Above Ground Storage Tank Design, Inspection, and Compliance
Management
By Gregory Coppola, P.E.
Kinder Morgan Energy Partners,
L.P.
![Page 2: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/2.jpg)
Introduction
• Kinder Morgan Overview
– Midstream Energy Company
– 900+ Storage Tanks in Pacific Region
– Critical Infrastructure for Fuel Distribution
![Page 3: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/3.jpg)
Completed New Tanks
El Paso, TX
![Page 4: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/4.jpg)
Organization of the Presentation
• Objective of the Presentation
• API Recommended Practice
• Tank Construction and Tank Components
• Out-of-Service Inspections
• Regulatory Framework
– SPCC Rule
– APSA
– DOT Regulations
– Air Regulations – Federal and Local
![Page 5: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/5.jpg)
Objective of the Presentation
• Provide CUPA members with an overview
of petroleum storage tanks.
• Provide an introduction to applicable
regulations.
• Assist with CUPA regulation under
Assembly Bill 1130, The Aboveground
Petroleum Storage Act.
![Page 6: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/6.jpg)
Aboveground Petroleum Storage Act (APSA),
Assembly Bill 1130
Effective January 1, 2008
• Transfers the responsibility for the
implementation, enforcement and administration
of the Aboveground Petroleum ACT (APSA)
from the State Water Resources Control Board
(SWRCB) to the CUPA’s.
• California Health and Safety Code Chapter 6.67,
Sections 25270 – 25270.13 are also known as
the APSA.
• APSA will be discussed in more detail later in
the presentation.
![Page 7: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/7.jpg)
API Recommended Practices
![Page 8: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/8.jpg)
API Recommended Practices
API 650
• API 650 – Design Standard for welded steel tanks for oil and fuel storage.
• Typically used for large field fabricated storage tanks operating at low pressures or atmospheric pressures.
• The standard covers materials of construction, design, fabrication/erection, construction inspection, and welding procedures.
![Page 9: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/9.jpg)
API 650
Welded Tanks for Oil Storage • Scope
• Reference
• Definitions
• Materials
• Design
• Fabrication
• Erection
• Methods of Inspection
• Welding Procedures
• Marking
![Page 10: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/10.jpg)
Tank Schematics
• The following schematics show the various
appurtenances for:
– Cone Roof Tanks
– Internal Floating Roof (IFR) Tank with Top
Foam Injection and Vapor Recovery
– Cable Suspended IFR
– External Floating Roof (EFR)
– EFR with Dome
![Page 11: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/11.jpg)
Cone Roof Tank
![Page 12: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/12.jpg)
IFR Tank w/Top Foam and Vapor Recovery
![Page 13: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/13.jpg)
Cable Suspended Internal Floating Roof
![Page 14: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/14.jpg)
External Floating Roof Tank
![Page 15: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/15.jpg)
EFR Tank with Aluminum Dome
![Page 16: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/16.jpg)
Tank Foundations
• Foundation Types
– Earth Foundations
– Gravel/Asphalt Surface
– Ring Walls
– Slab
– Piles with Ring or Slab Caps
![Page 17: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/17.jpg)
Tank Foundations (Con’t)
• Design Concepts
– Vertical Loading
• Liquid pressures
• Shell and roof loads
– Overturning
• Wind
• Seismic
– Foundation Settlement
![Page 18: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/18.jpg)
Liner Installation
![Page 19: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/19.jpg)
Foundation Rebar
![Page 20: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/20.jpg)
Concrete Tank Foundation
![Page 21: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/21.jpg)
Tank Bottoms
• Constructed of overlapping steel plates.
• Plates joined by manual or automatic arc
welding techniques.
• Tank bottom to shell welds undergo the
most stress and are considered critical
welds.
![Page 22: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/22.jpg)
Tank Bottom – In Progress
![Page 23: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/23.jpg)
View of Tank Bottom Beneath IFR Includes Center
Column, Roof Legs, and Reinforcing Pads
![Page 24: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/24.jpg)
Tank Double Bottoms
• Typical components (starting from below)
– Lower tank bottom
– HDPE liner
– Sand or concrete with drainage system
– Upper tank bottom
![Page 25: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/25.jpg)
Shell Design
• Tank shells are constructed from courses of steel plates.
• The designer will calculate a steel thickness for each course.
• The bottom courses are thicker steel due to hydrostatic pressure.
• Shell design criteria include hydrostatics and wind buckling.
• Thickness includes corrosion allowance.
![Page 26: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/26.jpg)
Construction of First Course –
Crane Inside
![Page 27: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/27.jpg)
Construction of First Course
![Page 28: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/28.jpg)
Hanging Plate for 4th Shell Course
![Page 29: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/29.jpg)
Nozzles and Penetrations
• Openings in the shell result in higher
stress.
• Repads or thickened inserts may be
required.
• Stress relieving may be required.
![Page 30: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/30.jpg)
Manway with Davit Arm
![Page 31: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/31.jpg)
Fixed Roof Types
• Self-supported
– Cones
– Domes and Umbrellas with stiffeners
• Supported Cone Roofs
– Columns are inside tank
• Aluminum Geodesic Domes
![Page 32: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/32.jpg)
Roof Construction – Bull Wheel
and Center Column
![Page 33: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/33.jpg)
Roof Rafter Construction
![Page 34: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/34.jpg)
Lifting Cone Roof
![Page 35: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/35.jpg)
Center Column Support
![Page 36: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/36.jpg)
Supported Roof, Partially Completed
![Page 37: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/37.jpg)
Aluminum Dome, Lifting on to EFR Tank
![Page 38: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/38.jpg)
Frangible Roof Joints
• Roof to shell junction designed to fail first
in an emergency.
• Future piping and maintenance must not
interfere with the functioning of the
frangible roof joint.
![Page 39: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/39.jpg)
Fixed Roof – 24” Mushroom Circulation Vent,
Sample Vent and Skid-Proof Surface Coating
![Page 40: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/40.jpg)
Floating Roofs, Objectives
• Reduces air emissions
• Prevents product loss
• Meets regulatory requirements
• Improves fire safety
![Page 41: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/41.jpg)
Floating Roofs
• Material of Construction: Steel or Aluminum
• Roof Types
– Floating pan
– Bulkhead
– Internal pontoon
– Double deck
– Honeycomb or Foam Core
– Cable suspended Aluminum
![Page 42: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/42.jpg)
IFR Pontoon Construction
![Page 43: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/43.jpg)
Floating Roof Support Leg and Sleeve
(High Leg Position)
![Page 44: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/44.jpg)
Reinforcing Pad for Roof Leg
![Page 45: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/45.jpg)
Floating Roof Seals
• Primary Seals
– Liquid mounted foam logs
– Liquid mounted shoe seals
– Vapor mounted foam logs
– Vapor Mounted wipers
• Secondary Seals
– Elastomeric wipers
– Metallic wipers
![Page 46: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/46.jpg)
Mechanical Primary Shoe Seal in IFR
![Page 47: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/47.jpg)
Compression Plate Secondary Seal
with Wiper Tip on EFR Tank
![Page 48: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/48.jpg)
Other Tank Appurtenances
• Spiral stairway
• Ladders
• Level gauges
• Pressure vacuum vents
• Shell and roof manways
• Inlet diffusers
• Drain sumps
• Roof drain hoses
![Page 49: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/49.jpg)
Spiral Stairway Leading up the
Tank Exterior
![Page 50: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/50.jpg)
Internal Ladders with 8-inch Slotted
Gauge Pole
![Page 51: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/51.jpg)
Level Gauging Systems
• Mechanical level gauging systems are frequently used. There are multiple alarm levels.
• Radar gauges can be mounted at the fixed roof or in a gauge well.
• The gauging system often ties into the overall facility SCADA system.
• A redundant alarm is recommended by API.
![Page 52: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/52.jpg)
Level Gauging System
Mounted on Tank Exterior
![Page 53: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/53.jpg)
Sample Hatch
![Page 54: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/54.jpg)
Top View of IFR
Two 12” Pressure Vacuum Vents and Center
Column
![Page 55: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/55.jpg)
Drip Tray for Center Column with
Hold Down Chains
![Page 56: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/56.jpg)
Ladder Well Drip Tray
and Chained Slide Plate
![Page 57: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/57.jpg)
Tank Bottom Sump
Newly Painted
![Page 58: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/58.jpg)
Ladder, Slotted Gauge Pole, and Sump
![Page 59: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/59.jpg)
Slotted Inlet Diffuser
Slotted pipe
![Page 60: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/60.jpg)
Inlet Diffuser -- Hole Type
![Page 61: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/61.jpg)
Suction Line Trough
![Page 62: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/62.jpg)
Water Draw Piping
![Page 63: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/63.jpg)
Coiled Roof Drain Hose
Beneath Internal Floating Roof
![Page 64: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/64.jpg)
Reinstalling a Door Sheet
at the Conclusion of the Project
![Page 65: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/65.jpg)
Fire Systems
• Refer to NFPA 11 – Standard for Low-,
Medium-, and High-Expansion Foam.
• The Standard contains design criteria for
hydrocarbon storage tanks.
• The criteria include:
– Application rate
– Discharge time
– Minimum number of outlets
![Page 66: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/66.jpg)
Fire Systems (Con’t)
• Fixed roof tanks may be designed with
subsurface injections.
• Floating roof tanks will be designed with
over-the-top injection.
• Foam dams are used to focus on fighting
seal area fires.
• Other fire systems are designed for “Full
Surface Fires.”
![Page 67: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/67.jpg)
Foam Fire Systems
![Page 68: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/68.jpg)
Foam Chamber Installed in Tank
Shell
![Page 69: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/69.jpg)
Tank Cathodic Protection
• Galvanic Corrosion
– Can occur on the underside of a tank bottom causing oxidation, general corrosion, and pitting.
– Galvanic cell requires: • Anode – active metal at the tank bottom.
• Cathode – less active metal in the vicinity of the tank.
• Electrical path – tank bottom and soil.
• Electrolyte.
![Page 70: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/70.jpg)
Tank Cathodic Protection (Con’t)
• Impressed Current Systems
– Includes a DC current source created by a rectifier and a buried impressed current anode.
– Creates a current to counteract the galvanic cell and forces current to the tank bottom to prevent oxidation (loss of electrons).
• Sacrificial Anode
– The anode losses electrons rather than the tank.
![Page 71: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/71.jpg)
Impressed Current Corrosion
Protection
![Page 72: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/72.jpg)
API Recommended Practices
API 653
• API 653 – Tank Inspection, Repair,
Alteration and Reconstruction.
• Tanks are inspected to determine their
suitability for service.
• The standard includes recommendations
for tank inspection interval.
• This standard governs out of service
inspection and repair work.
![Page 73: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/73.jpg)
API 653 Tank Inspection, Repair, Alteration and
Reconstruction
• Scope
• Reference
• Definitions
• Suitability for Service
• Brittle Fracture
• Inspection
• Materials
• Design Considerations
• Tank Repair and
Alterations
• Dismantling/Reconstr
uction
• Welding
• Examination Testing
• Marking
![Page 74: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/74.jpg)
Other API Methods Relevant to Tanks
• API 651 – Cathodic Protection for Storage
Tanks.
• API 652 – Linings for Storage Tanks.
Standard for Internal Coating.
• API 2000 – Venting for Atmospheric and
Low Pressure Tanks.
• API 2350 – Overfill Protection for Storage
Tanks.
![Page 75: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/75.jpg)
API Recommended Inspection
Schedule
• Routine In-Service Visual Inspection
– Frequency not to exceed one month.
– Can be performed by Owner/Operator personnel.
• External In-Service Inspection
– Visual inspection of the tank exterior .
– By Authorized Inspector (API 653 Certified).
– Frequency not to exceed 5 years, but may be more frequent based on corrosion calculation.
![Page 76: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/76.jpg)
API Recommended Inspection
Schedule
• Ultrasonic Inspection
– Ultrasonic measurement of tank shell.
– Inspections at 15 year intervals or possibly
more frequent based on shell corrosion
calculation.
– Initial inspection in 5 years to establish a
corrosion rate.
– Corrosion rate may be estimated from tanks
in similar service.
![Page 77: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/77.jpg)
API Recommended Inspection
Schedule (Con’t)
• Internal Inspection
– Inspections at 20 year intervals or possibly
more frequent based on tank bottom
corrosion calculation.
– Initial inspection in 10 years to establish a
corrosion rate.
– Corrosion rate may be estimated from tanks
in similar service.
![Page 78: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/78.jpg)
Tank Maintenance Projects
Typical Tasks
• Empty tank.
• Isolate.
• Clean and degas.
• Inspection blast of floor coating.
• API 653 inspection.
• Issue preliminary inspection report and develop list of maintenance/repair items.
• Perform tank maintenance and repair work.
![Page 79: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/79.jpg)
Tank Maintenance Projects
Typical Tasks (Con’t)
• Tank strapping
• Final blast
• Tank coating
• Final inspection
• Return tank to service
• Exterior painting or concrete/asphalt work (optional)
• Final construction documentation
![Page 80: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/80.jpg)
Safe Work Practices
• Safety is Everyone’s Job
• Learn to Recognize Safe Work Practices
![Page 81: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/81.jpg)
Safe Work Permitting Procedure
![Page 82: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/82.jpg)
Heavy Tools are Lifted by Rope
Tag Line not Hand Carried
![Page 83: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/83.jpg)
Confined Space Vapor Monitoring
![Page 84: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/84.jpg)
Radio Communication
![Page 85: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/85.jpg)
Leg Setting
• The tank contractor will set the IFR legs
from high position to low position to land
the roof.
• This requires a confined space entry from
the manway on the fixed roof.
![Page 86: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/86.jpg)
Use Body Harness and Tripod for
Confined Space Entry
![Page 87: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/87.jpg)
Tripods Must Have Leg Chains for Stability
![Page 88: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/88.jpg)
Pulley Must be Mounted and Secure
![Page 89: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/89.jpg)
Body Harness Must Be Properly Attached
![Page 90: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/90.jpg)
Lock Out / Tag Out
• Lock out, tag out procedures are followed for piping and electrical.
• Contractors verify that all valves have been closed and locked out.
• Ensure that the terminal piping has been totally isolated (review terminal piping drawings).
![Page 91: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/91.jpg)
Plan Lockout/Tagout
![Page 92: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/92.jpg)
Gauge the Tank to Check that it is
Empty
![Page 93: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/93.jpg)
Close, Lock, and Tag Valves to
Isolate
![Page 94: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/94.jpg)
Electrical Lockout/Tagout
![Page 95: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/95.jpg)
Tank Valve Lockout
![Page 96: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/96.jpg)
Document the Valve Positions
![Page 97: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/97.jpg)
Tank Isolation
• For all lines, a valve is removed and blinded to create an air gap.
• Metal drip pans and vacuum truck are required when isolating the tank.
• Bonding cables are required when removing valves.
• 150 lb. blind flanges and new gaskets are required.
• After blinding has been completed, the piping is visually inspected to ensure tightness.
![Page 98: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/98.jpg)
Inspecting Empty Vacuum Truck Prior to
Use
![Page 99: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/99.jpg)
Bonding Cables and Metal Drip Pan
![Page 100: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/100.jpg)
Valve removal including bonding cables,
respirators, gloves, fire extinguisher, metal
drip pans and vacuum truck hose.
![Page 101: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/101.jpg)
Isolated Tank Valve with Air Gap
![Page 102: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/102.jpg)
Isolated Buried Line with Barricades
![Page 103: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/103.jpg)
Tank Degassing
• Tank degassing is performed, when required,
based on product type and location in
accordance with EPA, State, or local air
regulations.
• Portable Thermal Oxidizers are most frequently
used to handle the combustion throughput. IC
engines or activated carbon systems can be
used.
• The units need to have the appropriate air
permit and operate in accordance with the
permits.
![Page 104: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/104.jpg)
Portable Thermal Oxidizer and Generator
![Page 105: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/105.jpg)
Degassing Unit Placed Outside of Tank
Berm
![Page 106: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/106.jpg)
IC Engine Degassing Unit
![Page 107: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/107.jpg)
Temperature and Flow Monitoring is
Typically Required by the Air Permit
![Page 108: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/108.jpg)
Once the Manway is Removed Plastic
Sheeting is Place over it Immediately
![Page 109: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/109.jpg)
The Vapor Hose Penetrates the Plastic
Sheeting
![Page 110: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/110.jpg)
Tank Cleaning
• Proper placement of equipment to separate vapors from ignition sources.
• Proper PPE (hard hats, rubber boots, gloves, suits, full body harness, etc.).
• Enter with supplied fresh air.
• Monitor vapors inside the manway away from inlet.
• OSHA allows tank entry below 10% LEL for fresh air work; however, the goal is to be significantly lower.
![Page 111: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/111.jpg)
Hose Extends from Vacuum Truck
to Tank Manway
![Page 112: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/112.jpg)
Vacuum Truck Exhaust Connected
to Carbon Canister
![Page 113: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/113.jpg)
Manway Setup – Plastic Sheet, Fire
Extinguisher, Confined Space Permits
![Page 114: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/114.jpg)
Intrinsically Safe Fan Mounted on
Opposite Manway from Entrance
![Page 115: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/115.jpg)
PPE for Tank Entry
![Page 116: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/116.jpg)
Interior Appurtenances Removed to
Drain Product
![Page 117: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/117.jpg)
Center Column Mouse Hole
Drained of Product
![Page 118: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/118.jpg)
Marine Chemist Certifies the Tank
as Gas Free
![Page 119: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/119.jpg)
The gas free
certificate is posted
over the manway.
It may have certain
restrictions to be
aware of.
![Page 120: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/120.jpg)
Confined Space Access is Secured when
the Contractor Leaves the Site
![Page 121: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/121.jpg)
Cribbing Blocks Installed to
Support Roof
![Page 122: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/122.jpg)
Anti-Rotational Roof Support
![Page 123: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/123.jpg)
API 653 Tank Inspection
Techniques
• Magnetic Flux Exclusion (MFE)
• Ultrasonic Testing (UT)
• Vacuum Box Testing
• Dye Penetrant Testing
• Bottom Settlement Survey
![Page 124: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/124.jpg)
Calibration of Magnetic Flux
Exclusion (MFE) Bottom Scanner
![Page 125: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/125.jpg)
Large MFE/UT Floor Scanner Scans within 2” of Lap Weld Seams
![Page 126: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/126.jpg)
Marking Corrosion Indications
Circles – Topside Corrosion
Square – Bottomside Corrosion
![Page 127: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/127.jpg)
Calibration of Smaller Hand
Scanner
![Page 128: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/128.jpg)
Smaller Scanner in Congested
Area
![Page 129: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/129.jpg)
Hand Scanner used at Corner
Weld
![Page 130: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/130.jpg)
Remaining Floor Thickness is Marked in
Area of Soil Side Corrosion
![Page 131: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/131.jpg)
Automated Ultrasonic Thickness Measurement
used to “Prove Up” locations marked during MFE
Scan
![Page 132: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/132.jpg)
Vacuum Box Testing of Corner Weld
![Page 133: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/133.jpg)
Vacuum Box Testing of Floor Plate Weld
Seam
![Page 134: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/134.jpg)
Fluorescent Dye Penetrant Applied
to Corner Weld
![Page 135: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/135.jpg)
Using Black Light to Find Defects
Detected with Fluorescent Dye
![Page 136: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/136.jpg)
Bottom Settlement Survey
![Page 137: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/137.jpg)
Ultrasonic Testing of Tank Shell
![Page 138: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/138.jpg)
Ultrasonic Testing of Shell
Reinforcement Pad and Nozzle
![Page 139: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/139.jpg)
Ultrasonic Testing of Internal
Floating Roof
![Page 140: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/140.jpg)
Tank Repairs
![Page 141: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/141.jpg)
Tank Repairs
• Floor Patches and Plate Replacements
• Shell Repairs
• IFR Repairs
• Nozzles
• Seal Replacement
• Tank Valve Repairs
• Calibration and Repair of Gauging System
• Follow-up Testing
![Page 142: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/142.jpg)
Testing of Vapors Beneath Tank Floor
Through Small Hole Drilled in the Floor
![Page 143: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/143.jpg)
Bottom Repair at Critical Zone
![Page 144: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/144.jpg)
Testing New Patch With Soapy Water
![Page 145: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/145.jpg)
Dye Penetrant Testing of Shell
Nozzle
![Page 146: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/146.jpg)
Roof Drain Hose Inspection
![Page 147: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/147.jpg)
Replacing Seal Apron Fabric
![Page 148: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/148.jpg)
Fluorescent Testing Beneath IFR
![Page 149: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/149.jpg)
Inspecting the Penetrant Test Above
the Roof to Search for Leaks
![Page 150: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/150.jpg)
Pressure Testing Pontoons
Following Repairs
![Page 151: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/151.jpg)
Tank Interior Coating
![Page 152: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/152.jpg)
SPCC Compliance
![Page 153: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/153.jpg)
Purpose of SPCC Rule
• Requirements help prevent oil discharges from reaching navigable waters or adjoining shorelines.
• Certain facilities are required to develop SPCC Plans that describe equipment, workforce, procedures, and training to prevent, control, and provide adequate countermeasures to a discharge of oil. – Must comply with the rule requirements.
– Must also implement the written Plan.
![Page 154: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/154.jpg)
What does the SPCC Rule Require?
• Requires facilities to develop and implement a site-specific SPCC Plan to address: – Containment and procedures to prevent oil discharge
(operating procedures, inspections & tank testing, training, etc.)
– Control measures to keep an oil discharge from entering navigable waters (containment, drainage valves
– Countermeasures to contain, clean up, and mitigate any oil discharge that affects navigable waters (spill response measures)
• Performance-based rule designed to implement the Congressional policy of “no oil discharges” to waters of the United States
![Page 155: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/155.jpg)
Aboveground Petroleum Storage
Tank Act (APSA)
![Page 156: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/156.jpg)
What is an Aboveground Petroleum
Storage Tank?
• 55 gallons or more.
• Located substantially above ground.
• Tanks are either UST or AST, but not
regulated as both.
• The volume for mixtures is based on the
total tank capacity not the volume of
petroleum in the mixture.
![Page 157: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/157.jpg)
APSA Exemptions
• Two broad exemptions:
– Exempt Tanks (HSC §25270.2(a)(1 – 6)) • Some exemption conditions (and compliance with
those conditions) should be verified
– Exempt Facilities (HSC §25270.4.5(b)) • Exempt only from APSA requirement to prepare
and implement an SPCC Plan
![Page 158: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/158.jpg)
Tanks Exempted Under APSA
• Boilers & pressure vessels
• Waste & used oil tanks – Located at DTSC permitted hazardous waste
TSD facilities (and listed on the permit), or specifically listed on a facility’s PBR Tiered Permit
• Crude oil production tanks
• Most oil-filled electrical equipment
• CUPA regulated USTs
• Transportation-related tank facility
![Page 159: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/159.jpg)
APSA (and SPCC Rule) Exempt Tanks
• ‘Transportation-related facilities’ are not regulated under federal SPCC rules or APSA
• Facilities are divided into three categories: – Transportation-related facilities (exclusively regulated
by DOT / DOI)
– Non-transportation-related facilities (not exclusively regulated by DOT / DOI)
– Complexes (regulated by both)
• Jurisdiction was established through a series of Executive Orders (EOs) and Memoranda of Understanding (MOUs)
![Page 160: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/160.jpg)
EOs and MOUs
• Executive Order 11548 delegated responsibilities for regulating oil discharges (later superseded by E.O. 11735 and 12777). – EPA: Non-transportation-related facilities
– DOT: Transportation-related facilities
• EPA-DOT MOU (1971) defines transportation- and non-transportation-related.
• DOT-DOI-EPA MOU (1994) establishes responsibilities for offshore facilities, including pipelines.
![Page 161: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/161.jpg)
Non-Transportation-Related Facilities (CUPA Jurisdiction under APSA)
• Oil refining and storage facilities
• Industrial, commercial, non-exempt agricultural, and public facilities that use and store oil
• Waste treatment facilities
• Loading areas and racks, transfer hoses, loading arms, and other equipment used to transfer oil in bulk to or from highway vehicles or railroad cars
• Highway vehicles, railroad cars, and pipelines used to transport oil within confines of non-transportation-related facility
![Page 162: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/162.jpg)
Transportation-Related Facilities (DOT Jurisdiction)
• Onshore and offshore terminal facilities, including transfer hoses, loading arms, and other equipment used to transfer oil in bulk to or from a vessel; including storage tanks and appurtenances for the reception of oily ballast water or tank washings from vessels
• Transfer hoses, loading arms, and other equipment appurtenant to a non-transportation-related facility used to transfer oil in bulk to or from a vessel
• Interstate and intrastate onshore and offshore pipeline systems
• Highway vehicles and railroad cars that are used for the transport of oil
![Page 163: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/163.jpg)
Complexes (CUPA and DOT Jurisdiction)
• A facility with both transportation-related
and non-transportation-related activities is
a “complex facility” and is subject to the
dual jurisdiction of the CUPA under APSA
and DOT.
![Page 164: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/164.jpg)
Underground Piping Associated
with Aboveground Tanks
• APSA does regulate buried piping.
• The federal SPCC regulations contain
requirements for buried piping at a
regulated facility and APSA requires the
implementation of the SPCC Plan for
ASTs.
![Page 165: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/165.jpg)
APSA Regulated Piping
• Must be connected to the tank.
• APSA applies to:
– Piping in the containment area.
– Piping up to the first valve or flange outside the
containment area.
– If there is no containment, piping connected to the
first flange or valve.
• Federal SPCC rules for the facility may be
broader and include piping not integrally related
to the storage tank.
![Page 166: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/166.jpg)
APSA (SPCC) Compliance Verification
• Written Plan review – All rule-required content (and format)
– Facility-specific descriptions, procedures, etc. • Can be narrative, generic
• Inspect for compliance with the detailed rule requirements – Whether adequately described in the Plan or not
• Verifying the written Plan is consistent with field conditions
• Verifying that the facility is implementing the Plan as written
![Page 167: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/167.jpg)
DOT Compliance
![Page 168: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/168.jpg)
Applicable DOT Regulations
• Applicable to breakout tanks and pressure
relief tanks at petroleum transportation
facilities.
• DOT views the tanks as part of the
pipeline.
• CFR Title 49 – Transportation.
– Part 195 – Transportation of Hazardous
Liquids by Pipeline.
![Page 169: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/169.jpg)
Applicable Sections of DOT
Regulations for Tanks
• 195.132 -- Design and Construction of
Above Ground Breakout Tanks.
• 195.307 -- Pressure Testing Above
Ground Breakout Tanks (hydrostatic
testing).
• 195.432 -- Inspection of In-Service
Breakout Tanks.
• Subpart G -- Operator Qualification (OQ)
Training Program.
![Page 170: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/170.jpg)
DOT Applicable Regulations
Part 195.432 “Each operator must inspect the
physical integrity of in-service atmospheric and
low-pressure steel aboveground breakout tanks
according to API Standard 653 (incorporated by
reference, see §195.3). However, if structural
conditions prevent access to the tank bottom,
the bottom integrity may be assessed according
to a plan included in the operations and
maintenance manual under §195.402(c)(3).”
![Page 171: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/171.jpg)
Air Regulations
![Page 172: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/172.jpg)
Air Compliance
• Air Compliance rules are confusing, complex, and sometimes conflicting.
• This presentation will just provide a broad outline of rules.
• Rule applicability determination depends on:
– the year the tank was built,
– tank volume,
– vapor pressure of liquid.
![Page 173: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/173.jpg)
Clean Air Act (CAA) Regulations
• Ozone Precursors (VOCs) – Title 1, the
source is the individual tank.
– NSPS Rule, 40CFR Part 60
• Subpart K – Effective 6/11/73
• Subpart Ka – Effective 5/18/78
• Subpart Kb – Effective 7/23/84
– Control Technology Guidelines (CTG),
Reasonably Available Control Technology
(RACT) rules
![Page 174: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/174.jpg)
Clean Air Act Regulations (Con’t)
– Control Technology Guidelines (CTG),
Reasonably Available Control Technology
(RACT) rules.
• Applies to existing source in non-attainment areas.
• 1977 Fixed Roof Tank.
• 1978 EFR Tank.
• 1994 ACT for VOL Storage.
![Page 175: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/175.jpg)
Clean Air Act Regulations (Con’t)
• Air Toxics – Hazardous Air Pollutants
(HAPs Rule), Title III
– NESHAPS (40 CFR Part 61).
• These rules are specific to individual chemical in
individual tanks.
• Subpart Y is for Benzene.
– NESHAPS (40 CFR 63)
• Rule applies to all HAPs and the source is the
entire facility.
![Page 176: Above Ground Storage Tank](https://reader036.vdocuments.us/reader036/viewer/2022082218/55cf9a72550346d033a1c749/html5/thumbnails/176.jpg)
Clean Air Act Regulations (Con’t)
– NESHAPS (40 CFR 63) – Continued
• SOCMI HON
• Gasoline Distribution
• Petroleum Refineries
• Oil and Gas Production (a.k.a. – E&P MACT)
• Organic Liquids Distribution (a.k.a. – Old MACT)