)250 (2)300 700230

(2) 75 2083 1415 2011230 YO (2) 60 409 (14) 70 (14) 380 504 525 (2) 250 (2)300 700 700

(2) 75 2083 472 300460 XL (2) 60 904 485 (14) 35 (14) 190 225 248 0000 250 300

12 75 974 539 904 162 250 300 300460 YO (2) 60 (14) 35 (14) 190 225 248 410

(2) 75 974 180 2083 1415 (2)300 700 700XL (16) 70 (16) 380 525 525 (2)300208 2083 1415 (2)300 700 700208 YO (16) 70 525 525 (2)300(16) 380

700 7002083 1415 (16) 70 (2300230 XL (16) 380 525 525 (2300 700 700(2300(4) 75 2083 472 (16) 70 (16) 380 525 525 (2300230 XL265

300250 300974 539 (16) 35 248 248 250XL (16) 380 460 (16) 35 300 300974 (16 380 248 250 250YO 539 248460

NOTES 1 XL Across the Line YO Star Delta 2 RLA Rated Load Amps (rated in accordance with ARI Standard 590) LRA Locked Rotor Amps 3 Wire Size Amps equal 125 of the rated load amps for the largest motor in the circuit plus 100 of the rated load amps for all other motors in the circuit per

NEC 4 Wire size based on copper conductors with 75degG insulation per NEG Table 310-16 Terminal block lugs are sized accordingly Use of oversize wiring may

not fit in terminal blocks 5 Maximum fuse size is based on 175 to 225 of the rated load amps for the largest motor in the circuit plus 100 of the rated load amps for a other motors

in the circuit per NEG VOLTAGE TOLERANCES 208V-230V min 187V Max 253V

480V Min414V Max506V

19

0

(Wd~) 3lV~ M011 ~31VM

006 009 00 OOt OOl OS L 00 L os 0 Ot

V D m (I) (I)

c D m c D o V

- m m -t o

~

~ m D-

aoao 3~nSS3~d ~3100~

APPLICATION DATA

POINT LOADING

ArMi I 1 5 1

ACWC 45 THRU 10 SC

COMPRESSOR CONDENSER SECTION SECTION

_ 2 4 bull 1

bull CA

J

Model Dimensions Size A B C D 45 91 - - -55 91 - - -70 145 - - -90 145 - - -110 60 40 160 -125 60 40 160 -135 60 40 160 -145 138 74 107 -160 13830 74 107 -185 138 129 107 -200 138 129 107 -215 106 82 106 80 240 106 82 134 107 265 133 110 134 107

1310

1310

~

1

1310

2

ACwe 110 THRU 200 Ie

COMPREIlOfl CONDENSER SECTION IECnoN

4 -

5Imiddot

ACWC 2t5 THRU 215 SC

Model Loadlnu (LBS) Size 1amp2 3amp4 5amp6 7amp8 9 amp10 45 585 765 550 - -55 705 810 635 - -70 660 890 700 - -90 1025 1500 1175 - -110 1195 635 1525 995 -125 1255 690 1835 1115 -135 1255 665 1880 1105 -145 1330 2380 2160 1450 -160 1330 2440 2280 1515 -185 1235 2575 2980 1360 -200 1275 2635 3020 1380 -215 1010 2270 2590 2240 840 240 1115 2550 2870 2715 1125 265 1380 2980 3515 2750 1175

11

II i middot 2 4 lIf 11 to L

21

TROUBLESHOOTING GUIDE

CHILLER UNIT WILL NOT START POSSIBLE CAUSE REMEDY 1 Power off 1 Check main disconnect switch

2 Main line open 2 Check main fuses

3 Incorrect wiring 3 Check the wiring diagram

4 Loose terminals 4 Tiqhten all terminals

5 Control circuit open 5 Check phase loss monitor flow switch circuit breakers temperature control low ambient thermostat low temperature thermostat remote switch etc

6 Time delay 6 Wait

COMPRESSOR HUMS BUT DOES NOT START

POSSIBLE CAUSE REMEDY

1 Low voltage 1a Check at service and unit for loss

b Consult power company

COMPRESSOR CUTS OUT ON LOW PRESSURE SAFETY CONTROL POSSIBLE CAUSE REMEDY 1 Refrigerant shortage 1 Check for leaks -- add refrigerant 2 Restriction in liquid line 2a Plugged strainer - dean or replace

b Liquid line valve partially closed - open valves fully c Expansion valve clogged or inoperative - clean or replace as

required d Solenoid valve partially open - clean or replace as required

3 Low water flow thru cooler 3 Check water flow thru cooler and correct as required

COMPRESSOR CYCLES ON HIGH PRESSURE CONTROL POSSIBLE CAUSE REMEDY 1 Compressor discharge valve partially closed 1 Open valve fully 2 Non-condensible gases in system 2 Operate condenser fans with compressors off If condenser

pressure exceeds saturated pressure corresponding to condenser entering air temperature then purge air from discharge line

3 Overcharge of R-22 3 Purge system while in operation until head pressure reaches a normal level

4 Dirty condenser 4 Clean the condenser 5 Compressor discharge check valve not operating properly 5 Replace if necessary 6 Fans not running 6 Check pressure control setting

CAUSES AND PREVENTION OF FREEZE-UP CAUSES PREVENTION 1 Improper charging 1 Charge per manufacturers recommendation

2 Improperly set safety time delay 2 Check the safety time delay low pressure control for proper setting at the beginning of each season

3 Improper chilled water circulation 3 Use an ample sized cleanable strainer in the chilled water circuit Make certain the strainer is clean to insure full flow and velocity of

chilled water It may sometimes be necessary to treat the water to prevent formation of deposits

4 Not draining for winter shutdown 4 When the system is shut down for the winter remove the drain

plugs and drain the cooler Blowout any remaining water with air

5 Improper pump shutdown 5 Make sure chiller barrel heater is working and flow switch is installed per wiring diagrams

6 Low ambient during air conditioning season 6 Make sure chiller barrel heater is working

NOTE If the ambient temperature is below 32degF freezing can be completely prevented by one of two methods

1 Drain all water from the equipment 2 Add antifreeze to the water

22

START-UP CHECK LIST

Unit Model No

Setting unit

Wiring

Piping

Alignment

Before Start-Up

After Start-Up

Yes No a Vibration isolator used

b Spring isolator adjusted for equal height c If rubber-in-shear isolators are used is unit leveled by shimming

a Power wiring complete

b Control wiring complete c Electric service adequate for load

d Power source voltage correct for motor(s) used

e Motor circuit has proper size fusetrons f System wired per diagram

g All lead connections tight h Wiring complies with local codes i Flow switch operation

a Piping complies with applicable codes b External piping independently supported c Chilled water lines insulated

a All belts adjusted and checked for tension b All pulleys checked and adjusted for proper pitch tightness and

alignment

a Open compressor discharge service valve b Open liquid valve(s) c Open suction and discharge valves to pressure gauges (if supplied) d Check rotation of all fan motors e Start auxiliary equipment (pumps fans etc) f Is crankcase heater operating Operate 24 hours prior to unit startup g Check the compressor oil level through the crankcase sight glass The oil

level should be to the top of the glass If the level is low add oil in accordance with the directions in the maintenance instruction

h Check all control settings as specified in Table 1 I Air purged from chilled water system

a Check high pressure control b Check oil temperature safety switch c Check and adjust low pressure or temperature freeze control d Check and adjust operating thermostat e Check and adjust low pressure operating control f Check and adjust expansion valve superheat g Check and adjust capacity control thermostat

23

OPERATING DATA CHILLER Voltage L-1 L-2 L-3 _ Pressure Gauge Readings 1 Suction psig 1 Discharge psig 2 Suction psig 2 Discharge _ psig 3 Suction psig 3 Discharge psig 4 Suction psig 4 Discharge _ psig High pressure switch setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-in) psig psig (Out) 4 (Cut-In) psig psig (Out) Checked Setting - Yes - No (each circuit) Low Pressure Switch Setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-In) psig psig (Out) 4 (Cut-in) psig psig (Out) Checked Setting -Yes -No (each circuit) 1 Oil Temperature Safety Switch Cut Out 2 Oil Temperature Safety Switch Cut Out 3 Oil Temperature Safety Switch Cut Out 4 Oil Temperature Safety Switch Cut Out If Star-Delta start time delay is seconds Temperature of air entering condenser F Temperature of air leaving condenser of Temperature of chilled water entering chiller OF Temperature of water (chilled) leaving chiller F Chilled water pressure entering chiller psig Chilled water pressure leaving chiller psig

MAINTENANCE Good maintenance practice will prolong the chiller life and will reduce the Ask of system breakdown and expensive service calls

A weekly check of the ACWC-SD unit requires only a few minutes and will prove beneficial in insuring long trouble free operation

WEEKLY CHECKS- with unit in operation for at least four hours 1) Check compressor oil level - At least above 12 of sight glass 2) Record suction and discharge pressures

Typical Condition R22 Ambient 95degF Return water 55degF Leaving water 45degF Suction 62 psig Discharge 270 psig

3) Record ambient temperature 4) Check liquid sight glass

Make sure liquid is clear - no bubbles 5) Check that all fans are running 6) Check entering face of condenser coil for cleanliness 7) Record voltage at unit

All of the above can be performed by building maintenance personnel If oil levels are low or any of the above checked items are questionable consult a qualified serviceman

At least once a year a qualified serviceman should check unit oil levels superheat and control operation

DUNHAM-BUSH USA

P l) bull 130 xUtUC t01 Bmgess RO~ Harrisonburg VA 22801 Phone (540) 434-0711 FAX (540) 434-~ 2118

wvvwdunham-bushcom Form No 6184

Page 3: ACWC-SD - · PDF fileACWC-SD • Screw . Type • • • Air-Cooled Packaged Chillers •• Installation, Operation, and •• • Maintenance Manual • • • •• DESCRIPTION

CAUTION

The discharge line valve must be open before starting the compressor Liquid line valves must also be open for sustained operation

All compressors are solid mounted on isopads therefore compressor hold-down bolts must not be loosened Loosening these bolts will cause excessive vibration of the compressor and may result in refrigerant line breakage Prior to start-up check all compressor hold-down bolts for tightness

MAINTENANCE

CONDENSER Units are equipped with direct drive fans that have inherently protected motors with permanently lubricated bearings

The air inlet of the condenser coil should be kept clean through a regular maintenance program

COMPRESSOR

1 OIL LEVEL - The oil level in the compressor(s) should be checked periodically with the compressor either running or stopped If the oil level is below one-half (12) the sight glass oil must be added

2 RECOMMENDED OIL -- The unit 4 factory-charged with DB SR-30 refrigeration 01

Do not add any other type of oil to this factory charge

Do not operate compressor If 011 level Is below one-half (12) sight glass

If the oil level is below the minimum specified above and DB SR-30 is not on hand you may drain the entire factory oil charge then refill with SUNISO 4GS refrigeration oil The factory (DB) oil is of the synthetic type and will not mix with SUNISO 4GS Do not attempt to operate the screw compressor with any oil other than these two specified above

It is suggested that a gallon or mom of DB SR-30 oil be obtained and kept on hand at the job site The substitution of SUNISO 4GS oil as outlined above will result in a 2 to 491 capacity loss and no reduction in input KW

PROCEDURE FOR ADDING OIL

Install temporary jumper wire around LPcontrol contacts of circuit to be serviced Manually close liquid line service valve Lower return water T-STAT (T1) setting to start compressor Run compressor until minimum positive pressure reading on suction service gauge (Do not run compressor in vacuum) Place the system onoff switch in the off position Close the line valve in the discharge line between compressor amp condenser Equalized pressure should now be a minimum of refrigerant vapor Reopen discharge line valve Remove jumper wire from pressure control Open liquid line service valve

3 COMPRESSOR REPAIRS (internal) - Contact factory or an authorized DB Service Agency if a compressor malfunction is suspected

4 COMPRESSOR REPAIRS (External) - Proper operation of unloaded ban loading and unloading is controlled by solenoid valves UL-1 UL-2 and UL-3 Any of these three (3) solenoid valves may be repaired or replaced in the field as required

5 Standard oil acid test kit is not compatible with synthetic oil See DB color chart for oil condition

HIGHPRESSURE PORT

SIGHT GLASS I

CRANKCASE HEATER

3

SLIDE VALVE UNLOADING SYSTEM

The Rotary screw compressor capacity control system for infinite modulation consists of a slide valve and hydraulic pistoncylinder operator intemal to the compressor plus three hydraulic solenoid valves (UL-1 UL-2 amp UL-3)

The slide valve forms a portion of the chamber wall in which the rotors turn thus its position with respect to the rotors determines the effective rotor length and thereby the percent of full load capacity

Upon compressor start-up UL-3 is opened This allows oil pressure to act upon the hydraulic piston holding it in the fully unloaded position After 30 seconds during which time full oil flow is established to all bearings surfaces UL-3 is closed At this point the temperature controller is free to open and close UL-1 or UL-2 in response to the supply water temperature

The slide valve will move to the left (loading) by force of discharge pressure whenever UL-1 opens to permit flow to the oil return (low

Load

centJ

Screw Rotor

Slide Valve

Unload

~ Oil Pressure

Oil Pressure Lines

Hydraulic Piston

pressure) line The slide valve will move to the right (unloading) whenever UL-2 opens the oil supply (high pressure) line since the force of the oil exceeds that of the discharge gas

The temperature controller sends a series of power (energizing) pulses to the appropriate solenoid to adjust to load conditions The further the supply water temperature is from the controller set point the longer is the duration of the pulses The series of pulses will continue until the controller is satisfied As the water temperature approaches the set point the pulses become quite brief to prevent overshooting the set point

This method of compressor unloading in conjunction with supply water sensing minimizes actionreaction lag time and overshoot resulting in an exceptionally precise and stable control of supply water temperature

Oil Oil Return Supply

The following table lists solenoid valve position for all three operating modes

UL-1 UL-2 UL-3 Starting Close Close Open Loadinq Open Close Close Unloading Close Open Close

4

LOW AMBIENT OPERATION

Due to the wide range of applications it is sometimes necessary to operate the Air Cooled Packaged Water Chillers at ambients below summer conditions Without proper control when ambients drop below 60degF the pressure differential between the condenser and the evaporator is below the level to insure proper thermal expansion valve operation As a result the unit may cycle off Two types of system control are available allowing the units to operate at the ambients indicated

FAN CYCLING MEDIUM AMBIENT CONTROL TO 30degF

(STANDARD EQUIPMENT-FACTORY INSTALLED)

A fan cycling control is standard on all Air Cooled Packaged Water Chillers to provide proper operating head pressures in ambient conditions to 30degF

This is an automatic operation in which the condenser fans are cycled on and off as required in response to head pressure This arrangement provides positive start-up control down to +30degF by delaying the condenser fan operation until a predetermined head pressure is obtained

LOW AMBIENT CONTROL TO OdegF

In conjunction with the standard fan cycling feature all compressors are enclosed in individual housings This housing assures adequate compressor oil temperature for lubrication A five minute time delay relay provides a bypass around the low pressure control to prevent nuisance trip-out during cold start up

COOLER FREEZE PROTECTION-LOW AMBIENT

Cooler freeze protection is a major concern with air cooled chillers To protect against freeze-up a heater cable is provided as standard which protects the cooler to -12degF However there is no freeze protection in the event of power failure or heater cable burnout so the following should be considered for additional protection

1 Drain the cooler and chilled water piping if the chiller is not to be operated over the winter months Drain connections are provided on the coolers

2 Add ethylene glycol to the chilled water system Freeze point should be approximately 10degFbelow minimum design ambient temperature See Page 11 for Glycol Performance

The cooler heater is wired to the control panel and is operational from the factory offered control transformer or field supplied control power

COOLER FREEZE PROTECTION-oPERATION

The ACWC-SD chiller is provided with a temperature sensing freezstat (38deg set point) and a field installed flow switch shutting off the compressors on loss of water flow is also required

Optional low pressure or hot gas bypass freeze protection is also available on the ACWC-SD If these options have not been purchased it is extremely important to guarantee proper chiller water gpm as well as double checking the temperature sensing freezstat calibration

ACWC-SD CONTROL SETTINGS

CUT-INCUT-OUT (PSIG)

UNIT FLP1 FLP2 FLP3 FLP4 FLP5 FLP6 FLP7 FLP8 FLP9 FLP10 FLP11 FLP12 FLP13 FLP14 ISM 44-55 280170 295180

70 260160 275175 2901215

90 260160 275175 2901215 260160 275175 2901215

110-135 260160 2751175 2851210 2951235 2601160 275175 285210 2951235

145-160 280170 2951180 260160 275175 2901215 260160 275175 2901215

185-200 280170 295180 260160 275175 2951235 2951235 260160 275175 285210 2951235 215 260160 275175 2901215 260160 2901215 2901215 260160 275175 290215 260160 275175 290215

240 260160 260160 275175 275175 2901215 2901215 260160 260160 275175 275175 2851210 2851210 295235 2951235

265 260160 260160 275175 275175 2851210 2851210 295235 2951235 260160 260160 275175 275175 285210 2851210 2951235

TEMPERATURE ACTUATED LEGEND FACTORY SETTING

Chiller Low Water Temperature Thermostat T2 Cut-Out 3rF Chiller Heater Thermostat

I(Non-Adiustable) Included With CBH1 Heater

Cut-In Cut-Out

40degF 45degF

Oil Temperature Safety Control (Adjustable) Manual Reset

OTS 1 OTS 2 OTS3

Cut-Out 240degF

Capacity Control Thermostat (Adj) Mode Control Position T1 Dial Set At 44degF

UNIT OPERATING LIMITATIONS

1 Maximum ambient air to condenser is 110degF (60 Hertz operation) 2 Maximum allowable cooler water pressure is 150 PSIG 3 Maximum allowable water temperature to cooler is 75degF 4 Units must not have leaving water temperatures of 42degF or lower unless used with a glycol solution

5

KEY TO WIRING DIAGRAM INDEXING SYSTEM

The wiring diagrams and sequence instructions on the following pages have been devised to simplify the understanding and tracing of circuit theory The following key shows how the indexing system can be used

12 Line number on wiring diagram

[12] Line number in text

(R5) Component identification symbol in text (Relay 5)

[E] Normally open contact - line number location

[E] Normally closed contact - line number location

Holding coil - line number location

amp Note number

SEQUENCE OF OPERATION (TYPICAL) MODELS ACWC 90-135 SO

The following sequence of operation is typical for all ACWC SD Models Refer to the wiring diagram furnished with the unit for specific information ( ) Control Identification Symbol [ ] Circuit Line Number

Important Notel With all the control circuit switches (SW1-SW3) in the off position and the staging thermostat (T1) to its highest temperature Terminals 2 and 4 on the Terminal Board (TER5) must have 115 volts supshyplied for a minimum of 24 hours to energize the compressor crankshycase heaters (CCH1 2) [6 8]

Preliminary Sequence Close the main power disconnect switch Check to see that the red indicating light on the phase loss monitor (PLM 1) is lit (Note There will be two phase loss monitors (PLM1) and (PLM2) on dual power block models) This light must be on to indicate proper phase rotation for the compressors If the light is not on disconnect the main power and reverse any two phase legs at the Main Incoming Power Terminal Block (WARNING DO NOT REVERSE THE LEADS ON THE PHASE LOSS MONITOR FOR THIS WILL ALLOW THE COMPRESSORS TO RUN BACKWARDS CAUSING SEVERE DAMAGE AND WILL VOID THE COMPRESSOR WARRANTY)

The crankcase heater relay contacts (R3) [6] and (R4) [8] are closed and are supplying power to the compressor crankcase heaters Power is also supplied to the chiller barrel heater (CBH1) [13) the optional receiver heaters (RH1 2 [1011] and the optional convenience outlet (CO) [14]

Control power goes through the control panel circuit breaker (CB1) [8] and field supplied remote time clock [36] Check to make sure time clock contacts close during occupied modes

Start up the chilled water pump The water flow is confirmed when the water flow switch completes the electrical circuit across Terminals 15 and 16 [38] on Terminal Board (TER5) Terminals 17 [47] and 18 [49] provide an interlock for the water pump starter(s) when either compressor is in operation Set the thermostat (T1) to the desired leaving water temperature (eg 44degF) Set point adjustment is acshycomplished directly on the control

Place the three (3) control circuit switches (SW1-SW3) in the On position thus energizing the balance of the control circuit [23] [33] [36] The system will be in the Time-In mode for five minutes before the first compressor will start

The low ambient lockout thermostat (LAT1) [38] and temperature freezestat (T2) [38] must also be satisfied to allow compressor operashytion

Stage 1 Starting Upon demand for cooling thefirst stepof the staging thermostat (T1) will be to close energizing relays (R1) [61] time delay (TD1) [60] and the optional time delay (TD3) [62] If all the safety controls and switches are closed (see Safety Controls section for more detail) the control

circuit for Compressor No1 will energize allowing the compressor to start Relay (R5) [20] will energize closing the normally open (NO) set of contacts [23] which energize the liquid line solenoid valve (SOL1) [23] Another set of NO contacts on (R5) [20) provide a series intershylock with all the safety and operating controls which will lock out the compressor if any safety trips during normal operation (See Note 6 on Wire Diagram) The last set of NO contacts on (R5) [48) provides an interlock circuit for the water circuiting pump(s)

The fan contactor (C13) [23] will also close supplying power to the side of the fan cycling pressure controls (See Power Wiring Diagram)

Note The fan motors are controlled by their own fan cycling controls and will cut in at different factory set head pressures

Time Delay (TD1) [601) has two (2) sets of contacts the first set of (TD1) [19] normally closed (NC) contacts provide a 30 second jumper around the low pressure control (LP1) [20] to prevent short cycling during start-up The second set of (TD1) [24) contacts in the NC posishytion power the unloader solenoid (UL3-1) [24] which hold the comshypressor in the full unload position for 30 seconds After (TD1) [60] times out (30 seconds) the contacts for the unloader solenoid (UL3-1) open and the NO set close which energize the relay (R3) [25]

Stage 1 Modulation Upon energizing relay (R3) [25) the crankcase heater (CCH 1) [6] is de-energized and the NO contacts of relay (R3) [45 48] are closed allowing the thermostat (T1) to energize the load solenoid (UL1-1) [45) and the unload solenoid (UL2-1) [481] upon demand The opshytional time delay (TD3) [62] is used to bypass low pressure control (LP1) [20] for five minutes for low ambient starts

Stage 2 Starting Subsequent to the start of Compressor No1 an approximate five minute time delay is incorporated into the microprocessor After this time delay and a further call for cooling the second step of the stagshying thermostat (T1) will close This will energize relay (R2) [58] time delay (TD2) [57] and the optional time delay (TD4) [59] If all the safety controls and switches are closed (see Safety Control section for more details) the control circuit for Compressor No2 will energize allowing the compressor to start Relay (R6) [3D] will energize allowshying the liquid line solenoid valve (SOL2) [331] to energize Relay (R6) [3D]will also interlock the water pump starters and the safety controls the same as Compressor No 1 circuit

The fan contactor (C14) [33] will close supplying power to the line side of the fan cycling pressure controls (See Power Wiring Diagram)

Time delay (TD2) will provide a 30 second jumper around the low pressure control (LP2) [30] and will energize the full unload solenoid (UL 3-2) [34] for 30 seconds then energize relay (R4) [35]

Upon energizing relay (R4) [35] the crankcase heater (CCH2) [8] is de-energized and the NO contacts of relay (R4) [46 49) are closed allowing the thermostat (T1) to energize the load solenoid (UL2-1) [46] and the unload solenoid (UL2-2) [49] upon demand

6

SHUTDOWN SEQUENCE

Stage 2 Shutdown Stage 1 Shutdown

After both compressors have unloaded fully and the leaving water temperature is still lower than the setpoint the second step of the thermostat (T1) will open and de-energize relay (R2) [58] providing an approximate five minute time delay again integral with the microshyprocessor has expired subsequent to the start of Compressor No2 This will close the liquid line solenoid (SOL2) [33] and turn off Comshypressor No2 Compressor No 1 will load and unload as required Compressor No2 will not be able to restart for five minutes due to integral time delays

SAFETY CONTROLS

The unit is protected by the following safety controls

1 High Pressure (HP) 2 Low Pressure (LP) (automatic reset) 3 High Discharge Temperature (OTS) 4 Compressor Solid State Module (CSTM) 5 Low Water Temperature (T2) 6 Low Ambient Thermostat (LAT) 7 Compressor Starter Overloads (OLH) (optional) 8 Phase Loss Monitor (PLM) 9 Control Circuit Breaker (CB1)

If any of these devices should open due to abnormal conditions the compressor(s) will automatically stop All controls must be manually reset except low ambient thermostat (LAT) and phase loss monitor (PLM) The individual compressor safeties (HP LP OTS and CSTM) contacts are found on Lines 20 (CTT1) or Line 30 (CTT1) The other safeties listed above are discussed in the preliminary sequence section

If the leaving water temperature is still lower than the setpoint the first step of the thermostat (T1) will open and de-energize relay(RI) [61]This will close the liquid line solenoid (SOL 1) [23] and turn off Compressor NO1 as long as it has run for approximately three minutes Compresshysor NO1 will not be able to restart for five minutes

FIELD CONTROL WIRING

In addition to 3 phase power (and optional 115 volt control) wiring described above the following control interlock wiring is recommended The as built control schematic provided with the unit provides detailed information Typical control schematics are as shown on pages 8-15

1) Alarm Circuit -Terminals 6-13 (2 per compressor circuit) can be used to trigger remote failure lights or alarm bells in the event of a refrigeration failure

2) Time Clock - All unit on-off control should be done through terminals 15 and 16 An open contact shuts down the unit Time clock night shut down and energy management shut down should all be done from these terminals and contacts should be applied in series

3) Flow Switch - The flow switch contacts should be installed between terminals 15 and 16 and be in series with time clock contacts

4) Chilled Water Pump - The control of the chilled water pump must be worked out by the system designer It is necessary for the pump to be on during any compressor operation and terminals 17 and 18 should be used to energize the pump starter However it is likely that the pump should remain on throughout all occupied operation or even at night for freeze protection Terminals 17 and 18 should not be the sole means of controlling pump operation

STARmiddotDELTA STARTING OPEN TRANSITION (OPTIONAL)

Typical For All Compressors On initial call for cooling staging relay (R1) holding coil will energize The (R1) contacts 7-4 close energizing star contactor (S1) and the five second transition timer (TD5) Transition contactor (S1) power contacts close tying the center legs of the compressor motor windings together into Star (WYE) configuration At the same time (S1) NC (Normally Closed) auxiliary contacts open preventing (C2) from closing (S1) NO (Normally Open) auxiliary contacts then close energizing contactor (C1) The (C1) power contacts close applying power to the

compressor winding (C1) NO (Normally Open) auxiliary contacts close locking (C1) in the energized position The compressor operates in the Star mode until (TD5) transition timer times out (five seconds) at which time contacts NC open and de-energize (S1) Star contactor (S1) NC auxiliary contacts close (TD5) timer NO contacts close energizing compressor contactor (C2) power contacts close thereby completing the Delta wiring configuration Compressor contactor (C2) NC auxiliary contacts open preventing (S1) star contactor from energizing until the next starting sequence

7

--

exgt

LE

GE

ND

m

rrbullbull

saN

OI

IlIG

CI-

Z

CO

HT

AC

TQ

ftmiddot (

0

[5

10

1t5

el

) C

ON

TA

ClO

middot A

NS

(C

UlT

middot pound

AM

III

bull C

ON

TO

L

(C

UlT

C

UtC

UIT

Ulaquo

III

H

IAT

EIt

I C

HllL

rU

lU

[AT

III

CU

Ne(

ASE

H

un

co

U

OIl

ll

SOL

ID

TA

U

MO

OU

Lt

H

US

UII

lI[

con

RO

L

LOW

Abullbull

IN

T

[

twO

fI

lO

W

nul

tt C

ON

TIIlI

OL

OIL

TU

II

r

UIIl

I(

SA

HA

S[

0

1$

M

ON

t T

O

lllE

LA

Tmiddot

tTA

GIH

O

1t[

LU

-U

CIT

Y ~OL

bull

CI

l

tC5

I H

el

C

Ubullbull

e

lHI

CC

HI

esr

P

I L

UI

VI

enst

P

LU

11

0)

(L

AY

middot tN

Uft

LO

CK

(

L[N

OIO

middot L

lOU

IO L

INI

SWIT

CN

CO

W

UD

C

C

UIT

S

SWIT

CH

ST

EN

fH(

MO

ST

AT

middot S

[OU

[Ne

EIt

TH

UM

OS

Tn

-L

OW

n

llI

IUU

[

TtIt

WIN

AL

10amp

1110

cu

no

wE

It

UN

I J

SO

LI

w

10

Tl T[l

Il

S

Tl

Ufl

Ul

10

0

-

CT

OII

I

WIl

WO

T

lM[

HU

T c

alli

CO

NTbull

bull L

OW

Ipound

n

LO

CC 0

1

TO

T

IllS

I

ond

tlt

UN

Lo

ao

t

OL

(NO

ID bull

(O

M

no

ll

Ul

ImiddotZ

~(

tU

IIL

T

IIS

VI

O

I

_

-~

OIO

HA

l

ell

C

UtC

Ul

[

amp1

(( -

(cri

VE

lli K

uru

en

C

IAC

Uff

A

UK

(jII

f bull

CO

[

I(

C(

OV

TL

lT

CI

I (O

NU

OL

If

Jll

AIr

IS

HO

UA

W

(fIA

S

LL

Tl

LO

AO

LI

T

(III

WO

STA

T

0

middot

5

O

(III

LO

AO

fU

UIS

LImiddot

H

OT

L

IGH

TS

H

IUC

IIY

[1II

H

[AU

IIIS

~ jllf

M1

III[

Cll

[

H

[U

t

US

UII

ll[

CO

NT

IIO

LS

~tCt

JVII

l N

(AU

III

14

(0

1

T

O)

TO

wI

DtL

AY

amp L

OW

U

tu

LO

CK

ou

r rt

(

O(L

IN

SlT

IO

C

OH

TA

(TO

Il

(O~USO

C

OH

O

lll

bull iT

A

OlL

C

Ol

CO

MV

[Nf

epound

o

un

n

Ctft

CU

lT I

DE

TA

IL

A

SlA

M

DE

LTA

ST

AR

T

O -~

OA

~ 5~U

Z

OI

Cl

U

I 14

(I

amp

~

NC

f

cl

AU

I

51

ZtA

LU

TOO C

21

NO

~~

bullbull

N

WHT

I---

I

l I J

II

A

CN

lCU

lT

If

OOHAI~

l

~i1

WH

It[

-

OI

ON

AL

r---

----

---

-I

Q

WT

I lt

raquo

I I L

JI

bull bull

I I

0

II

-

lJ

_ Ij

lf

I

cal

II

iOO

w

shy

) C

it

~

WTI~AL

r --------------------------------

Iamp

I

_l

[0

0

I

OO

CM

lL

00

LO

II

cu

U

II

bullL

~J

It

_U

I

TH

u

I

HT

I~

r-~~

~ --

-I=

=~==

=~I

11

2

N

~~~

~--

----

----

=~

I

-lt

l

= I

en

co

o J

rO~

2

~L

----------

-

-oS

f

I

r--shy

J

on

T

O)

vI

Q~~A

J T

Ot

L-

ll~_

f

1

II

CU

H ~

~OI

L1

-i

r---

----

-

~

10

rc

I

bullbull

lf

OIS

ti

l W

I H

Z

01

11

1

-J

o

u

L

shy

0bull

-

0 T

1

111

A -

bull 0

[0

HT

I

ll II

rgt ---

-ij

---

ITl~ll

t

1amp

I

1t

D

MIN

I[D

11

~

ill HTAILmiddot~

O

LM

I 01

1

OL

HJ

III0

1l~

tM

Ow

N

CI

amp

tt

I w

lO

OIO

HL

---

__

J

O ~

~Ll

~

tB1

It

CI)

n

IS

-1

M

k

V

Io

Jmiddot

r---

1

we

14

-4

I

Mill

I

CO

MPR

ESS

OR

C

IRC

UIT

I

Til

bull ~

r-

so li

e II

It

S

tON

L

N

O

fll

II

If

II

~

s~

o

oc

gt

(I)

r in

n

100

00U

lz

--I

~o

e

0

r ce

cn

shy0

0

Z

Ggt

bullbull bullbull bullbull bullbull bullbull bullbull

r~T~-

ICt

MQ

Teuro

CO

MT

It01

I T

IM C

lot

ll

~---

Cl

ll

(O

41

(

flO

W

5Wlf

CH

~

I

Olt

CO

NT

AC

TO

C

OIL

S C

I-I

bull C

tS

AN

D S

t sn

N

OW

IIt

Dll

QU

0

1 C

OM

UC

TI

I

111

114

0

(

U

II

NO

f T

O I

(

C

uNO

IO

ON

UtI

se

CO

HO

UI

li

D(

1

A

ND

1

n

WP

(IU

ult

l S

(NIC

tf1

I

LO

CU

ID

1M bullbullU

O

UT

UT

r-

----

shybullbull

0

11

UO

V

HA

Il

LO

IS

raquoON

TO

S

TE

lurN

AU

bull

AN

D

0111

IIC

O(

I A

ND

A

U(

Cfl

YpoundL

Y

So

C

rt

TO

0

0 M

AN

UA

L a

ll H

TO

tNT

AN

D

~10l

IA

NO

M

TII

UC

TtO

NS

II

rCO

tNO

m

IMIT

AL

CO

H

laquo

0

U

TI

I It

4

Ishy

C

OW

III

ISO

R

MO

DU

LES

dC

NO

MmiddotA

U

VA

TC

I

D

U

1111

WIL

L A

LSO

LO

C_ O

UT

(

let

Umiddot

I C

AL

L

WH

IM

IAI

TY

flit

TH

[I(

CO

Nmiddot

I

OL

I CA

Jrf I

I II

EM

T

IT T

Uft

I1

tW

ITC

H bullbull

0

VO

NIN

IL

f PO

C

Obullbull

bull

I w

UII

II

I

C

IL

Llf

i I

ITA

f[1

II

ItV

N

IWIT

ti r

raquo7

~Slt~1

~~~~( 1~~~~tlDOO

CO

N

CT

O

WU

UH

O 0f

II C

OW

bullbullbullbull

~~1

II

bull

LL

TI

lIT

AT

0

N

O 1

0 O

CA

TID

1

1 I

I IIl

ETU

IIPt

W4T

P

LU

WHE

N u

TI

It N

OT

lU

u

rD

ttl

III I

ICO

Ma-

aU

0 11

nM

H

u

l

UN

I()1

II M

UST

HA

V(

SH

llL

DID

C

AU

I

LO

Me

T

II

no O

R

ItUM

WT

M

ItO

WI

L

IAH

to u

ri N

T I

T H

-

ITbullbull

O

N

ft

0

-

011

II~T

K

ITI

GU

ION

An

ON

S

o H

O-

ON

G C

OI

-W

it

11

N(

NO

6 N

c

CO

NU

ClI

W

If

lIN

( N

O

o N

0

CO

NT

AC

TS

WIt

K

liN

t N

O

6 N

OT

t I

TH

L

Nt

NO

Y S

UI

-I

IS

5_

1

~

~

no

~ I

I I_

VLOA

Or- I

I ~~

vumiddot

S1 so

CO

Hit

so

0

amp

g A

SI ~

I

1

7100-

I -I

I 01

10

OH

0

10

f T

AN

I V

I

] CM

NG

( av

rlt

10

0 O

K__

ST

AG

(

COD

lJ-

L7

00

~It

A

lIT

00]

VL

I fi

ll

14

1

10A

O

f

_ III

rC

OH

O

In o

y

00bull

00

10 ~

0

10

CO

Ol

C

bull

] 4

U

rr

COL~

bull Jo

un

J

W bull

C~P

OJ [

ou

-t

urO

NT

01

CO

l0

1

N

Omiddot

~ ]

(jCO~_

0

)

un

ll

n ~

T

I 11

I1

III _~

n

~

amp

7

10

II

01

u II 17

II

0

II

01

IS

-I

-lt

sE

o

0 c

raquo

CD

r iii

0

~O

U

lZ

+-1

~

tI

t

0

r QE

CIJ

-c

tl

Z

Ggt

lt0

bullbull bullbull

bullbull

bullbullbullbull

~

o

tUN

oa

lllO

_--

-

shyC

t-4

CII

C

cn

bull

tlN

I

CC

HImiddot

t

csnu

middota

--1

LA

T

loP

a

01

11

-1

111

111

IIImiddota

It

4

IOL

IS

IW

Imiddot

I

I T

I n flbull

bull

TO

middot I

st

U

LImiddot

a

Oft

lo

tL

LtG

EN

D

CO

NlA

CT

IM ~

CO

lllf

lllt

UtO

JII

CO

NT

AC

TO

CII

CU

fT

IIIC

AICC

III

CO

NTJ

IIOL

CIC

UIT

U

NImiddot

HU

TI

eNU

LlII

I

Il

I

AU

It

C

NlaquoC

AU

NC

An

C

O

UIO

10

LIO

T

AU

N

t U

SU

I C

O T

OO

L LO

W

eT

fM

llltM

OT

AT

L

OW

Hl

III

UII

I C

Oft

TJl

OL

OU

n

ru

ulltl

A

nT

T

HA

-

0bullbull M

OH

IfOIt

fl

lLA

Y I

AO

INI

MU

C

AN

cn

CO

fTltO

Ibull

ItIL

A

INT

ILO

CIC

OL

EN

OtD

Ll

OU

ID L

INt

Cc

ulT

MOO

ULIE

C

NIC

CA

SE

ItS

C

(

OM

II

IOII

(lI

IieLf

W

I eM

-

UIE

R

TH

III

OIT

6Tmiddot S

lOU

lC

U

MC

ot

LOW

TlM

e

U1

T

lER

bullbull

L l

OA

JIIO

middotCU

lTo

tJ

II W

UU

Nt

TI

M

AL

IO

D

oC

0It

1 U

IIN

t T

IMe

OC

LU

middotCA

II C

ONT

a

LOW

IU

t L

OCK

OUT

NPD

WIU

UN

LOA

Olil

t 1

0L

(NO

I0

C

O

III

OIl

lI

cn

CIJ

tCU

IT

UII

lEIt

ft

EC

poundIV

E H

IAI

C

Ol

(C

UIT

1I

IUIIl

I1II

CO

NY

(NIE

NC

E

OU

TU

T

CU

I C

ON

nlo

0

1

AN

$ M

ill1

1

HO

YIll

MU

II

lLT

I l

OA

O

LlI

lIIT

T

H(

O

ITA

T

OL

O

VC

LO

AO

MIA

nl

L1

lI1

~HAII

LO

IS

MO

NIT

O

L

Imiddot J

~fOT

L

IOH

TS

1

1

IC

IIV

E

HE

UE

ItM

lIC

tmiddotl

rC

IIV

E

MU

TlI

t l

tIIS

UIl

l(

CO

NT

ItO

LI

T

lmiddot1

C

CC

lvllt

N

EA

fllt

T

lW

OS

TA

lI

TO

Jmiddot 4

T

INe

H

LA

Y

LOW

In

vlt

l LO

C

OU

T

1O

t-1

ft

lll

D

UA

Tmiddot

TA

SIT

ION

C

ON

TAC

TO

Ill

$middot

1

CO

C

O

(

lIO

C

ON

TA

CT

O

T

A

Dn

u

CO

WC

tllltN

CI

ount

T

DE1AIL~

ST

AR

D

EL

TA

S

TA

RT

r

2

~f

10

t10

II

amp

II

11

II

)

1IllI

1IU

--shy

OW

E

IV

-

utv

lO

f

I I Ibull

A

UR

C

IlltC

UIT

C

IRC

UIT

ALA

NlC

UfT

C

lflC

UIT

I I

I

~li

IT

I

Ot

ON

AL

il------~---l

-

tL

J --

--

C

it

prIlgjf~

II

ell

I

I

IfB

I

t

---------~~-------

__

~

L_ -

7 -

-r--

et

r

I

II10

-I

CII

-lt

PL

1amp

I I

II b

I

L _

__

J

II 3

2I

oo

II

Qraquo

~

IS

lI

(

)r-

t-_

_ o

J_

_

O

TIO

L

I ~~

--~-

I

I CD

oL

__

__

__

__

__

CO

I- f

_

JI I

t degz

OI

OIl

lAL

r-

---

IS

r

-l

0

I

I

+10$

IL

KS

I T

e

0 Lr

I J

II

T

ITI

lOL

l 1

40

bull (C

IS)

TO

bullbull

lD

A-

~ -

r--

-~l

)~II

I

~G

__

_~L_J

0

O

HA

I

~ -

-Ill

-

---

-10-

--

~E

II

cn

-C~

II

Z

0

G)

Il

l~

r- I W

lllltO

WH

IN

JU

L1

l0

I I

I

OL

M

OL

MI

OL

I ~ro

o

jo

o

Jt

JI

L

OT

10N

AI

II

0

(01

0 CO

MPR

ESS

OR

C

IRC

UIT

~

27

III

gt

0

IIA

IO

amp1

)amp

1

1

II

~

I rA

I

TA~

D

ELTA

STA~T

CONP~E~)

CU

lT 2

~

f

bull ]

A

U

4 ]I

IUft

middotJI

Mon

tUPlOI

NT

lOA

Ot-

-O

I

01

0

]

(N

GI

011

1

00

CT

AN

)

40

00

HN

a

_N

I

J00

I -

It IC

y

TO

I

I I

I

~

oiiO

NA

t

I bull bull

wi

i

lOa

r~TT~-

I M

OT

I C

ON

sr

0

llItt

(

co

ce

OZ

UK

1

11

_JO

I I

)--11

--

- ---

-

IJI

LD

~

I

A

CK

lS

C

UK

I

IL

UO

A

TO

O

WH

IT

1

L

OW

SW

ITC

HJl

AL

D

00

IZ

I

f

1It-

-

rl__ u-

poundL

J f

aT

ION

AL

TI

WfI

OO

f

~

ff

I

Dill

C

ON

TAC

TOIlI

C

OtL

S (1

middot4

(IS

middot14

A

ND

II-

I

01

1In

N

O

Wl

0

51

11

~

CO

NT

AC

TS

I

fH

IO

Uti

IS

N

OT

TO

IE

al

llauN

DIO

O

N H

I Sr

CO

NO

AIl

lf

StO

l

f

I

TI

AN

D

TI

TI

U

I

IIN

OII

t

0middot

f1L

OC

AT

IO

IN n

lll

GU

lUT

r-

----

shy~

(I

G

lIt

no

v

HA

I

LO

SS M

ON

IO

nf

1Na

bull

AN

D

ON

rc

I(

CO

M(

f A

IrfD

I

lItU

rC

TIY

(U

00

-

5

E

[CO

OIO

lItc

rlll

TO

0

0

AN

UA

L

t

OIN

T A

Na

f

oo

IlU

COfrt

TO

I U

ND

IN

Stt

UC

TIO

trl

r

co

rNH

D

01 11

raquoIN

ITIA

L

CO

NT

lIIiO

L

fII

I0 I

UT

IS

a

jshy

orshy

10bull

CO

M1

II1t1

Ol

MO

GU

LI

I N(

tN-a

UT

OM

AT

lC

I 1I

lfla

n

flS

bullbull

11

A

LSO

ampO

eMmiddotO

UT

luer

llt

middot I

no

C

AL

Y

WH

IM A

N

IUIT

T T

IIII

P

T

MU

I C

ON

egoo

IT

flO

LI

CA

l

ItU

I1 I

T

TU

NIN

G W

ITC

M

0

~r=

0 I

lIO

Wlf

lIT

A

L

fOtt

CO

lI

tbullbull

w

ITC

H_

I

on

WO

Nlf

lIT

JII

IL

POllt

COW

bull

I In

degz

r+-i

~~

t

u ~o

1 ~rI~~

~~

~~TtIc~~I~D

1

SW

lTC

HI ~

C

OIfT

AC

TcU

t W

lItN

t C

OM

bullbull

H

To

lIL

b

l

0t~~1

0

1

CO

tfC

TO

H

I

lIt

C

ltbull

IIT

C

~r-

bull

WM

IH

-

2

N

OT

1V

l

rD

wllI

I[ to

IlIC

OM

n

I W

I

It

I

fjC

Ofl

P

tE

CJ)shy

t W

IN L

UI N

OT

SU

PL

ID

W

IIIIC

O

J

lleo

W

ti

l

LU

KT

IT

10- A

ND

10ft

II

v

C~

LO

CA

TU

I II

1t

11V

MI

_T

at

I

z10

I

T

lNH

A

TU

RC

S

lNS

OIt

MU

tT

ve

IL

OID

C

IL

C

()

11II

L

AT

I

AT

10

_

A

U

IIIT

I0middot

PCA

LOW M

I_ lO

TI

I bullbull

n

II

DES

IGN

ATI

ON

S

II

CO

NT

IlID

t I

NO

-o

MO

LD

INfl

C

OIL

It L

tNI

NO

0

Q

N

C

CO

NU

ClI

W

ITH

UN

I N

O

01]

0 co

O

f

11

~

I

ILK

n

e

s IA

UL

It

ibull

o O

CO

NTA

CTS

w

nw L

INI

NO

01

fA

0

~

fItO

TI

LI

I N

O

v

A

II

~ ~ bull i middots

~

~~ - ~

~

1- I J I J I I I I I I I I I I I I I I L __ J

I

a bull bull a bull bull

I I I

_J

r------~

=~I = ~ ~ bull ~ I I

~

as coe ruq SV~ siapow ~NI~IM lO~lN03lV3ldAl

i 4

_

a

~FirI1 u~III - I I

~ 1I

00000 -

I=II~I~~~~raquoIIIItIII~ampI~

as ooz nJ4l sv ~ siapow ~NI~IM lO~lNOgt TVgtldAl

bullbull bullbull

bullbull

~

jgt

lpoundIt

ND

II

co

----

----

----

----

----

----

----

----

-

r-~-middot--=-~~

~

bull a

~

at~04

5

---

~1I

A

~n

bullbullmiddot-shy

wo

_-

bull

lIt

C-

I C

Cf

aC

TO

Ic

ow

n

CC

eM

ca

~C

M

OD

IAI

CI

T-

CO

IITA

CT

oa

bullbull

CMCU

rT I

ItIM

IA

co-l

to

c-c

VIT

C

I

rr

c

AfE

bull r~----Ef1

POW

I

III

IQ

W

Q

tIL

UT

I1I

U__~

J

COt

I

LD

W M

lMtr

f nc

IIO

ff

0

N

LO

W

C

OIIT

INM

I I

CO

M

US

ON

C

NC

UIT

II

II

-~

_T

shy

C

O

NU

SO

II

CIN

CU

IT Z

II

D[TA~

-

ST

AN

D(~TA

IT

AII

T

0

u III

r

amp

II

-~

If

10

MA

MI

eN

talI

Tco_

~

STA

N D[~TA

ST

AII

T

~

CIS

-I

LA

~ 1-4

nmiddot

00

-

-II

1t1S

-1 aw

o fI

fl

U- I -~ Ci

Pi=

i

t

shy

~

iii

i

iii=

ii

-

-shyiii

ClL

n

TU

U

LOt

e

bull It

lLA

Yn

C

AM

Im

CIII

IID

L bull

CU

_C

Abull

fl

lUY

_f

tMO

ea

UY

middotIO

CI

lO

Ll

t

NIU

_L

N

CO

WU

UO

ItC

U

llT

l bullbull 0

1middot

lit

TMC

MI0

8TA

T tc

_lt

CIl

it

11

II

_

middotLO

W

TII

IfN

T

UIlI

C

nll

-

D-C

UlT

QIIU

tW

n-T

PII

IU

LIO

MI-

AC

TC

Ntf

Wi

MI

II

II

tY

middotCM

OO

C

LOW

HIe U

(O

Uf

lIl_

L

OA

M

1OtI

1tO

lD

CO

OA

CM

UtT

1M

C

lIY

Dl

NC

Afi

ll ea

-tU

lT 1

ItUbullbull

lI

oo

ww

lItt

lffc

e O

Un

n

cT

IlG

I

Ie-

~U

IIIC

CIV

P

1T

1lt

C

bullbull

Off

AT

tw

ebullbull

ampOW

IC

IUT

~-

4ti

iT

~

co

ww

O

UfU

T

DITA~

A

ITA

A

OEL

TA

IT

AJI

IT

co

rn~

e

I

1amp

ItmiddotI

~ bull

I I

I

I r

~

bull Iamp

II

I ~

I-

oJ

II I

IrIf

I I I I

s~

o

-I I

ltDc

() raquo

L 10

V

i

()

~O

to

U

lZr0

t2

llJ

IL

C6

J=

_J

~-1

f

II

c 0

II

N

ge

cno

c-

II

Z

Ggt

If IO

IC

IIY

II

IIR

III

IJt

T H

llII

A

Il C

Olaquof

U

TMIbull

~LDM

fI

lAR

PM

Iamp L

Oll

lTV

ii

iLii

Uii

ii

~

U3

I iL

iii=

i

Uii

u

i

O

(no)

T

bull II

1

IOA~

bullr

~ I

[gtO(]O

~ i I Ii i 2 ~ ~ ~ i a bull il 2 ~

iiibullbullbull

~ I ~ I I I ~~ =l ~ iI I ~ I I I It I 1111 amp ~~

as ooz nJ4l SP~ SlapoUII ~NI~IM 10U1NOl lVlldAl

-------

---

TYPICAL POWER WIRING Models 45 thru 70 SC

----

rYl31I01 I

-Ii --ti-

_ I ~_-

~ lniJ -

LIIbullbullbullbull PC _ amp-II _--- ~

TYPICAL POWER WIRING Models 90 thru 135 SC

- --- _ Tt

~rfh c~

tP ~

_III ~

I r-- ~- IIlJ

bull - MIl Mf __ bull Ie_~--~ _shy- shy16

---

----------

TYPICAL POWER WIRING Models 145 thru 200 SC

_ --1a1 IIUrI

middotrFti~v_ bull I

i~i ~~ TaII IIOMLI ~tN T 100 WTIOII 011 lilOOCL a

~ t1

tI bullbullbull

L

i I r-~

I r

~ ~ ~ III

2 ~ ~ ~l

- ~IlD I hJOHr eo teO acshyt CmiddotClM ~ CIKUr1 --

TYPICAL POWER WIRING Models 215 thru 265 SC

ItUU 1D Wll1U1I fIa -rMI

rt-h I -au 11 1_ i r~ rt-f

-i rn f1 ft fi i- llil bullbull c~ I bull c =

~~~ ~i~-~

~~m

~~~CI1 R~~ ~ ~~ ~llAi4I

luv~ bull ~uf LL~~-

~Mfl l~t IrMiA

a I III nII I bull it d

~-t--J I Lll-l~j ~nL4111 WlJj== lit-

I bullbullbull I

UGEND

~

~l OJ

- c~

~~~---

~)~middotI

I

L _~~~ L _I__~_J I ~ (11_1 ~ H~ CUlTMIt tffC_) Ll N

-r_ 0 1ItCIIIl0AI lllQUlllCo as -0- bull bullbull fI PC 110 lNJCllII a Olil1100pound1 II 111 el 1101 ItCOU_ 011 IIOOIL140

I 011 CI-( H[ (0110 (fMCun ubullbull --- l(lD IMbullbull Ntlf 110 e414-7

--CTOttbullbull

2

17

ELECTRICAL DATA Model Volts Type COMPRESSOR FAN MOTORS MIN CIRCUIT RECOMMENDED MAXIMUM ACWC 60 Hz of Qty RLA Starting FLA LRA AMPACITY WIRESIZE FUSESIZE

SC 3 Ph Start HP Ea Curro Ea Ea Ea Circ1 Circ2 Circ1 Circ2 Circ1 eire 2

208230 XL 1788 1040 (4) 70 (4) 380 252 - 250 - 400 -45 208230 YO (1) 50 1788 347 (4) 70 (4) 380 252 - 250 - 400 -

460 XL 737 422 (4) 35 (4) 190 106 - 2 - 175 -460 YO 737 141 (4) 35 (4) 190 106 - 2 - 175 -

208230 XL 2051 1228 (4) 70 (4) 380 284 - 300 - 450 -55 208230 YO (1) 60 2051 409 (4) 70 (4) 380 284 - 300 - 450 -

460 XL 904 485 (4) 35 (4) 190 127 - 1 - 200 -460 YO 904 162 (4) 35 (4) 190 127 - 1 - 200 -

208230 XL 2083 1415 (6) 70 (6) 380 302 350 500 -70 208230 YO (1) 75 2083 472 (6) 70 (6) 380 302 350 500 -

460 XL 974 539 (6) 35 (6) 190 143 0 225 -460 YO 974 180 (6) 35 (6 190 143 0 225 -208 XL 1788 1040 (6) 70 (6) 380 266 224 300 0000 400 400 208 YO 1788 347 (6) 70 (6) 380 266 224 300 0000 400

90 230 XL (2) 50 1788 1040 (6) 70 (6) 380 266 224 400 I300 0000 400 400 230 YO 1788 347 (6) 70 (6) 380 266 224 300 0000 400 400 460 XL 737 422 (6) 35 (6) 190 187 - 000 - 250 460 YO 737 141 (6) 35 (6) 190 187 - =1000 - 250 208 XL 2051 1228 (8) 70 (8) 380 312 256 400 300 250 208 YO 2051 409 (8) 70 (8) 380 312 256 400 300 500

110 230 XL (2) 60 2051 1228 (8) 70 (8) 380 312 256 g I350 300 SOO 450 230 YO 2051 409 (8) 70 (8) 380 312 256 350 300 500 450 460 XL 914 485 (8) 35 (8) 190 231 - 0000 - 300 460 YO 904 162 (8) 35 (8) 190 231 - 0000 - 300 -

208 XL (1) 60 2051 1228 (8) 70 (8) 380 312 260 400 300 500 450(1) 75 2083 1415

208 YO (1) 60 2051 409 (8) 70 (8) 380 312 260 400 300 500 450(1) 75 2083 472

230 XL (1) 60 2051 1228 (8) 70 (8) 380 312 260 350 300 500 450(1) 75 2083 165125

230 YO (1) 60 2051 409 (8) 70 (8) 380 02 260 350 300 500 450 (1) 75 2083 472

460 XL (1) 60 904 485 (8) 35 (8) 190 240 - 250 - 300 -(1 75 974 539

460 YO (1) 60 904 162 (8) 35 (8) 190 240 - 250 - 300 -(1) 75 974 180

208 XL 2083 1415 (8) 70 (8) 380 316 260 400 300 500 450 208 YO 2083 472 (8) 70 (8) 380 316 260 400 300 500 450

135 230 XL (2) 75 2083 1415 (8) 70 (8) 380 316 260 400 300 500 450 I 230 YO 2083 472 (8) 70 (8) 380 316 260 400 300 500 450

460 XL 974 539 (8) 35 (8) 190 247 - 250 - 300 -460 YO 974 180 (8i 35 (8) 190 247 - 250 - 300 -

208 XL (2) SO 1788 1040 (10) 70 (10) 380 326 402 400 0000 500 500(1) 60 2051 1228

208 YO (2) 50 1788 347 (10) 70 (10) 380 326 402 400 0000 500 500(1 60 2051 409

230 XL (2) 50 1788 1040 (10) 70 (10) 380 326 402 400 0000 500 500 145 (1) 60 2011 1228

230 YO (2) 50 1788 347 (10) 70 (10) 380 326 402 400 0000 500 500(1) 60 2051 409

460 XL (2) 50 737 422 (10) 35 (10) 190 295 - 350 350 --(1) 60 904 485

460 YO (2) SO 731 141 10 (35) (10)190 295 - 350 350- -(1)60 904 162

208 XL 2051 1228 (10) 70 (10) 380 326 462 400 (2)250 500 600 208 YO 2051 409 (10) 70 (10) 380 326 462 400 (2)250 500 600

160 230 XL (3) 60 2051 1228 (10) 70 (10) 380 326 462 400 (2)250 500 230 YO 2051 409 (10) 70 (10) 380 326 462 600400 (2)250 500 600 460 XL 904 485 (10) 35 (10) 190 329 - 400 - 400 460 YO 904 167 (10) 35 (10) 190 329 - 400 - 400 - I

NOTES 1 XL Across the LineYOStarDelta 2 RLA Rated LoadAmps(ratedin accordance withARI Standard 590) LRA LockedRotorAmps 3 Wire Size Amps equal125of the ratedloadampsfor the largestmotorin thecircuitplus100of the ratedloadampsfor all othermotorsin the circuit per

NEC 4 Wire size based on copperconductorswith75C insulation perNECTable310-16 Terminal block lugs are sizedaccordingly Use of oversize wiringmay

not lit in terminal blocks 5 Maximumfuse size is basedon 175to 225of the ratedloadampsfor the largestmotorin the circuitplus 100of the rated loadampsfora othermotors

in the circuit per NEC VOLTAGE TOLERANCES 208V-230V min 187VMax 253V

480V Min414V Max506V

I

18

ELECTRICAL DATA Volts Type COMPRESSORModel FAN MOTORS MINCIRCUIT RECOMMENDED MAXIMUM 60 Hz of Oty RLA Starting FLAACWC LRA AMPACITY WIRESIZE FUSE SIZE 3 Ph Start Curro EaSC HP Ea Ea Ea Cire1 Cire2 Cire1 Cire2 Cire1 Cire2 208 XL 2051(1) 60 1228 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 1415 208 YO (1) 60 2051 409 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 472 230 XL (1) 60 2051 1228 (12)70 (12) 380 341 469 500 (2) 250 500 600

12 75 2083 1415185 230 YO (1) 60 2051 409 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 472 460 XL 485 (12) 35 (1) 60 904 (12) 190 352 500 400- - -

(2) 75 974 539 460 YO (1) 60 904 162 (12) 5(12)19 352 500 400- - -

(2) 75 974 180 208 XL 2083 1415 (12) 70 (12) 380 345 469 500 500(2) 250 600

472208 YO 2083 (12) 70 345(12) 380 469 500 (2) 250 500 600 230 XL (3) 75 2083 1415 (12) 70 345(12) 380 469 500 (2) 250 500 600200 230 YO 2083 472 (12) 70 (12) 190 345 469 500 500(2) 250 600 460 XL 539974 (12) 35 (12) 190 359 - 450500 - -

180 1(12) 35 460 YO 974 (12) 190 359 450 -500- -2051 1228208 XL (12) 70 504(12) 380 504 (2) 250 (2) 250 700 700

208 YO 2051 409 (12) 70 (12) 380 504 504 (2) 250 700(2) 250 700 (4) 60 2051 1228 (12) 70 230 XL (12) 380 504 504 (2) 250 (2) 250 700 700215

YO 2051 409230 (12) 70 (12) 380 504 504 (2) 250 (2) 250 700 700 460 904 485 (12) 35 XL (12) 190 225 225 0000 0000 300 300

(12) 35 460 YO 904 162 (12) 190 300225 225 0000 0000 300 2051 1228208 XL (2) 60 (14) 70 (14) 380 504 525 (2250 700 700(2)300

(2) 75 2083 1415 2051 409 (14) 70 700 700208 YO (2) 60 (14) 380 504 525 (2) 250 (2)300

(2) 75 2083 472240 700XL (2) 60 2051 1228 (14) 70 (14) 380 504 525 (2)250 (2)300 700230

(2) 75 2083 1415 2011230 YO (2) 60 409 (14) 70 (14) 380 504 525 (2) 250 (2)300 700 700

(2) 75 2083 472 300460 XL (2) 60 904 485 (14) 35 (14) 190 225 248 0000 250 300

12 75 974 539 904 162 250 300 300460 YO (2) 60 (14) 35 (14) 190 225 248 410

(2) 75 974 180 2083 1415 (2)300 700 700XL (16) 70 (16) 380 525 525 (2)300208 2083 1415 (2)300 700 700208 YO (16) 70 525 525 (2)300(16) 380

700 7002083 1415 (16) 70 (2300230 XL (16) 380 525 525 (2300 700 700(2300(4) 75 2083 472 (16) 70 (16) 380 525 525 (2300230 XL265

300250 300974 539 (16) 35 248 248 250XL (16) 380 460 (16) 35 300 300974 (16 380 248 250 250YO 539 248460

NOTES 1 XL Across the Line YO Star Delta 2 RLA Rated Load Amps (rated in accordance with ARI Standard 590) LRA Locked Rotor Amps 3 Wire Size Amps equal 125 of the rated load amps for the largest motor in the circuit plus 100 of the rated load amps for all other motors in the circuit per

NEC 4 Wire size based on copper conductors with 75degG insulation per NEG Table 310-16 Terminal block lugs are sized accordingly Use of oversize wiring may

not fit in terminal blocks 5 Maximum fuse size is based on 175 to 225 of the rated load amps for the largest motor in the circuit plus 100 of the rated load amps for a other motors

in the circuit per NEG VOLTAGE TOLERANCES 208V-230V min 187V Max 253V

480V Min414V Max506V

19

0

(Wd~) 3lV~ M011 ~31VM

006 009 00 OOt OOl OS L 00 L os 0 Ot

V D m (I) (I)

c D m c D o V

- m m -t o

~

~ m D-

aoao 3~nSS3~d ~3100~

APPLICATION DATA

POINT LOADING

ArMi I 1 5 1

ACWC 45 THRU 10 SC

COMPRESSOR CONDENSER SECTION SECTION

_ 2 4 bull 1

bull CA

J

Model Dimensions Size A B C D 45 91 - - -55 91 - - -70 145 - - -90 145 - - -110 60 40 160 -125 60 40 160 -135 60 40 160 -145 138 74 107 -160 13830 74 107 -185 138 129 107 -200 138 129 107 -215 106 82 106 80 240 106 82 134 107 265 133 110 134 107

1310

1310

~

1

1310

2

ACwe 110 THRU 200 Ie

COMPREIlOfl CONDENSER SECTION IECnoN

4 -

5Imiddot

ACWC 2t5 THRU 215 SC

Model Loadlnu (LBS) Size 1amp2 3amp4 5amp6 7amp8 9 amp10 45 585 765 550 - -55 705 810 635 - -70 660 890 700 - -90 1025 1500 1175 - -110 1195 635 1525 995 -125 1255 690 1835 1115 -135 1255 665 1880 1105 -145 1330 2380 2160 1450 -160 1330 2440 2280 1515 -185 1235 2575 2980 1360 -200 1275 2635 3020 1380 -215 1010 2270 2590 2240 840 240 1115 2550 2870 2715 1125 265 1380 2980 3515 2750 1175

11

II i middot 2 4 lIf 11 to L

21

TROUBLESHOOTING GUIDE

CHILLER UNIT WILL NOT START POSSIBLE CAUSE REMEDY 1 Power off 1 Check main disconnect switch

2 Main line open 2 Check main fuses

3 Incorrect wiring 3 Check the wiring diagram

4 Loose terminals 4 Tiqhten all terminals

5 Control circuit open 5 Check phase loss monitor flow switch circuit breakers temperature control low ambient thermostat low temperature thermostat remote switch etc

6 Time delay 6 Wait

COMPRESSOR HUMS BUT DOES NOT START

POSSIBLE CAUSE REMEDY

1 Low voltage 1a Check at service and unit for loss

b Consult power company

COMPRESSOR CUTS OUT ON LOW PRESSURE SAFETY CONTROL POSSIBLE CAUSE REMEDY 1 Refrigerant shortage 1 Check for leaks -- add refrigerant 2 Restriction in liquid line 2a Plugged strainer - dean or replace

b Liquid line valve partially closed - open valves fully c Expansion valve clogged or inoperative - clean or replace as

required d Solenoid valve partially open - clean or replace as required

3 Low water flow thru cooler 3 Check water flow thru cooler and correct as required

COMPRESSOR CYCLES ON HIGH PRESSURE CONTROL POSSIBLE CAUSE REMEDY 1 Compressor discharge valve partially closed 1 Open valve fully 2 Non-condensible gases in system 2 Operate condenser fans with compressors off If condenser

pressure exceeds saturated pressure corresponding to condenser entering air temperature then purge air from discharge line

3 Overcharge of R-22 3 Purge system while in operation until head pressure reaches a normal level

4 Dirty condenser 4 Clean the condenser 5 Compressor discharge check valve not operating properly 5 Replace if necessary 6 Fans not running 6 Check pressure control setting

CAUSES AND PREVENTION OF FREEZE-UP CAUSES PREVENTION 1 Improper charging 1 Charge per manufacturers recommendation

2 Improperly set safety time delay 2 Check the safety time delay low pressure control for proper setting at the beginning of each season

3 Improper chilled water circulation 3 Use an ample sized cleanable strainer in the chilled water circuit Make certain the strainer is clean to insure full flow and velocity of

chilled water It may sometimes be necessary to treat the water to prevent formation of deposits

4 Not draining for winter shutdown 4 When the system is shut down for the winter remove the drain

plugs and drain the cooler Blowout any remaining water with air

5 Improper pump shutdown 5 Make sure chiller barrel heater is working and flow switch is installed per wiring diagrams

6 Low ambient during air conditioning season 6 Make sure chiller barrel heater is working

NOTE If the ambient temperature is below 32degF freezing can be completely prevented by one of two methods

1 Drain all water from the equipment 2 Add antifreeze to the water

22

START-UP CHECK LIST

Unit Model No

Setting unit

Wiring

Piping

Alignment

Before Start-Up

After Start-Up

Yes No a Vibration isolator used

b Spring isolator adjusted for equal height c If rubber-in-shear isolators are used is unit leveled by shimming

a Power wiring complete

b Control wiring complete c Electric service adequate for load

d Power source voltage correct for motor(s) used

e Motor circuit has proper size fusetrons f System wired per diagram

g All lead connections tight h Wiring complies with local codes i Flow switch operation

a Piping complies with applicable codes b External piping independently supported c Chilled water lines insulated

a All belts adjusted and checked for tension b All pulleys checked and adjusted for proper pitch tightness and

alignment

a Open compressor discharge service valve b Open liquid valve(s) c Open suction and discharge valves to pressure gauges (if supplied) d Check rotation of all fan motors e Start auxiliary equipment (pumps fans etc) f Is crankcase heater operating Operate 24 hours prior to unit startup g Check the compressor oil level through the crankcase sight glass The oil

level should be to the top of the glass If the level is low add oil in accordance with the directions in the maintenance instruction

h Check all control settings as specified in Table 1 I Air purged from chilled water system

a Check high pressure control b Check oil temperature safety switch c Check and adjust low pressure or temperature freeze control d Check and adjust operating thermostat e Check and adjust low pressure operating control f Check and adjust expansion valve superheat g Check and adjust capacity control thermostat

23

OPERATING DATA CHILLER Voltage L-1 L-2 L-3 _ Pressure Gauge Readings 1 Suction psig 1 Discharge psig 2 Suction psig 2 Discharge _ psig 3 Suction psig 3 Discharge psig 4 Suction psig 4 Discharge _ psig High pressure switch setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-in) psig psig (Out) 4 (Cut-In) psig psig (Out) Checked Setting - Yes - No (each circuit) Low Pressure Switch Setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-In) psig psig (Out) 4 (Cut-in) psig psig (Out) Checked Setting -Yes -No (each circuit) 1 Oil Temperature Safety Switch Cut Out 2 Oil Temperature Safety Switch Cut Out 3 Oil Temperature Safety Switch Cut Out 4 Oil Temperature Safety Switch Cut Out If Star-Delta start time delay is seconds Temperature of air entering condenser F Temperature of air leaving condenser of Temperature of chilled water entering chiller OF Temperature of water (chilled) leaving chiller F Chilled water pressure entering chiller psig Chilled water pressure leaving chiller psig

MAINTENANCE Good maintenance practice will prolong the chiller life and will reduce the Ask of system breakdown and expensive service calls

A weekly check of the ACWC-SD unit requires only a few minutes and will prove beneficial in insuring long trouble free operation

WEEKLY CHECKS- with unit in operation for at least four hours 1) Check compressor oil level - At least above 12 of sight glass 2) Record suction and discharge pressures

Typical Condition R22 Ambient 95degF Return water 55degF Leaving water 45degF Suction 62 psig Discharge 270 psig

3) Record ambient temperature 4) Check liquid sight glass

Make sure liquid is clear - no bubbles 5) Check that all fans are running 6) Check entering face of condenser coil for cleanliness 7) Record voltage at unit

All of the above can be performed by building maintenance personnel If oil levels are low or any of the above checked items are questionable consult a qualified serviceman

At least once a year a qualified serviceman should check unit oil levels superheat and control operation

DUNHAM-BUSH USA

P l) bull 130 xUtUC t01 Bmgess RO~ Harrisonburg VA 22801 Phone (540) 434-0711 FAX (540) 434-~ 2118

wvvwdunham-bushcom Form No 6184

Page 4: ACWC-SD - · PDF fileACWC-SD • Screw . Type • • • Air-Cooled Packaged Chillers •• Installation, Operation, and •• • Maintenance Manual • • • •• DESCRIPTION

SLIDE VALVE UNLOADING SYSTEM

The Rotary screw compressor capacity control system for infinite modulation consists of a slide valve and hydraulic pistoncylinder operator intemal to the compressor plus three hydraulic solenoid valves (UL-1 UL-2 amp UL-3)

The slide valve forms a portion of the chamber wall in which the rotors turn thus its position with respect to the rotors determines the effective rotor length and thereby the percent of full load capacity

Upon compressor start-up UL-3 is opened This allows oil pressure to act upon the hydraulic piston holding it in the fully unloaded position After 30 seconds during which time full oil flow is established to all bearings surfaces UL-3 is closed At this point the temperature controller is free to open and close UL-1 or UL-2 in response to the supply water temperature

The slide valve will move to the left (loading) by force of discharge pressure whenever UL-1 opens to permit flow to the oil return (low

Load

centJ

Screw Rotor

Slide Valve

Unload

~ Oil Pressure

Oil Pressure Lines

Hydraulic Piston

pressure) line The slide valve will move to the right (unloading) whenever UL-2 opens the oil supply (high pressure) line since the force of the oil exceeds that of the discharge gas

The temperature controller sends a series of power (energizing) pulses to the appropriate solenoid to adjust to load conditions The further the supply water temperature is from the controller set point the longer is the duration of the pulses The series of pulses will continue until the controller is satisfied As the water temperature approaches the set point the pulses become quite brief to prevent overshooting the set point

This method of compressor unloading in conjunction with supply water sensing minimizes actionreaction lag time and overshoot resulting in an exceptionally precise and stable control of supply water temperature

Oil Oil Return Supply

The following table lists solenoid valve position for all three operating modes

UL-1 UL-2 UL-3 Starting Close Close Open Loadinq Open Close Close Unloading Close Open Close

4

LOW AMBIENT OPERATION

Due to the wide range of applications it is sometimes necessary to operate the Air Cooled Packaged Water Chillers at ambients below summer conditions Without proper control when ambients drop below 60degF the pressure differential between the condenser and the evaporator is below the level to insure proper thermal expansion valve operation As a result the unit may cycle off Two types of system control are available allowing the units to operate at the ambients indicated

FAN CYCLING MEDIUM AMBIENT CONTROL TO 30degF

(STANDARD EQUIPMENT-FACTORY INSTALLED)

A fan cycling control is standard on all Air Cooled Packaged Water Chillers to provide proper operating head pressures in ambient conditions to 30degF

This is an automatic operation in which the condenser fans are cycled on and off as required in response to head pressure This arrangement provides positive start-up control down to +30degF by delaying the condenser fan operation until a predetermined head pressure is obtained

LOW AMBIENT CONTROL TO OdegF

In conjunction with the standard fan cycling feature all compressors are enclosed in individual housings This housing assures adequate compressor oil temperature for lubrication A five minute time delay relay provides a bypass around the low pressure control to prevent nuisance trip-out during cold start up

COOLER FREEZE PROTECTION-LOW AMBIENT

Cooler freeze protection is a major concern with air cooled chillers To protect against freeze-up a heater cable is provided as standard which protects the cooler to -12degF However there is no freeze protection in the event of power failure or heater cable burnout so the following should be considered for additional protection

1 Drain the cooler and chilled water piping if the chiller is not to be operated over the winter months Drain connections are provided on the coolers

2 Add ethylene glycol to the chilled water system Freeze point should be approximately 10degFbelow minimum design ambient temperature See Page 11 for Glycol Performance

The cooler heater is wired to the control panel and is operational from the factory offered control transformer or field supplied control power

COOLER FREEZE PROTECTION-oPERATION

The ACWC-SD chiller is provided with a temperature sensing freezstat (38deg set point) and a field installed flow switch shutting off the compressors on loss of water flow is also required

Optional low pressure or hot gas bypass freeze protection is also available on the ACWC-SD If these options have not been purchased it is extremely important to guarantee proper chiller water gpm as well as double checking the temperature sensing freezstat calibration

ACWC-SD CONTROL SETTINGS

CUT-INCUT-OUT (PSIG)

UNIT FLP1 FLP2 FLP3 FLP4 FLP5 FLP6 FLP7 FLP8 FLP9 FLP10 FLP11 FLP12 FLP13 FLP14 ISM 44-55 280170 295180

70 260160 275175 2901215

90 260160 275175 2901215 260160 275175 2901215

110-135 260160 2751175 2851210 2951235 2601160 275175 285210 2951235

145-160 280170 2951180 260160 275175 2901215 260160 275175 2901215

185-200 280170 295180 260160 275175 2951235 2951235 260160 275175 285210 2951235 215 260160 275175 2901215 260160 2901215 2901215 260160 275175 290215 260160 275175 290215

240 260160 260160 275175 275175 2901215 2901215 260160 260160 275175 275175 2851210 2851210 295235 2951235

265 260160 260160 275175 275175 2851210 2851210 295235 2951235 260160 260160 275175 275175 285210 2851210 2951235

TEMPERATURE ACTUATED LEGEND FACTORY SETTING

Chiller Low Water Temperature Thermostat T2 Cut-Out 3rF Chiller Heater Thermostat

I(Non-Adiustable) Included With CBH1 Heater

Cut-In Cut-Out

40degF 45degF

Oil Temperature Safety Control (Adjustable) Manual Reset

OTS 1 OTS 2 OTS3

Cut-Out 240degF

Capacity Control Thermostat (Adj) Mode Control Position T1 Dial Set At 44degF

UNIT OPERATING LIMITATIONS

1 Maximum ambient air to condenser is 110degF (60 Hertz operation) 2 Maximum allowable cooler water pressure is 150 PSIG 3 Maximum allowable water temperature to cooler is 75degF 4 Units must not have leaving water temperatures of 42degF or lower unless used with a glycol solution

5

KEY TO WIRING DIAGRAM INDEXING SYSTEM

The wiring diagrams and sequence instructions on the following pages have been devised to simplify the understanding and tracing of circuit theory The following key shows how the indexing system can be used

12 Line number on wiring diagram

[12] Line number in text

(R5) Component identification symbol in text (Relay 5)

[E] Normally open contact - line number location

[E] Normally closed contact - line number location

Holding coil - line number location

amp Note number

SEQUENCE OF OPERATION (TYPICAL) MODELS ACWC 90-135 SO

The following sequence of operation is typical for all ACWC SD Models Refer to the wiring diagram furnished with the unit for specific information ( ) Control Identification Symbol [ ] Circuit Line Number

Important Notel With all the control circuit switches (SW1-SW3) in the off position and the staging thermostat (T1) to its highest temperature Terminals 2 and 4 on the Terminal Board (TER5) must have 115 volts supshyplied for a minimum of 24 hours to energize the compressor crankshycase heaters (CCH1 2) [6 8]

Preliminary Sequence Close the main power disconnect switch Check to see that the red indicating light on the phase loss monitor (PLM 1) is lit (Note There will be two phase loss monitors (PLM1) and (PLM2) on dual power block models) This light must be on to indicate proper phase rotation for the compressors If the light is not on disconnect the main power and reverse any two phase legs at the Main Incoming Power Terminal Block (WARNING DO NOT REVERSE THE LEADS ON THE PHASE LOSS MONITOR FOR THIS WILL ALLOW THE COMPRESSORS TO RUN BACKWARDS CAUSING SEVERE DAMAGE AND WILL VOID THE COMPRESSOR WARRANTY)

The crankcase heater relay contacts (R3) [6] and (R4) [8] are closed and are supplying power to the compressor crankcase heaters Power is also supplied to the chiller barrel heater (CBH1) [13) the optional receiver heaters (RH1 2 [1011] and the optional convenience outlet (CO) [14]

Control power goes through the control panel circuit breaker (CB1) [8] and field supplied remote time clock [36] Check to make sure time clock contacts close during occupied modes

Start up the chilled water pump The water flow is confirmed when the water flow switch completes the electrical circuit across Terminals 15 and 16 [38] on Terminal Board (TER5) Terminals 17 [47] and 18 [49] provide an interlock for the water pump starter(s) when either compressor is in operation Set the thermostat (T1) to the desired leaving water temperature (eg 44degF) Set point adjustment is acshycomplished directly on the control

Place the three (3) control circuit switches (SW1-SW3) in the On position thus energizing the balance of the control circuit [23] [33] [36] The system will be in the Time-In mode for five minutes before the first compressor will start

The low ambient lockout thermostat (LAT1) [38] and temperature freezestat (T2) [38] must also be satisfied to allow compressor operashytion

Stage 1 Starting Upon demand for cooling thefirst stepof the staging thermostat (T1) will be to close energizing relays (R1) [61] time delay (TD1) [60] and the optional time delay (TD3) [62] If all the safety controls and switches are closed (see Safety Controls section for more detail) the control

circuit for Compressor No1 will energize allowing the compressor to start Relay (R5) [20] will energize closing the normally open (NO) set of contacts [23] which energize the liquid line solenoid valve (SOL1) [23] Another set of NO contacts on (R5) [20) provide a series intershylock with all the safety and operating controls which will lock out the compressor if any safety trips during normal operation (See Note 6 on Wire Diagram) The last set of NO contacts on (R5) [48) provides an interlock circuit for the water circuiting pump(s)

The fan contactor (C13) [23] will also close supplying power to the side of the fan cycling pressure controls (See Power Wiring Diagram)

Note The fan motors are controlled by their own fan cycling controls and will cut in at different factory set head pressures

Time Delay (TD1) [601) has two (2) sets of contacts the first set of (TD1) [19] normally closed (NC) contacts provide a 30 second jumper around the low pressure control (LP1) [20] to prevent short cycling during start-up The second set of (TD1) [24) contacts in the NC posishytion power the unloader solenoid (UL3-1) [24] which hold the comshypressor in the full unload position for 30 seconds After (TD1) [60] times out (30 seconds) the contacts for the unloader solenoid (UL3-1) open and the NO set close which energize the relay (R3) [25]

Stage 1 Modulation Upon energizing relay (R3) [25) the crankcase heater (CCH 1) [6] is de-energized and the NO contacts of relay (R3) [45 48] are closed allowing the thermostat (T1) to energize the load solenoid (UL1-1) [45) and the unload solenoid (UL2-1) [481] upon demand The opshytional time delay (TD3) [62] is used to bypass low pressure control (LP1) [20] for five minutes for low ambient starts

Stage 2 Starting Subsequent to the start of Compressor No1 an approximate five minute time delay is incorporated into the microprocessor After this time delay and a further call for cooling the second step of the stagshying thermostat (T1) will close This will energize relay (R2) [58] time delay (TD2) [57] and the optional time delay (TD4) [59] If all the safety controls and switches are closed (see Safety Control section for more details) the control circuit for Compressor No2 will energize allowing the compressor to start Relay (R6) [3D] will energize allowshying the liquid line solenoid valve (SOL2) [331] to energize Relay (R6) [3D]will also interlock the water pump starters and the safety controls the same as Compressor No 1 circuit

The fan contactor (C14) [33] will close supplying power to the line side of the fan cycling pressure controls (See Power Wiring Diagram)

Time delay (TD2) will provide a 30 second jumper around the low pressure control (LP2) [30] and will energize the full unload solenoid (UL 3-2) [34] for 30 seconds then energize relay (R4) [35]

Upon energizing relay (R4) [35] the crankcase heater (CCH2) [8] is de-energized and the NO contacts of relay (R4) [46 49) are closed allowing the thermostat (T1) to energize the load solenoid (UL2-1) [46] and the unload solenoid (UL2-2) [49] upon demand

6

SHUTDOWN SEQUENCE

Stage 2 Shutdown Stage 1 Shutdown

After both compressors have unloaded fully and the leaving water temperature is still lower than the setpoint the second step of the thermostat (T1) will open and de-energize relay (R2) [58] providing an approximate five minute time delay again integral with the microshyprocessor has expired subsequent to the start of Compressor No2 This will close the liquid line solenoid (SOL2) [33] and turn off Comshypressor No2 Compressor No 1 will load and unload as required Compressor No2 will not be able to restart for five minutes due to integral time delays

SAFETY CONTROLS

The unit is protected by the following safety controls

1 High Pressure (HP) 2 Low Pressure (LP) (automatic reset) 3 High Discharge Temperature (OTS) 4 Compressor Solid State Module (CSTM) 5 Low Water Temperature (T2) 6 Low Ambient Thermostat (LAT) 7 Compressor Starter Overloads (OLH) (optional) 8 Phase Loss Monitor (PLM) 9 Control Circuit Breaker (CB1)

If any of these devices should open due to abnormal conditions the compressor(s) will automatically stop All controls must be manually reset except low ambient thermostat (LAT) and phase loss monitor (PLM) The individual compressor safeties (HP LP OTS and CSTM) contacts are found on Lines 20 (CTT1) or Line 30 (CTT1) The other safeties listed above are discussed in the preliminary sequence section

If the leaving water temperature is still lower than the setpoint the first step of the thermostat (T1) will open and de-energize relay(RI) [61]This will close the liquid line solenoid (SOL 1) [23] and turn off Compressor NO1 as long as it has run for approximately three minutes Compresshysor NO1 will not be able to restart for five minutes

FIELD CONTROL WIRING

In addition to 3 phase power (and optional 115 volt control) wiring described above the following control interlock wiring is recommended The as built control schematic provided with the unit provides detailed information Typical control schematics are as shown on pages 8-15

1) Alarm Circuit -Terminals 6-13 (2 per compressor circuit) can be used to trigger remote failure lights or alarm bells in the event of a refrigeration failure

2) Time Clock - All unit on-off control should be done through terminals 15 and 16 An open contact shuts down the unit Time clock night shut down and energy management shut down should all be done from these terminals and contacts should be applied in series

3) Flow Switch - The flow switch contacts should be installed between terminals 15 and 16 and be in series with time clock contacts

4) Chilled Water Pump - The control of the chilled water pump must be worked out by the system designer It is necessary for the pump to be on during any compressor operation and terminals 17 and 18 should be used to energize the pump starter However it is likely that the pump should remain on throughout all occupied operation or even at night for freeze protection Terminals 17 and 18 should not be the sole means of controlling pump operation

STARmiddotDELTA STARTING OPEN TRANSITION (OPTIONAL)

Typical For All Compressors On initial call for cooling staging relay (R1) holding coil will energize The (R1) contacts 7-4 close energizing star contactor (S1) and the five second transition timer (TD5) Transition contactor (S1) power contacts close tying the center legs of the compressor motor windings together into Star (WYE) configuration At the same time (S1) NC (Normally Closed) auxiliary contacts open preventing (C2) from closing (S1) NO (Normally Open) auxiliary contacts then close energizing contactor (C1) The (C1) power contacts close applying power to the

compressor winding (C1) NO (Normally Open) auxiliary contacts close locking (C1) in the energized position The compressor operates in the Star mode until (TD5) transition timer times out (five seconds) at which time contacts NC open and de-energize (S1) Star contactor (S1) NC auxiliary contacts close (TD5) timer NO contacts close energizing compressor contactor (C2) power contacts close thereby completing the Delta wiring configuration Compressor contactor (C2) NC auxiliary contacts open preventing (S1) star contactor from energizing until the next starting sequence

7

--

exgt

LE

GE

ND

m

rrbullbull

saN

OI

IlIG

CI-

Z

CO

HT

AC

TQ

ftmiddot (

0

[5

10

1t5

el

) C

ON

TA

ClO

middot A

NS

(C

UlT

middot pound

AM

III

bull C

ON

TO

L

(C

UlT

C

UtC

UIT

Ulaquo

III

H

IAT

EIt

I C

HllL

rU

lU

[AT

III

CU

Ne(

ASE

H

un

co

U

OIl

ll

SOL

ID

TA

U

MO

OU

Lt

H

US

UII

lI[

con

RO

L

LOW

Abullbull

IN

T

[

twO

fI

lO

W

nul

tt C

ON

TIIlI

OL

OIL

TU

II

r

UIIl

I(

SA

HA

S[

0

1$

M

ON

t T

O

lllE

LA

Tmiddot

tTA

GIH

O

1t[

LU

-U

CIT

Y ~OL

bull

CI

l

tC5

I H

el

C

Ubullbull

e

lHI

CC

HI

esr

P

I L

UI

VI

enst

P

LU

11

0)

(L

AY

middot tN

Uft

LO

CK

(

L[N

OIO

middot L

lOU

IO L

INI

SWIT

CN

CO

W

UD

C

C

UIT

S

SWIT

CH

ST

EN

fH(

MO

ST

AT

middot S

[OU

[Ne

EIt

TH

UM

OS

Tn

-L

OW

n

llI

IUU

[

TtIt

WIN

AL

10amp

1110

cu

no

wE

It

UN

I J

SO

LI

w

10

Tl T[l

Il

S

Tl

Ufl

Ul

10

0

-

CT

OII

I

WIl

WO

T

lM[

HU

T c

alli

CO

NTbull

bull L

OW

Ipound

n

LO

CC 0

1

TO

T

IllS

I

ond

tlt

UN

Lo

ao

t

OL

(NO

ID bull

(O

M

no

ll

Ul

ImiddotZ

~(

tU

IIL

T

IIS

VI

O

I

_

-~

OIO

HA

l

ell

C

UtC

Ul

[

amp1

(( -

(cri

VE

lli K

uru

en

C

IAC

Uff

A

UK

(jII

f bull

CO

[

I(

C(

OV

TL

lT

CI

I (O

NU

OL

If

Jll

AIr

IS

HO

UA

W

(fIA

S

LL

Tl

LO

AO

LI

T

(III

WO

STA

T

0

middot

5

O

(III

LO

AO

fU

UIS

LImiddot

H

OT

L

IGH

TS

H

IUC

IIY

[1II

H

[AU

IIIS

~ jllf

M1

III[

Cll

[

H

[U

t

US

UII

ll[

CO

NT

IIO

LS

~tCt

JVII

l N

(AU

III

14

(0

1

T

O)

TO

wI

DtL

AY

amp L

OW

U

tu

LO

CK

ou

r rt

(

O(L

IN

SlT

IO

C

OH

TA

(TO

Il

(O~USO

C

OH

O

lll

bull iT

A

OlL

C

Ol

CO

MV

[Nf

epound

o

un

n

Ctft

CU

lT I

DE

TA

IL

A

SlA

M

DE

LTA

ST

AR

T

O -~

OA

~ 5~U

Z

OI

Cl

U

I 14

(I

amp

~

NC

f

cl

AU

I

51

ZtA

LU

TOO C

21

NO

~~

bullbull

N

WHT

I---

I

l I J

II

A

CN

lCU

lT

If

OOHAI~

l

~i1

WH

It[

-

OI

ON

AL

r---

----

---

-I

Q

WT

I lt

raquo

I I L

JI

bull bull

I I

0

II

-

lJ

_ Ij

lf

I

cal

II

iOO

w

shy

) C

it

~

WTI~AL

r --------------------------------

Iamp

I

_l

[0

0

I

OO

CM

lL

00

LO

II

cu

U

II

bullL

~J

It

_U

I

TH

u

I

HT

I~

r-~~

~ --

-I=

=~==

=~I

11

2

N

~~~

~--

----

----

=~

I

-lt

l

= I

en

co

o J

rO~

2

~L

----------

-

-oS

f

I

r--shy

J

on

T

O)

vI

Q~~A

J T

Ot

L-

ll~_

f

1

II

CU

H ~

~OI

L1

-i

r---

----

-

~

10

rc

I

bullbull

lf

OIS

ti

l W

I H

Z

01

11

1

-J

o

u

L

shy

0bull

-

0 T

1

111

A -

bull 0

[0

HT

I

ll II

rgt ---

-ij

---

ITl~ll

t

1amp

I

1t

D

MIN

I[D

11

~

ill HTAILmiddot~

O

LM

I 01

1

OL

HJ

III0

1l~

tM

Ow

N

CI

amp

tt

I w

lO

OIO

HL

---

__

J

O ~

~Ll

~

tB1

It

CI)

n

IS

-1

M

k

V

Io

Jmiddot

r---

1

we

14

-4

I

Mill

I

CO

MPR

ESS

OR

C

IRC

UIT

I

Til

bull ~

r-

so li

e II

It

S

tON

L

N

O

fll

II

If

II

~

s~

o

oc

gt

(I)

r in

n

100

00U

lz

--I

~o

e

0

r ce

cn

shy0

0

Z

Ggt

bullbull bullbull bullbull bullbull bullbull bullbull

r~T~-

ICt

MQ

Teuro

CO

MT

It01

I T

IM C

lot

ll

~---

Cl

ll

(O

41

(

flO

W

5Wlf

CH

~

I

Olt

CO

NT

AC

TO

C

OIL

S C

I-I

bull C

tS

AN

D S

t sn

N

OW

IIt

Dll

QU

0

1 C

OM

UC

TI

I

111

114

0

(

U

II

NO

f T

O I

(

C

uNO

IO

ON

UtI

se

CO

HO

UI

li

D(

1

A

ND

1

n

WP

(IU

ult

l S

(NIC

tf1

I

LO

CU

ID

1M bullbullU

O

UT

UT

r-

----

shybullbull

0

11

UO

V

HA

Il

LO

IS

raquoON

TO

S

TE

lurN

AU

bull

AN

D

0111

IIC

O(

I A

ND

A

U(

Cfl

YpoundL

Y

So

C

rt

TO

0

0 M

AN

UA

L a

ll H

TO

tNT

AN

D

~10l

IA

NO

M

TII

UC

TtO

NS

II

rCO

tNO

m

IMIT

AL

CO

H

laquo

0

U

TI

I It

4

Ishy

C

OW

III

ISO

R

MO

DU

LES

dC

NO

MmiddotA

U

VA

TC

I

D

U

1111

WIL

L A

LSO

LO

C_ O

UT

(

let

Umiddot

I C

AL

L

WH

IM

IAI

TY

flit

TH

[I(

CO

Nmiddot

I

OL

I CA

Jrf I

I II

EM

T

IT T

Uft

I1

tW

ITC

H bullbull

0

VO

NIN

IL

f PO

C

Obullbull

bull

I w

UII

II

I

C

IL

Llf

i I

ITA

f[1

II

ItV

N

IWIT

ti r

raquo7

~Slt~1

~~~~( 1~~~~tlDOO

CO

N

CT

O

WU

UH

O 0f

II C

OW

bullbullbullbull

~~1

II

bull

LL

TI

lIT

AT

0

N

O 1

0 O

CA

TID

1

1 I

I IIl

ETU

IIPt

W4T

P

LU

WHE

N u

TI

It N

OT

lU

u

rD

ttl

III I

ICO

Ma-

aU

0 11

nM

H

u

l

UN

I()1

II M

UST

HA

V(

SH

llL

DID

C

AU

I

LO

Me

T

II

no O

R

ItUM

WT

M

ItO

WI

L

IAH

to u

ri N

T I

T H

-

ITbullbull

O

N

ft

0

-

011

II~T

K

ITI

GU

ION

An

ON

S

o H

O-

ON

G C

OI

-W

it

11

N(

NO

6 N

c

CO

NU

ClI

W

If

lIN

( N

O

o N

0

CO

NT

AC

TS

WIt

K

liN

t N

O

6 N

OT

t I

TH

L

Nt

NO

Y S

UI

-I

IS

5_

1

~

~

no

~ I

I I_

VLOA

Or- I

I ~~

vumiddot

S1 so

CO

Hit

so

0

amp

g A

SI ~

I

1

7100-

I -I

I 01

10

OH

0

10

f T

AN

I V

I

] CM

NG

( av

rlt

10

0 O

K__

ST

AG

(

COD

lJ-

L7

00

~It

A

lIT

00]

VL

I fi

ll

14

1

10A

O

f

_ III

rC

OH

O

In o

y

00bull

00

10 ~

0

10

CO

Ol

C

bull

] 4

U

rr

COL~

bull Jo

un

J

W bull

C~P

OJ [

ou

-t

urO

NT

01

CO

l0

1

N

Omiddot

~ ]

(jCO~_

0

)

un

ll

n ~

T

I 11

I1

III _~

n

~

amp

7

10

II

01

u II 17

II

0

II

01

IS

-I

-lt

sE

o

0 c

raquo

CD

r iii

0

~O

U

lZ

+-1

~

tI

t

0

r QE

CIJ

-c

tl

Z

Ggt

lt0

bullbull bullbull

bullbull

bullbullbullbull

~

o

tUN

oa

lllO

_--

-

shyC

t-4

CII

C

cn

bull

tlN

I

CC

HImiddot

t

csnu

middota

--1

LA

T

loP

a

01

11

-1

111

111

IIImiddota

It

4

IOL

IS

IW

Imiddot

I

I T

I n flbull

bull

TO

middot I

st

U

LImiddot

a

Oft

lo

tL

LtG

EN

D

CO

NlA

CT

IM ~

CO

lllf

lllt

UtO

JII

CO

NT

AC

TO

CII

CU

fT

IIIC

AICC

III

CO

NTJ

IIOL

CIC

UIT

U

NImiddot

HU

TI

eNU

LlII

I

Il

I

AU

It

C

NlaquoC

AU

NC

An

C

O

UIO

10

LIO

T

AU

N

t U

SU

I C

O T

OO

L LO

W

eT

fM

llltM

OT

AT

L

OW

Hl

III

UII

I C

Oft

TJl

OL

OU

n

ru

ulltl

A

nT

T

HA

-

0bullbull M

OH

IfOIt

fl

lLA

Y I

AO

INI

MU

C

AN

cn

CO

fTltO

Ibull

ItIL

A

INT

ILO

CIC

OL

EN

OtD

Ll

OU

ID L

INt

Cc

ulT

MOO

ULIE

C

NIC

CA

SE

ItS

C

(

OM

II

IOII

(lI

IieLf

W

I eM

-

UIE

R

TH

III

OIT

6Tmiddot S

lOU

lC

U

MC

ot

LOW

TlM

e

U1

T

lER

bullbull

L l

OA

JIIO

middotCU

lTo

tJ

II W

UU

Nt

TI

M

AL

IO

D

oC

0It

1 U

IIN

t T

IMe

OC

LU

middotCA

II C

ONT

a

LOW

IU

t L

OCK

OUT

NPD

WIU

UN

LOA

Olil

t 1

0L

(NO

I0

C

O

III

OIl

lI

cn

CIJ

tCU

IT

UII

lEIt

ft

EC

poundIV

E H

IAI

C

Ol

(C

UIT

1I

IUIIl

I1II

CO

NY

(NIE

NC

E

OU

TU

T

CU

I C

ON

nlo

0

1

AN

$ M

ill1

1

HO

YIll

MU

II

lLT

I l

OA

O

LlI

lIIT

T

H(

O

ITA

T

OL

O

VC

LO

AO

MIA

nl

L1

lI1

~HAII

LO

IS

MO

NIT

O

L

Imiddot J

~fOT

L

IOH

TS

1

1

IC

IIV

E

HE

UE

ItM

lIC

tmiddotl

rC

IIV

E

MU

TlI

t l

tIIS

UIl

l(

CO

NT

ItO

LI

T

lmiddot1

C

CC

lvllt

N

EA

fllt

T

lW

OS

TA

lI

TO

Jmiddot 4

T

INe

H

LA

Y

LOW

In

vlt

l LO

C

OU

T

1O

t-1

ft

lll

D

UA

Tmiddot

TA

SIT

ION

C

ON

TAC

TO

Ill

$middot

1

CO

C

O

(

lIO

C

ON

TA

CT

O

T

A

Dn

u

CO

WC

tllltN

CI

ount

T

DE1AIL~

ST

AR

D

EL

TA

S

TA

RT

r

2

~f

10

t10

II

amp

II

11

II

)

1IllI

1IU

--shy

OW

E

IV

-

utv

lO

f

I I Ibull

A

UR

C

IlltC

UIT

C

IRC

UIT

ALA

NlC

UfT

C

lflC

UIT

I I

I

~li

IT

I

Ot

ON

AL

il------~---l

-

tL

J --

--

C

it

prIlgjf~

II

ell

I

I

IfB

I

t

---------~~-------

__

~

L_ -

7 -

-r--

et

r

I

II10

-I

CII

-lt

PL

1amp

I I

II b

I

L _

__

J

II 3

2I

oo

II

Qraquo

~

IS

lI

(

)r-

t-_

_ o

J_

_

O

TIO

L

I ~~

--~-

I

I CD

oL

__

__

__

__

__

CO

I- f

_

JI I

t degz

OI

OIl

lAL

r-

---

IS

r

-l

0

I

I

+10$

IL

KS

I T

e

0 Lr

I J

II

T

ITI

lOL

l 1

40

bull (C

IS)

TO

bullbull

lD

A-

~ -

r--

-~l

)~II

I

~G

__

_~L_J

0

O

HA

I

~ -

-Ill

-

---

-10-

--

~E

II

cn

-C~

II

Z

0

G)

Il

l~

r- I W

lllltO

WH

IN

JU

L1

l0

I I

I

OL

M

OL

MI

OL

I ~ro

o

jo

o

Jt

JI

L

OT

10N

AI

II

0

(01

0 CO

MPR

ESS

OR

C

IRC

UIT

~

27

III

gt

0

IIA

IO

amp1

)amp

1

1

II

~

I rA

I

TA~

D

ELTA

STA~T

CONP~E~)

CU

lT 2

~

f

bull ]

A

U

4 ]I

IUft

middotJI

Mon

tUPlOI

NT

lOA

Ot-

-O

I

01

0

]

(N

GI

011

1

00

CT

AN

)

40

00

HN

a

_N

I

J00

I -

It IC

y

TO

I

I I

I

~

oiiO

NA

t

I bull bull

wi

i

lOa

r~TT~-

I M

OT

I C

ON

sr

0

llItt

(

co

ce

OZ

UK

1

11

_JO

I I

)--11

--

- ---

-

IJI

LD

~

I

A

CK

lS

C

UK

I

IL

UO

A

TO

O

WH

IT

1

L

OW

SW

ITC

HJl

AL

D

00

IZ

I

f

1It-

-

rl__ u-

poundL

J f

aT

ION

AL

TI

WfI

OO

f

~

ff

I

Dill

C

ON

TAC

TOIlI

C

OtL

S (1

middot4

(IS

middot14

A

ND

II-

I

01

1In

N

O

Wl

0

51

11

~

CO

NT

AC

TS

I

fH

IO

Uti

IS

N

OT

TO

IE

al

llauN

DIO

O

N H

I Sr

CO

NO

AIl

lf

StO

l

f

I

TI

AN

D

TI

TI

U

I

IIN

OII

t

0middot

f1L

OC

AT

IO

IN n

lll

GU

lUT

r-

----

shy~

(I

G

lIt

no

v

HA

I

LO

SS M

ON

IO

nf

1Na

bull

AN

D

ON

rc

I(

CO

M(

f A

IrfD

I

lItU

rC

TIY

(U

00

-

5

E

[CO

OIO

lItc

rlll

TO

0

0

AN

UA

L

t

OIN

T A

Na

f

oo

IlU

COfrt

TO

I U

ND

IN

Stt

UC

TIO

trl

r

co

rNH

D

01 11

raquoIN

ITIA

L

CO

NT

lIIiO

L

fII

I0 I

UT

IS

a

jshy

orshy

10bull

CO

M1

II1t1

Ol

MO

GU

LI

I N(

tN-a

UT

OM

AT

lC

I 1I

lfla

n

flS

bullbull

11

A

LSO

ampO

eMmiddotO

UT

luer

llt

middot I

no

C

AL

Y

WH

IM A

N

IUIT

T T

IIII

P

T

MU

I C

ON

egoo

IT

flO

LI

CA

l

ItU

I1 I

T

TU

NIN

G W

ITC

M

0

~r=

0 I

lIO

Wlf

lIT

A

L

fOtt

CO

lI

tbullbull

w

ITC

H_

I

on

WO

Nlf

lIT

JII

IL

POllt

COW

bull

I In

degz

r+-i

~~

t

u ~o

1 ~rI~~

~~

~~TtIc~~I~D

1

SW

lTC

HI ~

C

OIfT

AC

TcU

t W

lItN

t C

OM

bullbull

H

To

lIL

b

l

0t~~1

0

1

CO

tfC

TO

H

I

lIt

C

ltbull

IIT

C

~r-

bull

WM

IH

-

2

N

OT

1V

l

rD

wllI

I[ to

IlIC

OM

n

I W

I

It

I

fjC

Ofl

P

tE

CJ)shy

t W

IN L

UI N

OT

SU

PL

ID

W

IIIIC

O

J

lleo

W

ti

l

LU

KT

IT

10- A

ND

10ft

II

v

C~

LO

CA

TU

I II

1t

11V

MI

_T

at

I

z10

I

T

lNH

A

TU

RC

S

lNS

OIt

MU

tT

ve

IL

OID

C

IL

C

()

11II

L

AT

I

AT

10

_

A

U

IIIT

I0middot

PCA

LOW M

I_ lO

TI

I bullbull

n

II

DES

IGN

ATI

ON

S

II

CO

NT

IlID

t I

NO

-o

MO

LD

INfl

C

OIL

It L

tNI

NO

0

Q

N

C

CO

NU

ClI

W

ITH

UN

I N

O

01]

0 co

O

f

11

~

I

ILK

n

e

s IA

UL

It

ibull

o O

CO

NTA

CTS

w

nw L

INI

NO

01

fA

0

~

fItO

TI

LI

I N

O

v

A

II

~ ~ bull i middots

~

~~ - ~

~

1- I J I J I I I I I I I I I I I I I I L __ J

I

a bull bull a bull bull

I I I

_J

r------~

=~I = ~ ~ bull ~ I I

~

as coe ruq SV~ siapow ~NI~IM lO~lN03lV3ldAl

i 4

_

a

~FirI1 u~III - I I

~ 1I

00000 -

I=II~I~~~~raquoIIIItIII~ampI~

as ooz nJ4l sv ~ siapow ~NI~IM lO~lNOgt TVgtldAl

bullbull bullbull

bullbull

~

jgt

lpoundIt

ND

II

co

----

----

----

----

----

----

----

----

-

r-~-middot--=-~~

~

bull a

~

at~04

5

---

~1I

A

~n

bullbullmiddot-shy

wo

_-

bull

lIt

C-

I C

Cf

aC

TO

Ic

ow

n

CC

eM

ca

~C

M

OD

IAI

CI

T-

CO

IITA

CT

oa

bullbull

CMCU

rT I

ItIM

IA

co-l

to

c-c

VIT

C

I

rr

c

AfE

bull r~----Ef1

POW

I

III

IQ

W

Q

tIL

UT

I1I

U__~

J

COt

I

LD

W M

lMtr

f nc

IIO

ff

0

N

LO

W

C

OIIT

INM

I I

CO

M

US

ON

C

NC

UIT

II

II

-~

_T

shy

C

O

NU

SO

II

CIN

CU

IT Z

II

D[TA~

-

ST

AN

D(~TA

IT

AII

T

0

u III

r

amp

II

-~

If

10

MA

MI

eN

talI

Tco_

~

STA

N D[~TA

ST

AII

T

~

CIS

-I

LA

~ 1-4

nmiddot

00

-

-II

1t1S

-1 aw

o fI

fl

U- I -~ Ci

Pi=

i

t

shy

~

iii

i

iii=

ii

-

-shyiii

ClL

n

TU

U

LOt

e

bull It

lLA

Yn

C

AM

Im

CIII

IID

L bull

CU

_C

Abull

fl

lUY

_f

tMO

ea

UY

middotIO

CI

lO

Ll

t

NIU

_L

N

CO

WU

UO

ItC

U

llT

l bullbull 0

1middot

lit

TMC

MI0

8TA

T tc

_lt

CIl

it

11

II

_

middotLO

W

TII

IfN

T

UIlI

C

nll

-

D-C

UlT

QIIU

tW

n-T

PII

IU

LIO

MI-

AC

TC

Ntf

Wi

MI

II

II

tY

middotCM

OO

C

LOW

HIe U

(O

Uf

lIl_

L

OA

M

1OtI

1tO

lD

CO

OA

CM

UtT

1M

C

lIY

Dl

NC

Afi

ll ea

-tU

lT 1

ItUbullbull

lI

oo

ww

lItt

lffc

e O

Un

n

cT

IlG

I

Ie-

~U

IIIC

CIV

P

1T

1lt

C

bullbull

Off

AT

tw

ebullbull

ampOW

IC

IUT

~-

4ti

iT

~

co

ww

O

UfU

T

DITA~

A

ITA

A

OEL

TA

IT

AJI

IT

co

rn~

e

I

1amp

ItmiddotI

~ bull

I I

I

I r

~

bull Iamp

II

I ~

I-

oJ

II I

IrIf

I I I I

s~

o

-I I

ltDc

() raquo

L 10

V

i

()

~O

to

U

lZr0

t2

llJ

IL

C6

J=

_J

~-1

f

II

c 0

II

N

ge

cno

c-

II

Z

Ggt

If IO

IC

IIY

II

IIR

III

IJt

T H

llII

A

Il C

Olaquof

U

TMIbull

~LDM

fI

lAR

PM

Iamp L

Oll

lTV

ii

iLii

Uii

ii

~

U3

I iL

iii=

i

Uii

u

i

O

(no)

T

bull II

1

IOA~

bullr

~ I

[gtO(]O

~ i I Ii i 2 ~ ~ ~ i a bull il 2 ~

iiibullbullbull

~ I ~ I I I ~~ =l ~ iI I ~ I I I It I 1111 amp ~~

as ooz nJ4l SP~ SlapoUII ~NI~IM 10U1NOl lVlldAl

-------

---

TYPICAL POWER WIRING Models 45 thru 70 SC

----

rYl31I01 I

-Ii --ti-

_ I ~_-

~ lniJ -

LIIbullbullbullbull PC _ amp-II _--- ~

TYPICAL POWER WIRING Models 90 thru 135 SC

- --- _ Tt

~rfh c~

tP ~

_III ~

I r-- ~- IIlJ

bull - MIl Mf __ bull Ie_~--~ _shy- shy16

---

----------

TYPICAL POWER WIRING Models 145 thru 200 SC

_ --1a1 IIUrI

middotrFti~v_ bull I

i~i ~~ TaII IIOMLI ~tN T 100 WTIOII 011 lilOOCL a

~ t1

tI bullbullbull

L

i I r-~

I r

~ ~ ~ III

2 ~ ~ ~l

- ~IlD I hJOHr eo teO acshyt CmiddotClM ~ CIKUr1 --

TYPICAL POWER WIRING Models 215 thru 265 SC

ItUU 1D Wll1U1I fIa -rMI

rt-h I -au 11 1_ i r~ rt-f

-i rn f1 ft fi i- llil bullbull c~ I bull c =

~~~ ~i~-~

~~m

~~~CI1 R~~ ~ ~~ ~llAi4I

luv~ bull ~uf LL~~-

~Mfl l~t IrMiA

a I III nII I bull it d

~-t--J I Lll-l~j ~nL4111 WlJj== lit-

I bullbullbull I

UGEND

~

~l OJ

- c~

~~~---

~)~middotI

I

L _~~~ L _I__~_J I ~ (11_1 ~ H~ CUlTMIt tffC_) Ll N

-r_ 0 1ItCIIIl0AI lllQUlllCo as -0- bull bullbull fI PC 110 lNJCllII a Olil1100pound1 II 111 el 1101 ItCOU_ 011 IIOOIL140

I 011 CI-( H[ (0110 (fMCun ubullbull --- l(lD IMbullbull Ntlf 110 e414-7

--CTOttbullbull

2

17

ELECTRICAL DATA Model Volts Type COMPRESSOR FAN MOTORS MIN CIRCUIT RECOMMENDED MAXIMUM ACWC 60 Hz of Qty RLA Starting FLA LRA AMPACITY WIRESIZE FUSESIZE

SC 3 Ph Start HP Ea Curro Ea Ea Ea Circ1 Circ2 Circ1 Circ2 Circ1 eire 2

208230 XL 1788 1040 (4) 70 (4) 380 252 - 250 - 400 -45 208230 YO (1) 50 1788 347 (4) 70 (4) 380 252 - 250 - 400 -

460 XL 737 422 (4) 35 (4) 190 106 - 2 - 175 -460 YO 737 141 (4) 35 (4) 190 106 - 2 - 175 -

208230 XL 2051 1228 (4) 70 (4) 380 284 - 300 - 450 -55 208230 YO (1) 60 2051 409 (4) 70 (4) 380 284 - 300 - 450 -

460 XL 904 485 (4) 35 (4) 190 127 - 1 - 200 -460 YO 904 162 (4) 35 (4) 190 127 - 1 - 200 -

208230 XL 2083 1415 (6) 70 (6) 380 302 350 500 -70 208230 YO (1) 75 2083 472 (6) 70 (6) 380 302 350 500 -

460 XL 974 539 (6) 35 (6) 190 143 0 225 -460 YO 974 180 (6) 35 (6 190 143 0 225 -208 XL 1788 1040 (6) 70 (6) 380 266 224 300 0000 400 400 208 YO 1788 347 (6) 70 (6) 380 266 224 300 0000 400

90 230 XL (2) 50 1788 1040 (6) 70 (6) 380 266 224 400 I300 0000 400 400 230 YO 1788 347 (6) 70 (6) 380 266 224 300 0000 400 400 460 XL 737 422 (6) 35 (6) 190 187 - 000 - 250 460 YO 737 141 (6) 35 (6) 190 187 - =1000 - 250 208 XL 2051 1228 (8) 70 (8) 380 312 256 400 300 250 208 YO 2051 409 (8) 70 (8) 380 312 256 400 300 500

110 230 XL (2) 60 2051 1228 (8) 70 (8) 380 312 256 g I350 300 SOO 450 230 YO 2051 409 (8) 70 (8) 380 312 256 350 300 500 450 460 XL 914 485 (8) 35 (8) 190 231 - 0000 - 300 460 YO 904 162 (8) 35 (8) 190 231 - 0000 - 300 -

208 XL (1) 60 2051 1228 (8) 70 (8) 380 312 260 400 300 500 450(1) 75 2083 1415

208 YO (1) 60 2051 409 (8) 70 (8) 380 312 260 400 300 500 450(1) 75 2083 472

230 XL (1) 60 2051 1228 (8) 70 (8) 380 312 260 350 300 500 450(1) 75 2083 165125

230 YO (1) 60 2051 409 (8) 70 (8) 380 02 260 350 300 500 450 (1) 75 2083 472

460 XL (1) 60 904 485 (8) 35 (8) 190 240 - 250 - 300 -(1 75 974 539

460 YO (1) 60 904 162 (8) 35 (8) 190 240 - 250 - 300 -(1) 75 974 180

208 XL 2083 1415 (8) 70 (8) 380 316 260 400 300 500 450 208 YO 2083 472 (8) 70 (8) 380 316 260 400 300 500 450

135 230 XL (2) 75 2083 1415 (8) 70 (8) 380 316 260 400 300 500 450 I 230 YO 2083 472 (8) 70 (8) 380 316 260 400 300 500 450

460 XL 974 539 (8) 35 (8) 190 247 - 250 - 300 -460 YO 974 180 (8i 35 (8) 190 247 - 250 - 300 -

208 XL (2) SO 1788 1040 (10) 70 (10) 380 326 402 400 0000 500 500(1) 60 2051 1228

208 YO (2) 50 1788 347 (10) 70 (10) 380 326 402 400 0000 500 500(1 60 2051 409

230 XL (2) 50 1788 1040 (10) 70 (10) 380 326 402 400 0000 500 500 145 (1) 60 2011 1228

230 YO (2) 50 1788 347 (10) 70 (10) 380 326 402 400 0000 500 500(1) 60 2051 409

460 XL (2) 50 737 422 (10) 35 (10) 190 295 - 350 350 --(1) 60 904 485

460 YO (2) SO 731 141 10 (35) (10)190 295 - 350 350- -(1)60 904 162

208 XL 2051 1228 (10) 70 (10) 380 326 462 400 (2)250 500 600 208 YO 2051 409 (10) 70 (10) 380 326 462 400 (2)250 500 600

160 230 XL (3) 60 2051 1228 (10) 70 (10) 380 326 462 400 (2)250 500 230 YO 2051 409 (10) 70 (10) 380 326 462 600400 (2)250 500 600 460 XL 904 485 (10) 35 (10) 190 329 - 400 - 400 460 YO 904 167 (10) 35 (10) 190 329 - 400 - 400 - I

NOTES 1 XL Across the LineYOStarDelta 2 RLA Rated LoadAmps(ratedin accordance withARI Standard 590) LRA LockedRotorAmps 3 Wire Size Amps equal125of the ratedloadampsfor the largestmotorin thecircuitplus100of the ratedloadampsfor all othermotorsin the circuit per

NEC 4 Wire size based on copperconductorswith75C insulation perNECTable310-16 Terminal block lugs are sizedaccordingly Use of oversize wiringmay

not lit in terminal blocks 5 Maximumfuse size is basedon 175to 225of the ratedloadampsfor the largestmotorin the circuitplus 100of the rated loadampsfora othermotors

in the circuit per NEC VOLTAGE TOLERANCES 208V-230V min 187VMax 253V

480V Min414V Max506V

I

18

ELECTRICAL DATA Volts Type COMPRESSORModel FAN MOTORS MINCIRCUIT RECOMMENDED MAXIMUM 60 Hz of Oty RLA Starting FLAACWC LRA AMPACITY WIRESIZE FUSE SIZE 3 Ph Start Curro EaSC HP Ea Ea Ea Cire1 Cire2 Cire1 Cire2 Cire1 Cire2 208 XL 2051(1) 60 1228 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 1415 208 YO (1) 60 2051 409 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 472 230 XL (1) 60 2051 1228 (12)70 (12) 380 341 469 500 (2) 250 500 600

12 75 2083 1415185 230 YO (1) 60 2051 409 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 472 460 XL 485 (12) 35 (1) 60 904 (12) 190 352 500 400- - -

(2) 75 974 539 460 YO (1) 60 904 162 (12) 5(12)19 352 500 400- - -

(2) 75 974 180 208 XL 2083 1415 (12) 70 (12) 380 345 469 500 500(2) 250 600

472208 YO 2083 (12) 70 345(12) 380 469 500 (2) 250 500 600 230 XL (3) 75 2083 1415 (12) 70 345(12) 380 469 500 (2) 250 500 600200 230 YO 2083 472 (12) 70 (12) 190 345 469 500 500(2) 250 600 460 XL 539974 (12) 35 (12) 190 359 - 450500 - -

180 1(12) 35 460 YO 974 (12) 190 359 450 -500- -2051 1228208 XL (12) 70 504(12) 380 504 (2) 250 (2) 250 700 700

208 YO 2051 409 (12) 70 (12) 380 504 504 (2) 250 700(2) 250 700 (4) 60 2051 1228 (12) 70 230 XL (12) 380 504 504 (2) 250 (2) 250 700 700215

YO 2051 409230 (12) 70 (12) 380 504 504 (2) 250 (2) 250 700 700 460 904 485 (12) 35 XL (12) 190 225 225 0000 0000 300 300

(12) 35 460 YO 904 162 (12) 190 300225 225 0000 0000 300 2051 1228208 XL (2) 60 (14) 70 (14) 380 504 525 (2250 700 700(2)300

(2) 75 2083 1415 2051 409 (14) 70 700 700208 YO (2) 60 (14) 380 504 525 (2) 250 (2)300

(2) 75 2083 472240 700XL (2) 60 2051 1228 (14) 70 (14) 380 504 525 (2)250 (2)300 700230

(2) 75 2083 1415 2011230 YO (2) 60 409 (14) 70 (14) 380 504 525 (2) 250 (2)300 700 700

(2) 75 2083 472 300460 XL (2) 60 904 485 (14) 35 (14) 190 225 248 0000 250 300

12 75 974 539 904 162 250 300 300460 YO (2) 60 (14) 35 (14) 190 225 248 410

(2) 75 974 180 2083 1415 (2)300 700 700XL (16) 70 (16) 380 525 525 (2)300208 2083 1415 (2)300 700 700208 YO (16) 70 525 525 (2)300(16) 380

700 7002083 1415 (16) 70 (2300230 XL (16) 380 525 525 (2300 700 700(2300(4) 75 2083 472 (16) 70 (16) 380 525 525 (2300230 XL265

300250 300974 539 (16) 35 248 248 250XL (16) 380 460 (16) 35 300 300974 (16 380 248 250 250YO 539 248460

NOTES 1 XL Across the Line YO Star Delta 2 RLA Rated Load Amps (rated in accordance with ARI Standard 590) LRA Locked Rotor Amps 3 Wire Size Amps equal 125 of the rated load amps for the largest motor in the circuit plus 100 of the rated load amps for all other motors in the circuit per

NEC 4 Wire size based on copper conductors with 75degG insulation per NEG Table 310-16 Terminal block lugs are sized accordingly Use of oversize wiring may

not fit in terminal blocks 5 Maximum fuse size is based on 175 to 225 of the rated load amps for the largest motor in the circuit plus 100 of the rated load amps for a other motors

in the circuit per NEG VOLTAGE TOLERANCES 208V-230V min 187V Max 253V

480V Min414V Max506V

19

0

(Wd~) 3lV~ M011 ~31VM

006 009 00 OOt OOl OS L 00 L os 0 Ot

V D m (I) (I)

c D m c D o V

- m m -t o

~

~ m D-

aoao 3~nSS3~d ~3100~

APPLICATION DATA

POINT LOADING

ArMi I 1 5 1

ACWC 45 THRU 10 SC

COMPRESSOR CONDENSER SECTION SECTION

_ 2 4 bull 1

bull CA

J

Model Dimensions Size A B C D 45 91 - - -55 91 - - -70 145 - - -90 145 - - -110 60 40 160 -125 60 40 160 -135 60 40 160 -145 138 74 107 -160 13830 74 107 -185 138 129 107 -200 138 129 107 -215 106 82 106 80 240 106 82 134 107 265 133 110 134 107

1310

1310

~

1

1310

2

ACwe 110 THRU 200 Ie

COMPREIlOfl CONDENSER SECTION IECnoN

4 -

5Imiddot

ACWC 2t5 THRU 215 SC

Model Loadlnu (LBS) Size 1amp2 3amp4 5amp6 7amp8 9 amp10 45 585 765 550 - -55 705 810 635 - -70 660 890 700 - -90 1025 1500 1175 - -110 1195 635 1525 995 -125 1255 690 1835 1115 -135 1255 665 1880 1105 -145 1330 2380 2160 1450 -160 1330 2440 2280 1515 -185 1235 2575 2980 1360 -200 1275 2635 3020 1380 -215 1010 2270 2590 2240 840 240 1115 2550 2870 2715 1125 265 1380 2980 3515 2750 1175

11

II i middot 2 4 lIf 11 to L

21

TROUBLESHOOTING GUIDE

CHILLER UNIT WILL NOT START POSSIBLE CAUSE REMEDY 1 Power off 1 Check main disconnect switch

2 Main line open 2 Check main fuses

3 Incorrect wiring 3 Check the wiring diagram

4 Loose terminals 4 Tiqhten all terminals

5 Control circuit open 5 Check phase loss monitor flow switch circuit breakers temperature control low ambient thermostat low temperature thermostat remote switch etc

6 Time delay 6 Wait

COMPRESSOR HUMS BUT DOES NOT START

POSSIBLE CAUSE REMEDY

1 Low voltage 1a Check at service and unit for loss

b Consult power company

COMPRESSOR CUTS OUT ON LOW PRESSURE SAFETY CONTROL POSSIBLE CAUSE REMEDY 1 Refrigerant shortage 1 Check for leaks -- add refrigerant 2 Restriction in liquid line 2a Plugged strainer - dean or replace

b Liquid line valve partially closed - open valves fully c Expansion valve clogged or inoperative - clean or replace as

required d Solenoid valve partially open - clean or replace as required

3 Low water flow thru cooler 3 Check water flow thru cooler and correct as required

COMPRESSOR CYCLES ON HIGH PRESSURE CONTROL POSSIBLE CAUSE REMEDY 1 Compressor discharge valve partially closed 1 Open valve fully 2 Non-condensible gases in system 2 Operate condenser fans with compressors off If condenser

pressure exceeds saturated pressure corresponding to condenser entering air temperature then purge air from discharge line

3 Overcharge of R-22 3 Purge system while in operation until head pressure reaches a normal level

4 Dirty condenser 4 Clean the condenser 5 Compressor discharge check valve not operating properly 5 Replace if necessary 6 Fans not running 6 Check pressure control setting

CAUSES AND PREVENTION OF FREEZE-UP CAUSES PREVENTION 1 Improper charging 1 Charge per manufacturers recommendation

2 Improperly set safety time delay 2 Check the safety time delay low pressure control for proper setting at the beginning of each season

3 Improper chilled water circulation 3 Use an ample sized cleanable strainer in the chilled water circuit Make certain the strainer is clean to insure full flow and velocity of

chilled water It may sometimes be necessary to treat the water to prevent formation of deposits

4 Not draining for winter shutdown 4 When the system is shut down for the winter remove the drain

plugs and drain the cooler Blowout any remaining water with air

5 Improper pump shutdown 5 Make sure chiller barrel heater is working and flow switch is installed per wiring diagrams

6 Low ambient during air conditioning season 6 Make sure chiller barrel heater is working

NOTE If the ambient temperature is below 32degF freezing can be completely prevented by one of two methods

1 Drain all water from the equipment 2 Add antifreeze to the water

22

START-UP CHECK LIST

Unit Model No

Setting unit

Wiring

Piping

Alignment

Before Start-Up

After Start-Up

Yes No a Vibration isolator used

b Spring isolator adjusted for equal height c If rubber-in-shear isolators are used is unit leveled by shimming

a Power wiring complete

b Control wiring complete c Electric service adequate for load

d Power source voltage correct for motor(s) used

e Motor circuit has proper size fusetrons f System wired per diagram

g All lead connections tight h Wiring complies with local codes i Flow switch operation

a Piping complies with applicable codes b External piping independently supported c Chilled water lines insulated

a All belts adjusted and checked for tension b All pulleys checked and adjusted for proper pitch tightness and

alignment

a Open compressor discharge service valve b Open liquid valve(s) c Open suction and discharge valves to pressure gauges (if supplied) d Check rotation of all fan motors e Start auxiliary equipment (pumps fans etc) f Is crankcase heater operating Operate 24 hours prior to unit startup g Check the compressor oil level through the crankcase sight glass The oil

level should be to the top of the glass If the level is low add oil in accordance with the directions in the maintenance instruction

h Check all control settings as specified in Table 1 I Air purged from chilled water system

a Check high pressure control b Check oil temperature safety switch c Check and adjust low pressure or temperature freeze control d Check and adjust operating thermostat e Check and adjust low pressure operating control f Check and adjust expansion valve superheat g Check and adjust capacity control thermostat

23

OPERATING DATA CHILLER Voltage L-1 L-2 L-3 _ Pressure Gauge Readings 1 Suction psig 1 Discharge psig 2 Suction psig 2 Discharge _ psig 3 Suction psig 3 Discharge psig 4 Suction psig 4 Discharge _ psig High pressure switch setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-in) psig psig (Out) 4 (Cut-In) psig psig (Out) Checked Setting - Yes - No (each circuit) Low Pressure Switch Setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-In) psig psig (Out) 4 (Cut-in) psig psig (Out) Checked Setting -Yes -No (each circuit) 1 Oil Temperature Safety Switch Cut Out 2 Oil Temperature Safety Switch Cut Out 3 Oil Temperature Safety Switch Cut Out 4 Oil Temperature Safety Switch Cut Out If Star-Delta start time delay is seconds Temperature of air entering condenser F Temperature of air leaving condenser of Temperature of chilled water entering chiller OF Temperature of water (chilled) leaving chiller F Chilled water pressure entering chiller psig Chilled water pressure leaving chiller psig

MAINTENANCE Good maintenance practice will prolong the chiller life and will reduce the Ask of system breakdown and expensive service calls

A weekly check of the ACWC-SD unit requires only a few minutes and will prove beneficial in insuring long trouble free operation

WEEKLY CHECKS- with unit in operation for at least four hours 1) Check compressor oil level - At least above 12 of sight glass 2) Record suction and discharge pressures

Typical Condition R22 Ambient 95degF Return water 55degF Leaving water 45degF Suction 62 psig Discharge 270 psig

3) Record ambient temperature 4) Check liquid sight glass

Make sure liquid is clear - no bubbles 5) Check that all fans are running 6) Check entering face of condenser coil for cleanliness 7) Record voltage at unit

All of the above can be performed by building maintenance personnel If oil levels are low or any of the above checked items are questionable consult a qualified serviceman

At least once a year a qualified serviceman should check unit oil levels superheat and control operation

DUNHAM-BUSH USA

P l) bull 130 xUtUC t01 Bmgess RO~ Harrisonburg VA 22801 Phone (540) 434-0711 FAX (540) 434-~ 2118

wvvwdunham-bushcom Form No 6184

Page 5: ACWC-SD - · PDF fileACWC-SD • Screw . Type • • • Air-Cooled Packaged Chillers •• Installation, Operation, and •• • Maintenance Manual • • • •• DESCRIPTION

LOW AMBIENT OPERATION

Due to the wide range of applications it is sometimes necessary to operate the Air Cooled Packaged Water Chillers at ambients below summer conditions Without proper control when ambients drop below 60degF the pressure differential between the condenser and the evaporator is below the level to insure proper thermal expansion valve operation As a result the unit may cycle off Two types of system control are available allowing the units to operate at the ambients indicated

FAN CYCLING MEDIUM AMBIENT CONTROL TO 30degF

(STANDARD EQUIPMENT-FACTORY INSTALLED)

A fan cycling control is standard on all Air Cooled Packaged Water Chillers to provide proper operating head pressures in ambient conditions to 30degF

This is an automatic operation in which the condenser fans are cycled on and off as required in response to head pressure This arrangement provides positive start-up control down to +30degF by delaying the condenser fan operation until a predetermined head pressure is obtained

LOW AMBIENT CONTROL TO OdegF

In conjunction with the standard fan cycling feature all compressors are enclosed in individual housings This housing assures adequate compressor oil temperature for lubrication A five minute time delay relay provides a bypass around the low pressure control to prevent nuisance trip-out during cold start up

COOLER FREEZE PROTECTION-LOW AMBIENT

Cooler freeze protection is a major concern with air cooled chillers To protect against freeze-up a heater cable is provided as standard which protects the cooler to -12degF However there is no freeze protection in the event of power failure or heater cable burnout so the following should be considered for additional protection

1 Drain the cooler and chilled water piping if the chiller is not to be operated over the winter months Drain connections are provided on the coolers

2 Add ethylene glycol to the chilled water system Freeze point should be approximately 10degFbelow minimum design ambient temperature See Page 11 for Glycol Performance

The cooler heater is wired to the control panel and is operational from the factory offered control transformer or field supplied control power

COOLER FREEZE PROTECTION-oPERATION

The ACWC-SD chiller is provided with a temperature sensing freezstat (38deg set point) and a field installed flow switch shutting off the compressors on loss of water flow is also required

Optional low pressure or hot gas bypass freeze protection is also available on the ACWC-SD If these options have not been purchased it is extremely important to guarantee proper chiller water gpm as well as double checking the temperature sensing freezstat calibration

ACWC-SD CONTROL SETTINGS

CUT-INCUT-OUT (PSIG)

UNIT FLP1 FLP2 FLP3 FLP4 FLP5 FLP6 FLP7 FLP8 FLP9 FLP10 FLP11 FLP12 FLP13 FLP14 ISM 44-55 280170 295180

70 260160 275175 2901215

90 260160 275175 2901215 260160 275175 2901215

110-135 260160 2751175 2851210 2951235 2601160 275175 285210 2951235

145-160 280170 2951180 260160 275175 2901215 260160 275175 2901215

185-200 280170 295180 260160 275175 2951235 2951235 260160 275175 285210 2951235 215 260160 275175 2901215 260160 2901215 2901215 260160 275175 290215 260160 275175 290215

240 260160 260160 275175 275175 2901215 2901215 260160 260160 275175 275175 2851210 2851210 295235 2951235

265 260160 260160 275175 275175 2851210 2851210 295235 2951235 260160 260160 275175 275175 285210 2851210 2951235

TEMPERATURE ACTUATED LEGEND FACTORY SETTING

Chiller Low Water Temperature Thermostat T2 Cut-Out 3rF Chiller Heater Thermostat

I(Non-Adiustable) Included With CBH1 Heater

Cut-In Cut-Out

40degF 45degF

Oil Temperature Safety Control (Adjustable) Manual Reset

OTS 1 OTS 2 OTS3

Cut-Out 240degF

Capacity Control Thermostat (Adj) Mode Control Position T1 Dial Set At 44degF

UNIT OPERATING LIMITATIONS

1 Maximum ambient air to condenser is 110degF (60 Hertz operation) 2 Maximum allowable cooler water pressure is 150 PSIG 3 Maximum allowable water temperature to cooler is 75degF 4 Units must not have leaving water temperatures of 42degF or lower unless used with a glycol solution

5

KEY TO WIRING DIAGRAM INDEXING SYSTEM

The wiring diagrams and sequence instructions on the following pages have been devised to simplify the understanding and tracing of circuit theory The following key shows how the indexing system can be used

12 Line number on wiring diagram

[12] Line number in text

(R5) Component identification symbol in text (Relay 5)

[E] Normally open contact - line number location

[E] Normally closed contact - line number location

Holding coil - line number location

amp Note number

SEQUENCE OF OPERATION (TYPICAL) MODELS ACWC 90-135 SO

The following sequence of operation is typical for all ACWC SD Models Refer to the wiring diagram furnished with the unit for specific information ( ) Control Identification Symbol [ ] Circuit Line Number

Important Notel With all the control circuit switches (SW1-SW3) in the off position and the staging thermostat (T1) to its highest temperature Terminals 2 and 4 on the Terminal Board (TER5) must have 115 volts supshyplied for a minimum of 24 hours to energize the compressor crankshycase heaters (CCH1 2) [6 8]

Preliminary Sequence Close the main power disconnect switch Check to see that the red indicating light on the phase loss monitor (PLM 1) is lit (Note There will be two phase loss monitors (PLM1) and (PLM2) on dual power block models) This light must be on to indicate proper phase rotation for the compressors If the light is not on disconnect the main power and reverse any two phase legs at the Main Incoming Power Terminal Block (WARNING DO NOT REVERSE THE LEADS ON THE PHASE LOSS MONITOR FOR THIS WILL ALLOW THE COMPRESSORS TO RUN BACKWARDS CAUSING SEVERE DAMAGE AND WILL VOID THE COMPRESSOR WARRANTY)

The crankcase heater relay contacts (R3) [6] and (R4) [8] are closed and are supplying power to the compressor crankcase heaters Power is also supplied to the chiller barrel heater (CBH1) [13) the optional receiver heaters (RH1 2 [1011] and the optional convenience outlet (CO) [14]

Control power goes through the control panel circuit breaker (CB1) [8] and field supplied remote time clock [36] Check to make sure time clock contacts close during occupied modes

Start up the chilled water pump The water flow is confirmed when the water flow switch completes the electrical circuit across Terminals 15 and 16 [38] on Terminal Board (TER5) Terminals 17 [47] and 18 [49] provide an interlock for the water pump starter(s) when either compressor is in operation Set the thermostat (T1) to the desired leaving water temperature (eg 44degF) Set point adjustment is acshycomplished directly on the control

Place the three (3) control circuit switches (SW1-SW3) in the On position thus energizing the balance of the control circuit [23] [33] [36] The system will be in the Time-In mode for five minutes before the first compressor will start

The low ambient lockout thermostat (LAT1) [38] and temperature freezestat (T2) [38] must also be satisfied to allow compressor operashytion

Stage 1 Starting Upon demand for cooling thefirst stepof the staging thermostat (T1) will be to close energizing relays (R1) [61] time delay (TD1) [60] and the optional time delay (TD3) [62] If all the safety controls and switches are closed (see Safety Controls section for more detail) the control

circuit for Compressor No1 will energize allowing the compressor to start Relay (R5) [20] will energize closing the normally open (NO) set of contacts [23] which energize the liquid line solenoid valve (SOL1) [23] Another set of NO contacts on (R5) [20) provide a series intershylock with all the safety and operating controls which will lock out the compressor if any safety trips during normal operation (See Note 6 on Wire Diagram) The last set of NO contacts on (R5) [48) provides an interlock circuit for the water circuiting pump(s)

The fan contactor (C13) [23] will also close supplying power to the side of the fan cycling pressure controls (See Power Wiring Diagram)

Note The fan motors are controlled by their own fan cycling controls and will cut in at different factory set head pressures

Time Delay (TD1) [601) has two (2) sets of contacts the first set of (TD1) [19] normally closed (NC) contacts provide a 30 second jumper around the low pressure control (LP1) [20] to prevent short cycling during start-up The second set of (TD1) [24) contacts in the NC posishytion power the unloader solenoid (UL3-1) [24] which hold the comshypressor in the full unload position for 30 seconds After (TD1) [60] times out (30 seconds) the contacts for the unloader solenoid (UL3-1) open and the NO set close which energize the relay (R3) [25]

Stage 1 Modulation Upon energizing relay (R3) [25) the crankcase heater (CCH 1) [6] is de-energized and the NO contacts of relay (R3) [45 48] are closed allowing the thermostat (T1) to energize the load solenoid (UL1-1) [45) and the unload solenoid (UL2-1) [481] upon demand The opshytional time delay (TD3) [62] is used to bypass low pressure control (LP1) [20] for five minutes for low ambient starts

Stage 2 Starting Subsequent to the start of Compressor No1 an approximate five minute time delay is incorporated into the microprocessor After this time delay and a further call for cooling the second step of the stagshying thermostat (T1) will close This will energize relay (R2) [58] time delay (TD2) [57] and the optional time delay (TD4) [59] If all the safety controls and switches are closed (see Safety Control section for more details) the control circuit for Compressor No2 will energize allowing the compressor to start Relay (R6) [3D] will energize allowshying the liquid line solenoid valve (SOL2) [331] to energize Relay (R6) [3D]will also interlock the water pump starters and the safety controls the same as Compressor No 1 circuit

The fan contactor (C14) [33] will close supplying power to the line side of the fan cycling pressure controls (See Power Wiring Diagram)

Time delay (TD2) will provide a 30 second jumper around the low pressure control (LP2) [30] and will energize the full unload solenoid (UL 3-2) [34] for 30 seconds then energize relay (R4) [35]

Upon energizing relay (R4) [35] the crankcase heater (CCH2) [8] is de-energized and the NO contacts of relay (R4) [46 49) are closed allowing the thermostat (T1) to energize the load solenoid (UL2-1) [46] and the unload solenoid (UL2-2) [49] upon demand

6

SHUTDOWN SEQUENCE

Stage 2 Shutdown Stage 1 Shutdown

After both compressors have unloaded fully and the leaving water temperature is still lower than the setpoint the second step of the thermostat (T1) will open and de-energize relay (R2) [58] providing an approximate five minute time delay again integral with the microshyprocessor has expired subsequent to the start of Compressor No2 This will close the liquid line solenoid (SOL2) [33] and turn off Comshypressor No2 Compressor No 1 will load and unload as required Compressor No2 will not be able to restart for five minutes due to integral time delays

SAFETY CONTROLS

The unit is protected by the following safety controls

1 High Pressure (HP) 2 Low Pressure (LP) (automatic reset) 3 High Discharge Temperature (OTS) 4 Compressor Solid State Module (CSTM) 5 Low Water Temperature (T2) 6 Low Ambient Thermostat (LAT) 7 Compressor Starter Overloads (OLH) (optional) 8 Phase Loss Monitor (PLM) 9 Control Circuit Breaker (CB1)

If any of these devices should open due to abnormal conditions the compressor(s) will automatically stop All controls must be manually reset except low ambient thermostat (LAT) and phase loss monitor (PLM) The individual compressor safeties (HP LP OTS and CSTM) contacts are found on Lines 20 (CTT1) or Line 30 (CTT1) The other safeties listed above are discussed in the preliminary sequence section

If the leaving water temperature is still lower than the setpoint the first step of the thermostat (T1) will open and de-energize relay(RI) [61]This will close the liquid line solenoid (SOL 1) [23] and turn off Compressor NO1 as long as it has run for approximately three minutes Compresshysor NO1 will not be able to restart for five minutes

FIELD CONTROL WIRING

In addition to 3 phase power (and optional 115 volt control) wiring described above the following control interlock wiring is recommended The as built control schematic provided with the unit provides detailed information Typical control schematics are as shown on pages 8-15

1) Alarm Circuit -Terminals 6-13 (2 per compressor circuit) can be used to trigger remote failure lights or alarm bells in the event of a refrigeration failure

2) Time Clock - All unit on-off control should be done through terminals 15 and 16 An open contact shuts down the unit Time clock night shut down and energy management shut down should all be done from these terminals and contacts should be applied in series

3) Flow Switch - The flow switch contacts should be installed between terminals 15 and 16 and be in series with time clock contacts

4) Chilled Water Pump - The control of the chilled water pump must be worked out by the system designer It is necessary for the pump to be on during any compressor operation and terminals 17 and 18 should be used to energize the pump starter However it is likely that the pump should remain on throughout all occupied operation or even at night for freeze protection Terminals 17 and 18 should not be the sole means of controlling pump operation

STARmiddotDELTA STARTING OPEN TRANSITION (OPTIONAL)

Typical For All Compressors On initial call for cooling staging relay (R1) holding coil will energize The (R1) contacts 7-4 close energizing star contactor (S1) and the five second transition timer (TD5) Transition contactor (S1) power contacts close tying the center legs of the compressor motor windings together into Star (WYE) configuration At the same time (S1) NC (Normally Closed) auxiliary contacts open preventing (C2) from closing (S1) NO (Normally Open) auxiliary contacts then close energizing contactor (C1) The (C1) power contacts close applying power to the

compressor winding (C1) NO (Normally Open) auxiliary contacts close locking (C1) in the energized position The compressor operates in the Star mode until (TD5) transition timer times out (five seconds) at which time contacts NC open and de-energize (S1) Star contactor (S1) NC auxiliary contacts close (TD5) timer NO contacts close energizing compressor contactor (C2) power contacts close thereby completing the Delta wiring configuration Compressor contactor (C2) NC auxiliary contacts open preventing (S1) star contactor from energizing until the next starting sequence

7

--

exgt

LE

GE

ND

m

rrbullbull

saN

OI

IlIG

CI-

Z

CO

HT

AC

TQ

ftmiddot (

0

[5

10

1t5

el

) C

ON

TA

ClO

middot A

NS

(C

UlT

middot pound

AM

III

bull C

ON

TO

L

(C

UlT

C

UtC

UIT

Ulaquo

III

H

IAT

EIt

I C

HllL

rU

lU

[AT

III

CU

Ne(

ASE

H

un

co

U

OIl

ll

SOL

ID

TA

U

MO

OU

Lt

H

US

UII

lI[

con

RO

L

LOW

Abullbull

IN

T

[

twO

fI

lO

W

nul

tt C

ON

TIIlI

OL

OIL

TU

II

r

UIIl

I(

SA

HA

S[

0

1$

M

ON

t T

O

lllE

LA

Tmiddot

tTA

GIH

O

1t[

LU

-U

CIT

Y ~OL

bull

CI

l

tC5

I H

el

C

Ubullbull

e

lHI

CC

HI

esr

P

I L

UI

VI

enst

P

LU

11

0)

(L

AY

middot tN

Uft

LO

CK

(

L[N

OIO

middot L

lOU

IO L

INI

SWIT

CN

CO

W

UD

C

C

UIT

S

SWIT

CH

ST

EN

fH(

MO

ST

AT

middot S

[OU

[Ne

EIt

TH

UM

OS

Tn

-L

OW

n

llI

IUU

[

TtIt

WIN

AL

10amp

1110

cu

no

wE

It

UN

I J

SO

LI

w

10

Tl T[l

Il

S

Tl

Ufl

Ul

10

0

-

CT

OII

I

WIl

WO

T

lM[

HU

T c

alli

CO

NTbull

bull L

OW

Ipound

n

LO

CC 0

1

TO

T

IllS

I

ond

tlt

UN

Lo

ao

t

OL

(NO

ID bull

(O

M

no

ll

Ul

ImiddotZ

~(

tU

IIL

T

IIS

VI

O

I

_

-~

OIO

HA

l

ell

C

UtC

Ul

[

amp1

(( -

(cri

VE

lli K

uru

en

C

IAC

Uff

A

UK

(jII

f bull

CO

[

I(

C(

OV

TL

lT

CI

I (O

NU

OL

If

Jll

AIr

IS

HO

UA

W

(fIA

S

LL

Tl

LO

AO

LI

T

(III

WO

STA

T

0

middot

5

O

(III

LO

AO

fU

UIS

LImiddot

H

OT

L

IGH

TS

H

IUC

IIY

[1II

H

[AU

IIIS

~ jllf

M1

III[

Cll

[

H

[U

t

US

UII

ll[

CO

NT

IIO

LS

~tCt

JVII

l N

(AU

III

14

(0

1

T

O)

TO

wI

DtL

AY

amp L

OW

U

tu

LO

CK

ou

r rt

(

O(L

IN

SlT

IO

C

OH

TA

(TO

Il

(O~USO

C

OH

O

lll

bull iT

A

OlL

C

Ol

CO

MV

[Nf

epound

o

un

n

Ctft

CU

lT I

DE

TA

IL

A

SlA

M

DE

LTA

ST

AR

T

O -~

OA

~ 5~U

Z

OI

Cl

U

I 14

(I

amp

~

NC

f

cl

AU

I

51

ZtA

LU

TOO C

21

NO

~~

bullbull

N

WHT

I---

I

l I J

II

A

CN

lCU

lT

If

OOHAI~

l

~i1

WH

It[

-

OI

ON

AL

r---

----

---

-I

Q

WT

I lt

raquo

I I L

JI

bull bull

I I

0

II

-

lJ

_ Ij

lf

I

cal

II

iOO

w

shy

) C

it

~

WTI~AL

r --------------------------------

Iamp

I

_l

[0

0

I

OO

CM

lL

00

LO

II

cu

U

II

bullL

~J

It

_U

I

TH

u

I

HT

I~

r-~~

~ --

-I=

=~==

=~I

11

2

N

~~~

~--

----

----

=~

I

-lt

l

= I

en

co

o J

rO~

2

~L

----------

-

-oS

f

I

r--shy

J

on

T

O)

vI

Q~~A

J T

Ot

L-

ll~_

f

1

II

CU

H ~

~OI

L1

-i

r---

----

-

~

10

rc

I

bullbull

lf

OIS

ti

l W

I H

Z

01

11

1

-J

o

u

L

shy

0bull

-

0 T

1

111

A -

bull 0

[0

HT

I

ll II

rgt ---

-ij

---

ITl~ll

t

1amp

I

1t

D

MIN

I[D

11

~

ill HTAILmiddot~

O

LM

I 01

1

OL

HJ

III0

1l~

tM

Ow

N

CI

amp

tt

I w

lO

OIO

HL

---

__

J

O ~

~Ll

~

tB1

It

CI)

n

IS

-1

M

k

V

Io

Jmiddot

r---

1

we

14

-4

I

Mill

I

CO

MPR

ESS

OR

C

IRC

UIT

I

Til

bull ~

r-

so li

e II

It

S

tON

L

N

O

fll

II

If

II

~

s~

o

oc

gt

(I)

r in

n

100

00U

lz

--I

~o

e

0

r ce

cn

shy0

0

Z

Ggt

bullbull bullbull bullbull bullbull bullbull bullbull

r~T~-

ICt

MQ

Teuro

CO

MT

It01

I T

IM C

lot

ll

~---

Cl

ll

(O

41

(

flO

W

5Wlf

CH

~

I

Olt

CO

NT

AC

TO

C

OIL

S C

I-I

bull C

tS

AN

D S

t sn

N

OW

IIt

Dll

QU

0

1 C

OM

UC

TI

I

111

114

0

(

U

II

NO

f T

O I

(

C

uNO

IO

ON

UtI

se

CO

HO

UI

li

D(

1

A

ND

1

n

WP

(IU

ult

l S

(NIC

tf1

I

LO

CU

ID

1M bullbullU

O

UT

UT

r-

----

shybullbull

0

11

UO

V

HA

Il

LO

IS

raquoON

TO

S

TE

lurN

AU

bull

AN

D

0111

IIC

O(

I A

ND

A

U(

Cfl

YpoundL

Y

So

C

rt

TO

0

0 M

AN

UA

L a

ll H

TO

tNT

AN

D

~10l

IA

NO

M

TII

UC

TtO

NS

II

rCO

tNO

m

IMIT

AL

CO

H

laquo

0

U

TI

I It

4

Ishy

C

OW

III

ISO

R

MO

DU

LES

dC

NO

MmiddotA

U

VA

TC

I

D

U

1111

WIL

L A

LSO

LO

C_ O

UT

(

let

Umiddot

I C

AL

L

WH

IM

IAI

TY

flit

TH

[I(

CO

Nmiddot

I

OL

I CA

Jrf I

I II

EM

T

IT T

Uft

I1

tW

ITC

H bullbull

0

VO

NIN

IL

f PO

C

Obullbull

bull

I w

UII

II

I

C

IL

Llf

i I

ITA

f[1

II

ItV

N

IWIT

ti r

raquo7

~Slt~1

~~~~( 1~~~~tlDOO

CO

N

CT

O

WU

UH

O 0f

II C

OW

bullbullbullbull

~~1

II

bull

LL

TI

lIT

AT

0

N

O 1

0 O

CA

TID

1

1 I

I IIl

ETU

IIPt

W4T

P

LU

WHE

N u

TI

It N

OT

lU

u

rD

ttl

III I

ICO

Ma-

aU

0 11

nM

H

u

l

UN

I()1

II M

UST

HA

V(

SH

llL

DID

C

AU

I

LO

Me

T

II

no O

R

ItUM

WT

M

ItO

WI

L

IAH

to u

ri N

T I

T H

-

ITbullbull

O

N

ft

0

-

011

II~T

K

ITI

GU

ION

An

ON

S

o H

O-

ON

G C

OI

-W

it

11

N(

NO

6 N

c

CO

NU

ClI

W

If

lIN

( N

O

o N

0

CO

NT

AC

TS

WIt

K

liN

t N

O

6 N

OT

t I

TH

L

Nt

NO

Y S

UI

-I

IS

5_

1

~

~

no

~ I

I I_

VLOA

Or- I

I ~~

vumiddot

S1 so

CO

Hit

so

0

amp

g A

SI ~

I

1

7100-

I -I

I 01

10

OH

0

10

f T

AN

I V

I

] CM

NG

( av

rlt

10

0 O

K__

ST

AG

(

COD

lJ-

L7

00

~It

A

lIT

00]

VL

I fi

ll

14

1

10A

O

f

_ III

rC

OH

O

In o

y

00bull

00

10 ~

0

10

CO

Ol

C

bull

] 4

U

rr

COL~

bull Jo

un

J

W bull

C~P

OJ [

ou

-t

urO

NT

01

CO

l0

1

N

Omiddot

~ ]

(jCO~_

0

)

un

ll

n ~

T

I 11

I1

III _~

n

~

amp

7

10

II

01

u II 17

II

0

II

01

IS

-I

-lt

sE

o

0 c

raquo

CD

r iii

0

~O

U

lZ

+-1

~

tI

t

0

r QE

CIJ

-c

tl

Z

Ggt

lt0

bullbull bullbull

bullbull

bullbullbullbull

~

o

tUN

oa

lllO

_--

-

shyC

t-4

CII

C

cn

bull

tlN

I

CC

HImiddot

t

csnu

middota

--1

LA

T

loP

a

01

11

-1

111

111

IIImiddota

It

4

IOL

IS

IW

Imiddot

I

I T

I n flbull

bull

TO

middot I

st

U

LImiddot

a

Oft

lo

tL

LtG

EN

D

CO

NlA

CT

IM ~

CO

lllf

lllt

UtO

JII

CO

NT

AC

TO

CII

CU

fT

IIIC

AICC

III

CO

NTJ

IIOL

CIC

UIT

U

NImiddot

HU

TI

eNU

LlII

I

Il

I

AU

It

C

NlaquoC

AU

NC

An

C

O

UIO

10

LIO

T

AU

N

t U

SU

I C

O T

OO

L LO

W

eT

fM

llltM

OT

AT

L

OW

Hl

III

UII

I C

Oft

TJl

OL

OU

n

ru

ulltl

A

nT

T

HA

-

0bullbull M

OH

IfOIt

fl

lLA

Y I

AO

INI

MU

C

AN

cn

CO

fTltO

Ibull

ItIL

A

INT

ILO

CIC

OL

EN

OtD

Ll

OU

ID L

INt

Cc

ulT

MOO

ULIE

C

NIC

CA

SE

ItS

C

(

OM

II

IOII

(lI

IieLf

W

I eM

-

UIE

R

TH

III

OIT

6Tmiddot S

lOU

lC

U

MC

ot

LOW

TlM

e

U1

T

lER

bullbull

L l

OA

JIIO

middotCU

lTo

tJ

II W

UU

Nt

TI

M

AL

IO

D

oC

0It

1 U

IIN

t T

IMe

OC

LU

middotCA

II C

ONT

a

LOW

IU

t L

OCK

OUT

NPD

WIU

UN

LOA

Olil

t 1

0L

(NO

I0

C

O

III

OIl

lI

cn

CIJ

tCU

IT

UII

lEIt

ft

EC

poundIV

E H

IAI

C

Ol

(C

UIT

1I

IUIIl

I1II

CO

NY

(NIE

NC

E

OU

TU

T

CU

I C

ON

nlo

0

1

AN

$ M

ill1

1

HO

YIll

MU

II

lLT

I l

OA

O

LlI

lIIT

T

H(

O

ITA

T

OL

O

VC

LO

AO

MIA

nl

L1

lI1

~HAII

LO

IS

MO

NIT

O

L

Imiddot J

~fOT

L

IOH

TS

1

1

IC

IIV

E

HE

UE

ItM

lIC

tmiddotl

rC

IIV

E

MU

TlI

t l

tIIS

UIl

l(

CO

NT

ItO

LI

T

lmiddot1

C

CC

lvllt

N

EA

fllt

T

lW

OS

TA

lI

TO

Jmiddot 4

T

INe

H

LA

Y

LOW

In

vlt

l LO

C

OU

T

1O

t-1

ft

lll

D

UA

Tmiddot

TA

SIT

ION

C

ON

TAC

TO

Ill

$middot

1

CO

C

O

(

lIO

C

ON

TA

CT

O

T

A

Dn

u

CO

WC

tllltN

CI

ount

T

DE1AIL~

ST

AR

D

EL

TA

S

TA

RT

r

2

~f

10

t10

II

amp

II

11

II

)

1IllI

1IU

--shy

OW

E

IV

-

utv

lO

f

I I Ibull

A

UR

C

IlltC

UIT

C

IRC

UIT

ALA

NlC

UfT

C

lflC

UIT

I I

I

~li

IT

I

Ot

ON

AL

il------~---l

-

tL

J --

--

C

it

prIlgjf~

II

ell

I

I

IfB

I

t

---------~~-------

__

~

L_ -

7 -

-r--

et

r

I

II10

-I

CII

-lt

PL

1amp

I I

II b

I

L _

__

J

II 3

2I

oo

II

Qraquo

~

IS

lI

(

)r-

t-_

_ o

J_

_

O

TIO

L

I ~~

--~-

I

I CD

oL

__

__

__

__

__

CO

I- f

_

JI I

t degz

OI

OIl

lAL

r-

---

IS

r

-l

0

I

I

+10$

IL

KS

I T

e

0 Lr

I J

II

T

ITI

lOL

l 1

40

bull (C

IS)

TO

bullbull

lD

A-

~ -

r--

-~l

)~II

I

~G

__

_~L_J

0

O

HA

I

~ -

-Ill

-

---

-10-

--

~E

II

cn

-C~

II

Z

0

G)

Il

l~

r- I W

lllltO

WH

IN

JU

L1

l0

I I

I

OL

M

OL

MI

OL

I ~ro

o

jo

o

Jt

JI

L

OT

10N

AI

II

0

(01

0 CO

MPR

ESS

OR

C

IRC

UIT

~

27

III

gt

0

IIA

IO

amp1

)amp

1

1

II

~

I rA

I

TA~

D

ELTA

STA~T

CONP~E~)

CU

lT 2

~

f

bull ]

A

U

4 ]I

IUft

middotJI

Mon

tUPlOI

NT

lOA

Ot-

-O

I

01

0

]

(N

GI

011

1

00

CT

AN

)

40

00

HN

a

_N

I

J00

I -

It IC

y

TO

I

I I

I

~

oiiO

NA

t

I bull bull

wi

i

lOa

r~TT~-

I M

OT

I C

ON

sr

0

llItt

(

co

ce

OZ

UK

1

11

_JO

I I

)--11

--

- ---

-

IJI

LD

~

I

A

CK

lS

C

UK

I

IL

UO

A

TO

O

WH

IT

1

L

OW

SW

ITC

HJl

AL

D

00

IZ

I

f

1It-

-

rl__ u-

poundL

J f

aT

ION

AL

TI

WfI

OO

f

~

ff

I

Dill

C

ON

TAC

TOIlI

C

OtL

S (1

middot4

(IS

middot14

A

ND

II-

I

01

1In

N

O

Wl

0

51

11

~

CO

NT

AC

TS

I

fH

IO

Uti

IS

N

OT

TO

IE

al

llauN

DIO

O

N H

I Sr

CO

NO

AIl

lf

StO

l

f

I

TI

AN

D

TI

TI

U

I

IIN

OII

t

0middot

f1L

OC

AT

IO

IN n

lll

GU

lUT

r-

----

shy~

(I

G

lIt

no

v

HA

I

LO

SS M

ON

IO

nf

1Na

bull

AN

D

ON

rc

I(

CO

M(

f A

IrfD

I

lItU

rC

TIY

(U

00

-

5

E

[CO

OIO

lItc

rlll

TO

0

0

AN

UA

L

t

OIN

T A

Na

f

oo

IlU

COfrt

TO

I U

ND

IN

Stt

UC

TIO

trl

r

co

rNH

D

01 11

raquoIN

ITIA

L

CO

NT

lIIiO

L

fII

I0 I

UT

IS

a

jshy

orshy

10bull

CO

M1

II1t1

Ol

MO

GU

LI

I N(

tN-a

UT

OM

AT

lC

I 1I

lfla

n

flS

bullbull

11

A

LSO

ampO

eMmiddotO

UT

luer

llt

middot I

no

C

AL

Y

WH

IM A

N

IUIT

T T

IIII

P

T

MU

I C

ON

egoo

IT

flO

LI

CA

l

ItU

I1 I

T

TU

NIN

G W

ITC

M

0

~r=

0 I

lIO

Wlf

lIT

A

L

fOtt

CO

lI

tbullbull

w

ITC

H_

I

on

WO

Nlf

lIT

JII

IL

POllt

COW

bull

I In

degz

r+-i

~~

t

u ~o

1 ~rI~~

~~

~~TtIc~~I~D

1

SW

lTC

HI ~

C

OIfT

AC

TcU

t W

lItN

t C

OM

bullbull

H

To

lIL

b

l

0t~~1

0

1

CO

tfC

TO

H

I

lIt

C

ltbull

IIT

C

~r-

bull

WM

IH

-

2

N

OT

1V

l

rD

wllI

I[ to

IlIC

OM

n

I W

I

It

I

fjC

Ofl

P

tE

CJ)shy

t W

IN L

UI N

OT

SU

PL

ID

W

IIIIC

O

J

lleo

W

ti

l

LU

KT

IT

10- A

ND

10ft

II

v

C~

LO

CA

TU

I II

1t

11V

MI

_T

at

I

z10

I

T

lNH

A

TU

RC

S

lNS

OIt

MU

tT

ve

IL

OID

C

IL

C

()

11II

L

AT

I

AT

10

_

A

U

IIIT

I0middot

PCA

LOW M

I_ lO

TI

I bullbull

n

II

DES

IGN

ATI

ON

S

II

CO

NT

IlID

t I

NO

-o

MO

LD

INfl

C

OIL

It L

tNI

NO

0

Q

N

C

CO

NU

ClI

W

ITH

UN

I N

O

01]

0 co

O

f

11

~

I

ILK

n

e

s IA

UL

It

ibull

o O

CO

NTA

CTS

w

nw L

INI

NO

01

fA

0

~

fItO

TI

LI

I N

O

v

A

II

~ ~ bull i middots

~

~~ - ~

~

1- I J I J I I I I I I I I I I I I I I L __ J

I

a bull bull a bull bull

I I I

_J

r------~

=~I = ~ ~ bull ~ I I

~

as coe ruq SV~ siapow ~NI~IM lO~lN03lV3ldAl

i 4

_

a

~FirI1 u~III - I I

~ 1I

00000 -

I=II~I~~~~raquoIIIItIII~ampI~

as ooz nJ4l sv ~ siapow ~NI~IM lO~lNOgt TVgtldAl

bullbull bullbull

bullbull

~

jgt

lpoundIt

ND

II

co

----

----

----

----

----

----

----

----

-

r-~-middot--=-~~

~

bull a

~

at~04

5

---

~1I

A

~n

bullbullmiddot-shy

wo

_-

bull

lIt

C-

I C

Cf

aC

TO

Ic

ow

n

CC

eM

ca

~C

M

OD

IAI

CI

T-

CO

IITA

CT

oa

bullbull

CMCU

rT I

ItIM

IA

co-l

to

c-c

VIT

C

I

rr

c

AfE

bull r~----Ef1

POW

I

III

IQ

W

Q

tIL

UT

I1I

U__~

J

COt

I

LD

W M

lMtr

f nc

IIO

ff

0

N

LO

W

C

OIIT

INM

I I

CO

M

US

ON

C

NC

UIT

II

II

-~

_T

shy

C

O

NU

SO

II

CIN

CU

IT Z

II

D[TA~

-

ST

AN

D(~TA

IT

AII

T

0

u III

r

amp

II

-~

If

10

MA

MI

eN

talI

Tco_

~

STA

N D[~TA

ST

AII

T

~

CIS

-I

LA

~ 1-4

nmiddot

00

-

-II

1t1S

-1 aw

o fI

fl

U- I -~ Ci

Pi=

i

t

shy

~

iii

i

iii=

ii

-

-shyiii

ClL

n

TU

U

LOt

e

bull It

lLA

Yn

C

AM

Im

CIII

IID

L bull

CU

_C

Abull

fl

lUY

_f

tMO

ea

UY

middotIO

CI

lO

Ll

t

NIU

_L

N

CO

WU

UO

ItC

U

llT

l bullbull 0

1middot

lit

TMC

MI0

8TA

T tc

_lt

CIl

it

11

II

_

middotLO

W

TII

IfN

T

UIlI

C

nll

-

D-C

UlT

QIIU

tW

n-T

PII

IU

LIO

MI-

AC

TC

Ntf

Wi

MI

II

II

tY

middotCM

OO

C

LOW

HIe U

(O

Uf

lIl_

L

OA

M

1OtI

1tO

lD

CO

OA

CM

UtT

1M

C

lIY

Dl

NC

Afi

ll ea

-tU

lT 1

ItUbullbull

lI

oo

ww

lItt

lffc

e O

Un

n

cT

IlG

I

Ie-

~U

IIIC

CIV

P

1T

1lt

C

bullbull

Off

AT

tw

ebullbull

ampOW

IC

IUT

~-

4ti

iT

~

co

ww

O

UfU

T

DITA~

A

ITA

A

OEL

TA

IT

AJI

IT

co

rn~

e

I

1amp

ItmiddotI

~ bull

I I

I

I r

~

bull Iamp

II

I ~

I-

oJ

II I

IrIf

I I I I

s~

o

-I I

ltDc

() raquo

L 10

V

i

()

~O

to

U

lZr0

t2

llJ

IL

C6

J=

_J

~-1

f

II

c 0

II

N

ge

cno

c-

II

Z

Ggt

If IO

IC

IIY

II

IIR

III

IJt

T H

llII

A

Il C

Olaquof

U

TMIbull

~LDM

fI

lAR

PM

Iamp L

Oll

lTV

ii

iLii

Uii

ii

~

U3

I iL

iii=

i

Uii

u

i

O

(no)

T

bull II

1

IOA~

bullr

~ I

[gtO(]O

~ i I Ii i 2 ~ ~ ~ i a bull il 2 ~

iiibullbullbull

~ I ~ I I I ~~ =l ~ iI I ~ I I I It I 1111 amp ~~

as ooz nJ4l SP~ SlapoUII ~NI~IM 10U1NOl lVlldAl

-------

---

TYPICAL POWER WIRING Models 45 thru 70 SC

----

rYl31I01 I

-Ii --ti-

_ I ~_-

~ lniJ -

LIIbullbullbullbull PC _ amp-II _--- ~

TYPICAL POWER WIRING Models 90 thru 135 SC

- --- _ Tt

~rfh c~

tP ~

_III ~

I r-- ~- IIlJ

bull - MIl Mf __ bull Ie_~--~ _shy- shy16

---

----------

TYPICAL POWER WIRING Models 145 thru 200 SC

_ --1a1 IIUrI

middotrFti~v_ bull I

i~i ~~ TaII IIOMLI ~tN T 100 WTIOII 011 lilOOCL a

~ t1

tI bullbullbull

L

i I r-~

I r

~ ~ ~ III

2 ~ ~ ~l

- ~IlD I hJOHr eo teO acshyt CmiddotClM ~ CIKUr1 --

TYPICAL POWER WIRING Models 215 thru 265 SC

ItUU 1D Wll1U1I fIa -rMI

rt-h I -au 11 1_ i r~ rt-f

-i rn f1 ft fi i- llil bullbull c~ I bull c =

~~~ ~i~-~

~~m

~~~CI1 R~~ ~ ~~ ~llAi4I

luv~ bull ~uf LL~~-

~Mfl l~t IrMiA

a I III nII I bull it d

~-t--J I Lll-l~j ~nL4111 WlJj== lit-

I bullbullbull I

UGEND

~

~l OJ

- c~

~~~---

~)~middotI

I

L _~~~ L _I__~_J I ~ (11_1 ~ H~ CUlTMIt tffC_) Ll N

-r_ 0 1ItCIIIl0AI lllQUlllCo as -0- bull bullbull fI PC 110 lNJCllII a Olil1100pound1 II 111 el 1101 ItCOU_ 011 IIOOIL140

I 011 CI-( H[ (0110 (fMCun ubullbull --- l(lD IMbullbull Ntlf 110 e414-7

--CTOttbullbull

2

17

ELECTRICAL DATA Model Volts Type COMPRESSOR FAN MOTORS MIN CIRCUIT RECOMMENDED MAXIMUM ACWC 60 Hz of Qty RLA Starting FLA LRA AMPACITY WIRESIZE FUSESIZE

SC 3 Ph Start HP Ea Curro Ea Ea Ea Circ1 Circ2 Circ1 Circ2 Circ1 eire 2

208230 XL 1788 1040 (4) 70 (4) 380 252 - 250 - 400 -45 208230 YO (1) 50 1788 347 (4) 70 (4) 380 252 - 250 - 400 -

460 XL 737 422 (4) 35 (4) 190 106 - 2 - 175 -460 YO 737 141 (4) 35 (4) 190 106 - 2 - 175 -

208230 XL 2051 1228 (4) 70 (4) 380 284 - 300 - 450 -55 208230 YO (1) 60 2051 409 (4) 70 (4) 380 284 - 300 - 450 -

460 XL 904 485 (4) 35 (4) 190 127 - 1 - 200 -460 YO 904 162 (4) 35 (4) 190 127 - 1 - 200 -

208230 XL 2083 1415 (6) 70 (6) 380 302 350 500 -70 208230 YO (1) 75 2083 472 (6) 70 (6) 380 302 350 500 -

460 XL 974 539 (6) 35 (6) 190 143 0 225 -460 YO 974 180 (6) 35 (6 190 143 0 225 -208 XL 1788 1040 (6) 70 (6) 380 266 224 300 0000 400 400 208 YO 1788 347 (6) 70 (6) 380 266 224 300 0000 400

90 230 XL (2) 50 1788 1040 (6) 70 (6) 380 266 224 400 I300 0000 400 400 230 YO 1788 347 (6) 70 (6) 380 266 224 300 0000 400 400 460 XL 737 422 (6) 35 (6) 190 187 - 000 - 250 460 YO 737 141 (6) 35 (6) 190 187 - =1000 - 250 208 XL 2051 1228 (8) 70 (8) 380 312 256 400 300 250 208 YO 2051 409 (8) 70 (8) 380 312 256 400 300 500

110 230 XL (2) 60 2051 1228 (8) 70 (8) 380 312 256 g I350 300 SOO 450 230 YO 2051 409 (8) 70 (8) 380 312 256 350 300 500 450 460 XL 914 485 (8) 35 (8) 190 231 - 0000 - 300 460 YO 904 162 (8) 35 (8) 190 231 - 0000 - 300 -

208 XL (1) 60 2051 1228 (8) 70 (8) 380 312 260 400 300 500 450(1) 75 2083 1415

208 YO (1) 60 2051 409 (8) 70 (8) 380 312 260 400 300 500 450(1) 75 2083 472

230 XL (1) 60 2051 1228 (8) 70 (8) 380 312 260 350 300 500 450(1) 75 2083 165125

230 YO (1) 60 2051 409 (8) 70 (8) 380 02 260 350 300 500 450 (1) 75 2083 472

460 XL (1) 60 904 485 (8) 35 (8) 190 240 - 250 - 300 -(1 75 974 539

460 YO (1) 60 904 162 (8) 35 (8) 190 240 - 250 - 300 -(1) 75 974 180

208 XL 2083 1415 (8) 70 (8) 380 316 260 400 300 500 450 208 YO 2083 472 (8) 70 (8) 380 316 260 400 300 500 450

135 230 XL (2) 75 2083 1415 (8) 70 (8) 380 316 260 400 300 500 450 I 230 YO 2083 472 (8) 70 (8) 380 316 260 400 300 500 450

460 XL 974 539 (8) 35 (8) 190 247 - 250 - 300 -460 YO 974 180 (8i 35 (8) 190 247 - 250 - 300 -

208 XL (2) SO 1788 1040 (10) 70 (10) 380 326 402 400 0000 500 500(1) 60 2051 1228

208 YO (2) 50 1788 347 (10) 70 (10) 380 326 402 400 0000 500 500(1 60 2051 409

230 XL (2) 50 1788 1040 (10) 70 (10) 380 326 402 400 0000 500 500 145 (1) 60 2011 1228

230 YO (2) 50 1788 347 (10) 70 (10) 380 326 402 400 0000 500 500(1) 60 2051 409

460 XL (2) 50 737 422 (10) 35 (10) 190 295 - 350 350 --(1) 60 904 485

460 YO (2) SO 731 141 10 (35) (10)190 295 - 350 350- -(1)60 904 162

208 XL 2051 1228 (10) 70 (10) 380 326 462 400 (2)250 500 600 208 YO 2051 409 (10) 70 (10) 380 326 462 400 (2)250 500 600

160 230 XL (3) 60 2051 1228 (10) 70 (10) 380 326 462 400 (2)250 500 230 YO 2051 409 (10) 70 (10) 380 326 462 600400 (2)250 500 600 460 XL 904 485 (10) 35 (10) 190 329 - 400 - 400 460 YO 904 167 (10) 35 (10) 190 329 - 400 - 400 - I

NOTES 1 XL Across the LineYOStarDelta 2 RLA Rated LoadAmps(ratedin accordance withARI Standard 590) LRA LockedRotorAmps 3 Wire Size Amps equal125of the ratedloadampsfor the largestmotorin thecircuitplus100of the ratedloadampsfor all othermotorsin the circuit per

NEC 4 Wire size based on copperconductorswith75C insulation perNECTable310-16 Terminal block lugs are sizedaccordingly Use of oversize wiringmay

not lit in terminal blocks 5 Maximumfuse size is basedon 175to 225of the ratedloadampsfor the largestmotorin the circuitplus 100of the rated loadampsfora othermotors

in the circuit per NEC VOLTAGE TOLERANCES 208V-230V min 187VMax 253V

480V Min414V Max506V

I

18

ELECTRICAL DATA Volts Type COMPRESSORModel FAN MOTORS MINCIRCUIT RECOMMENDED MAXIMUM 60 Hz of Oty RLA Starting FLAACWC LRA AMPACITY WIRESIZE FUSE SIZE 3 Ph Start Curro EaSC HP Ea Ea Ea Cire1 Cire2 Cire1 Cire2 Cire1 Cire2 208 XL 2051(1) 60 1228 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 1415 208 YO (1) 60 2051 409 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 472 230 XL (1) 60 2051 1228 (12)70 (12) 380 341 469 500 (2) 250 500 600

12 75 2083 1415185 230 YO (1) 60 2051 409 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 472 460 XL 485 (12) 35 (1) 60 904 (12) 190 352 500 400- - -

(2) 75 974 539 460 YO (1) 60 904 162 (12) 5(12)19 352 500 400- - -

(2) 75 974 180 208 XL 2083 1415 (12) 70 (12) 380 345 469 500 500(2) 250 600

472208 YO 2083 (12) 70 345(12) 380 469 500 (2) 250 500 600 230 XL (3) 75 2083 1415 (12) 70 345(12) 380 469 500 (2) 250 500 600200 230 YO 2083 472 (12) 70 (12) 190 345 469 500 500(2) 250 600 460 XL 539974 (12) 35 (12) 190 359 - 450500 - -

180 1(12) 35 460 YO 974 (12) 190 359 450 -500- -2051 1228208 XL (12) 70 504(12) 380 504 (2) 250 (2) 250 700 700

208 YO 2051 409 (12) 70 (12) 380 504 504 (2) 250 700(2) 250 700 (4) 60 2051 1228 (12) 70 230 XL (12) 380 504 504 (2) 250 (2) 250 700 700215

YO 2051 409230 (12) 70 (12) 380 504 504 (2) 250 (2) 250 700 700 460 904 485 (12) 35 XL (12) 190 225 225 0000 0000 300 300

(12) 35 460 YO 904 162 (12) 190 300225 225 0000 0000 300 2051 1228208 XL (2) 60 (14) 70 (14) 380 504 525 (2250 700 700(2)300

(2) 75 2083 1415 2051 409 (14) 70 700 700208 YO (2) 60 (14) 380 504 525 (2) 250 (2)300

(2) 75 2083 472240 700XL (2) 60 2051 1228 (14) 70 (14) 380 504 525 (2)250 (2)300 700230

(2) 75 2083 1415 2011230 YO (2) 60 409 (14) 70 (14) 380 504 525 (2) 250 (2)300 700 700

(2) 75 2083 472 300460 XL (2) 60 904 485 (14) 35 (14) 190 225 248 0000 250 300

12 75 974 539 904 162 250 300 300460 YO (2) 60 (14) 35 (14) 190 225 248 410

(2) 75 974 180 2083 1415 (2)300 700 700XL (16) 70 (16) 380 525 525 (2)300208 2083 1415 (2)300 700 700208 YO (16) 70 525 525 (2)300(16) 380

700 7002083 1415 (16) 70 (2300230 XL (16) 380 525 525 (2300 700 700(2300(4) 75 2083 472 (16) 70 (16) 380 525 525 (2300230 XL265

300250 300974 539 (16) 35 248 248 250XL (16) 380 460 (16) 35 300 300974 (16 380 248 250 250YO 539 248460

NOTES 1 XL Across the Line YO Star Delta 2 RLA Rated Load Amps (rated in accordance with ARI Standard 590) LRA Locked Rotor Amps 3 Wire Size Amps equal 125 of the rated load amps for the largest motor in the circuit plus 100 of the rated load amps for all other motors in the circuit per

NEC 4 Wire size based on copper conductors with 75degG insulation per NEG Table 310-16 Terminal block lugs are sized accordingly Use of oversize wiring may

not fit in terminal blocks 5 Maximum fuse size is based on 175 to 225 of the rated load amps for the largest motor in the circuit plus 100 of the rated load amps for a other motors

in the circuit per NEG VOLTAGE TOLERANCES 208V-230V min 187V Max 253V

480V Min414V Max506V

19

0

(Wd~) 3lV~ M011 ~31VM

006 009 00 OOt OOl OS L 00 L os 0 Ot

V D m (I) (I)

c D m c D o V

- m m -t o

~

~ m D-

aoao 3~nSS3~d ~3100~

APPLICATION DATA

POINT LOADING

ArMi I 1 5 1

ACWC 45 THRU 10 SC

COMPRESSOR CONDENSER SECTION SECTION

_ 2 4 bull 1

bull CA

J

Model Dimensions Size A B C D 45 91 - - -55 91 - - -70 145 - - -90 145 - - -110 60 40 160 -125 60 40 160 -135 60 40 160 -145 138 74 107 -160 13830 74 107 -185 138 129 107 -200 138 129 107 -215 106 82 106 80 240 106 82 134 107 265 133 110 134 107

1310

1310

~

1

1310

2

ACwe 110 THRU 200 Ie

COMPREIlOfl CONDENSER SECTION IECnoN

4 -

5Imiddot

ACWC 2t5 THRU 215 SC

Model Loadlnu (LBS) Size 1amp2 3amp4 5amp6 7amp8 9 amp10 45 585 765 550 - -55 705 810 635 - -70 660 890 700 - -90 1025 1500 1175 - -110 1195 635 1525 995 -125 1255 690 1835 1115 -135 1255 665 1880 1105 -145 1330 2380 2160 1450 -160 1330 2440 2280 1515 -185 1235 2575 2980 1360 -200 1275 2635 3020 1380 -215 1010 2270 2590 2240 840 240 1115 2550 2870 2715 1125 265 1380 2980 3515 2750 1175

11

II i middot 2 4 lIf 11 to L

21

TROUBLESHOOTING GUIDE

CHILLER UNIT WILL NOT START POSSIBLE CAUSE REMEDY 1 Power off 1 Check main disconnect switch

2 Main line open 2 Check main fuses

3 Incorrect wiring 3 Check the wiring diagram

4 Loose terminals 4 Tiqhten all terminals

5 Control circuit open 5 Check phase loss monitor flow switch circuit breakers temperature control low ambient thermostat low temperature thermostat remote switch etc

6 Time delay 6 Wait

COMPRESSOR HUMS BUT DOES NOT START

POSSIBLE CAUSE REMEDY

1 Low voltage 1a Check at service and unit for loss

b Consult power company

COMPRESSOR CUTS OUT ON LOW PRESSURE SAFETY CONTROL POSSIBLE CAUSE REMEDY 1 Refrigerant shortage 1 Check for leaks -- add refrigerant 2 Restriction in liquid line 2a Plugged strainer - dean or replace

b Liquid line valve partially closed - open valves fully c Expansion valve clogged or inoperative - clean or replace as

required d Solenoid valve partially open - clean or replace as required

3 Low water flow thru cooler 3 Check water flow thru cooler and correct as required

COMPRESSOR CYCLES ON HIGH PRESSURE CONTROL POSSIBLE CAUSE REMEDY 1 Compressor discharge valve partially closed 1 Open valve fully 2 Non-condensible gases in system 2 Operate condenser fans with compressors off If condenser

pressure exceeds saturated pressure corresponding to condenser entering air temperature then purge air from discharge line

3 Overcharge of R-22 3 Purge system while in operation until head pressure reaches a normal level

4 Dirty condenser 4 Clean the condenser 5 Compressor discharge check valve not operating properly 5 Replace if necessary 6 Fans not running 6 Check pressure control setting

CAUSES AND PREVENTION OF FREEZE-UP CAUSES PREVENTION 1 Improper charging 1 Charge per manufacturers recommendation

2 Improperly set safety time delay 2 Check the safety time delay low pressure control for proper setting at the beginning of each season

3 Improper chilled water circulation 3 Use an ample sized cleanable strainer in the chilled water circuit Make certain the strainer is clean to insure full flow and velocity of

chilled water It may sometimes be necessary to treat the water to prevent formation of deposits

4 Not draining for winter shutdown 4 When the system is shut down for the winter remove the drain

plugs and drain the cooler Blowout any remaining water with air

5 Improper pump shutdown 5 Make sure chiller barrel heater is working and flow switch is installed per wiring diagrams

6 Low ambient during air conditioning season 6 Make sure chiller barrel heater is working

NOTE If the ambient temperature is below 32degF freezing can be completely prevented by one of two methods

1 Drain all water from the equipment 2 Add antifreeze to the water

22

START-UP CHECK LIST

Unit Model No

Setting unit

Wiring

Piping

Alignment

Before Start-Up

After Start-Up

Yes No a Vibration isolator used

b Spring isolator adjusted for equal height c If rubber-in-shear isolators are used is unit leveled by shimming

a Power wiring complete

b Control wiring complete c Electric service adequate for load

d Power source voltage correct for motor(s) used

e Motor circuit has proper size fusetrons f System wired per diagram

g All lead connections tight h Wiring complies with local codes i Flow switch operation

a Piping complies with applicable codes b External piping independently supported c Chilled water lines insulated

a All belts adjusted and checked for tension b All pulleys checked and adjusted for proper pitch tightness and

alignment

a Open compressor discharge service valve b Open liquid valve(s) c Open suction and discharge valves to pressure gauges (if supplied) d Check rotation of all fan motors e Start auxiliary equipment (pumps fans etc) f Is crankcase heater operating Operate 24 hours prior to unit startup g Check the compressor oil level through the crankcase sight glass The oil

level should be to the top of the glass If the level is low add oil in accordance with the directions in the maintenance instruction

h Check all control settings as specified in Table 1 I Air purged from chilled water system

a Check high pressure control b Check oil temperature safety switch c Check and adjust low pressure or temperature freeze control d Check and adjust operating thermostat e Check and adjust low pressure operating control f Check and adjust expansion valve superheat g Check and adjust capacity control thermostat

23

OPERATING DATA CHILLER Voltage L-1 L-2 L-3 _ Pressure Gauge Readings 1 Suction psig 1 Discharge psig 2 Suction psig 2 Discharge _ psig 3 Suction psig 3 Discharge psig 4 Suction psig 4 Discharge _ psig High pressure switch setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-in) psig psig (Out) 4 (Cut-In) psig psig (Out) Checked Setting - Yes - No (each circuit) Low Pressure Switch Setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-In) psig psig (Out) 4 (Cut-in) psig psig (Out) Checked Setting -Yes -No (each circuit) 1 Oil Temperature Safety Switch Cut Out 2 Oil Temperature Safety Switch Cut Out 3 Oil Temperature Safety Switch Cut Out 4 Oil Temperature Safety Switch Cut Out If Star-Delta start time delay is seconds Temperature of air entering condenser F Temperature of air leaving condenser of Temperature of chilled water entering chiller OF Temperature of water (chilled) leaving chiller F Chilled water pressure entering chiller psig Chilled water pressure leaving chiller psig

MAINTENANCE Good maintenance practice will prolong the chiller life and will reduce the Ask of system breakdown and expensive service calls

A weekly check of the ACWC-SD unit requires only a few minutes and will prove beneficial in insuring long trouble free operation

WEEKLY CHECKS- with unit in operation for at least four hours 1) Check compressor oil level - At least above 12 of sight glass 2) Record suction and discharge pressures

Typical Condition R22 Ambient 95degF Return water 55degF Leaving water 45degF Suction 62 psig Discharge 270 psig

3) Record ambient temperature 4) Check liquid sight glass

Make sure liquid is clear - no bubbles 5) Check that all fans are running 6) Check entering face of condenser coil for cleanliness 7) Record voltage at unit

All of the above can be performed by building maintenance personnel If oil levels are low or any of the above checked items are questionable consult a qualified serviceman

At least once a year a qualified serviceman should check unit oil levels superheat and control operation

DUNHAM-BUSH USA

P l) bull 130 xUtUC t01 Bmgess RO~ Harrisonburg VA 22801 Phone (540) 434-0711 FAX (540) 434-~ 2118

wvvwdunham-bushcom Form No 6184

Page 6: ACWC-SD - · PDF fileACWC-SD • Screw . Type • • • Air-Cooled Packaged Chillers •• Installation, Operation, and •• • Maintenance Manual • • • •• DESCRIPTION

KEY TO WIRING DIAGRAM INDEXING SYSTEM

The wiring diagrams and sequence instructions on the following pages have been devised to simplify the understanding and tracing of circuit theory The following key shows how the indexing system can be used

12 Line number on wiring diagram

[12] Line number in text

(R5) Component identification symbol in text (Relay 5)

[E] Normally open contact - line number location

[E] Normally closed contact - line number location

Holding coil - line number location

amp Note number

SEQUENCE OF OPERATION (TYPICAL) MODELS ACWC 90-135 SO

The following sequence of operation is typical for all ACWC SD Models Refer to the wiring diagram furnished with the unit for specific information ( ) Control Identification Symbol [ ] Circuit Line Number

Important Notel With all the control circuit switches (SW1-SW3) in the off position and the staging thermostat (T1) to its highest temperature Terminals 2 and 4 on the Terminal Board (TER5) must have 115 volts supshyplied for a minimum of 24 hours to energize the compressor crankshycase heaters (CCH1 2) [6 8]

Preliminary Sequence Close the main power disconnect switch Check to see that the red indicating light on the phase loss monitor (PLM 1) is lit (Note There will be two phase loss monitors (PLM1) and (PLM2) on dual power block models) This light must be on to indicate proper phase rotation for the compressors If the light is not on disconnect the main power and reverse any two phase legs at the Main Incoming Power Terminal Block (WARNING DO NOT REVERSE THE LEADS ON THE PHASE LOSS MONITOR FOR THIS WILL ALLOW THE COMPRESSORS TO RUN BACKWARDS CAUSING SEVERE DAMAGE AND WILL VOID THE COMPRESSOR WARRANTY)

The crankcase heater relay contacts (R3) [6] and (R4) [8] are closed and are supplying power to the compressor crankcase heaters Power is also supplied to the chiller barrel heater (CBH1) [13) the optional receiver heaters (RH1 2 [1011] and the optional convenience outlet (CO) [14]

Control power goes through the control panel circuit breaker (CB1) [8] and field supplied remote time clock [36] Check to make sure time clock contacts close during occupied modes

Start up the chilled water pump The water flow is confirmed when the water flow switch completes the electrical circuit across Terminals 15 and 16 [38] on Terminal Board (TER5) Terminals 17 [47] and 18 [49] provide an interlock for the water pump starter(s) when either compressor is in operation Set the thermostat (T1) to the desired leaving water temperature (eg 44degF) Set point adjustment is acshycomplished directly on the control

Place the three (3) control circuit switches (SW1-SW3) in the On position thus energizing the balance of the control circuit [23] [33] [36] The system will be in the Time-In mode for five minutes before the first compressor will start

The low ambient lockout thermostat (LAT1) [38] and temperature freezestat (T2) [38] must also be satisfied to allow compressor operashytion

Stage 1 Starting Upon demand for cooling thefirst stepof the staging thermostat (T1) will be to close energizing relays (R1) [61] time delay (TD1) [60] and the optional time delay (TD3) [62] If all the safety controls and switches are closed (see Safety Controls section for more detail) the control

circuit for Compressor No1 will energize allowing the compressor to start Relay (R5) [20] will energize closing the normally open (NO) set of contacts [23] which energize the liquid line solenoid valve (SOL1) [23] Another set of NO contacts on (R5) [20) provide a series intershylock with all the safety and operating controls which will lock out the compressor if any safety trips during normal operation (See Note 6 on Wire Diagram) The last set of NO contacts on (R5) [48) provides an interlock circuit for the water circuiting pump(s)

The fan contactor (C13) [23] will also close supplying power to the side of the fan cycling pressure controls (See Power Wiring Diagram)

Note The fan motors are controlled by their own fan cycling controls and will cut in at different factory set head pressures

Time Delay (TD1) [601) has two (2) sets of contacts the first set of (TD1) [19] normally closed (NC) contacts provide a 30 second jumper around the low pressure control (LP1) [20] to prevent short cycling during start-up The second set of (TD1) [24) contacts in the NC posishytion power the unloader solenoid (UL3-1) [24] which hold the comshypressor in the full unload position for 30 seconds After (TD1) [60] times out (30 seconds) the contacts for the unloader solenoid (UL3-1) open and the NO set close which energize the relay (R3) [25]

Stage 1 Modulation Upon energizing relay (R3) [25) the crankcase heater (CCH 1) [6] is de-energized and the NO contacts of relay (R3) [45 48] are closed allowing the thermostat (T1) to energize the load solenoid (UL1-1) [45) and the unload solenoid (UL2-1) [481] upon demand The opshytional time delay (TD3) [62] is used to bypass low pressure control (LP1) [20] for five minutes for low ambient starts

Stage 2 Starting Subsequent to the start of Compressor No1 an approximate five minute time delay is incorporated into the microprocessor After this time delay and a further call for cooling the second step of the stagshying thermostat (T1) will close This will energize relay (R2) [58] time delay (TD2) [57] and the optional time delay (TD4) [59] If all the safety controls and switches are closed (see Safety Control section for more details) the control circuit for Compressor No2 will energize allowing the compressor to start Relay (R6) [3D] will energize allowshying the liquid line solenoid valve (SOL2) [331] to energize Relay (R6) [3D]will also interlock the water pump starters and the safety controls the same as Compressor No 1 circuit

The fan contactor (C14) [33] will close supplying power to the line side of the fan cycling pressure controls (See Power Wiring Diagram)

Time delay (TD2) will provide a 30 second jumper around the low pressure control (LP2) [30] and will energize the full unload solenoid (UL 3-2) [34] for 30 seconds then energize relay (R4) [35]

Upon energizing relay (R4) [35] the crankcase heater (CCH2) [8] is de-energized and the NO contacts of relay (R4) [46 49) are closed allowing the thermostat (T1) to energize the load solenoid (UL2-1) [46] and the unload solenoid (UL2-2) [49] upon demand

6

SHUTDOWN SEQUENCE

Stage 2 Shutdown Stage 1 Shutdown

After both compressors have unloaded fully and the leaving water temperature is still lower than the setpoint the second step of the thermostat (T1) will open and de-energize relay (R2) [58] providing an approximate five minute time delay again integral with the microshyprocessor has expired subsequent to the start of Compressor No2 This will close the liquid line solenoid (SOL2) [33] and turn off Comshypressor No2 Compressor No 1 will load and unload as required Compressor No2 will not be able to restart for five minutes due to integral time delays

SAFETY CONTROLS

The unit is protected by the following safety controls

1 High Pressure (HP) 2 Low Pressure (LP) (automatic reset) 3 High Discharge Temperature (OTS) 4 Compressor Solid State Module (CSTM) 5 Low Water Temperature (T2) 6 Low Ambient Thermostat (LAT) 7 Compressor Starter Overloads (OLH) (optional) 8 Phase Loss Monitor (PLM) 9 Control Circuit Breaker (CB1)

If any of these devices should open due to abnormal conditions the compressor(s) will automatically stop All controls must be manually reset except low ambient thermostat (LAT) and phase loss monitor (PLM) The individual compressor safeties (HP LP OTS and CSTM) contacts are found on Lines 20 (CTT1) or Line 30 (CTT1) The other safeties listed above are discussed in the preliminary sequence section

If the leaving water temperature is still lower than the setpoint the first step of the thermostat (T1) will open and de-energize relay(RI) [61]This will close the liquid line solenoid (SOL 1) [23] and turn off Compressor NO1 as long as it has run for approximately three minutes Compresshysor NO1 will not be able to restart for five minutes

FIELD CONTROL WIRING

In addition to 3 phase power (and optional 115 volt control) wiring described above the following control interlock wiring is recommended The as built control schematic provided with the unit provides detailed information Typical control schematics are as shown on pages 8-15

1) Alarm Circuit -Terminals 6-13 (2 per compressor circuit) can be used to trigger remote failure lights or alarm bells in the event of a refrigeration failure

2) Time Clock - All unit on-off control should be done through terminals 15 and 16 An open contact shuts down the unit Time clock night shut down and energy management shut down should all be done from these terminals and contacts should be applied in series

3) Flow Switch - The flow switch contacts should be installed between terminals 15 and 16 and be in series with time clock contacts

4) Chilled Water Pump - The control of the chilled water pump must be worked out by the system designer It is necessary for the pump to be on during any compressor operation and terminals 17 and 18 should be used to energize the pump starter However it is likely that the pump should remain on throughout all occupied operation or even at night for freeze protection Terminals 17 and 18 should not be the sole means of controlling pump operation

STARmiddotDELTA STARTING OPEN TRANSITION (OPTIONAL)

Typical For All Compressors On initial call for cooling staging relay (R1) holding coil will energize The (R1) contacts 7-4 close energizing star contactor (S1) and the five second transition timer (TD5) Transition contactor (S1) power contacts close tying the center legs of the compressor motor windings together into Star (WYE) configuration At the same time (S1) NC (Normally Closed) auxiliary contacts open preventing (C2) from closing (S1) NO (Normally Open) auxiliary contacts then close energizing contactor (C1) The (C1) power contacts close applying power to the

compressor winding (C1) NO (Normally Open) auxiliary contacts close locking (C1) in the energized position The compressor operates in the Star mode until (TD5) transition timer times out (five seconds) at which time contacts NC open and de-energize (S1) Star contactor (S1) NC auxiliary contacts close (TD5) timer NO contacts close energizing compressor contactor (C2) power contacts close thereby completing the Delta wiring configuration Compressor contactor (C2) NC auxiliary contacts open preventing (S1) star contactor from energizing until the next starting sequence

7

--

exgt

LE

GE

ND

m

rrbullbull

saN

OI

IlIG

CI-

Z

CO

HT

AC

TQ

ftmiddot (

0

[5

10

1t5

el

) C

ON

TA

ClO

middot A

NS

(C

UlT

middot pound

AM

III

bull C

ON

TO

L

(C

UlT

C

UtC

UIT

Ulaquo

III

H

IAT

EIt

I C

HllL

rU

lU

[AT

III

CU

Ne(

ASE

H

un

co

U

OIl

ll

SOL

ID

TA

U

MO

OU

Lt

H

US

UII

lI[

con

RO

L

LOW

Abullbull

IN

T

[

twO

fI

lO

W

nul

tt C

ON

TIIlI

OL

OIL

TU

II

r

UIIl

I(

SA

HA

S[

0

1$

M

ON

t T

O

lllE

LA

Tmiddot

tTA

GIH

O

1t[

LU

-U

CIT

Y ~OL

bull

CI

l

tC5

I H

el

C

Ubullbull

e

lHI

CC

HI

esr

P

I L

UI

VI

enst

P

LU

11

0)

(L

AY

middot tN

Uft

LO

CK

(

L[N

OIO

middot L

lOU

IO L

INI

SWIT

CN

CO

W

UD

C

C

UIT

S

SWIT

CH

ST

EN

fH(

MO

ST

AT

middot S

[OU

[Ne

EIt

TH

UM

OS

Tn

-L

OW

n

llI

IUU

[

TtIt

WIN

AL

10amp

1110

cu

no

wE

It

UN

I J

SO

LI

w

10

Tl T[l

Il

S

Tl

Ufl

Ul

10

0

-

CT

OII

I

WIl

WO

T

lM[

HU

T c

alli

CO

NTbull

bull L

OW

Ipound

n

LO

CC 0

1

TO

T

IllS

I

ond

tlt

UN

Lo

ao

t

OL

(NO

ID bull

(O

M

no

ll

Ul

ImiddotZ

~(

tU

IIL

T

IIS

VI

O

I

_

-~

OIO

HA

l

ell

C

UtC

Ul

[

amp1

(( -

(cri

VE

lli K

uru

en

C

IAC

Uff

A

UK

(jII

f bull

CO

[

I(

C(

OV

TL

lT

CI

I (O

NU

OL

If

Jll

AIr

IS

HO

UA

W

(fIA

S

LL

Tl

LO

AO

LI

T

(III

WO

STA

T

0

middot

5

O

(III

LO

AO

fU

UIS

LImiddot

H

OT

L

IGH

TS

H

IUC

IIY

[1II

H

[AU

IIIS

~ jllf

M1

III[

Cll

[

H

[U

t

US

UII

ll[

CO

NT

IIO

LS

~tCt

JVII

l N

(AU

III

14

(0

1

T

O)

TO

wI

DtL

AY

amp L

OW

U

tu

LO

CK

ou

r rt

(

O(L

IN

SlT

IO

C

OH

TA

(TO

Il

(O~USO

C

OH

O

lll

bull iT

A

OlL

C

Ol

CO

MV

[Nf

epound

o

un

n

Ctft

CU

lT I

DE

TA

IL

A

SlA

M

DE

LTA

ST

AR

T

O -~

OA

~ 5~U

Z

OI

Cl

U

I 14

(I

amp

~

NC

f

cl

AU

I

51

ZtA

LU

TOO C

21

NO

~~

bullbull

N

WHT

I---

I

l I J

II

A

CN

lCU

lT

If

OOHAI~

l

~i1

WH

It[

-

OI

ON

AL

r---

----

---

-I

Q

WT

I lt

raquo

I I L

JI

bull bull

I I

0

II

-

lJ

_ Ij

lf

I

cal

II

iOO

w

shy

) C

it

~

WTI~AL

r --------------------------------

Iamp

I

_l

[0

0

I

OO

CM

lL

00

LO

II

cu

U

II

bullL

~J

It

_U

I

TH

u

I

HT

I~

r-~~

~ --

-I=

=~==

=~I

11

2

N

~~~

~--

----

----

=~

I

-lt

l

= I

en

co

o J

rO~

2

~L

----------

-

-oS

f

I

r--shy

J

on

T

O)

vI

Q~~A

J T

Ot

L-

ll~_

f

1

II

CU

H ~

~OI

L1

-i

r---

----

-

~

10

rc

I

bullbull

lf

OIS

ti

l W

I H

Z

01

11

1

-J

o

u

L

shy

0bull

-

0 T

1

111

A -

bull 0

[0

HT

I

ll II

rgt ---

-ij

---

ITl~ll

t

1amp

I

1t

D

MIN

I[D

11

~

ill HTAILmiddot~

O

LM

I 01

1

OL

HJ

III0

1l~

tM

Ow

N

CI

amp

tt

I w

lO

OIO

HL

---

__

J

O ~

~Ll

~

tB1

It

CI)

n

IS

-1

M

k

V

Io

Jmiddot

r---

1

we

14

-4

I

Mill

I

CO

MPR

ESS

OR

C

IRC

UIT

I

Til

bull ~

r-

so li

e II

It

S

tON

L

N

O

fll

II

If

II

~

s~

o

oc

gt

(I)

r in

n

100

00U

lz

--I

~o

e

0

r ce

cn

shy0

0

Z

Ggt

bullbull bullbull bullbull bullbull bullbull bullbull

r~T~-

ICt

MQ

Teuro

CO

MT

It01

I T

IM C

lot

ll

~---

Cl

ll

(O

41

(

flO

W

5Wlf

CH

~

I

Olt

CO

NT

AC

TO

C

OIL

S C

I-I

bull C

tS

AN

D S

t sn

N

OW

IIt

Dll

QU

0

1 C

OM

UC

TI

I

111

114

0

(

U

II

NO

f T

O I

(

C

uNO

IO

ON

UtI

se

CO

HO

UI

li

D(

1

A

ND

1

n

WP

(IU

ult

l S

(NIC

tf1

I

LO

CU

ID

1M bullbullU

O

UT

UT

r-

----

shybullbull

0

11

UO

V

HA

Il

LO

IS

raquoON

TO

S

TE

lurN

AU

bull

AN

D

0111

IIC

O(

I A

ND

A

U(

Cfl

YpoundL

Y

So

C

rt

TO

0

0 M

AN

UA

L a

ll H

TO

tNT

AN

D

~10l

IA

NO

M

TII

UC

TtO

NS

II

rCO

tNO

m

IMIT

AL

CO

H

laquo

0

U

TI

I It

4

Ishy

C

OW

III

ISO

R

MO

DU

LES

dC

NO

MmiddotA

U

VA

TC

I

D

U

1111

WIL

L A

LSO

LO

C_ O

UT

(

let

Umiddot

I C

AL

L

WH

IM

IAI

TY

flit

TH

[I(

CO

Nmiddot

I

OL

I CA

Jrf I

I II

EM

T

IT T

Uft

I1

tW

ITC

H bullbull

0

VO

NIN

IL

f PO

C

Obullbull

bull

I w

UII

II

I

C

IL

Llf

i I

ITA

f[1

II

ItV

N

IWIT

ti r

raquo7

~Slt~1

~~~~( 1~~~~tlDOO

CO

N

CT

O

WU

UH

O 0f

II C

OW

bullbullbullbull

~~1

II

bull

LL

TI

lIT

AT

0

N

O 1

0 O

CA

TID

1

1 I

I IIl

ETU

IIPt

W4T

P

LU

WHE

N u

TI

It N

OT

lU

u

rD

ttl

III I

ICO

Ma-

aU

0 11

nM

H

u

l

UN

I()1

II M

UST

HA

V(

SH

llL

DID

C

AU

I

LO

Me

T

II

no O

R

ItUM

WT

M

ItO

WI

L

IAH

to u

ri N

T I

T H

-

ITbullbull

O

N

ft

0

-

011

II~T

K

ITI

GU

ION

An

ON

S

o H

O-

ON

G C

OI

-W

it

11

N(

NO

6 N

c

CO

NU

ClI

W

If

lIN

( N

O

o N

0

CO

NT

AC

TS

WIt

K

liN

t N

O

6 N

OT

t I

TH

L

Nt

NO

Y S

UI

-I

IS

5_

1

~

~

no

~ I

I I_

VLOA

Or- I

I ~~

vumiddot

S1 so

CO

Hit

so

0

amp

g A

SI ~

I

1

7100-

I -I

I 01

10

OH

0

10

f T

AN

I V

I

] CM

NG

( av

rlt

10

0 O

K__

ST

AG

(

COD

lJ-

L7

00

~It

A

lIT

00]

VL

I fi

ll

14

1

10A

O

f

_ III

rC

OH

O

In o

y

00bull

00

10 ~

0

10

CO

Ol

C

bull

] 4

U

rr

COL~

bull Jo

un

J

W bull

C~P

OJ [

ou

-t

urO

NT

01

CO

l0

1

N

Omiddot

~ ]

(jCO~_

0

)

un

ll

n ~

T

I 11

I1

III _~

n

~

amp

7

10

II

01

u II 17

II

0

II

01

IS

-I

-lt

sE

o

0 c

raquo

CD

r iii

0

~O

U

lZ

+-1

~

tI

t

0

r QE

CIJ

-c

tl

Z

Ggt

lt0

bullbull bullbull

bullbull

bullbullbullbull

~

o

tUN

oa

lllO

_--

-

shyC

t-4

CII

C

cn

bull

tlN

I

CC

HImiddot

t

csnu

middota

--1

LA

T

loP

a

01

11

-1

111

111

IIImiddota

It

4

IOL

IS

IW

Imiddot

I

I T

I n flbull

bull

TO

middot I

st

U

LImiddot

a

Oft

lo

tL

LtG

EN

D

CO

NlA

CT

IM ~

CO

lllf

lllt

UtO

JII

CO

NT

AC

TO

CII

CU

fT

IIIC

AICC

III

CO

NTJ

IIOL

CIC

UIT

U

NImiddot

HU

TI

eNU

LlII

I

Il

I

AU

It

C

NlaquoC

AU

NC

An

C

O

UIO

10

LIO

T

AU

N

t U

SU

I C

O T

OO

L LO

W

eT

fM

llltM

OT

AT

L

OW

Hl

III

UII

I C

Oft

TJl

OL

OU

n

ru

ulltl

A

nT

T

HA

-

0bullbull M

OH

IfOIt

fl

lLA

Y I

AO

INI

MU

C

AN

cn

CO

fTltO

Ibull

ItIL

A

INT

ILO

CIC

OL

EN

OtD

Ll

OU

ID L

INt

Cc

ulT

MOO

ULIE

C

NIC

CA

SE

ItS

C

(

OM

II

IOII

(lI

IieLf

W

I eM

-

UIE

R

TH

III

OIT

6Tmiddot S

lOU

lC

U

MC

ot

LOW

TlM

e

U1

T

lER

bullbull

L l

OA

JIIO

middotCU

lTo

tJ

II W

UU

Nt

TI

M

AL

IO

D

oC

0It

1 U

IIN

t T

IMe

OC

LU

middotCA

II C

ONT

a

LOW

IU

t L

OCK

OUT

NPD

WIU

UN

LOA

Olil

t 1

0L

(NO

I0

C

O

III

OIl

lI

cn

CIJ

tCU

IT

UII

lEIt

ft

EC

poundIV

E H

IAI

C

Ol

(C

UIT

1I

IUIIl

I1II

CO

NY

(NIE

NC

E

OU

TU

T

CU

I C

ON

nlo

0

1

AN

$ M

ill1

1

HO

YIll

MU

II

lLT

I l

OA

O

LlI

lIIT

T

H(

O

ITA

T

OL

O

VC

LO

AO

MIA

nl

L1

lI1

~HAII

LO

IS

MO

NIT

O

L

Imiddot J

~fOT

L

IOH

TS

1

1

IC

IIV

E

HE

UE

ItM

lIC

tmiddotl

rC

IIV

E

MU

TlI

t l

tIIS

UIl

l(

CO

NT

ItO

LI

T

lmiddot1

C

CC

lvllt

N

EA

fllt

T

lW

OS

TA

lI

TO

Jmiddot 4

T

INe

H

LA

Y

LOW

In

vlt

l LO

C

OU

T

1O

t-1

ft

lll

D

UA

Tmiddot

TA

SIT

ION

C

ON

TAC

TO

Ill

$middot

1

CO

C

O

(

lIO

C

ON

TA

CT

O

T

A

Dn

u

CO

WC

tllltN

CI

ount

T

DE1AIL~

ST

AR

D

EL

TA

S

TA

RT

r

2

~f

10

t10

II

amp

II

11

II

)

1IllI

1IU

--shy

OW

E

IV

-

utv

lO

f

I I Ibull

A

UR

C

IlltC

UIT

C

IRC

UIT

ALA

NlC

UfT

C

lflC

UIT

I I

I

~li

IT

I

Ot

ON

AL

il------~---l

-

tL

J --

--

C

it

prIlgjf~

II

ell

I

I

IfB

I

t

---------~~-------

__

~

L_ -

7 -

-r--

et

r

I

II10

-I

CII

-lt

PL

1amp

I I

II b

I

L _

__

J

II 3

2I

oo

II

Qraquo

~

IS

lI

(

)r-

t-_

_ o

J_

_

O

TIO

L

I ~~

--~-

I

I CD

oL

__

__

__

__

__

CO

I- f

_

JI I

t degz

OI

OIl

lAL

r-

---

IS

r

-l

0

I

I

+10$

IL

KS

I T

e

0 Lr

I J

II

T

ITI

lOL

l 1

40

bull (C

IS)

TO

bullbull

lD

A-

~ -

r--

-~l

)~II

I

~G

__

_~L_J

0

O

HA

I

~ -

-Ill

-

---

-10-

--

~E

II

cn

-C~

II

Z

0

G)

Il

l~

r- I W

lllltO

WH

IN

JU

L1

l0

I I

I

OL

M

OL

MI

OL

I ~ro

o

jo

o

Jt

JI

L

OT

10N

AI

II

0

(01

0 CO

MPR

ESS

OR

C

IRC

UIT

~

27

III

gt

0

IIA

IO

amp1

)amp

1

1

II

~

I rA

I

TA~

D

ELTA

STA~T

CONP~E~)

CU

lT 2

~

f

bull ]

A

U

4 ]I

IUft

middotJI

Mon

tUPlOI

NT

lOA

Ot-

-O

I

01

0

]

(N

GI

011

1

00

CT

AN

)

40

00

HN

a

_N

I

J00

I -

It IC

y

TO

I

I I

I

~

oiiO

NA

t

I bull bull

wi

i

lOa

r~TT~-

I M

OT

I C

ON

sr

0

llItt

(

co

ce

OZ

UK

1

11

_JO

I I

)--11

--

- ---

-

IJI

LD

~

I

A

CK

lS

C

UK

I

IL

UO

A

TO

O

WH

IT

1

L

OW

SW

ITC

HJl

AL

D

00

IZ

I

f

1It-

-

rl__ u-

poundL

J f

aT

ION

AL

TI

WfI

OO

f

~

ff

I

Dill

C

ON

TAC

TOIlI

C

OtL

S (1

middot4

(IS

middot14

A

ND

II-

I

01

1In

N

O

Wl

0

51

11

~

CO

NT

AC

TS

I

fH

IO

Uti

IS

N

OT

TO

IE

al

llauN

DIO

O

N H

I Sr

CO

NO

AIl

lf

StO

l

f

I

TI

AN

D

TI

TI

U

I

IIN

OII

t

0middot

f1L

OC

AT

IO

IN n

lll

GU

lUT

r-

----

shy~

(I

G

lIt

no

v

HA

I

LO

SS M

ON

IO

nf

1Na

bull

AN

D

ON

rc

I(

CO

M(

f A

IrfD

I

lItU

rC

TIY

(U

00

-

5

E

[CO

OIO

lItc

rlll

TO

0

0

AN

UA

L

t

OIN

T A

Na

f

oo

IlU

COfrt

TO

I U

ND

IN

Stt

UC

TIO

trl

r

co

rNH

D

01 11

raquoIN

ITIA

L

CO

NT

lIIiO

L

fII

I0 I

UT

IS

a

jshy

orshy

10bull

CO

M1

II1t1

Ol

MO

GU

LI

I N(

tN-a

UT

OM

AT

lC

I 1I

lfla

n

flS

bullbull

11

A

LSO

ampO

eMmiddotO

UT

luer

llt

middot I

no

C

AL

Y

WH

IM A

N

IUIT

T T

IIII

P

T

MU

I C

ON

egoo

IT

flO

LI

CA

l

ItU

I1 I

T

TU

NIN

G W

ITC

M

0

~r=

0 I

lIO

Wlf

lIT

A

L

fOtt

CO

lI

tbullbull

w

ITC

H_

I

on

WO

Nlf

lIT

JII

IL

POllt

COW

bull

I In

degz

r+-i

~~

t

u ~o

1 ~rI~~

~~

~~TtIc~~I~D

1

SW

lTC

HI ~

C

OIfT

AC

TcU

t W

lItN

t C

OM

bullbull

H

To

lIL

b

l

0t~~1

0

1

CO

tfC

TO

H

I

lIt

C

ltbull

IIT

C

~r-

bull

WM

IH

-

2

N

OT

1V

l

rD

wllI

I[ to

IlIC

OM

n

I W

I

It

I

fjC

Ofl

P

tE

CJ)shy

t W

IN L

UI N

OT

SU

PL

ID

W

IIIIC

O

J

lleo

W

ti

l

LU

KT

IT

10- A

ND

10ft

II

v

C~

LO

CA

TU

I II

1t

11V

MI

_T

at

I

z10

I

T

lNH

A

TU

RC

S

lNS

OIt

MU

tT

ve

IL

OID

C

IL

C

()

11II

L

AT

I

AT

10

_

A

U

IIIT

I0middot

PCA

LOW M

I_ lO

TI

I bullbull

n

II

DES

IGN

ATI

ON

S

II

CO

NT

IlID

t I

NO

-o

MO

LD

INfl

C

OIL

It L

tNI

NO

0

Q

N

C

CO

NU

ClI

W

ITH

UN

I N

O

01]

0 co

O

f

11

~

I

ILK

n

e

s IA

UL

It

ibull

o O

CO

NTA

CTS

w

nw L

INI

NO

01

fA

0

~

fItO

TI

LI

I N

O

v

A

II

~ ~ bull i middots

~

~~ - ~

~

1- I J I J I I I I I I I I I I I I I I L __ J

I

a bull bull a bull bull

I I I

_J

r------~

=~I = ~ ~ bull ~ I I

~

as coe ruq SV~ siapow ~NI~IM lO~lN03lV3ldAl

i 4

_

a

~FirI1 u~III - I I

~ 1I

00000 -

I=II~I~~~~raquoIIIItIII~ampI~

as ooz nJ4l sv ~ siapow ~NI~IM lO~lNOgt TVgtldAl

bullbull bullbull

bullbull

~

jgt

lpoundIt

ND

II

co

----

----

----

----

----

----

----

----

-

r-~-middot--=-~~

~

bull a

~

at~04

5

---

~1I

A

~n

bullbullmiddot-shy

wo

_-

bull

lIt

C-

I C

Cf

aC

TO

Ic

ow

n

CC

eM

ca

~C

M

OD

IAI

CI

T-

CO

IITA

CT

oa

bullbull

CMCU

rT I

ItIM

IA

co-l

to

c-c

VIT

C

I

rr

c

AfE

bull r~----Ef1

POW

I

III

IQ

W

Q

tIL

UT

I1I

U__~

J

COt

I

LD

W M

lMtr

f nc

IIO

ff

0

N

LO

W

C

OIIT

INM

I I

CO

M

US

ON

C

NC

UIT

II

II

-~

_T

shy

C

O

NU

SO

II

CIN

CU

IT Z

II

D[TA~

-

ST

AN

D(~TA

IT

AII

T

0

u III

r

amp

II

-~

If

10

MA

MI

eN

talI

Tco_

~

STA

N D[~TA

ST

AII

T

~

CIS

-I

LA

~ 1-4

nmiddot

00

-

-II

1t1S

-1 aw

o fI

fl

U- I -~ Ci

Pi=

i

t

shy

~

iii

i

iii=

ii

-

-shyiii

ClL

n

TU

U

LOt

e

bull It

lLA

Yn

C

AM

Im

CIII

IID

L bull

CU

_C

Abull

fl

lUY

_f

tMO

ea

UY

middotIO

CI

lO

Ll

t

NIU

_L

N

CO

WU

UO

ItC

U

llT

l bullbull 0

1middot

lit

TMC

MI0

8TA

T tc

_lt

CIl

it

11

II

_

middotLO

W

TII

IfN

T

UIlI

C

nll

-

D-C

UlT

QIIU

tW

n-T

PII

IU

LIO

MI-

AC

TC

Ntf

Wi

MI

II

II

tY

middotCM

OO

C

LOW

HIe U

(O

Uf

lIl_

L

OA

M

1OtI

1tO

lD

CO

OA

CM

UtT

1M

C

lIY

Dl

NC

Afi

ll ea

-tU

lT 1

ItUbullbull

lI

oo

ww

lItt

lffc

e O

Un

n

cT

IlG

I

Ie-

~U

IIIC

CIV

P

1T

1lt

C

bullbull

Off

AT

tw

ebullbull

ampOW

IC

IUT

~-

4ti

iT

~

co

ww

O

UfU

T

DITA~

A

ITA

A

OEL

TA

IT

AJI

IT

co

rn~

e

I

1amp

ItmiddotI

~ bull

I I

I

I r

~

bull Iamp

II

I ~

I-

oJ

II I

IrIf

I I I I

s~

o

-I I

ltDc

() raquo

L 10

V

i

()

~O

to

U

lZr0

t2

llJ

IL

C6

J=

_J

~-1

f

II

c 0

II

N

ge

cno

c-

II

Z

Ggt

If IO

IC

IIY

II

IIR

III

IJt

T H

llII

A

Il C

Olaquof

U

TMIbull

~LDM

fI

lAR

PM

Iamp L

Oll

lTV

ii

iLii

Uii

ii

~

U3

I iL

iii=

i

Uii

u

i

O

(no)

T

bull II

1

IOA~

bullr

~ I

[gtO(]O

~ i I Ii i 2 ~ ~ ~ i a bull il 2 ~

iiibullbullbull

~ I ~ I I I ~~ =l ~ iI I ~ I I I It I 1111 amp ~~

as ooz nJ4l SP~ SlapoUII ~NI~IM 10U1NOl lVlldAl

-------

---

TYPICAL POWER WIRING Models 45 thru 70 SC

----

rYl31I01 I

-Ii --ti-

_ I ~_-

~ lniJ -

LIIbullbullbullbull PC _ amp-II _--- ~

TYPICAL POWER WIRING Models 90 thru 135 SC

- --- _ Tt

~rfh c~

tP ~

_III ~

I r-- ~- IIlJ

bull - MIl Mf __ bull Ie_~--~ _shy- shy16

---

----------

TYPICAL POWER WIRING Models 145 thru 200 SC

_ --1a1 IIUrI

middotrFti~v_ bull I

i~i ~~ TaII IIOMLI ~tN T 100 WTIOII 011 lilOOCL a

~ t1

tI bullbullbull

L

i I r-~

I r

~ ~ ~ III

2 ~ ~ ~l

- ~IlD I hJOHr eo teO acshyt CmiddotClM ~ CIKUr1 --

TYPICAL POWER WIRING Models 215 thru 265 SC

ItUU 1D Wll1U1I fIa -rMI

rt-h I -au 11 1_ i r~ rt-f

-i rn f1 ft fi i- llil bullbull c~ I bull c =

~~~ ~i~-~

~~m

~~~CI1 R~~ ~ ~~ ~llAi4I

luv~ bull ~uf LL~~-

~Mfl l~t IrMiA

a I III nII I bull it d

~-t--J I Lll-l~j ~nL4111 WlJj== lit-

I bullbullbull I

UGEND

~

~l OJ

- c~

~~~---

~)~middotI

I

L _~~~ L _I__~_J I ~ (11_1 ~ H~ CUlTMIt tffC_) Ll N

-r_ 0 1ItCIIIl0AI lllQUlllCo as -0- bull bullbull fI PC 110 lNJCllII a Olil1100pound1 II 111 el 1101 ItCOU_ 011 IIOOIL140

I 011 CI-( H[ (0110 (fMCun ubullbull --- l(lD IMbullbull Ntlf 110 e414-7

--CTOttbullbull

2

17

ELECTRICAL DATA Model Volts Type COMPRESSOR FAN MOTORS MIN CIRCUIT RECOMMENDED MAXIMUM ACWC 60 Hz of Qty RLA Starting FLA LRA AMPACITY WIRESIZE FUSESIZE

SC 3 Ph Start HP Ea Curro Ea Ea Ea Circ1 Circ2 Circ1 Circ2 Circ1 eire 2

208230 XL 1788 1040 (4) 70 (4) 380 252 - 250 - 400 -45 208230 YO (1) 50 1788 347 (4) 70 (4) 380 252 - 250 - 400 -

460 XL 737 422 (4) 35 (4) 190 106 - 2 - 175 -460 YO 737 141 (4) 35 (4) 190 106 - 2 - 175 -

208230 XL 2051 1228 (4) 70 (4) 380 284 - 300 - 450 -55 208230 YO (1) 60 2051 409 (4) 70 (4) 380 284 - 300 - 450 -

460 XL 904 485 (4) 35 (4) 190 127 - 1 - 200 -460 YO 904 162 (4) 35 (4) 190 127 - 1 - 200 -

208230 XL 2083 1415 (6) 70 (6) 380 302 350 500 -70 208230 YO (1) 75 2083 472 (6) 70 (6) 380 302 350 500 -

460 XL 974 539 (6) 35 (6) 190 143 0 225 -460 YO 974 180 (6) 35 (6 190 143 0 225 -208 XL 1788 1040 (6) 70 (6) 380 266 224 300 0000 400 400 208 YO 1788 347 (6) 70 (6) 380 266 224 300 0000 400

90 230 XL (2) 50 1788 1040 (6) 70 (6) 380 266 224 400 I300 0000 400 400 230 YO 1788 347 (6) 70 (6) 380 266 224 300 0000 400 400 460 XL 737 422 (6) 35 (6) 190 187 - 000 - 250 460 YO 737 141 (6) 35 (6) 190 187 - =1000 - 250 208 XL 2051 1228 (8) 70 (8) 380 312 256 400 300 250 208 YO 2051 409 (8) 70 (8) 380 312 256 400 300 500

110 230 XL (2) 60 2051 1228 (8) 70 (8) 380 312 256 g I350 300 SOO 450 230 YO 2051 409 (8) 70 (8) 380 312 256 350 300 500 450 460 XL 914 485 (8) 35 (8) 190 231 - 0000 - 300 460 YO 904 162 (8) 35 (8) 190 231 - 0000 - 300 -

208 XL (1) 60 2051 1228 (8) 70 (8) 380 312 260 400 300 500 450(1) 75 2083 1415

208 YO (1) 60 2051 409 (8) 70 (8) 380 312 260 400 300 500 450(1) 75 2083 472

230 XL (1) 60 2051 1228 (8) 70 (8) 380 312 260 350 300 500 450(1) 75 2083 165125

230 YO (1) 60 2051 409 (8) 70 (8) 380 02 260 350 300 500 450 (1) 75 2083 472

460 XL (1) 60 904 485 (8) 35 (8) 190 240 - 250 - 300 -(1 75 974 539

460 YO (1) 60 904 162 (8) 35 (8) 190 240 - 250 - 300 -(1) 75 974 180

208 XL 2083 1415 (8) 70 (8) 380 316 260 400 300 500 450 208 YO 2083 472 (8) 70 (8) 380 316 260 400 300 500 450

135 230 XL (2) 75 2083 1415 (8) 70 (8) 380 316 260 400 300 500 450 I 230 YO 2083 472 (8) 70 (8) 380 316 260 400 300 500 450

460 XL 974 539 (8) 35 (8) 190 247 - 250 - 300 -460 YO 974 180 (8i 35 (8) 190 247 - 250 - 300 -

208 XL (2) SO 1788 1040 (10) 70 (10) 380 326 402 400 0000 500 500(1) 60 2051 1228

208 YO (2) 50 1788 347 (10) 70 (10) 380 326 402 400 0000 500 500(1 60 2051 409

230 XL (2) 50 1788 1040 (10) 70 (10) 380 326 402 400 0000 500 500 145 (1) 60 2011 1228

230 YO (2) 50 1788 347 (10) 70 (10) 380 326 402 400 0000 500 500(1) 60 2051 409

460 XL (2) 50 737 422 (10) 35 (10) 190 295 - 350 350 --(1) 60 904 485

460 YO (2) SO 731 141 10 (35) (10)190 295 - 350 350- -(1)60 904 162

208 XL 2051 1228 (10) 70 (10) 380 326 462 400 (2)250 500 600 208 YO 2051 409 (10) 70 (10) 380 326 462 400 (2)250 500 600

160 230 XL (3) 60 2051 1228 (10) 70 (10) 380 326 462 400 (2)250 500 230 YO 2051 409 (10) 70 (10) 380 326 462 600400 (2)250 500 600 460 XL 904 485 (10) 35 (10) 190 329 - 400 - 400 460 YO 904 167 (10) 35 (10) 190 329 - 400 - 400 - I

NOTES 1 XL Across the LineYOStarDelta 2 RLA Rated LoadAmps(ratedin accordance withARI Standard 590) LRA LockedRotorAmps 3 Wire Size Amps equal125of the ratedloadampsfor the largestmotorin thecircuitplus100of the ratedloadampsfor all othermotorsin the circuit per

NEC 4 Wire size based on copperconductorswith75C insulation perNECTable310-16 Terminal block lugs are sizedaccordingly Use of oversize wiringmay

not lit in terminal blocks 5 Maximumfuse size is basedon 175to 225of the ratedloadampsfor the largestmotorin the circuitplus 100of the rated loadampsfora othermotors

in the circuit per NEC VOLTAGE TOLERANCES 208V-230V min 187VMax 253V

480V Min414V Max506V

I

18

ELECTRICAL DATA Volts Type COMPRESSORModel FAN MOTORS MINCIRCUIT RECOMMENDED MAXIMUM 60 Hz of Oty RLA Starting FLAACWC LRA AMPACITY WIRESIZE FUSE SIZE 3 Ph Start Curro EaSC HP Ea Ea Ea Cire1 Cire2 Cire1 Cire2 Cire1 Cire2 208 XL 2051(1) 60 1228 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 1415 208 YO (1) 60 2051 409 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 472 230 XL (1) 60 2051 1228 (12)70 (12) 380 341 469 500 (2) 250 500 600

12 75 2083 1415185 230 YO (1) 60 2051 409 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 472 460 XL 485 (12) 35 (1) 60 904 (12) 190 352 500 400- - -

(2) 75 974 539 460 YO (1) 60 904 162 (12) 5(12)19 352 500 400- - -

(2) 75 974 180 208 XL 2083 1415 (12) 70 (12) 380 345 469 500 500(2) 250 600

472208 YO 2083 (12) 70 345(12) 380 469 500 (2) 250 500 600 230 XL (3) 75 2083 1415 (12) 70 345(12) 380 469 500 (2) 250 500 600200 230 YO 2083 472 (12) 70 (12) 190 345 469 500 500(2) 250 600 460 XL 539974 (12) 35 (12) 190 359 - 450500 - -

180 1(12) 35 460 YO 974 (12) 190 359 450 -500- -2051 1228208 XL (12) 70 504(12) 380 504 (2) 250 (2) 250 700 700

208 YO 2051 409 (12) 70 (12) 380 504 504 (2) 250 700(2) 250 700 (4) 60 2051 1228 (12) 70 230 XL (12) 380 504 504 (2) 250 (2) 250 700 700215

YO 2051 409230 (12) 70 (12) 380 504 504 (2) 250 (2) 250 700 700 460 904 485 (12) 35 XL (12) 190 225 225 0000 0000 300 300

(12) 35 460 YO 904 162 (12) 190 300225 225 0000 0000 300 2051 1228208 XL (2) 60 (14) 70 (14) 380 504 525 (2250 700 700(2)300

(2) 75 2083 1415 2051 409 (14) 70 700 700208 YO (2) 60 (14) 380 504 525 (2) 250 (2)300

(2) 75 2083 472240 700XL (2) 60 2051 1228 (14) 70 (14) 380 504 525 (2)250 (2)300 700230

(2) 75 2083 1415 2011230 YO (2) 60 409 (14) 70 (14) 380 504 525 (2) 250 (2)300 700 700

(2) 75 2083 472 300460 XL (2) 60 904 485 (14) 35 (14) 190 225 248 0000 250 300

12 75 974 539 904 162 250 300 300460 YO (2) 60 (14) 35 (14) 190 225 248 410

(2) 75 974 180 2083 1415 (2)300 700 700XL (16) 70 (16) 380 525 525 (2)300208 2083 1415 (2)300 700 700208 YO (16) 70 525 525 (2)300(16) 380

700 7002083 1415 (16) 70 (2300230 XL (16) 380 525 525 (2300 700 700(2300(4) 75 2083 472 (16) 70 (16) 380 525 525 (2300230 XL265

300250 300974 539 (16) 35 248 248 250XL (16) 380 460 (16) 35 300 300974 (16 380 248 250 250YO 539 248460

NOTES 1 XL Across the Line YO Star Delta 2 RLA Rated Load Amps (rated in accordance with ARI Standard 590) LRA Locked Rotor Amps 3 Wire Size Amps equal 125 of the rated load amps for the largest motor in the circuit plus 100 of the rated load amps for all other motors in the circuit per

NEC 4 Wire size based on copper conductors with 75degG insulation per NEG Table 310-16 Terminal block lugs are sized accordingly Use of oversize wiring may

not fit in terminal blocks 5 Maximum fuse size is based on 175 to 225 of the rated load amps for the largest motor in the circuit plus 100 of the rated load amps for a other motors

in the circuit per NEG VOLTAGE TOLERANCES 208V-230V min 187V Max 253V

480V Min414V Max506V

19

0

(Wd~) 3lV~ M011 ~31VM

006 009 00 OOt OOl OS L 00 L os 0 Ot

V D m (I) (I)

c D m c D o V

- m m -t o

~

~ m D-

aoao 3~nSS3~d ~3100~

APPLICATION DATA

POINT LOADING

ArMi I 1 5 1

ACWC 45 THRU 10 SC

COMPRESSOR CONDENSER SECTION SECTION

_ 2 4 bull 1

bull CA

J

Model Dimensions Size A B C D 45 91 - - -55 91 - - -70 145 - - -90 145 - - -110 60 40 160 -125 60 40 160 -135 60 40 160 -145 138 74 107 -160 13830 74 107 -185 138 129 107 -200 138 129 107 -215 106 82 106 80 240 106 82 134 107 265 133 110 134 107

1310

1310

~

1

1310

2

ACwe 110 THRU 200 Ie

COMPREIlOfl CONDENSER SECTION IECnoN

4 -

5Imiddot

ACWC 2t5 THRU 215 SC

Model Loadlnu (LBS) Size 1amp2 3amp4 5amp6 7amp8 9 amp10 45 585 765 550 - -55 705 810 635 - -70 660 890 700 - -90 1025 1500 1175 - -110 1195 635 1525 995 -125 1255 690 1835 1115 -135 1255 665 1880 1105 -145 1330 2380 2160 1450 -160 1330 2440 2280 1515 -185 1235 2575 2980 1360 -200 1275 2635 3020 1380 -215 1010 2270 2590 2240 840 240 1115 2550 2870 2715 1125 265 1380 2980 3515 2750 1175

11

II i middot 2 4 lIf 11 to L

21

TROUBLESHOOTING GUIDE

CHILLER UNIT WILL NOT START POSSIBLE CAUSE REMEDY 1 Power off 1 Check main disconnect switch

2 Main line open 2 Check main fuses

3 Incorrect wiring 3 Check the wiring diagram

4 Loose terminals 4 Tiqhten all terminals

5 Control circuit open 5 Check phase loss monitor flow switch circuit breakers temperature control low ambient thermostat low temperature thermostat remote switch etc

6 Time delay 6 Wait

COMPRESSOR HUMS BUT DOES NOT START

POSSIBLE CAUSE REMEDY

1 Low voltage 1a Check at service and unit for loss

b Consult power company

COMPRESSOR CUTS OUT ON LOW PRESSURE SAFETY CONTROL POSSIBLE CAUSE REMEDY 1 Refrigerant shortage 1 Check for leaks -- add refrigerant 2 Restriction in liquid line 2a Plugged strainer - dean or replace

b Liquid line valve partially closed - open valves fully c Expansion valve clogged or inoperative - clean or replace as

required d Solenoid valve partially open - clean or replace as required

3 Low water flow thru cooler 3 Check water flow thru cooler and correct as required

COMPRESSOR CYCLES ON HIGH PRESSURE CONTROL POSSIBLE CAUSE REMEDY 1 Compressor discharge valve partially closed 1 Open valve fully 2 Non-condensible gases in system 2 Operate condenser fans with compressors off If condenser

pressure exceeds saturated pressure corresponding to condenser entering air temperature then purge air from discharge line

3 Overcharge of R-22 3 Purge system while in operation until head pressure reaches a normal level

4 Dirty condenser 4 Clean the condenser 5 Compressor discharge check valve not operating properly 5 Replace if necessary 6 Fans not running 6 Check pressure control setting

CAUSES AND PREVENTION OF FREEZE-UP CAUSES PREVENTION 1 Improper charging 1 Charge per manufacturers recommendation

2 Improperly set safety time delay 2 Check the safety time delay low pressure control for proper setting at the beginning of each season

3 Improper chilled water circulation 3 Use an ample sized cleanable strainer in the chilled water circuit Make certain the strainer is clean to insure full flow and velocity of

chilled water It may sometimes be necessary to treat the water to prevent formation of deposits

4 Not draining for winter shutdown 4 When the system is shut down for the winter remove the drain

plugs and drain the cooler Blowout any remaining water with air

5 Improper pump shutdown 5 Make sure chiller barrel heater is working and flow switch is installed per wiring diagrams

6 Low ambient during air conditioning season 6 Make sure chiller barrel heater is working

NOTE If the ambient temperature is below 32degF freezing can be completely prevented by one of two methods

1 Drain all water from the equipment 2 Add antifreeze to the water

22

START-UP CHECK LIST

Unit Model No

Setting unit

Wiring

Piping

Alignment

Before Start-Up

After Start-Up

Yes No a Vibration isolator used

b Spring isolator adjusted for equal height c If rubber-in-shear isolators are used is unit leveled by shimming

a Power wiring complete

b Control wiring complete c Electric service adequate for load

d Power source voltage correct for motor(s) used

e Motor circuit has proper size fusetrons f System wired per diagram

g All lead connections tight h Wiring complies with local codes i Flow switch operation

a Piping complies with applicable codes b External piping independently supported c Chilled water lines insulated

a All belts adjusted and checked for tension b All pulleys checked and adjusted for proper pitch tightness and

alignment

a Open compressor discharge service valve b Open liquid valve(s) c Open suction and discharge valves to pressure gauges (if supplied) d Check rotation of all fan motors e Start auxiliary equipment (pumps fans etc) f Is crankcase heater operating Operate 24 hours prior to unit startup g Check the compressor oil level through the crankcase sight glass The oil

level should be to the top of the glass If the level is low add oil in accordance with the directions in the maintenance instruction

h Check all control settings as specified in Table 1 I Air purged from chilled water system

a Check high pressure control b Check oil temperature safety switch c Check and adjust low pressure or temperature freeze control d Check and adjust operating thermostat e Check and adjust low pressure operating control f Check and adjust expansion valve superheat g Check and adjust capacity control thermostat

23

OPERATING DATA CHILLER Voltage L-1 L-2 L-3 _ Pressure Gauge Readings 1 Suction psig 1 Discharge psig 2 Suction psig 2 Discharge _ psig 3 Suction psig 3 Discharge psig 4 Suction psig 4 Discharge _ psig High pressure switch setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-in) psig psig (Out) 4 (Cut-In) psig psig (Out) Checked Setting - Yes - No (each circuit) Low Pressure Switch Setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-In) psig psig (Out) 4 (Cut-in) psig psig (Out) Checked Setting -Yes -No (each circuit) 1 Oil Temperature Safety Switch Cut Out 2 Oil Temperature Safety Switch Cut Out 3 Oil Temperature Safety Switch Cut Out 4 Oil Temperature Safety Switch Cut Out If Star-Delta start time delay is seconds Temperature of air entering condenser F Temperature of air leaving condenser of Temperature of chilled water entering chiller OF Temperature of water (chilled) leaving chiller F Chilled water pressure entering chiller psig Chilled water pressure leaving chiller psig

MAINTENANCE Good maintenance practice will prolong the chiller life and will reduce the Ask of system breakdown and expensive service calls

A weekly check of the ACWC-SD unit requires only a few minutes and will prove beneficial in insuring long trouble free operation

WEEKLY CHECKS- with unit in operation for at least four hours 1) Check compressor oil level - At least above 12 of sight glass 2) Record suction and discharge pressures

Typical Condition R22 Ambient 95degF Return water 55degF Leaving water 45degF Suction 62 psig Discharge 270 psig

3) Record ambient temperature 4) Check liquid sight glass

Make sure liquid is clear - no bubbles 5) Check that all fans are running 6) Check entering face of condenser coil for cleanliness 7) Record voltage at unit

All of the above can be performed by building maintenance personnel If oil levels are low or any of the above checked items are questionable consult a qualified serviceman

At least once a year a qualified serviceman should check unit oil levels superheat and control operation

DUNHAM-BUSH USA

P l) bull 130 xUtUC t01 Bmgess RO~ Harrisonburg VA 22801 Phone (540) 434-0711 FAX (540) 434-~ 2118

wvvwdunham-bushcom Form No 6184

Page 7: ACWC-SD - · PDF fileACWC-SD • Screw . Type • • • Air-Cooled Packaged Chillers •• Installation, Operation, and •• • Maintenance Manual • • • •• DESCRIPTION

SHUTDOWN SEQUENCE

Stage 2 Shutdown Stage 1 Shutdown

After both compressors have unloaded fully and the leaving water temperature is still lower than the setpoint the second step of the thermostat (T1) will open and de-energize relay (R2) [58] providing an approximate five minute time delay again integral with the microshyprocessor has expired subsequent to the start of Compressor No2 This will close the liquid line solenoid (SOL2) [33] and turn off Comshypressor No2 Compressor No 1 will load and unload as required Compressor No2 will not be able to restart for five minutes due to integral time delays

SAFETY CONTROLS

The unit is protected by the following safety controls

1 High Pressure (HP) 2 Low Pressure (LP) (automatic reset) 3 High Discharge Temperature (OTS) 4 Compressor Solid State Module (CSTM) 5 Low Water Temperature (T2) 6 Low Ambient Thermostat (LAT) 7 Compressor Starter Overloads (OLH) (optional) 8 Phase Loss Monitor (PLM) 9 Control Circuit Breaker (CB1)

If any of these devices should open due to abnormal conditions the compressor(s) will automatically stop All controls must be manually reset except low ambient thermostat (LAT) and phase loss monitor (PLM) The individual compressor safeties (HP LP OTS and CSTM) contacts are found on Lines 20 (CTT1) or Line 30 (CTT1) The other safeties listed above are discussed in the preliminary sequence section

If the leaving water temperature is still lower than the setpoint the first step of the thermostat (T1) will open and de-energize relay(RI) [61]This will close the liquid line solenoid (SOL 1) [23] and turn off Compressor NO1 as long as it has run for approximately three minutes Compresshysor NO1 will not be able to restart for five minutes

FIELD CONTROL WIRING

In addition to 3 phase power (and optional 115 volt control) wiring described above the following control interlock wiring is recommended The as built control schematic provided with the unit provides detailed information Typical control schematics are as shown on pages 8-15

1) Alarm Circuit -Terminals 6-13 (2 per compressor circuit) can be used to trigger remote failure lights or alarm bells in the event of a refrigeration failure

2) Time Clock - All unit on-off control should be done through terminals 15 and 16 An open contact shuts down the unit Time clock night shut down and energy management shut down should all be done from these terminals and contacts should be applied in series

3) Flow Switch - The flow switch contacts should be installed between terminals 15 and 16 and be in series with time clock contacts

4) Chilled Water Pump - The control of the chilled water pump must be worked out by the system designer It is necessary for the pump to be on during any compressor operation and terminals 17 and 18 should be used to energize the pump starter However it is likely that the pump should remain on throughout all occupied operation or even at night for freeze protection Terminals 17 and 18 should not be the sole means of controlling pump operation

STARmiddotDELTA STARTING OPEN TRANSITION (OPTIONAL)

Typical For All Compressors On initial call for cooling staging relay (R1) holding coil will energize The (R1) contacts 7-4 close energizing star contactor (S1) and the five second transition timer (TD5) Transition contactor (S1) power contacts close tying the center legs of the compressor motor windings together into Star (WYE) configuration At the same time (S1) NC (Normally Closed) auxiliary contacts open preventing (C2) from closing (S1) NO (Normally Open) auxiliary contacts then close energizing contactor (C1) The (C1) power contacts close applying power to the

compressor winding (C1) NO (Normally Open) auxiliary contacts close locking (C1) in the energized position The compressor operates in the Star mode until (TD5) transition timer times out (five seconds) at which time contacts NC open and de-energize (S1) Star contactor (S1) NC auxiliary contacts close (TD5) timer NO contacts close energizing compressor contactor (C2) power contacts close thereby completing the Delta wiring configuration Compressor contactor (C2) NC auxiliary contacts open preventing (S1) star contactor from energizing until the next starting sequence

7

--

exgt

LE

GE

ND

m

rrbullbull

saN

OI

IlIG

CI-

Z

CO

HT

AC

TQ

ftmiddot (

0

[5

10

1t5

el

) C

ON

TA

ClO

middot A

NS

(C

UlT

middot pound

AM

III

bull C

ON

TO

L

(C

UlT

C

UtC

UIT

Ulaquo

III

H

IAT

EIt

I C

HllL

rU

lU

[AT

III

CU

Ne(

ASE

H

un

co

U

OIl

ll

SOL

ID

TA

U

MO

OU

Lt

H

US

UII

lI[

con

RO

L

LOW

Abullbull

IN

T

[

twO

fI

lO

W

nul

tt C

ON

TIIlI

OL

OIL

TU

II

r

UIIl

I(

SA

HA

S[

0

1$

M

ON

t T

O

lllE

LA

Tmiddot

tTA

GIH

O

1t[

LU

-U

CIT

Y ~OL

bull

CI

l

tC5

I H

el

C

Ubullbull

e

lHI

CC

HI

esr

P

I L

UI

VI

enst

P

LU

11

0)

(L

AY

middot tN

Uft

LO

CK

(

L[N

OIO

middot L

lOU

IO L

INI

SWIT

CN

CO

W

UD

C

C

UIT

S

SWIT

CH

ST

EN

fH(

MO

ST

AT

middot S

[OU

[Ne

EIt

TH

UM

OS

Tn

-L

OW

n

llI

IUU

[

TtIt

WIN

AL

10amp

1110

cu

no

wE

It

UN

I J

SO

LI

w

10

Tl T[l

Il

S

Tl

Ufl

Ul

10

0

-

CT

OII

I

WIl

WO

T

lM[

HU

T c

alli

CO

NTbull

bull L

OW

Ipound

n

LO

CC 0

1

TO

T

IllS

I

ond

tlt

UN

Lo

ao

t

OL

(NO

ID bull

(O

M

no

ll

Ul

ImiddotZ

~(

tU

IIL

T

IIS

VI

O

I

_

-~

OIO

HA

l

ell

C

UtC

Ul

[

amp1

(( -

(cri

VE

lli K

uru

en

C

IAC

Uff

A

UK

(jII

f bull

CO

[

I(

C(

OV

TL

lT

CI

I (O

NU

OL

If

Jll

AIr

IS

HO

UA

W

(fIA

S

LL

Tl

LO

AO

LI

T

(III

WO

STA

T

0

middot

5

O

(III

LO

AO

fU

UIS

LImiddot

H

OT

L

IGH

TS

H

IUC

IIY

[1II

H

[AU

IIIS

~ jllf

M1

III[

Cll

[

H

[U

t

US

UII

ll[

CO

NT

IIO

LS

~tCt

JVII

l N

(AU

III

14

(0

1

T

O)

TO

wI

DtL

AY

amp L

OW

U

tu

LO

CK

ou

r rt

(

O(L

IN

SlT

IO

C

OH

TA

(TO

Il

(O~USO

C

OH

O

lll

bull iT

A

OlL

C

Ol

CO

MV

[Nf

epound

o

un

n

Ctft

CU

lT I

DE

TA

IL

A

SlA

M

DE

LTA

ST

AR

T

O -~

OA

~ 5~U

Z

OI

Cl

U

I 14

(I

amp

~

NC

f

cl

AU

I

51

ZtA

LU

TOO C

21

NO

~~

bullbull

N

WHT

I---

I

l I J

II

A

CN

lCU

lT

If

OOHAI~

l

~i1

WH

It[

-

OI

ON

AL

r---

----

---

-I

Q

WT

I lt

raquo

I I L

JI

bull bull

I I

0

II

-

lJ

_ Ij

lf

I

cal

II

iOO

w

shy

) C

it

~

WTI~AL

r --------------------------------

Iamp

I

_l

[0

0

I

OO

CM

lL

00

LO

II

cu

U

II

bullL

~J

It

_U

I

TH

u

I

HT

I~

r-~~

~ --

-I=

=~==

=~I

11

2

N

~~~

~--

----

----

=~

I

-lt

l

= I

en

co

o J

rO~

2

~L

----------

-

-oS

f

I

r--shy

J

on

T

O)

vI

Q~~A

J T

Ot

L-

ll~_

f

1

II

CU

H ~

~OI

L1

-i

r---

----

-

~

10

rc

I

bullbull

lf

OIS

ti

l W

I H

Z

01

11

1

-J

o

u

L

shy

0bull

-

0 T

1

111

A -

bull 0

[0

HT

I

ll II

rgt ---

-ij

---

ITl~ll

t

1amp

I

1t

D

MIN

I[D

11

~

ill HTAILmiddot~

O

LM

I 01

1

OL

HJ

III0

1l~

tM

Ow

N

CI

amp

tt

I w

lO

OIO

HL

---

__

J

O ~

~Ll

~

tB1

It

CI)

n

IS

-1

M

k

V

Io

Jmiddot

r---

1

we

14

-4

I

Mill

I

CO

MPR

ESS

OR

C

IRC

UIT

I

Til

bull ~

r-

so li

e II

It

S

tON

L

N

O

fll

II

If

II

~

s~

o

oc

gt

(I)

r in

n

100

00U

lz

--I

~o

e

0

r ce

cn

shy0

0

Z

Ggt

bullbull bullbull bullbull bullbull bullbull bullbull

r~T~-

ICt

MQ

Teuro

CO

MT

It01

I T

IM C

lot

ll

~---

Cl

ll

(O

41

(

flO

W

5Wlf

CH

~

I

Olt

CO

NT

AC

TO

C

OIL

S C

I-I

bull C

tS

AN

D S

t sn

N

OW

IIt

Dll

QU

0

1 C

OM

UC

TI

I

111

114

0

(

U

II

NO

f T

O I

(

C

uNO

IO

ON

UtI

se

CO

HO

UI

li

D(

1

A

ND

1

n

WP

(IU

ult

l S

(NIC

tf1

I

LO

CU

ID

1M bullbullU

O

UT

UT

r-

----

shybullbull

0

11

UO

V

HA

Il

LO

IS

raquoON

TO

S

TE

lurN

AU

bull

AN

D

0111

IIC

O(

I A

ND

A

U(

Cfl

YpoundL

Y

So

C

rt

TO

0

0 M

AN

UA

L a

ll H

TO

tNT

AN

D

~10l

IA

NO

M

TII

UC

TtO

NS

II

rCO

tNO

m

IMIT

AL

CO

H

laquo

0

U

TI

I It

4

Ishy

C

OW

III

ISO

R

MO

DU

LES

dC

NO

MmiddotA

U

VA

TC

I

D

U

1111

WIL

L A

LSO

LO

C_ O

UT

(

let

Umiddot

I C

AL

L

WH

IM

IAI

TY

flit

TH

[I(

CO

Nmiddot

I

OL

I CA

Jrf I

I II

EM

T

IT T

Uft

I1

tW

ITC

H bullbull

0

VO

NIN

IL

f PO

C

Obullbull

bull

I w

UII

II

I

C

IL

Llf

i I

ITA

f[1

II

ItV

N

IWIT

ti r

raquo7

~Slt~1

~~~~( 1~~~~tlDOO

CO

N

CT

O

WU

UH

O 0f

II C

OW

bullbullbullbull

~~1

II

bull

LL

TI

lIT

AT

0

N

O 1

0 O

CA

TID

1

1 I

I IIl

ETU

IIPt

W4T

P

LU

WHE

N u

TI

It N

OT

lU

u

rD

ttl

III I

ICO

Ma-

aU

0 11

nM

H

u

l

UN

I()1

II M

UST

HA

V(

SH

llL

DID

C

AU

I

LO

Me

T

II

no O

R

ItUM

WT

M

ItO

WI

L

IAH

to u

ri N

T I

T H

-

ITbullbull

O

N

ft

0

-

011

II~T

K

ITI

GU

ION

An

ON

S

o H

O-

ON

G C

OI

-W

it

11

N(

NO

6 N

c

CO

NU

ClI

W

If

lIN

( N

O

o N

0

CO

NT

AC

TS

WIt

K

liN

t N

O

6 N

OT

t I

TH

L

Nt

NO

Y S

UI

-I

IS

5_

1

~

~

no

~ I

I I_

VLOA

Or- I

I ~~

vumiddot

S1 so

CO

Hit

so

0

amp

g A

SI ~

I

1

7100-

I -I

I 01

10

OH

0

10

f T

AN

I V

I

] CM

NG

( av

rlt

10

0 O

K__

ST

AG

(

COD

lJ-

L7

00

~It

A

lIT

00]

VL

I fi

ll

14

1

10A

O

f

_ III

rC

OH

O

In o

y

00bull

00

10 ~

0

10

CO

Ol

C

bull

] 4

U

rr

COL~

bull Jo

un

J

W bull

C~P

OJ [

ou

-t

urO

NT

01

CO

l0

1

N

Omiddot

~ ]

(jCO~_

0

)

un

ll

n ~

T

I 11

I1

III _~

n

~

amp

7

10

II

01

u II 17

II

0

II

01

IS

-I

-lt

sE

o

0 c

raquo

CD

r iii

0

~O

U

lZ

+-1

~

tI

t

0

r QE

CIJ

-c

tl

Z

Ggt

lt0

bullbull bullbull

bullbull

bullbullbullbull

~

o

tUN

oa

lllO

_--

-

shyC

t-4

CII

C

cn

bull

tlN

I

CC

HImiddot

t

csnu

middota

--1

LA

T

loP

a

01

11

-1

111

111

IIImiddota

It

4

IOL

IS

IW

Imiddot

I

I T

I n flbull

bull

TO

middot I

st

U

LImiddot

a

Oft

lo

tL

LtG

EN

D

CO

NlA

CT

IM ~

CO

lllf

lllt

UtO

JII

CO

NT

AC

TO

CII

CU

fT

IIIC

AICC

III

CO

NTJ

IIOL

CIC

UIT

U

NImiddot

HU

TI

eNU

LlII

I

Il

I

AU

It

C

NlaquoC

AU

NC

An

C

O

UIO

10

LIO

T

AU

N

t U

SU

I C

O T

OO

L LO

W

eT

fM

llltM

OT

AT

L

OW

Hl

III

UII

I C

Oft

TJl

OL

OU

n

ru

ulltl

A

nT

T

HA

-

0bullbull M

OH

IfOIt

fl

lLA

Y I

AO

INI

MU

C

AN

cn

CO

fTltO

Ibull

ItIL

A

INT

ILO

CIC

OL

EN

OtD

Ll

OU

ID L

INt

Cc

ulT

MOO

ULIE

C

NIC

CA

SE

ItS

C

(

OM

II

IOII

(lI

IieLf

W

I eM

-

UIE

R

TH

III

OIT

6Tmiddot S

lOU

lC

U

MC

ot

LOW

TlM

e

U1

T

lER

bullbull

L l

OA

JIIO

middotCU

lTo

tJ

II W

UU

Nt

TI

M

AL

IO

D

oC

0It

1 U

IIN

t T

IMe

OC

LU

middotCA

II C

ONT

a

LOW

IU

t L

OCK

OUT

NPD

WIU

UN

LOA

Olil

t 1

0L

(NO

I0

C

O

III

OIl

lI

cn

CIJ

tCU

IT

UII

lEIt

ft

EC

poundIV

E H

IAI

C

Ol

(C

UIT

1I

IUIIl

I1II

CO

NY

(NIE

NC

E

OU

TU

T

CU

I C

ON

nlo

0

1

AN

$ M

ill1

1

HO

YIll

MU

II

lLT

I l

OA

O

LlI

lIIT

T

H(

O

ITA

T

OL

O

VC

LO

AO

MIA

nl

L1

lI1

~HAII

LO

IS

MO

NIT

O

L

Imiddot J

~fOT

L

IOH

TS

1

1

IC

IIV

E

HE

UE

ItM

lIC

tmiddotl

rC

IIV

E

MU

TlI

t l

tIIS

UIl

l(

CO

NT

ItO

LI

T

lmiddot1

C

CC

lvllt

N

EA

fllt

T

lW

OS

TA

lI

TO

Jmiddot 4

T

INe

H

LA

Y

LOW

In

vlt

l LO

C

OU

T

1O

t-1

ft

lll

D

UA

Tmiddot

TA

SIT

ION

C

ON

TAC

TO

Ill

$middot

1

CO

C

O

(

lIO

C

ON

TA

CT

O

T

A

Dn

u

CO

WC

tllltN

CI

ount

T

DE1AIL~

ST

AR

D

EL

TA

S

TA

RT

r

2

~f

10

t10

II

amp

II

11

II

)

1IllI

1IU

--shy

OW

E

IV

-

utv

lO

f

I I Ibull

A

UR

C

IlltC

UIT

C

IRC

UIT

ALA

NlC

UfT

C

lflC

UIT

I I

I

~li

IT

I

Ot

ON

AL

il------~---l

-

tL

J --

--

C

it

prIlgjf~

II

ell

I

I

IfB

I

t

---------~~-------

__

~

L_ -

7 -

-r--

et

r

I

II10

-I

CII

-lt

PL

1amp

I I

II b

I

L _

__

J

II 3

2I

oo

II

Qraquo

~

IS

lI

(

)r-

t-_

_ o

J_

_

O

TIO

L

I ~~

--~-

I

I CD

oL

__

__

__

__

__

CO

I- f

_

JI I

t degz

OI

OIl

lAL

r-

---

IS

r

-l

0

I

I

+10$

IL

KS

I T

e

0 Lr

I J

II

T

ITI

lOL

l 1

40

bull (C

IS)

TO

bullbull

lD

A-

~ -

r--

-~l

)~II

I

~G

__

_~L_J

0

O

HA

I

~ -

-Ill

-

---

-10-

--

~E

II

cn

-C~

II

Z

0

G)

Il

l~

r- I W

lllltO

WH

IN

JU

L1

l0

I I

I

OL

M

OL

MI

OL

I ~ro

o

jo

o

Jt

JI

L

OT

10N

AI

II

0

(01

0 CO

MPR

ESS

OR

C

IRC

UIT

~

27

III

gt

0

IIA

IO

amp1

)amp

1

1

II

~

I rA

I

TA~

D

ELTA

STA~T

CONP~E~)

CU

lT 2

~

f

bull ]

A

U

4 ]I

IUft

middotJI

Mon

tUPlOI

NT

lOA

Ot-

-O

I

01

0

]

(N

GI

011

1

00

CT

AN

)

40

00

HN

a

_N

I

J00

I -

It IC

y

TO

I

I I

I

~

oiiO

NA

t

I bull bull

wi

i

lOa

r~TT~-

I M

OT

I C

ON

sr

0

llItt

(

co

ce

OZ

UK

1

11

_JO

I I

)--11

--

- ---

-

IJI

LD

~

I

A

CK

lS

C

UK

I

IL

UO

A

TO

O

WH

IT

1

L

OW

SW

ITC

HJl

AL

D

00

IZ

I

f

1It-

-

rl__ u-

poundL

J f

aT

ION

AL

TI

WfI

OO

f

~

ff

I

Dill

C

ON

TAC

TOIlI

C

OtL

S (1

middot4

(IS

middot14

A

ND

II-

I

01

1In

N

O

Wl

0

51

11

~

CO

NT

AC

TS

I

fH

IO

Uti

IS

N

OT

TO

IE

al

llauN

DIO

O

N H

I Sr

CO

NO

AIl

lf

StO

l

f

I

TI

AN

D

TI

TI

U

I

IIN

OII

t

0middot

f1L

OC

AT

IO

IN n

lll

GU

lUT

r-

----

shy~

(I

G

lIt

no

v

HA

I

LO

SS M

ON

IO

nf

1Na

bull

AN

D

ON

rc

I(

CO

M(

f A

IrfD

I

lItU

rC

TIY

(U

00

-

5

E

[CO

OIO

lItc

rlll

TO

0

0

AN

UA

L

t

OIN

T A

Na

f

oo

IlU

COfrt

TO

I U

ND

IN

Stt

UC

TIO

trl

r

co

rNH

D

01 11

raquoIN

ITIA

L

CO

NT

lIIiO

L

fII

I0 I

UT

IS

a

jshy

orshy

10bull

CO

M1

II1t1

Ol

MO

GU

LI

I N(

tN-a

UT

OM

AT

lC

I 1I

lfla

n

flS

bullbull

11

A

LSO

ampO

eMmiddotO

UT

luer

llt

middot I

no

C

AL

Y

WH

IM A

N

IUIT

T T

IIII

P

T

MU

I C

ON

egoo

IT

flO

LI

CA

l

ItU

I1 I

T

TU

NIN

G W

ITC

M

0

~r=

0 I

lIO

Wlf

lIT

A

L

fOtt

CO

lI

tbullbull

w

ITC

H_

I

on

WO

Nlf

lIT

JII

IL

POllt

COW

bull

I In

degz

r+-i

~~

t

u ~o

1 ~rI~~

~~

~~TtIc~~I~D

1

SW

lTC

HI ~

C

OIfT

AC

TcU

t W

lItN

t C

OM

bullbull

H

To

lIL

b

l

0t~~1

0

1

CO

tfC

TO

H

I

lIt

C

ltbull

IIT

C

~r-

bull

WM

IH

-

2

N

OT

1V

l

rD

wllI

I[ to

IlIC

OM

n

I W

I

It

I

fjC

Ofl

P

tE

CJ)shy

t W

IN L

UI N

OT

SU

PL

ID

W

IIIIC

O

J

lleo

W

ti

l

LU

KT

IT

10- A

ND

10ft

II

v

C~

LO

CA

TU

I II

1t

11V

MI

_T

at

I

z10

I

T

lNH

A

TU

RC

S

lNS

OIt

MU

tT

ve

IL

OID

C

IL

C

()

11II

L

AT

I

AT

10

_

A

U

IIIT

I0middot

PCA

LOW M

I_ lO

TI

I bullbull

n

II

DES

IGN

ATI

ON

S

II

CO

NT

IlID

t I

NO

-o

MO

LD

INfl

C

OIL

It L

tNI

NO

0

Q

N

C

CO

NU

ClI

W

ITH

UN

I N

O

01]

0 co

O

f

11

~

I

ILK

n

e

s IA

UL

It

ibull

o O

CO

NTA

CTS

w

nw L

INI

NO

01

fA

0

~

fItO

TI

LI

I N

O

v

A

II

~ ~ bull i middots

~

~~ - ~

~

1- I J I J I I I I I I I I I I I I I I L __ J

I

a bull bull a bull bull

I I I

_J

r------~

=~I = ~ ~ bull ~ I I

~

as coe ruq SV~ siapow ~NI~IM lO~lN03lV3ldAl

i 4

_

a

~FirI1 u~III - I I

~ 1I

00000 -

I=II~I~~~~raquoIIIItIII~ampI~

as ooz nJ4l sv ~ siapow ~NI~IM lO~lNOgt TVgtldAl

bullbull bullbull

bullbull

~

jgt

lpoundIt

ND

II

co

----

----

----

----

----

----

----

----

-

r-~-middot--=-~~

~

bull a

~

at~04

5

---

~1I

A

~n

bullbullmiddot-shy

wo

_-

bull

lIt

C-

I C

Cf

aC

TO

Ic

ow

n

CC

eM

ca

~C

M

OD

IAI

CI

T-

CO

IITA

CT

oa

bullbull

CMCU

rT I

ItIM

IA

co-l

to

c-c

VIT

C

I

rr

c

AfE

bull r~----Ef1

POW

I

III

IQ

W

Q

tIL

UT

I1I

U__~

J

COt

I

LD

W M

lMtr

f nc

IIO

ff

0

N

LO

W

C

OIIT

INM

I I

CO

M

US

ON

C

NC

UIT

II

II

-~

_T

shy

C

O

NU

SO

II

CIN

CU

IT Z

II

D[TA~

-

ST

AN

D(~TA

IT

AII

T

0

u III

r

amp

II

-~

If

10

MA

MI

eN

talI

Tco_

~

STA

N D[~TA

ST

AII

T

~

CIS

-I

LA

~ 1-4

nmiddot

00

-

-II

1t1S

-1 aw

o fI

fl

U- I -~ Ci

Pi=

i

t

shy

~

iii

i

iii=

ii

-

-shyiii

ClL

n

TU

U

LOt

e

bull It

lLA

Yn

C

AM

Im

CIII

IID

L bull

CU

_C

Abull

fl

lUY

_f

tMO

ea

UY

middotIO

CI

lO

Ll

t

NIU

_L

N

CO

WU

UO

ItC

U

llT

l bullbull 0

1middot

lit

TMC

MI0

8TA

T tc

_lt

CIl

it

11

II

_

middotLO

W

TII

IfN

T

UIlI

C

nll

-

D-C

UlT

QIIU

tW

n-T

PII

IU

LIO

MI-

AC

TC

Ntf

Wi

MI

II

II

tY

middotCM

OO

C

LOW

HIe U

(O

Uf

lIl_

L

OA

M

1OtI

1tO

lD

CO

OA

CM

UtT

1M

C

lIY

Dl

NC

Afi

ll ea

-tU

lT 1

ItUbullbull

lI

oo

ww

lItt

lffc

e O

Un

n

cT

IlG

I

Ie-

~U

IIIC

CIV

P

1T

1lt

C

bullbull

Off

AT

tw

ebullbull

ampOW

IC

IUT

~-

4ti

iT

~

co

ww

O

UfU

T

DITA~

A

ITA

A

OEL

TA

IT

AJI

IT

co

rn~

e

I

1amp

ItmiddotI

~ bull

I I

I

I r

~

bull Iamp

II

I ~

I-

oJ

II I

IrIf

I I I I

s~

o

-I I

ltDc

() raquo

L 10

V

i

()

~O

to

U

lZr0

t2

llJ

IL

C6

J=

_J

~-1

f

II

c 0

II

N

ge

cno

c-

II

Z

Ggt

If IO

IC

IIY

II

IIR

III

IJt

T H

llII

A

Il C

Olaquof

U

TMIbull

~LDM

fI

lAR

PM

Iamp L

Oll

lTV

ii

iLii

Uii

ii

~

U3

I iL

iii=

i

Uii

u

i

O

(no)

T

bull II

1

IOA~

bullr

~ I

[gtO(]O

~ i I Ii i 2 ~ ~ ~ i a bull il 2 ~

iiibullbullbull

~ I ~ I I I ~~ =l ~ iI I ~ I I I It I 1111 amp ~~

as ooz nJ4l SP~ SlapoUII ~NI~IM 10U1NOl lVlldAl

-------

---

TYPICAL POWER WIRING Models 45 thru 70 SC

----

rYl31I01 I

-Ii --ti-

_ I ~_-

~ lniJ -

LIIbullbullbullbull PC _ amp-II _--- ~

TYPICAL POWER WIRING Models 90 thru 135 SC

- --- _ Tt

~rfh c~

tP ~

_III ~

I r-- ~- IIlJ

bull - MIl Mf __ bull Ie_~--~ _shy- shy16

---

----------

TYPICAL POWER WIRING Models 145 thru 200 SC

_ --1a1 IIUrI

middotrFti~v_ bull I

i~i ~~ TaII IIOMLI ~tN T 100 WTIOII 011 lilOOCL a

~ t1

tI bullbullbull

L

i I r-~

I r

~ ~ ~ III

2 ~ ~ ~l

- ~IlD I hJOHr eo teO acshyt CmiddotClM ~ CIKUr1 --

TYPICAL POWER WIRING Models 215 thru 265 SC

ItUU 1D Wll1U1I fIa -rMI

rt-h I -au 11 1_ i r~ rt-f

-i rn f1 ft fi i- llil bullbull c~ I bull c =

~~~ ~i~-~

~~m

~~~CI1 R~~ ~ ~~ ~llAi4I

luv~ bull ~uf LL~~-

~Mfl l~t IrMiA

a I III nII I bull it d

~-t--J I Lll-l~j ~nL4111 WlJj== lit-

I bullbullbull I

UGEND

~

~l OJ

- c~

~~~---

~)~middotI

I

L _~~~ L _I__~_J I ~ (11_1 ~ H~ CUlTMIt tffC_) Ll N

-r_ 0 1ItCIIIl0AI lllQUlllCo as -0- bull bullbull fI PC 110 lNJCllII a Olil1100pound1 II 111 el 1101 ItCOU_ 011 IIOOIL140

I 011 CI-( H[ (0110 (fMCun ubullbull --- l(lD IMbullbull Ntlf 110 e414-7

--CTOttbullbull

2

17

ELECTRICAL DATA Model Volts Type COMPRESSOR FAN MOTORS MIN CIRCUIT RECOMMENDED MAXIMUM ACWC 60 Hz of Qty RLA Starting FLA LRA AMPACITY WIRESIZE FUSESIZE

SC 3 Ph Start HP Ea Curro Ea Ea Ea Circ1 Circ2 Circ1 Circ2 Circ1 eire 2

208230 XL 1788 1040 (4) 70 (4) 380 252 - 250 - 400 -45 208230 YO (1) 50 1788 347 (4) 70 (4) 380 252 - 250 - 400 -

460 XL 737 422 (4) 35 (4) 190 106 - 2 - 175 -460 YO 737 141 (4) 35 (4) 190 106 - 2 - 175 -

208230 XL 2051 1228 (4) 70 (4) 380 284 - 300 - 450 -55 208230 YO (1) 60 2051 409 (4) 70 (4) 380 284 - 300 - 450 -

460 XL 904 485 (4) 35 (4) 190 127 - 1 - 200 -460 YO 904 162 (4) 35 (4) 190 127 - 1 - 200 -

208230 XL 2083 1415 (6) 70 (6) 380 302 350 500 -70 208230 YO (1) 75 2083 472 (6) 70 (6) 380 302 350 500 -

460 XL 974 539 (6) 35 (6) 190 143 0 225 -460 YO 974 180 (6) 35 (6 190 143 0 225 -208 XL 1788 1040 (6) 70 (6) 380 266 224 300 0000 400 400 208 YO 1788 347 (6) 70 (6) 380 266 224 300 0000 400

90 230 XL (2) 50 1788 1040 (6) 70 (6) 380 266 224 400 I300 0000 400 400 230 YO 1788 347 (6) 70 (6) 380 266 224 300 0000 400 400 460 XL 737 422 (6) 35 (6) 190 187 - 000 - 250 460 YO 737 141 (6) 35 (6) 190 187 - =1000 - 250 208 XL 2051 1228 (8) 70 (8) 380 312 256 400 300 250 208 YO 2051 409 (8) 70 (8) 380 312 256 400 300 500

110 230 XL (2) 60 2051 1228 (8) 70 (8) 380 312 256 g I350 300 SOO 450 230 YO 2051 409 (8) 70 (8) 380 312 256 350 300 500 450 460 XL 914 485 (8) 35 (8) 190 231 - 0000 - 300 460 YO 904 162 (8) 35 (8) 190 231 - 0000 - 300 -

208 XL (1) 60 2051 1228 (8) 70 (8) 380 312 260 400 300 500 450(1) 75 2083 1415

208 YO (1) 60 2051 409 (8) 70 (8) 380 312 260 400 300 500 450(1) 75 2083 472

230 XL (1) 60 2051 1228 (8) 70 (8) 380 312 260 350 300 500 450(1) 75 2083 165125

230 YO (1) 60 2051 409 (8) 70 (8) 380 02 260 350 300 500 450 (1) 75 2083 472

460 XL (1) 60 904 485 (8) 35 (8) 190 240 - 250 - 300 -(1 75 974 539

460 YO (1) 60 904 162 (8) 35 (8) 190 240 - 250 - 300 -(1) 75 974 180

208 XL 2083 1415 (8) 70 (8) 380 316 260 400 300 500 450 208 YO 2083 472 (8) 70 (8) 380 316 260 400 300 500 450

135 230 XL (2) 75 2083 1415 (8) 70 (8) 380 316 260 400 300 500 450 I 230 YO 2083 472 (8) 70 (8) 380 316 260 400 300 500 450

460 XL 974 539 (8) 35 (8) 190 247 - 250 - 300 -460 YO 974 180 (8i 35 (8) 190 247 - 250 - 300 -

208 XL (2) SO 1788 1040 (10) 70 (10) 380 326 402 400 0000 500 500(1) 60 2051 1228

208 YO (2) 50 1788 347 (10) 70 (10) 380 326 402 400 0000 500 500(1 60 2051 409

230 XL (2) 50 1788 1040 (10) 70 (10) 380 326 402 400 0000 500 500 145 (1) 60 2011 1228

230 YO (2) 50 1788 347 (10) 70 (10) 380 326 402 400 0000 500 500(1) 60 2051 409

460 XL (2) 50 737 422 (10) 35 (10) 190 295 - 350 350 --(1) 60 904 485

460 YO (2) SO 731 141 10 (35) (10)190 295 - 350 350- -(1)60 904 162

208 XL 2051 1228 (10) 70 (10) 380 326 462 400 (2)250 500 600 208 YO 2051 409 (10) 70 (10) 380 326 462 400 (2)250 500 600

160 230 XL (3) 60 2051 1228 (10) 70 (10) 380 326 462 400 (2)250 500 230 YO 2051 409 (10) 70 (10) 380 326 462 600400 (2)250 500 600 460 XL 904 485 (10) 35 (10) 190 329 - 400 - 400 460 YO 904 167 (10) 35 (10) 190 329 - 400 - 400 - I

NOTES 1 XL Across the LineYOStarDelta 2 RLA Rated LoadAmps(ratedin accordance withARI Standard 590) LRA LockedRotorAmps 3 Wire Size Amps equal125of the ratedloadampsfor the largestmotorin thecircuitplus100of the ratedloadampsfor all othermotorsin the circuit per

NEC 4 Wire size based on copperconductorswith75C insulation perNECTable310-16 Terminal block lugs are sizedaccordingly Use of oversize wiringmay

not lit in terminal blocks 5 Maximumfuse size is basedon 175to 225of the ratedloadampsfor the largestmotorin the circuitplus 100of the rated loadampsfora othermotors

in the circuit per NEC VOLTAGE TOLERANCES 208V-230V min 187VMax 253V

480V Min414V Max506V

I

18

ELECTRICAL DATA Volts Type COMPRESSORModel FAN MOTORS MINCIRCUIT RECOMMENDED MAXIMUM 60 Hz of Oty RLA Starting FLAACWC LRA AMPACITY WIRESIZE FUSE SIZE 3 Ph Start Curro EaSC HP Ea Ea Ea Cire1 Cire2 Cire1 Cire2 Cire1 Cire2 208 XL 2051(1) 60 1228 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 1415 208 YO (1) 60 2051 409 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 472 230 XL (1) 60 2051 1228 (12)70 (12) 380 341 469 500 (2) 250 500 600

12 75 2083 1415185 230 YO (1) 60 2051 409 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 472 460 XL 485 (12) 35 (1) 60 904 (12) 190 352 500 400- - -

(2) 75 974 539 460 YO (1) 60 904 162 (12) 5(12)19 352 500 400- - -

(2) 75 974 180 208 XL 2083 1415 (12) 70 (12) 380 345 469 500 500(2) 250 600

472208 YO 2083 (12) 70 345(12) 380 469 500 (2) 250 500 600 230 XL (3) 75 2083 1415 (12) 70 345(12) 380 469 500 (2) 250 500 600200 230 YO 2083 472 (12) 70 (12) 190 345 469 500 500(2) 250 600 460 XL 539974 (12) 35 (12) 190 359 - 450500 - -

180 1(12) 35 460 YO 974 (12) 190 359 450 -500- -2051 1228208 XL (12) 70 504(12) 380 504 (2) 250 (2) 250 700 700

208 YO 2051 409 (12) 70 (12) 380 504 504 (2) 250 700(2) 250 700 (4) 60 2051 1228 (12) 70 230 XL (12) 380 504 504 (2) 250 (2) 250 700 700215

YO 2051 409230 (12) 70 (12) 380 504 504 (2) 250 (2) 250 700 700 460 904 485 (12) 35 XL (12) 190 225 225 0000 0000 300 300

(12) 35 460 YO 904 162 (12) 190 300225 225 0000 0000 300 2051 1228208 XL (2) 60 (14) 70 (14) 380 504 525 (2250 700 700(2)300

(2) 75 2083 1415 2051 409 (14) 70 700 700208 YO (2) 60 (14) 380 504 525 (2) 250 (2)300

(2) 75 2083 472240 700XL (2) 60 2051 1228 (14) 70 (14) 380 504 525 (2)250 (2)300 700230

(2) 75 2083 1415 2011230 YO (2) 60 409 (14) 70 (14) 380 504 525 (2) 250 (2)300 700 700

(2) 75 2083 472 300460 XL (2) 60 904 485 (14) 35 (14) 190 225 248 0000 250 300

12 75 974 539 904 162 250 300 300460 YO (2) 60 (14) 35 (14) 190 225 248 410

(2) 75 974 180 2083 1415 (2)300 700 700XL (16) 70 (16) 380 525 525 (2)300208 2083 1415 (2)300 700 700208 YO (16) 70 525 525 (2)300(16) 380

700 7002083 1415 (16) 70 (2300230 XL (16) 380 525 525 (2300 700 700(2300(4) 75 2083 472 (16) 70 (16) 380 525 525 (2300230 XL265

300250 300974 539 (16) 35 248 248 250XL (16) 380 460 (16) 35 300 300974 (16 380 248 250 250YO 539 248460

NOTES 1 XL Across the Line YO Star Delta 2 RLA Rated Load Amps (rated in accordance with ARI Standard 590) LRA Locked Rotor Amps 3 Wire Size Amps equal 125 of the rated load amps for the largest motor in the circuit plus 100 of the rated load amps for all other motors in the circuit per

NEC 4 Wire size based on copper conductors with 75degG insulation per NEG Table 310-16 Terminal block lugs are sized accordingly Use of oversize wiring may

not fit in terminal blocks 5 Maximum fuse size is based on 175 to 225 of the rated load amps for the largest motor in the circuit plus 100 of the rated load amps for a other motors

in the circuit per NEG VOLTAGE TOLERANCES 208V-230V min 187V Max 253V

480V Min414V Max506V

19

0

(Wd~) 3lV~ M011 ~31VM

006 009 00 OOt OOl OS L 00 L os 0 Ot

V D m (I) (I)

c D m c D o V

- m m -t o

~

~ m D-

aoao 3~nSS3~d ~3100~

APPLICATION DATA

POINT LOADING

ArMi I 1 5 1

ACWC 45 THRU 10 SC

COMPRESSOR CONDENSER SECTION SECTION

_ 2 4 bull 1

bull CA

J

Model Dimensions Size A B C D 45 91 - - -55 91 - - -70 145 - - -90 145 - - -110 60 40 160 -125 60 40 160 -135 60 40 160 -145 138 74 107 -160 13830 74 107 -185 138 129 107 -200 138 129 107 -215 106 82 106 80 240 106 82 134 107 265 133 110 134 107

1310

1310

~

1

1310

2

ACwe 110 THRU 200 Ie

COMPREIlOfl CONDENSER SECTION IECnoN

4 -

5Imiddot

ACWC 2t5 THRU 215 SC

Model Loadlnu (LBS) Size 1amp2 3amp4 5amp6 7amp8 9 amp10 45 585 765 550 - -55 705 810 635 - -70 660 890 700 - -90 1025 1500 1175 - -110 1195 635 1525 995 -125 1255 690 1835 1115 -135 1255 665 1880 1105 -145 1330 2380 2160 1450 -160 1330 2440 2280 1515 -185 1235 2575 2980 1360 -200 1275 2635 3020 1380 -215 1010 2270 2590 2240 840 240 1115 2550 2870 2715 1125 265 1380 2980 3515 2750 1175

11

II i middot 2 4 lIf 11 to L

21

TROUBLESHOOTING GUIDE

CHILLER UNIT WILL NOT START POSSIBLE CAUSE REMEDY 1 Power off 1 Check main disconnect switch

2 Main line open 2 Check main fuses

3 Incorrect wiring 3 Check the wiring diagram

4 Loose terminals 4 Tiqhten all terminals

5 Control circuit open 5 Check phase loss monitor flow switch circuit breakers temperature control low ambient thermostat low temperature thermostat remote switch etc

6 Time delay 6 Wait

COMPRESSOR HUMS BUT DOES NOT START

POSSIBLE CAUSE REMEDY

1 Low voltage 1a Check at service and unit for loss

b Consult power company

COMPRESSOR CUTS OUT ON LOW PRESSURE SAFETY CONTROL POSSIBLE CAUSE REMEDY 1 Refrigerant shortage 1 Check for leaks -- add refrigerant 2 Restriction in liquid line 2a Plugged strainer - dean or replace

b Liquid line valve partially closed - open valves fully c Expansion valve clogged or inoperative - clean or replace as

required d Solenoid valve partially open - clean or replace as required

3 Low water flow thru cooler 3 Check water flow thru cooler and correct as required

COMPRESSOR CYCLES ON HIGH PRESSURE CONTROL POSSIBLE CAUSE REMEDY 1 Compressor discharge valve partially closed 1 Open valve fully 2 Non-condensible gases in system 2 Operate condenser fans with compressors off If condenser

pressure exceeds saturated pressure corresponding to condenser entering air temperature then purge air from discharge line

3 Overcharge of R-22 3 Purge system while in operation until head pressure reaches a normal level

4 Dirty condenser 4 Clean the condenser 5 Compressor discharge check valve not operating properly 5 Replace if necessary 6 Fans not running 6 Check pressure control setting

CAUSES AND PREVENTION OF FREEZE-UP CAUSES PREVENTION 1 Improper charging 1 Charge per manufacturers recommendation

2 Improperly set safety time delay 2 Check the safety time delay low pressure control for proper setting at the beginning of each season

3 Improper chilled water circulation 3 Use an ample sized cleanable strainer in the chilled water circuit Make certain the strainer is clean to insure full flow and velocity of

chilled water It may sometimes be necessary to treat the water to prevent formation of deposits

4 Not draining for winter shutdown 4 When the system is shut down for the winter remove the drain

plugs and drain the cooler Blowout any remaining water with air

5 Improper pump shutdown 5 Make sure chiller barrel heater is working and flow switch is installed per wiring diagrams

6 Low ambient during air conditioning season 6 Make sure chiller barrel heater is working

NOTE If the ambient temperature is below 32degF freezing can be completely prevented by one of two methods

1 Drain all water from the equipment 2 Add antifreeze to the water

22

START-UP CHECK LIST

Unit Model No

Setting unit

Wiring

Piping

Alignment

Before Start-Up

After Start-Up

Yes No a Vibration isolator used

b Spring isolator adjusted for equal height c If rubber-in-shear isolators are used is unit leveled by shimming

a Power wiring complete

b Control wiring complete c Electric service adequate for load

d Power source voltage correct for motor(s) used

e Motor circuit has proper size fusetrons f System wired per diagram

g All lead connections tight h Wiring complies with local codes i Flow switch operation

a Piping complies with applicable codes b External piping independently supported c Chilled water lines insulated

a All belts adjusted and checked for tension b All pulleys checked and adjusted for proper pitch tightness and

alignment

a Open compressor discharge service valve b Open liquid valve(s) c Open suction and discharge valves to pressure gauges (if supplied) d Check rotation of all fan motors e Start auxiliary equipment (pumps fans etc) f Is crankcase heater operating Operate 24 hours prior to unit startup g Check the compressor oil level through the crankcase sight glass The oil

level should be to the top of the glass If the level is low add oil in accordance with the directions in the maintenance instruction

h Check all control settings as specified in Table 1 I Air purged from chilled water system

a Check high pressure control b Check oil temperature safety switch c Check and adjust low pressure or temperature freeze control d Check and adjust operating thermostat e Check and adjust low pressure operating control f Check and adjust expansion valve superheat g Check and adjust capacity control thermostat

23

OPERATING DATA CHILLER Voltage L-1 L-2 L-3 _ Pressure Gauge Readings 1 Suction psig 1 Discharge psig 2 Suction psig 2 Discharge _ psig 3 Suction psig 3 Discharge psig 4 Suction psig 4 Discharge _ psig High pressure switch setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-in) psig psig (Out) 4 (Cut-In) psig psig (Out) Checked Setting - Yes - No (each circuit) Low Pressure Switch Setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-In) psig psig (Out) 4 (Cut-in) psig psig (Out) Checked Setting -Yes -No (each circuit) 1 Oil Temperature Safety Switch Cut Out 2 Oil Temperature Safety Switch Cut Out 3 Oil Temperature Safety Switch Cut Out 4 Oil Temperature Safety Switch Cut Out If Star-Delta start time delay is seconds Temperature of air entering condenser F Temperature of air leaving condenser of Temperature of chilled water entering chiller OF Temperature of water (chilled) leaving chiller F Chilled water pressure entering chiller psig Chilled water pressure leaving chiller psig

MAINTENANCE Good maintenance practice will prolong the chiller life and will reduce the Ask of system breakdown and expensive service calls

A weekly check of the ACWC-SD unit requires only a few minutes and will prove beneficial in insuring long trouble free operation

WEEKLY CHECKS- with unit in operation for at least four hours 1) Check compressor oil level - At least above 12 of sight glass 2) Record suction and discharge pressures

Typical Condition R22 Ambient 95degF Return water 55degF Leaving water 45degF Suction 62 psig Discharge 270 psig

3) Record ambient temperature 4) Check liquid sight glass

Make sure liquid is clear - no bubbles 5) Check that all fans are running 6) Check entering face of condenser coil for cleanliness 7) Record voltage at unit

All of the above can be performed by building maintenance personnel If oil levels are low or any of the above checked items are questionable consult a qualified serviceman

At least once a year a qualified serviceman should check unit oil levels superheat and control operation

DUNHAM-BUSH USA

P l) bull 130 xUtUC t01 Bmgess RO~ Harrisonburg VA 22801 Phone (540) 434-0711 FAX (540) 434-~ 2118

wvvwdunham-bushcom Form No 6184

Page 8: ACWC-SD - · PDF fileACWC-SD • Screw . Type • • • Air-Cooled Packaged Chillers •• Installation, Operation, and •• • Maintenance Manual • • • •• DESCRIPTION

--

exgt

LE

GE

ND

m

rrbullbull

saN

OI

IlIG

CI-

Z

CO

HT

AC

TQ

ftmiddot (

0

[5

10

1t5

el

) C

ON

TA

ClO

middot A

NS

(C

UlT

middot pound

AM

III

bull C

ON

TO

L

(C

UlT

C

UtC

UIT

Ulaquo

III

H

IAT

EIt

I C

HllL

rU

lU

[AT

III

CU

Ne(

ASE

H

un

co

U

OIl

ll

SOL

ID

TA

U

MO

OU

Lt

H

US

UII

lI[

con

RO

L

LOW

Abullbull

IN

T

[

twO

fI

lO

W

nul

tt C

ON

TIIlI

OL

OIL

TU

II

r

UIIl

I(

SA

HA

S[

0

1$

M

ON

t T

O

lllE

LA

Tmiddot

tTA

GIH

O

1t[

LU

-U

CIT

Y ~OL

bull

CI

l

tC5

I H

el

C

Ubullbull

e

lHI

CC

HI

esr

P

I L

UI

VI

enst

P

LU

11

0)

(L

AY

middot tN

Uft

LO

CK

(

L[N

OIO

middot L

lOU

IO L

INI

SWIT

CN

CO

W

UD

C

C

UIT

S

SWIT

CH

ST

EN

fH(

MO

ST

AT

middot S

[OU

[Ne

EIt

TH

UM

OS

Tn

-L

OW

n

llI

IUU

[

TtIt

WIN

AL

10amp

1110

cu

no

wE

It

UN

I J

SO

LI

w

10

Tl T[l

Il

S

Tl

Ufl

Ul

10

0

-

CT

OII

I

WIl

WO

T

lM[

HU

T c

alli

CO

NTbull

bull L

OW

Ipound

n

LO

CC 0

1

TO

T

IllS

I

ond

tlt

UN

Lo

ao

t

OL

(NO

ID bull

(O

M

no

ll

Ul

ImiddotZ

~(

tU

IIL

T

IIS

VI

O

I

_

-~

OIO

HA

l

ell

C

UtC

Ul

[

amp1

(( -

(cri

VE

lli K

uru

en

C

IAC

Uff

A

UK

(jII

f bull

CO

[

I(

C(

OV

TL

lT

CI

I (O

NU

OL

If

Jll

AIr

IS

HO

UA

W

(fIA

S

LL

Tl

LO

AO

LI

T

(III

WO

STA

T

0

middot

5

O

(III

LO

AO

fU

UIS

LImiddot

H

OT

L

IGH

TS

H

IUC

IIY

[1II

H

[AU

IIIS

~ jllf

M1

III[

Cll

[

H

[U

t

US

UII

ll[

CO

NT

IIO

LS

~tCt

JVII

l N

(AU

III

14

(0

1

T

O)

TO

wI

DtL

AY

amp L

OW

U

tu

LO

CK

ou

r rt

(

O(L

IN

SlT

IO

C

OH

TA

(TO

Il

(O~USO

C

OH

O

lll

bull iT

A

OlL

C

Ol

CO

MV

[Nf

epound

o

un

n

Ctft

CU

lT I

DE

TA

IL

A

SlA

M

DE

LTA

ST

AR

T

O -~

OA

~ 5~U

Z

OI

Cl

U

I 14

(I

amp

~

NC

f

cl

AU

I

51

ZtA

LU

TOO C

21

NO

~~

bullbull

N

WHT

I---

I

l I J

II

A

CN

lCU

lT

If

OOHAI~

l

~i1

WH

It[

-

OI

ON

AL

r---

----

---

-I

Q

WT

I lt

raquo

I I L

JI

bull bull

I I

0

II

-

lJ

_ Ij

lf

I

cal

II

iOO

w

shy

) C

it

~

WTI~AL

r --------------------------------

Iamp

I

_l

[0

0

I

OO

CM

lL

00

LO

II

cu

U

II

bullL

~J

It

_U

I

TH

u

I

HT

I~

r-~~

~ --

-I=

=~==

=~I

11

2

N

~~~

~--

----

----

=~

I

-lt

l

= I

en

co

o J

rO~

2

~L

----------

-

-oS

f

I

r--shy

J

on

T

O)

vI

Q~~A

J T

Ot

L-

ll~_

f

1

II

CU

H ~

~OI

L1

-i

r---

----

-

~

10

rc

I

bullbull

lf

OIS

ti

l W

I H

Z

01

11

1

-J

o

u

L

shy

0bull

-

0 T

1

111

A -

bull 0

[0

HT

I

ll II

rgt ---

-ij

---

ITl~ll

t

1amp

I

1t

D

MIN

I[D

11

~

ill HTAILmiddot~

O

LM

I 01

1

OL

HJ

III0

1l~

tM

Ow

N

CI

amp

tt

I w

lO

OIO

HL

---

__

J

O ~

~Ll

~

tB1

It

CI)

n

IS

-1

M

k

V

Io

Jmiddot

r---

1

we

14

-4

I

Mill

I

CO

MPR

ESS

OR

C

IRC

UIT

I

Til

bull ~

r-

so li

e II

It

S

tON

L

N

O

fll

II

If

II

~

s~

o

oc

gt

(I)

r in

n

100

00U

lz

--I

~o

e

0

r ce

cn

shy0

0

Z

Ggt

bullbull bullbull bullbull bullbull bullbull bullbull

r~T~-

ICt

MQ

Teuro

CO

MT

It01

I T

IM C

lot

ll

~---

Cl

ll

(O

41

(

flO

W

5Wlf

CH

~

I

Olt

CO

NT

AC

TO

C

OIL

S C

I-I

bull C

tS

AN

D S

t sn

N

OW

IIt

Dll

QU

0

1 C

OM

UC

TI

I

111

114

0

(

U

II

NO

f T

O I

(

C

uNO

IO

ON

UtI

se

CO

HO

UI

li

D(

1

A

ND

1

n

WP

(IU

ult

l S

(NIC

tf1

I

LO

CU

ID

1M bullbullU

O

UT

UT

r-

----

shybullbull

0

11

UO

V

HA

Il

LO

IS

raquoON

TO

S

TE

lurN

AU

bull

AN

D

0111

IIC

O(

I A

ND

A

U(

Cfl

YpoundL

Y

So

C

rt

TO

0

0 M

AN

UA

L a

ll H

TO

tNT

AN

D

~10l

IA

NO

M

TII

UC

TtO

NS

II

rCO

tNO

m

IMIT

AL

CO

H

laquo

0

U

TI

I It

4

Ishy

C

OW

III

ISO

R

MO

DU

LES

dC

NO

MmiddotA

U

VA

TC

I

D

U

1111

WIL

L A

LSO

LO

C_ O

UT

(

let

Umiddot

I C

AL

L

WH

IM

IAI

TY

flit

TH

[I(

CO

Nmiddot

I

OL

I CA

Jrf I

I II

EM

T

IT T

Uft

I1

tW

ITC

H bullbull

0

VO

NIN

IL

f PO

C

Obullbull

bull

I w

UII

II

I

C

IL

Llf

i I

ITA

f[1

II

ItV

N

IWIT

ti r

raquo7

~Slt~1

~~~~( 1~~~~tlDOO

CO

N

CT

O

WU

UH

O 0f

II C

OW

bullbullbullbull

~~1

II

bull

LL

TI

lIT

AT

0

N

O 1

0 O

CA

TID

1

1 I

I IIl

ETU

IIPt

W4T

P

LU

WHE

N u

TI

It N

OT

lU

u

rD

ttl

III I

ICO

Ma-

aU

0 11

nM

H

u

l

UN

I()1

II M

UST

HA

V(

SH

llL

DID

C

AU

I

LO

Me

T

II

no O

R

ItUM

WT

M

ItO

WI

L

IAH

to u

ri N

T I

T H

-

ITbullbull

O

N

ft

0

-

011

II~T

K

ITI

GU

ION

An

ON

S

o H

O-

ON

G C

OI

-W

it

11

N(

NO

6 N

c

CO

NU

ClI

W

If

lIN

( N

O

o N

0

CO

NT

AC

TS

WIt

K

liN

t N

O

6 N

OT

t I

TH

L

Nt

NO

Y S

UI

-I

IS

5_

1

~

~

no

~ I

I I_

VLOA

Or- I

I ~~

vumiddot

S1 so

CO

Hit

so

0

amp

g A

SI ~

I

1

7100-

I -I

I 01

10

OH

0

10

f T

AN

I V

I

] CM

NG

( av

rlt

10

0 O

K__

ST

AG

(

COD

lJ-

L7

00

~It

A

lIT

00]

VL

I fi

ll

14

1

10A

O

f

_ III

rC

OH

O

In o

y

00bull

00

10 ~

0

10

CO

Ol

C

bull

] 4

U

rr

COL~

bull Jo

un

J

W bull

C~P

OJ [

ou

-t

urO

NT

01

CO

l0

1

N

Omiddot

~ ]

(jCO~_

0

)

un

ll

n ~

T

I 11

I1

III _~

n

~

amp

7

10

II

01

u II 17

II

0

II

01

IS

-I

-lt

sE

o

0 c

raquo

CD

r iii

0

~O

U

lZ

+-1

~

tI

t

0

r QE

CIJ

-c

tl

Z

Ggt

lt0

bullbull bullbull

bullbull

bullbullbullbull

~

o

tUN

oa

lllO

_--

-

shyC

t-4

CII

C

cn

bull

tlN

I

CC

HImiddot

t

csnu

middota

--1

LA

T

loP

a

01

11

-1

111

111

IIImiddota

It

4

IOL

IS

IW

Imiddot

I

I T

I n flbull

bull

TO

middot I

st

U

LImiddot

a

Oft

lo

tL

LtG

EN

D

CO

NlA

CT

IM ~

CO

lllf

lllt

UtO

JII

CO

NT

AC

TO

CII

CU

fT

IIIC

AICC

III

CO

NTJ

IIOL

CIC

UIT

U

NImiddot

HU

TI

eNU

LlII

I

Il

I

AU

It

C

NlaquoC

AU

NC

An

C

O

UIO

10

LIO

T

AU

N

t U

SU

I C

O T

OO

L LO

W

eT

fM

llltM

OT

AT

L

OW

Hl

III

UII

I C

Oft

TJl

OL

OU

n

ru

ulltl

A

nT

T

HA

-

0bullbull M

OH

IfOIt

fl

lLA

Y I

AO

INI

MU

C

AN

cn

CO

fTltO

Ibull

ItIL

A

INT

ILO

CIC

OL

EN

OtD

Ll

OU

ID L

INt

Cc

ulT

MOO

ULIE

C

NIC

CA

SE

ItS

C

(

OM

II

IOII

(lI

IieLf

W

I eM

-

UIE

R

TH

III

OIT

6Tmiddot S

lOU

lC

U

MC

ot

LOW

TlM

e

U1

T

lER

bullbull

L l

OA

JIIO

middotCU

lTo

tJ

II W

UU

Nt

TI

M

AL

IO

D

oC

0It

1 U

IIN

t T

IMe

OC

LU

middotCA

II C

ONT

a

LOW

IU

t L

OCK

OUT

NPD

WIU

UN

LOA

Olil

t 1

0L

(NO

I0

C

O

III

OIl

lI

cn

CIJ

tCU

IT

UII

lEIt

ft

EC

poundIV

E H

IAI

C

Ol

(C

UIT

1I

IUIIl

I1II

CO

NY

(NIE

NC

E

OU

TU

T

CU

I C

ON

nlo

0

1

AN

$ M

ill1

1

HO

YIll

MU

II

lLT

I l

OA

O

LlI

lIIT

T

H(

O

ITA

T

OL

O

VC

LO

AO

MIA

nl

L1

lI1

~HAII

LO

IS

MO

NIT

O

L

Imiddot J

~fOT

L

IOH

TS

1

1

IC

IIV

E

HE

UE

ItM

lIC

tmiddotl

rC

IIV

E

MU

TlI

t l

tIIS

UIl

l(

CO

NT

ItO

LI

T

lmiddot1

C

CC

lvllt

N

EA

fllt

T

lW

OS

TA

lI

TO

Jmiddot 4

T

INe

H

LA

Y

LOW

In

vlt

l LO

C

OU

T

1O

t-1

ft

lll

D

UA

Tmiddot

TA

SIT

ION

C

ON

TAC

TO

Ill

$middot

1

CO

C

O

(

lIO

C

ON

TA

CT

O

T

A

Dn

u

CO

WC

tllltN

CI

ount

T

DE1AIL~

ST

AR

D

EL

TA

S

TA

RT

r

2

~f

10

t10

II

amp

II

11

II

)

1IllI

1IU

--shy

OW

E

IV

-

utv

lO

f

I I Ibull

A

UR

C

IlltC

UIT

C

IRC

UIT

ALA

NlC

UfT

C

lflC

UIT

I I

I

~li

IT

I

Ot

ON

AL

il------~---l

-

tL

J --

--

C

it

prIlgjf~

II

ell

I

I

IfB

I

t

---------~~-------

__

~

L_ -

7 -

-r--

et

r

I

II10

-I

CII

-lt

PL

1amp

I I

II b

I

L _

__

J

II 3

2I

oo

II

Qraquo

~

IS

lI

(

)r-

t-_

_ o

J_

_

O

TIO

L

I ~~

--~-

I

I CD

oL

__

__

__

__

__

CO

I- f

_

JI I

t degz

OI

OIl

lAL

r-

---

IS

r

-l

0

I

I

+10$

IL

KS

I T

e

0 Lr

I J

II

T

ITI

lOL

l 1

40

bull (C

IS)

TO

bullbull

lD

A-

~ -

r--

-~l

)~II

I

~G

__

_~L_J

0

O

HA

I

~ -

-Ill

-

---

-10-

--

~E

II

cn

-C~

II

Z

0

G)

Il

l~

r- I W

lllltO

WH

IN

JU

L1

l0

I I

I

OL

M

OL

MI

OL

I ~ro

o

jo

o

Jt

JI

L

OT

10N

AI

II

0

(01

0 CO

MPR

ESS

OR

C

IRC

UIT

~

27

III

gt

0

IIA

IO

amp1

)amp

1

1

II

~

I rA

I

TA~

D

ELTA

STA~T

CONP~E~)

CU

lT 2

~

f

bull ]

A

U

4 ]I

IUft

middotJI

Mon

tUPlOI

NT

lOA

Ot-

-O

I

01

0

]

(N

GI

011

1

00

CT

AN

)

40

00

HN

a

_N

I

J00

I -

It IC

y

TO

I

I I

I

~

oiiO

NA

t

I bull bull

wi

i

lOa

r~TT~-

I M

OT

I C

ON

sr

0

llItt

(

co

ce

OZ

UK

1

11

_JO

I I

)--11

--

- ---

-

IJI

LD

~

I

A

CK

lS

C

UK

I

IL

UO

A

TO

O

WH

IT

1

L

OW

SW

ITC

HJl

AL

D

00

IZ

I

f

1It-

-

rl__ u-

poundL

J f

aT

ION

AL

TI

WfI

OO

f

~

ff

I

Dill

C

ON

TAC

TOIlI

C

OtL

S (1

middot4

(IS

middot14

A

ND

II-

I

01

1In

N

O

Wl

0

51

11

~

CO

NT

AC

TS

I

fH

IO

Uti

IS

N

OT

TO

IE

al

llauN

DIO

O

N H

I Sr

CO

NO

AIl

lf

StO

l

f

I

TI

AN

D

TI

TI

U

I

IIN

OII

t

0middot

f1L

OC

AT

IO

IN n

lll

GU

lUT

r-

----

shy~

(I

G

lIt

no

v

HA

I

LO

SS M

ON

IO

nf

1Na

bull

AN

D

ON

rc

I(

CO

M(

f A

IrfD

I

lItU

rC

TIY

(U

00

-

5

E

[CO

OIO

lItc

rlll

TO

0

0

AN

UA

L

t

OIN

T A

Na

f

oo

IlU

COfrt

TO

I U

ND

IN

Stt

UC

TIO

trl

r

co

rNH

D

01 11

raquoIN

ITIA

L

CO

NT

lIIiO

L

fII

I0 I

UT

IS

a

jshy

orshy

10bull

CO

M1

II1t1

Ol

MO

GU

LI

I N(

tN-a

UT

OM

AT

lC

I 1I

lfla

n

flS

bullbull

11

A

LSO

ampO

eMmiddotO

UT

luer

llt

middot I

no

C

AL

Y

WH

IM A

N

IUIT

T T

IIII

P

T

MU

I C

ON

egoo

IT

flO

LI

CA

l

ItU

I1 I

T

TU

NIN

G W

ITC

M

0

~r=

0 I

lIO

Wlf

lIT

A

L

fOtt

CO

lI

tbullbull

w

ITC

H_

I

on

WO

Nlf

lIT

JII

IL

POllt

COW

bull

I In

degz

r+-i

~~

t

u ~o

1 ~rI~~

~~

~~TtIc~~I~D

1

SW

lTC

HI ~

C

OIfT

AC

TcU

t W

lItN

t C

OM

bullbull

H

To

lIL

b

l

0t~~1

0

1

CO

tfC

TO

H

I

lIt

C

ltbull

IIT

C

~r-

bull

WM

IH

-

2

N

OT

1V

l

rD

wllI

I[ to

IlIC

OM

n

I W

I

It

I

fjC

Ofl

P

tE

CJ)shy

t W

IN L

UI N

OT

SU

PL

ID

W

IIIIC

O

J

lleo

W

ti

l

LU

KT

IT

10- A

ND

10ft

II

v

C~

LO

CA

TU

I II

1t

11V

MI

_T

at

I

z10

I

T

lNH

A

TU

RC

S

lNS

OIt

MU

tT

ve

IL

OID

C

IL

C

()

11II

L

AT

I

AT

10

_

A

U

IIIT

I0middot

PCA

LOW M

I_ lO

TI

I bullbull

n

II

DES

IGN

ATI

ON

S

II

CO

NT

IlID

t I

NO

-o

MO

LD

INfl

C

OIL

It L

tNI

NO

0

Q

N

C

CO

NU

ClI

W

ITH

UN

I N

O

01]

0 co

O

f

11

~

I

ILK

n

e

s IA

UL

It

ibull

o O

CO

NTA

CTS

w

nw L

INI

NO

01

fA

0

~

fItO

TI

LI

I N

O

v

A

II

~ ~ bull i middots

~

~~ - ~

~

1- I J I J I I I I I I I I I I I I I I L __ J

I

a bull bull a bull bull

I I I

_J

r------~

=~I = ~ ~ bull ~ I I

~

as coe ruq SV~ siapow ~NI~IM lO~lN03lV3ldAl

i 4

_

a

~FirI1 u~III - I I

~ 1I

00000 -

I=II~I~~~~raquoIIIItIII~ampI~

as ooz nJ4l sv ~ siapow ~NI~IM lO~lNOgt TVgtldAl

bullbull bullbull

bullbull

~

jgt

lpoundIt

ND

II

co

----

----

----

----

----

----

----

----

-

r-~-middot--=-~~

~

bull a

~

at~04

5

---

~1I

A

~n

bullbullmiddot-shy

wo

_-

bull

lIt

C-

I C

Cf

aC

TO

Ic

ow

n

CC

eM

ca

~C

M

OD

IAI

CI

T-

CO

IITA

CT

oa

bullbull

CMCU

rT I

ItIM

IA

co-l

to

c-c

VIT

C

I

rr

c

AfE

bull r~----Ef1

POW

I

III

IQ

W

Q

tIL

UT

I1I

U__~

J

COt

I

LD

W M

lMtr

f nc

IIO

ff

0

N

LO

W

C

OIIT

INM

I I

CO

M

US

ON

C

NC

UIT

II

II

-~

_T

shy

C

O

NU

SO

II

CIN

CU

IT Z

II

D[TA~

-

ST

AN

D(~TA

IT

AII

T

0

u III

r

amp

II

-~

If

10

MA

MI

eN

talI

Tco_

~

STA

N D[~TA

ST

AII

T

~

CIS

-I

LA

~ 1-4

nmiddot

00

-

-II

1t1S

-1 aw

o fI

fl

U- I -~ Ci

Pi=

i

t

shy

~

iii

i

iii=

ii

-

-shyiii

ClL

n

TU

U

LOt

e

bull It

lLA

Yn

C

AM

Im

CIII

IID

L bull

CU

_C

Abull

fl

lUY

_f

tMO

ea

UY

middotIO

CI

lO

Ll

t

NIU

_L

N

CO

WU

UO

ItC

U

llT

l bullbull 0

1middot

lit

TMC

MI0

8TA

T tc

_lt

CIl

it

11

II

_

middotLO

W

TII

IfN

T

UIlI

C

nll

-

D-C

UlT

QIIU

tW

n-T

PII

IU

LIO

MI-

AC

TC

Ntf

Wi

MI

II

II

tY

middotCM

OO

C

LOW

HIe U

(O

Uf

lIl_

L

OA

M

1OtI

1tO

lD

CO

OA

CM

UtT

1M

C

lIY

Dl

NC

Afi

ll ea

-tU

lT 1

ItUbullbull

lI

oo

ww

lItt

lffc

e O

Un

n

cT

IlG

I

Ie-

~U

IIIC

CIV

P

1T

1lt

C

bullbull

Off

AT

tw

ebullbull

ampOW

IC

IUT

~-

4ti

iT

~

co

ww

O

UfU

T

DITA~

A

ITA

A

OEL

TA

IT

AJI

IT

co

rn~

e

I

1amp

ItmiddotI

~ bull

I I

I

I r

~

bull Iamp

II

I ~

I-

oJ

II I

IrIf

I I I I

s~

o

-I I

ltDc

() raquo

L 10

V

i

()

~O

to

U

lZr0

t2

llJ

IL

C6

J=

_J

~-1

f

II

c 0

II

N

ge

cno

c-

II

Z

Ggt

If IO

IC

IIY

II

IIR

III

IJt

T H

llII

A

Il C

Olaquof

U

TMIbull

~LDM

fI

lAR

PM

Iamp L

Oll

lTV

ii

iLii

Uii

ii

~

U3

I iL

iii=

i

Uii

u

i

O

(no)

T

bull II

1

IOA~

bullr

~ I

[gtO(]O

~ i I Ii i 2 ~ ~ ~ i a bull il 2 ~

iiibullbullbull

~ I ~ I I I ~~ =l ~ iI I ~ I I I It I 1111 amp ~~

as ooz nJ4l SP~ SlapoUII ~NI~IM 10U1NOl lVlldAl

-------

---

TYPICAL POWER WIRING Models 45 thru 70 SC

----

rYl31I01 I

-Ii --ti-

_ I ~_-

~ lniJ -

LIIbullbullbullbull PC _ amp-II _--- ~

TYPICAL POWER WIRING Models 90 thru 135 SC

- --- _ Tt

~rfh c~

tP ~

_III ~

I r-- ~- IIlJ

bull - MIl Mf __ bull Ie_~--~ _shy- shy16

---

----------

TYPICAL POWER WIRING Models 145 thru 200 SC

_ --1a1 IIUrI

middotrFti~v_ bull I

i~i ~~ TaII IIOMLI ~tN T 100 WTIOII 011 lilOOCL a

~ t1

tI bullbullbull

L

i I r-~

I r

~ ~ ~ III

2 ~ ~ ~l

- ~IlD I hJOHr eo teO acshyt CmiddotClM ~ CIKUr1 --

TYPICAL POWER WIRING Models 215 thru 265 SC

ItUU 1D Wll1U1I fIa -rMI

rt-h I -au 11 1_ i r~ rt-f

-i rn f1 ft fi i- llil bullbull c~ I bull c =

~~~ ~i~-~

~~m

~~~CI1 R~~ ~ ~~ ~llAi4I

luv~ bull ~uf LL~~-

~Mfl l~t IrMiA

a I III nII I bull it d

~-t--J I Lll-l~j ~nL4111 WlJj== lit-

I bullbullbull I

UGEND

~

~l OJ

- c~

~~~---

~)~middotI

I

L _~~~ L _I__~_J I ~ (11_1 ~ H~ CUlTMIt tffC_) Ll N

-r_ 0 1ItCIIIl0AI lllQUlllCo as -0- bull bullbull fI PC 110 lNJCllII a Olil1100pound1 II 111 el 1101 ItCOU_ 011 IIOOIL140

I 011 CI-( H[ (0110 (fMCun ubullbull --- l(lD IMbullbull Ntlf 110 e414-7

--CTOttbullbull

2

17

ELECTRICAL DATA Model Volts Type COMPRESSOR FAN MOTORS MIN CIRCUIT RECOMMENDED MAXIMUM ACWC 60 Hz of Qty RLA Starting FLA LRA AMPACITY WIRESIZE FUSESIZE

SC 3 Ph Start HP Ea Curro Ea Ea Ea Circ1 Circ2 Circ1 Circ2 Circ1 eire 2

208230 XL 1788 1040 (4) 70 (4) 380 252 - 250 - 400 -45 208230 YO (1) 50 1788 347 (4) 70 (4) 380 252 - 250 - 400 -

460 XL 737 422 (4) 35 (4) 190 106 - 2 - 175 -460 YO 737 141 (4) 35 (4) 190 106 - 2 - 175 -

208230 XL 2051 1228 (4) 70 (4) 380 284 - 300 - 450 -55 208230 YO (1) 60 2051 409 (4) 70 (4) 380 284 - 300 - 450 -

460 XL 904 485 (4) 35 (4) 190 127 - 1 - 200 -460 YO 904 162 (4) 35 (4) 190 127 - 1 - 200 -

208230 XL 2083 1415 (6) 70 (6) 380 302 350 500 -70 208230 YO (1) 75 2083 472 (6) 70 (6) 380 302 350 500 -

460 XL 974 539 (6) 35 (6) 190 143 0 225 -460 YO 974 180 (6) 35 (6 190 143 0 225 -208 XL 1788 1040 (6) 70 (6) 380 266 224 300 0000 400 400 208 YO 1788 347 (6) 70 (6) 380 266 224 300 0000 400

90 230 XL (2) 50 1788 1040 (6) 70 (6) 380 266 224 400 I300 0000 400 400 230 YO 1788 347 (6) 70 (6) 380 266 224 300 0000 400 400 460 XL 737 422 (6) 35 (6) 190 187 - 000 - 250 460 YO 737 141 (6) 35 (6) 190 187 - =1000 - 250 208 XL 2051 1228 (8) 70 (8) 380 312 256 400 300 250 208 YO 2051 409 (8) 70 (8) 380 312 256 400 300 500

110 230 XL (2) 60 2051 1228 (8) 70 (8) 380 312 256 g I350 300 SOO 450 230 YO 2051 409 (8) 70 (8) 380 312 256 350 300 500 450 460 XL 914 485 (8) 35 (8) 190 231 - 0000 - 300 460 YO 904 162 (8) 35 (8) 190 231 - 0000 - 300 -

208 XL (1) 60 2051 1228 (8) 70 (8) 380 312 260 400 300 500 450(1) 75 2083 1415

208 YO (1) 60 2051 409 (8) 70 (8) 380 312 260 400 300 500 450(1) 75 2083 472

230 XL (1) 60 2051 1228 (8) 70 (8) 380 312 260 350 300 500 450(1) 75 2083 165125

230 YO (1) 60 2051 409 (8) 70 (8) 380 02 260 350 300 500 450 (1) 75 2083 472

460 XL (1) 60 904 485 (8) 35 (8) 190 240 - 250 - 300 -(1 75 974 539

460 YO (1) 60 904 162 (8) 35 (8) 190 240 - 250 - 300 -(1) 75 974 180

208 XL 2083 1415 (8) 70 (8) 380 316 260 400 300 500 450 208 YO 2083 472 (8) 70 (8) 380 316 260 400 300 500 450

135 230 XL (2) 75 2083 1415 (8) 70 (8) 380 316 260 400 300 500 450 I 230 YO 2083 472 (8) 70 (8) 380 316 260 400 300 500 450

460 XL 974 539 (8) 35 (8) 190 247 - 250 - 300 -460 YO 974 180 (8i 35 (8) 190 247 - 250 - 300 -

208 XL (2) SO 1788 1040 (10) 70 (10) 380 326 402 400 0000 500 500(1) 60 2051 1228

208 YO (2) 50 1788 347 (10) 70 (10) 380 326 402 400 0000 500 500(1 60 2051 409

230 XL (2) 50 1788 1040 (10) 70 (10) 380 326 402 400 0000 500 500 145 (1) 60 2011 1228

230 YO (2) 50 1788 347 (10) 70 (10) 380 326 402 400 0000 500 500(1) 60 2051 409

460 XL (2) 50 737 422 (10) 35 (10) 190 295 - 350 350 --(1) 60 904 485

460 YO (2) SO 731 141 10 (35) (10)190 295 - 350 350- -(1)60 904 162

208 XL 2051 1228 (10) 70 (10) 380 326 462 400 (2)250 500 600 208 YO 2051 409 (10) 70 (10) 380 326 462 400 (2)250 500 600

160 230 XL (3) 60 2051 1228 (10) 70 (10) 380 326 462 400 (2)250 500 230 YO 2051 409 (10) 70 (10) 380 326 462 600400 (2)250 500 600 460 XL 904 485 (10) 35 (10) 190 329 - 400 - 400 460 YO 904 167 (10) 35 (10) 190 329 - 400 - 400 - I

NOTES 1 XL Across the LineYOStarDelta 2 RLA Rated LoadAmps(ratedin accordance withARI Standard 590) LRA LockedRotorAmps 3 Wire Size Amps equal125of the ratedloadampsfor the largestmotorin thecircuitplus100of the ratedloadampsfor all othermotorsin the circuit per

NEC 4 Wire size based on copperconductorswith75C insulation perNECTable310-16 Terminal block lugs are sizedaccordingly Use of oversize wiringmay

not lit in terminal blocks 5 Maximumfuse size is basedon 175to 225of the ratedloadampsfor the largestmotorin the circuitplus 100of the rated loadampsfora othermotors

in the circuit per NEC VOLTAGE TOLERANCES 208V-230V min 187VMax 253V

480V Min414V Max506V

I

18

ELECTRICAL DATA Volts Type COMPRESSORModel FAN MOTORS MINCIRCUIT RECOMMENDED MAXIMUM 60 Hz of Oty RLA Starting FLAACWC LRA AMPACITY WIRESIZE FUSE SIZE 3 Ph Start Curro EaSC HP Ea Ea Ea Cire1 Cire2 Cire1 Cire2 Cire1 Cire2 208 XL 2051(1) 60 1228 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 1415 208 YO (1) 60 2051 409 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 472 230 XL (1) 60 2051 1228 (12)70 (12) 380 341 469 500 (2) 250 500 600

12 75 2083 1415185 230 YO (1) 60 2051 409 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 472 460 XL 485 (12) 35 (1) 60 904 (12) 190 352 500 400- - -

(2) 75 974 539 460 YO (1) 60 904 162 (12) 5(12)19 352 500 400- - -

(2) 75 974 180 208 XL 2083 1415 (12) 70 (12) 380 345 469 500 500(2) 250 600

472208 YO 2083 (12) 70 345(12) 380 469 500 (2) 250 500 600 230 XL (3) 75 2083 1415 (12) 70 345(12) 380 469 500 (2) 250 500 600200 230 YO 2083 472 (12) 70 (12) 190 345 469 500 500(2) 250 600 460 XL 539974 (12) 35 (12) 190 359 - 450500 - -

180 1(12) 35 460 YO 974 (12) 190 359 450 -500- -2051 1228208 XL (12) 70 504(12) 380 504 (2) 250 (2) 250 700 700

208 YO 2051 409 (12) 70 (12) 380 504 504 (2) 250 700(2) 250 700 (4) 60 2051 1228 (12) 70 230 XL (12) 380 504 504 (2) 250 (2) 250 700 700215

YO 2051 409230 (12) 70 (12) 380 504 504 (2) 250 (2) 250 700 700 460 904 485 (12) 35 XL (12) 190 225 225 0000 0000 300 300

(12) 35 460 YO 904 162 (12) 190 300225 225 0000 0000 300 2051 1228208 XL (2) 60 (14) 70 (14) 380 504 525 (2250 700 700(2)300

(2) 75 2083 1415 2051 409 (14) 70 700 700208 YO (2) 60 (14) 380 504 525 (2) 250 (2)300

(2) 75 2083 472240 700XL (2) 60 2051 1228 (14) 70 (14) 380 504 525 (2)250 (2)300 700230

(2) 75 2083 1415 2011230 YO (2) 60 409 (14) 70 (14) 380 504 525 (2) 250 (2)300 700 700

(2) 75 2083 472 300460 XL (2) 60 904 485 (14) 35 (14) 190 225 248 0000 250 300

12 75 974 539 904 162 250 300 300460 YO (2) 60 (14) 35 (14) 190 225 248 410

(2) 75 974 180 2083 1415 (2)300 700 700XL (16) 70 (16) 380 525 525 (2)300208 2083 1415 (2)300 700 700208 YO (16) 70 525 525 (2)300(16) 380

700 7002083 1415 (16) 70 (2300230 XL (16) 380 525 525 (2300 700 700(2300(4) 75 2083 472 (16) 70 (16) 380 525 525 (2300230 XL265

300250 300974 539 (16) 35 248 248 250XL (16) 380 460 (16) 35 300 300974 (16 380 248 250 250YO 539 248460

NOTES 1 XL Across the Line YO Star Delta 2 RLA Rated Load Amps (rated in accordance with ARI Standard 590) LRA Locked Rotor Amps 3 Wire Size Amps equal 125 of the rated load amps for the largest motor in the circuit plus 100 of the rated load amps for all other motors in the circuit per

NEC 4 Wire size based on copper conductors with 75degG insulation per NEG Table 310-16 Terminal block lugs are sized accordingly Use of oversize wiring may

not fit in terminal blocks 5 Maximum fuse size is based on 175 to 225 of the rated load amps for the largest motor in the circuit plus 100 of the rated load amps for a other motors

in the circuit per NEG VOLTAGE TOLERANCES 208V-230V min 187V Max 253V

480V Min414V Max506V

19

0

(Wd~) 3lV~ M011 ~31VM

006 009 00 OOt OOl OS L 00 L os 0 Ot

V D m (I) (I)

c D m c D o V

- m m -t o

~

~ m D-

aoao 3~nSS3~d ~3100~

APPLICATION DATA

POINT LOADING

ArMi I 1 5 1

ACWC 45 THRU 10 SC

COMPRESSOR CONDENSER SECTION SECTION

_ 2 4 bull 1

bull CA

J

Model Dimensions Size A B C D 45 91 - - -55 91 - - -70 145 - - -90 145 - - -110 60 40 160 -125 60 40 160 -135 60 40 160 -145 138 74 107 -160 13830 74 107 -185 138 129 107 -200 138 129 107 -215 106 82 106 80 240 106 82 134 107 265 133 110 134 107

1310

1310

~

1

1310

2

ACwe 110 THRU 200 Ie

COMPREIlOfl CONDENSER SECTION IECnoN

4 -

5Imiddot

ACWC 2t5 THRU 215 SC

Model Loadlnu (LBS) Size 1amp2 3amp4 5amp6 7amp8 9 amp10 45 585 765 550 - -55 705 810 635 - -70 660 890 700 - -90 1025 1500 1175 - -110 1195 635 1525 995 -125 1255 690 1835 1115 -135 1255 665 1880 1105 -145 1330 2380 2160 1450 -160 1330 2440 2280 1515 -185 1235 2575 2980 1360 -200 1275 2635 3020 1380 -215 1010 2270 2590 2240 840 240 1115 2550 2870 2715 1125 265 1380 2980 3515 2750 1175

11

II i middot 2 4 lIf 11 to L

21

TROUBLESHOOTING GUIDE

CHILLER UNIT WILL NOT START POSSIBLE CAUSE REMEDY 1 Power off 1 Check main disconnect switch

2 Main line open 2 Check main fuses

3 Incorrect wiring 3 Check the wiring diagram

4 Loose terminals 4 Tiqhten all terminals

5 Control circuit open 5 Check phase loss monitor flow switch circuit breakers temperature control low ambient thermostat low temperature thermostat remote switch etc

6 Time delay 6 Wait

COMPRESSOR HUMS BUT DOES NOT START

POSSIBLE CAUSE REMEDY

1 Low voltage 1a Check at service and unit for loss

b Consult power company

COMPRESSOR CUTS OUT ON LOW PRESSURE SAFETY CONTROL POSSIBLE CAUSE REMEDY 1 Refrigerant shortage 1 Check for leaks -- add refrigerant 2 Restriction in liquid line 2a Plugged strainer - dean or replace

b Liquid line valve partially closed - open valves fully c Expansion valve clogged or inoperative - clean or replace as

required d Solenoid valve partially open - clean or replace as required

3 Low water flow thru cooler 3 Check water flow thru cooler and correct as required

COMPRESSOR CYCLES ON HIGH PRESSURE CONTROL POSSIBLE CAUSE REMEDY 1 Compressor discharge valve partially closed 1 Open valve fully 2 Non-condensible gases in system 2 Operate condenser fans with compressors off If condenser

pressure exceeds saturated pressure corresponding to condenser entering air temperature then purge air from discharge line

3 Overcharge of R-22 3 Purge system while in operation until head pressure reaches a normal level

4 Dirty condenser 4 Clean the condenser 5 Compressor discharge check valve not operating properly 5 Replace if necessary 6 Fans not running 6 Check pressure control setting

CAUSES AND PREVENTION OF FREEZE-UP CAUSES PREVENTION 1 Improper charging 1 Charge per manufacturers recommendation

2 Improperly set safety time delay 2 Check the safety time delay low pressure control for proper setting at the beginning of each season

3 Improper chilled water circulation 3 Use an ample sized cleanable strainer in the chilled water circuit Make certain the strainer is clean to insure full flow and velocity of

chilled water It may sometimes be necessary to treat the water to prevent formation of deposits

4 Not draining for winter shutdown 4 When the system is shut down for the winter remove the drain

plugs and drain the cooler Blowout any remaining water with air

5 Improper pump shutdown 5 Make sure chiller barrel heater is working and flow switch is installed per wiring diagrams

6 Low ambient during air conditioning season 6 Make sure chiller barrel heater is working

NOTE If the ambient temperature is below 32degF freezing can be completely prevented by one of two methods

1 Drain all water from the equipment 2 Add antifreeze to the water

22

START-UP CHECK LIST

Unit Model No

Setting unit

Wiring

Piping

Alignment

Before Start-Up

After Start-Up

Yes No a Vibration isolator used

b Spring isolator adjusted for equal height c If rubber-in-shear isolators are used is unit leveled by shimming

a Power wiring complete

b Control wiring complete c Electric service adequate for load

d Power source voltage correct for motor(s) used

e Motor circuit has proper size fusetrons f System wired per diagram

g All lead connections tight h Wiring complies with local codes i Flow switch operation

a Piping complies with applicable codes b External piping independently supported c Chilled water lines insulated

a All belts adjusted and checked for tension b All pulleys checked and adjusted for proper pitch tightness and

alignment

a Open compressor discharge service valve b Open liquid valve(s) c Open suction and discharge valves to pressure gauges (if supplied) d Check rotation of all fan motors e Start auxiliary equipment (pumps fans etc) f Is crankcase heater operating Operate 24 hours prior to unit startup g Check the compressor oil level through the crankcase sight glass The oil

level should be to the top of the glass If the level is low add oil in accordance with the directions in the maintenance instruction

h Check all control settings as specified in Table 1 I Air purged from chilled water system

a Check high pressure control b Check oil temperature safety switch c Check and adjust low pressure or temperature freeze control d Check and adjust operating thermostat e Check and adjust low pressure operating control f Check and adjust expansion valve superheat g Check and adjust capacity control thermostat

23

OPERATING DATA CHILLER Voltage L-1 L-2 L-3 _ Pressure Gauge Readings 1 Suction psig 1 Discharge psig 2 Suction psig 2 Discharge _ psig 3 Suction psig 3 Discharge psig 4 Suction psig 4 Discharge _ psig High pressure switch setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-in) psig psig (Out) 4 (Cut-In) psig psig (Out) Checked Setting - Yes - No (each circuit) Low Pressure Switch Setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-In) psig psig (Out) 4 (Cut-in) psig psig (Out) Checked Setting -Yes -No (each circuit) 1 Oil Temperature Safety Switch Cut Out 2 Oil Temperature Safety Switch Cut Out 3 Oil Temperature Safety Switch Cut Out 4 Oil Temperature Safety Switch Cut Out If Star-Delta start time delay is seconds Temperature of air entering condenser F Temperature of air leaving condenser of Temperature of chilled water entering chiller OF Temperature of water (chilled) leaving chiller F Chilled water pressure entering chiller psig Chilled water pressure leaving chiller psig

MAINTENANCE Good maintenance practice will prolong the chiller life and will reduce the Ask of system breakdown and expensive service calls

A weekly check of the ACWC-SD unit requires only a few minutes and will prove beneficial in insuring long trouble free operation

WEEKLY CHECKS- with unit in operation for at least four hours 1) Check compressor oil level - At least above 12 of sight glass 2) Record suction and discharge pressures

Typical Condition R22 Ambient 95degF Return water 55degF Leaving water 45degF Suction 62 psig Discharge 270 psig

3) Record ambient temperature 4) Check liquid sight glass

Make sure liquid is clear - no bubbles 5) Check that all fans are running 6) Check entering face of condenser coil for cleanliness 7) Record voltage at unit

All of the above can be performed by building maintenance personnel If oil levels are low or any of the above checked items are questionable consult a qualified serviceman

At least once a year a qualified serviceman should check unit oil levels superheat and control operation

DUNHAM-BUSH USA

P l) bull 130 xUtUC t01 Bmgess RO~ Harrisonburg VA 22801 Phone (540) 434-0711 FAX (540) 434-~ 2118

wvvwdunham-bushcom Form No 6184

Page 9: ACWC-SD - · PDF fileACWC-SD • Screw . Type • • • Air-Cooled Packaged Chillers •• Installation, Operation, and •• • Maintenance Manual • • • •• DESCRIPTION

bullbull bullbull bullbull bullbull bullbull bullbull

r~T~-

ICt

MQ

Teuro

CO

MT

It01

I T

IM C

lot

ll

~---

Cl

ll

(O

41

(

flO

W

5Wlf

CH

~

I

Olt

CO

NT

AC

TO

C

OIL

S C

I-I

bull C

tS

AN

D S

t sn

N

OW

IIt

Dll

QU

0

1 C

OM

UC

TI

I

111

114

0

(

U

II

NO

f T

O I

(

C

uNO

IO

ON

UtI

se

CO

HO

UI

li

D(

1

A

ND

1

n

WP

(IU

ult

l S

(NIC

tf1

I

LO

CU

ID

1M bullbullU

O

UT

UT

r-

----

shybullbull

0

11

UO

V

HA

Il

LO

IS

raquoON

TO

S

TE

lurN

AU

bull

AN

D

0111

IIC

O(

I A

ND

A

U(

Cfl

YpoundL

Y

So

C

rt

TO

0

0 M

AN

UA

L a

ll H

TO

tNT

AN

D

~10l

IA

NO

M

TII

UC

TtO

NS

II

rCO

tNO

m

IMIT

AL

CO

H

laquo

0

U

TI

I It

4

Ishy

C

OW

III

ISO

R

MO

DU

LES

dC

NO

MmiddotA

U

VA

TC

I

D

U

1111

WIL

L A

LSO

LO

C_ O

UT

(

let

Umiddot

I C

AL

L

WH

IM

IAI

TY

flit

TH

[I(

CO

Nmiddot

I

OL

I CA

Jrf I

I II

EM

T

IT T

Uft

I1

tW

ITC

H bullbull

0

VO

NIN

IL

f PO

C

Obullbull

bull

I w

UII

II

I

C

IL

Llf

i I

ITA

f[1

II

ItV

N

IWIT

ti r

raquo7

~Slt~1

~~~~( 1~~~~tlDOO

CO

N

CT

O

WU

UH

O 0f

II C

OW

bullbullbullbull

~~1

II

bull

LL

TI

lIT

AT

0

N

O 1

0 O

CA

TID

1

1 I

I IIl

ETU

IIPt

W4T

P

LU

WHE

N u

TI

It N

OT

lU

u

rD

ttl

III I

ICO

Ma-

aU

0 11

nM

H

u

l

UN

I()1

II M

UST

HA

V(

SH

llL

DID

C

AU

I

LO

Me

T

II

no O

R

ItUM

WT

M

ItO

WI

L

IAH

to u

ri N

T I

T H

-

ITbullbull

O

N

ft

0

-

011

II~T

K

ITI

GU

ION

An

ON

S

o H

O-

ON

G C

OI

-W

it

11

N(

NO

6 N

c

CO

NU

ClI

W

If

lIN

( N

O

o N

0

CO

NT

AC

TS

WIt

K

liN

t N

O

6 N

OT

t I

TH

L

Nt

NO

Y S

UI

-I

IS

5_

1

~

~

no

~ I

I I_

VLOA

Or- I

I ~~

vumiddot

S1 so

CO

Hit

so

0

amp

g A

SI ~

I

1

7100-

I -I

I 01

10

OH

0

10

f T

AN

I V

I

] CM

NG

( av

rlt

10

0 O

K__

ST

AG

(

COD

lJ-

L7

00

~It

A

lIT

00]

VL

I fi

ll

14

1

10A

O

f

_ III

rC

OH

O

In o

y

00bull

00

10 ~

0

10

CO

Ol

C

bull

] 4

U

rr

COL~

bull Jo

un

J

W bull

C~P

OJ [

ou

-t

urO

NT

01

CO

l0

1

N

Omiddot

~ ]

(jCO~_

0

)

un

ll

n ~

T

I 11

I1

III _~

n

~

amp

7

10

II

01

u II 17

II

0

II

01

IS

-I

-lt

sE

o

0 c

raquo

CD

r iii

0

~O

U

lZ

+-1

~

tI

t

0

r QE

CIJ

-c

tl

Z

Ggt

lt0

bullbull bullbull

bullbull

bullbullbullbull

~

o

tUN

oa

lllO

_--

-

shyC

t-4

CII

C

cn

bull

tlN

I

CC

HImiddot

t

csnu

middota

--1

LA

T

loP

a

01

11

-1

111

111

IIImiddota

It

4

IOL

IS

IW

Imiddot

I

I T

I n flbull

bull

TO

middot I

st

U

LImiddot

a

Oft

lo

tL

LtG

EN

D

CO

NlA

CT

IM ~

CO

lllf

lllt

UtO

JII

CO

NT

AC

TO

CII

CU

fT

IIIC

AICC

III

CO

NTJ

IIOL

CIC

UIT

U

NImiddot

HU

TI

eNU

LlII

I

Il

I

AU

It

C

NlaquoC

AU

NC

An

C

O

UIO

10

LIO

T

AU

N

t U

SU

I C

O T

OO

L LO

W

eT

fM

llltM

OT

AT

L

OW

Hl

III

UII

I C

Oft

TJl

OL

OU

n

ru

ulltl

A

nT

T

HA

-

0bullbull M

OH

IfOIt

fl

lLA

Y I

AO

INI

MU

C

AN

cn

CO

fTltO

Ibull

ItIL

A

INT

ILO

CIC

OL

EN

OtD

Ll

OU

ID L

INt

Cc

ulT

MOO

ULIE

C

NIC

CA

SE

ItS

C

(

OM

II

IOII

(lI

IieLf

W

I eM

-

UIE

R

TH

III

OIT

6Tmiddot S

lOU

lC

U

MC

ot

LOW

TlM

e

U1

T

lER

bullbull

L l

OA

JIIO

middotCU

lTo

tJ

II W

UU

Nt

TI

M

AL

IO

D

oC

0It

1 U

IIN

t T

IMe

OC

LU

middotCA

II C

ONT

a

LOW

IU

t L

OCK

OUT

NPD

WIU

UN

LOA

Olil

t 1

0L

(NO

I0

C

O

III

OIl

lI

cn

CIJ

tCU

IT

UII

lEIt

ft

EC

poundIV

E H

IAI

C

Ol

(C

UIT

1I

IUIIl

I1II

CO

NY

(NIE

NC

E

OU

TU

T

CU

I C

ON

nlo

0

1

AN

$ M

ill1

1

HO

YIll

MU

II

lLT

I l

OA

O

LlI

lIIT

T

H(

O

ITA

T

OL

O

VC

LO

AO

MIA

nl

L1

lI1

~HAII

LO

IS

MO

NIT

O

L

Imiddot J

~fOT

L

IOH

TS

1

1

IC

IIV

E

HE

UE

ItM

lIC

tmiddotl

rC

IIV

E

MU

TlI

t l

tIIS

UIl

l(

CO

NT

ItO

LI

T

lmiddot1

C

CC

lvllt

N

EA

fllt

T

lW

OS

TA

lI

TO

Jmiddot 4

T

INe

H

LA

Y

LOW

In

vlt

l LO

C

OU

T

1O

t-1

ft

lll

D

UA

Tmiddot

TA

SIT

ION

C

ON

TAC

TO

Ill

$middot

1

CO

C

O

(

lIO

C

ON

TA

CT

O

T

A

Dn

u

CO

WC

tllltN

CI

ount

T

DE1AIL~

ST

AR

D

EL

TA

S

TA

RT

r

2

~f

10

t10

II

amp

II

11

II

)

1IllI

1IU

--shy

OW

E

IV

-

utv

lO

f

I I Ibull

A

UR

C

IlltC

UIT

C

IRC

UIT

ALA

NlC

UfT

C

lflC

UIT

I I

I

~li

IT

I

Ot

ON

AL

il------~---l

-

tL

J --

--

C

it

prIlgjf~

II

ell

I

I

IfB

I

t

---------~~-------

__

~

L_ -

7 -

-r--

et

r

I

II10

-I

CII

-lt

PL

1amp

I I

II b

I

L _

__

J

II 3

2I

oo

II

Qraquo

~

IS

lI

(

)r-

t-_

_ o

J_

_

O

TIO

L

I ~~

--~-

I

I CD

oL

__

__

__

__

__

CO

I- f

_

JI I

t degz

OI

OIl

lAL

r-

---

IS

r

-l

0

I

I

+10$

IL

KS

I T

e

0 Lr

I J

II

T

ITI

lOL

l 1

40

bull (C

IS)

TO

bullbull

lD

A-

~ -

r--

-~l

)~II

I

~G

__

_~L_J

0

O

HA

I

~ -

-Ill

-

---

-10-

--

~E

II

cn

-C~

II

Z

0

G)

Il

l~

r- I W

lllltO

WH

IN

JU

L1

l0

I I

I

OL

M

OL

MI

OL

I ~ro

o

jo

o

Jt

JI

L

OT

10N

AI

II

0

(01

0 CO

MPR

ESS

OR

C

IRC

UIT

~

27

III

gt

0

IIA

IO

amp1

)amp

1

1

II

~

I rA

I

TA~

D

ELTA

STA~T

CONP~E~)

CU

lT 2

~

f

bull ]

A

U

4 ]I

IUft

middotJI

Mon

tUPlOI

NT

lOA

Ot-

-O

I

01

0

]

(N

GI

011

1

00

CT

AN

)

40

00

HN

a

_N

I

J00

I -

It IC

y

TO

I

I I

I

~

oiiO

NA

t

I bull bull

wi

i

lOa

r~TT~-

I M

OT

I C

ON

sr

0

llItt

(

co

ce

OZ

UK

1

11

_JO

I I

)--11

--

- ---

-

IJI

LD

~

I

A

CK

lS

C

UK

I

IL

UO

A

TO

O

WH

IT

1

L

OW

SW

ITC

HJl

AL

D

00

IZ

I

f

1It-

-

rl__ u-

poundL

J f

aT

ION

AL

TI

WfI

OO

f

~

ff

I

Dill

C

ON

TAC

TOIlI

C

OtL

S (1

middot4

(IS

middot14

A

ND

II-

I

01

1In

N

O

Wl

0

51

11

~

CO

NT

AC

TS

I

fH

IO

Uti

IS

N

OT

TO

IE

al

llauN

DIO

O

N H

I Sr

CO

NO

AIl

lf

StO

l

f

I

TI

AN

D

TI

TI

U

I

IIN

OII

t

0middot

f1L

OC

AT

IO

IN n

lll

GU

lUT

r-

----

shy~

(I

G

lIt

no

v

HA

I

LO

SS M

ON

IO

nf

1Na

bull

AN

D

ON

rc

I(

CO

M(

f A

IrfD

I

lItU

rC

TIY

(U

00

-

5

E

[CO

OIO

lItc

rlll

TO

0

0

AN

UA

L

t

OIN

T A

Na

f

oo

IlU

COfrt

TO

I U

ND

IN

Stt

UC

TIO

trl

r

co

rNH

D

01 11

raquoIN

ITIA

L

CO

NT

lIIiO

L

fII

I0 I

UT

IS

a

jshy

orshy

10bull

CO

M1

II1t1

Ol

MO

GU

LI

I N(

tN-a

UT

OM

AT

lC

I 1I

lfla

n

flS

bullbull

11

A

LSO

ampO

eMmiddotO

UT

luer

llt

middot I

no

C

AL

Y

WH

IM A

N

IUIT

T T

IIII

P

T

MU

I C

ON

egoo

IT

flO

LI

CA

l

ItU

I1 I

T

TU

NIN

G W

ITC

M

0

~r=

0 I

lIO

Wlf

lIT

A

L

fOtt

CO

lI

tbullbull

w

ITC

H_

I

on

WO

Nlf

lIT

JII

IL

POllt

COW

bull

I In

degz

r+-i

~~

t

u ~o

1 ~rI~~

~~

~~TtIc~~I~D

1

SW

lTC

HI ~

C

OIfT

AC

TcU

t W

lItN

t C

OM

bullbull

H

To

lIL

b

l

0t~~1

0

1

CO

tfC

TO

H

I

lIt

C

ltbull

IIT

C

~r-

bull

WM

IH

-

2

N

OT

1V

l

rD

wllI

I[ to

IlIC

OM

n

I W

I

It

I

fjC

Ofl

P

tE

CJ)shy

t W

IN L

UI N

OT

SU

PL

ID

W

IIIIC

O

J

lleo

W

ti

l

LU

KT

IT

10- A

ND

10ft

II

v

C~

LO

CA

TU

I II

1t

11V

MI

_T

at

I

z10

I

T

lNH

A

TU

RC

S

lNS

OIt

MU

tT

ve

IL

OID

C

IL

C

()

11II

L

AT

I

AT

10

_

A

U

IIIT

I0middot

PCA

LOW M

I_ lO

TI

I bullbull

n

II

DES

IGN

ATI

ON

S

II

CO

NT

IlID

t I

NO

-o

MO

LD

INfl

C

OIL

It L

tNI

NO

0

Q

N

C

CO

NU

ClI

W

ITH

UN

I N

O

01]

0 co

O

f

11

~

I

ILK

n

e

s IA

UL

It

ibull

o O

CO

NTA

CTS

w

nw L

INI

NO

01

fA

0

~

fItO

TI

LI

I N

O

v

A

II

~ ~ bull i middots

~

~~ - ~

~

1- I J I J I I I I I I I I I I I I I I L __ J

I

a bull bull a bull bull

I I I

_J

r------~

=~I = ~ ~ bull ~ I I

~

as coe ruq SV~ siapow ~NI~IM lO~lN03lV3ldAl

i 4

_

a

~FirI1 u~III - I I

~ 1I

00000 -

I=II~I~~~~raquoIIIItIII~ampI~

as ooz nJ4l sv ~ siapow ~NI~IM lO~lNOgt TVgtldAl

bullbull bullbull

bullbull

~

jgt

lpoundIt

ND

II

co

----

----

----

----

----

----

----

----

-

r-~-middot--=-~~

~

bull a

~

at~04

5

---

~1I

A

~n

bullbullmiddot-shy

wo

_-

bull

lIt

C-

I C

Cf

aC

TO

Ic

ow

n

CC

eM

ca

~C

M

OD

IAI

CI

T-

CO

IITA

CT

oa

bullbull

CMCU

rT I

ItIM

IA

co-l

to

c-c

VIT

C

I

rr

c

AfE

bull r~----Ef1

POW

I

III

IQ

W

Q

tIL

UT

I1I

U__~

J

COt

I

LD

W M

lMtr

f nc

IIO

ff

0

N

LO

W

C

OIIT

INM

I I

CO

M

US

ON

C

NC

UIT

II

II

-~

_T

shy

C

O

NU

SO

II

CIN

CU

IT Z

II

D[TA~

-

ST

AN

D(~TA

IT

AII

T

0

u III

r

amp

II

-~

If

10

MA

MI

eN

talI

Tco_

~

STA

N D[~TA

ST

AII

T

~

CIS

-I

LA

~ 1-4

nmiddot

00

-

-II

1t1S

-1 aw

o fI

fl

U- I -~ Ci

Pi=

i

t

shy

~

iii

i

iii=

ii

-

-shyiii

ClL

n

TU

U

LOt

e

bull It

lLA

Yn

C

AM

Im

CIII

IID

L bull

CU

_C

Abull

fl

lUY

_f

tMO

ea

UY

middotIO

CI

lO

Ll

t

NIU

_L

N

CO

WU

UO

ItC

U

llT

l bullbull 0

1middot

lit

TMC

MI0

8TA

T tc

_lt

CIl

it

11

II

_

middotLO

W

TII

IfN

T

UIlI

C

nll

-

D-C

UlT

QIIU

tW

n-T

PII

IU

LIO

MI-

AC

TC

Ntf

Wi

MI

II

II

tY

middotCM

OO

C

LOW

HIe U

(O

Uf

lIl_

L

OA

M

1OtI

1tO

lD

CO

OA

CM

UtT

1M

C

lIY

Dl

NC

Afi

ll ea

-tU

lT 1

ItUbullbull

lI

oo

ww

lItt

lffc

e O

Un

n

cT

IlG

I

Ie-

~U

IIIC

CIV

P

1T

1lt

C

bullbull

Off

AT

tw

ebullbull

ampOW

IC

IUT

~-

4ti

iT

~

co

ww

O

UfU

T

DITA~

A

ITA

A

OEL

TA

IT

AJI

IT

co

rn~

e

I

1amp

ItmiddotI

~ bull

I I

I

I r

~

bull Iamp

II

I ~

I-

oJ

II I

IrIf

I I I I

s~

o

-I I

ltDc

() raquo

L 10

V

i

()

~O

to

U

lZr0

t2

llJ

IL

C6

J=

_J

~-1

f

II

c 0

II

N

ge

cno

c-

II

Z

Ggt

If IO

IC

IIY

II

IIR

III

IJt

T H

llII

A

Il C

Olaquof

U

TMIbull

~LDM

fI

lAR

PM

Iamp L

Oll

lTV

ii

iLii

Uii

ii

~

U3

I iL

iii=

i

Uii

u

i

O

(no)

T

bull II

1

IOA~

bullr

~ I

[gtO(]O

~ i I Ii i 2 ~ ~ ~ i a bull il 2 ~

iiibullbullbull

~ I ~ I I I ~~ =l ~ iI I ~ I I I It I 1111 amp ~~

as ooz nJ4l SP~ SlapoUII ~NI~IM 10U1NOl lVlldAl

-------

---

TYPICAL POWER WIRING Models 45 thru 70 SC

----

rYl31I01 I

-Ii --ti-

_ I ~_-

~ lniJ -

LIIbullbullbullbull PC _ amp-II _--- ~

TYPICAL POWER WIRING Models 90 thru 135 SC

- --- _ Tt

~rfh c~

tP ~

_III ~

I r-- ~- IIlJ

bull - MIl Mf __ bull Ie_~--~ _shy- shy16

---

----------

TYPICAL POWER WIRING Models 145 thru 200 SC

_ --1a1 IIUrI

middotrFti~v_ bull I

i~i ~~ TaII IIOMLI ~tN T 100 WTIOII 011 lilOOCL a

~ t1

tI bullbullbull

L

i I r-~

I r

~ ~ ~ III

2 ~ ~ ~l

- ~IlD I hJOHr eo teO acshyt CmiddotClM ~ CIKUr1 --

TYPICAL POWER WIRING Models 215 thru 265 SC

ItUU 1D Wll1U1I fIa -rMI

rt-h I -au 11 1_ i r~ rt-f

-i rn f1 ft fi i- llil bullbull c~ I bull c =

~~~ ~i~-~

~~m

~~~CI1 R~~ ~ ~~ ~llAi4I

luv~ bull ~uf LL~~-

~Mfl l~t IrMiA

a I III nII I bull it d

~-t--J I Lll-l~j ~nL4111 WlJj== lit-

I bullbullbull I

UGEND

~

~l OJ

- c~

~~~---

~)~middotI

I

L _~~~ L _I__~_J I ~ (11_1 ~ H~ CUlTMIt tffC_) Ll N

-r_ 0 1ItCIIIl0AI lllQUlllCo as -0- bull bullbull fI PC 110 lNJCllII a Olil1100pound1 II 111 el 1101 ItCOU_ 011 IIOOIL140

I 011 CI-( H[ (0110 (fMCun ubullbull --- l(lD IMbullbull Ntlf 110 e414-7

--CTOttbullbull

2

17

ELECTRICAL DATA Model Volts Type COMPRESSOR FAN MOTORS MIN CIRCUIT RECOMMENDED MAXIMUM ACWC 60 Hz of Qty RLA Starting FLA LRA AMPACITY WIRESIZE FUSESIZE

SC 3 Ph Start HP Ea Curro Ea Ea Ea Circ1 Circ2 Circ1 Circ2 Circ1 eire 2

208230 XL 1788 1040 (4) 70 (4) 380 252 - 250 - 400 -45 208230 YO (1) 50 1788 347 (4) 70 (4) 380 252 - 250 - 400 -

460 XL 737 422 (4) 35 (4) 190 106 - 2 - 175 -460 YO 737 141 (4) 35 (4) 190 106 - 2 - 175 -

208230 XL 2051 1228 (4) 70 (4) 380 284 - 300 - 450 -55 208230 YO (1) 60 2051 409 (4) 70 (4) 380 284 - 300 - 450 -

460 XL 904 485 (4) 35 (4) 190 127 - 1 - 200 -460 YO 904 162 (4) 35 (4) 190 127 - 1 - 200 -

208230 XL 2083 1415 (6) 70 (6) 380 302 350 500 -70 208230 YO (1) 75 2083 472 (6) 70 (6) 380 302 350 500 -

460 XL 974 539 (6) 35 (6) 190 143 0 225 -460 YO 974 180 (6) 35 (6 190 143 0 225 -208 XL 1788 1040 (6) 70 (6) 380 266 224 300 0000 400 400 208 YO 1788 347 (6) 70 (6) 380 266 224 300 0000 400

90 230 XL (2) 50 1788 1040 (6) 70 (6) 380 266 224 400 I300 0000 400 400 230 YO 1788 347 (6) 70 (6) 380 266 224 300 0000 400 400 460 XL 737 422 (6) 35 (6) 190 187 - 000 - 250 460 YO 737 141 (6) 35 (6) 190 187 - =1000 - 250 208 XL 2051 1228 (8) 70 (8) 380 312 256 400 300 250 208 YO 2051 409 (8) 70 (8) 380 312 256 400 300 500

110 230 XL (2) 60 2051 1228 (8) 70 (8) 380 312 256 g I350 300 SOO 450 230 YO 2051 409 (8) 70 (8) 380 312 256 350 300 500 450 460 XL 914 485 (8) 35 (8) 190 231 - 0000 - 300 460 YO 904 162 (8) 35 (8) 190 231 - 0000 - 300 -

208 XL (1) 60 2051 1228 (8) 70 (8) 380 312 260 400 300 500 450(1) 75 2083 1415

208 YO (1) 60 2051 409 (8) 70 (8) 380 312 260 400 300 500 450(1) 75 2083 472

230 XL (1) 60 2051 1228 (8) 70 (8) 380 312 260 350 300 500 450(1) 75 2083 165125

230 YO (1) 60 2051 409 (8) 70 (8) 380 02 260 350 300 500 450 (1) 75 2083 472

460 XL (1) 60 904 485 (8) 35 (8) 190 240 - 250 - 300 -(1 75 974 539

460 YO (1) 60 904 162 (8) 35 (8) 190 240 - 250 - 300 -(1) 75 974 180

208 XL 2083 1415 (8) 70 (8) 380 316 260 400 300 500 450 208 YO 2083 472 (8) 70 (8) 380 316 260 400 300 500 450

135 230 XL (2) 75 2083 1415 (8) 70 (8) 380 316 260 400 300 500 450 I 230 YO 2083 472 (8) 70 (8) 380 316 260 400 300 500 450

460 XL 974 539 (8) 35 (8) 190 247 - 250 - 300 -460 YO 974 180 (8i 35 (8) 190 247 - 250 - 300 -

208 XL (2) SO 1788 1040 (10) 70 (10) 380 326 402 400 0000 500 500(1) 60 2051 1228

208 YO (2) 50 1788 347 (10) 70 (10) 380 326 402 400 0000 500 500(1 60 2051 409

230 XL (2) 50 1788 1040 (10) 70 (10) 380 326 402 400 0000 500 500 145 (1) 60 2011 1228

230 YO (2) 50 1788 347 (10) 70 (10) 380 326 402 400 0000 500 500(1) 60 2051 409

460 XL (2) 50 737 422 (10) 35 (10) 190 295 - 350 350 --(1) 60 904 485

460 YO (2) SO 731 141 10 (35) (10)190 295 - 350 350- -(1)60 904 162

208 XL 2051 1228 (10) 70 (10) 380 326 462 400 (2)250 500 600 208 YO 2051 409 (10) 70 (10) 380 326 462 400 (2)250 500 600

160 230 XL (3) 60 2051 1228 (10) 70 (10) 380 326 462 400 (2)250 500 230 YO 2051 409 (10) 70 (10) 380 326 462 600400 (2)250 500 600 460 XL 904 485 (10) 35 (10) 190 329 - 400 - 400 460 YO 904 167 (10) 35 (10) 190 329 - 400 - 400 - I

NOTES 1 XL Across the LineYOStarDelta 2 RLA Rated LoadAmps(ratedin accordance withARI Standard 590) LRA LockedRotorAmps 3 Wire Size Amps equal125of the ratedloadampsfor the largestmotorin thecircuitplus100of the ratedloadampsfor all othermotorsin the circuit per

NEC 4 Wire size based on copperconductorswith75C insulation perNECTable310-16 Terminal block lugs are sizedaccordingly Use of oversize wiringmay

not lit in terminal blocks 5 Maximumfuse size is basedon 175to 225of the ratedloadampsfor the largestmotorin the circuitplus 100of the rated loadampsfora othermotors

in the circuit per NEC VOLTAGE TOLERANCES 208V-230V min 187VMax 253V

480V Min414V Max506V

I

18

ELECTRICAL DATA Volts Type COMPRESSORModel FAN MOTORS MINCIRCUIT RECOMMENDED MAXIMUM 60 Hz of Oty RLA Starting FLAACWC LRA AMPACITY WIRESIZE FUSE SIZE 3 Ph Start Curro EaSC HP Ea Ea Ea Cire1 Cire2 Cire1 Cire2 Cire1 Cire2 208 XL 2051(1) 60 1228 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 1415 208 YO (1) 60 2051 409 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 472 230 XL (1) 60 2051 1228 (12)70 (12) 380 341 469 500 (2) 250 500 600

12 75 2083 1415185 230 YO (1) 60 2051 409 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 472 460 XL 485 (12) 35 (1) 60 904 (12) 190 352 500 400- - -

(2) 75 974 539 460 YO (1) 60 904 162 (12) 5(12)19 352 500 400- - -

(2) 75 974 180 208 XL 2083 1415 (12) 70 (12) 380 345 469 500 500(2) 250 600

472208 YO 2083 (12) 70 345(12) 380 469 500 (2) 250 500 600 230 XL (3) 75 2083 1415 (12) 70 345(12) 380 469 500 (2) 250 500 600200 230 YO 2083 472 (12) 70 (12) 190 345 469 500 500(2) 250 600 460 XL 539974 (12) 35 (12) 190 359 - 450500 - -

180 1(12) 35 460 YO 974 (12) 190 359 450 -500- -2051 1228208 XL (12) 70 504(12) 380 504 (2) 250 (2) 250 700 700

208 YO 2051 409 (12) 70 (12) 380 504 504 (2) 250 700(2) 250 700 (4) 60 2051 1228 (12) 70 230 XL (12) 380 504 504 (2) 250 (2) 250 700 700215

YO 2051 409230 (12) 70 (12) 380 504 504 (2) 250 (2) 250 700 700 460 904 485 (12) 35 XL (12) 190 225 225 0000 0000 300 300

(12) 35 460 YO 904 162 (12) 190 300225 225 0000 0000 300 2051 1228208 XL (2) 60 (14) 70 (14) 380 504 525 (2250 700 700(2)300

(2) 75 2083 1415 2051 409 (14) 70 700 700208 YO (2) 60 (14) 380 504 525 (2) 250 (2)300

(2) 75 2083 472240 700XL (2) 60 2051 1228 (14) 70 (14) 380 504 525 (2)250 (2)300 700230

(2) 75 2083 1415 2011230 YO (2) 60 409 (14) 70 (14) 380 504 525 (2) 250 (2)300 700 700

(2) 75 2083 472 300460 XL (2) 60 904 485 (14) 35 (14) 190 225 248 0000 250 300

12 75 974 539 904 162 250 300 300460 YO (2) 60 (14) 35 (14) 190 225 248 410

(2) 75 974 180 2083 1415 (2)300 700 700XL (16) 70 (16) 380 525 525 (2)300208 2083 1415 (2)300 700 700208 YO (16) 70 525 525 (2)300(16) 380

700 7002083 1415 (16) 70 (2300230 XL (16) 380 525 525 (2300 700 700(2300(4) 75 2083 472 (16) 70 (16) 380 525 525 (2300230 XL265

300250 300974 539 (16) 35 248 248 250XL (16) 380 460 (16) 35 300 300974 (16 380 248 250 250YO 539 248460

NOTES 1 XL Across the Line YO Star Delta 2 RLA Rated Load Amps (rated in accordance with ARI Standard 590) LRA Locked Rotor Amps 3 Wire Size Amps equal 125 of the rated load amps for the largest motor in the circuit plus 100 of the rated load amps for all other motors in the circuit per

NEC 4 Wire size based on copper conductors with 75degG insulation per NEG Table 310-16 Terminal block lugs are sized accordingly Use of oversize wiring may

not fit in terminal blocks 5 Maximum fuse size is based on 175 to 225 of the rated load amps for the largest motor in the circuit plus 100 of the rated load amps for a other motors

in the circuit per NEG VOLTAGE TOLERANCES 208V-230V min 187V Max 253V

480V Min414V Max506V

19

0

(Wd~) 3lV~ M011 ~31VM

006 009 00 OOt OOl OS L 00 L os 0 Ot

V D m (I) (I)

c D m c D o V

- m m -t o

~

~ m D-

aoao 3~nSS3~d ~3100~

APPLICATION DATA

POINT LOADING

ArMi I 1 5 1

ACWC 45 THRU 10 SC

COMPRESSOR CONDENSER SECTION SECTION

_ 2 4 bull 1

bull CA

J

Model Dimensions Size A B C D 45 91 - - -55 91 - - -70 145 - - -90 145 - - -110 60 40 160 -125 60 40 160 -135 60 40 160 -145 138 74 107 -160 13830 74 107 -185 138 129 107 -200 138 129 107 -215 106 82 106 80 240 106 82 134 107 265 133 110 134 107

1310

1310

~

1

1310

2

ACwe 110 THRU 200 Ie

COMPREIlOfl CONDENSER SECTION IECnoN

4 -

5Imiddot

ACWC 2t5 THRU 215 SC

Model Loadlnu (LBS) Size 1amp2 3amp4 5amp6 7amp8 9 amp10 45 585 765 550 - -55 705 810 635 - -70 660 890 700 - -90 1025 1500 1175 - -110 1195 635 1525 995 -125 1255 690 1835 1115 -135 1255 665 1880 1105 -145 1330 2380 2160 1450 -160 1330 2440 2280 1515 -185 1235 2575 2980 1360 -200 1275 2635 3020 1380 -215 1010 2270 2590 2240 840 240 1115 2550 2870 2715 1125 265 1380 2980 3515 2750 1175

11

II i middot 2 4 lIf 11 to L

21

TROUBLESHOOTING GUIDE

CHILLER UNIT WILL NOT START POSSIBLE CAUSE REMEDY 1 Power off 1 Check main disconnect switch

2 Main line open 2 Check main fuses

3 Incorrect wiring 3 Check the wiring diagram

4 Loose terminals 4 Tiqhten all terminals

5 Control circuit open 5 Check phase loss monitor flow switch circuit breakers temperature control low ambient thermostat low temperature thermostat remote switch etc

6 Time delay 6 Wait

COMPRESSOR HUMS BUT DOES NOT START

POSSIBLE CAUSE REMEDY

1 Low voltage 1a Check at service and unit for loss

b Consult power company

COMPRESSOR CUTS OUT ON LOW PRESSURE SAFETY CONTROL POSSIBLE CAUSE REMEDY 1 Refrigerant shortage 1 Check for leaks -- add refrigerant 2 Restriction in liquid line 2a Plugged strainer - dean or replace

b Liquid line valve partially closed - open valves fully c Expansion valve clogged or inoperative - clean or replace as

required d Solenoid valve partially open - clean or replace as required

3 Low water flow thru cooler 3 Check water flow thru cooler and correct as required

COMPRESSOR CYCLES ON HIGH PRESSURE CONTROL POSSIBLE CAUSE REMEDY 1 Compressor discharge valve partially closed 1 Open valve fully 2 Non-condensible gases in system 2 Operate condenser fans with compressors off If condenser

pressure exceeds saturated pressure corresponding to condenser entering air temperature then purge air from discharge line

3 Overcharge of R-22 3 Purge system while in operation until head pressure reaches a normal level

4 Dirty condenser 4 Clean the condenser 5 Compressor discharge check valve not operating properly 5 Replace if necessary 6 Fans not running 6 Check pressure control setting

CAUSES AND PREVENTION OF FREEZE-UP CAUSES PREVENTION 1 Improper charging 1 Charge per manufacturers recommendation

2 Improperly set safety time delay 2 Check the safety time delay low pressure control for proper setting at the beginning of each season

3 Improper chilled water circulation 3 Use an ample sized cleanable strainer in the chilled water circuit Make certain the strainer is clean to insure full flow and velocity of

chilled water It may sometimes be necessary to treat the water to prevent formation of deposits

4 Not draining for winter shutdown 4 When the system is shut down for the winter remove the drain

plugs and drain the cooler Blowout any remaining water with air

5 Improper pump shutdown 5 Make sure chiller barrel heater is working and flow switch is installed per wiring diagrams

6 Low ambient during air conditioning season 6 Make sure chiller barrel heater is working

NOTE If the ambient temperature is below 32degF freezing can be completely prevented by one of two methods

1 Drain all water from the equipment 2 Add antifreeze to the water

22

START-UP CHECK LIST

Unit Model No

Setting unit

Wiring

Piping

Alignment

Before Start-Up

After Start-Up

Yes No a Vibration isolator used

b Spring isolator adjusted for equal height c If rubber-in-shear isolators are used is unit leveled by shimming

a Power wiring complete

b Control wiring complete c Electric service adequate for load

d Power source voltage correct for motor(s) used

e Motor circuit has proper size fusetrons f System wired per diagram

g All lead connections tight h Wiring complies with local codes i Flow switch operation

a Piping complies with applicable codes b External piping independently supported c Chilled water lines insulated

a All belts adjusted and checked for tension b All pulleys checked and adjusted for proper pitch tightness and

alignment

a Open compressor discharge service valve b Open liquid valve(s) c Open suction and discharge valves to pressure gauges (if supplied) d Check rotation of all fan motors e Start auxiliary equipment (pumps fans etc) f Is crankcase heater operating Operate 24 hours prior to unit startup g Check the compressor oil level through the crankcase sight glass The oil

level should be to the top of the glass If the level is low add oil in accordance with the directions in the maintenance instruction

h Check all control settings as specified in Table 1 I Air purged from chilled water system

a Check high pressure control b Check oil temperature safety switch c Check and adjust low pressure or temperature freeze control d Check and adjust operating thermostat e Check and adjust low pressure operating control f Check and adjust expansion valve superheat g Check and adjust capacity control thermostat

23

OPERATING DATA CHILLER Voltage L-1 L-2 L-3 _ Pressure Gauge Readings 1 Suction psig 1 Discharge psig 2 Suction psig 2 Discharge _ psig 3 Suction psig 3 Discharge psig 4 Suction psig 4 Discharge _ psig High pressure switch setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-in) psig psig (Out) 4 (Cut-In) psig psig (Out) Checked Setting - Yes - No (each circuit) Low Pressure Switch Setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-In) psig psig (Out) 4 (Cut-in) psig psig (Out) Checked Setting -Yes -No (each circuit) 1 Oil Temperature Safety Switch Cut Out 2 Oil Temperature Safety Switch Cut Out 3 Oil Temperature Safety Switch Cut Out 4 Oil Temperature Safety Switch Cut Out If Star-Delta start time delay is seconds Temperature of air entering condenser F Temperature of air leaving condenser of Temperature of chilled water entering chiller OF Temperature of water (chilled) leaving chiller F Chilled water pressure entering chiller psig Chilled water pressure leaving chiller psig

MAINTENANCE Good maintenance practice will prolong the chiller life and will reduce the Ask of system breakdown and expensive service calls

A weekly check of the ACWC-SD unit requires only a few minutes and will prove beneficial in insuring long trouble free operation

WEEKLY CHECKS- with unit in operation for at least four hours 1) Check compressor oil level - At least above 12 of sight glass 2) Record suction and discharge pressures

Typical Condition R22 Ambient 95degF Return water 55degF Leaving water 45degF Suction 62 psig Discharge 270 psig

3) Record ambient temperature 4) Check liquid sight glass

Make sure liquid is clear - no bubbles 5) Check that all fans are running 6) Check entering face of condenser coil for cleanliness 7) Record voltage at unit

All of the above can be performed by building maintenance personnel If oil levels are low or any of the above checked items are questionable consult a qualified serviceman

At least once a year a qualified serviceman should check unit oil levels superheat and control operation

DUNHAM-BUSH USA

P l) bull 130 xUtUC t01 Bmgess RO~ Harrisonburg VA 22801 Phone (540) 434-0711 FAX (540) 434-~ 2118

wvvwdunham-bushcom Form No 6184

Page 10: ACWC-SD - · PDF fileACWC-SD • Screw . Type • • • Air-Cooled Packaged Chillers •• Installation, Operation, and •• • Maintenance Manual • • • •• DESCRIPTION

bullbull bullbull

bullbull

bullbullbullbull

~

o

tUN

oa

lllO

_--

-

shyC

t-4

CII

C

cn

bull

tlN

I

CC

HImiddot

t

csnu

middota

--1

LA

T

loP

a

01

11

-1

111

111

IIImiddota

It

4

IOL

IS

IW

Imiddot

I

I T

I n flbull

bull

TO

middot I

st

U

LImiddot

a

Oft

lo

tL

LtG

EN

D

CO

NlA

CT

IM ~

CO

lllf

lllt

UtO

JII

CO

NT

AC

TO

CII

CU

fT

IIIC

AICC

III

CO

NTJ

IIOL

CIC

UIT

U

NImiddot

HU

TI

eNU

LlII

I

Il

I

AU

It

C

NlaquoC

AU

NC

An

C

O

UIO

10

LIO

T

AU

N

t U

SU

I C

O T

OO

L LO

W

eT

fM

llltM

OT

AT

L

OW

Hl

III

UII

I C

Oft

TJl

OL

OU

n

ru

ulltl

A

nT

T

HA

-

0bullbull M

OH

IfOIt

fl

lLA

Y I

AO

INI

MU

C

AN

cn

CO

fTltO

Ibull

ItIL

A

INT

ILO

CIC

OL

EN

OtD

Ll

OU

ID L

INt

Cc

ulT

MOO

ULIE

C

NIC

CA

SE

ItS

C

(

OM

II

IOII

(lI

IieLf

W

I eM

-

UIE

R

TH

III

OIT

6Tmiddot S

lOU

lC

U

MC

ot

LOW

TlM

e

U1

T

lER

bullbull

L l

OA

JIIO

middotCU

lTo

tJ

II W

UU

Nt

TI

M

AL

IO

D

oC

0It

1 U

IIN

t T

IMe

OC

LU

middotCA

II C

ONT

a

LOW

IU

t L

OCK

OUT

NPD

WIU

UN

LOA

Olil

t 1

0L

(NO

I0

C

O

III

OIl

lI

cn

CIJ

tCU

IT

UII

lEIt

ft

EC

poundIV

E H

IAI

C

Ol

(C

UIT

1I

IUIIl

I1II

CO

NY

(NIE

NC

E

OU

TU

T

CU

I C

ON

nlo

0

1

AN

$ M

ill1

1

HO

YIll

MU

II

lLT

I l

OA

O

LlI

lIIT

T

H(

O

ITA

T

OL

O

VC

LO

AO

MIA

nl

L1

lI1

~HAII

LO

IS

MO

NIT

O

L

Imiddot J

~fOT

L

IOH

TS

1

1

IC

IIV

E

HE

UE

ItM

lIC

tmiddotl

rC

IIV

E

MU

TlI

t l

tIIS

UIl

l(

CO

NT

ItO

LI

T

lmiddot1

C

CC

lvllt

N

EA

fllt

T

lW

OS

TA

lI

TO

Jmiddot 4

T

INe

H

LA

Y

LOW

In

vlt

l LO

C

OU

T

1O

t-1

ft

lll

D

UA

Tmiddot

TA

SIT

ION

C

ON

TAC

TO

Ill

$middot

1

CO

C

O

(

lIO

C

ON

TA

CT

O

T

A

Dn

u

CO

WC

tllltN

CI

ount

T

DE1AIL~

ST

AR

D

EL

TA

S

TA

RT

r

2

~f

10

t10

II

amp

II

11

II

)

1IllI

1IU

--shy

OW

E

IV

-

utv

lO

f

I I Ibull

A

UR

C

IlltC

UIT

C

IRC

UIT

ALA

NlC

UfT

C

lflC

UIT

I I

I

~li

IT

I

Ot

ON

AL

il------~---l

-

tL

J --

--

C

it

prIlgjf~

II

ell

I

I

IfB

I

t

---------~~-------

__

~

L_ -

7 -

-r--

et

r

I

II10

-I

CII

-lt

PL

1amp

I I

II b

I

L _

__

J

II 3

2I

oo

II

Qraquo

~

IS

lI

(

)r-

t-_

_ o

J_

_

O

TIO

L

I ~~

--~-

I

I CD

oL

__

__

__

__

__

CO

I- f

_

JI I

t degz

OI

OIl

lAL

r-

---

IS

r

-l

0

I

I

+10$

IL

KS

I T

e

0 Lr

I J

II

T

ITI

lOL

l 1

40

bull (C

IS)

TO

bullbull

lD

A-

~ -

r--

-~l

)~II

I

~G

__

_~L_J

0

O

HA

I

~ -

-Ill

-

---

-10-

--

~E

II

cn

-C~

II

Z

0

G)

Il

l~

r- I W

lllltO

WH

IN

JU

L1

l0

I I

I

OL

M

OL

MI

OL

I ~ro

o

jo

o

Jt

JI

L

OT

10N

AI

II

0

(01

0 CO

MPR

ESS

OR

C

IRC

UIT

~

27

III

gt

0

IIA

IO

amp1

)amp

1

1

II

~

I rA

I

TA~

D

ELTA

STA~T

CONP~E~)

CU

lT 2

~

f

bull ]

A

U

4 ]I

IUft

middotJI

Mon

tUPlOI

NT

lOA

Ot-

-O

I

01

0

]

(N

GI

011

1

00

CT

AN

)

40

00

HN

a

_N

I

J00

I -

It IC

y

TO

I

I I

I

~

oiiO

NA

t

I bull bull

wi

i

lOa

r~TT~-

I M

OT

I C

ON

sr

0

llItt

(

co

ce

OZ

UK

1

11

_JO

I I

)--11

--

- ---

-

IJI

LD

~

I

A

CK

lS

C

UK

I

IL

UO

A

TO

O

WH

IT

1

L

OW

SW

ITC

HJl

AL

D

00

IZ

I

f

1It-

-

rl__ u-

poundL

J f

aT

ION

AL

TI

WfI

OO

f

~

ff

I

Dill

C

ON

TAC

TOIlI

C

OtL

S (1

middot4

(IS

middot14

A

ND

II-

I

01

1In

N

O

Wl

0

51

11

~

CO

NT

AC

TS

I

fH

IO

Uti

IS

N

OT

TO

IE

al

llauN

DIO

O

N H

I Sr

CO

NO

AIl

lf

StO

l

f

I

TI

AN

D

TI

TI

U

I

IIN

OII

t

0middot

f1L

OC

AT

IO

IN n

lll

GU

lUT

r-

----

shy~

(I

G

lIt

no

v

HA

I

LO

SS M

ON

IO

nf

1Na

bull

AN

D

ON

rc

I(

CO

M(

f A

IrfD

I

lItU

rC

TIY

(U

00

-

5

E

[CO

OIO

lItc

rlll

TO

0

0

AN

UA

L

t

OIN

T A

Na

f

oo

IlU

COfrt

TO

I U

ND

IN

Stt

UC

TIO

trl

r

co

rNH

D

01 11

raquoIN

ITIA

L

CO

NT

lIIiO

L

fII

I0 I

UT

IS

a

jshy

orshy

10bull

CO

M1

II1t1

Ol

MO

GU

LI

I N(

tN-a

UT

OM

AT

lC

I 1I

lfla

n

flS

bullbull

11

A

LSO

ampO

eMmiddotO

UT

luer

llt

middot I

no

C

AL

Y

WH

IM A

N

IUIT

T T

IIII

P

T

MU

I C

ON

egoo

IT

flO

LI

CA

l

ItU

I1 I

T

TU

NIN

G W

ITC

M

0

~r=

0 I

lIO

Wlf

lIT

A

L

fOtt

CO

lI

tbullbull

w

ITC

H_

I

on

WO

Nlf

lIT

JII

IL

POllt

COW

bull

I In

degz

r+-i

~~

t

u ~o

1 ~rI~~

~~

~~TtIc~~I~D

1

SW

lTC

HI ~

C

OIfT

AC

TcU

t W

lItN

t C

OM

bullbull

H

To

lIL

b

l

0t~~1

0

1

CO

tfC

TO

H

I

lIt

C

ltbull

IIT

C

~r-

bull

WM

IH

-

2

N

OT

1V

l

rD

wllI

I[ to

IlIC

OM

n

I W

I

It

I

fjC

Ofl

P

tE

CJ)shy

t W

IN L

UI N

OT

SU

PL

ID

W

IIIIC

O

J

lleo

W

ti

l

LU

KT

IT

10- A

ND

10ft

II

v

C~

LO

CA

TU

I II

1t

11V

MI

_T

at

I

z10

I

T

lNH

A

TU

RC

S

lNS

OIt

MU

tT

ve

IL

OID

C

IL

C

()

11II

L

AT

I

AT

10

_

A

U

IIIT

I0middot

PCA

LOW M

I_ lO

TI

I bullbull

n

II

DES

IGN

ATI

ON

S

II

CO

NT

IlID

t I

NO

-o

MO

LD

INfl

C

OIL

It L

tNI

NO

0

Q

N

C

CO

NU

ClI

W

ITH

UN

I N

O

01]

0 co

O

f

11

~

I

ILK

n

e

s IA

UL

It

ibull

o O

CO

NTA

CTS

w

nw L

INI

NO

01

fA

0

~

fItO

TI

LI

I N

O

v

A

II

~ ~ bull i middots

~

~~ - ~

~

1- I J I J I I I I I I I I I I I I I I L __ J

I

a bull bull a bull bull

I I I

_J

r------~

=~I = ~ ~ bull ~ I I

~

as coe ruq SV~ siapow ~NI~IM lO~lN03lV3ldAl

i 4

_

a

~FirI1 u~III - I I

~ 1I

00000 -

I=II~I~~~~raquoIIIItIII~ampI~

as ooz nJ4l sv ~ siapow ~NI~IM lO~lNOgt TVgtldAl

bullbull bullbull

bullbull

~

jgt

lpoundIt

ND

II

co

----

----

----

----

----

----

----

----

-

r-~-middot--=-~~

~

bull a

~

at~04

5

---

~1I

A

~n

bullbullmiddot-shy

wo

_-

bull

lIt

C-

I C

Cf

aC

TO

Ic

ow

n

CC

eM

ca

~C

M

OD

IAI

CI

T-

CO

IITA

CT

oa

bullbull

CMCU

rT I

ItIM

IA

co-l

to

c-c

VIT

C

I

rr

c

AfE

bull r~----Ef1

POW

I

III

IQ

W

Q

tIL

UT

I1I

U__~

J

COt

I

LD

W M

lMtr

f nc

IIO

ff

0

N

LO

W

C

OIIT

INM

I I

CO

M

US

ON

C

NC

UIT

II

II

-~

_T

shy

C

O

NU

SO

II

CIN

CU

IT Z

II

D[TA~

-

ST

AN

D(~TA

IT

AII

T

0

u III

r

amp

II

-~

If

10

MA

MI

eN

talI

Tco_

~

STA

N D[~TA

ST

AII

T

~

CIS

-I

LA

~ 1-4

nmiddot

00

-

-II

1t1S

-1 aw

o fI

fl

U- I -~ Ci

Pi=

i

t

shy

~

iii

i

iii=

ii

-

-shyiii

ClL

n

TU

U

LOt

e

bull It

lLA

Yn

C

AM

Im

CIII

IID

L bull

CU

_C

Abull

fl

lUY

_f

tMO

ea

UY

middotIO

CI

lO

Ll

t

NIU

_L

N

CO

WU

UO

ItC

U

llT

l bullbull 0

1middot

lit

TMC

MI0

8TA

T tc

_lt

CIl

it

11

II

_

middotLO

W

TII

IfN

T

UIlI

C

nll

-

D-C

UlT

QIIU

tW

n-T

PII

IU

LIO

MI-

AC

TC

Ntf

Wi

MI

II

II

tY

middotCM

OO

C

LOW

HIe U

(O

Uf

lIl_

L

OA

M

1OtI

1tO

lD

CO

OA

CM

UtT

1M

C

lIY

Dl

NC

Afi

ll ea

-tU

lT 1

ItUbullbull

lI

oo

ww

lItt

lffc

e O

Un

n

cT

IlG

I

Ie-

~U

IIIC

CIV

P

1T

1lt

C

bullbull

Off

AT

tw

ebullbull

ampOW

IC

IUT

~-

4ti

iT

~

co

ww

O

UfU

T

DITA~

A

ITA

A

OEL

TA

IT

AJI

IT

co

rn~

e

I

1amp

ItmiddotI

~ bull

I I

I

I r

~

bull Iamp

II

I ~

I-

oJ

II I

IrIf

I I I I

s~

o

-I I

ltDc

() raquo

L 10

V

i

()

~O

to

U

lZr0

t2

llJ

IL

C6

J=

_J

~-1

f

II

c 0

II

N

ge

cno

c-

II

Z

Ggt

If IO

IC

IIY

II

IIR

III

IJt

T H

llII

A

Il C

Olaquof

U

TMIbull

~LDM

fI

lAR

PM

Iamp L

Oll

lTV

ii

iLii

Uii

ii

~

U3

I iL

iii=

i

Uii

u

i

O

(no)

T

bull II

1

IOA~

bullr

~ I

[gtO(]O

~ i I Ii i 2 ~ ~ ~ i a bull il 2 ~

iiibullbullbull

~ I ~ I I I ~~ =l ~ iI I ~ I I I It I 1111 amp ~~

as ooz nJ4l SP~ SlapoUII ~NI~IM 10U1NOl lVlldAl

-------

---

TYPICAL POWER WIRING Models 45 thru 70 SC

----

rYl31I01 I

-Ii --ti-

_ I ~_-

~ lniJ -

LIIbullbullbullbull PC _ amp-II _--- ~

TYPICAL POWER WIRING Models 90 thru 135 SC

- --- _ Tt

~rfh c~

tP ~

_III ~

I r-- ~- IIlJ

bull - MIl Mf __ bull Ie_~--~ _shy- shy16

---

----------

TYPICAL POWER WIRING Models 145 thru 200 SC

_ --1a1 IIUrI

middotrFti~v_ bull I

i~i ~~ TaII IIOMLI ~tN T 100 WTIOII 011 lilOOCL a

~ t1

tI bullbullbull

L

i I r-~

I r

~ ~ ~ III

2 ~ ~ ~l

- ~IlD I hJOHr eo teO acshyt CmiddotClM ~ CIKUr1 --

TYPICAL POWER WIRING Models 215 thru 265 SC

ItUU 1D Wll1U1I fIa -rMI

rt-h I -au 11 1_ i r~ rt-f

-i rn f1 ft fi i- llil bullbull c~ I bull c =

~~~ ~i~-~

~~m

~~~CI1 R~~ ~ ~~ ~llAi4I

luv~ bull ~uf LL~~-

~Mfl l~t IrMiA

a I III nII I bull it d

~-t--J I Lll-l~j ~nL4111 WlJj== lit-

I bullbullbull I

UGEND

~

~l OJ

- c~

~~~---

~)~middotI

I

L _~~~ L _I__~_J I ~ (11_1 ~ H~ CUlTMIt tffC_) Ll N

-r_ 0 1ItCIIIl0AI lllQUlllCo as -0- bull bullbull fI PC 110 lNJCllII a Olil1100pound1 II 111 el 1101 ItCOU_ 011 IIOOIL140

I 011 CI-( H[ (0110 (fMCun ubullbull --- l(lD IMbullbull Ntlf 110 e414-7

--CTOttbullbull

2

17

ELECTRICAL DATA Model Volts Type COMPRESSOR FAN MOTORS MIN CIRCUIT RECOMMENDED MAXIMUM ACWC 60 Hz of Qty RLA Starting FLA LRA AMPACITY WIRESIZE FUSESIZE

SC 3 Ph Start HP Ea Curro Ea Ea Ea Circ1 Circ2 Circ1 Circ2 Circ1 eire 2

208230 XL 1788 1040 (4) 70 (4) 380 252 - 250 - 400 -45 208230 YO (1) 50 1788 347 (4) 70 (4) 380 252 - 250 - 400 -

460 XL 737 422 (4) 35 (4) 190 106 - 2 - 175 -460 YO 737 141 (4) 35 (4) 190 106 - 2 - 175 -

208230 XL 2051 1228 (4) 70 (4) 380 284 - 300 - 450 -55 208230 YO (1) 60 2051 409 (4) 70 (4) 380 284 - 300 - 450 -

460 XL 904 485 (4) 35 (4) 190 127 - 1 - 200 -460 YO 904 162 (4) 35 (4) 190 127 - 1 - 200 -

208230 XL 2083 1415 (6) 70 (6) 380 302 350 500 -70 208230 YO (1) 75 2083 472 (6) 70 (6) 380 302 350 500 -

460 XL 974 539 (6) 35 (6) 190 143 0 225 -460 YO 974 180 (6) 35 (6 190 143 0 225 -208 XL 1788 1040 (6) 70 (6) 380 266 224 300 0000 400 400 208 YO 1788 347 (6) 70 (6) 380 266 224 300 0000 400

90 230 XL (2) 50 1788 1040 (6) 70 (6) 380 266 224 400 I300 0000 400 400 230 YO 1788 347 (6) 70 (6) 380 266 224 300 0000 400 400 460 XL 737 422 (6) 35 (6) 190 187 - 000 - 250 460 YO 737 141 (6) 35 (6) 190 187 - =1000 - 250 208 XL 2051 1228 (8) 70 (8) 380 312 256 400 300 250 208 YO 2051 409 (8) 70 (8) 380 312 256 400 300 500

110 230 XL (2) 60 2051 1228 (8) 70 (8) 380 312 256 g I350 300 SOO 450 230 YO 2051 409 (8) 70 (8) 380 312 256 350 300 500 450 460 XL 914 485 (8) 35 (8) 190 231 - 0000 - 300 460 YO 904 162 (8) 35 (8) 190 231 - 0000 - 300 -

208 XL (1) 60 2051 1228 (8) 70 (8) 380 312 260 400 300 500 450(1) 75 2083 1415

208 YO (1) 60 2051 409 (8) 70 (8) 380 312 260 400 300 500 450(1) 75 2083 472

230 XL (1) 60 2051 1228 (8) 70 (8) 380 312 260 350 300 500 450(1) 75 2083 165125

230 YO (1) 60 2051 409 (8) 70 (8) 380 02 260 350 300 500 450 (1) 75 2083 472

460 XL (1) 60 904 485 (8) 35 (8) 190 240 - 250 - 300 -(1 75 974 539

460 YO (1) 60 904 162 (8) 35 (8) 190 240 - 250 - 300 -(1) 75 974 180

208 XL 2083 1415 (8) 70 (8) 380 316 260 400 300 500 450 208 YO 2083 472 (8) 70 (8) 380 316 260 400 300 500 450

135 230 XL (2) 75 2083 1415 (8) 70 (8) 380 316 260 400 300 500 450 I 230 YO 2083 472 (8) 70 (8) 380 316 260 400 300 500 450

460 XL 974 539 (8) 35 (8) 190 247 - 250 - 300 -460 YO 974 180 (8i 35 (8) 190 247 - 250 - 300 -

208 XL (2) SO 1788 1040 (10) 70 (10) 380 326 402 400 0000 500 500(1) 60 2051 1228

208 YO (2) 50 1788 347 (10) 70 (10) 380 326 402 400 0000 500 500(1 60 2051 409

230 XL (2) 50 1788 1040 (10) 70 (10) 380 326 402 400 0000 500 500 145 (1) 60 2011 1228

230 YO (2) 50 1788 347 (10) 70 (10) 380 326 402 400 0000 500 500(1) 60 2051 409

460 XL (2) 50 737 422 (10) 35 (10) 190 295 - 350 350 --(1) 60 904 485

460 YO (2) SO 731 141 10 (35) (10)190 295 - 350 350- -(1)60 904 162

208 XL 2051 1228 (10) 70 (10) 380 326 462 400 (2)250 500 600 208 YO 2051 409 (10) 70 (10) 380 326 462 400 (2)250 500 600

160 230 XL (3) 60 2051 1228 (10) 70 (10) 380 326 462 400 (2)250 500 230 YO 2051 409 (10) 70 (10) 380 326 462 600400 (2)250 500 600 460 XL 904 485 (10) 35 (10) 190 329 - 400 - 400 460 YO 904 167 (10) 35 (10) 190 329 - 400 - 400 - I

NOTES 1 XL Across the LineYOStarDelta 2 RLA Rated LoadAmps(ratedin accordance withARI Standard 590) LRA LockedRotorAmps 3 Wire Size Amps equal125of the ratedloadampsfor the largestmotorin thecircuitplus100of the ratedloadampsfor all othermotorsin the circuit per

NEC 4 Wire size based on copperconductorswith75C insulation perNECTable310-16 Terminal block lugs are sizedaccordingly Use of oversize wiringmay

not lit in terminal blocks 5 Maximumfuse size is basedon 175to 225of the ratedloadampsfor the largestmotorin the circuitplus 100of the rated loadampsfora othermotors

in the circuit per NEC VOLTAGE TOLERANCES 208V-230V min 187VMax 253V

480V Min414V Max506V

I

18

ELECTRICAL DATA Volts Type COMPRESSORModel FAN MOTORS MINCIRCUIT RECOMMENDED MAXIMUM 60 Hz of Oty RLA Starting FLAACWC LRA AMPACITY WIRESIZE FUSE SIZE 3 Ph Start Curro EaSC HP Ea Ea Ea Cire1 Cire2 Cire1 Cire2 Cire1 Cire2 208 XL 2051(1) 60 1228 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 1415 208 YO (1) 60 2051 409 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 472 230 XL (1) 60 2051 1228 (12)70 (12) 380 341 469 500 (2) 250 500 600

12 75 2083 1415185 230 YO (1) 60 2051 409 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 472 460 XL 485 (12) 35 (1) 60 904 (12) 190 352 500 400- - -

(2) 75 974 539 460 YO (1) 60 904 162 (12) 5(12)19 352 500 400- - -

(2) 75 974 180 208 XL 2083 1415 (12) 70 (12) 380 345 469 500 500(2) 250 600

472208 YO 2083 (12) 70 345(12) 380 469 500 (2) 250 500 600 230 XL (3) 75 2083 1415 (12) 70 345(12) 380 469 500 (2) 250 500 600200 230 YO 2083 472 (12) 70 (12) 190 345 469 500 500(2) 250 600 460 XL 539974 (12) 35 (12) 190 359 - 450500 - -

180 1(12) 35 460 YO 974 (12) 190 359 450 -500- -2051 1228208 XL (12) 70 504(12) 380 504 (2) 250 (2) 250 700 700

208 YO 2051 409 (12) 70 (12) 380 504 504 (2) 250 700(2) 250 700 (4) 60 2051 1228 (12) 70 230 XL (12) 380 504 504 (2) 250 (2) 250 700 700215

YO 2051 409230 (12) 70 (12) 380 504 504 (2) 250 (2) 250 700 700 460 904 485 (12) 35 XL (12) 190 225 225 0000 0000 300 300

(12) 35 460 YO 904 162 (12) 190 300225 225 0000 0000 300 2051 1228208 XL (2) 60 (14) 70 (14) 380 504 525 (2250 700 700(2)300

(2) 75 2083 1415 2051 409 (14) 70 700 700208 YO (2) 60 (14) 380 504 525 (2) 250 (2)300

(2) 75 2083 472240 700XL (2) 60 2051 1228 (14) 70 (14) 380 504 525 (2)250 (2)300 700230

(2) 75 2083 1415 2011230 YO (2) 60 409 (14) 70 (14) 380 504 525 (2) 250 (2)300 700 700

(2) 75 2083 472 300460 XL (2) 60 904 485 (14) 35 (14) 190 225 248 0000 250 300

12 75 974 539 904 162 250 300 300460 YO (2) 60 (14) 35 (14) 190 225 248 410

(2) 75 974 180 2083 1415 (2)300 700 700XL (16) 70 (16) 380 525 525 (2)300208 2083 1415 (2)300 700 700208 YO (16) 70 525 525 (2)300(16) 380

700 7002083 1415 (16) 70 (2300230 XL (16) 380 525 525 (2300 700 700(2300(4) 75 2083 472 (16) 70 (16) 380 525 525 (2300230 XL265

300250 300974 539 (16) 35 248 248 250XL (16) 380 460 (16) 35 300 300974 (16 380 248 250 250YO 539 248460

NOTES 1 XL Across the Line YO Star Delta 2 RLA Rated Load Amps (rated in accordance with ARI Standard 590) LRA Locked Rotor Amps 3 Wire Size Amps equal 125 of the rated load amps for the largest motor in the circuit plus 100 of the rated load amps for all other motors in the circuit per

NEC 4 Wire size based on copper conductors with 75degG insulation per NEG Table 310-16 Terminal block lugs are sized accordingly Use of oversize wiring may

not fit in terminal blocks 5 Maximum fuse size is based on 175 to 225 of the rated load amps for the largest motor in the circuit plus 100 of the rated load amps for a other motors

in the circuit per NEG VOLTAGE TOLERANCES 208V-230V min 187V Max 253V

480V Min414V Max506V

19

0

(Wd~) 3lV~ M011 ~31VM

006 009 00 OOt OOl OS L 00 L os 0 Ot

V D m (I) (I)

c D m c D o V

- m m -t o

~

~ m D-

aoao 3~nSS3~d ~3100~

APPLICATION DATA

POINT LOADING

ArMi I 1 5 1

ACWC 45 THRU 10 SC

COMPRESSOR CONDENSER SECTION SECTION

_ 2 4 bull 1

bull CA

J

Model Dimensions Size A B C D 45 91 - - -55 91 - - -70 145 - - -90 145 - - -110 60 40 160 -125 60 40 160 -135 60 40 160 -145 138 74 107 -160 13830 74 107 -185 138 129 107 -200 138 129 107 -215 106 82 106 80 240 106 82 134 107 265 133 110 134 107

1310

1310

~

1

1310

2

ACwe 110 THRU 200 Ie

COMPREIlOfl CONDENSER SECTION IECnoN

4 -

5Imiddot

ACWC 2t5 THRU 215 SC

Model Loadlnu (LBS) Size 1amp2 3amp4 5amp6 7amp8 9 amp10 45 585 765 550 - -55 705 810 635 - -70 660 890 700 - -90 1025 1500 1175 - -110 1195 635 1525 995 -125 1255 690 1835 1115 -135 1255 665 1880 1105 -145 1330 2380 2160 1450 -160 1330 2440 2280 1515 -185 1235 2575 2980 1360 -200 1275 2635 3020 1380 -215 1010 2270 2590 2240 840 240 1115 2550 2870 2715 1125 265 1380 2980 3515 2750 1175

11

II i middot 2 4 lIf 11 to L

21

TROUBLESHOOTING GUIDE

CHILLER UNIT WILL NOT START POSSIBLE CAUSE REMEDY 1 Power off 1 Check main disconnect switch

2 Main line open 2 Check main fuses

3 Incorrect wiring 3 Check the wiring diagram

4 Loose terminals 4 Tiqhten all terminals

5 Control circuit open 5 Check phase loss monitor flow switch circuit breakers temperature control low ambient thermostat low temperature thermostat remote switch etc

6 Time delay 6 Wait

COMPRESSOR HUMS BUT DOES NOT START

POSSIBLE CAUSE REMEDY

1 Low voltage 1a Check at service and unit for loss

b Consult power company

COMPRESSOR CUTS OUT ON LOW PRESSURE SAFETY CONTROL POSSIBLE CAUSE REMEDY 1 Refrigerant shortage 1 Check for leaks -- add refrigerant 2 Restriction in liquid line 2a Plugged strainer - dean or replace

b Liquid line valve partially closed - open valves fully c Expansion valve clogged or inoperative - clean or replace as

required d Solenoid valve partially open - clean or replace as required

3 Low water flow thru cooler 3 Check water flow thru cooler and correct as required

COMPRESSOR CYCLES ON HIGH PRESSURE CONTROL POSSIBLE CAUSE REMEDY 1 Compressor discharge valve partially closed 1 Open valve fully 2 Non-condensible gases in system 2 Operate condenser fans with compressors off If condenser

pressure exceeds saturated pressure corresponding to condenser entering air temperature then purge air from discharge line

3 Overcharge of R-22 3 Purge system while in operation until head pressure reaches a normal level

4 Dirty condenser 4 Clean the condenser 5 Compressor discharge check valve not operating properly 5 Replace if necessary 6 Fans not running 6 Check pressure control setting

CAUSES AND PREVENTION OF FREEZE-UP CAUSES PREVENTION 1 Improper charging 1 Charge per manufacturers recommendation

2 Improperly set safety time delay 2 Check the safety time delay low pressure control for proper setting at the beginning of each season

3 Improper chilled water circulation 3 Use an ample sized cleanable strainer in the chilled water circuit Make certain the strainer is clean to insure full flow and velocity of

chilled water It may sometimes be necessary to treat the water to prevent formation of deposits

4 Not draining for winter shutdown 4 When the system is shut down for the winter remove the drain

plugs and drain the cooler Blowout any remaining water with air

5 Improper pump shutdown 5 Make sure chiller barrel heater is working and flow switch is installed per wiring diagrams

6 Low ambient during air conditioning season 6 Make sure chiller barrel heater is working

NOTE If the ambient temperature is below 32degF freezing can be completely prevented by one of two methods

1 Drain all water from the equipment 2 Add antifreeze to the water

22

START-UP CHECK LIST

Unit Model No

Setting unit

Wiring

Piping

Alignment

Before Start-Up

After Start-Up

Yes No a Vibration isolator used

b Spring isolator adjusted for equal height c If rubber-in-shear isolators are used is unit leveled by shimming

a Power wiring complete

b Control wiring complete c Electric service adequate for load

d Power source voltage correct for motor(s) used

e Motor circuit has proper size fusetrons f System wired per diagram

g All lead connections tight h Wiring complies with local codes i Flow switch operation

a Piping complies with applicable codes b External piping independently supported c Chilled water lines insulated

a All belts adjusted and checked for tension b All pulleys checked and adjusted for proper pitch tightness and

alignment

a Open compressor discharge service valve b Open liquid valve(s) c Open suction and discharge valves to pressure gauges (if supplied) d Check rotation of all fan motors e Start auxiliary equipment (pumps fans etc) f Is crankcase heater operating Operate 24 hours prior to unit startup g Check the compressor oil level through the crankcase sight glass The oil

level should be to the top of the glass If the level is low add oil in accordance with the directions in the maintenance instruction

h Check all control settings as specified in Table 1 I Air purged from chilled water system

a Check high pressure control b Check oil temperature safety switch c Check and adjust low pressure or temperature freeze control d Check and adjust operating thermostat e Check and adjust low pressure operating control f Check and adjust expansion valve superheat g Check and adjust capacity control thermostat

23

OPERATING DATA CHILLER Voltage L-1 L-2 L-3 _ Pressure Gauge Readings 1 Suction psig 1 Discharge psig 2 Suction psig 2 Discharge _ psig 3 Suction psig 3 Discharge psig 4 Suction psig 4 Discharge _ psig High pressure switch setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-in) psig psig (Out) 4 (Cut-In) psig psig (Out) Checked Setting - Yes - No (each circuit) Low Pressure Switch Setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-In) psig psig (Out) 4 (Cut-in) psig psig (Out) Checked Setting -Yes -No (each circuit) 1 Oil Temperature Safety Switch Cut Out 2 Oil Temperature Safety Switch Cut Out 3 Oil Temperature Safety Switch Cut Out 4 Oil Temperature Safety Switch Cut Out If Star-Delta start time delay is seconds Temperature of air entering condenser F Temperature of air leaving condenser of Temperature of chilled water entering chiller OF Temperature of water (chilled) leaving chiller F Chilled water pressure entering chiller psig Chilled water pressure leaving chiller psig

MAINTENANCE Good maintenance practice will prolong the chiller life and will reduce the Ask of system breakdown and expensive service calls

A weekly check of the ACWC-SD unit requires only a few minutes and will prove beneficial in insuring long trouble free operation

WEEKLY CHECKS- with unit in operation for at least four hours 1) Check compressor oil level - At least above 12 of sight glass 2) Record suction and discharge pressures

Typical Condition R22 Ambient 95degF Return water 55degF Leaving water 45degF Suction 62 psig Discharge 270 psig

3) Record ambient temperature 4) Check liquid sight glass

Make sure liquid is clear - no bubbles 5) Check that all fans are running 6) Check entering face of condenser coil for cleanliness 7) Record voltage at unit

All of the above can be performed by building maintenance personnel If oil levels are low or any of the above checked items are questionable consult a qualified serviceman

At least once a year a qualified serviceman should check unit oil levels superheat and control operation

DUNHAM-BUSH USA

P l) bull 130 xUtUC t01 Bmgess RO~ Harrisonburg VA 22801 Phone (540) 434-0711 FAX (540) 434-~ 2118

wvvwdunham-bushcom Form No 6184

Page 11: ACWC-SD - · PDF fileACWC-SD • Screw . Type • • • Air-Cooled Packaged Chillers •• Installation, Operation, and •• • Maintenance Manual • • • •• DESCRIPTION

II

~

I rA

I

TA~

D

ELTA

STA~T

CONP~E~)

CU

lT 2

~

f

bull ]

A

U

4 ]I

IUft

middotJI

Mon

tUPlOI

NT

lOA

Ot-

-O

I

01

0

]

(N

GI

011

1

00

CT

AN

)

40

00

HN

a

_N

I

J00

I -

It IC

y

TO

I

I I

I

~

oiiO

NA

t

I bull bull

wi

i

lOa

r~TT~-

I M

OT

I C

ON

sr

0

llItt

(

co

ce

OZ

UK

1

11

_JO

I I

)--11

--

- ---

-

IJI

LD

~

I

A

CK

lS

C

UK

I

IL

UO

A

TO

O

WH

IT

1

L

OW

SW

ITC

HJl

AL

D

00

IZ

I

f

1It-

-

rl__ u-

poundL

J f

aT

ION

AL

TI

WfI

OO

f

~

ff

I

Dill

C

ON

TAC

TOIlI

C

OtL

S (1

middot4

(IS

middot14

A

ND

II-

I

01

1In

N

O

Wl

0

51

11

~

CO

NT

AC

TS

I

fH

IO

Uti

IS

N

OT

TO

IE

al

llauN

DIO

O

N H

I Sr

CO

NO

AIl

lf

StO

l

f

I

TI

AN

D

TI

TI

U

I

IIN

OII

t

0middot

f1L

OC

AT

IO

IN n

lll

GU

lUT

r-

----

shy~

(I

G

lIt

no

v

HA

I

LO

SS M

ON

IO

nf

1Na

bull

AN

D

ON

rc

I(

CO

M(

f A

IrfD

I

lItU

rC

TIY

(U

00

-

5

E

[CO

OIO

lItc

rlll

TO

0

0

AN

UA

L

t

OIN

T A

Na

f

oo

IlU

COfrt

TO

I U

ND

IN

Stt

UC

TIO

trl

r

co

rNH

D

01 11

raquoIN

ITIA

L

CO

NT

lIIiO

L

fII

I0 I

UT

IS

a

jshy

orshy

10bull

CO

M1

II1t1

Ol

MO

GU

LI

I N(

tN-a

UT

OM

AT

lC

I 1I

lfla

n

flS

bullbull

11

A

LSO

ampO

eMmiddotO

UT

luer

llt

middot I

no

C

AL

Y

WH

IM A

N

IUIT

T T

IIII

P

T

MU

I C

ON

egoo

IT

flO

LI

CA

l

ItU

I1 I

T

TU

NIN

G W

ITC

M

0

~r=

0 I

lIO

Wlf

lIT

A

L

fOtt

CO

lI

tbullbull

w

ITC

H_

I

on

WO

Nlf

lIT

JII

IL

POllt

COW

bull

I In

degz

r+-i

~~

t

u ~o

1 ~rI~~

~~

~~TtIc~~I~D

1

SW

lTC

HI ~

C

OIfT

AC

TcU

t W

lItN

t C

OM

bullbull

H

To

lIL

b

l

0t~~1

0

1

CO

tfC

TO

H

I

lIt

C

ltbull

IIT

C

~r-

bull

WM

IH

-

2

N

OT

1V

l

rD

wllI

I[ to

IlIC

OM

n

I W

I

It

I

fjC

Ofl

P

tE

CJ)shy

t W

IN L

UI N

OT

SU

PL

ID

W

IIIIC

O

J

lleo

W

ti

l

LU

KT

IT

10- A

ND

10ft

II

v

C~

LO

CA

TU

I II

1t

11V

MI

_T

at

I

z10

I

T

lNH

A

TU

RC

S

lNS

OIt

MU

tT

ve

IL

OID

C

IL

C

()

11II

L

AT

I

AT

10

_

A

U

IIIT

I0middot

PCA

LOW M

I_ lO

TI

I bullbull

n

II

DES

IGN

ATI

ON

S

II

CO

NT

IlID

t I

NO

-o

MO

LD

INfl

C

OIL

It L

tNI

NO

0

Q

N

C

CO

NU

ClI

W

ITH

UN

I N

O

01]

0 co

O

f

11

~

I

ILK

n

e

s IA

UL

It

ibull

o O

CO

NTA

CTS

w

nw L

INI

NO

01

fA

0

~

fItO

TI

LI

I N

O

v

A

II

~ ~ bull i middots

~

~~ - ~

~

1- I J I J I I I I I I I I I I I I I I L __ J

I

a bull bull a bull bull

I I I

_J

r------~

=~I = ~ ~ bull ~ I I

~

as coe ruq SV~ siapow ~NI~IM lO~lN03lV3ldAl

i 4

_

a

~FirI1 u~III - I I

~ 1I

00000 -

I=II~I~~~~raquoIIIItIII~ampI~

as ooz nJ4l sv ~ siapow ~NI~IM lO~lNOgt TVgtldAl

bullbull bullbull

bullbull

~

jgt

lpoundIt

ND

II

co

----

----

----

----

----

----

----

----

-

r-~-middot--=-~~

~

bull a

~

at~04

5

---

~1I

A

~n

bullbullmiddot-shy

wo

_-

bull

lIt

C-

I C

Cf

aC

TO

Ic

ow

n

CC

eM

ca

~C

M

OD

IAI

CI

T-

CO

IITA

CT

oa

bullbull

CMCU

rT I

ItIM

IA

co-l

to

c-c

VIT

C

I

rr

c

AfE

bull r~----Ef1

POW

I

III

IQ

W

Q

tIL

UT

I1I

U__~

J

COt

I

LD

W M

lMtr

f nc

IIO

ff

0

N

LO

W

C

OIIT

INM

I I

CO

M

US

ON

C

NC

UIT

II

II

-~

_T

shy

C

O

NU

SO

II

CIN

CU

IT Z

II

D[TA~

-

ST

AN

D(~TA

IT

AII

T

0

u III

r

amp

II

-~

If

10

MA

MI

eN

talI

Tco_

~

STA

N D[~TA

ST

AII

T

~

CIS

-I

LA

~ 1-4

nmiddot

00

-

-II

1t1S

-1 aw

o fI

fl

U- I -~ Ci

Pi=

i

t

shy

~

iii

i

iii=

ii

-

-shyiii

ClL

n

TU

U

LOt

e

bull It

lLA

Yn

C

AM

Im

CIII

IID

L bull

CU

_C

Abull

fl

lUY

_f

tMO

ea

UY

middotIO

CI

lO

Ll

t

NIU

_L

N

CO

WU

UO

ItC

U

llT

l bullbull 0

1middot

lit

TMC

MI0

8TA

T tc

_lt

CIl

it

11

II

_

middotLO

W

TII

IfN

T

UIlI

C

nll

-

D-C

UlT

QIIU

tW

n-T

PII

IU

LIO

MI-

AC

TC

Ntf

Wi

MI

II

II

tY

middotCM

OO

C

LOW

HIe U

(O

Uf

lIl_

L

OA

M

1OtI

1tO

lD

CO

OA

CM

UtT

1M

C

lIY

Dl

NC

Afi

ll ea

-tU

lT 1

ItUbullbull

lI

oo

ww

lItt

lffc

e O

Un

n

cT

IlG

I

Ie-

~U

IIIC

CIV

P

1T

1lt

C

bullbull

Off

AT

tw

ebullbull

ampOW

IC

IUT

~-

4ti

iT

~

co

ww

O

UfU

T

DITA~

A

ITA

A

OEL

TA

IT

AJI

IT

co

rn~

e

I

1amp

ItmiddotI

~ bull

I I

I

I r

~

bull Iamp

II

I ~

I-

oJ

II I

IrIf

I I I I

s~

o

-I I

ltDc

() raquo

L 10

V

i

()

~O

to

U

lZr0

t2

llJ

IL

C6

J=

_J

~-1

f

II

c 0

II

N

ge

cno

c-

II

Z

Ggt

If IO

IC

IIY

II

IIR

III

IJt

T H

llII

A

Il C

Olaquof

U

TMIbull

~LDM

fI

lAR

PM

Iamp L

Oll

lTV

ii

iLii

Uii

ii

~

U3

I iL

iii=

i

Uii

u

i

O

(no)

T

bull II

1

IOA~

bullr

~ I

[gtO(]O

~ i I Ii i 2 ~ ~ ~ i a bull il 2 ~

iiibullbullbull

~ I ~ I I I ~~ =l ~ iI I ~ I I I It I 1111 amp ~~

as ooz nJ4l SP~ SlapoUII ~NI~IM 10U1NOl lVlldAl

-------

---

TYPICAL POWER WIRING Models 45 thru 70 SC

----

rYl31I01 I

-Ii --ti-

_ I ~_-

~ lniJ -

LIIbullbullbullbull PC _ amp-II _--- ~

TYPICAL POWER WIRING Models 90 thru 135 SC

- --- _ Tt

~rfh c~

tP ~

_III ~

I r-- ~- IIlJ

bull - MIl Mf __ bull Ie_~--~ _shy- shy16

---

----------

TYPICAL POWER WIRING Models 145 thru 200 SC

_ --1a1 IIUrI

middotrFti~v_ bull I

i~i ~~ TaII IIOMLI ~tN T 100 WTIOII 011 lilOOCL a

~ t1

tI bullbullbull

L

i I r-~

I r

~ ~ ~ III

2 ~ ~ ~l

- ~IlD I hJOHr eo teO acshyt CmiddotClM ~ CIKUr1 --

TYPICAL POWER WIRING Models 215 thru 265 SC

ItUU 1D Wll1U1I fIa -rMI

rt-h I -au 11 1_ i r~ rt-f

-i rn f1 ft fi i- llil bullbull c~ I bull c =

~~~ ~i~-~

~~m

~~~CI1 R~~ ~ ~~ ~llAi4I

luv~ bull ~uf LL~~-

~Mfl l~t IrMiA

a I III nII I bull it d

~-t--J I Lll-l~j ~nL4111 WlJj== lit-

I bullbullbull I

UGEND

~

~l OJ

- c~

~~~---

~)~middotI

I

L _~~~ L _I__~_J I ~ (11_1 ~ H~ CUlTMIt tffC_) Ll N

-r_ 0 1ItCIIIl0AI lllQUlllCo as -0- bull bullbull fI PC 110 lNJCllII a Olil1100pound1 II 111 el 1101 ItCOU_ 011 IIOOIL140

I 011 CI-( H[ (0110 (fMCun ubullbull --- l(lD IMbullbull Ntlf 110 e414-7

--CTOttbullbull

2

17

ELECTRICAL DATA Model Volts Type COMPRESSOR FAN MOTORS MIN CIRCUIT RECOMMENDED MAXIMUM ACWC 60 Hz of Qty RLA Starting FLA LRA AMPACITY WIRESIZE FUSESIZE

SC 3 Ph Start HP Ea Curro Ea Ea Ea Circ1 Circ2 Circ1 Circ2 Circ1 eire 2

208230 XL 1788 1040 (4) 70 (4) 380 252 - 250 - 400 -45 208230 YO (1) 50 1788 347 (4) 70 (4) 380 252 - 250 - 400 -

460 XL 737 422 (4) 35 (4) 190 106 - 2 - 175 -460 YO 737 141 (4) 35 (4) 190 106 - 2 - 175 -

208230 XL 2051 1228 (4) 70 (4) 380 284 - 300 - 450 -55 208230 YO (1) 60 2051 409 (4) 70 (4) 380 284 - 300 - 450 -

460 XL 904 485 (4) 35 (4) 190 127 - 1 - 200 -460 YO 904 162 (4) 35 (4) 190 127 - 1 - 200 -

208230 XL 2083 1415 (6) 70 (6) 380 302 350 500 -70 208230 YO (1) 75 2083 472 (6) 70 (6) 380 302 350 500 -

460 XL 974 539 (6) 35 (6) 190 143 0 225 -460 YO 974 180 (6) 35 (6 190 143 0 225 -208 XL 1788 1040 (6) 70 (6) 380 266 224 300 0000 400 400 208 YO 1788 347 (6) 70 (6) 380 266 224 300 0000 400

90 230 XL (2) 50 1788 1040 (6) 70 (6) 380 266 224 400 I300 0000 400 400 230 YO 1788 347 (6) 70 (6) 380 266 224 300 0000 400 400 460 XL 737 422 (6) 35 (6) 190 187 - 000 - 250 460 YO 737 141 (6) 35 (6) 190 187 - =1000 - 250 208 XL 2051 1228 (8) 70 (8) 380 312 256 400 300 250 208 YO 2051 409 (8) 70 (8) 380 312 256 400 300 500

110 230 XL (2) 60 2051 1228 (8) 70 (8) 380 312 256 g I350 300 SOO 450 230 YO 2051 409 (8) 70 (8) 380 312 256 350 300 500 450 460 XL 914 485 (8) 35 (8) 190 231 - 0000 - 300 460 YO 904 162 (8) 35 (8) 190 231 - 0000 - 300 -

208 XL (1) 60 2051 1228 (8) 70 (8) 380 312 260 400 300 500 450(1) 75 2083 1415

208 YO (1) 60 2051 409 (8) 70 (8) 380 312 260 400 300 500 450(1) 75 2083 472

230 XL (1) 60 2051 1228 (8) 70 (8) 380 312 260 350 300 500 450(1) 75 2083 165125

230 YO (1) 60 2051 409 (8) 70 (8) 380 02 260 350 300 500 450 (1) 75 2083 472

460 XL (1) 60 904 485 (8) 35 (8) 190 240 - 250 - 300 -(1 75 974 539

460 YO (1) 60 904 162 (8) 35 (8) 190 240 - 250 - 300 -(1) 75 974 180

208 XL 2083 1415 (8) 70 (8) 380 316 260 400 300 500 450 208 YO 2083 472 (8) 70 (8) 380 316 260 400 300 500 450

135 230 XL (2) 75 2083 1415 (8) 70 (8) 380 316 260 400 300 500 450 I 230 YO 2083 472 (8) 70 (8) 380 316 260 400 300 500 450

460 XL 974 539 (8) 35 (8) 190 247 - 250 - 300 -460 YO 974 180 (8i 35 (8) 190 247 - 250 - 300 -

208 XL (2) SO 1788 1040 (10) 70 (10) 380 326 402 400 0000 500 500(1) 60 2051 1228

208 YO (2) 50 1788 347 (10) 70 (10) 380 326 402 400 0000 500 500(1 60 2051 409

230 XL (2) 50 1788 1040 (10) 70 (10) 380 326 402 400 0000 500 500 145 (1) 60 2011 1228

230 YO (2) 50 1788 347 (10) 70 (10) 380 326 402 400 0000 500 500(1) 60 2051 409

460 XL (2) 50 737 422 (10) 35 (10) 190 295 - 350 350 --(1) 60 904 485

460 YO (2) SO 731 141 10 (35) (10)190 295 - 350 350- -(1)60 904 162

208 XL 2051 1228 (10) 70 (10) 380 326 462 400 (2)250 500 600 208 YO 2051 409 (10) 70 (10) 380 326 462 400 (2)250 500 600

160 230 XL (3) 60 2051 1228 (10) 70 (10) 380 326 462 400 (2)250 500 230 YO 2051 409 (10) 70 (10) 380 326 462 600400 (2)250 500 600 460 XL 904 485 (10) 35 (10) 190 329 - 400 - 400 460 YO 904 167 (10) 35 (10) 190 329 - 400 - 400 - I

NOTES 1 XL Across the LineYOStarDelta 2 RLA Rated LoadAmps(ratedin accordance withARI Standard 590) LRA LockedRotorAmps 3 Wire Size Amps equal125of the ratedloadampsfor the largestmotorin thecircuitplus100of the ratedloadampsfor all othermotorsin the circuit per

NEC 4 Wire size based on copperconductorswith75C insulation perNECTable310-16 Terminal block lugs are sizedaccordingly Use of oversize wiringmay

not lit in terminal blocks 5 Maximumfuse size is basedon 175to 225of the ratedloadampsfor the largestmotorin the circuitplus 100of the rated loadampsfora othermotors

in the circuit per NEC VOLTAGE TOLERANCES 208V-230V min 187VMax 253V

480V Min414V Max506V

I

18

ELECTRICAL DATA Volts Type COMPRESSORModel FAN MOTORS MINCIRCUIT RECOMMENDED MAXIMUM 60 Hz of Oty RLA Starting FLAACWC LRA AMPACITY WIRESIZE FUSE SIZE 3 Ph Start Curro EaSC HP Ea Ea Ea Cire1 Cire2 Cire1 Cire2 Cire1 Cire2 208 XL 2051(1) 60 1228 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 1415 208 YO (1) 60 2051 409 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 472 230 XL (1) 60 2051 1228 (12)70 (12) 380 341 469 500 (2) 250 500 600

12 75 2083 1415185 230 YO (1) 60 2051 409 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 472 460 XL 485 (12) 35 (1) 60 904 (12) 190 352 500 400- - -

(2) 75 974 539 460 YO (1) 60 904 162 (12) 5(12)19 352 500 400- - -

(2) 75 974 180 208 XL 2083 1415 (12) 70 (12) 380 345 469 500 500(2) 250 600

472208 YO 2083 (12) 70 345(12) 380 469 500 (2) 250 500 600 230 XL (3) 75 2083 1415 (12) 70 345(12) 380 469 500 (2) 250 500 600200 230 YO 2083 472 (12) 70 (12) 190 345 469 500 500(2) 250 600 460 XL 539974 (12) 35 (12) 190 359 - 450500 - -

180 1(12) 35 460 YO 974 (12) 190 359 450 -500- -2051 1228208 XL (12) 70 504(12) 380 504 (2) 250 (2) 250 700 700

208 YO 2051 409 (12) 70 (12) 380 504 504 (2) 250 700(2) 250 700 (4) 60 2051 1228 (12) 70 230 XL (12) 380 504 504 (2) 250 (2) 250 700 700215

YO 2051 409230 (12) 70 (12) 380 504 504 (2) 250 (2) 250 700 700 460 904 485 (12) 35 XL (12) 190 225 225 0000 0000 300 300

(12) 35 460 YO 904 162 (12) 190 300225 225 0000 0000 300 2051 1228208 XL (2) 60 (14) 70 (14) 380 504 525 (2250 700 700(2)300

(2) 75 2083 1415 2051 409 (14) 70 700 700208 YO (2) 60 (14) 380 504 525 (2) 250 (2)300

(2) 75 2083 472240 700XL (2) 60 2051 1228 (14) 70 (14) 380 504 525 (2)250 (2)300 700230

(2) 75 2083 1415 2011230 YO (2) 60 409 (14) 70 (14) 380 504 525 (2) 250 (2)300 700 700

(2) 75 2083 472 300460 XL (2) 60 904 485 (14) 35 (14) 190 225 248 0000 250 300

12 75 974 539 904 162 250 300 300460 YO (2) 60 (14) 35 (14) 190 225 248 410

(2) 75 974 180 2083 1415 (2)300 700 700XL (16) 70 (16) 380 525 525 (2)300208 2083 1415 (2)300 700 700208 YO (16) 70 525 525 (2)300(16) 380

700 7002083 1415 (16) 70 (2300230 XL (16) 380 525 525 (2300 700 700(2300(4) 75 2083 472 (16) 70 (16) 380 525 525 (2300230 XL265

300250 300974 539 (16) 35 248 248 250XL (16) 380 460 (16) 35 300 300974 (16 380 248 250 250YO 539 248460

NOTES 1 XL Across the Line YO Star Delta 2 RLA Rated Load Amps (rated in accordance with ARI Standard 590) LRA Locked Rotor Amps 3 Wire Size Amps equal 125 of the rated load amps for the largest motor in the circuit plus 100 of the rated load amps for all other motors in the circuit per

NEC 4 Wire size based on copper conductors with 75degG insulation per NEG Table 310-16 Terminal block lugs are sized accordingly Use of oversize wiring may

not fit in terminal blocks 5 Maximum fuse size is based on 175 to 225 of the rated load amps for the largest motor in the circuit plus 100 of the rated load amps for a other motors

in the circuit per NEG VOLTAGE TOLERANCES 208V-230V min 187V Max 253V

480V Min414V Max506V

19

0

(Wd~) 3lV~ M011 ~31VM

006 009 00 OOt OOl OS L 00 L os 0 Ot

V D m (I) (I)

c D m c D o V

- m m -t o

~

~ m D-

aoao 3~nSS3~d ~3100~

APPLICATION DATA

POINT LOADING

ArMi I 1 5 1

ACWC 45 THRU 10 SC

COMPRESSOR CONDENSER SECTION SECTION

_ 2 4 bull 1

bull CA

J

Model Dimensions Size A B C D 45 91 - - -55 91 - - -70 145 - - -90 145 - - -110 60 40 160 -125 60 40 160 -135 60 40 160 -145 138 74 107 -160 13830 74 107 -185 138 129 107 -200 138 129 107 -215 106 82 106 80 240 106 82 134 107 265 133 110 134 107

1310

1310

~

1

1310

2

ACwe 110 THRU 200 Ie

COMPREIlOfl CONDENSER SECTION IECnoN

4 -

5Imiddot

ACWC 2t5 THRU 215 SC

Model Loadlnu (LBS) Size 1amp2 3amp4 5amp6 7amp8 9 amp10 45 585 765 550 - -55 705 810 635 - -70 660 890 700 - -90 1025 1500 1175 - -110 1195 635 1525 995 -125 1255 690 1835 1115 -135 1255 665 1880 1105 -145 1330 2380 2160 1450 -160 1330 2440 2280 1515 -185 1235 2575 2980 1360 -200 1275 2635 3020 1380 -215 1010 2270 2590 2240 840 240 1115 2550 2870 2715 1125 265 1380 2980 3515 2750 1175

11

II i middot 2 4 lIf 11 to L

21

TROUBLESHOOTING GUIDE

CHILLER UNIT WILL NOT START POSSIBLE CAUSE REMEDY 1 Power off 1 Check main disconnect switch

2 Main line open 2 Check main fuses

3 Incorrect wiring 3 Check the wiring diagram

4 Loose terminals 4 Tiqhten all terminals

5 Control circuit open 5 Check phase loss monitor flow switch circuit breakers temperature control low ambient thermostat low temperature thermostat remote switch etc

6 Time delay 6 Wait

COMPRESSOR HUMS BUT DOES NOT START

POSSIBLE CAUSE REMEDY

1 Low voltage 1a Check at service and unit for loss

b Consult power company

COMPRESSOR CUTS OUT ON LOW PRESSURE SAFETY CONTROL POSSIBLE CAUSE REMEDY 1 Refrigerant shortage 1 Check for leaks -- add refrigerant 2 Restriction in liquid line 2a Plugged strainer - dean or replace

b Liquid line valve partially closed - open valves fully c Expansion valve clogged or inoperative - clean or replace as

required d Solenoid valve partially open - clean or replace as required

3 Low water flow thru cooler 3 Check water flow thru cooler and correct as required

COMPRESSOR CYCLES ON HIGH PRESSURE CONTROL POSSIBLE CAUSE REMEDY 1 Compressor discharge valve partially closed 1 Open valve fully 2 Non-condensible gases in system 2 Operate condenser fans with compressors off If condenser

pressure exceeds saturated pressure corresponding to condenser entering air temperature then purge air from discharge line

3 Overcharge of R-22 3 Purge system while in operation until head pressure reaches a normal level

4 Dirty condenser 4 Clean the condenser 5 Compressor discharge check valve not operating properly 5 Replace if necessary 6 Fans not running 6 Check pressure control setting

CAUSES AND PREVENTION OF FREEZE-UP CAUSES PREVENTION 1 Improper charging 1 Charge per manufacturers recommendation

2 Improperly set safety time delay 2 Check the safety time delay low pressure control for proper setting at the beginning of each season

3 Improper chilled water circulation 3 Use an ample sized cleanable strainer in the chilled water circuit Make certain the strainer is clean to insure full flow and velocity of

chilled water It may sometimes be necessary to treat the water to prevent formation of deposits

4 Not draining for winter shutdown 4 When the system is shut down for the winter remove the drain

plugs and drain the cooler Blowout any remaining water with air

5 Improper pump shutdown 5 Make sure chiller barrel heater is working and flow switch is installed per wiring diagrams

6 Low ambient during air conditioning season 6 Make sure chiller barrel heater is working

NOTE If the ambient temperature is below 32degF freezing can be completely prevented by one of two methods

1 Drain all water from the equipment 2 Add antifreeze to the water

22

START-UP CHECK LIST

Unit Model No

Setting unit

Wiring

Piping

Alignment

Before Start-Up

After Start-Up

Yes No a Vibration isolator used

b Spring isolator adjusted for equal height c If rubber-in-shear isolators are used is unit leveled by shimming

a Power wiring complete

b Control wiring complete c Electric service adequate for load

d Power source voltage correct for motor(s) used

e Motor circuit has proper size fusetrons f System wired per diagram

g All lead connections tight h Wiring complies with local codes i Flow switch operation

a Piping complies with applicable codes b External piping independently supported c Chilled water lines insulated

a All belts adjusted and checked for tension b All pulleys checked and adjusted for proper pitch tightness and

alignment

a Open compressor discharge service valve b Open liquid valve(s) c Open suction and discharge valves to pressure gauges (if supplied) d Check rotation of all fan motors e Start auxiliary equipment (pumps fans etc) f Is crankcase heater operating Operate 24 hours prior to unit startup g Check the compressor oil level through the crankcase sight glass The oil

level should be to the top of the glass If the level is low add oil in accordance with the directions in the maintenance instruction

h Check all control settings as specified in Table 1 I Air purged from chilled water system

a Check high pressure control b Check oil temperature safety switch c Check and adjust low pressure or temperature freeze control d Check and adjust operating thermostat e Check and adjust low pressure operating control f Check and adjust expansion valve superheat g Check and adjust capacity control thermostat

23

OPERATING DATA CHILLER Voltage L-1 L-2 L-3 _ Pressure Gauge Readings 1 Suction psig 1 Discharge psig 2 Suction psig 2 Discharge _ psig 3 Suction psig 3 Discharge psig 4 Suction psig 4 Discharge _ psig High pressure switch setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-in) psig psig (Out) 4 (Cut-In) psig psig (Out) Checked Setting - Yes - No (each circuit) Low Pressure Switch Setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-In) psig psig (Out) 4 (Cut-in) psig psig (Out) Checked Setting -Yes -No (each circuit) 1 Oil Temperature Safety Switch Cut Out 2 Oil Temperature Safety Switch Cut Out 3 Oil Temperature Safety Switch Cut Out 4 Oil Temperature Safety Switch Cut Out If Star-Delta start time delay is seconds Temperature of air entering condenser F Temperature of air leaving condenser of Temperature of chilled water entering chiller OF Temperature of water (chilled) leaving chiller F Chilled water pressure entering chiller psig Chilled water pressure leaving chiller psig

MAINTENANCE Good maintenance practice will prolong the chiller life and will reduce the Ask of system breakdown and expensive service calls

A weekly check of the ACWC-SD unit requires only a few minutes and will prove beneficial in insuring long trouble free operation

WEEKLY CHECKS- with unit in operation for at least four hours 1) Check compressor oil level - At least above 12 of sight glass 2) Record suction and discharge pressures

Typical Condition R22 Ambient 95degF Return water 55degF Leaving water 45degF Suction 62 psig Discharge 270 psig

3) Record ambient temperature 4) Check liquid sight glass

Make sure liquid is clear - no bubbles 5) Check that all fans are running 6) Check entering face of condenser coil for cleanliness 7) Record voltage at unit

All of the above can be performed by building maintenance personnel If oil levels are low or any of the above checked items are questionable consult a qualified serviceman

At least once a year a qualified serviceman should check unit oil levels superheat and control operation

DUNHAM-BUSH USA

P l) bull 130 xUtUC t01 Bmgess RO~ Harrisonburg VA 22801 Phone (540) 434-0711 FAX (540) 434-~ 2118

wvvwdunham-bushcom Form No 6184

Page 12: ACWC-SD - · PDF fileACWC-SD • Screw . Type • • • Air-Cooled Packaged Chillers •• Installation, Operation, and •• • Maintenance Manual • • • •• DESCRIPTION

~ ~ bull i middots

~

~~ - ~

~

1- I J I J I I I I I I I I I I I I I I L __ J

I

a bull bull a bull bull

I I I

_J

r------~

=~I = ~ ~ bull ~ I I

~

as coe ruq SV~ siapow ~NI~IM lO~lN03lV3ldAl

i 4

_

a

~FirI1 u~III - I I

~ 1I

00000 -

I=II~I~~~~raquoIIIItIII~ampI~

as ooz nJ4l sv ~ siapow ~NI~IM lO~lNOgt TVgtldAl

bullbull bullbull

bullbull

~

jgt

lpoundIt

ND

II

co

----

----

----

----

----

----

----

----

-

r-~-middot--=-~~

~

bull a

~

at~04

5

---

~1I

A

~n

bullbullmiddot-shy

wo

_-

bull

lIt

C-

I C

Cf

aC

TO

Ic

ow

n

CC

eM

ca

~C

M

OD

IAI

CI

T-

CO

IITA

CT

oa

bullbull

CMCU

rT I

ItIM

IA

co-l

to

c-c

VIT

C

I

rr

c

AfE

bull r~----Ef1

POW

I

III

IQ

W

Q

tIL

UT

I1I

U__~

J

COt

I

LD

W M

lMtr

f nc

IIO

ff

0

N

LO

W

C

OIIT

INM

I I

CO

M

US

ON

C

NC

UIT

II

II

-~

_T

shy

C

O

NU

SO

II

CIN

CU

IT Z

II

D[TA~

-

ST

AN

D(~TA

IT

AII

T

0

u III

r

amp

II

-~

If

10

MA

MI

eN

talI

Tco_

~

STA

N D[~TA

ST

AII

T

~

CIS

-I

LA

~ 1-4

nmiddot

00

-

-II

1t1S

-1 aw

o fI

fl

U- I -~ Ci

Pi=

i

t

shy

~

iii

i

iii=

ii

-

-shyiii

ClL

n

TU

U

LOt

e

bull It

lLA

Yn

C

AM

Im

CIII

IID

L bull

CU

_C

Abull

fl

lUY

_f

tMO

ea

UY

middotIO

CI

lO

Ll

t

NIU

_L

N

CO

WU

UO

ItC

U

llT

l bullbull 0

1middot

lit

TMC

MI0

8TA

T tc

_lt

CIl

it

11

II

_

middotLO

W

TII

IfN

T

UIlI

C

nll

-

D-C

UlT

QIIU

tW

n-T

PII

IU

LIO

MI-

AC

TC

Ntf

Wi

MI

II

II

tY

middotCM

OO

C

LOW

HIe U

(O

Uf

lIl_

L

OA

M

1OtI

1tO

lD

CO

OA

CM

UtT

1M

C

lIY

Dl

NC

Afi

ll ea

-tU

lT 1

ItUbullbull

lI

oo

ww

lItt

lffc

e O

Un

n

cT

IlG

I

Ie-

~U

IIIC

CIV

P

1T

1lt

C

bullbull

Off

AT

tw

ebullbull

ampOW

IC

IUT

~-

4ti

iT

~

co

ww

O

UfU

T

DITA~

A

ITA

A

OEL

TA

IT

AJI

IT

co

rn~

e

I

1amp

ItmiddotI

~ bull

I I

I

I r

~

bull Iamp

II

I ~

I-

oJ

II I

IrIf

I I I I

s~

o

-I I

ltDc

() raquo

L 10

V

i

()

~O

to

U

lZr0

t2

llJ

IL

C6

J=

_J

~-1

f

II

c 0

II

N

ge

cno

c-

II

Z

Ggt

If IO

IC

IIY

II

IIR

III

IJt

T H

llII

A

Il C

Olaquof

U

TMIbull

~LDM

fI

lAR

PM

Iamp L

Oll

lTV

ii

iLii

Uii

ii

~

U3

I iL

iii=

i

Uii

u

i

O

(no)

T

bull II

1

IOA~

bullr

~ I

[gtO(]O

~ i I Ii i 2 ~ ~ ~ i a bull il 2 ~

iiibullbullbull

~ I ~ I I I ~~ =l ~ iI I ~ I I I It I 1111 amp ~~

as ooz nJ4l SP~ SlapoUII ~NI~IM 10U1NOl lVlldAl

-------

---

TYPICAL POWER WIRING Models 45 thru 70 SC

----

rYl31I01 I

-Ii --ti-

_ I ~_-

~ lniJ -

LIIbullbullbullbull PC _ amp-II _--- ~

TYPICAL POWER WIRING Models 90 thru 135 SC

- --- _ Tt

~rfh c~

tP ~

_III ~

I r-- ~- IIlJ

bull - MIl Mf __ bull Ie_~--~ _shy- shy16

---

----------

TYPICAL POWER WIRING Models 145 thru 200 SC

_ --1a1 IIUrI

middotrFti~v_ bull I

i~i ~~ TaII IIOMLI ~tN T 100 WTIOII 011 lilOOCL a

~ t1

tI bullbullbull

L

i I r-~

I r

~ ~ ~ III

2 ~ ~ ~l

- ~IlD I hJOHr eo teO acshyt CmiddotClM ~ CIKUr1 --

TYPICAL POWER WIRING Models 215 thru 265 SC

ItUU 1D Wll1U1I fIa -rMI

rt-h I -au 11 1_ i r~ rt-f

-i rn f1 ft fi i- llil bullbull c~ I bull c =

~~~ ~i~-~

~~m

~~~CI1 R~~ ~ ~~ ~llAi4I

luv~ bull ~uf LL~~-

~Mfl l~t IrMiA

a I III nII I bull it d

~-t--J I Lll-l~j ~nL4111 WlJj== lit-

I bullbullbull I

UGEND

~

~l OJ

- c~

~~~---

~)~middotI

I

L _~~~ L _I__~_J I ~ (11_1 ~ H~ CUlTMIt tffC_) Ll N

-r_ 0 1ItCIIIl0AI lllQUlllCo as -0- bull bullbull fI PC 110 lNJCllII a Olil1100pound1 II 111 el 1101 ItCOU_ 011 IIOOIL140

I 011 CI-( H[ (0110 (fMCun ubullbull --- l(lD IMbullbull Ntlf 110 e414-7

--CTOttbullbull

2

17

ELECTRICAL DATA Model Volts Type COMPRESSOR FAN MOTORS MIN CIRCUIT RECOMMENDED MAXIMUM ACWC 60 Hz of Qty RLA Starting FLA LRA AMPACITY WIRESIZE FUSESIZE

SC 3 Ph Start HP Ea Curro Ea Ea Ea Circ1 Circ2 Circ1 Circ2 Circ1 eire 2

208230 XL 1788 1040 (4) 70 (4) 380 252 - 250 - 400 -45 208230 YO (1) 50 1788 347 (4) 70 (4) 380 252 - 250 - 400 -

460 XL 737 422 (4) 35 (4) 190 106 - 2 - 175 -460 YO 737 141 (4) 35 (4) 190 106 - 2 - 175 -

208230 XL 2051 1228 (4) 70 (4) 380 284 - 300 - 450 -55 208230 YO (1) 60 2051 409 (4) 70 (4) 380 284 - 300 - 450 -

460 XL 904 485 (4) 35 (4) 190 127 - 1 - 200 -460 YO 904 162 (4) 35 (4) 190 127 - 1 - 200 -

208230 XL 2083 1415 (6) 70 (6) 380 302 350 500 -70 208230 YO (1) 75 2083 472 (6) 70 (6) 380 302 350 500 -

460 XL 974 539 (6) 35 (6) 190 143 0 225 -460 YO 974 180 (6) 35 (6 190 143 0 225 -208 XL 1788 1040 (6) 70 (6) 380 266 224 300 0000 400 400 208 YO 1788 347 (6) 70 (6) 380 266 224 300 0000 400

90 230 XL (2) 50 1788 1040 (6) 70 (6) 380 266 224 400 I300 0000 400 400 230 YO 1788 347 (6) 70 (6) 380 266 224 300 0000 400 400 460 XL 737 422 (6) 35 (6) 190 187 - 000 - 250 460 YO 737 141 (6) 35 (6) 190 187 - =1000 - 250 208 XL 2051 1228 (8) 70 (8) 380 312 256 400 300 250 208 YO 2051 409 (8) 70 (8) 380 312 256 400 300 500

110 230 XL (2) 60 2051 1228 (8) 70 (8) 380 312 256 g I350 300 SOO 450 230 YO 2051 409 (8) 70 (8) 380 312 256 350 300 500 450 460 XL 914 485 (8) 35 (8) 190 231 - 0000 - 300 460 YO 904 162 (8) 35 (8) 190 231 - 0000 - 300 -

208 XL (1) 60 2051 1228 (8) 70 (8) 380 312 260 400 300 500 450(1) 75 2083 1415

208 YO (1) 60 2051 409 (8) 70 (8) 380 312 260 400 300 500 450(1) 75 2083 472

230 XL (1) 60 2051 1228 (8) 70 (8) 380 312 260 350 300 500 450(1) 75 2083 165125

230 YO (1) 60 2051 409 (8) 70 (8) 380 02 260 350 300 500 450 (1) 75 2083 472

460 XL (1) 60 904 485 (8) 35 (8) 190 240 - 250 - 300 -(1 75 974 539

460 YO (1) 60 904 162 (8) 35 (8) 190 240 - 250 - 300 -(1) 75 974 180

208 XL 2083 1415 (8) 70 (8) 380 316 260 400 300 500 450 208 YO 2083 472 (8) 70 (8) 380 316 260 400 300 500 450

135 230 XL (2) 75 2083 1415 (8) 70 (8) 380 316 260 400 300 500 450 I 230 YO 2083 472 (8) 70 (8) 380 316 260 400 300 500 450

460 XL 974 539 (8) 35 (8) 190 247 - 250 - 300 -460 YO 974 180 (8i 35 (8) 190 247 - 250 - 300 -

208 XL (2) SO 1788 1040 (10) 70 (10) 380 326 402 400 0000 500 500(1) 60 2051 1228

208 YO (2) 50 1788 347 (10) 70 (10) 380 326 402 400 0000 500 500(1 60 2051 409

230 XL (2) 50 1788 1040 (10) 70 (10) 380 326 402 400 0000 500 500 145 (1) 60 2011 1228

230 YO (2) 50 1788 347 (10) 70 (10) 380 326 402 400 0000 500 500(1) 60 2051 409

460 XL (2) 50 737 422 (10) 35 (10) 190 295 - 350 350 --(1) 60 904 485

460 YO (2) SO 731 141 10 (35) (10)190 295 - 350 350- -(1)60 904 162

208 XL 2051 1228 (10) 70 (10) 380 326 462 400 (2)250 500 600 208 YO 2051 409 (10) 70 (10) 380 326 462 400 (2)250 500 600

160 230 XL (3) 60 2051 1228 (10) 70 (10) 380 326 462 400 (2)250 500 230 YO 2051 409 (10) 70 (10) 380 326 462 600400 (2)250 500 600 460 XL 904 485 (10) 35 (10) 190 329 - 400 - 400 460 YO 904 167 (10) 35 (10) 190 329 - 400 - 400 - I

NOTES 1 XL Across the LineYOStarDelta 2 RLA Rated LoadAmps(ratedin accordance withARI Standard 590) LRA LockedRotorAmps 3 Wire Size Amps equal125of the ratedloadampsfor the largestmotorin thecircuitplus100of the ratedloadampsfor all othermotorsin the circuit per

NEC 4 Wire size based on copperconductorswith75C insulation perNECTable310-16 Terminal block lugs are sizedaccordingly Use of oversize wiringmay

not lit in terminal blocks 5 Maximumfuse size is basedon 175to 225of the ratedloadampsfor the largestmotorin the circuitplus 100of the rated loadampsfora othermotors

in the circuit per NEC VOLTAGE TOLERANCES 208V-230V min 187VMax 253V

480V Min414V Max506V

I

18

ELECTRICAL DATA Volts Type COMPRESSORModel FAN MOTORS MINCIRCUIT RECOMMENDED MAXIMUM 60 Hz of Oty RLA Starting FLAACWC LRA AMPACITY WIRESIZE FUSE SIZE 3 Ph Start Curro EaSC HP Ea Ea Ea Cire1 Cire2 Cire1 Cire2 Cire1 Cire2 208 XL 2051(1) 60 1228 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 1415 208 YO (1) 60 2051 409 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 472 230 XL (1) 60 2051 1228 (12)70 (12) 380 341 469 500 (2) 250 500 600

12 75 2083 1415185 230 YO (1) 60 2051 409 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 472 460 XL 485 (12) 35 (1) 60 904 (12) 190 352 500 400- - -

(2) 75 974 539 460 YO (1) 60 904 162 (12) 5(12)19 352 500 400- - -

(2) 75 974 180 208 XL 2083 1415 (12) 70 (12) 380 345 469 500 500(2) 250 600

472208 YO 2083 (12) 70 345(12) 380 469 500 (2) 250 500 600 230 XL (3) 75 2083 1415 (12) 70 345(12) 380 469 500 (2) 250 500 600200 230 YO 2083 472 (12) 70 (12) 190 345 469 500 500(2) 250 600 460 XL 539974 (12) 35 (12) 190 359 - 450500 - -

180 1(12) 35 460 YO 974 (12) 190 359 450 -500- -2051 1228208 XL (12) 70 504(12) 380 504 (2) 250 (2) 250 700 700

208 YO 2051 409 (12) 70 (12) 380 504 504 (2) 250 700(2) 250 700 (4) 60 2051 1228 (12) 70 230 XL (12) 380 504 504 (2) 250 (2) 250 700 700215

YO 2051 409230 (12) 70 (12) 380 504 504 (2) 250 (2) 250 700 700 460 904 485 (12) 35 XL (12) 190 225 225 0000 0000 300 300

(12) 35 460 YO 904 162 (12) 190 300225 225 0000 0000 300 2051 1228208 XL (2) 60 (14) 70 (14) 380 504 525 (2250 700 700(2)300

(2) 75 2083 1415 2051 409 (14) 70 700 700208 YO (2) 60 (14) 380 504 525 (2) 250 (2)300

(2) 75 2083 472240 700XL (2) 60 2051 1228 (14) 70 (14) 380 504 525 (2)250 (2)300 700230

(2) 75 2083 1415 2011230 YO (2) 60 409 (14) 70 (14) 380 504 525 (2) 250 (2)300 700 700

(2) 75 2083 472 300460 XL (2) 60 904 485 (14) 35 (14) 190 225 248 0000 250 300

12 75 974 539 904 162 250 300 300460 YO (2) 60 (14) 35 (14) 190 225 248 410

(2) 75 974 180 2083 1415 (2)300 700 700XL (16) 70 (16) 380 525 525 (2)300208 2083 1415 (2)300 700 700208 YO (16) 70 525 525 (2)300(16) 380

700 7002083 1415 (16) 70 (2300230 XL (16) 380 525 525 (2300 700 700(2300(4) 75 2083 472 (16) 70 (16) 380 525 525 (2300230 XL265

300250 300974 539 (16) 35 248 248 250XL (16) 380 460 (16) 35 300 300974 (16 380 248 250 250YO 539 248460

NOTES 1 XL Across the Line YO Star Delta 2 RLA Rated Load Amps (rated in accordance with ARI Standard 590) LRA Locked Rotor Amps 3 Wire Size Amps equal 125 of the rated load amps for the largest motor in the circuit plus 100 of the rated load amps for all other motors in the circuit per

NEC 4 Wire size based on copper conductors with 75degG insulation per NEG Table 310-16 Terminal block lugs are sized accordingly Use of oversize wiring may

not fit in terminal blocks 5 Maximum fuse size is based on 175 to 225 of the rated load amps for the largest motor in the circuit plus 100 of the rated load amps for a other motors

in the circuit per NEG VOLTAGE TOLERANCES 208V-230V min 187V Max 253V

480V Min414V Max506V

19

0

(Wd~) 3lV~ M011 ~31VM

006 009 00 OOt OOl OS L 00 L os 0 Ot

V D m (I) (I)

c D m c D o V

- m m -t o

~

~ m D-

aoao 3~nSS3~d ~3100~

APPLICATION DATA

POINT LOADING

ArMi I 1 5 1

ACWC 45 THRU 10 SC

COMPRESSOR CONDENSER SECTION SECTION

_ 2 4 bull 1

bull CA

J

Model Dimensions Size A B C D 45 91 - - -55 91 - - -70 145 - - -90 145 - - -110 60 40 160 -125 60 40 160 -135 60 40 160 -145 138 74 107 -160 13830 74 107 -185 138 129 107 -200 138 129 107 -215 106 82 106 80 240 106 82 134 107 265 133 110 134 107

1310

1310

~

1

1310

2

ACwe 110 THRU 200 Ie

COMPREIlOfl CONDENSER SECTION IECnoN

4 -

5Imiddot

ACWC 2t5 THRU 215 SC

Model Loadlnu (LBS) Size 1amp2 3amp4 5amp6 7amp8 9 amp10 45 585 765 550 - -55 705 810 635 - -70 660 890 700 - -90 1025 1500 1175 - -110 1195 635 1525 995 -125 1255 690 1835 1115 -135 1255 665 1880 1105 -145 1330 2380 2160 1450 -160 1330 2440 2280 1515 -185 1235 2575 2980 1360 -200 1275 2635 3020 1380 -215 1010 2270 2590 2240 840 240 1115 2550 2870 2715 1125 265 1380 2980 3515 2750 1175

11

II i middot 2 4 lIf 11 to L

21

TROUBLESHOOTING GUIDE

CHILLER UNIT WILL NOT START POSSIBLE CAUSE REMEDY 1 Power off 1 Check main disconnect switch

2 Main line open 2 Check main fuses

3 Incorrect wiring 3 Check the wiring diagram

4 Loose terminals 4 Tiqhten all terminals

5 Control circuit open 5 Check phase loss monitor flow switch circuit breakers temperature control low ambient thermostat low temperature thermostat remote switch etc

6 Time delay 6 Wait

COMPRESSOR HUMS BUT DOES NOT START

POSSIBLE CAUSE REMEDY

1 Low voltage 1a Check at service and unit for loss

b Consult power company

COMPRESSOR CUTS OUT ON LOW PRESSURE SAFETY CONTROL POSSIBLE CAUSE REMEDY 1 Refrigerant shortage 1 Check for leaks -- add refrigerant 2 Restriction in liquid line 2a Plugged strainer - dean or replace

b Liquid line valve partially closed - open valves fully c Expansion valve clogged or inoperative - clean or replace as

required d Solenoid valve partially open - clean or replace as required

3 Low water flow thru cooler 3 Check water flow thru cooler and correct as required

COMPRESSOR CYCLES ON HIGH PRESSURE CONTROL POSSIBLE CAUSE REMEDY 1 Compressor discharge valve partially closed 1 Open valve fully 2 Non-condensible gases in system 2 Operate condenser fans with compressors off If condenser

pressure exceeds saturated pressure corresponding to condenser entering air temperature then purge air from discharge line

3 Overcharge of R-22 3 Purge system while in operation until head pressure reaches a normal level

4 Dirty condenser 4 Clean the condenser 5 Compressor discharge check valve not operating properly 5 Replace if necessary 6 Fans not running 6 Check pressure control setting

CAUSES AND PREVENTION OF FREEZE-UP CAUSES PREVENTION 1 Improper charging 1 Charge per manufacturers recommendation

2 Improperly set safety time delay 2 Check the safety time delay low pressure control for proper setting at the beginning of each season

3 Improper chilled water circulation 3 Use an ample sized cleanable strainer in the chilled water circuit Make certain the strainer is clean to insure full flow and velocity of

chilled water It may sometimes be necessary to treat the water to prevent formation of deposits

4 Not draining for winter shutdown 4 When the system is shut down for the winter remove the drain

plugs and drain the cooler Blowout any remaining water with air

5 Improper pump shutdown 5 Make sure chiller barrel heater is working and flow switch is installed per wiring diagrams

6 Low ambient during air conditioning season 6 Make sure chiller barrel heater is working

NOTE If the ambient temperature is below 32degF freezing can be completely prevented by one of two methods

1 Drain all water from the equipment 2 Add antifreeze to the water

22

START-UP CHECK LIST

Unit Model No

Setting unit

Wiring

Piping

Alignment

Before Start-Up

After Start-Up

Yes No a Vibration isolator used

b Spring isolator adjusted for equal height c If rubber-in-shear isolators are used is unit leveled by shimming

a Power wiring complete

b Control wiring complete c Electric service adequate for load

d Power source voltage correct for motor(s) used

e Motor circuit has proper size fusetrons f System wired per diagram

g All lead connections tight h Wiring complies with local codes i Flow switch operation

a Piping complies with applicable codes b External piping independently supported c Chilled water lines insulated

a All belts adjusted and checked for tension b All pulleys checked and adjusted for proper pitch tightness and

alignment

a Open compressor discharge service valve b Open liquid valve(s) c Open suction and discharge valves to pressure gauges (if supplied) d Check rotation of all fan motors e Start auxiliary equipment (pumps fans etc) f Is crankcase heater operating Operate 24 hours prior to unit startup g Check the compressor oil level through the crankcase sight glass The oil

level should be to the top of the glass If the level is low add oil in accordance with the directions in the maintenance instruction

h Check all control settings as specified in Table 1 I Air purged from chilled water system

a Check high pressure control b Check oil temperature safety switch c Check and adjust low pressure or temperature freeze control d Check and adjust operating thermostat e Check and adjust low pressure operating control f Check and adjust expansion valve superheat g Check and adjust capacity control thermostat

23

OPERATING DATA CHILLER Voltage L-1 L-2 L-3 _ Pressure Gauge Readings 1 Suction psig 1 Discharge psig 2 Suction psig 2 Discharge _ psig 3 Suction psig 3 Discharge psig 4 Suction psig 4 Discharge _ psig High pressure switch setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-in) psig psig (Out) 4 (Cut-In) psig psig (Out) Checked Setting - Yes - No (each circuit) Low Pressure Switch Setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-In) psig psig (Out) 4 (Cut-in) psig psig (Out) Checked Setting -Yes -No (each circuit) 1 Oil Temperature Safety Switch Cut Out 2 Oil Temperature Safety Switch Cut Out 3 Oil Temperature Safety Switch Cut Out 4 Oil Temperature Safety Switch Cut Out If Star-Delta start time delay is seconds Temperature of air entering condenser F Temperature of air leaving condenser of Temperature of chilled water entering chiller OF Temperature of water (chilled) leaving chiller F Chilled water pressure entering chiller psig Chilled water pressure leaving chiller psig

MAINTENANCE Good maintenance practice will prolong the chiller life and will reduce the Ask of system breakdown and expensive service calls

A weekly check of the ACWC-SD unit requires only a few minutes and will prove beneficial in insuring long trouble free operation

WEEKLY CHECKS- with unit in operation for at least four hours 1) Check compressor oil level - At least above 12 of sight glass 2) Record suction and discharge pressures

Typical Condition R22 Ambient 95degF Return water 55degF Leaving water 45degF Suction 62 psig Discharge 270 psig

3) Record ambient temperature 4) Check liquid sight glass

Make sure liquid is clear - no bubbles 5) Check that all fans are running 6) Check entering face of condenser coil for cleanliness 7) Record voltage at unit

All of the above can be performed by building maintenance personnel If oil levels are low or any of the above checked items are questionable consult a qualified serviceman

At least once a year a qualified serviceman should check unit oil levels superheat and control operation

DUNHAM-BUSH USA

P l) bull 130 xUtUC t01 Bmgess RO~ Harrisonburg VA 22801 Phone (540) 434-0711 FAX (540) 434-~ 2118

wvvwdunham-bushcom Form No 6184

Page 13: ACWC-SD - · PDF fileACWC-SD • Screw . Type • • • Air-Cooled Packaged Chillers •• Installation, Operation, and •• • Maintenance Manual • • • •• DESCRIPTION

i 4

_

a

~FirI1 u~III - I I

~ 1I

00000 -

I=II~I~~~~raquoIIIItIII~ampI~

as ooz nJ4l sv ~ siapow ~NI~IM lO~lNOgt TVgtldAl

bullbull bullbull

bullbull

~

jgt

lpoundIt

ND

II

co

----

----

----

----

----

----

----

----

-

r-~-middot--=-~~

~

bull a

~

at~04

5

---

~1I

A

~n

bullbullmiddot-shy

wo

_-

bull

lIt

C-

I C

Cf

aC

TO

Ic

ow

n

CC

eM

ca

~C

M

OD

IAI

CI

T-

CO

IITA

CT

oa

bullbull

CMCU

rT I

ItIM

IA

co-l

to

c-c

VIT

C

I

rr

c

AfE

bull r~----Ef1

POW

I

III

IQ

W

Q

tIL

UT

I1I

U__~

J

COt

I

LD

W M

lMtr

f nc

IIO

ff

0

N

LO

W

C

OIIT

INM

I I

CO

M

US

ON

C

NC

UIT

II

II

-~

_T

shy

C

O

NU

SO

II

CIN

CU

IT Z

II

D[TA~

-

ST

AN

D(~TA

IT

AII

T

0

u III

r

amp

II

-~

If

10

MA

MI

eN

talI

Tco_

~

STA

N D[~TA

ST

AII

T

~

CIS

-I

LA

~ 1-4

nmiddot

00

-

-II

1t1S

-1 aw

o fI

fl

U- I -~ Ci

Pi=

i

t

shy

~

iii

i

iii=

ii

-

-shyiii

ClL

n

TU

U

LOt

e

bull It

lLA

Yn

C

AM

Im

CIII

IID

L bull

CU

_C

Abull

fl

lUY

_f

tMO

ea

UY

middotIO

CI

lO

Ll

t

NIU

_L

N

CO

WU

UO

ItC

U

llT

l bullbull 0

1middot

lit

TMC

MI0

8TA

T tc

_lt

CIl

it

11

II

_

middotLO

W

TII

IfN

T

UIlI

C

nll

-

D-C

UlT

QIIU

tW

n-T

PII

IU

LIO

MI-

AC

TC

Ntf

Wi

MI

II

II

tY

middotCM

OO

C

LOW

HIe U

(O

Uf

lIl_

L

OA

M

1OtI

1tO

lD

CO

OA

CM

UtT

1M

C

lIY

Dl

NC

Afi

ll ea

-tU

lT 1

ItUbullbull

lI

oo

ww

lItt

lffc

e O

Un

n

cT

IlG

I

Ie-

~U

IIIC

CIV

P

1T

1lt

C

bullbull

Off

AT

tw

ebullbull

ampOW

IC

IUT

~-

4ti

iT

~

co

ww

O

UfU

T

DITA~

A

ITA

A

OEL

TA

IT

AJI

IT

co

rn~

e

I

1amp

ItmiddotI

~ bull

I I

I

I r

~

bull Iamp

II

I ~

I-

oJ

II I

IrIf

I I I I

s~

o

-I I

ltDc

() raquo

L 10

V

i

()

~O

to

U

lZr0

t2

llJ

IL

C6

J=

_J

~-1

f

II

c 0

II

N

ge

cno

c-

II

Z

Ggt

If IO

IC

IIY

II

IIR

III

IJt

T H

llII

A

Il C

Olaquof

U

TMIbull

~LDM

fI

lAR

PM

Iamp L

Oll

lTV

ii

iLii

Uii

ii

~

U3

I iL

iii=

i

Uii

u

i

O

(no)

T

bull II

1

IOA~

bullr

~ I

[gtO(]O

~ i I Ii i 2 ~ ~ ~ i a bull il 2 ~

iiibullbullbull

~ I ~ I I I ~~ =l ~ iI I ~ I I I It I 1111 amp ~~

as ooz nJ4l SP~ SlapoUII ~NI~IM 10U1NOl lVlldAl

-------

---

TYPICAL POWER WIRING Models 45 thru 70 SC

----

rYl31I01 I

-Ii --ti-

_ I ~_-

~ lniJ -

LIIbullbullbullbull PC _ amp-II _--- ~

TYPICAL POWER WIRING Models 90 thru 135 SC

- --- _ Tt

~rfh c~

tP ~

_III ~

I r-- ~- IIlJ

bull - MIl Mf __ bull Ie_~--~ _shy- shy16

---

----------

TYPICAL POWER WIRING Models 145 thru 200 SC

_ --1a1 IIUrI

middotrFti~v_ bull I

i~i ~~ TaII IIOMLI ~tN T 100 WTIOII 011 lilOOCL a

~ t1

tI bullbullbull

L

i I r-~

I r

~ ~ ~ III

2 ~ ~ ~l

- ~IlD I hJOHr eo teO acshyt CmiddotClM ~ CIKUr1 --

TYPICAL POWER WIRING Models 215 thru 265 SC

ItUU 1D Wll1U1I fIa -rMI

rt-h I -au 11 1_ i r~ rt-f

-i rn f1 ft fi i- llil bullbull c~ I bull c =

~~~ ~i~-~

~~m

~~~CI1 R~~ ~ ~~ ~llAi4I

luv~ bull ~uf LL~~-

~Mfl l~t IrMiA

a I III nII I bull it d

~-t--J I Lll-l~j ~nL4111 WlJj== lit-

I bullbullbull I

UGEND

~

~l OJ

- c~

~~~---

~)~middotI

I

L _~~~ L _I__~_J I ~ (11_1 ~ H~ CUlTMIt tffC_) Ll N

-r_ 0 1ItCIIIl0AI lllQUlllCo as -0- bull bullbull fI PC 110 lNJCllII a Olil1100pound1 II 111 el 1101 ItCOU_ 011 IIOOIL140

I 011 CI-( H[ (0110 (fMCun ubullbull --- l(lD IMbullbull Ntlf 110 e414-7

--CTOttbullbull

2

17

ELECTRICAL DATA Model Volts Type COMPRESSOR FAN MOTORS MIN CIRCUIT RECOMMENDED MAXIMUM ACWC 60 Hz of Qty RLA Starting FLA LRA AMPACITY WIRESIZE FUSESIZE

SC 3 Ph Start HP Ea Curro Ea Ea Ea Circ1 Circ2 Circ1 Circ2 Circ1 eire 2

208230 XL 1788 1040 (4) 70 (4) 380 252 - 250 - 400 -45 208230 YO (1) 50 1788 347 (4) 70 (4) 380 252 - 250 - 400 -

460 XL 737 422 (4) 35 (4) 190 106 - 2 - 175 -460 YO 737 141 (4) 35 (4) 190 106 - 2 - 175 -

208230 XL 2051 1228 (4) 70 (4) 380 284 - 300 - 450 -55 208230 YO (1) 60 2051 409 (4) 70 (4) 380 284 - 300 - 450 -

460 XL 904 485 (4) 35 (4) 190 127 - 1 - 200 -460 YO 904 162 (4) 35 (4) 190 127 - 1 - 200 -

208230 XL 2083 1415 (6) 70 (6) 380 302 350 500 -70 208230 YO (1) 75 2083 472 (6) 70 (6) 380 302 350 500 -

460 XL 974 539 (6) 35 (6) 190 143 0 225 -460 YO 974 180 (6) 35 (6 190 143 0 225 -208 XL 1788 1040 (6) 70 (6) 380 266 224 300 0000 400 400 208 YO 1788 347 (6) 70 (6) 380 266 224 300 0000 400

90 230 XL (2) 50 1788 1040 (6) 70 (6) 380 266 224 400 I300 0000 400 400 230 YO 1788 347 (6) 70 (6) 380 266 224 300 0000 400 400 460 XL 737 422 (6) 35 (6) 190 187 - 000 - 250 460 YO 737 141 (6) 35 (6) 190 187 - =1000 - 250 208 XL 2051 1228 (8) 70 (8) 380 312 256 400 300 250 208 YO 2051 409 (8) 70 (8) 380 312 256 400 300 500

110 230 XL (2) 60 2051 1228 (8) 70 (8) 380 312 256 g I350 300 SOO 450 230 YO 2051 409 (8) 70 (8) 380 312 256 350 300 500 450 460 XL 914 485 (8) 35 (8) 190 231 - 0000 - 300 460 YO 904 162 (8) 35 (8) 190 231 - 0000 - 300 -

208 XL (1) 60 2051 1228 (8) 70 (8) 380 312 260 400 300 500 450(1) 75 2083 1415

208 YO (1) 60 2051 409 (8) 70 (8) 380 312 260 400 300 500 450(1) 75 2083 472

230 XL (1) 60 2051 1228 (8) 70 (8) 380 312 260 350 300 500 450(1) 75 2083 165125

230 YO (1) 60 2051 409 (8) 70 (8) 380 02 260 350 300 500 450 (1) 75 2083 472

460 XL (1) 60 904 485 (8) 35 (8) 190 240 - 250 - 300 -(1 75 974 539

460 YO (1) 60 904 162 (8) 35 (8) 190 240 - 250 - 300 -(1) 75 974 180

208 XL 2083 1415 (8) 70 (8) 380 316 260 400 300 500 450 208 YO 2083 472 (8) 70 (8) 380 316 260 400 300 500 450

135 230 XL (2) 75 2083 1415 (8) 70 (8) 380 316 260 400 300 500 450 I 230 YO 2083 472 (8) 70 (8) 380 316 260 400 300 500 450

460 XL 974 539 (8) 35 (8) 190 247 - 250 - 300 -460 YO 974 180 (8i 35 (8) 190 247 - 250 - 300 -

208 XL (2) SO 1788 1040 (10) 70 (10) 380 326 402 400 0000 500 500(1) 60 2051 1228

208 YO (2) 50 1788 347 (10) 70 (10) 380 326 402 400 0000 500 500(1 60 2051 409

230 XL (2) 50 1788 1040 (10) 70 (10) 380 326 402 400 0000 500 500 145 (1) 60 2011 1228

230 YO (2) 50 1788 347 (10) 70 (10) 380 326 402 400 0000 500 500(1) 60 2051 409

460 XL (2) 50 737 422 (10) 35 (10) 190 295 - 350 350 --(1) 60 904 485

460 YO (2) SO 731 141 10 (35) (10)190 295 - 350 350- -(1)60 904 162

208 XL 2051 1228 (10) 70 (10) 380 326 462 400 (2)250 500 600 208 YO 2051 409 (10) 70 (10) 380 326 462 400 (2)250 500 600

160 230 XL (3) 60 2051 1228 (10) 70 (10) 380 326 462 400 (2)250 500 230 YO 2051 409 (10) 70 (10) 380 326 462 600400 (2)250 500 600 460 XL 904 485 (10) 35 (10) 190 329 - 400 - 400 460 YO 904 167 (10) 35 (10) 190 329 - 400 - 400 - I

NOTES 1 XL Across the LineYOStarDelta 2 RLA Rated LoadAmps(ratedin accordance withARI Standard 590) LRA LockedRotorAmps 3 Wire Size Amps equal125of the ratedloadampsfor the largestmotorin thecircuitplus100of the ratedloadampsfor all othermotorsin the circuit per

NEC 4 Wire size based on copperconductorswith75C insulation perNECTable310-16 Terminal block lugs are sizedaccordingly Use of oversize wiringmay

not lit in terminal blocks 5 Maximumfuse size is basedon 175to 225of the ratedloadampsfor the largestmotorin the circuitplus 100of the rated loadampsfora othermotors

in the circuit per NEC VOLTAGE TOLERANCES 208V-230V min 187VMax 253V

480V Min414V Max506V

I

18

ELECTRICAL DATA Volts Type COMPRESSORModel FAN MOTORS MINCIRCUIT RECOMMENDED MAXIMUM 60 Hz of Oty RLA Starting FLAACWC LRA AMPACITY WIRESIZE FUSE SIZE 3 Ph Start Curro EaSC HP Ea Ea Ea Cire1 Cire2 Cire1 Cire2 Cire1 Cire2 208 XL 2051(1) 60 1228 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 1415 208 YO (1) 60 2051 409 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 472 230 XL (1) 60 2051 1228 (12)70 (12) 380 341 469 500 (2) 250 500 600

12 75 2083 1415185 230 YO (1) 60 2051 409 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 472 460 XL 485 (12) 35 (1) 60 904 (12) 190 352 500 400- - -

(2) 75 974 539 460 YO (1) 60 904 162 (12) 5(12)19 352 500 400- - -

(2) 75 974 180 208 XL 2083 1415 (12) 70 (12) 380 345 469 500 500(2) 250 600

472208 YO 2083 (12) 70 345(12) 380 469 500 (2) 250 500 600 230 XL (3) 75 2083 1415 (12) 70 345(12) 380 469 500 (2) 250 500 600200 230 YO 2083 472 (12) 70 (12) 190 345 469 500 500(2) 250 600 460 XL 539974 (12) 35 (12) 190 359 - 450500 - -

180 1(12) 35 460 YO 974 (12) 190 359 450 -500- -2051 1228208 XL (12) 70 504(12) 380 504 (2) 250 (2) 250 700 700

208 YO 2051 409 (12) 70 (12) 380 504 504 (2) 250 700(2) 250 700 (4) 60 2051 1228 (12) 70 230 XL (12) 380 504 504 (2) 250 (2) 250 700 700215

YO 2051 409230 (12) 70 (12) 380 504 504 (2) 250 (2) 250 700 700 460 904 485 (12) 35 XL (12) 190 225 225 0000 0000 300 300

(12) 35 460 YO 904 162 (12) 190 300225 225 0000 0000 300 2051 1228208 XL (2) 60 (14) 70 (14) 380 504 525 (2250 700 700(2)300

(2) 75 2083 1415 2051 409 (14) 70 700 700208 YO (2) 60 (14) 380 504 525 (2) 250 (2)300

(2) 75 2083 472240 700XL (2) 60 2051 1228 (14) 70 (14) 380 504 525 (2)250 (2)300 700230

(2) 75 2083 1415 2011230 YO (2) 60 409 (14) 70 (14) 380 504 525 (2) 250 (2)300 700 700

(2) 75 2083 472 300460 XL (2) 60 904 485 (14) 35 (14) 190 225 248 0000 250 300

12 75 974 539 904 162 250 300 300460 YO (2) 60 (14) 35 (14) 190 225 248 410

(2) 75 974 180 2083 1415 (2)300 700 700XL (16) 70 (16) 380 525 525 (2)300208 2083 1415 (2)300 700 700208 YO (16) 70 525 525 (2)300(16) 380

700 7002083 1415 (16) 70 (2300230 XL (16) 380 525 525 (2300 700 700(2300(4) 75 2083 472 (16) 70 (16) 380 525 525 (2300230 XL265

300250 300974 539 (16) 35 248 248 250XL (16) 380 460 (16) 35 300 300974 (16 380 248 250 250YO 539 248460

NOTES 1 XL Across the Line YO Star Delta 2 RLA Rated Load Amps (rated in accordance with ARI Standard 590) LRA Locked Rotor Amps 3 Wire Size Amps equal 125 of the rated load amps for the largest motor in the circuit plus 100 of the rated load amps for all other motors in the circuit per

NEC 4 Wire size based on copper conductors with 75degG insulation per NEG Table 310-16 Terminal block lugs are sized accordingly Use of oversize wiring may

not fit in terminal blocks 5 Maximum fuse size is based on 175 to 225 of the rated load amps for the largest motor in the circuit plus 100 of the rated load amps for a other motors

in the circuit per NEG VOLTAGE TOLERANCES 208V-230V min 187V Max 253V

480V Min414V Max506V

19

0

(Wd~) 3lV~ M011 ~31VM

006 009 00 OOt OOl OS L 00 L os 0 Ot

V D m (I) (I)

c D m c D o V

- m m -t o

~

~ m D-

aoao 3~nSS3~d ~3100~

APPLICATION DATA

POINT LOADING

ArMi I 1 5 1

ACWC 45 THRU 10 SC

COMPRESSOR CONDENSER SECTION SECTION

_ 2 4 bull 1

bull CA

J

Model Dimensions Size A B C D 45 91 - - -55 91 - - -70 145 - - -90 145 - - -110 60 40 160 -125 60 40 160 -135 60 40 160 -145 138 74 107 -160 13830 74 107 -185 138 129 107 -200 138 129 107 -215 106 82 106 80 240 106 82 134 107 265 133 110 134 107

1310

1310

~

1

1310

2

ACwe 110 THRU 200 Ie

COMPREIlOfl CONDENSER SECTION IECnoN

4 -

5Imiddot

ACWC 2t5 THRU 215 SC

Model Loadlnu (LBS) Size 1amp2 3amp4 5amp6 7amp8 9 amp10 45 585 765 550 - -55 705 810 635 - -70 660 890 700 - -90 1025 1500 1175 - -110 1195 635 1525 995 -125 1255 690 1835 1115 -135 1255 665 1880 1105 -145 1330 2380 2160 1450 -160 1330 2440 2280 1515 -185 1235 2575 2980 1360 -200 1275 2635 3020 1380 -215 1010 2270 2590 2240 840 240 1115 2550 2870 2715 1125 265 1380 2980 3515 2750 1175

11

II i middot 2 4 lIf 11 to L

21

TROUBLESHOOTING GUIDE

CHILLER UNIT WILL NOT START POSSIBLE CAUSE REMEDY 1 Power off 1 Check main disconnect switch

2 Main line open 2 Check main fuses

3 Incorrect wiring 3 Check the wiring diagram

4 Loose terminals 4 Tiqhten all terminals

5 Control circuit open 5 Check phase loss monitor flow switch circuit breakers temperature control low ambient thermostat low temperature thermostat remote switch etc

6 Time delay 6 Wait

COMPRESSOR HUMS BUT DOES NOT START

POSSIBLE CAUSE REMEDY

1 Low voltage 1a Check at service and unit for loss

b Consult power company

COMPRESSOR CUTS OUT ON LOW PRESSURE SAFETY CONTROL POSSIBLE CAUSE REMEDY 1 Refrigerant shortage 1 Check for leaks -- add refrigerant 2 Restriction in liquid line 2a Plugged strainer - dean or replace

b Liquid line valve partially closed - open valves fully c Expansion valve clogged or inoperative - clean or replace as

required d Solenoid valve partially open - clean or replace as required

3 Low water flow thru cooler 3 Check water flow thru cooler and correct as required

COMPRESSOR CYCLES ON HIGH PRESSURE CONTROL POSSIBLE CAUSE REMEDY 1 Compressor discharge valve partially closed 1 Open valve fully 2 Non-condensible gases in system 2 Operate condenser fans with compressors off If condenser

pressure exceeds saturated pressure corresponding to condenser entering air temperature then purge air from discharge line

3 Overcharge of R-22 3 Purge system while in operation until head pressure reaches a normal level

4 Dirty condenser 4 Clean the condenser 5 Compressor discharge check valve not operating properly 5 Replace if necessary 6 Fans not running 6 Check pressure control setting

CAUSES AND PREVENTION OF FREEZE-UP CAUSES PREVENTION 1 Improper charging 1 Charge per manufacturers recommendation

2 Improperly set safety time delay 2 Check the safety time delay low pressure control for proper setting at the beginning of each season

3 Improper chilled water circulation 3 Use an ample sized cleanable strainer in the chilled water circuit Make certain the strainer is clean to insure full flow and velocity of

chilled water It may sometimes be necessary to treat the water to prevent formation of deposits

4 Not draining for winter shutdown 4 When the system is shut down for the winter remove the drain

plugs and drain the cooler Blowout any remaining water with air

5 Improper pump shutdown 5 Make sure chiller barrel heater is working and flow switch is installed per wiring diagrams

6 Low ambient during air conditioning season 6 Make sure chiller barrel heater is working

NOTE If the ambient temperature is below 32degF freezing can be completely prevented by one of two methods

1 Drain all water from the equipment 2 Add antifreeze to the water

22

START-UP CHECK LIST

Unit Model No

Setting unit

Wiring

Piping

Alignment

Before Start-Up

After Start-Up

Yes No a Vibration isolator used

b Spring isolator adjusted for equal height c If rubber-in-shear isolators are used is unit leveled by shimming

a Power wiring complete

b Control wiring complete c Electric service adequate for load

d Power source voltage correct for motor(s) used

e Motor circuit has proper size fusetrons f System wired per diagram

g All lead connections tight h Wiring complies with local codes i Flow switch operation

a Piping complies with applicable codes b External piping independently supported c Chilled water lines insulated

a All belts adjusted and checked for tension b All pulleys checked and adjusted for proper pitch tightness and

alignment

a Open compressor discharge service valve b Open liquid valve(s) c Open suction and discharge valves to pressure gauges (if supplied) d Check rotation of all fan motors e Start auxiliary equipment (pumps fans etc) f Is crankcase heater operating Operate 24 hours prior to unit startup g Check the compressor oil level through the crankcase sight glass The oil

level should be to the top of the glass If the level is low add oil in accordance with the directions in the maintenance instruction

h Check all control settings as specified in Table 1 I Air purged from chilled water system

a Check high pressure control b Check oil temperature safety switch c Check and adjust low pressure or temperature freeze control d Check and adjust operating thermostat e Check and adjust low pressure operating control f Check and adjust expansion valve superheat g Check and adjust capacity control thermostat

23

OPERATING DATA CHILLER Voltage L-1 L-2 L-3 _ Pressure Gauge Readings 1 Suction psig 1 Discharge psig 2 Suction psig 2 Discharge _ psig 3 Suction psig 3 Discharge psig 4 Suction psig 4 Discharge _ psig High pressure switch setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-in) psig psig (Out) 4 (Cut-In) psig psig (Out) Checked Setting - Yes - No (each circuit) Low Pressure Switch Setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-In) psig psig (Out) 4 (Cut-in) psig psig (Out) Checked Setting -Yes -No (each circuit) 1 Oil Temperature Safety Switch Cut Out 2 Oil Temperature Safety Switch Cut Out 3 Oil Temperature Safety Switch Cut Out 4 Oil Temperature Safety Switch Cut Out If Star-Delta start time delay is seconds Temperature of air entering condenser F Temperature of air leaving condenser of Temperature of chilled water entering chiller OF Temperature of water (chilled) leaving chiller F Chilled water pressure entering chiller psig Chilled water pressure leaving chiller psig

MAINTENANCE Good maintenance practice will prolong the chiller life and will reduce the Ask of system breakdown and expensive service calls

A weekly check of the ACWC-SD unit requires only a few minutes and will prove beneficial in insuring long trouble free operation

WEEKLY CHECKS- with unit in operation for at least four hours 1) Check compressor oil level - At least above 12 of sight glass 2) Record suction and discharge pressures

Typical Condition R22 Ambient 95degF Return water 55degF Leaving water 45degF Suction 62 psig Discharge 270 psig

3) Record ambient temperature 4) Check liquid sight glass

Make sure liquid is clear - no bubbles 5) Check that all fans are running 6) Check entering face of condenser coil for cleanliness 7) Record voltage at unit

All of the above can be performed by building maintenance personnel If oil levels are low or any of the above checked items are questionable consult a qualified serviceman

At least once a year a qualified serviceman should check unit oil levels superheat and control operation

DUNHAM-BUSH USA

P l) bull 130 xUtUC t01 Bmgess RO~ Harrisonburg VA 22801 Phone (540) 434-0711 FAX (540) 434-~ 2118

wvvwdunham-bushcom Form No 6184

Page 14: ACWC-SD - · PDF fileACWC-SD • Screw . Type • • • Air-Cooled Packaged Chillers •• Installation, Operation, and •• • Maintenance Manual • • • •• DESCRIPTION

bullbull bullbull

bullbull

~

jgt

lpoundIt

ND

II

co

----

----

----

----

----

----

----

----

-

r-~-middot--=-~~

~

bull a

~

at~04

5

---

~1I

A

~n

bullbullmiddot-shy

wo

_-

bull

lIt

C-

I C

Cf

aC

TO

Ic

ow

n

CC

eM

ca

~C

M

OD

IAI

CI

T-

CO

IITA

CT

oa

bullbull

CMCU

rT I

ItIM

IA

co-l

to

c-c

VIT

C

I

rr

c

AfE

bull r~----Ef1

POW

I

III

IQ

W

Q

tIL

UT

I1I

U__~

J

COt

I

LD

W M

lMtr

f nc

IIO

ff

0

N

LO

W

C

OIIT

INM

I I

CO

M

US

ON

C

NC

UIT

II

II

-~

_T

shy

C

O

NU

SO

II

CIN

CU

IT Z

II

D[TA~

-

ST

AN

D(~TA

IT

AII

T

0

u III

r

amp

II

-~

If

10

MA

MI

eN

talI

Tco_

~

STA

N D[~TA

ST

AII

T

~

CIS

-I

LA

~ 1-4

nmiddot

00

-

-II

1t1S

-1 aw

o fI

fl

U- I -~ Ci

Pi=

i

t

shy

~

iii

i

iii=

ii

-

-shyiii

ClL

n

TU

U

LOt

e

bull It

lLA

Yn

C

AM

Im

CIII

IID

L bull

CU

_C

Abull

fl

lUY

_f

tMO

ea

UY

middotIO

CI

lO

Ll

t

NIU

_L

N

CO

WU

UO

ItC

U

llT

l bullbull 0

1middot

lit

TMC

MI0

8TA

T tc

_lt

CIl

it

11

II

_

middotLO

W

TII

IfN

T

UIlI

C

nll

-

D-C

UlT

QIIU

tW

n-T

PII

IU

LIO

MI-

AC

TC

Ntf

Wi

MI

II

II

tY

middotCM

OO

C

LOW

HIe U

(O

Uf

lIl_

L

OA

M

1OtI

1tO

lD

CO

OA

CM

UtT

1M

C

lIY

Dl

NC

Afi

ll ea

-tU

lT 1

ItUbullbull

lI

oo

ww

lItt

lffc

e O

Un

n

cT

IlG

I

Ie-

~U

IIIC

CIV

P

1T

1lt

C

bullbull

Off

AT

tw

ebullbull

ampOW

IC

IUT

~-

4ti

iT

~

co

ww

O

UfU

T

DITA~

A

ITA

A

OEL

TA

IT

AJI

IT

co

rn~

e

I

1amp

ItmiddotI

~ bull

I I

I

I r

~

bull Iamp

II

I ~

I-

oJ

II I

IrIf

I I I I

s~

o

-I I

ltDc

() raquo

L 10

V

i

()

~O

to

U

lZr0

t2

llJ

IL

C6

J=

_J

~-1

f

II

c 0

II

N

ge

cno

c-

II

Z

Ggt

If IO

IC

IIY

II

IIR

III

IJt

T H

llII

A

Il C

Olaquof

U

TMIbull

~LDM

fI

lAR

PM

Iamp L

Oll

lTV

ii

iLii

Uii

ii

~

U3

I iL

iii=

i

Uii

u

i

O

(no)

T

bull II

1

IOA~

bullr

~ I

[gtO(]O

~ i I Ii i 2 ~ ~ ~ i a bull il 2 ~

iiibullbullbull

~ I ~ I I I ~~ =l ~ iI I ~ I I I It I 1111 amp ~~

as ooz nJ4l SP~ SlapoUII ~NI~IM 10U1NOl lVlldAl

-------

---

TYPICAL POWER WIRING Models 45 thru 70 SC

----

rYl31I01 I

-Ii --ti-

_ I ~_-

~ lniJ -

LIIbullbullbullbull PC _ amp-II _--- ~

TYPICAL POWER WIRING Models 90 thru 135 SC

- --- _ Tt

~rfh c~

tP ~

_III ~

I r-- ~- IIlJ

bull - MIl Mf __ bull Ie_~--~ _shy- shy16

---

----------

TYPICAL POWER WIRING Models 145 thru 200 SC

_ --1a1 IIUrI

middotrFti~v_ bull I

i~i ~~ TaII IIOMLI ~tN T 100 WTIOII 011 lilOOCL a

~ t1

tI bullbullbull

L

i I r-~

I r

~ ~ ~ III

2 ~ ~ ~l

- ~IlD I hJOHr eo teO acshyt CmiddotClM ~ CIKUr1 --

TYPICAL POWER WIRING Models 215 thru 265 SC

ItUU 1D Wll1U1I fIa -rMI

rt-h I -au 11 1_ i r~ rt-f

-i rn f1 ft fi i- llil bullbull c~ I bull c =

~~~ ~i~-~

~~m

~~~CI1 R~~ ~ ~~ ~llAi4I

luv~ bull ~uf LL~~-

~Mfl l~t IrMiA

a I III nII I bull it d

~-t--J I Lll-l~j ~nL4111 WlJj== lit-

I bullbullbull I

UGEND

~

~l OJ

- c~

~~~---

~)~middotI

I

L _~~~ L _I__~_J I ~ (11_1 ~ H~ CUlTMIt tffC_) Ll N

-r_ 0 1ItCIIIl0AI lllQUlllCo as -0- bull bullbull fI PC 110 lNJCllII a Olil1100pound1 II 111 el 1101 ItCOU_ 011 IIOOIL140

I 011 CI-( H[ (0110 (fMCun ubullbull --- l(lD IMbullbull Ntlf 110 e414-7

--CTOttbullbull

2

17

ELECTRICAL DATA Model Volts Type COMPRESSOR FAN MOTORS MIN CIRCUIT RECOMMENDED MAXIMUM ACWC 60 Hz of Qty RLA Starting FLA LRA AMPACITY WIRESIZE FUSESIZE

SC 3 Ph Start HP Ea Curro Ea Ea Ea Circ1 Circ2 Circ1 Circ2 Circ1 eire 2

208230 XL 1788 1040 (4) 70 (4) 380 252 - 250 - 400 -45 208230 YO (1) 50 1788 347 (4) 70 (4) 380 252 - 250 - 400 -

460 XL 737 422 (4) 35 (4) 190 106 - 2 - 175 -460 YO 737 141 (4) 35 (4) 190 106 - 2 - 175 -

208230 XL 2051 1228 (4) 70 (4) 380 284 - 300 - 450 -55 208230 YO (1) 60 2051 409 (4) 70 (4) 380 284 - 300 - 450 -

460 XL 904 485 (4) 35 (4) 190 127 - 1 - 200 -460 YO 904 162 (4) 35 (4) 190 127 - 1 - 200 -

208230 XL 2083 1415 (6) 70 (6) 380 302 350 500 -70 208230 YO (1) 75 2083 472 (6) 70 (6) 380 302 350 500 -

460 XL 974 539 (6) 35 (6) 190 143 0 225 -460 YO 974 180 (6) 35 (6 190 143 0 225 -208 XL 1788 1040 (6) 70 (6) 380 266 224 300 0000 400 400 208 YO 1788 347 (6) 70 (6) 380 266 224 300 0000 400

90 230 XL (2) 50 1788 1040 (6) 70 (6) 380 266 224 400 I300 0000 400 400 230 YO 1788 347 (6) 70 (6) 380 266 224 300 0000 400 400 460 XL 737 422 (6) 35 (6) 190 187 - 000 - 250 460 YO 737 141 (6) 35 (6) 190 187 - =1000 - 250 208 XL 2051 1228 (8) 70 (8) 380 312 256 400 300 250 208 YO 2051 409 (8) 70 (8) 380 312 256 400 300 500

110 230 XL (2) 60 2051 1228 (8) 70 (8) 380 312 256 g I350 300 SOO 450 230 YO 2051 409 (8) 70 (8) 380 312 256 350 300 500 450 460 XL 914 485 (8) 35 (8) 190 231 - 0000 - 300 460 YO 904 162 (8) 35 (8) 190 231 - 0000 - 300 -

208 XL (1) 60 2051 1228 (8) 70 (8) 380 312 260 400 300 500 450(1) 75 2083 1415

208 YO (1) 60 2051 409 (8) 70 (8) 380 312 260 400 300 500 450(1) 75 2083 472

230 XL (1) 60 2051 1228 (8) 70 (8) 380 312 260 350 300 500 450(1) 75 2083 165125

230 YO (1) 60 2051 409 (8) 70 (8) 380 02 260 350 300 500 450 (1) 75 2083 472

460 XL (1) 60 904 485 (8) 35 (8) 190 240 - 250 - 300 -(1 75 974 539

460 YO (1) 60 904 162 (8) 35 (8) 190 240 - 250 - 300 -(1) 75 974 180

208 XL 2083 1415 (8) 70 (8) 380 316 260 400 300 500 450 208 YO 2083 472 (8) 70 (8) 380 316 260 400 300 500 450

135 230 XL (2) 75 2083 1415 (8) 70 (8) 380 316 260 400 300 500 450 I 230 YO 2083 472 (8) 70 (8) 380 316 260 400 300 500 450

460 XL 974 539 (8) 35 (8) 190 247 - 250 - 300 -460 YO 974 180 (8i 35 (8) 190 247 - 250 - 300 -

208 XL (2) SO 1788 1040 (10) 70 (10) 380 326 402 400 0000 500 500(1) 60 2051 1228

208 YO (2) 50 1788 347 (10) 70 (10) 380 326 402 400 0000 500 500(1 60 2051 409

230 XL (2) 50 1788 1040 (10) 70 (10) 380 326 402 400 0000 500 500 145 (1) 60 2011 1228

230 YO (2) 50 1788 347 (10) 70 (10) 380 326 402 400 0000 500 500(1) 60 2051 409

460 XL (2) 50 737 422 (10) 35 (10) 190 295 - 350 350 --(1) 60 904 485

460 YO (2) SO 731 141 10 (35) (10)190 295 - 350 350- -(1)60 904 162

208 XL 2051 1228 (10) 70 (10) 380 326 462 400 (2)250 500 600 208 YO 2051 409 (10) 70 (10) 380 326 462 400 (2)250 500 600

160 230 XL (3) 60 2051 1228 (10) 70 (10) 380 326 462 400 (2)250 500 230 YO 2051 409 (10) 70 (10) 380 326 462 600400 (2)250 500 600 460 XL 904 485 (10) 35 (10) 190 329 - 400 - 400 460 YO 904 167 (10) 35 (10) 190 329 - 400 - 400 - I

NOTES 1 XL Across the LineYOStarDelta 2 RLA Rated LoadAmps(ratedin accordance withARI Standard 590) LRA LockedRotorAmps 3 Wire Size Amps equal125of the ratedloadampsfor the largestmotorin thecircuitplus100of the ratedloadampsfor all othermotorsin the circuit per

NEC 4 Wire size based on copperconductorswith75C insulation perNECTable310-16 Terminal block lugs are sizedaccordingly Use of oversize wiringmay

not lit in terminal blocks 5 Maximumfuse size is basedon 175to 225of the ratedloadampsfor the largestmotorin the circuitplus 100of the rated loadampsfora othermotors

in the circuit per NEC VOLTAGE TOLERANCES 208V-230V min 187VMax 253V

480V Min414V Max506V

I

18

ELECTRICAL DATA Volts Type COMPRESSORModel FAN MOTORS MINCIRCUIT RECOMMENDED MAXIMUM 60 Hz of Oty RLA Starting FLAACWC LRA AMPACITY WIRESIZE FUSE SIZE 3 Ph Start Curro EaSC HP Ea Ea Ea Cire1 Cire2 Cire1 Cire2 Cire1 Cire2 208 XL 2051(1) 60 1228 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 1415 208 YO (1) 60 2051 409 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 472 230 XL (1) 60 2051 1228 (12)70 (12) 380 341 469 500 (2) 250 500 600

12 75 2083 1415185 230 YO (1) 60 2051 409 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 472 460 XL 485 (12) 35 (1) 60 904 (12) 190 352 500 400- - -

(2) 75 974 539 460 YO (1) 60 904 162 (12) 5(12)19 352 500 400- - -

(2) 75 974 180 208 XL 2083 1415 (12) 70 (12) 380 345 469 500 500(2) 250 600

472208 YO 2083 (12) 70 345(12) 380 469 500 (2) 250 500 600 230 XL (3) 75 2083 1415 (12) 70 345(12) 380 469 500 (2) 250 500 600200 230 YO 2083 472 (12) 70 (12) 190 345 469 500 500(2) 250 600 460 XL 539974 (12) 35 (12) 190 359 - 450500 - -

180 1(12) 35 460 YO 974 (12) 190 359 450 -500- -2051 1228208 XL (12) 70 504(12) 380 504 (2) 250 (2) 250 700 700

208 YO 2051 409 (12) 70 (12) 380 504 504 (2) 250 700(2) 250 700 (4) 60 2051 1228 (12) 70 230 XL (12) 380 504 504 (2) 250 (2) 250 700 700215

YO 2051 409230 (12) 70 (12) 380 504 504 (2) 250 (2) 250 700 700 460 904 485 (12) 35 XL (12) 190 225 225 0000 0000 300 300

(12) 35 460 YO 904 162 (12) 190 300225 225 0000 0000 300 2051 1228208 XL (2) 60 (14) 70 (14) 380 504 525 (2250 700 700(2)300

(2) 75 2083 1415 2051 409 (14) 70 700 700208 YO (2) 60 (14) 380 504 525 (2) 250 (2)300

(2) 75 2083 472240 700XL (2) 60 2051 1228 (14) 70 (14) 380 504 525 (2)250 (2)300 700230

(2) 75 2083 1415 2011230 YO (2) 60 409 (14) 70 (14) 380 504 525 (2) 250 (2)300 700 700

(2) 75 2083 472 300460 XL (2) 60 904 485 (14) 35 (14) 190 225 248 0000 250 300

12 75 974 539 904 162 250 300 300460 YO (2) 60 (14) 35 (14) 190 225 248 410

(2) 75 974 180 2083 1415 (2)300 700 700XL (16) 70 (16) 380 525 525 (2)300208 2083 1415 (2)300 700 700208 YO (16) 70 525 525 (2)300(16) 380

700 7002083 1415 (16) 70 (2300230 XL (16) 380 525 525 (2300 700 700(2300(4) 75 2083 472 (16) 70 (16) 380 525 525 (2300230 XL265

300250 300974 539 (16) 35 248 248 250XL (16) 380 460 (16) 35 300 300974 (16 380 248 250 250YO 539 248460

NOTES 1 XL Across the Line YO Star Delta 2 RLA Rated Load Amps (rated in accordance with ARI Standard 590) LRA Locked Rotor Amps 3 Wire Size Amps equal 125 of the rated load amps for the largest motor in the circuit plus 100 of the rated load amps for all other motors in the circuit per

NEC 4 Wire size based on copper conductors with 75degG insulation per NEG Table 310-16 Terminal block lugs are sized accordingly Use of oversize wiring may

not fit in terminal blocks 5 Maximum fuse size is based on 175 to 225 of the rated load amps for the largest motor in the circuit plus 100 of the rated load amps for a other motors

in the circuit per NEG VOLTAGE TOLERANCES 208V-230V min 187V Max 253V

480V Min414V Max506V

19

0

(Wd~) 3lV~ M011 ~31VM

006 009 00 OOt OOl OS L 00 L os 0 Ot

V D m (I) (I)

c D m c D o V

- m m -t o

~

~ m D-

aoao 3~nSS3~d ~3100~

APPLICATION DATA

POINT LOADING

ArMi I 1 5 1

ACWC 45 THRU 10 SC

COMPRESSOR CONDENSER SECTION SECTION

_ 2 4 bull 1

bull CA

J

Model Dimensions Size A B C D 45 91 - - -55 91 - - -70 145 - - -90 145 - - -110 60 40 160 -125 60 40 160 -135 60 40 160 -145 138 74 107 -160 13830 74 107 -185 138 129 107 -200 138 129 107 -215 106 82 106 80 240 106 82 134 107 265 133 110 134 107

1310

1310

~

1

1310

2

ACwe 110 THRU 200 Ie

COMPREIlOfl CONDENSER SECTION IECnoN

4 -

5Imiddot

ACWC 2t5 THRU 215 SC

Model Loadlnu (LBS) Size 1amp2 3amp4 5amp6 7amp8 9 amp10 45 585 765 550 - -55 705 810 635 - -70 660 890 700 - -90 1025 1500 1175 - -110 1195 635 1525 995 -125 1255 690 1835 1115 -135 1255 665 1880 1105 -145 1330 2380 2160 1450 -160 1330 2440 2280 1515 -185 1235 2575 2980 1360 -200 1275 2635 3020 1380 -215 1010 2270 2590 2240 840 240 1115 2550 2870 2715 1125 265 1380 2980 3515 2750 1175

11

II i middot 2 4 lIf 11 to L

21

TROUBLESHOOTING GUIDE

CHILLER UNIT WILL NOT START POSSIBLE CAUSE REMEDY 1 Power off 1 Check main disconnect switch

2 Main line open 2 Check main fuses

3 Incorrect wiring 3 Check the wiring diagram

4 Loose terminals 4 Tiqhten all terminals

5 Control circuit open 5 Check phase loss monitor flow switch circuit breakers temperature control low ambient thermostat low temperature thermostat remote switch etc

6 Time delay 6 Wait

COMPRESSOR HUMS BUT DOES NOT START

POSSIBLE CAUSE REMEDY

1 Low voltage 1a Check at service and unit for loss

b Consult power company

COMPRESSOR CUTS OUT ON LOW PRESSURE SAFETY CONTROL POSSIBLE CAUSE REMEDY 1 Refrigerant shortage 1 Check for leaks -- add refrigerant 2 Restriction in liquid line 2a Plugged strainer - dean or replace

b Liquid line valve partially closed - open valves fully c Expansion valve clogged or inoperative - clean or replace as

required d Solenoid valve partially open - clean or replace as required

3 Low water flow thru cooler 3 Check water flow thru cooler and correct as required

COMPRESSOR CYCLES ON HIGH PRESSURE CONTROL POSSIBLE CAUSE REMEDY 1 Compressor discharge valve partially closed 1 Open valve fully 2 Non-condensible gases in system 2 Operate condenser fans with compressors off If condenser

pressure exceeds saturated pressure corresponding to condenser entering air temperature then purge air from discharge line

3 Overcharge of R-22 3 Purge system while in operation until head pressure reaches a normal level

4 Dirty condenser 4 Clean the condenser 5 Compressor discharge check valve not operating properly 5 Replace if necessary 6 Fans not running 6 Check pressure control setting

CAUSES AND PREVENTION OF FREEZE-UP CAUSES PREVENTION 1 Improper charging 1 Charge per manufacturers recommendation

2 Improperly set safety time delay 2 Check the safety time delay low pressure control for proper setting at the beginning of each season

3 Improper chilled water circulation 3 Use an ample sized cleanable strainer in the chilled water circuit Make certain the strainer is clean to insure full flow and velocity of

chilled water It may sometimes be necessary to treat the water to prevent formation of deposits

4 Not draining for winter shutdown 4 When the system is shut down for the winter remove the drain

plugs and drain the cooler Blowout any remaining water with air

5 Improper pump shutdown 5 Make sure chiller barrel heater is working and flow switch is installed per wiring diagrams

6 Low ambient during air conditioning season 6 Make sure chiller barrel heater is working

NOTE If the ambient temperature is below 32degF freezing can be completely prevented by one of two methods

1 Drain all water from the equipment 2 Add antifreeze to the water

22

START-UP CHECK LIST

Unit Model No

Setting unit

Wiring

Piping

Alignment

Before Start-Up

After Start-Up

Yes No a Vibration isolator used

b Spring isolator adjusted for equal height c If rubber-in-shear isolators are used is unit leveled by shimming

a Power wiring complete

b Control wiring complete c Electric service adequate for load

d Power source voltage correct for motor(s) used

e Motor circuit has proper size fusetrons f System wired per diagram

g All lead connections tight h Wiring complies with local codes i Flow switch operation

a Piping complies with applicable codes b External piping independently supported c Chilled water lines insulated

a All belts adjusted and checked for tension b All pulleys checked and adjusted for proper pitch tightness and

alignment

a Open compressor discharge service valve b Open liquid valve(s) c Open suction and discharge valves to pressure gauges (if supplied) d Check rotation of all fan motors e Start auxiliary equipment (pumps fans etc) f Is crankcase heater operating Operate 24 hours prior to unit startup g Check the compressor oil level through the crankcase sight glass The oil

level should be to the top of the glass If the level is low add oil in accordance with the directions in the maintenance instruction

h Check all control settings as specified in Table 1 I Air purged from chilled water system

a Check high pressure control b Check oil temperature safety switch c Check and adjust low pressure or temperature freeze control d Check and adjust operating thermostat e Check and adjust low pressure operating control f Check and adjust expansion valve superheat g Check and adjust capacity control thermostat

23

OPERATING DATA CHILLER Voltage L-1 L-2 L-3 _ Pressure Gauge Readings 1 Suction psig 1 Discharge psig 2 Suction psig 2 Discharge _ psig 3 Suction psig 3 Discharge psig 4 Suction psig 4 Discharge _ psig High pressure switch setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-in) psig psig (Out) 4 (Cut-In) psig psig (Out) Checked Setting - Yes - No (each circuit) Low Pressure Switch Setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-In) psig psig (Out) 4 (Cut-in) psig psig (Out) Checked Setting -Yes -No (each circuit) 1 Oil Temperature Safety Switch Cut Out 2 Oil Temperature Safety Switch Cut Out 3 Oil Temperature Safety Switch Cut Out 4 Oil Temperature Safety Switch Cut Out If Star-Delta start time delay is seconds Temperature of air entering condenser F Temperature of air leaving condenser of Temperature of chilled water entering chiller OF Temperature of water (chilled) leaving chiller F Chilled water pressure entering chiller psig Chilled water pressure leaving chiller psig

MAINTENANCE Good maintenance practice will prolong the chiller life and will reduce the Ask of system breakdown and expensive service calls

A weekly check of the ACWC-SD unit requires only a few minutes and will prove beneficial in insuring long trouble free operation

WEEKLY CHECKS- with unit in operation for at least four hours 1) Check compressor oil level - At least above 12 of sight glass 2) Record suction and discharge pressures

Typical Condition R22 Ambient 95degF Return water 55degF Leaving water 45degF Suction 62 psig Discharge 270 psig

3) Record ambient temperature 4) Check liquid sight glass

Make sure liquid is clear - no bubbles 5) Check that all fans are running 6) Check entering face of condenser coil for cleanliness 7) Record voltage at unit

All of the above can be performed by building maintenance personnel If oil levels are low or any of the above checked items are questionable consult a qualified serviceman

At least once a year a qualified serviceman should check unit oil levels superheat and control operation

DUNHAM-BUSH USA

P l) bull 130 xUtUC t01 Bmgess RO~ Harrisonburg VA 22801 Phone (540) 434-0711 FAX (540) 434-~ 2118

wvvwdunham-bushcom Form No 6184

Page 15: ACWC-SD - · PDF fileACWC-SD • Screw . Type • • • Air-Cooled Packaged Chillers •• Installation, Operation, and •• • Maintenance Manual • • • •• DESCRIPTION

~ I

[gtO(]O

~ i I Ii i 2 ~ ~ ~ i a bull il 2 ~

iiibullbullbull

~ I ~ I I I ~~ =l ~ iI I ~ I I I It I 1111 amp ~~

as ooz nJ4l SP~ SlapoUII ~NI~IM 10U1NOl lVlldAl

-------

---

TYPICAL POWER WIRING Models 45 thru 70 SC

----

rYl31I01 I

-Ii --ti-

_ I ~_-

~ lniJ -

LIIbullbullbullbull PC _ amp-II _--- ~

TYPICAL POWER WIRING Models 90 thru 135 SC

- --- _ Tt

~rfh c~

tP ~

_III ~

I r-- ~- IIlJ

bull - MIl Mf __ bull Ie_~--~ _shy- shy16

---

----------

TYPICAL POWER WIRING Models 145 thru 200 SC

_ --1a1 IIUrI

middotrFti~v_ bull I

i~i ~~ TaII IIOMLI ~tN T 100 WTIOII 011 lilOOCL a

~ t1

tI bullbullbull

L

i I r-~

I r

~ ~ ~ III

2 ~ ~ ~l

- ~IlD I hJOHr eo teO acshyt CmiddotClM ~ CIKUr1 --

TYPICAL POWER WIRING Models 215 thru 265 SC

ItUU 1D Wll1U1I fIa -rMI

rt-h I -au 11 1_ i r~ rt-f

-i rn f1 ft fi i- llil bullbull c~ I bull c =

~~~ ~i~-~

~~m

~~~CI1 R~~ ~ ~~ ~llAi4I

luv~ bull ~uf LL~~-

~Mfl l~t IrMiA

a I III nII I bull it d

~-t--J I Lll-l~j ~nL4111 WlJj== lit-

I bullbullbull I

UGEND

~

~l OJ

- c~

~~~---

~)~middotI

I

L _~~~ L _I__~_J I ~ (11_1 ~ H~ CUlTMIt tffC_) Ll N

-r_ 0 1ItCIIIl0AI lllQUlllCo as -0- bull bullbull fI PC 110 lNJCllII a Olil1100pound1 II 111 el 1101 ItCOU_ 011 IIOOIL140

I 011 CI-( H[ (0110 (fMCun ubullbull --- l(lD IMbullbull Ntlf 110 e414-7

--CTOttbullbull

2

17

ELECTRICAL DATA Model Volts Type COMPRESSOR FAN MOTORS MIN CIRCUIT RECOMMENDED MAXIMUM ACWC 60 Hz of Qty RLA Starting FLA LRA AMPACITY WIRESIZE FUSESIZE

SC 3 Ph Start HP Ea Curro Ea Ea Ea Circ1 Circ2 Circ1 Circ2 Circ1 eire 2

208230 XL 1788 1040 (4) 70 (4) 380 252 - 250 - 400 -45 208230 YO (1) 50 1788 347 (4) 70 (4) 380 252 - 250 - 400 -

460 XL 737 422 (4) 35 (4) 190 106 - 2 - 175 -460 YO 737 141 (4) 35 (4) 190 106 - 2 - 175 -

208230 XL 2051 1228 (4) 70 (4) 380 284 - 300 - 450 -55 208230 YO (1) 60 2051 409 (4) 70 (4) 380 284 - 300 - 450 -

460 XL 904 485 (4) 35 (4) 190 127 - 1 - 200 -460 YO 904 162 (4) 35 (4) 190 127 - 1 - 200 -

208230 XL 2083 1415 (6) 70 (6) 380 302 350 500 -70 208230 YO (1) 75 2083 472 (6) 70 (6) 380 302 350 500 -

460 XL 974 539 (6) 35 (6) 190 143 0 225 -460 YO 974 180 (6) 35 (6 190 143 0 225 -208 XL 1788 1040 (6) 70 (6) 380 266 224 300 0000 400 400 208 YO 1788 347 (6) 70 (6) 380 266 224 300 0000 400

90 230 XL (2) 50 1788 1040 (6) 70 (6) 380 266 224 400 I300 0000 400 400 230 YO 1788 347 (6) 70 (6) 380 266 224 300 0000 400 400 460 XL 737 422 (6) 35 (6) 190 187 - 000 - 250 460 YO 737 141 (6) 35 (6) 190 187 - =1000 - 250 208 XL 2051 1228 (8) 70 (8) 380 312 256 400 300 250 208 YO 2051 409 (8) 70 (8) 380 312 256 400 300 500

110 230 XL (2) 60 2051 1228 (8) 70 (8) 380 312 256 g I350 300 SOO 450 230 YO 2051 409 (8) 70 (8) 380 312 256 350 300 500 450 460 XL 914 485 (8) 35 (8) 190 231 - 0000 - 300 460 YO 904 162 (8) 35 (8) 190 231 - 0000 - 300 -

208 XL (1) 60 2051 1228 (8) 70 (8) 380 312 260 400 300 500 450(1) 75 2083 1415

208 YO (1) 60 2051 409 (8) 70 (8) 380 312 260 400 300 500 450(1) 75 2083 472

230 XL (1) 60 2051 1228 (8) 70 (8) 380 312 260 350 300 500 450(1) 75 2083 165125

230 YO (1) 60 2051 409 (8) 70 (8) 380 02 260 350 300 500 450 (1) 75 2083 472

460 XL (1) 60 904 485 (8) 35 (8) 190 240 - 250 - 300 -(1 75 974 539

460 YO (1) 60 904 162 (8) 35 (8) 190 240 - 250 - 300 -(1) 75 974 180

208 XL 2083 1415 (8) 70 (8) 380 316 260 400 300 500 450 208 YO 2083 472 (8) 70 (8) 380 316 260 400 300 500 450

135 230 XL (2) 75 2083 1415 (8) 70 (8) 380 316 260 400 300 500 450 I 230 YO 2083 472 (8) 70 (8) 380 316 260 400 300 500 450

460 XL 974 539 (8) 35 (8) 190 247 - 250 - 300 -460 YO 974 180 (8i 35 (8) 190 247 - 250 - 300 -

208 XL (2) SO 1788 1040 (10) 70 (10) 380 326 402 400 0000 500 500(1) 60 2051 1228

208 YO (2) 50 1788 347 (10) 70 (10) 380 326 402 400 0000 500 500(1 60 2051 409

230 XL (2) 50 1788 1040 (10) 70 (10) 380 326 402 400 0000 500 500 145 (1) 60 2011 1228

230 YO (2) 50 1788 347 (10) 70 (10) 380 326 402 400 0000 500 500(1) 60 2051 409

460 XL (2) 50 737 422 (10) 35 (10) 190 295 - 350 350 --(1) 60 904 485

460 YO (2) SO 731 141 10 (35) (10)190 295 - 350 350- -(1)60 904 162

208 XL 2051 1228 (10) 70 (10) 380 326 462 400 (2)250 500 600 208 YO 2051 409 (10) 70 (10) 380 326 462 400 (2)250 500 600

160 230 XL (3) 60 2051 1228 (10) 70 (10) 380 326 462 400 (2)250 500 230 YO 2051 409 (10) 70 (10) 380 326 462 600400 (2)250 500 600 460 XL 904 485 (10) 35 (10) 190 329 - 400 - 400 460 YO 904 167 (10) 35 (10) 190 329 - 400 - 400 - I

NOTES 1 XL Across the LineYOStarDelta 2 RLA Rated LoadAmps(ratedin accordance withARI Standard 590) LRA LockedRotorAmps 3 Wire Size Amps equal125of the ratedloadampsfor the largestmotorin thecircuitplus100of the ratedloadampsfor all othermotorsin the circuit per

NEC 4 Wire size based on copperconductorswith75C insulation perNECTable310-16 Terminal block lugs are sizedaccordingly Use of oversize wiringmay

not lit in terminal blocks 5 Maximumfuse size is basedon 175to 225of the ratedloadampsfor the largestmotorin the circuitplus 100of the rated loadampsfora othermotors

in the circuit per NEC VOLTAGE TOLERANCES 208V-230V min 187VMax 253V

480V Min414V Max506V

I

18

ELECTRICAL DATA Volts Type COMPRESSORModel FAN MOTORS MINCIRCUIT RECOMMENDED MAXIMUM 60 Hz of Oty RLA Starting FLAACWC LRA AMPACITY WIRESIZE FUSE SIZE 3 Ph Start Curro EaSC HP Ea Ea Ea Cire1 Cire2 Cire1 Cire2 Cire1 Cire2 208 XL 2051(1) 60 1228 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 1415 208 YO (1) 60 2051 409 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 472 230 XL (1) 60 2051 1228 (12)70 (12) 380 341 469 500 (2) 250 500 600

12 75 2083 1415185 230 YO (1) 60 2051 409 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 472 460 XL 485 (12) 35 (1) 60 904 (12) 190 352 500 400- - -

(2) 75 974 539 460 YO (1) 60 904 162 (12) 5(12)19 352 500 400- - -

(2) 75 974 180 208 XL 2083 1415 (12) 70 (12) 380 345 469 500 500(2) 250 600

472208 YO 2083 (12) 70 345(12) 380 469 500 (2) 250 500 600 230 XL (3) 75 2083 1415 (12) 70 345(12) 380 469 500 (2) 250 500 600200 230 YO 2083 472 (12) 70 (12) 190 345 469 500 500(2) 250 600 460 XL 539974 (12) 35 (12) 190 359 - 450500 - -

180 1(12) 35 460 YO 974 (12) 190 359 450 -500- -2051 1228208 XL (12) 70 504(12) 380 504 (2) 250 (2) 250 700 700

208 YO 2051 409 (12) 70 (12) 380 504 504 (2) 250 700(2) 250 700 (4) 60 2051 1228 (12) 70 230 XL (12) 380 504 504 (2) 250 (2) 250 700 700215

YO 2051 409230 (12) 70 (12) 380 504 504 (2) 250 (2) 250 700 700 460 904 485 (12) 35 XL (12) 190 225 225 0000 0000 300 300

(12) 35 460 YO 904 162 (12) 190 300225 225 0000 0000 300 2051 1228208 XL (2) 60 (14) 70 (14) 380 504 525 (2250 700 700(2)300

(2) 75 2083 1415 2051 409 (14) 70 700 700208 YO (2) 60 (14) 380 504 525 (2) 250 (2)300

(2) 75 2083 472240 700XL (2) 60 2051 1228 (14) 70 (14) 380 504 525 (2)250 (2)300 700230

(2) 75 2083 1415 2011230 YO (2) 60 409 (14) 70 (14) 380 504 525 (2) 250 (2)300 700 700

(2) 75 2083 472 300460 XL (2) 60 904 485 (14) 35 (14) 190 225 248 0000 250 300

12 75 974 539 904 162 250 300 300460 YO (2) 60 (14) 35 (14) 190 225 248 410

(2) 75 974 180 2083 1415 (2)300 700 700XL (16) 70 (16) 380 525 525 (2)300208 2083 1415 (2)300 700 700208 YO (16) 70 525 525 (2)300(16) 380

700 7002083 1415 (16) 70 (2300230 XL (16) 380 525 525 (2300 700 700(2300(4) 75 2083 472 (16) 70 (16) 380 525 525 (2300230 XL265

300250 300974 539 (16) 35 248 248 250XL (16) 380 460 (16) 35 300 300974 (16 380 248 250 250YO 539 248460

NOTES 1 XL Across the Line YO Star Delta 2 RLA Rated Load Amps (rated in accordance with ARI Standard 590) LRA Locked Rotor Amps 3 Wire Size Amps equal 125 of the rated load amps for the largest motor in the circuit plus 100 of the rated load amps for all other motors in the circuit per

NEC 4 Wire size based on copper conductors with 75degG insulation per NEG Table 310-16 Terminal block lugs are sized accordingly Use of oversize wiring may

not fit in terminal blocks 5 Maximum fuse size is based on 175 to 225 of the rated load amps for the largest motor in the circuit plus 100 of the rated load amps for a other motors

in the circuit per NEG VOLTAGE TOLERANCES 208V-230V min 187V Max 253V

480V Min414V Max506V

19

0

(Wd~) 3lV~ M011 ~31VM

006 009 00 OOt OOl OS L 00 L os 0 Ot

V D m (I) (I)

c D m c D o V

- m m -t o

~

~ m D-

aoao 3~nSS3~d ~3100~

APPLICATION DATA

POINT LOADING

ArMi I 1 5 1

ACWC 45 THRU 10 SC

COMPRESSOR CONDENSER SECTION SECTION

_ 2 4 bull 1

bull CA

J

Model Dimensions Size A B C D 45 91 - - -55 91 - - -70 145 - - -90 145 - - -110 60 40 160 -125 60 40 160 -135 60 40 160 -145 138 74 107 -160 13830 74 107 -185 138 129 107 -200 138 129 107 -215 106 82 106 80 240 106 82 134 107 265 133 110 134 107

1310

1310

~

1

1310

2

ACwe 110 THRU 200 Ie

COMPREIlOfl CONDENSER SECTION IECnoN

4 -

5Imiddot

ACWC 2t5 THRU 215 SC

Model Loadlnu (LBS) Size 1amp2 3amp4 5amp6 7amp8 9 amp10 45 585 765 550 - -55 705 810 635 - -70 660 890 700 - -90 1025 1500 1175 - -110 1195 635 1525 995 -125 1255 690 1835 1115 -135 1255 665 1880 1105 -145 1330 2380 2160 1450 -160 1330 2440 2280 1515 -185 1235 2575 2980 1360 -200 1275 2635 3020 1380 -215 1010 2270 2590 2240 840 240 1115 2550 2870 2715 1125 265 1380 2980 3515 2750 1175

11

II i middot 2 4 lIf 11 to L

21

TROUBLESHOOTING GUIDE

CHILLER UNIT WILL NOT START POSSIBLE CAUSE REMEDY 1 Power off 1 Check main disconnect switch

2 Main line open 2 Check main fuses

3 Incorrect wiring 3 Check the wiring diagram

4 Loose terminals 4 Tiqhten all terminals

5 Control circuit open 5 Check phase loss monitor flow switch circuit breakers temperature control low ambient thermostat low temperature thermostat remote switch etc

6 Time delay 6 Wait

COMPRESSOR HUMS BUT DOES NOT START

POSSIBLE CAUSE REMEDY

1 Low voltage 1a Check at service and unit for loss

b Consult power company

COMPRESSOR CUTS OUT ON LOW PRESSURE SAFETY CONTROL POSSIBLE CAUSE REMEDY 1 Refrigerant shortage 1 Check for leaks -- add refrigerant 2 Restriction in liquid line 2a Plugged strainer - dean or replace

b Liquid line valve partially closed - open valves fully c Expansion valve clogged or inoperative - clean or replace as

required d Solenoid valve partially open - clean or replace as required

3 Low water flow thru cooler 3 Check water flow thru cooler and correct as required

COMPRESSOR CYCLES ON HIGH PRESSURE CONTROL POSSIBLE CAUSE REMEDY 1 Compressor discharge valve partially closed 1 Open valve fully 2 Non-condensible gases in system 2 Operate condenser fans with compressors off If condenser

pressure exceeds saturated pressure corresponding to condenser entering air temperature then purge air from discharge line

3 Overcharge of R-22 3 Purge system while in operation until head pressure reaches a normal level

4 Dirty condenser 4 Clean the condenser 5 Compressor discharge check valve not operating properly 5 Replace if necessary 6 Fans not running 6 Check pressure control setting

CAUSES AND PREVENTION OF FREEZE-UP CAUSES PREVENTION 1 Improper charging 1 Charge per manufacturers recommendation

2 Improperly set safety time delay 2 Check the safety time delay low pressure control for proper setting at the beginning of each season

3 Improper chilled water circulation 3 Use an ample sized cleanable strainer in the chilled water circuit Make certain the strainer is clean to insure full flow and velocity of

chilled water It may sometimes be necessary to treat the water to prevent formation of deposits

4 Not draining for winter shutdown 4 When the system is shut down for the winter remove the drain

plugs and drain the cooler Blowout any remaining water with air

5 Improper pump shutdown 5 Make sure chiller barrel heater is working and flow switch is installed per wiring diagrams

6 Low ambient during air conditioning season 6 Make sure chiller barrel heater is working

NOTE If the ambient temperature is below 32degF freezing can be completely prevented by one of two methods

1 Drain all water from the equipment 2 Add antifreeze to the water

22

START-UP CHECK LIST

Unit Model No

Setting unit

Wiring

Piping

Alignment

Before Start-Up

After Start-Up

Yes No a Vibration isolator used

b Spring isolator adjusted for equal height c If rubber-in-shear isolators are used is unit leveled by shimming

a Power wiring complete

b Control wiring complete c Electric service adequate for load

d Power source voltage correct for motor(s) used

e Motor circuit has proper size fusetrons f System wired per diagram

g All lead connections tight h Wiring complies with local codes i Flow switch operation

a Piping complies with applicable codes b External piping independently supported c Chilled water lines insulated

a All belts adjusted and checked for tension b All pulleys checked and adjusted for proper pitch tightness and

alignment

a Open compressor discharge service valve b Open liquid valve(s) c Open suction and discharge valves to pressure gauges (if supplied) d Check rotation of all fan motors e Start auxiliary equipment (pumps fans etc) f Is crankcase heater operating Operate 24 hours prior to unit startup g Check the compressor oil level through the crankcase sight glass The oil

level should be to the top of the glass If the level is low add oil in accordance with the directions in the maintenance instruction

h Check all control settings as specified in Table 1 I Air purged from chilled water system

a Check high pressure control b Check oil temperature safety switch c Check and adjust low pressure or temperature freeze control d Check and adjust operating thermostat e Check and adjust low pressure operating control f Check and adjust expansion valve superheat g Check and adjust capacity control thermostat

23

OPERATING DATA CHILLER Voltage L-1 L-2 L-3 _ Pressure Gauge Readings 1 Suction psig 1 Discharge psig 2 Suction psig 2 Discharge _ psig 3 Suction psig 3 Discharge psig 4 Suction psig 4 Discharge _ psig High pressure switch setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-in) psig psig (Out) 4 (Cut-In) psig psig (Out) Checked Setting - Yes - No (each circuit) Low Pressure Switch Setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-In) psig psig (Out) 4 (Cut-in) psig psig (Out) Checked Setting -Yes -No (each circuit) 1 Oil Temperature Safety Switch Cut Out 2 Oil Temperature Safety Switch Cut Out 3 Oil Temperature Safety Switch Cut Out 4 Oil Temperature Safety Switch Cut Out If Star-Delta start time delay is seconds Temperature of air entering condenser F Temperature of air leaving condenser of Temperature of chilled water entering chiller OF Temperature of water (chilled) leaving chiller F Chilled water pressure entering chiller psig Chilled water pressure leaving chiller psig

MAINTENANCE Good maintenance practice will prolong the chiller life and will reduce the Ask of system breakdown and expensive service calls

A weekly check of the ACWC-SD unit requires only a few minutes and will prove beneficial in insuring long trouble free operation

WEEKLY CHECKS- with unit in operation for at least four hours 1) Check compressor oil level - At least above 12 of sight glass 2) Record suction and discharge pressures

Typical Condition R22 Ambient 95degF Return water 55degF Leaving water 45degF Suction 62 psig Discharge 270 psig

3) Record ambient temperature 4) Check liquid sight glass

Make sure liquid is clear - no bubbles 5) Check that all fans are running 6) Check entering face of condenser coil for cleanliness 7) Record voltage at unit

All of the above can be performed by building maintenance personnel If oil levels are low or any of the above checked items are questionable consult a qualified serviceman

At least once a year a qualified serviceman should check unit oil levels superheat and control operation

DUNHAM-BUSH USA

P l) bull 130 xUtUC t01 Bmgess RO~ Harrisonburg VA 22801 Phone (540) 434-0711 FAX (540) 434-~ 2118

wvvwdunham-bushcom Form No 6184

Page 16: ACWC-SD - · PDF fileACWC-SD • Screw . Type • • • Air-Cooled Packaged Chillers •• Installation, Operation, and •• • Maintenance Manual • • • •• DESCRIPTION

-------

---

TYPICAL POWER WIRING Models 45 thru 70 SC

----

rYl31I01 I

-Ii --ti-

_ I ~_-

~ lniJ -

LIIbullbullbullbull PC _ amp-II _--- ~

TYPICAL POWER WIRING Models 90 thru 135 SC

- --- _ Tt

~rfh c~

tP ~

_III ~

I r-- ~- IIlJ

bull - MIl Mf __ bull Ie_~--~ _shy- shy16

---

----------

TYPICAL POWER WIRING Models 145 thru 200 SC

_ --1a1 IIUrI

middotrFti~v_ bull I

i~i ~~ TaII IIOMLI ~tN T 100 WTIOII 011 lilOOCL a

~ t1

tI bullbullbull

L

i I r-~

I r

~ ~ ~ III

2 ~ ~ ~l

- ~IlD I hJOHr eo teO acshyt CmiddotClM ~ CIKUr1 --

TYPICAL POWER WIRING Models 215 thru 265 SC

ItUU 1D Wll1U1I fIa -rMI

rt-h I -au 11 1_ i r~ rt-f

-i rn f1 ft fi i- llil bullbull c~ I bull c =

~~~ ~i~-~

~~m

~~~CI1 R~~ ~ ~~ ~llAi4I

luv~ bull ~uf LL~~-

~Mfl l~t IrMiA

a I III nII I bull it d

~-t--J I Lll-l~j ~nL4111 WlJj== lit-

I bullbullbull I

UGEND

~

~l OJ

- c~

~~~---

~)~middotI

I

L _~~~ L _I__~_J I ~ (11_1 ~ H~ CUlTMIt tffC_) Ll N

-r_ 0 1ItCIIIl0AI lllQUlllCo as -0- bull bullbull fI PC 110 lNJCllII a Olil1100pound1 II 111 el 1101 ItCOU_ 011 IIOOIL140

I 011 CI-( H[ (0110 (fMCun ubullbull --- l(lD IMbullbull Ntlf 110 e414-7

--CTOttbullbull

2

17

ELECTRICAL DATA Model Volts Type COMPRESSOR FAN MOTORS MIN CIRCUIT RECOMMENDED MAXIMUM ACWC 60 Hz of Qty RLA Starting FLA LRA AMPACITY WIRESIZE FUSESIZE

SC 3 Ph Start HP Ea Curro Ea Ea Ea Circ1 Circ2 Circ1 Circ2 Circ1 eire 2

208230 XL 1788 1040 (4) 70 (4) 380 252 - 250 - 400 -45 208230 YO (1) 50 1788 347 (4) 70 (4) 380 252 - 250 - 400 -

460 XL 737 422 (4) 35 (4) 190 106 - 2 - 175 -460 YO 737 141 (4) 35 (4) 190 106 - 2 - 175 -

208230 XL 2051 1228 (4) 70 (4) 380 284 - 300 - 450 -55 208230 YO (1) 60 2051 409 (4) 70 (4) 380 284 - 300 - 450 -

460 XL 904 485 (4) 35 (4) 190 127 - 1 - 200 -460 YO 904 162 (4) 35 (4) 190 127 - 1 - 200 -

208230 XL 2083 1415 (6) 70 (6) 380 302 350 500 -70 208230 YO (1) 75 2083 472 (6) 70 (6) 380 302 350 500 -

460 XL 974 539 (6) 35 (6) 190 143 0 225 -460 YO 974 180 (6) 35 (6 190 143 0 225 -208 XL 1788 1040 (6) 70 (6) 380 266 224 300 0000 400 400 208 YO 1788 347 (6) 70 (6) 380 266 224 300 0000 400

90 230 XL (2) 50 1788 1040 (6) 70 (6) 380 266 224 400 I300 0000 400 400 230 YO 1788 347 (6) 70 (6) 380 266 224 300 0000 400 400 460 XL 737 422 (6) 35 (6) 190 187 - 000 - 250 460 YO 737 141 (6) 35 (6) 190 187 - =1000 - 250 208 XL 2051 1228 (8) 70 (8) 380 312 256 400 300 250 208 YO 2051 409 (8) 70 (8) 380 312 256 400 300 500

110 230 XL (2) 60 2051 1228 (8) 70 (8) 380 312 256 g I350 300 SOO 450 230 YO 2051 409 (8) 70 (8) 380 312 256 350 300 500 450 460 XL 914 485 (8) 35 (8) 190 231 - 0000 - 300 460 YO 904 162 (8) 35 (8) 190 231 - 0000 - 300 -

208 XL (1) 60 2051 1228 (8) 70 (8) 380 312 260 400 300 500 450(1) 75 2083 1415

208 YO (1) 60 2051 409 (8) 70 (8) 380 312 260 400 300 500 450(1) 75 2083 472

230 XL (1) 60 2051 1228 (8) 70 (8) 380 312 260 350 300 500 450(1) 75 2083 165125

230 YO (1) 60 2051 409 (8) 70 (8) 380 02 260 350 300 500 450 (1) 75 2083 472

460 XL (1) 60 904 485 (8) 35 (8) 190 240 - 250 - 300 -(1 75 974 539

460 YO (1) 60 904 162 (8) 35 (8) 190 240 - 250 - 300 -(1) 75 974 180

208 XL 2083 1415 (8) 70 (8) 380 316 260 400 300 500 450 208 YO 2083 472 (8) 70 (8) 380 316 260 400 300 500 450

135 230 XL (2) 75 2083 1415 (8) 70 (8) 380 316 260 400 300 500 450 I 230 YO 2083 472 (8) 70 (8) 380 316 260 400 300 500 450

460 XL 974 539 (8) 35 (8) 190 247 - 250 - 300 -460 YO 974 180 (8i 35 (8) 190 247 - 250 - 300 -

208 XL (2) SO 1788 1040 (10) 70 (10) 380 326 402 400 0000 500 500(1) 60 2051 1228

208 YO (2) 50 1788 347 (10) 70 (10) 380 326 402 400 0000 500 500(1 60 2051 409

230 XL (2) 50 1788 1040 (10) 70 (10) 380 326 402 400 0000 500 500 145 (1) 60 2011 1228

230 YO (2) 50 1788 347 (10) 70 (10) 380 326 402 400 0000 500 500(1) 60 2051 409

460 XL (2) 50 737 422 (10) 35 (10) 190 295 - 350 350 --(1) 60 904 485

460 YO (2) SO 731 141 10 (35) (10)190 295 - 350 350- -(1)60 904 162

208 XL 2051 1228 (10) 70 (10) 380 326 462 400 (2)250 500 600 208 YO 2051 409 (10) 70 (10) 380 326 462 400 (2)250 500 600

160 230 XL (3) 60 2051 1228 (10) 70 (10) 380 326 462 400 (2)250 500 230 YO 2051 409 (10) 70 (10) 380 326 462 600400 (2)250 500 600 460 XL 904 485 (10) 35 (10) 190 329 - 400 - 400 460 YO 904 167 (10) 35 (10) 190 329 - 400 - 400 - I

NOTES 1 XL Across the LineYOStarDelta 2 RLA Rated LoadAmps(ratedin accordance withARI Standard 590) LRA LockedRotorAmps 3 Wire Size Amps equal125of the ratedloadampsfor the largestmotorin thecircuitplus100of the ratedloadampsfor all othermotorsin the circuit per

NEC 4 Wire size based on copperconductorswith75C insulation perNECTable310-16 Terminal block lugs are sizedaccordingly Use of oversize wiringmay

not lit in terminal blocks 5 Maximumfuse size is basedon 175to 225of the ratedloadampsfor the largestmotorin the circuitplus 100of the rated loadampsfora othermotors

in the circuit per NEC VOLTAGE TOLERANCES 208V-230V min 187VMax 253V

480V Min414V Max506V

I

18

ELECTRICAL DATA Volts Type COMPRESSORModel FAN MOTORS MINCIRCUIT RECOMMENDED MAXIMUM 60 Hz of Oty RLA Starting FLAACWC LRA AMPACITY WIRESIZE FUSE SIZE 3 Ph Start Curro EaSC HP Ea Ea Ea Cire1 Cire2 Cire1 Cire2 Cire1 Cire2 208 XL 2051(1) 60 1228 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 1415 208 YO (1) 60 2051 409 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 472 230 XL (1) 60 2051 1228 (12)70 (12) 380 341 469 500 (2) 250 500 600

12 75 2083 1415185 230 YO (1) 60 2051 409 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 472 460 XL 485 (12) 35 (1) 60 904 (12) 190 352 500 400- - -

(2) 75 974 539 460 YO (1) 60 904 162 (12) 5(12)19 352 500 400- - -

(2) 75 974 180 208 XL 2083 1415 (12) 70 (12) 380 345 469 500 500(2) 250 600

472208 YO 2083 (12) 70 345(12) 380 469 500 (2) 250 500 600 230 XL (3) 75 2083 1415 (12) 70 345(12) 380 469 500 (2) 250 500 600200 230 YO 2083 472 (12) 70 (12) 190 345 469 500 500(2) 250 600 460 XL 539974 (12) 35 (12) 190 359 - 450500 - -

180 1(12) 35 460 YO 974 (12) 190 359 450 -500- -2051 1228208 XL (12) 70 504(12) 380 504 (2) 250 (2) 250 700 700

208 YO 2051 409 (12) 70 (12) 380 504 504 (2) 250 700(2) 250 700 (4) 60 2051 1228 (12) 70 230 XL (12) 380 504 504 (2) 250 (2) 250 700 700215

YO 2051 409230 (12) 70 (12) 380 504 504 (2) 250 (2) 250 700 700 460 904 485 (12) 35 XL (12) 190 225 225 0000 0000 300 300

(12) 35 460 YO 904 162 (12) 190 300225 225 0000 0000 300 2051 1228208 XL (2) 60 (14) 70 (14) 380 504 525 (2250 700 700(2)300

(2) 75 2083 1415 2051 409 (14) 70 700 700208 YO (2) 60 (14) 380 504 525 (2) 250 (2)300

(2) 75 2083 472240 700XL (2) 60 2051 1228 (14) 70 (14) 380 504 525 (2)250 (2)300 700230

(2) 75 2083 1415 2011230 YO (2) 60 409 (14) 70 (14) 380 504 525 (2) 250 (2)300 700 700

(2) 75 2083 472 300460 XL (2) 60 904 485 (14) 35 (14) 190 225 248 0000 250 300

12 75 974 539 904 162 250 300 300460 YO (2) 60 (14) 35 (14) 190 225 248 410

(2) 75 974 180 2083 1415 (2)300 700 700XL (16) 70 (16) 380 525 525 (2)300208 2083 1415 (2)300 700 700208 YO (16) 70 525 525 (2)300(16) 380

700 7002083 1415 (16) 70 (2300230 XL (16) 380 525 525 (2300 700 700(2300(4) 75 2083 472 (16) 70 (16) 380 525 525 (2300230 XL265

300250 300974 539 (16) 35 248 248 250XL (16) 380 460 (16) 35 300 300974 (16 380 248 250 250YO 539 248460

NOTES 1 XL Across the Line YO Star Delta 2 RLA Rated Load Amps (rated in accordance with ARI Standard 590) LRA Locked Rotor Amps 3 Wire Size Amps equal 125 of the rated load amps for the largest motor in the circuit plus 100 of the rated load amps for all other motors in the circuit per

NEC 4 Wire size based on copper conductors with 75degG insulation per NEG Table 310-16 Terminal block lugs are sized accordingly Use of oversize wiring may

not fit in terminal blocks 5 Maximum fuse size is based on 175 to 225 of the rated load amps for the largest motor in the circuit plus 100 of the rated load amps for a other motors

in the circuit per NEG VOLTAGE TOLERANCES 208V-230V min 187V Max 253V

480V Min414V Max506V

19

0

(Wd~) 3lV~ M011 ~31VM

006 009 00 OOt OOl OS L 00 L os 0 Ot

V D m (I) (I)

c D m c D o V

- m m -t o

~

~ m D-

aoao 3~nSS3~d ~3100~

APPLICATION DATA

POINT LOADING

ArMi I 1 5 1

ACWC 45 THRU 10 SC

COMPRESSOR CONDENSER SECTION SECTION

_ 2 4 bull 1

bull CA

J

Model Dimensions Size A B C D 45 91 - - -55 91 - - -70 145 - - -90 145 - - -110 60 40 160 -125 60 40 160 -135 60 40 160 -145 138 74 107 -160 13830 74 107 -185 138 129 107 -200 138 129 107 -215 106 82 106 80 240 106 82 134 107 265 133 110 134 107

1310

1310

~

1

1310

2

ACwe 110 THRU 200 Ie

COMPREIlOfl CONDENSER SECTION IECnoN

4 -

5Imiddot

ACWC 2t5 THRU 215 SC

Model Loadlnu (LBS) Size 1amp2 3amp4 5amp6 7amp8 9 amp10 45 585 765 550 - -55 705 810 635 - -70 660 890 700 - -90 1025 1500 1175 - -110 1195 635 1525 995 -125 1255 690 1835 1115 -135 1255 665 1880 1105 -145 1330 2380 2160 1450 -160 1330 2440 2280 1515 -185 1235 2575 2980 1360 -200 1275 2635 3020 1380 -215 1010 2270 2590 2240 840 240 1115 2550 2870 2715 1125 265 1380 2980 3515 2750 1175

11

II i middot 2 4 lIf 11 to L

21

TROUBLESHOOTING GUIDE

CHILLER UNIT WILL NOT START POSSIBLE CAUSE REMEDY 1 Power off 1 Check main disconnect switch

2 Main line open 2 Check main fuses

3 Incorrect wiring 3 Check the wiring diagram

4 Loose terminals 4 Tiqhten all terminals

5 Control circuit open 5 Check phase loss monitor flow switch circuit breakers temperature control low ambient thermostat low temperature thermostat remote switch etc

6 Time delay 6 Wait

COMPRESSOR HUMS BUT DOES NOT START

POSSIBLE CAUSE REMEDY

1 Low voltage 1a Check at service and unit for loss

b Consult power company

COMPRESSOR CUTS OUT ON LOW PRESSURE SAFETY CONTROL POSSIBLE CAUSE REMEDY 1 Refrigerant shortage 1 Check for leaks -- add refrigerant 2 Restriction in liquid line 2a Plugged strainer - dean or replace

b Liquid line valve partially closed - open valves fully c Expansion valve clogged or inoperative - clean or replace as

required d Solenoid valve partially open - clean or replace as required

3 Low water flow thru cooler 3 Check water flow thru cooler and correct as required

COMPRESSOR CYCLES ON HIGH PRESSURE CONTROL POSSIBLE CAUSE REMEDY 1 Compressor discharge valve partially closed 1 Open valve fully 2 Non-condensible gases in system 2 Operate condenser fans with compressors off If condenser

pressure exceeds saturated pressure corresponding to condenser entering air temperature then purge air from discharge line

3 Overcharge of R-22 3 Purge system while in operation until head pressure reaches a normal level

4 Dirty condenser 4 Clean the condenser 5 Compressor discharge check valve not operating properly 5 Replace if necessary 6 Fans not running 6 Check pressure control setting

CAUSES AND PREVENTION OF FREEZE-UP CAUSES PREVENTION 1 Improper charging 1 Charge per manufacturers recommendation

2 Improperly set safety time delay 2 Check the safety time delay low pressure control for proper setting at the beginning of each season

3 Improper chilled water circulation 3 Use an ample sized cleanable strainer in the chilled water circuit Make certain the strainer is clean to insure full flow and velocity of

chilled water It may sometimes be necessary to treat the water to prevent formation of deposits

4 Not draining for winter shutdown 4 When the system is shut down for the winter remove the drain

plugs and drain the cooler Blowout any remaining water with air

5 Improper pump shutdown 5 Make sure chiller barrel heater is working and flow switch is installed per wiring diagrams

6 Low ambient during air conditioning season 6 Make sure chiller barrel heater is working

NOTE If the ambient temperature is below 32degF freezing can be completely prevented by one of two methods

1 Drain all water from the equipment 2 Add antifreeze to the water

22

START-UP CHECK LIST

Unit Model No

Setting unit

Wiring

Piping

Alignment

Before Start-Up

After Start-Up

Yes No a Vibration isolator used

b Spring isolator adjusted for equal height c If rubber-in-shear isolators are used is unit leveled by shimming

a Power wiring complete

b Control wiring complete c Electric service adequate for load

d Power source voltage correct for motor(s) used

e Motor circuit has proper size fusetrons f System wired per diagram

g All lead connections tight h Wiring complies with local codes i Flow switch operation

a Piping complies with applicable codes b External piping independently supported c Chilled water lines insulated

a All belts adjusted and checked for tension b All pulleys checked and adjusted for proper pitch tightness and

alignment

a Open compressor discharge service valve b Open liquid valve(s) c Open suction and discharge valves to pressure gauges (if supplied) d Check rotation of all fan motors e Start auxiliary equipment (pumps fans etc) f Is crankcase heater operating Operate 24 hours prior to unit startup g Check the compressor oil level through the crankcase sight glass The oil

level should be to the top of the glass If the level is low add oil in accordance with the directions in the maintenance instruction

h Check all control settings as specified in Table 1 I Air purged from chilled water system

a Check high pressure control b Check oil temperature safety switch c Check and adjust low pressure or temperature freeze control d Check and adjust operating thermostat e Check and adjust low pressure operating control f Check and adjust expansion valve superheat g Check and adjust capacity control thermostat

23

OPERATING DATA CHILLER Voltage L-1 L-2 L-3 _ Pressure Gauge Readings 1 Suction psig 1 Discharge psig 2 Suction psig 2 Discharge _ psig 3 Suction psig 3 Discharge psig 4 Suction psig 4 Discharge _ psig High pressure switch setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-in) psig psig (Out) 4 (Cut-In) psig psig (Out) Checked Setting - Yes - No (each circuit) Low Pressure Switch Setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-In) psig psig (Out) 4 (Cut-in) psig psig (Out) Checked Setting -Yes -No (each circuit) 1 Oil Temperature Safety Switch Cut Out 2 Oil Temperature Safety Switch Cut Out 3 Oil Temperature Safety Switch Cut Out 4 Oil Temperature Safety Switch Cut Out If Star-Delta start time delay is seconds Temperature of air entering condenser F Temperature of air leaving condenser of Temperature of chilled water entering chiller OF Temperature of water (chilled) leaving chiller F Chilled water pressure entering chiller psig Chilled water pressure leaving chiller psig

MAINTENANCE Good maintenance practice will prolong the chiller life and will reduce the Ask of system breakdown and expensive service calls

A weekly check of the ACWC-SD unit requires only a few minutes and will prove beneficial in insuring long trouble free operation

WEEKLY CHECKS- with unit in operation for at least four hours 1) Check compressor oil level - At least above 12 of sight glass 2) Record suction and discharge pressures

Typical Condition R22 Ambient 95degF Return water 55degF Leaving water 45degF Suction 62 psig Discharge 270 psig

3) Record ambient temperature 4) Check liquid sight glass

Make sure liquid is clear - no bubbles 5) Check that all fans are running 6) Check entering face of condenser coil for cleanliness 7) Record voltage at unit

All of the above can be performed by building maintenance personnel If oil levels are low or any of the above checked items are questionable consult a qualified serviceman

At least once a year a qualified serviceman should check unit oil levels superheat and control operation

DUNHAM-BUSH USA

P l) bull 130 xUtUC t01 Bmgess RO~ Harrisonburg VA 22801 Phone (540) 434-0711 FAX (540) 434-~ 2118

wvvwdunham-bushcom Form No 6184

Page 17: ACWC-SD - · PDF fileACWC-SD • Screw . Type • • • Air-Cooled Packaged Chillers •• Installation, Operation, and •• • Maintenance Manual • • • •• DESCRIPTION

---

----------

TYPICAL POWER WIRING Models 145 thru 200 SC

_ --1a1 IIUrI

middotrFti~v_ bull I

i~i ~~ TaII IIOMLI ~tN T 100 WTIOII 011 lilOOCL a

~ t1

tI bullbullbull

L

i I r-~

I r

~ ~ ~ III

2 ~ ~ ~l

- ~IlD I hJOHr eo teO acshyt CmiddotClM ~ CIKUr1 --

TYPICAL POWER WIRING Models 215 thru 265 SC

ItUU 1D Wll1U1I fIa -rMI

rt-h I -au 11 1_ i r~ rt-f

-i rn f1 ft fi i- llil bullbull c~ I bull c =

~~~ ~i~-~

~~m

~~~CI1 R~~ ~ ~~ ~llAi4I

luv~ bull ~uf LL~~-

~Mfl l~t IrMiA

a I III nII I bull it d

~-t--J I Lll-l~j ~nL4111 WlJj== lit-

I bullbullbull I

UGEND

~

~l OJ

- c~

~~~---

~)~middotI

I

L _~~~ L _I__~_J I ~ (11_1 ~ H~ CUlTMIt tffC_) Ll N

-r_ 0 1ItCIIIl0AI lllQUlllCo as -0- bull bullbull fI PC 110 lNJCllII a Olil1100pound1 II 111 el 1101 ItCOU_ 011 IIOOIL140

I 011 CI-( H[ (0110 (fMCun ubullbull --- l(lD IMbullbull Ntlf 110 e414-7

--CTOttbullbull

2

17

ELECTRICAL DATA Model Volts Type COMPRESSOR FAN MOTORS MIN CIRCUIT RECOMMENDED MAXIMUM ACWC 60 Hz of Qty RLA Starting FLA LRA AMPACITY WIRESIZE FUSESIZE

SC 3 Ph Start HP Ea Curro Ea Ea Ea Circ1 Circ2 Circ1 Circ2 Circ1 eire 2

208230 XL 1788 1040 (4) 70 (4) 380 252 - 250 - 400 -45 208230 YO (1) 50 1788 347 (4) 70 (4) 380 252 - 250 - 400 -

460 XL 737 422 (4) 35 (4) 190 106 - 2 - 175 -460 YO 737 141 (4) 35 (4) 190 106 - 2 - 175 -

208230 XL 2051 1228 (4) 70 (4) 380 284 - 300 - 450 -55 208230 YO (1) 60 2051 409 (4) 70 (4) 380 284 - 300 - 450 -

460 XL 904 485 (4) 35 (4) 190 127 - 1 - 200 -460 YO 904 162 (4) 35 (4) 190 127 - 1 - 200 -

208230 XL 2083 1415 (6) 70 (6) 380 302 350 500 -70 208230 YO (1) 75 2083 472 (6) 70 (6) 380 302 350 500 -

460 XL 974 539 (6) 35 (6) 190 143 0 225 -460 YO 974 180 (6) 35 (6 190 143 0 225 -208 XL 1788 1040 (6) 70 (6) 380 266 224 300 0000 400 400 208 YO 1788 347 (6) 70 (6) 380 266 224 300 0000 400

90 230 XL (2) 50 1788 1040 (6) 70 (6) 380 266 224 400 I300 0000 400 400 230 YO 1788 347 (6) 70 (6) 380 266 224 300 0000 400 400 460 XL 737 422 (6) 35 (6) 190 187 - 000 - 250 460 YO 737 141 (6) 35 (6) 190 187 - =1000 - 250 208 XL 2051 1228 (8) 70 (8) 380 312 256 400 300 250 208 YO 2051 409 (8) 70 (8) 380 312 256 400 300 500

110 230 XL (2) 60 2051 1228 (8) 70 (8) 380 312 256 g I350 300 SOO 450 230 YO 2051 409 (8) 70 (8) 380 312 256 350 300 500 450 460 XL 914 485 (8) 35 (8) 190 231 - 0000 - 300 460 YO 904 162 (8) 35 (8) 190 231 - 0000 - 300 -

208 XL (1) 60 2051 1228 (8) 70 (8) 380 312 260 400 300 500 450(1) 75 2083 1415

208 YO (1) 60 2051 409 (8) 70 (8) 380 312 260 400 300 500 450(1) 75 2083 472

230 XL (1) 60 2051 1228 (8) 70 (8) 380 312 260 350 300 500 450(1) 75 2083 165125

230 YO (1) 60 2051 409 (8) 70 (8) 380 02 260 350 300 500 450 (1) 75 2083 472

460 XL (1) 60 904 485 (8) 35 (8) 190 240 - 250 - 300 -(1 75 974 539

460 YO (1) 60 904 162 (8) 35 (8) 190 240 - 250 - 300 -(1) 75 974 180

208 XL 2083 1415 (8) 70 (8) 380 316 260 400 300 500 450 208 YO 2083 472 (8) 70 (8) 380 316 260 400 300 500 450

135 230 XL (2) 75 2083 1415 (8) 70 (8) 380 316 260 400 300 500 450 I 230 YO 2083 472 (8) 70 (8) 380 316 260 400 300 500 450

460 XL 974 539 (8) 35 (8) 190 247 - 250 - 300 -460 YO 974 180 (8i 35 (8) 190 247 - 250 - 300 -

208 XL (2) SO 1788 1040 (10) 70 (10) 380 326 402 400 0000 500 500(1) 60 2051 1228

208 YO (2) 50 1788 347 (10) 70 (10) 380 326 402 400 0000 500 500(1 60 2051 409

230 XL (2) 50 1788 1040 (10) 70 (10) 380 326 402 400 0000 500 500 145 (1) 60 2011 1228

230 YO (2) 50 1788 347 (10) 70 (10) 380 326 402 400 0000 500 500(1) 60 2051 409

460 XL (2) 50 737 422 (10) 35 (10) 190 295 - 350 350 --(1) 60 904 485

460 YO (2) SO 731 141 10 (35) (10)190 295 - 350 350- -(1)60 904 162

208 XL 2051 1228 (10) 70 (10) 380 326 462 400 (2)250 500 600 208 YO 2051 409 (10) 70 (10) 380 326 462 400 (2)250 500 600

160 230 XL (3) 60 2051 1228 (10) 70 (10) 380 326 462 400 (2)250 500 230 YO 2051 409 (10) 70 (10) 380 326 462 600400 (2)250 500 600 460 XL 904 485 (10) 35 (10) 190 329 - 400 - 400 460 YO 904 167 (10) 35 (10) 190 329 - 400 - 400 - I

NOTES 1 XL Across the LineYOStarDelta 2 RLA Rated LoadAmps(ratedin accordance withARI Standard 590) LRA LockedRotorAmps 3 Wire Size Amps equal125of the ratedloadampsfor the largestmotorin thecircuitplus100of the ratedloadampsfor all othermotorsin the circuit per

NEC 4 Wire size based on copperconductorswith75C insulation perNECTable310-16 Terminal block lugs are sizedaccordingly Use of oversize wiringmay

not lit in terminal blocks 5 Maximumfuse size is basedon 175to 225of the ratedloadampsfor the largestmotorin the circuitplus 100of the rated loadampsfora othermotors

in the circuit per NEC VOLTAGE TOLERANCES 208V-230V min 187VMax 253V

480V Min414V Max506V

I

18

ELECTRICAL DATA Volts Type COMPRESSORModel FAN MOTORS MINCIRCUIT RECOMMENDED MAXIMUM 60 Hz of Oty RLA Starting FLAACWC LRA AMPACITY WIRESIZE FUSE SIZE 3 Ph Start Curro EaSC HP Ea Ea Ea Cire1 Cire2 Cire1 Cire2 Cire1 Cire2 208 XL 2051(1) 60 1228 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 1415 208 YO (1) 60 2051 409 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 472 230 XL (1) 60 2051 1228 (12)70 (12) 380 341 469 500 (2) 250 500 600

12 75 2083 1415185 230 YO (1) 60 2051 409 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 472 460 XL 485 (12) 35 (1) 60 904 (12) 190 352 500 400- - -

(2) 75 974 539 460 YO (1) 60 904 162 (12) 5(12)19 352 500 400- - -

(2) 75 974 180 208 XL 2083 1415 (12) 70 (12) 380 345 469 500 500(2) 250 600

472208 YO 2083 (12) 70 345(12) 380 469 500 (2) 250 500 600 230 XL (3) 75 2083 1415 (12) 70 345(12) 380 469 500 (2) 250 500 600200 230 YO 2083 472 (12) 70 (12) 190 345 469 500 500(2) 250 600 460 XL 539974 (12) 35 (12) 190 359 - 450500 - -

180 1(12) 35 460 YO 974 (12) 190 359 450 -500- -2051 1228208 XL (12) 70 504(12) 380 504 (2) 250 (2) 250 700 700

208 YO 2051 409 (12) 70 (12) 380 504 504 (2) 250 700(2) 250 700 (4) 60 2051 1228 (12) 70 230 XL (12) 380 504 504 (2) 250 (2) 250 700 700215

YO 2051 409230 (12) 70 (12) 380 504 504 (2) 250 (2) 250 700 700 460 904 485 (12) 35 XL (12) 190 225 225 0000 0000 300 300

(12) 35 460 YO 904 162 (12) 190 300225 225 0000 0000 300 2051 1228208 XL (2) 60 (14) 70 (14) 380 504 525 (2250 700 700(2)300

(2) 75 2083 1415 2051 409 (14) 70 700 700208 YO (2) 60 (14) 380 504 525 (2) 250 (2)300

(2) 75 2083 472240 700XL (2) 60 2051 1228 (14) 70 (14) 380 504 525 (2)250 (2)300 700230

(2) 75 2083 1415 2011230 YO (2) 60 409 (14) 70 (14) 380 504 525 (2) 250 (2)300 700 700

(2) 75 2083 472 300460 XL (2) 60 904 485 (14) 35 (14) 190 225 248 0000 250 300

12 75 974 539 904 162 250 300 300460 YO (2) 60 (14) 35 (14) 190 225 248 410

(2) 75 974 180 2083 1415 (2)300 700 700XL (16) 70 (16) 380 525 525 (2)300208 2083 1415 (2)300 700 700208 YO (16) 70 525 525 (2)300(16) 380

700 7002083 1415 (16) 70 (2300230 XL (16) 380 525 525 (2300 700 700(2300(4) 75 2083 472 (16) 70 (16) 380 525 525 (2300230 XL265

300250 300974 539 (16) 35 248 248 250XL (16) 380 460 (16) 35 300 300974 (16 380 248 250 250YO 539 248460

NOTES 1 XL Across the Line YO Star Delta 2 RLA Rated Load Amps (rated in accordance with ARI Standard 590) LRA Locked Rotor Amps 3 Wire Size Amps equal 125 of the rated load amps for the largest motor in the circuit plus 100 of the rated load amps for all other motors in the circuit per

NEC 4 Wire size based on copper conductors with 75degG insulation per NEG Table 310-16 Terminal block lugs are sized accordingly Use of oversize wiring may

not fit in terminal blocks 5 Maximum fuse size is based on 175 to 225 of the rated load amps for the largest motor in the circuit plus 100 of the rated load amps for a other motors

in the circuit per NEG VOLTAGE TOLERANCES 208V-230V min 187V Max 253V

480V Min414V Max506V

19

0

(Wd~) 3lV~ M011 ~31VM

006 009 00 OOt OOl OS L 00 L os 0 Ot

V D m (I) (I)

c D m c D o V

- m m -t o

~

~ m D-

aoao 3~nSS3~d ~3100~

APPLICATION DATA

POINT LOADING

ArMi I 1 5 1

ACWC 45 THRU 10 SC

COMPRESSOR CONDENSER SECTION SECTION

_ 2 4 bull 1

bull CA

J

Model Dimensions Size A B C D 45 91 - - -55 91 - - -70 145 - - -90 145 - - -110 60 40 160 -125 60 40 160 -135 60 40 160 -145 138 74 107 -160 13830 74 107 -185 138 129 107 -200 138 129 107 -215 106 82 106 80 240 106 82 134 107 265 133 110 134 107

1310

1310

~

1

1310

2

ACwe 110 THRU 200 Ie

COMPREIlOfl CONDENSER SECTION IECnoN

4 -

5Imiddot

ACWC 2t5 THRU 215 SC

Model Loadlnu (LBS) Size 1amp2 3amp4 5amp6 7amp8 9 amp10 45 585 765 550 - -55 705 810 635 - -70 660 890 700 - -90 1025 1500 1175 - -110 1195 635 1525 995 -125 1255 690 1835 1115 -135 1255 665 1880 1105 -145 1330 2380 2160 1450 -160 1330 2440 2280 1515 -185 1235 2575 2980 1360 -200 1275 2635 3020 1380 -215 1010 2270 2590 2240 840 240 1115 2550 2870 2715 1125 265 1380 2980 3515 2750 1175

11

II i middot 2 4 lIf 11 to L

21

TROUBLESHOOTING GUIDE

CHILLER UNIT WILL NOT START POSSIBLE CAUSE REMEDY 1 Power off 1 Check main disconnect switch

2 Main line open 2 Check main fuses

3 Incorrect wiring 3 Check the wiring diagram

4 Loose terminals 4 Tiqhten all terminals

5 Control circuit open 5 Check phase loss monitor flow switch circuit breakers temperature control low ambient thermostat low temperature thermostat remote switch etc

6 Time delay 6 Wait

COMPRESSOR HUMS BUT DOES NOT START

POSSIBLE CAUSE REMEDY

1 Low voltage 1a Check at service and unit for loss

b Consult power company

COMPRESSOR CUTS OUT ON LOW PRESSURE SAFETY CONTROL POSSIBLE CAUSE REMEDY 1 Refrigerant shortage 1 Check for leaks -- add refrigerant 2 Restriction in liquid line 2a Plugged strainer - dean or replace

b Liquid line valve partially closed - open valves fully c Expansion valve clogged or inoperative - clean or replace as

required d Solenoid valve partially open - clean or replace as required

3 Low water flow thru cooler 3 Check water flow thru cooler and correct as required

COMPRESSOR CYCLES ON HIGH PRESSURE CONTROL POSSIBLE CAUSE REMEDY 1 Compressor discharge valve partially closed 1 Open valve fully 2 Non-condensible gases in system 2 Operate condenser fans with compressors off If condenser

pressure exceeds saturated pressure corresponding to condenser entering air temperature then purge air from discharge line

3 Overcharge of R-22 3 Purge system while in operation until head pressure reaches a normal level

4 Dirty condenser 4 Clean the condenser 5 Compressor discharge check valve not operating properly 5 Replace if necessary 6 Fans not running 6 Check pressure control setting

CAUSES AND PREVENTION OF FREEZE-UP CAUSES PREVENTION 1 Improper charging 1 Charge per manufacturers recommendation

2 Improperly set safety time delay 2 Check the safety time delay low pressure control for proper setting at the beginning of each season

3 Improper chilled water circulation 3 Use an ample sized cleanable strainer in the chilled water circuit Make certain the strainer is clean to insure full flow and velocity of

chilled water It may sometimes be necessary to treat the water to prevent formation of deposits

4 Not draining for winter shutdown 4 When the system is shut down for the winter remove the drain

plugs and drain the cooler Blowout any remaining water with air

5 Improper pump shutdown 5 Make sure chiller barrel heater is working and flow switch is installed per wiring diagrams

6 Low ambient during air conditioning season 6 Make sure chiller barrel heater is working

NOTE If the ambient temperature is below 32degF freezing can be completely prevented by one of two methods

1 Drain all water from the equipment 2 Add antifreeze to the water

22

START-UP CHECK LIST

Unit Model No

Setting unit

Wiring

Piping

Alignment

Before Start-Up

After Start-Up

Yes No a Vibration isolator used

b Spring isolator adjusted for equal height c If rubber-in-shear isolators are used is unit leveled by shimming

a Power wiring complete

b Control wiring complete c Electric service adequate for load

d Power source voltage correct for motor(s) used

e Motor circuit has proper size fusetrons f System wired per diagram

g All lead connections tight h Wiring complies with local codes i Flow switch operation

a Piping complies with applicable codes b External piping independently supported c Chilled water lines insulated

a All belts adjusted and checked for tension b All pulleys checked and adjusted for proper pitch tightness and

alignment

a Open compressor discharge service valve b Open liquid valve(s) c Open suction and discharge valves to pressure gauges (if supplied) d Check rotation of all fan motors e Start auxiliary equipment (pumps fans etc) f Is crankcase heater operating Operate 24 hours prior to unit startup g Check the compressor oil level through the crankcase sight glass The oil

level should be to the top of the glass If the level is low add oil in accordance with the directions in the maintenance instruction

h Check all control settings as specified in Table 1 I Air purged from chilled water system

a Check high pressure control b Check oil temperature safety switch c Check and adjust low pressure or temperature freeze control d Check and adjust operating thermostat e Check and adjust low pressure operating control f Check and adjust expansion valve superheat g Check and adjust capacity control thermostat

23

OPERATING DATA CHILLER Voltage L-1 L-2 L-3 _ Pressure Gauge Readings 1 Suction psig 1 Discharge psig 2 Suction psig 2 Discharge _ psig 3 Suction psig 3 Discharge psig 4 Suction psig 4 Discharge _ psig High pressure switch setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-in) psig psig (Out) 4 (Cut-In) psig psig (Out) Checked Setting - Yes - No (each circuit) Low Pressure Switch Setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-In) psig psig (Out) 4 (Cut-in) psig psig (Out) Checked Setting -Yes -No (each circuit) 1 Oil Temperature Safety Switch Cut Out 2 Oil Temperature Safety Switch Cut Out 3 Oil Temperature Safety Switch Cut Out 4 Oil Temperature Safety Switch Cut Out If Star-Delta start time delay is seconds Temperature of air entering condenser F Temperature of air leaving condenser of Temperature of chilled water entering chiller OF Temperature of water (chilled) leaving chiller F Chilled water pressure entering chiller psig Chilled water pressure leaving chiller psig

MAINTENANCE Good maintenance practice will prolong the chiller life and will reduce the Ask of system breakdown and expensive service calls

A weekly check of the ACWC-SD unit requires only a few minutes and will prove beneficial in insuring long trouble free operation

WEEKLY CHECKS- with unit in operation for at least four hours 1) Check compressor oil level - At least above 12 of sight glass 2) Record suction and discharge pressures

Typical Condition R22 Ambient 95degF Return water 55degF Leaving water 45degF Suction 62 psig Discharge 270 psig

3) Record ambient temperature 4) Check liquid sight glass

Make sure liquid is clear - no bubbles 5) Check that all fans are running 6) Check entering face of condenser coil for cleanliness 7) Record voltage at unit

All of the above can be performed by building maintenance personnel If oil levels are low or any of the above checked items are questionable consult a qualified serviceman

At least once a year a qualified serviceman should check unit oil levels superheat and control operation

DUNHAM-BUSH USA

P l) bull 130 xUtUC t01 Bmgess RO~ Harrisonburg VA 22801 Phone (540) 434-0711 FAX (540) 434-~ 2118

wvvwdunham-bushcom Form No 6184

Page 18: ACWC-SD - · PDF fileACWC-SD • Screw . Type • • • Air-Cooled Packaged Chillers •• Installation, Operation, and •• • Maintenance Manual • • • •• DESCRIPTION

ELECTRICAL DATA Model Volts Type COMPRESSOR FAN MOTORS MIN CIRCUIT RECOMMENDED MAXIMUM ACWC 60 Hz of Qty RLA Starting FLA LRA AMPACITY WIRESIZE FUSESIZE

SC 3 Ph Start HP Ea Curro Ea Ea Ea Circ1 Circ2 Circ1 Circ2 Circ1 eire 2

208230 XL 1788 1040 (4) 70 (4) 380 252 - 250 - 400 -45 208230 YO (1) 50 1788 347 (4) 70 (4) 380 252 - 250 - 400 -

460 XL 737 422 (4) 35 (4) 190 106 - 2 - 175 -460 YO 737 141 (4) 35 (4) 190 106 - 2 - 175 -

208230 XL 2051 1228 (4) 70 (4) 380 284 - 300 - 450 -55 208230 YO (1) 60 2051 409 (4) 70 (4) 380 284 - 300 - 450 -

460 XL 904 485 (4) 35 (4) 190 127 - 1 - 200 -460 YO 904 162 (4) 35 (4) 190 127 - 1 - 200 -

208230 XL 2083 1415 (6) 70 (6) 380 302 350 500 -70 208230 YO (1) 75 2083 472 (6) 70 (6) 380 302 350 500 -

460 XL 974 539 (6) 35 (6) 190 143 0 225 -460 YO 974 180 (6) 35 (6 190 143 0 225 -208 XL 1788 1040 (6) 70 (6) 380 266 224 300 0000 400 400 208 YO 1788 347 (6) 70 (6) 380 266 224 300 0000 400

90 230 XL (2) 50 1788 1040 (6) 70 (6) 380 266 224 400 I300 0000 400 400 230 YO 1788 347 (6) 70 (6) 380 266 224 300 0000 400 400 460 XL 737 422 (6) 35 (6) 190 187 - 000 - 250 460 YO 737 141 (6) 35 (6) 190 187 - =1000 - 250 208 XL 2051 1228 (8) 70 (8) 380 312 256 400 300 250 208 YO 2051 409 (8) 70 (8) 380 312 256 400 300 500

110 230 XL (2) 60 2051 1228 (8) 70 (8) 380 312 256 g I350 300 SOO 450 230 YO 2051 409 (8) 70 (8) 380 312 256 350 300 500 450 460 XL 914 485 (8) 35 (8) 190 231 - 0000 - 300 460 YO 904 162 (8) 35 (8) 190 231 - 0000 - 300 -

208 XL (1) 60 2051 1228 (8) 70 (8) 380 312 260 400 300 500 450(1) 75 2083 1415

208 YO (1) 60 2051 409 (8) 70 (8) 380 312 260 400 300 500 450(1) 75 2083 472

230 XL (1) 60 2051 1228 (8) 70 (8) 380 312 260 350 300 500 450(1) 75 2083 165125

230 YO (1) 60 2051 409 (8) 70 (8) 380 02 260 350 300 500 450 (1) 75 2083 472

460 XL (1) 60 904 485 (8) 35 (8) 190 240 - 250 - 300 -(1 75 974 539

460 YO (1) 60 904 162 (8) 35 (8) 190 240 - 250 - 300 -(1) 75 974 180

208 XL 2083 1415 (8) 70 (8) 380 316 260 400 300 500 450 208 YO 2083 472 (8) 70 (8) 380 316 260 400 300 500 450

135 230 XL (2) 75 2083 1415 (8) 70 (8) 380 316 260 400 300 500 450 I 230 YO 2083 472 (8) 70 (8) 380 316 260 400 300 500 450

460 XL 974 539 (8) 35 (8) 190 247 - 250 - 300 -460 YO 974 180 (8i 35 (8) 190 247 - 250 - 300 -

208 XL (2) SO 1788 1040 (10) 70 (10) 380 326 402 400 0000 500 500(1) 60 2051 1228

208 YO (2) 50 1788 347 (10) 70 (10) 380 326 402 400 0000 500 500(1 60 2051 409

230 XL (2) 50 1788 1040 (10) 70 (10) 380 326 402 400 0000 500 500 145 (1) 60 2011 1228

230 YO (2) 50 1788 347 (10) 70 (10) 380 326 402 400 0000 500 500(1) 60 2051 409

460 XL (2) 50 737 422 (10) 35 (10) 190 295 - 350 350 --(1) 60 904 485

460 YO (2) SO 731 141 10 (35) (10)190 295 - 350 350- -(1)60 904 162

208 XL 2051 1228 (10) 70 (10) 380 326 462 400 (2)250 500 600 208 YO 2051 409 (10) 70 (10) 380 326 462 400 (2)250 500 600

160 230 XL (3) 60 2051 1228 (10) 70 (10) 380 326 462 400 (2)250 500 230 YO 2051 409 (10) 70 (10) 380 326 462 600400 (2)250 500 600 460 XL 904 485 (10) 35 (10) 190 329 - 400 - 400 460 YO 904 167 (10) 35 (10) 190 329 - 400 - 400 - I

NOTES 1 XL Across the LineYOStarDelta 2 RLA Rated LoadAmps(ratedin accordance withARI Standard 590) LRA LockedRotorAmps 3 Wire Size Amps equal125of the ratedloadampsfor the largestmotorin thecircuitplus100of the ratedloadampsfor all othermotorsin the circuit per

NEC 4 Wire size based on copperconductorswith75C insulation perNECTable310-16 Terminal block lugs are sizedaccordingly Use of oversize wiringmay

not lit in terminal blocks 5 Maximumfuse size is basedon 175to 225of the ratedloadampsfor the largestmotorin the circuitplus 100of the rated loadampsfora othermotors

in the circuit per NEC VOLTAGE TOLERANCES 208V-230V min 187VMax 253V

480V Min414V Max506V

I

18

ELECTRICAL DATA Volts Type COMPRESSORModel FAN MOTORS MINCIRCUIT RECOMMENDED MAXIMUM 60 Hz of Oty RLA Starting FLAACWC LRA AMPACITY WIRESIZE FUSE SIZE 3 Ph Start Curro EaSC HP Ea Ea Ea Cire1 Cire2 Cire1 Cire2 Cire1 Cire2 208 XL 2051(1) 60 1228 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 1415 208 YO (1) 60 2051 409 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 472 230 XL (1) 60 2051 1228 (12)70 (12) 380 341 469 500 (2) 250 500 600

12 75 2083 1415185 230 YO (1) 60 2051 409 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 472 460 XL 485 (12) 35 (1) 60 904 (12) 190 352 500 400- - -

(2) 75 974 539 460 YO (1) 60 904 162 (12) 5(12)19 352 500 400- - -

(2) 75 974 180 208 XL 2083 1415 (12) 70 (12) 380 345 469 500 500(2) 250 600

472208 YO 2083 (12) 70 345(12) 380 469 500 (2) 250 500 600 230 XL (3) 75 2083 1415 (12) 70 345(12) 380 469 500 (2) 250 500 600200 230 YO 2083 472 (12) 70 (12) 190 345 469 500 500(2) 250 600 460 XL 539974 (12) 35 (12) 190 359 - 450500 - -

180 1(12) 35 460 YO 974 (12) 190 359 450 -500- -2051 1228208 XL (12) 70 504(12) 380 504 (2) 250 (2) 250 700 700

208 YO 2051 409 (12) 70 (12) 380 504 504 (2) 250 700(2) 250 700 (4) 60 2051 1228 (12) 70 230 XL (12) 380 504 504 (2) 250 (2) 250 700 700215

YO 2051 409230 (12) 70 (12) 380 504 504 (2) 250 (2) 250 700 700 460 904 485 (12) 35 XL (12) 190 225 225 0000 0000 300 300

(12) 35 460 YO 904 162 (12) 190 300225 225 0000 0000 300 2051 1228208 XL (2) 60 (14) 70 (14) 380 504 525 (2250 700 700(2)300

(2) 75 2083 1415 2051 409 (14) 70 700 700208 YO (2) 60 (14) 380 504 525 (2) 250 (2)300

(2) 75 2083 472240 700XL (2) 60 2051 1228 (14) 70 (14) 380 504 525 (2)250 (2)300 700230

(2) 75 2083 1415 2011230 YO (2) 60 409 (14) 70 (14) 380 504 525 (2) 250 (2)300 700 700

(2) 75 2083 472 300460 XL (2) 60 904 485 (14) 35 (14) 190 225 248 0000 250 300

12 75 974 539 904 162 250 300 300460 YO (2) 60 (14) 35 (14) 190 225 248 410

(2) 75 974 180 2083 1415 (2)300 700 700XL (16) 70 (16) 380 525 525 (2)300208 2083 1415 (2)300 700 700208 YO (16) 70 525 525 (2)300(16) 380

700 7002083 1415 (16) 70 (2300230 XL (16) 380 525 525 (2300 700 700(2300(4) 75 2083 472 (16) 70 (16) 380 525 525 (2300230 XL265

300250 300974 539 (16) 35 248 248 250XL (16) 380 460 (16) 35 300 300974 (16 380 248 250 250YO 539 248460

NOTES 1 XL Across the Line YO Star Delta 2 RLA Rated Load Amps (rated in accordance with ARI Standard 590) LRA Locked Rotor Amps 3 Wire Size Amps equal 125 of the rated load amps for the largest motor in the circuit plus 100 of the rated load amps for all other motors in the circuit per

NEC 4 Wire size based on copper conductors with 75degG insulation per NEG Table 310-16 Terminal block lugs are sized accordingly Use of oversize wiring may

not fit in terminal blocks 5 Maximum fuse size is based on 175 to 225 of the rated load amps for the largest motor in the circuit plus 100 of the rated load amps for a other motors

in the circuit per NEG VOLTAGE TOLERANCES 208V-230V min 187V Max 253V

480V Min414V Max506V

19

0

(Wd~) 3lV~ M011 ~31VM

006 009 00 OOt OOl OS L 00 L os 0 Ot

V D m (I) (I)

c D m c D o V

- m m -t o

~

~ m D-

aoao 3~nSS3~d ~3100~

APPLICATION DATA

POINT LOADING

ArMi I 1 5 1

ACWC 45 THRU 10 SC

COMPRESSOR CONDENSER SECTION SECTION

_ 2 4 bull 1

bull CA

J

Model Dimensions Size A B C D 45 91 - - -55 91 - - -70 145 - - -90 145 - - -110 60 40 160 -125 60 40 160 -135 60 40 160 -145 138 74 107 -160 13830 74 107 -185 138 129 107 -200 138 129 107 -215 106 82 106 80 240 106 82 134 107 265 133 110 134 107

1310

1310

~

1

1310

2

ACwe 110 THRU 200 Ie

COMPREIlOfl CONDENSER SECTION IECnoN

4 -

5Imiddot

ACWC 2t5 THRU 215 SC

Model Loadlnu (LBS) Size 1amp2 3amp4 5amp6 7amp8 9 amp10 45 585 765 550 - -55 705 810 635 - -70 660 890 700 - -90 1025 1500 1175 - -110 1195 635 1525 995 -125 1255 690 1835 1115 -135 1255 665 1880 1105 -145 1330 2380 2160 1450 -160 1330 2440 2280 1515 -185 1235 2575 2980 1360 -200 1275 2635 3020 1380 -215 1010 2270 2590 2240 840 240 1115 2550 2870 2715 1125 265 1380 2980 3515 2750 1175

11

II i middot 2 4 lIf 11 to L

21

TROUBLESHOOTING GUIDE

CHILLER UNIT WILL NOT START POSSIBLE CAUSE REMEDY 1 Power off 1 Check main disconnect switch

2 Main line open 2 Check main fuses

3 Incorrect wiring 3 Check the wiring diagram

4 Loose terminals 4 Tiqhten all terminals

5 Control circuit open 5 Check phase loss monitor flow switch circuit breakers temperature control low ambient thermostat low temperature thermostat remote switch etc

6 Time delay 6 Wait

COMPRESSOR HUMS BUT DOES NOT START

POSSIBLE CAUSE REMEDY

1 Low voltage 1a Check at service and unit for loss

b Consult power company

COMPRESSOR CUTS OUT ON LOW PRESSURE SAFETY CONTROL POSSIBLE CAUSE REMEDY 1 Refrigerant shortage 1 Check for leaks -- add refrigerant 2 Restriction in liquid line 2a Plugged strainer - dean or replace

b Liquid line valve partially closed - open valves fully c Expansion valve clogged or inoperative - clean or replace as

required d Solenoid valve partially open - clean or replace as required

3 Low water flow thru cooler 3 Check water flow thru cooler and correct as required

COMPRESSOR CYCLES ON HIGH PRESSURE CONTROL POSSIBLE CAUSE REMEDY 1 Compressor discharge valve partially closed 1 Open valve fully 2 Non-condensible gases in system 2 Operate condenser fans with compressors off If condenser

pressure exceeds saturated pressure corresponding to condenser entering air temperature then purge air from discharge line

3 Overcharge of R-22 3 Purge system while in operation until head pressure reaches a normal level

4 Dirty condenser 4 Clean the condenser 5 Compressor discharge check valve not operating properly 5 Replace if necessary 6 Fans not running 6 Check pressure control setting

CAUSES AND PREVENTION OF FREEZE-UP CAUSES PREVENTION 1 Improper charging 1 Charge per manufacturers recommendation

2 Improperly set safety time delay 2 Check the safety time delay low pressure control for proper setting at the beginning of each season

3 Improper chilled water circulation 3 Use an ample sized cleanable strainer in the chilled water circuit Make certain the strainer is clean to insure full flow and velocity of

chilled water It may sometimes be necessary to treat the water to prevent formation of deposits

4 Not draining for winter shutdown 4 When the system is shut down for the winter remove the drain

plugs and drain the cooler Blowout any remaining water with air

5 Improper pump shutdown 5 Make sure chiller barrel heater is working and flow switch is installed per wiring diagrams

6 Low ambient during air conditioning season 6 Make sure chiller barrel heater is working

NOTE If the ambient temperature is below 32degF freezing can be completely prevented by one of two methods

1 Drain all water from the equipment 2 Add antifreeze to the water

22

START-UP CHECK LIST

Unit Model No

Setting unit

Wiring

Piping

Alignment

Before Start-Up

After Start-Up

Yes No a Vibration isolator used

b Spring isolator adjusted for equal height c If rubber-in-shear isolators are used is unit leveled by shimming

a Power wiring complete

b Control wiring complete c Electric service adequate for load

d Power source voltage correct for motor(s) used

e Motor circuit has proper size fusetrons f System wired per diagram

g All lead connections tight h Wiring complies with local codes i Flow switch operation

a Piping complies with applicable codes b External piping independently supported c Chilled water lines insulated

a All belts adjusted and checked for tension b All pulleys checked and adjusted for proper pitch tightness and

alignment

a Open compressor discharge service valve b Open liquid valve(s) c Open suction and discharge valves to pressure gauges (if supplied) d Check rotation of all fan motors e Start auxiliary equipment (pumps fans etc) f Is crankcase heater operating Operate 24 hours prior to unit startup g Check the compressor oil level through the crankcase sight glass The oil

level should be to the top of the glass If the level is low add oil in accordance with the directions in the maintenance instruction

h Check all control settings as specified in Table 1 I Air purged from chilled water system

a Check high pressure control b Check oil temperature safety switch c Check and adjust low pressure or temperature freeze control d Check and adjust operating thermostat e Check and adjust low pressure operating control f Check and adjust expansion valve superheat g Check and adjust capacity control thermostat

23

OPERATING DATA CHILLER Voltage L-1 L-2 L-3 _ Pressure Gauge Readings 1 Suction psig 1 Discharge psig 2 Suction psig 2 Discharge _ psig 3 Suction psig 3 Discharge psig 4 Suction psig 4 Discharge _ psig High pressure switch setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-in) psig psig (Out) 4 (Cut-In) psig psig (Out) Checked Setting - Yes - No (each circuit) Low Pressure Switch Setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-In) psig psig (Out) 4 (Cut-in) psig psig (Out) Checked Setting -Yes -No (each circuit) 1 Oil Temperature Safety Switch Cut Out 2 Oil Temperature Safety Switch Cut Out 3 Oil Temperature Safety Switch Cut Out 4 Oil Temperature Safety Switch Cut Out If Star-Delta start time delay is seconds Temperature of air entering condenser F Temperature of air leaving condenser of Temperature of chilled water entering chiller OF Temperature of water (chilled) leaving chiller F Chilled water pressure entering chiller psig Chilled water pressure leaving chiller psig

MAINTENANCE Good maintenance practice will prolong the chiller life and will reduce the Ask of system breakdown and expensive service calls

A weekly check of the ACWC-SD unit requires only a few minutes and will prove beneficial in insuring long trouble free operation

WEEKLY CHECKS- with unit in operation for at least four hours 1) Check compressor oil level - At least above 12 of sight glass 2) Record suction and discharge pressures

Typical Condition R22 Ambient 95degF Return water 55degF Leaving water 45degF Suction 62 psig Discharge 270 psig

3) Record ambient temperature 4) Check liquid sight glass

Make sure liquid is clear - no bubbles 5) Check that all fans are running 6) Check entering face of condenser coil for cleanliness 7) Record voltage at unit

All of the above can be performed by building maintenance personnel If oil levels are low or any of the above checked items are questionable consult a qualified serviceman

At least once a year a qualified serviceman should check unit oil levels superheat and control operation

DUNHAM-BUSH USA

P l) bull 130 xUtUC t01 Bmgess RO~ Harrisonburg VA 22801 Phone (540) 434-0711 FAX (540) 434-~ 2118

wvvwdunham-bushcom Form No 6184

Page 19: ACWC-SD - · PDF fileACWC-SD • Screw . Type • • • Air-Cooled Packaged Chillers •• Installation, Operation, and •• • Maintenance Manual • • • •• DESCRIPTION

ELECTRICAL DATA Volts Type COMPRESSORModel FAN MOTORS MINCIRCUIT RECOMMENDED MAXIMUM 60 Hz of Oty RLA Starting FLAACWC LRA AMPACITY WIRESIZE FUSE SIZE 3 Ph Start Curro EaSC HP Ea Ea Ea Cire1 Cire2 Cire1 Cire2 Cire1 Cire2 208 XL 2051(1) 60 1228 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 1415 208 YO (1) 60 2051 409 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 472 230 XL (1) 60 2051 1228 (12)70 (12) 380 341 469 500 (2) 250 500 600

12 75 2083 1415185 230 YO (1) 60 2051 409 (12) 70 (12) 380 341 469 500 (2) 250 500 600

(2) 75 2083 472 460 XL 485 (12) 35 (1) 60 904 (12) 190 352 500 400- - -

(2) 75 974 539 460 YO (1) 60 904 162 (12) 5(12)19 352 500 400- - -

(2) 75 974 180 208 XL 2083 1415 (12) 70 (12) 380 345 469 500 500(2) 250 600

472208 YO 2083 (12) 70 345(12) 380 469 500 (2) 250 500 600 230 XL (3) 75 2083 1415 (12) 70 345(12) 380 469 500 (2) 250 500 600200 230 YO 2083 472 (12) 70 (12) 190 345 469 500 500(2) 250 600 460 XL 539974 (12) 35 (12) 190 359 - 450500 - -

180 1(12) 35 460 YO 974 (12) 190 359 450 -500- -2051 1228208 XL (12) 70 504(12) 380 504 (2) 250 (2) 250 700 700

208 YO 2051 409 (12) 70 (12) 380 504 504 (2) 250 700(2) 250 700 (4) 60 2051 1228 (12) 70 230 XL (12) 380 504 504 (2) 250 (2) 250 700 700215

YO 2051 409230 (12) 70 (12) 380 504 504 (2) 250 (2) 250 700 700 460 904 485 (12) 35 XL (12) 190 225 225 0000 0000 300 300

(12) 35 460 YO 904 162 (12) 190 300225 225 0000 0000 300 2051 1228208 XL (2) 60 (14) 70 (14) 380 504 525 (2250 700 700(2)300

(2) 75 2083 1415 2051 409 (14) 70 700 700208 YO (2) 60 (14) 380 504 525 (2) 250 (2)300

(2) 75 2083 472240 700XL (2) 60 2051 1228 (14) 70 (14) 380 504 525 (2)250 (2)300 700230

(2) 75 2083 1415 2011230 YO (2) 60 409 (14) 70 (14) 380 504 525 (2) 250 (2)300 700 700

(2) 75 2083 472 300460 XL (2) 60 904 485 (14) 35 (14) 190 225 248 0000 250 300

12 75 974 539 904 162 250 300 300460 YO (2) 60 (14) 35 (14) 190 225 248 410

(2) 75 974 180 2083 1415 (2)300 700 700XL (16) 70 (16) 380 525 525 (2)300208 2083 1415 (2)300 700 700208 YO (16) 70 525 525 (2)300(16) 380

700 7002083 1415 (16) 70 (2300230 XL (16) 380 525 525 (2300 700 700(2300(4) 75 2083 472 (16) 70 (16) 380 525 525 (2300230 XL265

300250 300974 539 (16) 35 248 248 250XL (16) 380 460 (16) 35 300 300974 (16 380 248 250 250YO 539 248460

NOTES 1 XL Across the Line YO Star Delta 2 RLA Rated Load Amps (rated in accordance with ARI Standard 590) LRA Locked Rotor Amps 3 Wire Size Amps equal 125 of the rated load amps for the largest motor in the circuit plus 100 of the rated load amps for all other motors in the circuit per

NEC 4 Wire size based on copper conductors with 75degG insulation per NEG Table 310-16 Terminal block lugs are sized accordingly Use of oversize wiring may

not fit in terminal blocks 5 Maximum fuse size is based on 175 to 225 of the rated load amps for the largest motor in the circuit plus 100 of the rated load amps for a other motors

in the circuit per NEG VOLTAGE TOLERANCES 208V-230V min 187V Max 253V

480V Min414V Max506V

19

0

(Wd~) 3lV~ M011 ~31VM

006 009 00 OOt OOl OS L 00 L os 0 Ot

V D m (I) (I)

c D m c D o V

- m m -t o

~

~ m D-

aoao 3~nSS3~d ~3100~

APPLICATION DATA

POINT LOADING

ArMi I 1 5 1

ACWC 45 THRU 10 SC

COMPRESSOR CONDENSER SECTION SECTION

_ 2 4 bull 1

bull CA

J

Model Dimensions Size A B C D 45 91 - - -55 91 - - -70 145 - - -90 145 - - -110 60 40 160 -125 60 40 160 -135 60 40 160 -145 138 74 107 -160 13830 74 107 -185 138 129 107 -200 138 129 107 -215 106 82 106 80 240 106 82 134 107 265 133 110 134 107

1310

1310

~

1

1310

2

ACwe 110 THRU 200 Ie

COMPREIlOfl CONDENSER SECTION IECnoN

4 -

5Imiddot

ACWC 2t5 THRU 215 SC

Model Loadlnu (LBS) Size 1amp2 3amp4 5amp6 7amp8 9 amp10 45 585 765 550 - -55 705 810 635 - -70 660 890 700 - -90 1025 1500 1175 - -110 1195 635 1525 995 -125 1255 690 1835 1115 -135 1255 665 1880 1105 -145 1330 2380 2160 1450 -160 1330 2440 2280 1515 -185 1235 2575 2980 1360 -200 1275 2635 3020 1380 -215 1010 2270 2590 2240 840 240 1115 2550 2870 2715 1125 265 1380 2980 3515 2750 1175

11

II i middot 2 4 lIf 11 to L

21

TROUBLESHOOTING GUIDE

CHILLER UNIT WILL NOT START POSSIBLE CAUSE REMEDY 1 Power off 1 Check main disconnect switch

2 Main line open 2 Check main fuses

3 Incorrect wiring 3 Check the wiring diagram

4 Loose terminals 4 Tiqhten all terminals

5 Control circuit open 5 Check phase loss monitor flow switch circuit breakers temperature control low ambient thermostat low temperature thermostat remote switch etc

6 Time delay 6 Wait

COMPRESSOR HUMS BUT DOES NOT START

POSSIBLE CAUSE REMEDY

1 Low voltage 1a Check at service and unit for loss

b Consult power company

COMPRESSOR CUTS OUT ON LOW PRESSURE SAFETY CONTROL POSSIBLE CAUSE REMEDY 1 Refrigerant shortage 1 Check for leaks -- add refrigerant 2 Restriction in liquid line 2a Plugged strainer - dean or replace

b Liquid line valve partially closed - open valves fully c Expansion valve clogged or inoperative - clean or replace as

required d Solenoid valve partially open - clean or replace as required

3 Low water flow thru cooler 3 Check water flow thru cooler and correct as required

COMPRESSOR CYCLES ON HIGH PRESSURE CONTROL POSSIBLE CAUSE REMEDY 1 Compressor discharge valve partially closed 1 Open valve fully 2 Non-condensible gases in system 2 Operate condenser fans with compressors off If condenser

pressure exceeds saturated pressure corresponding to condenser entering air temperature then purge air from discharge line

3 Overcharge of R-22 3 Purge system while in operation until head pressure reaches a normal level

4 Dirty condenser 4 Clean the condenser 5 Compressor discharge check valve not operating properly 5 Replace if necessary 6 Fans not running 6 Check pressure control setting

CAUSES AND PREVENTION OF FREEZE-UP CAUSES PREVENTION 1 Improper charging 1 Charge per manufacturers recommendation

2 Improperly set safety time delay 2 Check the safety time delay low pressure control for proper setting at the beginning of each season

3 Improper chilled water circulation 3 Use an ample sized cleanable strainer in the chilled water circuit Make certain the strainer is clean to insure full flow and velocity of

chilled water It may sometimes be necessary to treat the water to prevent formation of deposits

4 Not draining for winter shutdown 4 When the system is shut down for the winter remove the drain

plugs and drain the cooler Blowout any remaining water with air

5 Improper pump shutdown 5 Make sure chiller barrel heater is working and flow switch is installed per wiring diagrams

6 Low ambient during air conditioning season 6 Make sure chiller barrel heater is working

NOTE If the ambient temperature is below 32degF freezing can be completely prevented by one of two methods

1 Drain all water from the equipment 2 Add antifreeze to the water

22

START-UP CHECK LIST

Unit Model No

Setting unit

Wiring

Piping

Alignment

Before Start-Up

After Start-Up

Yes No a Vibration isolator used

b Spring isolator adjusted for equal height c If rubber-in-shear isolators are used is unit leveled by shimming

a Power wiring complete

b Control wiring complete c Electric service adequate for load

d Power source voltage correct for motor(s) used

e Motor circuit has proper size fusetrons f System wired per diagram

g All lead connections tight h Wiring complies with local codes i Flow switch operation

a Piping complies with applicable codes b External piping independently supported c Chilled water lines insulated

a All belts adjusted and checked for tension b All pulleys checked and adjusted for proper pitch tightness and

alignment

a Open compressor discharge service valve b Open liquid valve(s) c Open suction and discharge valves to pressure gauges (if supplied) d Check rotation of all fan motors e Start auxiliary equipment (pumps fans etc) f Is crankcase heater operating Operate 24 hours prior to unit startup g Check the compressor oil level through the crankcase sight glass The oil

level should be to the top of the glass If the level is low add oil in accordance with the directions in the maintenance instruction

h Check all control settings as specified in Table 1 I Air purged from chilled water system

a Check high pressure control b Check oil temperature safety switch c Check and adjust low pressure or temperature freeze control d Check and adjust operating thermostat e Check and adjust low pressure operating control f Check and adjust expansion valve superheat g Check and adjust capacity control thermostat

23

OPERATING DATA CHILLER Voltage L-1 L-2 L-3 _ Pressure Gauge Readings 1 Suction psig 1 Discharge psig 2 Suction psig 2 Discharge _ psig 3 Suction psig 3 Discharge psig 4 Suction psig 4 Discharge _ psig High pressure switch setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-in) psig psig (Out) 4 (Cut-In) psig psig (Out) Checked Setting - Yes - No (each circuit) Low Pressure Switch Setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-In) psig psig (Out) 4 (Cut-in) psig psig (Out) Checked Setting -Yes -No (each circuit) 1 Oil Temperature Safety Switch Cut Out 2 Oil Temperature Safety Switch Cut Out 3 Oil Temperature Safety Switch Cut Out 4 Oil Temperature Safety Switch Cut Out If Star-Delta start time delay is seconds Temperature of air entering condenser F Temperature of air leaving condenser of Temperature of chilled water entering chiller OF Temperature of water (chilled) leaving chiller F Chilled water pressure entering chiller psig Chilled water pressure leaving chiller psig

MAINTENANCE Good maintenance practice will prolong the chiller life and will reduce the Ask of system breakdown and expensive service calls

A weekly check of the ACWC-SD unit requires only a few minutes and will prove beneficial in insuring long trouble free operation

WEEKLY CHECKS- with unit in operation for at least four hours 1) Check compressor oil level - At least above 12 of sight glass 2) Record suction and discharge pressures

Typical Condition R22 Ambient 95degF Return water 55degF Leaving water 45degF Suction 62 psig Discharge 270 psig

3) Record ambient temperature 4) Check liquid sight glass

Make sure liquid is clear - no bubbles 5) Check that all fans are running 6) Check entering face of condenser coil for cleanliness 7) Record voltage at unit

All of the above can be performed by building maintenance personnel If oil levels are low or any of the above checked items are questionable consult a qualified serviceman

At least once a year a qualified serviceman should check unit oil levels superheat and control operation

DUNHAM-BUSH USA

P l) bull 130 xUtUC t01 Bmgess RO~ Harrisonburg VA 22801 Phone (540) 434-0711 FAX (540) 434-~ 2118

wvvwdunham-bushcom Form No 6184

Page 20: ACWC-SD - · PDF fileACWC-SD • Screw . Type • • • Air-Cooled Packaged Chillers •• Installation, Operation, and •• • Maintenance Manual • • • •• DESCRIPTION

0

(Wd~) 3lV~ M011 ~31VM

006 009 00 OOt OOl OS L 00 L os 0 Ot

V D m (I) (I)

c D m c D o V

- m m -t o

~

~ m D-

aoao 3~nSS3~d ~3100~

APPLICATION DATA

POINT LOADING

ArMi I 1 5 1

ACWC 45 THRU 10 SC

COMPRESSOR CONDENSER SECTION SECTION

_ 2 4 bull 1

bull CA

J

Model Dimensions Size A B C D 45 91 - - -55 91 - - -70 145 - - -90 145 - - -110 60 40 160 -125 60 40 160 -135 60 40 160 -145 138 74 107 -160 13830 74 107 -185 138 129 107 -200 138 129 107 -215 106 82 106 80 240 106 82 134 107 265 133 110 134 107

1310

1310

~

1

1310

2

ACwe 110 THRU 200 Ie

COMPREIlOfl CONDENSER SECTION IECnoN

4 -

5Imiddot

ACWC 2t5 THRU 215 SC

Model Loadlnu (LBS) Size 1amp2 3amp4 5amp6 7amp8 9 amp10 45 585 765 550 - -55 705 810 635 - -70 660 890 700 - -90 1025 1500 1175 - -110 1195 635 1525 995 -125 1255 690 1835 1115 -135 1255 665 1880 1105 -145 1330 2380 2160 1450 -160 1330 2440 2280 1515 -185 1235 2575 2980 1360 -200 1275 2635 3020 1380 -215 1010 2270 2590 2240 840 240 1115 2550 2870 2715 1125 265 1380 2980 3515 2750 1175

11

II i middot 2 4 lIf 11 to L

21

TROUBLESHOOTING GUIDE

CHILLER UNIT WILL NOT START POSSIBLE CAUSE REMEDY 1 Power off 1 Check main disconnect switch

2 Main line open 2 Check main fuses

3 Incorrect wiring 3 Check the wiring diagram

4 Loose terminals 4 Tiqhten all terminals

5 Control circuit open 5 Check phase loss monitor flow switch circuit breakers temperature control low ambient thermostat low temperature thermostat remote switch etc

6 Time delay 6 Wait

COMPRESSOR HUMS BUT DOES NOT START

POSSIBLE CAUSE REMEDY

1 Low voltage 1a Check at service and unit for loss

b Consult power company

COMPRESSOR CUTS OUT ON LOW PRESSURE SAFETY CONTROL POSSIBLE CAUSE REMEDY 1 Refrigerant shortage 1 Check for leaks -- add refrigerant 2 Restriction in liquid line 2a Plugged strainer - dean or replace

b Liquid line valve partially closed - open valves fully c Expansion valve clogged or inoperative - clean or replace as

required d Solenoid valve partially open - clean or replace as required

3 Low water flow thru cooler 3 Check water flow thru cooler and correct as required

COMPRESSOR CYCLES ON HIGH PRESSURE CONTROL POSSIBLE CAUSE REMEDY 1 Compressor discharge valve partially closed 1 Open valve fully 2 Non-condensible gases in system 2 Operate condenser fans with compressors off If condenser

pressure exceeds saturated pressure corresponding to condenser entering air temperature then purge air from discharge line

3 Overcharge of R-22 3 Purge system while in operation until head pressure reaches a normal level

4 Dirty condenser 4 Clean the condenser 5 Compressor discharge check valve not operating properly 5 Replace if necessary 6 Fans not running 6 Check pressure control setting

CAUSES AND PREVENTION OF FREEZE-UP CAUSES PREVENTION 1 Improper charging 1 Charge per manufacturers recommendation

2 Improperly set safety time delay 2 Check the safety time delay low pressure control for proper setting at the beginning of each season

3 Improper chilled water circulation 3 Use an ample sized cleanable strainer in the chilled water circuit Make certain the strainer is clean to insure full flow and velocity of

chilled water It may sometimes be necessary to treat the water to prevent formation of deposits

4 Not draining for winter shutdown 4 When the system is shut down for the winter remove the drain

plugs and drain the cooler Blowout any remaining water with air

5 Improper pump shutdown 5 Make sure chiller barrel heater is working and flow switch is installed per wiring diagrams

6 Low ambient during air conditioning season 6 Make sure chiller barrel heater is working

NOTE If the ambient temperature is below 32degF freezing can be completely prevented by one of two methods

1 Drain all water from the equipment 2 Add antifreeze to the water

22

START-UP CHECK LIST

Unit Model No

Setting unit

Wiring

Piping

Alignment

Before Start-Up

After Start-Up

Yes No a Vibration isolator used

b Spring isolator adjusted for equal height c If rubber-in-shear isolators are used is unit leveled by shimming

a Power wiring complete

b Control wiring complete c Electric service adequate for load

d Power source voltage correct for motor(s) used

e Motor circuit has proper size fusetrons f System wired per diagram

g All lead connections tight h Wiring complies with local codes i Flow switch operation

a Piping complies with applicable codes b External piping independently supported c Chilled water lines insulated

a All belts adjusted and checked for tension b All pulleys checked and adjusted for proper pitch tightness and

alignment

a Open compressor discharge service valve b Open liquid valve(s) c Open suction and discharge valves to pressure gauges (if supplied) d Check rotation of all fan motors e Start auxiliary equipment (pumps fans etc) f Is crankcase heater operating Operate 24 hours prior to unit startup g Check the compressor oil level through the crankcase sight glass The oil

level should be to the top of the glass If the level is low add oil in accordance with the directions in the maintenance instruction

h Check all control settings as specified in Table 1 I Air purged from chilled water system

a Check high pressure control b Check oil temperature safety switch c Check and adjust low pressure or temperature freeze control d Check and adjust operating thermostat e Check and adjust low pressure operating control f Check and adjust expansion valve superheat g Check and adjust capacity control thermostat

23

OPERATING DATA CHILLER Voltage L-1 L-2 L-3 _ Pressure Gauge Readings 1 Suction psig 1 Discharge psig 2 Suction psig 2 Discharge _ psig 3 Suction psig 3 Discharge psig 4 Suction psig 4 Discharge _ psig High pressure switch setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-in) psig psig (Out) 4 (Cut-In) psig psig (Out) Checked Setting - Yes - No (each circuit) Low Pressure Switch Setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-In) psig psig (Out) 4 (Cut-in) psig psig (Out) Checked Setting -Yes -No (each circuit) 1 Oil Temperature Safety Switch Cut Out 2 Oil Temperature Safety Switch Cut Out 3 Oil Temperature Safety Switch Cut Out 4 Oil Temperature Safety Switch Cut Out If Star-Delta start time delay is seconds Temperature of air entering condenser F Temperature of air leaving condenser of Temperature of chilled water entering chiller OF Temperature of water (chilled) leaving chiller F Chilled water pressure entering chiller psig Chilled water pressure leaving chiller psig

MAINTENANCE Good maintenance practice will prolong the chiller life and will reduce the Ask of system breakdown and expensive service calls

A weekly check of the ACWC-SD unit requires only a few minutes and will prove beneficial in insuring long trouble free operation

WEEKLY CHECKS- with unit in operation for at least four hours 1) Check compressor oil level - At least above 12 of sight glass 2) Record suction and discharge pressures

Typical Condition R22 Ambient 95degF Return water 55degF Leaving water 45degF Suction 62 psig Discharge 270 psig

3) Record ambient temperature 4) Check liquid sight glass

Make sure liquid is clear - no bubbles 5) Check that all fans are running 6) Check entering face of condenser coil for cleanliness 7) Record voltage at unit

All of the above can be performed by building maintenance personnel If oil levels are low or any of the above checked items are questionable consult a qualified serviceman

At least once a year a qualified serviceman should check unit oil levels superheat and control operation

DUNHAM-BUSH USA

P l) bull 130 xUtUC t01 Bmgess RO~ Harrisonburg VA 22801 Phone (540) 434-0711 FAX (540) 434-~ 2118

wvvwdunham-bushcom Form No 6184

Page 21: ACWC-SD - · PDF fileACWC-SD • Screw . Type • • • Air-Cooled Packaged Chillers •• Installation, Operation, and •• • Maintenance Manual • • • •• DESCRIPTION

APPLICATION DATA

POINT LOADING

ArMi I 1 5 1

ACWC 45 THRU 10 SC

COMPRESSOR CONDENSER SECTION SECTION

_ 2 4 bull 1

bull CA

J

Model Dimensions Size A B C D 45 91 - - -55 91 - - -70 145 - - -90 145 - - -110 60 40 160 -125 60 40 160 -135 60 40 160 -145 138 74 107 -160 13830 74 107 -185 138 129 107 -200 138 129 107 -215 106 82 106 80 240 106 82 134 107 265 133 110 134 107

1310

1310

~

1

1310

2

ACwe 110 THRU 200 Ie

COMPREIlOfl CONDENSER SECTION IECnoN

4 -

5Imiddot

ACWC 2t5 THRU 215 SC

Model Loadlnu (LBS) Size 1amp2 3amp4 5amp6 7amp8 9 amp10 45 585 765 550 - -55 705 810 635 - -70 660 890 700 - -90 1025 1500 1175 - -110 1195 635 1525 995 -125 1255 690 1835 1115 -135 1255 665 1880 1105 -145 1330 2380 2160 1450 -160 1330 2440 2280 1515 -185 1235 2575 2980 1360 -200 1275 2635 3020 1380 -215 1010 2270 2590 2240 840 240 1115 2550 2870 2715 1125 265 1380 2980 3515 2750 1175

11

II i middot 2 4 lIf 11 to L

21

TROUBLESHOOTING GUIDE

CHILLER UNIT WILL NOT START POSSIBLE CAUSE REMEDY 1 Power off 1 Check main disconnect switch

2 Main line open 2 Check main fuses

3 Incorrect wiring 3 Check the wiring diagram

4 Loose terminals 4 Tiqhten all terminals

5 Control circuit open 5 Check phase loss monitor flow switch circuit breakers temperature control low ambient thermostat low temperature thermostat remote switch etc

6 Time delay 6 Wait

COMPRESSOR HUMS BUT DOES NOT START

POSSIBLE CAUSE REMEDY

1 Low voltage 1a Check at service and unit for loss

b Consult power company

COMPRESSOR CUTS OUT ON LOW PRESSURE SAFETY CONTROL POSSIBLE CAUSE REMEDY 1 Refrigerant shortage 1 Check for leaks -- add refrigerant 2 Restriction in liquid line 2a Plugged strainer - dean or replace

b Liquid line valve partially closed - open valves fully c Expansion valve clogged or inoperative - clean or replace as

required d Solenoid valve partially open - clean or replace as required

3 Low water flow thru cooler 3 Check water flow thru cooler and correct as required

COMPRESSOR CYCLES ON HIGH PRESSURE CONTROL POSSIBLE CAUSE REMEDY 1 Compressor discharge valve partially closed 1 Open valve fully 2 Non-condensible gases in system 2 Operate condenser fans with compressors off If condenser

pressure exceeds saturated pressure corresponding to condenser entering air temperature then purge air from discharge line

3 Overcharge of R-22 3 Purge system while in operation until head pressure reaches a normal level

4 Dirty condenser 4 Clean the condenser 5 Compressor discharge check valve not operating properly 5 Replace if necessary 6 Fans not running 6 Check pressure control setting

CAUSES AND PREVENTION OF FREEZE-UP CAUSES PREVENTION 1 Improper charging 1 Charge per manufacturers recommendation

2 Improperly set safety time delay 2 Check the safety time delay low pressure control for proper setting at the beginning of each season

3 Improper chilled water circulation 3 Use an ample sized cleanable strainer in the chilled water circuit Make certain the strainer is clean to insure full flow and velocity of

chilled water It may sometimes be necessary to treat the water to prevent formation of deposits

4 Not draining for winter shutdown 4 When the system is shut down for the winter remove the drain

plugs and drain the cooler Blowout any remaining water with air

5 Improper pump shutdown 5 Make sure chiller barrel heater is working and flow switch is installed per wiring diagrams

6 Low ambient during air conditioning season 6 Make sure chiller barrel heater is working

NOTE If the ambient temperature is below 32degF freezing can be completely prevented by one of two methods

1 Drain all water from the equipment 2 Add antifreeze to the water

22

START-UP CHECK LIST

Unit Model No

Setting unit

Wiring

Piping

Alignment

Before Start-Up

After Start-Up

Yes No a Vibration isolator used

b Spring isolator adjusted for equal height c If rubber-in-shear isolators are used is unit leveled by shimming

a Power wiring complete

b Control wiring complete c Electric service adequate for load

d Power source voltage correct for motor(s) used

e Motor circuit has proper size fusetrons f System wired per diagram

g All lead connections tight h Wiring complies with local codes i Flow switch operation

a Piping complies with applicable codes b External piping independently supported c Chilled water lines insulated

a All belts adjusted and checked for tension b All pulleys checked and adjusted for proper pitch tightness and

alignment

a Open compressor discharge service valve b Open liquid valve(s) c Open suction and discharge valves to pressure gauges (if supplied) d Check rotation of all fan motors e Start auxiliary equipment (pumps fans etc) f Is crankcase heater operating Operate 24 hours prior to unit startup g Check the compressor oil level through the crankcase sight glass The oil

level should be to the top of the glass If the level is low add oil in accordance with the directions in the maintenance instruction

h Check all control settings as specified in Table 1 I Air purged from chilled water system

a Check high pressure control b Check oil temperature safety switch c Check and adjust low pressure or temperature freeze control d Check and adjust operating thermostat e Check and adjust low pressure operating control f Check and adjust expansion valve superheat g Check and adjust capacity control thermostat

23

OPERATING DATA CHILLER Voltage L-1 L-2 L-3 _ Pressure Gauge Readings 1 Suction psig 1 Discharge psig 2 Suction psig 2 Discharge _ psig 3 Suction psig 3 Discharge psig 4 Suction psig 4 Discharge _ psig High pressure switch setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-in) psig psig (Out) 4 (Cut-In) psig psig (Out) Checked Setting - Yes - No (each circuit) Low Pressure Switch Setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-In) psig psig (Out) 4 (Cut-in) psig psig (Out) Checked Setting -Yes -No (each circuit) 1 Oil Temperature Safety Switch Cut Out 2 Oil Temperature Safety Switch Cut Out 3 Oil Temperature Safety Switch Cut Out 4 Oil Temperature Safety Switch Cut Out If Star-Delta start time delay is seconds Temperature of air entering condenser F Temperature of air leaving condenser of Temperature of chilled water entering chiller OF Temperature of water (chilled) leaving chiller F Chilled water pressure entering chiller psig Chilled water pressure leaving chiller psig

MAINTENANCE Good maintenance practice will prolong the chiller life and will reduce the Ask of system breakdown and expensive service calls

A weekly check of the ACWC-SD unit requires only a few minutes and will prove beneficial in insuring long trouble free operation

WEEKLY CHECKS- with unit in operation for at least four hours 1) Check compressor oil level - At least above 12 of sight glass 2) Record suction and discharge pressures

Typical Condition R22 Ambient 95degF Return water 55degF Leaving water 45degF Suction 62 psig Discharge 270 psig

3) Record ambient temperature 4) Check liquid sight glass

Make sure liquid is clear - no bubbles 5) Check that all fans are running 6) Check entering face of condenser coil for cleanliness 7) Record voltage at unit

All of the above can be performed by building maintenance personnel If oil levels are low or any of the above checked items are questionable consult a qualified serviceman

At least once a year a qualified serviceman should check unit oil levels superheat and control operation

DUNHAM-BUSH USA

P l) bull 130 xUtUC t01 Bmgess RO~ Harrisonburg VA 22801 Phone (540) 434-0711 FAX (540) 434-~ 2118

wvvwdunham-bushcom Form No 6184

Page 22: ACWC-SD - · PDF fileACWC-SD • Screw . Type • • • Air-Cooled Packaged Chillers •• Installation, Operation, and •• • Maintenance Manual • • • •• DESCRIPTION

TROUBLESHOOTING GUIDE

CHILLER UNIT WILL NOT START POSSIBLE CAUSE REMEDY 1 Power off 1 Check main disconnect switch

2 Main line open 2 Check main fuses

3 Incorrect wiring 3 Check the wiring diagram

4 Loose terminals 4 Tiqhten all terminals

5 Control circuit open 5 Check phase loss monitor flow switch circuit breakers temperature control low ambient thermostat low temperature thermostat remote switch etc

6 Time delay 6 Wait

COMPRESSOR HUMS BUT DOES NOT START

POSSIBLE CAUSE REMEDY

1 Low voltage 1a Check at service and unit for loss

b Consult power company

COMPRESSOR CUTS OUT ON LOW PRESSURE SAFETY CONTROL POSSIBLE CAUSE REMEDY 1 Refrigerant shortage 1 Check for leaks -- add refrigerant 2 Restriction in liquid line 2a Plugged strainer - dean or replace

b Liquid line valve partially closed - open valves fully c Expansion valve clogged or inoperative - clean or replace as

required d Solenoid valve partially open - clean or replace as required

3 Low water flow thru cooler 3 Check water flow thru cooler and correct as required

COMPRESSOR CYCLES ON HIGH PRESSURE CONTROL POSSIBLE CAUSE REMEDY 1 Compressor discharge valve partially closed 1 Open valve fully 2 Non-condensible gases in system 2 Operate condenser fans with compressors off If condenser

pressure exceeds saturated pressure corresponding to condenser entering air temperature then purge air from discharge line

3 Overcharge of R-22 3 Purge system while in operation until head pressure reaches a normal level

4 Dirty condenser 4 Clean the condenser 5 Compressor discharge check valve not operating properly 5 Replace if necessary 6 Fans not running 6 Check pressure control setting

CAUSES AND PREVENTION OF FREEZE-UP CAUSES PREVENTION 1 Improper charging 1 Charge per manufacturers recommendation

2 Improperly set safety time delay 2 Check the safety time delay low pressure control for proper setting at the beginning of each season

3 Improper chilled water circulation 3 Use an ample sized cleanable strainer in the chilled water circuit Make certain the strainer is clean to insure full flow and velocity of

chilled water It may sometimes be necessary to treat the water to prevent formation of deposits

4 Not draining for winter shutdown 4 When the system is shut down for the winter remove the drain

plugs and drain the cooler Blowout any remaining water with air

5 Improper pump shutdown 5 Make sure chiller barrel heater is working and flow switch is installed per wiring diagrams

6 Low ambient during air conditioning season 6 Make sure chiller barrel heater is working

NOTE If the ambient temperature is below 32degF freezing can be completely prevented by one of two methods

1 Drain all water from the equipment 2 Add antifreeze to the water

22

START-UP CHECK LIST

Unit Model No

Setting unit

Wiring

Piping

Alignment

Before Start-Up

After Start-Up

Yes No a Vibration isolator used

b Spring isolator adjusted for equal height c If rubber-in-shear isolators are used is unit leveled by shimming

a Power wiring complete

b Control wiring complete c Electric service adequate for load

d Power source voltage correct for motor(s) used

e Motor circuit has proper size fusetrons f System wired per diagram

g All lead connections tight h Wiring complies with local codes i Flow switch operation

a Piping complies with applicable codes b External piping independently supported c Chilled water lines insulated

a All belts adjusted and checked for tension b All pulleys checked and adjusted for proper pitch tightness and

alignment

a Open compressor discharge service valve b Open liquid valve(s) c Open suction and discharge valves to pressure gauges (if supplied) d Check rotation of all fan motors e Start auxiliary equipment (pumps fans etc) f Is crankcase heater operating Operate 24 hours prior to unit startup g Check the compressor oil level through the crankcase sight glass The oil

level should be to the top of the glass If the level is low add oil in accordance with the directions in the maintenance instruction

h Check all control settings as specified in Table 1 I Air purged from chilled water system

a Check high pressure control b Check oil temperature safety switch c Check and adjust low pressure or temperature freeze control d Check and adjust operating thermostat e Check and adjust low pressure operating control f Check and adjust expansion valve superheat g Check and adjust capacity control thermostat

23

OPERATING DATA CHILLER Voltage L-1 L-2 L-3 _ Pressure Gauge Readings 1 Suction psig 1 Discharge psig 2 Suction psig 2 Discharge _ psig 3 Suction psig 3 Discharge psig 4 Suction psig 4 Discharge _ psig High pressure switch setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-in) psig psig (Out) 4 (Cut-In) psig psig (Out) Checked Setting - Yes - No (each circuit) Low Pressure Switch Setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-In) psig psig (Out) 4 (Cut-in) psig psig (Out) Checked Setting -Yes -No (each circuit) 1 Oil Temperature Safety Switch Cut Out 2 Oil Temperature Safety Switch Cut Out 3 Oil Temperature Safety Switch Cut Out 4 Oil Temperature Safety Switch Cut Out If Star-Delta start time delay is seconds Temperature of air entering condenser F Temperature of air leaving condenser of Temperature of chilled water entering chiller OF Temperature of water (chilled) leaving chiller F Chilled water pressure entering chiller psig Chilled water pressure leaving chiller psig

MAINTENANCE Good maintenance practice will prolong the chiller life and will reduce the Ask of system breakdown and expensive service calls

A weekly check of the ACWC-SD unit requires only a few minutes and will prove beneficial in insuring long trouble free operation

WEEKLY CHECKS- with unit in operation for at least four hours 1) Check compressor oil level - At least above 12 of sight glass 2) Record suction and discharge pressures

Typical Condition R22 Ambient 95degF Return water 55degF Leaving water 45degF Suction 62 psig Discharge 270 psig

3) Record ambient temperature 4) Check liquid sight glass

Make sure liquid is clear - no bubbles 5) Check that all fans are running 6) Check entering face of condenser coil for cleanliness 7) Record voltage at unit

All of the above can be performed by building maintenance personnel If oil levels are low or any of the above checked items are questionable consult a qualified serviceman

At least once a year a qualified serviceman should check unit oil levels superheat and control operation

DUNHAM-BUSH USA

P l) bull 130 xUtUC t01 Bmgess RO~ Harrisonburg VA 22801 Phone (540) 434-0711 FAX (540) 434-~ 2118

wvvwdunham-bushcom Form No 6184

Page 23: ACWC-SD - · PDF fileACWC-SD • Screw . Type • • • Air-Cooled Packaged Chillers •• Installation, Operation, and •• • Maintenance Manual • • • •• DESCRIPTION

START-UP CHECK LIST

Unit Model No

Setting unit

Wiring

Piping

Alignment

Before Start-Up

After Start-Up

Yes No a Vibration isolator used

b Spring isolator adjusted for equal height c If rubber-in-shear isolators are used is unit leveled by shimming

a Power wiring complete

b Control wiring complete c Electric service adequate for load

d Power source voltage correct for motor(s) used

e Motor circuit has proper size fusetrons f System wired per diagram

g All lead connections tight h Wiring complies with local codes i Flow switch operation

a Piping complies with applicable codes b External piping independently supported c Chilled water lines insulated

a All belts adjusted and checked for tension b All pulleys checked and adjusted for proper pitch tightness and

alignment

a Open compressor discharge service valve b Open liquid valve(s) c Open suction and discharge valves to pressure gauges (if supplied) d Check rotation of all fan motors e Start auxiliary equipment (pumps fans etc) f Is crankcase heater operating Operate 24 hours prior to unit startup g Check the compressor oil level through the crankcase sight glass The oil

level should be to the top of the glass If the level is low add oil in accordance with the directions in the maintenance instruction

h Check all control settings as specified in Table 1 I Air purged from chilled water system

a Check high pressure control b Check oil temperature safety switch c Check and adjust low pressure or temperature freeze control d Check and adjust operating thermostat e Check and adjust low pressure operating control f Check and adjust expansion valve superheat g Check and adjust capacity control thermostat

23

OPERATING DATA CHILLER Voltage L-1 L-2 L-3 _ Pressure Gauge Readings 1 Suction psig 1 Discharge psig 2 Suction psig 2 Discharge _ psig 3 Suction psig 3 Discharge psig 4 Suction psig 4 Discharge _ psig High pressure switch setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-in) psig psig (Out) 4 (Cut-In) psig psig (Out) Checked Setting - Yes - No (each circuit) Low Pressure Switch Setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-In) psig psig (Out) 4 (Cut-in) psig psig (Out) Checked Setting -Yes -No (each circuit) 1 Oil Temperature Safety Switch Cut Out 2 Oil Temperature Safety Switch Cut Out 3 Oil Temperature Safety Switch Cut Out 4 Oil Temperature Safety Switch Cut Out If Star-Delta start time delay is seconds Temperature of air entering condenser F Temperature of air leaving condenser of Temperature of chilled water entering chiller OF Temperature of water (chilled) leaving chiller F Chilled water pressure entering chiller psig Chilled water pressure leaving chiller psig

MAINTENANCE Good maintenance practice will prolong the chiller life and will reduce the Ask of system breakdown and expensive service calls

A weekly check of the ACWC-SD unit requires only a few minutes and will prove beneficial in insuring long trouble free operation

WEEKLY CHECKS- with unit in operation for at least four hours 1) Check compressor oil level - At least above 12 of sight glass 2) Record suction and discharge pressures

Typical Condition R22 Ambient 95degF Return water 55degF Leaving water 45degF Suction 62 psig Discharge 270 psig

3) Record ambient temperature 4) Check liquid sight glass

Make sure liquid is clear - no bubbles 5) Check that all fans are running 6) Check entering face of condenser coil for cleanliness 7) Record voltage at unit

All of the above can be performed by building maintenance personnel If oil levels are low or any of the above checked items are questionable consult a qualified serviceman

At least once a year a qualified serviceman should check unit oil levels superheat and control operation

DUNHAM-BUSH USA

P l) bull 130 xUtUC t01 Bmgess RO~ Harrisonburg VA 22801 Phone (540) 434-0711 FAX (540) 434-~ 2118

wvvwdunham-bushcom Form No 6184

Page 24: ACWC-SD - · PDF fileACWC-SD • Screw . Type • • • Air-Cooled Packaged Chillers •• Installation, Operation, and •• • Maintenance Manual • • • •• DESCRIPTION

OPERATING DATA CHILLER Voltage L-1 L-2 L-3 _ Pressure Gauge Readings 1 Suction psig 1 Discharge psig 2 Suction psig 2 Discharge _ psig 3 Suction psig 3 Discharge psig 4 Suction psig 4 Discharge _ psig High pressure switch setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-in) psig psig (Out) 4 (Cut-In) psig psig (Out) Checked Setting - Yes - No (each circuit) Low Pressure Switch Setting 1 (Cut-in) psig psig (Out) 2 (Cut-in) psig psig (Out) 3 (Cut-In) psig psig (Out) 4 (Cut-in) psig psig (Out) Checked Setting -Yes -No (each circuit) 1 Oil Temperature Safety Switch Cut Out 2 Oil Temperature Safety Switch Cut Out 3 Oil Temperature Safety Switch Cut Out 4 Oil Temperature Safety Switch Cut Out If Star-Delta start time delay is seconds Temperature of air entering condenser F Temperature of air leaving condenser of Temperature of chilled water entering chiller OF Temperature of water (chilled) leaving chiller F Chilled water pressure entering chiller psig Chilled water pressure leaving chiller psig

MAINTENANCE Good maintenance practice will prolong the chiller life and will reduce the Ask of system breakdown and expensive service calls

A weekly check of the ACWC-SD unit requires only a few minutes and will prove beneficial in insuring long trouble free operation

WEEKLY CHECKS- with unit in operation for at least four hours 1) Check compressor oil level - At least above 12 of sight glass 2) Record suction and discharge pressures

Typical Condition R22 Ambient 95degF Return water 55degF Leaving water 45degF Suction 62 psig Discharge 270 psig

3) Record ambient temperature 4) Check liquid sight glass

Make sure liquid is clear - no bubbles 5) Check that all fans are running 6) Check entering face of condenser coil for cleanliness 7) Record voltage at unit

All of the above can be performed by building maintenance personnel If oil levels are low or any of the above checked items are questionable consult a qualified serviceman

At least once a year a qualified serviceman should check unit oil levels superheat and control operation

DUNHAM-BUSH USA

P l) bull 130 xUtUC t01 Bmgess RO~ Harrisonburg VA 22801 Phone (540) 434-0711 FAX (540) 434-~ 2118

wvvwdunham-bushcom Form No 6184