accessibility requirements in canada – based on canadian building codes presented to: interior...
TRANSCRIPT
ACCESSIBILITY REQUIREMENTS IN CANADA – BASED ON
CANADIAN BUILDING CODES
Presented to: Interior Designers of Canada
Largest and oldest Building Code/fire protection firm in Canada
3 offices: Toronto (Head Office), Ottawa, Owen Sound
We provide services for projects across North America and Internationally
LRI: WHO WE ARE
Code Consulting Services• Building Code Review, Fire Code Review,
Drawing Review, Fire Modeling, Alternative Solutions
Life Safety Services• Fire Safety Planning, Fire Safety Training
Seminars, Fire Drill Evaluations
System Engineering Services• Fire Protection Systems Evaluation, Fire
Alarm/Fire Suppression Systems Design
LRI: WHAT WE DO
Review of: • Building Codes in Canada
• Highlights of Barrier-free sections within the National Building Code and Provincial Building Codes
• Focused highlights of the Accessible Design for the Built Environment (CAN/CSA B651)
WEBINAR AGENDA
BUILDING CODES IN CANADA
2010 National Building Code of Canada (NBC)• Model Code for Canada
Provincial adoption or adaption of NBC• New Brunswick• Manitoba• Nova Scotia• Saskatchewan• Newfoundland and Labrador• Northwest Territories• Nunavut• Yukon• Prince Edward Island
BUILDING CODES IN CANADA
Provincial Building Codes• 2006 Alberta Building Code (ABC)• 2006 British Columbia Building Code (BCBC)• 2006 Ontario Building Code (OBC)• 2006 Quebec Construction Code (QCC)
BUILDING CODES IN CANADA
2006 Provincial Codes are based on 2005 NBC
2010 NBC Section 3.8.• No significant change from 2005 NBC
Upcoming 2011 Provincial Codes• Section 3.8. may be revised from 2006 editions
2005 NBC 2010 NBC
OTHER REGULATIONS
Canadian Standard which can be used in the design and construction of new facilities or modifications to existing facilities, generally as a reference document
ACCESSIBLE DESIGN FOR THE BUILT ENVIRONMENT (CAN/CSA B651)
Additional accessibility documents and standards may be applicable to projects in some provinces/municipalities
Client/contract requirements
It is the designers responsibility to be aware of all legislated documents and standards applicable to each project
OTHER ACCESSIBILITY STANDARDS
Highlights of Barrier-free National Building Code and Provincial Building Codes
An accessible route into and throughout a floor area
Permitted to include ramps, passenger elevators, other platform equipped passenger elevating device to overcome a difference in level greater than 13 mm
BARRIER-FREE PATH OF TRAVEL
Minimum unobstructed width must be 920 mm with the following exceptions:• 1100 mm – OBC• 1500 mm – BCBC
“lay-by” spaces, for wheelchair passing, must be located not more than 30 m apart and provide a minimum 1500 mm x 1500 mm clear space except the following:• 1600 mm x 1600 mm (where the path is less than
1600 mm) – OBC• Not required (due to wider path of travel) – BCBC
BARRIER-FREE PATH OF TRAVEL
BARRIER-FREE PATH OF TRAVEL
MINIMUMUnobstructed Width
30mMaximum
Lay by Spaces
Floor levels not served by an elevator, escalator, moving walk, etc.
Elevated/sunken portions of a floor area which are provided with the same amenities as the main floor area
Dwelling units (i.e. houses and within suites of residential occupancy ); except 10% OBC
Rooms/spaces that are “not occupied” are not exempt (i.e. storage rooms)
EXEMPTIONS TO BARRIER-FREE PATH OF TRAVEL (EXCEPT BCBC)
Storeys above or below the accessible entrance storey in a building/suite not more than two storeys if:• less than 600 m2 in area, • don’t contain facilities integral to the function of the
accessible storey, and • don’t contain an assembly occupancy greater than 100
m2
Group C dwelling units, row houses, boarding houses, and lodging houses
Floor levels not served by an elevator, escalator, moving walk, etc. are not exempt.
EXEMPTIONS TO BARRIER-FREE PATH OF TRAVEL - BCBC
Barrier-free path of travel is described for specific occupancy groups and specific building types, such as:• Theatres, Studios, Opera Houses, Amusement
Arcades and Billiard Halls, Schools and Colleges (residential and nonresidential), Drive-in Theatres, Psychiatric Hospitals and Police Stations, Banks, etc.
BARRIER-FREE PATH OF TRAVEL – BCBC
Assembly Occupancies - Access must be provided to:• Each type of public facility (refreshments,
recreational, offices, etc.)• Accessible viewing positions• Amenities, special-use public areas (i.e.
changing rooms, interview rooms, bowling lanes, etc.) Some amenities/areas require “all” to be
accessible, others require “at least one” to be accessible
BARRIER-FREE PATH OF TRAVEL – BCBC
Care and Detention Occupancies – Access must be provided to: • Jails
areas where visitors are admitted accessible visitor washrooms
• Psychiatric Hospitals, Police Stations, and Care Facilities areas where work functions can reasonably be
expected to be performed by persons with disabilities
accessible washrooms serving each accessible area each type of facility
BARRIER-FREE PATH OF TRAVEL – BCBC
Residential Occupancies• Apartment/Condominium Buildings
Access must be provided from the street and a private parking area to the main entrance, and from the main entrance to an elevator
• Hotels/Motels Access must be provided to all public facilities/storeys At least one in every 40 sleeping units must be
accessible At least one in every 20 sleeping units, which is not
accessible must have a visual warning system Public washrooms must be accessible
BARRIER-FREE PATH OF TRAVEL – BCBC
Residential Occupancies• Residential schools/colleges and Dormitories
At least one in every 40 bed spaces must be accessible Bed spaces which are not accessible must have a visual
warning system Accessible washrooms must be provided to serve
accessible bed spaces
• Residential Clubs Where sleeping accommodation is provided for 10 or more
people in single or double rooms, at least one room must be accessible *
Sleeping rooms which are not accessible must have a visual warning system
BARRIER-FREE PATH OF TRAVEL – BCBC
Business and Personal Services Occupancies• General
At least one accessible washroom must be either available to all suites or provided in each suite
Access must be provided to all public areas
• Banks Access must be provided to every type of public
facility, at least one teller location, and ATMs, night deposit boxes, where provided
BARRIER-FREE PATH OF TRAVEL – BCBC
Business and Personal Services Occupancies• Barbers and Hairdressers
Access must be provided to at least one hairdressing sink, where provided
• Self-service Laundry and Dry-cleaning Access must be provided to at least one of each
type of equipment for public use
BARRIER-FREE PATH OF TRAVEL – BCBC
Mercantile Occupancies• At least one accessible washroom must be
either available to all suites or provided in each suite
• Access must be provided to all public facilities
BARRIER-FREE PATH OF TRAVEL – BCBC
Industrial Occupancies• High Hazard – not required
• Low/Medium Hazard, Service Stations, Parking Garages Access must be provided to all public areas Washrooms provided within a service station
must be accessible Within a parking garage, access must only be
provided to storeys containing accessible parking spaces
BARRIER-FREE PATH OF TRAVEL – BCBC
Where a barrier-free path of travel is provided to levels above/below the entrance level, protection of the floor area must be protected.
Protection is achieved by:• Vestibules serving elevator lobbies,• Fire compartments (i.e. zones) such that persons with
disabilities can be accommodated in each zone and the travel distance from one zone to the other does not exceed the travel distance permitted for the occupancy, or
• Sprinkler protection
PROTECTION ON FLOOR AREAS WITH A BARRIER-FREE PATH OF TRAVEL
PROTECTION ON FLOOR AREAS WITH A BARRIER-FREE PATH OF TRAVEL
SPRINKLERED FLOOR AREA FLOOR AREA SERVED BYPROTECTED ELEVATOR
FLOOR AREA DIVIDED INTO FIRE ZONES
PRESSUIZE OVER 3STOREYS
ZONE 'A' ZONE 'B'
OPEN INTOVESTIBULE ORPUBLIC CORRIDOR
Each building must have barrier-free entrances • Not less than 50% of pedestrian entrances - NBC, ABC,
QCC• At least one main entrance - BCBC• Based on table below - OBC
BARRIER-FREE ENTRANCES
Pedestrian Entrances
Minimum # of Barrier-Free Pedestrian Entrances
1-3 1
4-5 2
6+ Not less than 50%
Required minimum clear door width is 800 mm except:• 850 mm – OBC
Only the active leaf in a multiple leaf door in a barrier-free path of travel must be barrier-free.
DOORS
DOORS
Clear space on the latch-side of the doorway is required to provide maneuvering space for wheeled mobility devices on both sides of a door
Clear space extends the height of the door and • Minimum 300 mm beside the door latch on the push side• Minimum 600 mm beside the door latch on the pull side
Sliding doors• Not specifically addressed – rule of thumb: Minimum 300 mm
both sides
Each side of any door opening onto a suite in a hotel or motel must have a maneuvering area minimum 1500 mm in diameter on each side (QCC)
DOORS
DOORS
Where doors are located in a series (i.e. vestibule) the space between the doors must:• Allow for movement of
wheelchairs between doors• The minimum distance
between doors when in the open position is 1200 mm
DOORS
300 mm
1200 mm
600 mm
Where vision panels are provided in a door, the panel must be (OBC):• at least 75 mm wide• located with bottom of the panel not more than
900 mm above the floor• edge of the panel not more than 250 mm from
latch side of the door
DOORS
900
min
.M
ax.
250 mmMax.
250 mmMax.
250 mmMax.
900
min
.M
ax.
75 mmMin.
Glazed doors must be designed so that the position of the door is apparent by means of installing non-transparent hardware, bars, or other permanent fixtures. (All except OBC)
Glazed doors must be marked with a continuous opaque strip that is (OBC):• Colour and brightness contrast with
background• Minimum 50 mm wide• Be located at a height of 1350 mm – 1500 mm
above the floor
DOORS
Power door operators must be provided at:• Barrier-free designated entrances with the following
exceptions: Buildings containing a Group B-1, Group C (except hotels), or Group F
occupancy Buildings smaller than 500 m2 containing a Group A, Group B-3, Group
D, or Group E occupancy Individual suites smaller than 500 m2 in a building containing only
suites of Group A, Group B, Group D, or Group E occupancy
• Universal toilet rooms if equipped with a self-closing device (OBC)
• Doors not provided with required latch side clearances
DOORS
Minimum clear width between handrails must be 870 mm, except:• 890 mm – 940 mm, 1500 mm (BCBC)• 900 mm (OBC)
Maximum clear width between handrails• 920 mm if the ramp does not reduce the required
width of a means of egress (QCC)
RAMPS
Maximum slope must be 1:12 except:• BCBC based on table below
RAMPS
Slope Max. Length
Max. Landing Interval
Required Ramp Width
Handrail Required
Over 1:20 – 1:16
None 12 m 890 mm – 940 mm
Both sides
Over 1:16 – 1:12
None 9 m 890 mm - 940 mm
Both sides
Over 1:12 – 1:10
6 m - 1500 mm Both sides if > 2 m
Over 1:10 – 1:8
600 mm - 1500 mm Not required
Minimum 1500 mm x 1500 mm landings must be provided at the top, bottom, and at intermediate levels leading to a door, except:• 1670 mm x 1670 mm (OBC)• 1500 mm x width of the ramp (BCBC)
At intervals not more than 9 m, landings measuring at least 1200 mm by the width of the ramp must be provided except:• 1670 mm x width of the ramp (OBC)• 1500 mm x width of the ramp (BCBC – at intervals
specified in table on above slide)
RAMPS
Landings measuring at least 1200 mm by the width of ramp must be provided at abrupt changes in the direction of the ramp, except:• 1200 mm x 1200 mm (ABC - 90° turn)• 1500 mm x 1500 mm (ABC - 180° turn)• 1500 mm x width of the ramp (BCBC)• 1670 mm x width of the ramp (OBC)
RAMPS
Walls or guards must be provided on both sides of a ramp
Minimum guard height is 1070 mm
Guard openings must not permit the passage of a sphere with diameter more than 100 mm
Guards must be designed to prevent climbability between 140 mm – 900 mm above the ramp (i.e. horizontal members, attachment, etc.)
RAMPS
A ramp must have a curb where a solid enclosure or solid guard is not provided:• Minimum 75 mm (BCBC)• Minimum 50 mm (OBC)
Otherwise, ramps must have a railing or other barrier that extends to:• 75 mm of the finished ramp surface (BCBC)• 50 mm of the finished ramp surface (OBC)
RAMPS
Intermediate handrail if ramp is required to be > 2200 mm wide
Handrail height must be 865 mm – 965 mm along the length of ramp
Handrails must extend at least 300 mm beyond the top and bottom of the ramp
RAMPS
RAMPS
Controls for power door operators, building services or safety devices, including electrical switches, thermostats, and intercom switches must be installed 400 mm – 1200 mm above the floor except:• 900 mm – 1200 mm above the floor (OBC)
CONTROLS
WASHROOMS
A washroom provided on a floor level with a barrier-free path of travel must be barrier-free unless other barrier-free washrooms are provided on the same floor area within 45 m, unless:• It is located within a suite of D, E, or F occupancy, • is less than 500 m2 (NBC), 300 m2 (OBC), and• is completely separated with no access to the
remainder of the building.
All washrooms in a barrier-free path of travel must be barrier-free unless they are located within an individual suite less than 500 m2 and there are barrier-free washrooms on the same floor area within 45 m (ABC). Where more than one washroom is required, one barrier-free stall must be provided for every 10 stalls (or part thereof).
REQUIRED BARRIER-FREE WASHROOMS
A washroom provided on a floor level required to be barrier-free must be barrier-free unless (QCC):• It is located within a suite less than 250 m2 and other barrier-free
washrooms are provided on the same floor area within 45 m, or • The suite has at least one barrier-free washroom on the same floor area
In buildings and occupancies required to have washrooms, where the occupant load of the building or occupancy exceeds 150 , barrier-free public washrooms must be provided on floor areas required to be barrier-free (BCBC)
At least one universal toilet room is required per accessible building/occupancy (BCBC only)
REQUIRED BARRIER-FREE WASHROOMS
Seat height must be 400 mm – 460 mm above the floor except:
• 430 mm- 480 mm above the floor (BCBC)
Seat back must be equipped with seat lid or other back support
Seat type must not be spring-actuated
Flushing controls must be hand-operated and easily accessible to a wheelchair user or automatically operable
WATER CLOSETS
WATER CLOSETS
* BCBC – 430 mm – 480 mm
Water closet must be located 285 mm – 305 mm from an adjacent side wall (NBC, QCC)
Centreline of water closet 460 mm – 480 mm from an adjacent side wall (ABC, OBC)
Centreline of water closet 420 mm – 480 mm from an adjacent side wall and at least 1020 mm from any obstruction on the opposite side (BCBC)
WATER CLOSET LOCATION WITHIN A STALL
Water closet 285 mm – 305 mm from an adjacent sidewall on one side and not less than 875 mm on the other side (NBC, ABC, QCC)
Centreline of water closet 460 mm – 480 mm from an adjacent sidewall on one side and not less than 1020 mm on the other side (OBC)
Same requirements as water closet stall (BCBC)
WATER CLOSET LOCATION WITHIN A UNIVERSAL
Height of a wall mounted urinal must be 488 mm – 512 mm above the floor except:• 490 mm – 510 mm above the floor (BCBC)
Height of a floor mounted urinal must be such that the rim is level with the finished floor
Minimum clear width of approach must be 800 mm with no step in front
Grab bars must be vertically mounted on each side
URINALS (not addressed in OBC)
Centreline location must be at least 460 mm to the sidewall
Height of lavatories must be such that the top is not more than 865 mm above the floor except:• 840 mm (OBC)
LAVATORIES
Clearance beneath the lavatory must be at least 760 mm wide and:• 735 mm high at front edge (All except QCC)
• 685 mm high at a point 205 mm back from front edge except: 250 mm back from front edge (BCBC) 280mm back from front edge (QCC)
• 230 mm high over the distance from a point 280 mm to a point 430 mm back from front edge except: 250 mm high to a point 500 mm back from front edge
(BCBC)
LAVATORIES
Lavatory faucet handles• Operate automatically or have lever-type handles that do
not close under spring action (BCBC, OBC)• Located with centreline of faucet to the edge of the basin
or front edge of vanity is not more than 485 mm (OBC)• Not regulated (NBC, ABC, QCC)
Where mirrors are provided above lavatories, at least one must be mounted with bottom edge not more than 1000 mm above the floor, or, be inclined to be usable by a person in a wheelchair
LAVATORIES
LAVATORIES
Dimensions reflect typical requirements (BCBC and QCC differ slightly)
230
mm
min
.
685
mm
min
.
735
mm
min
.
840
mm
MA
X.
100
0 m
m M
AX
.
UN
LE
SS
MIR
RO
R I
S I
NC
LIN
ED
INSULATE PIPESWHERE WATERTEMPERATURE ISGREATER THAN43 DEG. C.
WHERE MIRRORSARE PROVIDED INBARRIER-FREEWASHROOMS, INCLINEMIN. OF 1 MIRRORTO THE VERTICAL
485 mm MAX.
205 mm
min.
Horizontal, vertical, sloping and/or L-shaped grab bars are required within water closet stalls, universal toilet rooms, showers and bathtubs.• Location varies by fixture and Province
Soap dispensers are required
Hand dryers/towel dispensers are required
ADDITIONAL EQUIPMENT
Water closet stall enclosures must be at least 1500 mm x 1500 mm, except: • Provide an open space 1500 mm diameter (ABC)
Doors serving the water closet stall must be at least 800 mm except:• 810 mm (OBC)
Doors must swing outward, except that inward swinging doors are permitted provided the door swing permits the door to close without interfering with a wheelchair, except:• A clear unobstructed space of 760 mm x 1220 mm is provided (OBC)• A clear unobstructed space 1200 mm in diameter is provided (QCC)• Inward swinging not permitted (BCBC)
STALL ENCLOSURES
STALL ENCLOSURES
min.clear opening
Clearance beyond water closet stall door must be:• Minimum of 1700 mm from stall wall to an in-
swinging door • 1400 mm from stall wall to wall-mounted
fixture/obstruction
STALL ENCLOSURES
STALL ENCLOSURES
wall mountedfixture
door towashroom
stall stall stall
1.4
m
1.7
m
Internal dimensions between all walls must not be less than 1700 mm except:• Floor area not less than 3.7 m2 and no internal
dimension between walls less than 1700 mm when door swings out, or
• Floor area not less than 4.0 m2 and no internal dimension between walls less than 1800 mm when door swings in (BCBC only)
Minimum 1500 mm diameter clear space must be provided and is not permitted to overlap fixtures
UNIVERSAL TOILET ROOMS
UNIVERSAL TOILET ROOMS
1500
1500
If showers are provided, at least one shower in each group of showers must be at least 1500 mm wide x 900 mm deep
Clear space at shower entrance must be at least 900 mm x the width of the shower except:• 1500 mm wide entrance (BCBC)
SHOWERS
Hinged seat must be minimum 450 mm x 400 mm, at a height of 450 mm above the floor (NBC, ABC, OBC, QCC)
Portable or wall-mounted folding seat must be 40 mm – 60 mm less than the shower compartment depth by 430 mm – 530 mm wide, at a height of 430 mm – 480 mm above the floor (BCBC)
SHOWERS - SEAT
SHOWERS
900
mm
min
.90
0 m
m m
in.
500 mm
900 mm min.
1500 mm min.
CLEARFLOORAREA
Max. 13 mm.THRESHOLD
Bathtubs must be barrier-free if:• Installed in a suite of residential occupancy that is required to be
barrier-free (NBC, ABC, and OBC for hotels)• If bathtubs are provided in a non-residential club, school, or
college, a dormitory, or public toilets, at least one bathtub (BCBC)• Individual bathtubs provided for patients/residents in Group B, Div.
2 or 3 (OBC)
Bathtub must be located in a room that has no internal dimension between walls less than 1700 mm and a 1500 mm diameter clear space (NBC, ABC)
Clear floor space must be:• 750 mm wide x length of bathtub (NBC)• 900 mm wide x length of bathtub (ABC)• 800 mm wide x 1500 mm long (BCBC, QCC)
BATHTUBS
BATHTUBS
Every counter more than 2 m long which serves the public is required to have a barrier-free section except:• OBC – not addressed
Barrier-free section of counter must be• Not less than 760 mm long centered over a knee space not less
than 760 mm wide, 685 mm high, and 485 mm deep, and • Not more than 865 mm above the floor
COUNTERS
COUNTERS
760 mm min.
485 mm
685
mm
min
.
865
mm
max
.
min.
CAN/CSA B651 ACCESSIBLE DESIGN FOR THE BUILT
ENVIRONMENT
Addresses topics not regulated by NBC such as:• Signage and visual displays• Rest area seating• Furniture/counters• Floor and ground surfaces
CSA B651
Seating spaces for persons in wheelchairs, provided at counters, tables, or other work surfaces must have:• Clear floor area at least 750 mm x 1200 mm• Adequate maneuvering space to approach them• Height between 730 mm – 860 mm from the floor• Knee clearance at least 750 mm wide by 480 mm deep by 680
mm high where s forward approach is used (may overlap clear floor area by up to 480 mm)
CSA B651
CSA B651
CSA B651
A bench or seat area must• Be located adjacent to an accessible route (barrier-
free path of travel)• Have a level and firm surface• Have an adjacent level and firm area at least 850 mm
x 1200 mm that is not part of the route of travel
Benches and seats must:• Be stable• Have a seat height of 450 mm – 500 mm from the floor• Provide back rest and arm rest options (i.e. some
with, some without)
CSA B651
CSA B651
Floor and ground surfaces must:• Be stable and firm• Be slip resistant• Produce minimal glare• Not be heavily patterned
Detectible floor and ground warning surfaces must be used to inform persons who are walking over them of three possible situations:• A hazard indicator signals that a person should stop• A warning indicator signals that caution should be taken• A directional indicator facilitates way-finding in open
areas and signals a route to be taken
CSA B651
A detectible hazard indicator must be located at:• An unprotected drop-off edge such as a transit
platform, where the elevation change is greater than 250 mm and the slope is steeper than 1:3
• The unprotected edges of a reflecting pool• Curb ramps• An entry into a vehicular route or area where no
curbs or other elements separate it from the pedestrian route of travel
CSA B651
CSA B651
A detectible warning indicator must be located at:• At the top of stairs where the stairs are not
enclosed• At each landing incorporating an entrance into a
stair system• Where the regular pattern of a stairway is
broken• Where the run of a landing not having
continuous handrail is greater than 2100 mm
CSA B651
CSA B651
Where signage, including electronic display monitors, is provided, it must:• Be consistently located• Be positioned to avoid shadow areas and glare• Have a glare-free surface• Be of uniform design• When used to display the same type of
information within the same facility, be consistently shaped, coloured, and positioned
• Colour-contrasted with its background
CSA B651
Information on visual displays must be:• Supplemented by tactile and/or auditory
information• Colour-contrasted• Located on a glare-free surface
CSA B651
1. 2010 National Building Code of Canada2. 2006 Alberta Building Code3. 2006 British Columbia Building Code4. 2006 Quebec Construction Code5. 2006 Ontario Building Code6. Illustrated Guide to the 1997 Building
Code (graphics only)7. CAN/CSA B651 Accessible Design for the
Built Environment
BIBLIOGRAPHY
NATIONAL ACCESSIBILITY