abb_triguar

Upload: pankajskec

Post on 10-Apr-2018

217 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/8/2019 ABB_Triguar

    1/20

    ABB Safety

    Triguard 2

    TMR Safety Products

  • 8/8/2019 ABB_Triguar

    2/20

    T R I G U A R D S C 3 0 0 E

    2

    ADNOCAGIPAMEC

    Arabian Industrial FibersAzot RussiaBechtelBP/AMOCOBritish Nuclear FuelsCegelecChiyodaConocoCrescent PetroleumDowEcopetrolElf EnterpriseEPA Taiwan

    Exxon/MobilFoster WheelerGas Authority IndiaGazpromHanwha ChemicalHuntsman ChemicalsHyundai PetrochemicalIOCL IndiaKBRKNPCMadras Refinery

    McDermottPacific Gas & ElectricPemex

    PetrobrasPetrokemyaPetrominPetronas GasQatar GasQGPCRalph M ParsonsSaipemSARAS ItalySarawak ShellSaudi AramcoSnamprogettiSouthern Petrochemical

    TechnipTechnipgeoproductionTecnimontThai AromaticsTorch EnergyTotalToyo Engineering CoUK Atomic EnergyUS Steel

    Westlake Group

    ABBTMR Safety and Control

    August Systems, founded in 1978, was the worldwide pioneer in the development of Triple Modular Redundant

    (TMR) processing for real time, fault tolerant control. August Systems became an ABB company in 1997 adding

    TMR technology to the well established Dual Redundant Safety systems developed within ABB. The new

    business group of ABB Safety has been established to offer a broad range of safety solutions to industry.

    The Triguard SC300E products are available as engineered systems from ABB or products for integration by

    third party system integrators and OEMs, enabling the technology to be made available to a wide range of

    customers and applications.

  • 8/8/2019 ABB_Triguar

    3/20

    The ABB Triguard SC300E is theevolution of 20 years of combinedvendor and customer experienceintegrated into the design of theultimate TMR product. Building on aproven platform, the Triguard SC300Ecombines features that will maintainexcellence well into the future.

    Today ABB is a global supplier withkey operating bases in North America,Europe, Middle East and Asia Pacific.The Company has successfully

    supplied TMR products and systems tomeet an ever increasing diverse rangeof applications, including:

    3

    C o n t e n t s

    SC300E Features and Benefits 4 5

    SC300E Product Description 6 13

    SC300E Software Description 14 15

    T r i g u a r d S C 3 0 0 E

    International Standards 16

    Global Support 17

    Product Summary 18

    Product Specifications 19

    Safety Shutdown Electrical Stability and Load Control Process Shutdown Reactor Control Emergency Shutdown Critical Batch Processing Sequence and Interlock Control Fire & Gas Protection and Detection Critical Process Control Burner Management and Control Turbine and Compressor Control Wellhead/Sub-Sea Control Unmanned Installations

    FPSOs

  • 8/8/2019 ABB_Triguar

    4/20

    SC300E TMR Architecture

    Highest Availability

    The Triguard SC300E achieves thehighest possible TMR availability

    (99.999%) by maximising theMean Time To Failure (MTTF) anddecreasing the Mean Time To Repair(MTTR).

    Modern low power integratedtechnology allows the TMRarchitecture to be cost effective foran increasing range of high integrityapplications.

    Simple to Use, Operate

    and Maintain

    The Triguard SC300E TMR product

    functions as a single set of hardwareand software. The three processorsand triplicated I/O circuitry aretransparent to the user. Purchasing aTriguard SC300E system will provide:

    Lowest Life Cycle Cost The Maximum Safety andAvailability

    The Highest Level of Safety andOn-Line Maintenance

    Fail Safe Operation

    Failure modes of the processors,input/output circuitry, control program

    and watchdog timer circuits aremanaged so that circuits will default toa predetermined safe state.

    Highest Speed of Response

    By using advanced processortechnology, whilst maintaining thestability of the original core software,Triguard SC300E delivers an

    unrivalled scan time resolution

    of 10ms.

    T R I G U A R D S C 3 0 0 E

    Fewer unscheduled stoppages

    highest availability, fault tolerant electronics with transient immunity and 320 or 3210 voting

    Security for plant, product and people

    fail-safe operation at all levels provides plant, product and personnel with the highest security

    Quality data

    sequence of event and extensive diagnostics keep the operator informed

    FIELD

    TERMINATION

    FIELD

    TERMINATION

    MICRO

    CONTROLLER

    A

    PROCESSOR

    A

    PROCESSOR

    B

    PROCESSOR

    C

    MICRO

    CONTROLLER

    B

    MICRO

    CONTROLLER

    C

    MICRO

    CONTROLLER

    A

    MICRO

    CONTROLLER

    B

    6 ELEMENT

    2003

    VOTER

    MICRO

    CONTROLLER

    C

    INPUT MODULE

    READ ONLY LINKS

    READ ONLY LINKS

    READ ONLY LINKS

    READ ONLY LINKS

    LOOP

    BACK

    READ ONLY LINKS

    READ ONLY LINKS

    HOT REPAIR MODULE HOT REPAIR MODULE

    OUTPUT MODULE

    4

    P r o d u c t F a m i l y

    The ABB Triguard SC300E TMR product family gives unrivalled performance in areas of reliability, availability, test coverage,

    diagnostics and simplicity of operation. Advances in technology and improved production methods add cost benefits that

    give significant price/performance advantages.

  • 8/8/2019 ABB_Triguar

    5/20

    High speed of response benefits thecustomer application which specifiesSequence of Events recording (SoE)

    without the cost of additionalequipment. It also enables TMR to beused for applications requiring highspeed advanced control.

    Fault Tolerant Hardware and

    Software

    The system is designed to continue tooperate correctly with the presence ofa major component fault and iscapable of tolerating multiple, nonconcurrent faults.

    Easy to Use Software WindowsTM

    TriBuildTM configuration andapplication programming andTriCommandTM Server(WONDERWARE MMI interfacesoftware) are WindowsTM compliant,making the system easier to use forthe engineer and the operator. Forcustomers with existing ABB equipmentbackward compatibility is providedmaking upgrading or adding new

    facilities economic to implement.

    TriBuildTM and TriCommandTM Servercan be used with Windows NTTM.Features include:

    True multitasking capability Strategies can be saved on-line

    without halting the system operation Ability to upload the configuration Changes can be made on-line

    without halting the system operation Bumpless changeover of hot repair

    modules Comprehensive diagnostic displays

    for ease of maintenance

    Fault Tolerance and

    Selective RedundancyImprovements in the system to keep aprocess plant running safely withoutthe nuisance of false trips have beenachieved by full diagnostic coverageof all modules and selectiveredundancy.

    Processors 3210

    Input/Output Circuits 3210 or320

    Importance of Transient

    Immunity

    Comprehensive physical and electrical

    isolation combined with asynchronousprocessors and software votingensures the Triguard SC300E isimmune to transient errors.

    Smallest Footprint Size

    The Triguard SC300E TMR offers ourcustomers the best utilisation ofavailable space. ABB have developedplug and play cabinet layoutconfigurations that offer pre-designedhardware for system applications.

    Plug and socketed system cables makemarshalling and terminationinterconnection quick and easy toimplement.

    5

    SC300E Chassis

  • 8/8/2019 ABB_Triguar

    6/20

  • 8/8/2019 ABB_Triguar

    7/20

    each of the three processors to theI/O and communications modules.

    The Triguard SC300E has an operatingsystem known as the Real Time TaskSupervisor (RTTS), which is installed

    in each of the three processors. Theoperating system has been proven bywell over 10 million operational hours.RTTS is transparent to the user, itcontrols the off-line/start-up andon-line continuous diagnostic and

    voting functions, and provides a singleenvironment for the applicationprogramming.

    On power up, comprehensivediagnostic routines check and validatethe correct operating parameters of

    each processor.

    The Triguard SC300E operatingsystem, RTTS, will permit theprocessors to operate in a 321format allowing a system to continueto function with one healthyprocessor. A replaced processor willautomatically acquire the data itrequires to become operational fromthe on-line processor before goingon-line.

    Input/Output Modules

    All I/O module types share anelement of common design, providing

    component rationalisation andimplementing distributed processing.

    The three isolated TMR signal paths ofall input/output modules aresupervised by a micro-controllers

    which:

    Provides fault isolation Co-ordinate signal processing Provides diagnostics Provides on-line to off-line

    switching (hot repair)

    Provides data validation routines Provides data to the processor Provides latent fault detection

    A fault in one signal path cannot bepassed to another. I/O modules canbe fitted in any of the 10 slots in anychassis. Hot Repair is a customerconfigurable option on a per modulebasis. All modules are keyed toprevent improper installation.

    7

    Processor Module

    Processor

    Each Triguard SC300E TMR systemcontains three processors. Eachprocessor operates asynchronously inparallel with the other two processormodules and receives power from theredundant power supply units in themain chassis. A triplicated bus systemon the chassis backplane connects

    Key features of the processor modules: Intel processor Battery backed static RAM for

    application logic RAM Battery backup supply for six

    months 1 Mbyte of EPROM Real time clock for data logging to

    10ms resolution

    Triguard SC300E Chassis System plus cables

    and Termination Modules

  • 8/8/2019 ABB_Triguar

    8/20

    100% triplicated to provide maximumavailability.

    Each signal path conditions signalsindependently and provides fulloptical isolation between the field andthe SC300E. A fault on one signal pathcannot propagate to another.

    Automatic latent fault testing willdetect stuck on states.

    Line monitored inputs can beimplemented using analogue inputmodules with line monitor terminationcards.

    Each of the three micro-controllersoperate two isolated switches perchannel which together form a sixelement voting network.

    Digital Input Modules

    The types of digital input modulesavailable are:

    32 channel isolated24Vdc\120Vdc\120Vac TMR

    64 channel isolated 24Vdc Simplex

    All TMR digital input modules are

    Digital Output Modules

    The types of digital output modulesavailable are:

    32 channel supervised 24VdcTMR*

    16 channel supervised120Vdc\120Vac TMR*

    All TMR digital output modules areequipped with:

    Line monitoring circuits to confirmenergised field loop integrity

    Six element voting circuits formaximum safety and availability

    Automatic latent fault testing and

    diagnostics with 100% coverage (TMR)

    T R I G U A R D S C 3 0 0 E

    8

    P r o d u c t H a r d w a r e a n d S o f t w a r eD e s c r i p t i o n

    ISOLATOR

    ISOLATOR

    ISOLATOR

    ISOLATOR

    ISOLATOR

    ISOLATOR

    SIGNAL

    PROCESSING

    SIGNAL

    PROCESSING

    DRIVER

    SIGNAL

    STATUS LED

    MICRO

    CONTROLLE

    R A

    MICRO

    CONTROLLER

    B

    MICRO

    CONTROLLER

    C

    TEST

    TEST

    TEST

    INPUT

    FILTER

    SIGNAL

    PROCESSING

    Typical Digital Input Circuit

    INPUT

    FILTER

    INPUT

    FILTER

    DRIVER

    DRIVER

    DRIVER

    V/I

    MONITOR

    V/I MONITOR

    V/I MONITOROUTPUT

    STATUS LED

    MICRO

    CONTROLLER

    A

    MICRO

    CONTROLLER

    B

    MICRO

    CONTROLLE

    R C

    SUPPLY +

    SUPPLY

    OUTPUT

    A A B C

    B C

    C

    A B

    Typical Digital Output Circuit

    * Line monitoring of de-energised field

    loops may be achieved using alternative

    termination cards.

  • 8/8/2019 ABB_Triguar

    9/20

    Analogue Input Modules

    The types of analogue input modulesavailable are:

    32 channel isolated 0 to 5Vdc and 0to 10Vdc TMR(0 to 40mA and 0/4 to 20mA withburden resistor at the terminationcard)

    Each analogue input signal pathcontains three identical circuits of:

    Isolation Noise Filtering Multiplexing

    Amplification Analogue to digital conversion

    and each of the three circuits issupervised by a micro-controller.

    The three circuits synchronouslymeasure the input signals, vote thedata and transmit the data to theprocessors.

    The processors condition the input

    signal data, making any necessarycorrections, and then select themid-value from the three sets of inputdata. This mid-value is then used bythe control program.

    9

    The output voting, testing, feedbackand diagnostics are co-ordinated by theTriguard SC300E operating system. Allmodules provide 2oo3 voted outputs.

    Selective redundancy operating in321 or 320 modes is available,

    with selectable fall back to fail safe orretain last value states.

    Thermocouple Inputs

    Thermocouple and resistancethermometer inputs are provided bythe use of third party transmitters orconverters mounted in the field or

    within the marshalling cabinets. Inputsfrom these devices are then handledby the standard TMR analogue inputmodules.

    NOISE F ILTER

    NOISE FILTER

    NOISE FILTER

    MUX

    MUX

    A/D

    A/D

    A/D

    AMP

    AMP

    AMP

    MUX

    1

    32

    1

    32

    1

    32

    SELECTVREF 1 VREF 2

    VREF 1

    VREF 1 VREF 2

    VREF 2

    SELECT

    SELECT

    MICRO

    CONTROLLER

    A

    MICRO

    CONTROLLER B

    MICRO

    CONTROLLER

    C

    RANGE

    RANGE

    RANGE

    Typical Analogue Input Circuit

  • 8/8/2019 ABB_Triguar

    10/20

    T R I G U A R D S C 3 0 0 E

    10

    Analogue Output Modules

    4 channel 12 bit resolution420mA TMR

    Each of the three Triguard SC300Eprocessors sends voted output voltagedata to the analogue output modules.The commands are received viathe bus system by the threemicro-controllers on each module.

    Each micro-controller controls a digitalto analogue converter which drivestwo elements of the six elementoutput voting network. Each elementof the six element voter is an isolatedfield effect transistor operated withinits linear range. The final output ofthe field device is selected as themid-value from the three circuits ofoutput data.

    Feedback to each of the threemicro-controllers provides continuouschecking for correctness. Diagnosticsdeclare any fault to the processors formaintenance information and action.

    P r o d u c t H a r d w a r e a n d S o f t w a r eD e s c r i p t i o n

    Typical Analogue Output Circuit

    V MONITOR

    D/A CONVERTER

    D/A CONVERTER

    D/A CONVERTER

    V MONITOR

    V MONITOR

    MICRO

    CONTROLLER A

    MICRO

    CONTROLLER B

    MICRO

    CONTROLLER C

    V REF

    MID VALUESELECTED

    A

    B C A B

    C

    A B C

  • 8/8/2019 ABB_Triguar

    11/20

    a gear wheel for example, andaccumulates this data to an accuracyof +_0.01% over 20Hz to 20KHz.

    Output values to 12 bit resolution canprovide voted and validated data tofield devices for control (see analogueoutput module for output circuitoperation).

    Communications Module

    A four channel serial communicationsmodule is always fitted to a Triguard

    SC300E TMR system to allowcommunications to the engineeringworkstation and is installed in I/O slotnumber 10 of the main chassis. Allfour channels operate RS232\423 upto 19.2 kbits/sec and all fourcommunication ports are fully isolated.

    The four channel communicationsmodule is directly addressed by thethree Triguard SC300E processors andcontains a micro-computer thatcontrols the four programmable

    multi-protocol ports. Data receivedfrom the three processors is voted2oo3 providing correct data foronward transmission.

    High speed network

    connectivity feature (to be

    released)

    Triguard may be interfaced to standardcommunications networks such asEthernet/TCP/IP using approvedgateway products.

    DCS connectivity includes: Yokogawa Electric, Elsag-Bailey,

    Fisher Rosemount, ABB, Honeywelland Foxboro

    11

    Pulse Input Analogue Output

    Module (PIANO)

    8 channel, 4 pulse input, 4 analogueoutput TMR

    The PIANO module contains fullytriplicated circuits. Each pulse inputpath receives input pulses, a valueequivalent to the number of teeth on

    O/P

    DRIVERS

    020mA

    O/Ps

    PULSE

    I/Ps

    MODULE

    POWER HEALTHCIRCUITRY

    SYSTEM SUPPLY 1

    I/O BUS A

    I/O BUS B

    I/O BUS C

    HEALTH LED ONLINE LEDS

    ONLINE/

    OFFLINE

    SWITCH

    SYSTEM SUPPLY 2FIELD SUPPLY 1FIELD SUPPLY 2

    ONLINECIRCUITRY

    MODULE TYPEIDENTIFY

    I/P

    FILTERS

    TMR

    INTERFACE

    (PULSE)

    TMR

    INTERFACE

    (ANALOGUE)

    INDICATORS

    MICROCONTROLLER

    A

    WATCHDOG

    WATCHDOG

    WATCHDOG

    MICROCONTROLLER

    B

    MICROCONTROLLER

    C

    COMMON INTERFACE CIRCUITRY

    Typical Pulse Input Circuit

    Serial Communication Module

  • 8/8/2019 ABB_Triguar

    12/20

    done bumplessly without interruptingthe normal operation of the systemand process.

    The operating system, RTTS, routinelyexecutes a hot repair task, checkingand validating that all configurationdata is correct, eg. correct I/Omodule, on-line/off-line hot repairfunctions.

    There are three ways to replace anon-line I/O module:

    Module with no additional hotrepair slot single slot hot repair Module has an unpopulated hot

    repair partner slot manual hotrepair

    Module with a populated hot repairpartner slot hot repair

    16 channel analogue input 4 channel analogue output 16 channel digital output with line

    monitoring 4 channel pulse input

    DIN rail mounted termination cardsfor field wiring can be supplied as aneasy to fit method to route field cablesto the Triguard SC300E system I/Omodules, and distribute field wettingcurrent to each I/O point.

    A termination card has an associatedsystem cable fitted with DINconnectors to provide the plug and

    socket arrangement. Cable lengths canbe specified to suit the application.

    Alternative cables with Elcoconnectors or free wires at the fieldend are available for third partymarshalling systems.

    Power and fusing for the field circuitsare standard. Options are available tosuit all field configurations.

    System cables from the TriguardSC300E are also available with free

    wire ends so that the system mayconnect to a separate cablemarshalling and power/fusing system.

    T R I G U A R D S C 3 0 0 E

    12

    P r o d u c t H a r d w a r e a n d S o f t w a r eD e s c r i p t i o n

    Hot Repair Facility

    A quick repair procedure, once anyfault is revealed, is important in thetotal fault tolerant product strategy.

    The hot repair facility achieves a quickand easy repair by the user and this is

    All I/O modules can be programmedfor a hot repair facility. A wrong orfaulty module in an allocated hotrepair I/O slot will not be accepted.Hot repair slots are selected to benext to the system I/O residentmodule.

    Field Termination Cards

    The types of termination cardsavailable:

    16 channel digital input 32 channel digital input 16 channel digital output

  • 8/8/2019 ABB_Triguar

    13/20

    2000mm high cabinets, and providefront and rear access. Front accessonly configurations are available.

    System Structure

    A major benefit of the TriguardSC300E system is that it can be assmall as one chassis or as large as 15,giving a 9,500 total I/O capacity. TheTMR bus extender modules and cablesets are used to size the system to suitthe application. Interfacing to remoteTMR I/O chassis or gateway modulesto connect to DCS networks, canbe provided to suit a combineddistributed safety and control strategy.

    A customer who has a futurerequirement to add to an existingsystem will find the Triguard SC300Eeasy and economical to extend.

    Forward and backward compatibilitymeans that users can readily intermixCS300 and Triguard SC300E systemsusing the same programming tools.

    Application logic written for a CS300system will run with minimum

    modification on the Triguard SC300E.

    13

    Cabinet Layouts

    Optional cabinets to house theTriguard SC300E TMR control systemare industry standard 19 rackmounted configurations with a widthof 600mm and a depth of 800mm. Thelayouts shown are based on a standard

    A fully distributed safety system,using the Triguard SC300E, can beconfigured by utilising a Safeway8000 bus structure and theTriguard peer to peer safetyapproved protocol.

    Triguard SC300E System Architecture

    MAIN CHASSIS

    EXTENSION

    CHASSIS 1

    16-WAY

    TERMINATION

    CARDS

    161

    161

    Field Terminals

    3 x Twin Fibre

    Optic Cables

    REMOTE

    CHASSIS 14

    EXTENSION

    CHASSIS 13

    Up to 2 km

    Typical Triguard SC300E Cabinet Layouts

    Triguard SC300E

    MAIN CHASSIS

    EXTENSION CHASSIS

    Field Power Supplies

    FIELD POWER FUSING

    AND DISTRIBUTION

    FIELD MARSHALING

    TERMINALS

    TERMINATION

    CARDS

  • 8/8/2019 ABB_Triguar

    14/20

    TriBuildTM

    TriBuild is an easy to use, menudriven, software package running

    under Windows NTTM

    . It is used forthe creation of system applicationlogic of the Triguard SC300Econtrol system.

    Key features of TriBuild:

    System Configurator easy guidefor system build

    Ladder Annotator adds notes tothe ladder logic

    Network Editor on-line/off-lineediting of logic functions

    On-Line Help reduces need torefer to printed manual

    Ladder Simulator allows testingduring program development

    Built-In Compiler for high leveluser functions

    Password Protection selectiveaccess and protection

    Function Block Programmingusing IEC 1131 standard function asapplicable to safety

    These can be developed quickly andeffectively with the assistance ofsearch and replace, cut and paste and

    a standard library of logic symbols andprogramming functions. Completedcontrol programs can be loaded into aTriguard SC300E system and theexecution of the control program canbe monitored on-line with the TriBuild

    workstation.

    advanced fault tolerant controlapplications

    Application specific control

    functions, eg auto-test routines, gasdetection calibration tables,advanced control

    System interrogation Control and user changes with date

    and time Off-line configuration, simulation

    and applications testing of thecontrol programs

    The Triguard SC300E supports threemain application software packages,all are Windows compatible:TriBuildTM for developing and

    programming application logicTriCommandTM a display and

    control system workstation(WONDERWARE)

    TriLogTM simple PC basedalarm/event logger

    The TriBuild Workstation is connectedto a Triguard SC300E TMR system viathe communications module.

    TriBuild provides on and off-lineconfiguration, programming,documentation and testing functions.Programming uses both conventionalladder logic displays, function blockprogramming and structured networks.

    TriBuildTM software provides:

    A comprehensive library ofprogramming elements, eg logic,arithmetic, data conversion, timers,counters, block elements, bit shift,comparators, mid value select,NooM voting blocks

    An environment for users todevelop special functions, functionblocks, custom programs for

    T R I G U A R D S C 3 0 0 E

    14

    S o f t w a r e

    TMR Software Architecture

    CPU/CPU

    COMMUNICATIONS

    FIELD I/O

    INTERFACE

    SYSTEM

    START UP AND

    DIAGNOSTICS

    R.T.T.S.

    VOTED DATA

    BASE

    APPLICATION

    LOGICAPPLICATION

    COMMUNICATIONS

    MESSAGE

    PROCESSING

    WORKSTATION

    INTERFACE

    TRIBUILD

    WORKSTATION

    DCS AND

    3rd PARTY

    OPERATOR STATION

    AND SERIAL I/O

  • 8/8/2019 ABB_Triguar

    15/20

    provides real time system control andmonitoring facilities. It can operate aspart of a Triguard SC300E system in a

    single station configuration or asmultiple TriCommand stations fordistributed applications. TriCommand

    workstations can be connectedto a Triguard SC300E system via peerto peer, single, or dual serialcommunication links, networked viasingle or dual redundant LANs.

    TriCommand is Windows NTTM

    compliant. Standard off-the-shelfhardware makes customer ownershipand support easy to achieve.

    TriCommand workstations may beinstalled in the control room foroperator display and control or at aremote location where there may be aneed for local information and control.

    TriCommand allows a user to startsmall and expand into an integratedenvironment providing a singleseamless network. Expansion is simpleand cost effective.

    Key features of TriCommand: A real time database of up to 32,000

    points that can be mapped to field

    or virtual I/O points Dynamic Data Exchange (DDE)allowing TriCommand to pass datato other Windows applications, egExcelTM

    Supports a comprehensive range ofindustry standard protocols, such asTCP/IP via the DDE server library

    Can display an almost unlimitednumber of mimic pages

    Extensive alarm handlingcapabilities, including accept, reset,cross functions (for multiple

    systems), zone hierarchy, first out,status, prioritising, displays,summaries

    Data logging, data archiving, datatrending

    Event status, event history, eventdisplay, event printing

    Fault diagnostics communication,systems

    Advanced control digital, analogue Multi-level security access

    The Graphical User Interface foroperators, engineers and managers isa multiple Windows display on a

    single screen. Displays can howeverbe locked on full screen making theWindows feature unavailable.

    Operators can choose different meansof navigating and interacting with thesystem, from full keyboard to arestricted pushbutton selection pad.Engineers can develop graphicaldisplays using a powerful displaybuilder which can be tailored to theneeds of the process operation.

    TriLogTM

    TriLog is a message logger, it isdesigned to monitor up to fourTriguard SC300E systems acceptingand storing sequence of event andalarm messages from each system. Ituses a dedicated PC with WindowsNTTM compliance. Windows areallocated to display time and datetogether with current and archivedinformation from each system.

    15

    TriBuild provides a secureenvironment to make programchanges on-line and withoutinterrupting the normal processoperations.

    TriCommandTM

    TriCommand is a PC-based operatorworkstation, utilising WonderwaresInTouchTM products. TriCommand

    TRIBUILD Windows Workstation

  • 8/8/2019 ABB_Triguar

    16/20

    Increased awareness of safety integraldesign has been brought about by theintroduction of international legislationIEC 61508. These standards requireformal assessment of hazards to takeplace and the use of certified systemsfor all hazardous processes.

    Comprehensive product testing is

    performed at board and system levelsincluding temperature and powercycling to eliminate infant mortalityfailures.

    Rigorous control of any hardware orsoftware change is maintained andinternal and external audits areperformed at regular intervals toensure the highest quality of productprior to shipment.

    Product pre-delivery quality assuranceincludes a 100% test to ensure product

    quality to the customer on delivery.

    Third Party Certification

    With the ever increasing demand forindependent international certification

    and end user specific approvals,ABBs products meet the requirementsoutlined in the standards and guidelines as follows:

    TUV Rheinland/Berlin Brandenburg

    (and Product Services)

    Safety Related Applications Requirement Class 5 and 6/VDE 0801Suitable up to Safety IntegrityLevel 3 (SIL 3)/IEC61508see http://www.tuvasi.com

    European Union CE MarkLow voltage directiveEMC directive

    USA/Canada

    UL/C Industrial Control Equipment

    GOST

    Russian guidelines for safetyrelated systems

    IEC 61508

    Functional safety requirements toSafety Integrity Levels 1 to 3

    NFPA 72

    8501 and 8502

    EN54

    T R I G U A R D S C 3 0 0 E

    16

    I n t e r n a t i o n a l S t a n d a r d s

    Quality

    ABB quality system meets International Standards and is certified to the requirements of BS EN ISO 9001

    1994, Certificate Number FM 1353 for safety systems and products. The certification for Quality Assurance at

    ABB, covers all aspects of design, manufacturing, testing, software verification, software validation and

    service activities.

  • 8/8/2019 ABB_Triguar

    17/20

    Product Technical Support

    ABB operates a worldwide producttechnical support service for all OEMs

    and System Integrators. Additionally,where required, ABB can provideinstallation supervision, commissioningand site acceptance testing.

    Consultancy and Application

    Engineering consultancy services aredesigned to provide assistance withthe assessment of reliability andavailability applied to the use andapplication of TMR Systems. Suppliersof systems are frequently requested toprovide:

    Markov modelling Fault tree analysis Failure mode effects and criticality

    analysis Reliability/availability calculations Life cycle cost analysis Functional design specifications Engineering assessments

    Application engineering support andassistance is available pre-sales and

    post-sales, and includes advice on:

    Correct hardware configuration Communications and interfacing Programming

    Software/firmware upgrades Remote diagnostics and problem

    solving

    Maintenance and operations

    Spares and Repairs

    All regions carry a quantity of productinventory to support the installedbase. Each region has sufficientTriguard SC300E equipment toperform customer demonstrations,hardware and software applicationtesting, and first line troubleshootingfor any product problem solving.

    Spares and repairs policies can be

    recommended to provide customerswith the support necessary tomaximise the performance of theirTMR system, minimising life-cyclecost.

    Recommendations may include:

    All spares held by the customers

    Minimum spares held by customer,guaranteed replacement times fromABB

    Planned maintenance contracts Total support contracts by ABB Emergency callouts

    Product Training

    Comprehensive training facilities andtraining courses are available and cancover every aspect of the maintenanceand application of TMR technology.

    Courses are available for:

    OEM/Integrator Configurations Project Design Engineers Plant Technicians/Maintenance

    Engineering Operations Personnel Management Teams

    17

    Support services can be obtained from any of the ABB Worldwide

    Business and Engineering Centres. The resources and expertise within

    the company can be channelled into any region as required to suit a

    particular customer demand. Each region can support the following range

    of services:

    G l o b a l S u p p o r t

    Product Test Facility

    Training Facility

  • 8/8/2019 ABB_Triguar

    18/20

    T R I G U A R D S C 3 0 0 E

    18

    P r o d u c t S u m m a r y

    Description Model

    SC300E MAIN Chassis, complete with 3 processors and 2 PSUs

    SC300E main chassis, 110/240Vac CXP 10A 11SC300E main chassis, 24Vdc CXP 10D 24

    SC300E Extension I/O Chassis, complete with 3 bus extender modules and 2 PSUs

    SC300E extension chassis 110/240Vac CXB 10A 11SC300E extension chassis, 24Vdc CXB 10D 24

    SC300E Remote I/O Chassis, complete with 3 fibre optic bus extender modules and 2 PSUs

    SC300E master remote I/O chassis, 110/240Vac CXM 10A 11

    SC300E master remote I/O chassis, 24Vdc CXM 10D 24

    SC300E slave remote I/O chassis, 110/240Vac CXS 10A 11SC300E slave remote I/O chassis, 24Vdc CXS 10D 24

    SC300E Input/Output Modules

    Serial communications module, 4 port, RS232 MSR 04 XI

    32 channel digital input module, 24Vdc MDI 32 BIS32 channel digital input module, 120Vac/dc MDI 32 FIS32 channel digital input module, line monitored, 24Vdc MDI 32 SNL64 channel digital input module, simplex, 24Vdc MDI 64 BNS

    32 channel digital output module, line monitored, 24Vdc MDO 32 BNS16 channel digital output module, line monitored, 120Vac/dc MDO 16 FNS

    32 channel analogue input module, isolated, 0/5Vdc MAI 32 LAD32 channel analogue input module, isolated, 0/10Vdc MAI 32 MAD

    4 channel analogue output module, non isolated, 4/20mA MAO 04 NND

    4 Channel pulse input/4 channel analogue output module (PIANO), 4/20mA MHB 44 IND

    64 channel display driver, motherboard (single/dual) TM117DMxM/B

    64 channel display driver, daughterboard (single) TM117DMxD/B

    Hot repair adaptor (set of two) THR Blanking plate ML

  • 8/8/2019 ABB_Triguar

    19/20

    19

    G e n e r a l P r o d u c t S p e c i f i c a t i o n s

    Overall Sizes

    All Chassis Types 19 Rack Mounted x 398mm height x 474mm depthAll I/O Module Types 365.8mm high x 28mm width x 394mm depthAll Termination Cards Types DIN Rail mounted 162mm high x 110mm width x 56mm depthAll Power Supply Types 198mm high x 67mm width x 417mm depth

    Approximate Weights

    Main Chassis with two PSUs and three Processors 16.8kg (37.0lb)Extension/Remote Chassis with two PSUs andThree Extender Modules 17.1kg (37.7lb)Power Supply Module 2.3kg ( 5.1lb)

    Processor Module 1.4kg ( 3.1lb)I/O Module 1.6kg ( 3.5lb)Communication Module 1.1kg ( 2.4lb)

    Termination Cards 310gm ( 0.7lb)Fully Populated Chassis 32.3kg (71.2lb)

    Fabrication and Paint Finish Aluminium Chassis with Dusty Grey, Front Panel

    Finish (RAL 7037)

    Environment Specifications

    Operating Temperature 060CStorage Temperature with Battery 30C to +75CRelative Humidity 5 to 95% Non-Condensing

    Vibration 1g at 5 to 500 Hz SinusoidalShock 20G for 12msElectro-static Discharge 8kV (IEC 801-4, level 3)

    EMC

    Immunity EN50082-2Emissions EN50081-2

    Power Supply Modules

    Nominal Input Voltage 24Vdc 120/240VacInput Voltage Range 20-36Vdc 92-132V & 192-276VacInput Power 200W Max 235W MaxOutput Power 150W Max 175W MaxOutputs 5.35V, 12Vdc 5.35V, 12VdcOutput Hold Up Time 20ms 20ms

    Fuse Ratings 10A 5AIsolation 2500Vdc 3750VacOutput Current 23A, 4A 23A, 4A

  • 8/8/2019 ABB_Triguar

    20/20

    ABB is a global electrical engineering group which is active in manyareas associated with the generation, transmission, distribution anduse of electrical power. The ABB Group comprises 1,000 companies

    in 140 countries.

    ABB is one of the Worlds largest suppliers of industrial automation anddrive systems, products and services. The company uses its uniqueglobal resources to provide the highest level of customer value throughindustry-leading technology and cost effective, industry-specificapplication knowledge with uncompromising commitment to quality.

    ABB is a leading supplier of fault tolerant TMR products and systemsfor emergency shut down, fire and gas and critical controlapplications.

    Email: [email protected]

    ABB Industri LtdManor RoyalCrawleyWest SussexRH10 2PUK

    Tel: +44 (0)1293 442135Fax: +44 (0)1293 442149

    ABB Automation Inc.3010 Briarpark DriveHouston, Texas 77042USA

    Tel: +1 713 821 8800Fax: +1 713 821 3510

    ABB Automation LtdHoward RoadEaton SoconSt Neots

    HuntingdonCambridgeshirePE19 3EU

    Tel: +44 (0)1480 475321Fax: +44 (0)1480 217948

    ABB Automation Pte Ltd539 Yishun Industrial Park ASingapore 768740

    Tel: +65 756 7655Fax: +65 257 9839

    ABB Industri ASHasleveien 50PO Box 6540 Rodelkka0501 OsloNorway

    Tel: +47 22 87 20 00Fax: +47 22 37 74 23