accsesory 11bg for asco® series 300 _ kit installation _ 381339-252 e _ asco™.pdf
TRANSCRIPT
381339–252 EASCO POWER TECHNOLOGIES L.P. 50 Hanover Road, Florham Park, New Jersey 07932 USA www.asco.compage 1
Automatic Transfer Switchesfor Series 300Accessory 11BG
Kit Installation
Automatic Power Transfer Load Centersand some* Series 300L
* Can be installed on only this Series 300LAutomatic Power Transfer Load Center
Check the BOM number listed in PRODUCT DATA area of the nameplate.
BOM number Catalog Number
769561 D300L32200F1XM with Acc. 96CPin aluminum outdoor enclosure
Accessory 11BG module includes a programmableengine– generator exerciser and power sourceavailability contacts. It can be added to a Series 300Automatic Transfer Switch (ATS) that has a Group 1Controller. If an existing engine exerciser (Acc. 11CD)is already installed, it must be disconnected first.
The Accessory 11BG module mounts directly behindthe Series 300 ATS operator interface on the inside ofthe enclosure door. Themodule connects to the Series300 ATS operator interface board and Group 1controller.
Kits K629830 & K749999 include the Acc. 11BGmodule, mounting hardware, andall necessarywiring.
Tools 1/4”, 5/16” nutdrivers,required: small blade screwdriver
your Series 300 ATS Operator’s Manualfor setting the DIP switches
ELECTROCUTION – FLASH HAZARDDo not work on the transfer switch untilboth the utility and generator are off.Turn OFF both circuit breakers.
J1
2–linedisplay
3 buttonsconnections forpower sourceavailability signalcontacts
Figure 1. Accessory 11BG Module in kits.
381339–252 E ASCO POWER TECHNOLOGIES L.P. 50 Hanover Road, Florham Park, New Jersey 07932 USA www.asco.com
page 2
Module Installation – Figures 2 & 31. With all power OFF, open the enclosure door. Locatethe operator interface (membrane controls) mountedon the inside of the enclosure door. Use a 5/16”nutdriver to remove (counterclockwise) the four hexnuts from the corners of the operator interface. Do notremove the operator interface board (Figures 2 & 3).
2. Install (clockwise) four standoffs (from the kit) ontothe four studs and tighten them with a 1/4” nutdriver.
3. Install the Acc. 11BG module on top of the operatorinterface so that four standoffs fit through the cornerholes. Then install (clockwise) four 6–32hex nuts (fromthe kit) to secure the assembly. Tighten the nuts.
Connecting the Module – Figures 1, 2, 41. With all power OFF, locate the two ribbon cables andnote direction and orientation of each cable.
2. Unplug the ribbon cable (coming from the Controller)from the operator interface (J3 lower right side) andreconnect it (same orientation) to theAcc. 11BGmodule(J1 lower right side). See Figures 1, 2, & 4.
3. Connect the new ribbon cable (coming from the Acc.11BGmodule upper right side) to the operator interface(J3 lower right side) with the same orientation as theoriginal cable that was moved. See Figures 2 & 4.
4. Strip the insulation from both ends of the #16 gaugewhite wire (from the kit). Connect this prepared wirebetween Acc. 11BG module terminal 9 (right side) andthe Group 1 Controller terminal 4 (bottom). Figure 4.
J3
Figure 2. Series 300 ATS operator Interface boardmounted on the enclosure door (back view).
original mounting of Series 300 ATSoperator interface on enclosure door
standoff added for Acc. 11BG Module
add 4 standoffs
install Acc. 11BG board
operatorinterfaceboard
stud
reinstall4 nuts
remove 4 nuts(with captivelockwashers)
Step 1
Step 2
Step 3
Figure 3. Module installation hardware.
J3
J1
9
wiring
Group 1 Controller(cover removed)
4
Acc. 11BG Modulemounted behindoperator interface.
Figure 4. Accessory 11BG module (mounted behind operator interface and connected to the controller [shown atthe right] ) includes power source availability signal contacts and a programmable engine exerciser.
381339–252 EASCO POWER TECHNOLOGIES L.P. 50 Hanover Road, Florham Park, New Jersey 07932 USA www.asco.compage 3
Power Source Availability Signal ContactsThe module provides one Form C contact each for thenormal and emergency power sources to signal theacceptability of the source as sensed by the controller. Thesignal contacts operate in conjunction with the SourceAvailable lights on the operator interface. Field wiringterminals are provided as shown in Figure 5 and the wiringdiagram.
Contact ratings:2 amps @ 30 Vdc, 0.5 amp. @ 125 Vac resistive Figure 5. Power source availability signal contacts.
Programmable Engine–Generator ExerciserNote: Refer to your Series 300 ATS Operator’s Manualto set DIP switches S1&S2 in theGroup 1Controller.
A backup battery in the Series 300 ATSGroup 1Controller(see Operator’s Manual, Sections 4 and 5) must be turnedon to maintain the settings and to allow programming withthe normal and emergency power sources turned off.
The Acc. 11BG module includes a programmable genera-tor exerciser that provides for weekly or biweekly opera-tion. The exerciser may have to be turned on (enabled) bysetting S1DIP switch actuator 7 to OFF (left position), andS2 DIP switch actuator 5 to OFF (left position).
The programmable engine–generator exerciser incorpo-rates a 7–day or 14–day time base. Proper Group 1Controller settings must be made to determine whether ornot the test will be done with or without load transfer(S1 DIP switch actuator 8).
See next page for instructions on setting the exerciser.
S1 DIP Switch Settingsin Series 300 ATS Group 1 Controller
ProgrammableExerciserFunction
ACTUATORS 7 & 8OFF ON
Enabled &Exercisewithout Load
Actuator 7 OFFActuator 8 OFF
7 EXER ACTV
8 LOAD
Enabled &Exercisewith Load
Actuator 7 OFFActuator 8 ON
78
EXER ACTV
LOAD
S2 DIP Switch Settingsin Series 300 ATS Group 1 Controller
ProgrammableExerciserFunction
ACTUATOR 5OFF ON
Enabled Actuator 5 OFF 5
EXT EXER
Disabled Actuator 5 ON 5
EXT EXER
Shaded DIP switches are standard factory settings.
Programmable Engine Exerciser SettingsFill in your settings for future reference
Weekly or Bi–weekly Day of Week Start Time Run Time
Every = weekly
Alt = bi–weeklySun through Sat
0 – 23 hour
0 – 59 minute
0 – 23 hour0 – 59 minute30 minutes is thedefault setting
Date exerciser was set ______________________________________
381339–252 E ASCO POWER TECHNOLOGIES L.P. 50 Hanover Road, Florham Park, New Jersey 07932 USA www.asco.com
page 4
How to Set OptionalProgrammable Engine Exerciser
(part of Acc. 11BG module)
Hazardous voltage capable of causing shock,burns, or death is used in this transfer switch.Deenergize both Normal & Emergency powersources before programming the exerciser.
Navigating the MenuUse the UP and DOWN arrow keys to move through thedisplays.
Fast/Slow Adjust
Daylight SavingTime Adjust
Date
Time
Start TIme
Engine Exerciser
Run TIme
Changing the ParametersUse the UP and DOWN arrow keys to move though thedisplays to the parameter to be changed. Push the ENTERkey to start the editing process. The first parameter willflash. Use the UP and DOWN arrow keys to adjust theparameter to thedesired value andpress theENTERkey tosave the value. The next parameter will now flash. Repeatthe process until each parameter is properly configured.
Engine Exerciser DisplayThe Engine Exerciser Display shows the status of theengine exerciser. When the unit is shipped from the factorythe programmable engine exerciser is “Disabled” andmustbe set to “Enabled” by the customer. When the engineexerciser is running, this display will count down theremaining time until the end of the exercise period.
Start Time DisplayThe Start Time Display shows the engine exerciser starttime. There are four parameters that determine the starttime:
weekly (”Every”) or bi–weekly (”Alt”) operationday of week (”Sun” through “Sat”)
start hour (0 through 23)start minutes (0 through 59)
For example, if the user wants the exerciser to run everyother Saturday at 3 PM, the proper configuration would be:
“Alt Sat @ 15:00”NOTE:When choosing bi–weekly operation, the exerciserwill always run on the week designated “(1)” on the datedisplay.
Run Time DisplayThe Run Time Display shows the run time for the engineexerciser. The default setting from the factory is 30minutes.
Time DisplayThe Time Display shows the present system time. Theformat is “hours:minutes:seconds”.
NOTE:During total power outages, power to the accessoryismaintained by a battery in theController (see page 4–2 ofOperator’s Manual). Be sure that the 9–volt alkalinebattery is fresh andenabled (jumper inONposition) so thatthe time and date settings are not lost.
Date DisplayThe Date Display shows the present system date. Theformat is “day of week (week) month/day of month/year”.
NOTE: Week is either week 1 or week 2. This is used inconjunction with the bi–weekly timer.
Daylight Savings Time Adjust DisplayThis display shows whether the automatic daylight savingtime adjustment is active. The factory default is “NO”. Ifenabled, the unit will automatically adjust for daylightsaving time at 2 AM on Sunday as follows:
Part No. 629857–001* 629857–002*Start first Sunday in April 2nd Sunday in MarchStop last Sunday in Oct first Sunday in Nov* Part no. on back of circuit board. New DST starts in 2007.
Fast / Slow Adjust DisplayThis display shows the automatic fast/slow adjustmentvalue. The factory default is 0. This feature can be used totrima clock that runs fast or slow. For example, if your clockruns 10 seconds slow per week, change the fast/slow adjustvalue to “+10” and the unit will automatically add 10seconds to the clock every week.
NOTE:Adjustments are made Sundaymorning at 2 AM. Ifyou want your exerciser period to start at 2 AM on Sunday,you cannot use this feature and the adjustment must be setto 0.