abb © ptmv - 1 abb medium voltage outdoor apparatus portfolio july 2004 brian johnson

36
ABB © PTMV - 1 Medium Voltage Outdoor Apparatus Portfolio July 2004 Brian Johnson

Upload: joy-hicks

Post on 14-Dec-2015

242 views

Category:

Documents


2 download

TRANSCRIPT

AB

B© P

TM

V -

1

Medium Voltage Outdoor Apparatus Portfolio

July 2004

Brian Johnson

AB

B© P

TM

V -

2

Typical Overhead Distribution System

B RB / R

B

B

S

Cutout OR1 Ph Sectionalizer

Switch - Manual- Automated

3PH

3PH

1PH

Line Recloser

CapacitorSwitch

Breaker /Recloser

3 Ph Sectionalizer

Switch - 1 Ph Manual OR Fuse OR Cutout

Switch - 1 Ph Manual

3PH

Reconfiguration Switch - Manual- Automated

AB

B© P

TM

V -

3

PTMV Outdoor Apparatus Portfolio

Outdoor Circuit Breakers

Reclosers

Automated Sectionalizers

Sealed Switches

Air Switches

Fused Cutouts

Not in portfolio, today: Voltage Regulators

Insulators, Cables, Hardware

AB

B© P

TM

V -

4

Outdoor Circuit Breakers

Dead Tank

Live Tank

Type R15-27 kV

ANSI

Type V38 kVANSI

Type SDB 1212 kVIEC

Type R-Mag15-27 kV

ANSI & IEC

Type OHB24-36 kV

IEC

AB

B© P

TM

V -

5

Type R Dead Tank Circuit Breaker

Vacuum Interruption

Spring Operated Mechanism

ANSI C37.06 – 1997

Dead tank design reduces cost of CTs and installation

Manufactured ABB, USA

VoltageRated

Continuous Current

Interrupting Current

15 – 27 kV 600 – 3,000 A 12 – 25 kA

AB

B© P

TM

V -

6

Type R-Magnetic Dead Tank Circuit Breaker

Vacuum Interruption

Magnetic Actuator Mechanism reduces maintenance costs and concerns

ANSI C37.06 – 1997 & IEC 56

Manufactured ABB, USA

VoltageRated

Continuous Current

Interrupting Current

15 – 27 kV 600 – 3,000 A 12 – 25 kA

AB

B© P

TM

V -

7

Type V Dead Tank Circuit Breaker Vacuum Interruption Spring Operated Mechanism 150 or 200 kV BIL High capacitor switching ratings to use

to protect and switch substation capacitor banks

Redundant vacuum bottle ANSI C37.06 – 1997 Manufactured ABB, USA

VoltageRated

Continuous Current

Interrupting Current

38 kV 1,200 – 2,000 A 25 – 40 kA

AB

B© P

TM

V -

8

Type SDB 12 Live Tank Circuit Breaker

Vacuum Interruption

Spring Operated Mechanism or Magnetic Actuator Drive

IEC

Manufactured ABB, India

VoltageRated

Continuous Current

Interrupting Current

12 kV 630 – 1,600 A 18.4 – 26.3 kA

AB

B© P

TM

V -

9

Type OHB Live Tank Circuit Breaker

SF6 Interruption

Spring Operated Mechanism

IEC

Manufactured ABB, India

VoltageRated

Continuous Current

Interrupting Current

24 – 36 kV 2,500 A 31.5 kA

AB

B© P

TM

V -

10

Automated Reclosers and Sectionalizers

OVR – 3 PhaseRecloser

15-38 kVANSI & IEC

OVS – 3 Phase

Sectionalizer15-38 kV

ANSI & IEC

Autolink –1 Phase

Sectionalizer12-38 kV

IEC

OVR –1 Phase Recloser

15-38 kVANSI & IEC

AB

B© P

TM

V -

11

OVR Three Phase Automated Recloser Embedded Vacuum Interrupters in

Solid Dielectric (no oil, nor SF6 to maintain)

Magnetic Actuators

Pole or Substation Mounting

Programmable PCD Control to automate system protection – loop schemes, automatic alternate settings

ANSI C37.60+90 – 1997

Manufactured ABB, USA

12 – 16 kA560 – 800 A15 – 38 kV

Interrupting Current

Rated Continuous

CurrentVoltage

AB

B© P

TM

V -

12

Ratings: 15 – 38 kV 630 / 800 Amp Up to 170 kV BIL 12.5 kA

Compact, lightweight HCEP Insulation Material Superior life – rated for 10,000 operations 2nd Generation Magnetic Actuators Environmentally friendly – no oil or gas ANSI C37.60+90 – 1997 Manufactured ABB, USA

OVR Single Phase Automated Recloser

AB

B© P

TM

V -

13

OVS Three Phase Automated Sectionalizer

Embedded Vacuum Interrupters in Solid Dielectric

Magnetic Actuators

Pole or Substation Mounting

Simple Sectionalizing Control

ANSI & IEC

Manufactured ABB, USA

16 – 20 kA630 A15 – 38 kV

Short Time Withstand Current

3 Sec. Sym

Rated Continuous Current

Voltage

AB

B© P

TM

V -

14

Autolink Single Phase Sectionalizer

Single Phase Automatic Sectionalizer

Specialty device to reduce nuisance tripping problems

Magnetic Actuation to eliminate fuse replacement costs

IEC

Manufactured ABB T&D Ltd, Australia

VoltageRated

Continuous Current

Interrupting Current

Actuating Current

12 – 36 kV 250 A 6 kA 5 – 224 A

AB

B© P

TM

V -

15

Sealed Contact, Loadbreak Switches

OVS15-38 kV

ANSI & IEC

Sectos NXA38 kV

ANSI & IEC

Sectos NXBD12-24 kV

IEC

Sectos NXB12-24 kV

IEC

AB

B© P

TM

V -

16

OVS Automated Switch Embedded Vacuum Interrupters in Solid

Dielectric Magnetic Actuators ISD or PCD Control for simple applications or

sophisticated automation schemes ANSI & IEC Manufactured ABB Inc., USA Development project to add visible break 10,000 loadbreak operations SCADA Ready – integrated current sensing,

voltage sensing on frame, control cabinet space and power for customer communications

16 – 20 kA630 A15 – 38 kV

Short Time Withstand Current

3 Sec. Sym

Rated Continuous Current

Voltage

AB

B© P

TM

V -

17

Sectos NXA Switch Disconnector

Two-position Load Break-Fault Make Switch Disconnector

Single or Double Spring Mechanism Manual (Hook stick) or Integrated Motor

Operated Shipped complete, Simple to install SF6 insulation IEC (General Purpose Type) & ANSI Manufactured ABB, China

12.5 kA

Short Time Withstand Current 3 Sec. Sym

630 A36 kV (38 kV ANSI)

Rated Continuous

CurrentVoltage

AB

B© P

TM

V -

18

Sectos NXB Switch Disconnector

Two or Three-position Load Break-Fault Make Switch Disconnector

Single or Double Spring Mechanism

Manual (Hook stick) or Integrated Motor Operated

Shipped complete, Simple to install

Available in single phase for special applications

SF6 insulation

IEC (General Purpose Type)

Manufactured ABB, China

20 kA

Short Time Withstand Current

3 Sec. Sym

630 A12 – 24 kV

Rated Continuous

CurrentVoltage

AB

B© P

TM

V -

19

Sectos NXBD Switch Disconnector Two Switches in Same Housing

Two Switched Ways and One Tapped Way

Two or Three-Position Load Break-Fault Make Switches Disconnector

Single or Double Spring Mechanism

Manual Operation by Hook Stick

Shipped complete, Simple to install

SF6 Insulation

IEC (General Purpose Type)

Manufactured ABB, China

20 kA

Short Time Withstand Current

3 Sec. Sym

630 A12 – 24 kV

Rated Continuous Current

Voltage

AB

B© P

TM

V -

20

Three Phase Air Switch Disconnects

Series ‘R’12-36 kV

IEC

Series ‘U’12-36 kV

IEC

NPS12-36 kV

IEC

AB

B© P

TM

V -

21

NPS Switch Disconnector Vertical and Horizontal Break Vertical and Horizontal Pole-

Mounted Optional Load Break and Load

Make Control Units (DTU) available IEC (Limited Purpose Type) Manufactured ABB, Finland Easy to localize, if desired

Up to 16 kA630 A12 – 24 kV

Short Time Withstand Current

3 Sec. Sym

Rated Continuous

CurrentVoltage

AB

B© P

TM

V -

22

Series ‘R’ Disconnect Switch

Vertical Break

Horizontal & Vertical Pole Mounted

Optional Load Break

IEC

Manufactured ABB, Australia

Up to 31.5 kA800 – 2000 A12 – 36 kV

Short Time Withstand Current

3 Sec. Sym

Rated Continuous

CurrentVoltage

AB

B© P

TM

V -

23

Series ‘U’ Disconnect Switch

Side Break

Horizontal & Vertical Pole Mounted

Optional Load Break

IEC

Manufactured ABB, Australia

20 kA630 A12 – 36 kV

Short Time Withstand Current

3 Sec. Sym

Rated Continuous

CurrentVoltage

AB

B© P

TM

V -

24

Series ‘SLD’ & DCD

12-36 kVIEC & ANSI SID, LSID &

SLS12-38 kV

NEMA, ANSI & IEC

Single Phase Air Switch Disconnects

RBD & SLDT – Recloser

Bypass Switch15-36 kV

ANSI & IEC

ITD – Inline Disconnect

15-36 kVANSI

Series ‘SLSB’12-24 kV

IEC

AB

B© P

TM

V -

25

Series ‘SLD’ & ‘DCD’ Disconnect Switches

SLD/DCD: Single Phase Double Insulator

SLD/DCD: Horizontal & Vertical Pole Mounted

SLD – IEC; DCD - ANSI

SLD - Manufactured ABB, Australia

DCD - Manufactured ABB, USA

16 – 25 kA630 – 900 A12 – 36 kV

Short Time Withstand Current

3 Sec. Sym

Rated Continuous

CurrentVoltage

AB

B© P

TM

V -

26

ITD Disconnect Switches

ITD: Inline Tension Single Phase Disconnect

Installs directly into the distribution line

ANSI Standards

ITD - Manufactured ABB, USA

200kV BIL insulation to limit flashovers

16 – 25 kA600 – 900 A12 – 36 kV

Short Time Withstand Current

3 Sec. Sym

Rated Continuous

CurrentVoltage

AB

B© P

TM

V -

27

SID, LSID, SLS Disconnect Switches

SID & SLS: Single Phase

LSID: Single Phase Load Break

SID & LSID: NEMA & ANSI

SLS: IEC

SID & LSID: Manufactured ABB, USA

SLS: Manufactured ABB, Australia

Good design for narrow installations and riser pole installations

16 – 40 kA600 – 900 A12 – 38 kV

Short Time Withstand Current

3 Sec. Sym

Rated Continuous

CurrentVoltage

AB

B© P

TM

V -

28

Series RBD & ‘SLDT’ Bypass Switches

RBD/SLDT: Single Phase Bypass Switch

RBD/SLDT: Horizontal & Vertical Pole Mounted

Main application – bypassing reclosers and voltage regulators to perform maintenance

SLDT – IEC; RBD - ANSI

SLDT - Manufactured ABB, Australia

RBD - Manufactured ABB, USA

16 – 25 kA630 – 900 A12 – 36 kV

Short Time Withstand Current

3 Sec. Sym

Rated Continuous

CurrentVoltage

AB

B© P

TM

V -

29

Series ‘SLSB’

Single Phase By-Pass Disconnector

Integrated Fused Cutout for fault protection

IEC

Manufactured ABB, Australia

VoltageRated

Continuous Current

Interrupting Current

12 – 24 kV 630 A 25 kA

AB

B© P

TM

V -

30

Fused Cutouts

Type NCX7.8-38 kV

NEMA & ANSI

Type ICX7.8-38 kV

NEMA & ANSI

Series ‘V’12-36 kV

IEC

Type LBU-II7.8-34.5 kV

NEMA & ANSI

Type EU & EUH2.6-7.8 kV

NEMA & ANSI

Most complete portfolio in the world!

AB

B© P

TM

V -

31

Type NCX Fused Cutout

VoltageRated

Continuous Current

Interrupting Current

7.8 – 38 kV 100 – 300 A 2 – 20 kA

NEMA & ANSI

Manufactured ABB, USA

Dual-venting to reach higher interrupting ratings

AB

B© P

TM

V -

32

Type ICX Fused Cutout

VoltageRated

Continuous Current

Interrupting Current

7.8 – 38 kV 100 – 300 A 8 – 16 kA

Interchangeable Fuse Tube (with S & C, Chance, Cooper)

Moisture Proof Fuse Tube reduces swelling over time

NEMA & ANSI

Manufactured ABB, USA

AB

B© P

TM

V -

33

Type LBU-II Fused Cutout

VoltageRated

Continuous Current

Interrupting Current

7.8 – 34.5 kV 100 – 300 A 6 – 20 kA

Integrated Load Break Device to loadbreak safer, simpler and without special tools

NEMA & ANSI

Manufactured ABB, USA

AB

B© P

TM

V -

34

Series ‘V’ Fused Cutout

Single & Three Phase

IEC

Manufactured ABB, Australia

VoltageRated

Continuous Current

Interrupting Current

12 – 36 kV 100 A 2 – 8 kA

AB

B© P

TM

V -

35

Type EU and EUH

VoltageRated

Continuous Current

Interrupting Current

2.6 – 7.8 kV 100 – 200 A 4 – 20 kA

Enclosed Cutouts

Specialty cutout normally used in indoor and grid applications

Dropout or Non-dropout

NEMA & ANSI

Manufactured ABB, USA

Only major producer in the world

AB

B© P

TM

V -

36