a) three similar completed works each costing not less

26
Building Electrification of 24 Nos. B type Quarters, one No.of GLR&OHT,SITC of Street lighting& Periphery lighting work. Scope of the work: Building Electrification for the following 1). 24 Nos. of B type Quarters, 2). Electrification of GLR&OHT 3). SITC of Street lighting & Periphery lighting Pre-qualification conditions for the bidders. 1. Bidder should have valid Class – I, Electrical Contractor License, bids shall be accompanied by attested copy of the license. 2. Bidders shall have experience of completing similar Internal building electrification work/ works from April 2010to till date. To satisfy any one of the conditions listed below a) Three similar completed works each costing not less than Rs. 15.0 lakhs OR b) Two similar completed works each costing not less than Rs. 18.76 lakhs OR c) One similar completed work costing not less than Rs. 30.00 lakhs The experience details shall be produced in the format prescribed below. Sl. no. Nature and description of work Value of the work Period of work and completion date Client persons to whom reference may be made with address& official Telephone number Bidder should produce attested copies of completion certificates for satisfactory completion of Internal building electrification works so as to satisfy any one of the conditions mentioned above. Experience in Government / Government Enterprises / Public Sector Units will be appreciated. 3. Bidders should have provident fund registration certificate as applicable to Govt. rules for service providers irrespective of manpower engaged by supplier for the work. (attested copy to be enclosed with the bid) 4. Bidders should also have ESI registration certificate for service providers as applicable to Govt. Rules. General Instructions for bidding in E- procurement method. 1. TWO PART: Offers should be submitted in two parts, I)Techno commercial Bid (containing compliance / deviation for all the items in the Bill of quantities, supporting catalogues of the items offered, commercial terms like payment terms, delivery schedule, taxes and duties, etc.,) II) Price Bid. (Shall contain item wise price and total prices, rates shall be in both words and figures there shall be no discrepancy in rates written in figures and words. However, if a discrepancy is found the rates which correspond with the amount worked out by the bidder shall be taken as correct.) 2. Bidders should give clause-by-clause confirmation / Deviations for all the items of the specifications ambiguous / incomplete bids will not be considered. It shall contain the information about the make and catalogue numbers for each of supply item. Bidders may elaborate the specifications where ever felt necessary. 3. Bidders shall also comply for the each clause of the terms and conditions 16

Upload: others

Post on 01-Dec-2021

3 views

Category:

Documents


0 download

TRANSCRIPT

B u i l d i n g E l e c t r i f i c a t i o n o f 2 4 N o s . B t y p e Q u a r t e r s , o n e N o . o f G L R & O H T , S I T C o f S t r e e t l i g h t i n g & P e r i p h e r y l i g h t i n g w o r k .

Scope of the work: Building Electrification for the following 1). 24 Nos. of B type Quarters, 2). Electrification of GLR&OHT 3). SITC of Street lighting & Periphery lighting

Pre-qualification conditions for the bidders.

1. Bidder should have valid Class – I, Electrical Contractor License, bids shall be accompanied by attested copy of the license.

2. Bidders shall have experience of completing similar Internal building electrification work/ works from April 2010to till date. To satisfy any one of the conditions listed below

a) Three similar completed works each costing not less than Rs. 15.0 lakhs OR b) Two similar completed works each costing not less than Rs. 18.76 lakhs OR c) One similar completed work costing not less than Rs. 30.00 lakhs The experience details shall be produced in the format prescribed below.

Sl. no. Nature and description of work

Value of the work

Period of work and completion date

Client persons to whom reference may be made with address& official Telephone number

Bidder should produce attested copies of completion certificates for satisfactory completion of Internal building electrification works so as to satisfy any one of the conditions mentioned above. Experience in Government / Government Enterprises / Public Sector Units will be appreciated. 3. Bidders should have provident fund registration certificate as applicable to Govt. rules for

service providers irrespective of manpower engaged by supplier for the work. (attested copy to be enclosed with the bid)

4. Bidders should also have ESI registration certificate for service providers as applicable to Govt. Rules.

General Instructions for bidding in E- procurement method.

1. TWO PART: Offers should be submitted in two parts, I)Techno commercial Bid (containing compliance / deviation for all the items in the Bill of quantities, supporting catalogues of the items offered, commercial terms like payment terms, delivery schedule, taxes and duties, etc.,) II) Price Bid. (Shall contain item wise price and total prices, rates shall be in both words and figures there shall be no discrepancy in rates written in figures and words. However, if a discrepancy is found the rates which correspond with the amount worked out by the bidder shall be taken as correct.) 2. Bidders should give clause-by-clause confirmation / Deviations for all the items of the

specifications ambiguous / incomplete bids will not be considered. It shall contain the information about the make and catalogue numbers for each of supply item. Bidders may elaborate the specifications where ever felt necessary.

3. Bidders shall also comply for the each clause of the terms and conditions

16

4. For all the supply of items catalogues shall be enclosed. And quote shall be with in the enclosed approved list.

5. Bidders should quote for all the items of the inquiry. Partial bids will not be considered.

Terms and conditions: 1. Technical Supervisor: Electrical Supervisor possessing a valid supervisory license &

having minimum 7 years experience.

Completion period: The complete work shall be completed within 11 months+30 days from date of completion of civil works (from the 15th day, after the date of issue of Purchase order or from 7th day after issue of site clearance by EIC-Electrical.

The period includes monsoon periods also. 2. Site Clearance The work shall be started only after issue of site clearance by EIC-

Electrical. 2.1 The work shall be carried out in co-ordination with civil construction works. The

technical supervisor shall obtain clearance form civil agencies through EIC-Electrical.for carrying out certain critical activities like roof conduit work, wall/floor/beam conduit work and fixing of fittings in fall ceiling fixing of fittings on walls and ceiling etc., and issue return clearances through EIC-Electrical. after completion of that stage of electrical works for civil personnel to proceed with certain civil works like beam/ceiling concreting, wall plastering, thermal insulation, fall ceiling work and painting etc., )

2.2 If the supplier fails to complete the works within the time specified / causes undue delay during. The specified time as for the cases listed below. The MCF shall recover from the supplier as liquidated damages a sum of one half of the one percent (0.5 percent) of the order price of the uncompleted work for each calendar week of delay. The total liquidated damages shall not exceed ten percent (10 percent) of the total order value. Work will be deemed to have been completed only when all the components are delivered and work is complete in all respects in the opinion of EIC-Electrical. (which will be deemed to be final).

a. Not starting of work / stage of work within 7 days from issue of clearance / remainder

will be treated as delay. b. Stoppage of work/deputing insufficient manpower for more than 7 day when there is

hindrance to work will also be treated as delay. 2.3 Supplier shall desire an extension of time for the completion of the work on the grounds of his having been unavoidably hindered in execution or any other ground, he shall apply in writing to stores officer-MCF within 7 days of the date of such hindrance on account of which he desires such extensions. If MCF finds the grounds shown for the extension are reasonable (which shall be final) can extend the completion period.

3. Quality of the work: Work shall be carried out under the directions of the EIC- Electrical in addition subject to inspection by the representative of EIC(Ele.) to ensure strict compliance with the terms, specifications and conditions. Whenever the engineer in charge / his representative finds any work is not done properly,inefficiently or in a unworkmen like manner, he shall be instruct to replace / redo the work in a proper manner during the period of work or after completion up to a period of 12 months form the date of issue of certificate of completion. His instructions to be

17

complied to without any additional cost.

3.1 For the supply the brand and catalogue nos. should be proposed and an approval shall be obtained form the engineer in charge before effecting the supply. 3.2 Work shall be carried out as per the relevant IS and as per the specifications in the specifications book of MCF and reference drawings. 3.3 EIC(Ele.) shall be at liberty to object the contractor to remove any person from work employed by the supplier in or about execution of works who in the opinion of the Engineer in charge misconducts himself or incompetent or negligent in the proper performance of this duties. And all such persons shall not again be employed upon the works without the permission of the EIC(Ele.)

4 Documentation: The supplier shall produce conduit layout and circuit distribution drawings separately for each distribution board, telephone wiring etc., and get it approved from EIC(Ele) well in advance of starting the work. These drawings shall be updated if any changes are made during the course of carrying out the work. As built drawing shall be submitted after completion of the work ( 5 hard copies(laminated) and one soft copy )

5. Safety Clause: 5.1 Contractor shall read “Contractor safety manual” and sign on each pages and submit a copy.

5.2 Supplier should employ adequately qualified, experienced and licensed personnel to carry out the work, 5.3 Should provide requisite personal safety equipment / gadgets to their workmen, and

also the contractor’s workmen should observe all safety precautions to avoid any kind of accidents.

5.4 Supplier should also maintain a first aid kit containing items and shall be placed at location easily accessible to their workers.

5.5 In case of any accident occurring due to any reasons during carrying out the work MCF campus, Department will not be responsible in any way for the same. No extra payments shall be made to the supplier and No claim of what so ever nature will be considered or paid on this account and Supplier is fully responsible for such eventualities and he should indemnify the Department from such happenings.

6. Compliance to Labour laws: Display of wages board, Labour acts, rules, laws, wages

act, child Labour act and any other rules, regulations and acts prevailing during the execution period of the wok shall be complied to by the supplier. Supplier shall also maintain all the documents required by these rules, regulations and acts.

7.Security Deposit: Within 20 days from the receipt of purchase order, the contractor should submit a Security deposit of 10 % of the order value in the form of crossed DD in favor of Accounts Officer, MCF, Hassan or a bank guarantee for the same value from the scheduled banks in the format provided by Accounts Officer MCF, Hassan.

8Guarantee & PBG: The materials supplied and the works carried out shall be guaranteed for a period of one year form the completion date against manufacturing defects and poor workmanship. After completion of the work a 10% Performance bank guarantee shall be given for a period of one year.

18

9 Payment terms:

9.1For supply items . a) 80 %( maximum) payment shall be released after receipt and acceptance of all

the components and accessories of items at MCF, Stores. b) Further 10 % after installation and testing of the items. c) Balance 10% after final commissioning & handing over and receipt of

performance bank guarantee. 9.2 For supply and installation /wiring / fixing /laying / works.

a) 90 %( maximum) payment after completion of wiring, fixing of switches & sockets, testing & commissioning etc.

b) Balance 10% after final commissioning & handing over and receipt of performance bank guarantee

For the release of payments related to installation and testing. The supplier / his technical supervisor shall give a inspection offer letter to the Engineer in charge, giving a detailed list of completed work giving details like item in P. O no. , Brief description of work, quantity of work, and location of the work. The supplier / his technical supervisor should be present on the dates fixed for the inspection ( by Engineer in charge) All the manpower, instruments(with valid calibration) and tools required for testing and taking measurements shall be provided by the supplier without any additional cost.

10 Increase or decrease in quantity of the items: MCF reserves right to decrease or not to operate any of the item in the order, any increase in quantity of any of the item in the order shall be carried out by supplier at the P. O rates upon issue of amendment. Party

11.Tools tackles and power supply: Supplier has to arrange for necessary tools dies or ladders / scaffolding required for the work. Party may apply for temporary power supply with CESC, Hassan.

12 Correspondence with CESCo ltd. for obtaining power connection: Contractor should complete all the formalities as required by CESCO (Chamundeshwari Electricity Supply Company ltd. ,Hassan) for acquiring power connection, however all the security deposits and fees as stipulated by CESCo will be paid by MCF.

19

Anexture :A.   BOM for  24 Nos. of "B" type CISF Qtrs.Modular point wiring in Existing  concealed PVC pipe & Modular Concealed Boxes

Sn Description of Item Qty Unit Rate Amount

1 PRIMARY POINT:(MODULAR) in existing Concealed pipe & metal modular box 200 Point.Supply and wiring with 1.5 sq.mm.1.1 KV grade, ISI marked PVC insulated, stranded, FRLS Copper conductor cable conforming to IS:694 (withlatest amendments) in exsiting 20mm dia. PVC conduit concealed in column/ floor, wall.supply and fixing of modular 6 Amp,flush type control switch fixed in suitable size modular mettallic plate and covered with modular switch plates, in existing metal sheet flush boxesand earthing with 1.5sq.mm insulated copper wire (green ) run inside the conduit including supply of all fixing materials ,accessories ,and interconnectionscomplete as required.(For Qtr-192 points & Shed -08 points)NOTES:*1.Concealed (Embedment )work for PVC conduit & Modular box is alredy completed and it existing in the building. 2.All the point wiring items from Distribution board to the first switch board are 2.5 sq. mm 1.1 kV grade, ISI marked PVC insulated, stranded FRLS copper conductor cable confirming to conforming to IS:694 (with latest amendments) & 2.5 sq, mm insulated copper wire (green color) run inside the conduit for earthing also.

2 TWO WAY SWITCH LIGHT POINT Supply and wiring generally same as item 1 above but for staircase / bed room light point with 2 nos of 2 way modular 6 Amps. Control switches. (for qtr-48 points & Staircase -08 points)

56 Point.

3 POINT WITH WATER TIGHT SWITCH 8 Point.

Supply and wiring generally same as item 1 above but with 5 A single pole, water tight switch for control fixed in exsiting 14 SWG M. S. box earthing with 1.5sq.mm insulated copper wire (green) run inside the conduit including supply of all fixing materials ,accessories ,and interconnections complete as required.

4 CEILING FAN POINT (MODULAR) : in existing Concealed pipe & metal modular box 96 Point.Supply and wiring for ceiling fan point with 1.5 sq.mm. 1.1KV grade, ISI marked, PVC insulated, FRLS single core, stranded, Copper conductor cable conforming to IS : 694.( with latest amendments) in exsiting 20mm dia. PVC conduit concealed in column/ floor, wall.supply and fixing of modular 6 Amp,flush type control switch along with modular type 120 W, 5 step electronic fan regulator(2 modules) fixed in suitable size mettallic

Page 1 Specifications and bill of materials B type qtr.

modular plate, covered with modular plate in existing metal sheet flush boxes andearthing with .5sq.mm insulated copper wire run continuously along the conduitincluding supply of all fixing materials ,accessories ,and interconnectionsterminal block, interconnections complete as required.

5 6 AMP 3 PIN COMBINED SWITCH SOCKET OUTLET POINT:(MODULAR) 24 Point.Supply and wiring generally same as item No.1 above, but for modular 5 amp switch & 3 pin socket outlet point including supply and fixing of 6 Amps, 3 pin, combined socket outlet in existing metal sheet box and covered with modular plate. Rates for the power point wiring items is inclusive of necessary power circuit from the DB to the power socket.

6 6 AMPS,3 PIN SWITCH SOCKET OUTLET IN LIGHTING SWITCH BOARD:(MODULAR) 72 Point.Supply and fixing of modular 6 Amps,3 pin ,combined switch socket outlet in the lighting control switch board including interconnections complete as required.

7 6/16 AMP COMBINED SWITCH SOCKET OUTLET :(MODULAR) 48 Point.Supply and wiring with 2.5 sq.mm, FRLS 1.1 K V grade, ISI marked PVC insulated,single core, stranded Copper conductor cable conforming to IS:694 (with latestamendments) in existing 20 mm dia.2mm thick , Ele. grade PVC conduit concealedin ceiling or wall or floor, including supply and fixing of modular 6/16 AMP, 3 pin singlephase switch socket outlet, fixed in a exsiting sheet metal box and covered with modular switch plate, and earthing with 2.5 sq.mm insulated copper wire ( green)run inside the conduit including supply and fixing materials,interconnections complete as required.Note:- Rate for the power point wiring items are inclusive of necessary power circuit from theDB to the power socket.

8 EXHAUST FAN POINT:(MODULAR) 48 Point.Supply and wiring generally same as item 1 above, but for exhaust fan with 6 Amp modularSPMCB for control.( for Kitchen & toilet)

9 CALL BELL POINT(MODULAR) 24 Point.Supply and wiring for call bell point with 1.5 sq.mm 1.1 KV. grade, ISI marked,PVC insulated,FRLS single core, stranded Copper conductor cableconforming to IS:694 (with latest amendments) in existing 20mm. dia. 2mm thick ele. GradePVC conduit concealed in ceiling or wall or floor, including supplyand fixing of 6 Amp modular (plate) bell push for control and call bell fixed in exsiting independent metal sheet boxes and suitable for modular switches boxes covered with modular switch plates sheet, and earthing with 1.5sq.mm insulated copper wire run inside the conduit including supply of fixing materials and interconnections complete as required.

Page 2 Specifications and bill of materials B type qtr.

10 GEYSER POINT:(MODULAR) 24 Point.

Same as Sl No 7, 16 A,3 pin socket outlet point but with 30A modular DP switch as control11 Supply and drawing of 2-pair 0.5mm dia PVC insulated annealed and tinned copper conductor,

unarmored telephone cables in existing PVC conduits including making interconnections at the telephone tag box end and telephone junction box end complete.

384 Mtrs

12 Supply and fixing of suitable RJ-11 modular Telephone socket in existing consealed metal sheet box and covered with modular switch plate including supply of all fixing materials, complete with interconnections etc complete as required and as directed by EIC.

24 Point.

13( )

Supply and fixing of same as Sl no. 12 but for TV cable termination including supply of modular co-axial TV socket fixed surface plates and in existing concealed modular junction box, and and complete as required.

24 Point.

14 Run of mains.Supply and wiring with 2 runs of FRLS 4 sq. mm 1.1 kV grade PVC insulated, Single core, stranded copper conductor cable conforming to IS: 694 (with latest amendments) in 20 mm dia Ele. Grade PVC conduit concealed in wall, or ceiling and earthing with 4sq. mm insulated copper wire for earthing run inside the conduit including supply of fixing materials and accessories, interconnections complete as required.

240 Mtrs

15 Supply run of mains wiring with two runs of FRLS 2.5 sq.mm 1.1 kv grade PVC insulated, singlecore,stranded Copper conductor cable conforming to IS:694 (with latest amendments) in 20 mm 40 Mtrsdia.Ele. grade PVC conduit concealed in wall, or ceiling and earthing with 1.5sq.mm insulated copper wire run inside the conduit including supply of fixing materials and accessories,interconnections complete as required.

16 CEILING FANS 72 Nos.Supply of 1200 mm sweep ceiling fans, capacitor type with 300 mm down rod,canopies, shackle, rubber bush, blades suitable for operation on 230V, 50HZ single phase AC supply conforming to IS-374 Split pin locking arrangement must be provided for Fan - down rod, Down rod to yoke & yoke to celing hook coupling bolts.completely pre wired up to terminal block.

17 Installation charges for ceiling fan 72 Nos.

Page 3 Specifications and bill of materials B type qtr.

18 EXHAUST FANSSupply of light Duty, totally enclosed motor type, exhaust fans suitable for operation on 230 V, 50 Hz single phase AC supply complete with 3 core flexible copper conductor cable, gravitylouvers shutters rigid frame with rubber mounting and of following size confiming to IS-2312(with latest ammendments). 225 mm Sweep 900 rpm.

48 Nos.

19 Installation charges for Exhaust fans. 48 Nos.

20 Supply of fluorescent light fittings with Electronic ballast and all accessories including supply 72 Nos. of lamps.1 x 28 W, T5 Box type fitting among CEPO Brands.

21 Supply of compact fluorescent light fittings with copper VPIT ballast and all other accessories 56 Nos.including lamps.1 x 11W modular CFL fitting with diffuser ( for toilet,passage, bath &shed ).

22 Supply of Compact fluorescent light fittings with copper VPIT ballast and all other accessories including supply of lamps.1 X 36 W modular CFL fitting ( for dining ) among enclosed approved Brands

24 Nos.

23 Supply of compact fluorescent light fittings with copper VPIT ballast and all other accessories including supply of lamps.2 X 18 W mirror optic louver CFL fitting ( for kitchen ) among enclosed approved Brands

24 Nos.

24 Supply of fluorescent light fittings with copper VPIT ballast and all other accessories including supply of lamps. 1 x13W bulk head CFL fitting 64 Nos.

among enclosed approved Brands ( for Qtrs-48 & 8 stair case points)25 Supply of fluorscent light fitting with copper VPIT ballast and all other accessories including supply

of lamps.1 x 11 W CFL Mirror light fitting among enclosed approved Brands24 Nos.

26 Installation charges for above CFL fittings ceiling mounting type/wall mounting type with all fixing materials required 264 Nos.

27 GEYSERS (Fiber plastic body geyser) with 5 star rating 24 Nos.15 Ltrs capacitySupply of non-pressure type Geysers with all required materials Geysers conforming to IS:2082 (with latest amendments) and suitable for 230V.50HZ single phase AC supplycomplete with water inlet/ outlet manifolds and safety devices like thermostat cutout(96- 97deg C), Fusible plug ( 99 deg C), Pressure relief valve and semi return device to keep the heating element immersed even though over head tank becomes empty. with reset, LED indication lamp (Heating and cutout) and 3 core flexible copper cable and plug top.The geyser shall bear ISI certification mark.

Page 4 Specifications and bill of materials B type qtr.

28 Installation of Geysers on wall/ column with necessary baseplate, bracket made out of MS angle iron/flat of suitable sizeincluding cutting, welding, grouting and supply of all installation materials, fixing of inlet/ outlet water pipes, interconnection complete as required.

24 Nos.

29 MCB DISTRIBUTION BOARDS: 24 Nos.Supply of following double door type SPN MCB DBs in 16 SWG CRCA sheet steel enclosure, dust and vermin protected, rated for 240V. 1 phase, 50 HZ AC supply operation, inclusive of busbar of suitable capacity, neutral link, earth bus bar with required outgoing, DIN bar, fully factory fabricated and powdercoated suitable for incorporating SP/SPN MCB as specified below including necessary adaptor boxes for incoming and outgoing cables/wires , but excludingsupply of MCBs. Suitable for Two pole (4 module) SPN ELMCB as incomingcontrol and 4 ways 5/10/15/ 20/30 AMP SP ( total 8 Ways ) MCB as outgoing.

30 Supply of following double door type SPN MCB DBs in 16 SWG CRCA sheet steel 4 Nos.enclosure, dust and vermin protected, rated for 240V. 1 phase, 50 HZ AC supply operation, inclusive of busbar of suitable capacity, neutral link, earth bus bar with required outgoing, DIN bar, fully factory fabricated and powdercoated suitable for incorporating SP/SPN MCB as specified below including necessary adaptor boxes for incoming and outgoing cables/wires , but excludingsupply of MCBs. Suitable for Two pole (4 module) SPN ELMCB as incoming

31a. Installation charges of SPN - DB-8 ways 24 Nos.

31b. Installation charges of SPN DB-4 ways 4 Nos.

32 Supply and installation of RCBO operational on 230V, 1 Phase with neutral , 50 HZ,AC, 2 Pole with but provided with over current and Earth Leakage specifications as follows. Circuit Breaker ( RCBO ) Residual current device type with trip free mechanism terminals suitable for Aluminium cable- termination , terminal covers, test button and positive contact indication of the following leakage current tripping sensitivities and operating time less than 30 m Sec. ELCB shall conform to IS- 12640 with latest amendments complete as required.short circuit protections complete of the following leakage current tripping sensitivities and current ratings.

32a 25A 2 Pole, RCBO 30 mA tripping sensitivity 24 Nos.32b 10 A 2 Pole, RCBO 30 mA tripping sensitivity 4 Nos.

31

Page 5 Specifications and bill of materials B type qtr.

33 Supply of Miniature circuit breakers 9 KA / 10 KA breaking capacity conforming to IS 8828 100 Nos.with latest amendments of following capacities:Single pole MCB of following capacities6A -28 Nos,10A -24 Nos,16A - 24 Nos, 25A - 24Nos

34 Supply and installation of the following telephone tag blocks in a suitable size sheet steel enclosure including supply of all fixing materials painting complete as required (Krone type)10 pair.

8 nos.

35 GI Pipe Earthing Providing standard pipe earth for earth stations with GI pipe, conforming to IS: 3043 with latest amendments and as per drg.no. MCF/ELECT/15/2009 and including supply of all materials and providing chamber complete as required. With 2.5 m long, 40 mm dia, GI pipe, medium class as per IS: 1239. (4 nos for quarters& 2 nos for building lightning protection)

24 Nos.

36 Supply and laying of GI strip(External) of following sizes including supply and fixing using GIsaddles with all fixing materials required and when laid inside the building and inclusive of excavation and refilling of earth when laid outside the building and welding of all the joints and terminations interconnections with earth pit and equipment, terminations/ interconnections in an approved manner as per IS 3043 ( with latest amendments) inclusive of supply of all hardwares complete as required. Size:- 25 x3 mm.

350 Mtrs

37 Supply and External laying of GI strip of following sizes including supply and fixing using GI saddles with all fixing materials required and when laid inside the building and inclusive of excavation and refilling of earth when laid outside the building and welding of all the joints and terminations interconnections with earth pit and equipment, terminations/ interconnections in an approved manner as per IS 3043 ( with latest amendments) inclusive of supply of all hardwares complete as required. Size:- 32 x 6 mm

240 Mtrs

38 Supply and laying of GI wire of 8 SWG sizes including supply of fixing clamps and accessories when laid inside the building and inclusive of excavation and refilling of earth when laid outside the building and interconnections with earth pit and equipment, terminations/ interconnections in an approved manner as per IS 3043 (with latest amendments) inclusive of supply of all hardwares complete as required.

40 Mtrs

39 Supply of 1.1KV grade,4C,16 sq. mm XLPE insulated, and overall sheathed, stranded 360 meters aluminium conductor, flat steel strip/ wire armoured cables conforming to IS: 7098/ Part I (with latest amendments). The cable shall bear ISI certification mark.

40 laying of 4 core , 16 sq. mm, 1.1 kV grade FRLS ,XLPEcables armoured / unarmored, aluminium / copper conductor cables.

Page 6 Specifications and bill of materials B type qtr.

In ground, in hard / soft soil, 750mm below ground level including transportation of cable to site, 320 Mtrs excavation, refilling with sand and baked bricks on top and sides and providing cable route / joint markers complete as per specifications and as per drawing no.CED/ELE/S/8 and 10.

41 In existing trench / on cable tray, on wall / floor / ceiling / above false ceiling / below false floor 40 Mtrsincluding transportation of cable to site, removing of trench / false ceiling/ false flooring coversand reclosing the covers after laying the cables in good condition with supply of all necessary materials such as brackets , clamps , MS spacers complete as required

42 Providing end terminations for 4 core 16 sq. mm, 1.1 kV grade XLPE insulated armoured , aluminium conductor cables including supply of cable gland, lugs, neoprene bushes and other materials and tools required complete with terminal connections, earthing of gland and as required and as directed by Engineer - in - charge.

16 Nos.

43 HUME PIPE 60 MtrsSupply and laying of 150 mm dia. Hume pipe with collars confirming to IS: 458 (with latest amendments) for road crossing including excavation and refilling of earth, complete as required.

Total;

Page 7 Specifications and bill of materials B type qtr.

Annexture -B, BOM of 1 no of GLR & OHT at proposed CISF campusModular Point wiring with Concealed MS Conduit

Specification for Internal Electrification for GLR & OHT at CISF housing-MCF Hassan.

Sn Description of items Qty Unit Rate Amount.

A - Modular Point wiring with Concealed MS ConduitPRIMARY POINT:(MODULAR)Supply and wiring with 1.5 sq.mm.1.1 KV grade, ISI marked PVC insulated, stranded, FRLS Copper conductor cable conforming to IS:694 (with latest amendments) in 20mm dia.,16 SWG MS conduit concealed in column/ floor, wall, or ceiling including supply and fixing of modular (plate) 5 Amp,flush type control switch, fixed in suitable size metal sheet flush boxes suitable for modular switchesand covered with modular switch plates, and earthing with 14 SWG bare insulated copper wire run inside the conduit including suitable ceiling rose, lamp holder and all other fixing materials ,accessories ,and interconnections complete as required.NOTES: All the point wiring items are from distribution board to the first switch board are 2.5 sq. mm 1.1 kV grade, ISI marked PVC insulated, stranded FRLS copper conductor cable confirming to IS : 694. in 20mm dia ,16 SWG MS conduit with 14 SWG bare copper wire run inside the conduit for earthing .circuit. .SECONDARY POINT:(MODULAR)Supply and wiring generally same as item no.1above, but without control switch.The secondary point in case of point wiring shall include necessary wiring looped from the primary light point.

3 16A + 6 AMP GROUP SWITCH SOCKET OUTLET ( Modular) 2 Point.Supply and wiring with 2.5 sq.mm, FRLS 1.1K V grade, ISI markedPVC insulated, single core, stranded Copper conductor cable conformingto IS:694(with latest amendments) in 20 mm dia.16 SWG MS conduit concealed in ceiling or wall or floor, including supply and fixingof modular 16Amps + 6 AMP, 6 pin switch socket outlet, fixed in suitable size metal sheet box suitable for switches and covered with modular switch plate and socket and covered with modular switch plate and earthing with 12 SWG pare copper wire run along the conduit continuously including supply of fixing materials, inter connections complete as required

1

7 Point.

27 Point.

Page 1 Specifications for GLR & OHT

Specification for Internal Electrification for GLR & OHT at CISF housing-MCF Hassan.

Sn Description of items Qty Unit Rate Amount.

6 AMP 3 PIN COMBINED SWITCH SOCKET OUTLET POINT:(MODULAR)Supply and wiring generally same as item No.1 above, but for modular 6 amp,3 pin combined switch socket outlet point including supply and fixing of6 Amps, 3pin,combined switch socket outlet in a suitable size metal sheet box and covered with modular switch plate .Rates for the power point wiring items is inclusive of necessary power circuit from the DB to the power required.

5 FLOOD LIGHTING POINT . Supply and wiring same as item No. 1 above,but for flood light fitting fixed on wall with 10 Amps SPMCB for comtrol fixed in asuitable size 14 SWG weather proof box with hinged door, gasket and locking facility.

3 Point.

6 AMPS,3 PIN SWITCH SOCKET OUTLET IN LIGHTING SWITCH BOARD:(MODULAR)Supply and fixing of modular 6 Amps,3 pin ,comb-ined switch socket outlet in the lighting control switch board including interconnections complete as required.

7 EXHAUST FAN POINT:(MODULAR) 3 Point.Supply and wiring generally same as item 1 above, but for exhaust fan with 6 Amp modular SPMCB for control.Conduit for Telephone wiring Supply and embedment of 25mm dia 16 SWG MS conduit concealed in wall, floor/ceiling including supply and drawing of 14 swg wire as fish wire including supply of all fixing materials as required.

9 Supply and drawing of 2-pair 0.5mm dia PVC insulated annealed and tinned copper conductor, unarmored telephone cables in the already laid conduits including making interconnections at the telephone tag box end and telephone junction box end complete.

35 Meter

10 Supply and fixing of RJ-11 modular Telephone socket in a suitable size metal sheet flush box suitable for modular telephone socket and covered with modular switch plate including supply of all fixing materials, painting with approved shade paint and associated civil works complete with interconnections etc complete as required and as directed by EIC.

1 Point.

11 EXHAUST FANS 3 Nos.Supply of heavy duty, totally enclosed motor type exhaust fans suitable for operation on 230Volts, 50Hz single phase AC supply complete with 3 core flexible copper conductor cable, gravity louvers shutters rigid frame with rubber mountings and of following sizes conforming to IS-2312 (with latest amendments) Size:- 300 mm sweep 900 rpm

4

1 Point.

Point.

Meter8

16

20

Page 2 Specifications for GLR & OHT

Specification for Internal Electrification for GLR & OHT at CISF housing-MCF Hassan.

Sn Description of items Qty Unit Rate Amount.

12 Installation charges for Exhaust fans with all fixing materials. 3 Nos.

13 Supply of Surface mounting,mirror optic type CFL fittings with Electronic ballast and all other 6 Nos.accessories including lamps.2 x 28 W, T5 type fitting among enclosed approved brands.

14 Supply of fluorescent light fittings with copper VPIT ballast and all other accessories including 9 Nos. supply of lamps. 1 x 11W bulk head CFL fitting.among enclosed approved brand

15 Installation charges for above CFL fittings, Box type, modular CFL and CFL bulk head. 15 Nos.

16 Supply of integral type flood light fitting with copper wound ballast, vizor glass assembly with lamp .150 Watts, Metal Halide. 3 Nos.

17 Supply of Single piece Aviation warning light with cast aluminium neonspiral lamp, poly corbonate dome and all accessories 1 Nos.

18a Installation of flood light fitting with all fixing materials complete as required 3 Nos.

18b Installation of Aviation warning light with 32 mm dia Class "C " GI pipe 600 mm long including cutting,welding,threading and supply of all accessories like GI pipe, interconnecting cables, bolts,nuts,MS terminal box control fuse for installation including painting ,earthing, grouting of bolts with pedestal and water proffing around the prdestal complete as required

1 Nos.

19 MCB DISTRIBUTION BOARD:Supply of following double door type TPN MCB DBs in 16 SWG CRCAsheet steel enclosure, dust and vermin protected, rated for 415V. 3 phase, 50 HZAC supply operation, inclusive of busbar of suitable capacity, neutral link,earth bus bar with required outgoing, DIN bar, fully factory fabricated and powdercoated suitable for incorporating Single phase & three phase MCB and ELMCB as a incommerspecified below including necessary adaptor boxes for incoming and outgoingcables/wires , but excluding supply of MCBs suitable for following as outgoing.8 Way per phase, Rating:- 63 Amps 1 Nos.

20 Supply and installation of four pole RCBO operational on 415V, 3 Phase with neutral , 50 HZ,and provided with over current and Earth Leakage specifications as follows. Circuit Breaker ( RCBO ) Residual current device type with trip free mechanism

Page 3 Specifications for GLR & OHT

Specification for Internal Electrification for GLR & OHT at CISF housing-MCF Hassan.

Sn Description of items Qty Unit Rate Amount.

terminals suitable for Aluminium cable- termination , terminal covers, test button and positive contact indication of the following leakage current trippingsensitivities and operating time less than 30 m Sec. ELCB shall conform to

20 IS- 12640 with latest amendments complete as required.short circuit protections complete of the following leakage current tripping sensitivities and current ratings. RCBO 63 Amps,300 mA, 1 No.

21

Motor Protection Circuit Breakers (MPCB)MPCB has to be operated as Switch, S/C, O/L & single phase protection, 3 Pole, S/C breaking capacity 35 kA, 2NO+2NC auxiliary contact block, O/L setting range from 70-100 %, Utilization category AC-3, Flush / Din rail mounting type with rotary operating handle mechanism, Confirms to IEC947-I, 947-II, 947-IV-I, Suitable for 5 HP / 3.75 kW, ST34417OOVOM, Make L&T

2 Nos.

Supply of Miniature circuit breakers 9 KA / 10 KAbreaking capacity conforming to IS 8828 with latest amendments of following.Single pole breakers of capacities 6 A :-3 N0s, 10 A;- 6 nos,& 20 A :-3 Nos,

23 Installation charges for the 8 way -TPN DB with all fixing materials 1 Nos.

24 Supply and Installation of weather proof boxes made out by14 SWG CRCA sheet with 2 mm thick folded sheet or with angle iron frame work( according to size and rating of panel) including seven tank metal treatment and powder coating. The panel shall be of weather proof type. and double door type. IP - 65. with mounting plate for mounting the meters. The box should be suitable for mounting 1no. of Three phase- neutral 25A energy meters, including supply and fixing of 4 pole 40 Amps rated MCB, 3 nos. of 40 Amps rated Porcelain fuse cut outs and one No. of Nuetrol link and shall have provision for taking 4 core cable incoming. It shall be concealed inside the wall at 1.5 meter height. ( only door portion projecting outside the wall) installation includes supply and fixing of 2"PVC pipe with bends and other accessories required for routing the incoming cable to the panel.

1 Nos.

25

DOL Starter suitable for 5HP/3.75kWSupply of starters in sheet steel enclosure and with suitable capacity AC3 duty air break contactors with2NO-2NC auxiliary contacts ON/OFF buttons suitable range bi-metallic over load relays with all interconnections complete as required.

2 Nos.

22Nos.12

Page 4 Specifications for GLR & OHT

Specification for Internal Electrification for GLR & OHT at CISF housing-MCF Hassan.

Sn Description of items Qty Unit Rate Amount.

26 GI Pipe Earthing Providing standard pipe earth for earth stations with GI pipe, conforming to IS: 3043 with latest amendments and as per drg.no. MCF/ELECT/15/2009 and including supply of all materials and providing chamber complete as required. With 2.5 m long, 40 mm dia GI pipe.2 nos for DB & motor body Earthing & 2 Nos for Building lightening protection

4 Nos.

27 LIGHTNING PROTECTION SYSTEMSupply & Installation of vertial lightning protection arrangement with 100 mm dia. Copper hallow sphere with spike and 25 mm dia. Copper tube OR 15/8 mm dia copper rod air terminal rigidly fixed on RCC roof as per drawing No: CED/ELE/S/6A OR 6B including supply of all fixing material, cutting ,welding, grouting and water proofing the roof around the base complete as required .

1 Nos.

28 Supply and laying of GI strip of following sizes including supply and fixing using MS saddles with all fixing materials required and when laid inside the building and inclusive of excavation and refilling of earth when laid outside the building and tinning of all the joints and terminations interconnections with earth pit and equipment, terminations/ interconnections in an approved manner as per IS 3043 ( with latest amendments) inclusive of supply of all hardwares complete as required. Size:- 25 x3 mm.

45 mtrs

29 Supply and laying of GI strip of following sizes including supply and fixing using MS saddles with all fixing materials required and when laid inside the building and inclusive of excavation and refilling of earth when laid outside the building and tinning of all the joints and terminations interconnections with earth pit and equipment, terminations/ interconnections in an approved manner as per IS 3043 ( with latest amendments) inclusive of supply of all hardwares complete as required. Size:- 32 x 6 mm.

50 mtrs

30 Supply and laying of GI wire of 8 SWG sizes including supply of fixing clamps and accessories when laid inside the building and inclusive of excavation and refilling of earth when laid outside the building and interconnections with earth pit and equipment, terminations/ interconnections in an approved manner as per IS 3043 (with latest amendments) inclusive of supply of all hardwares complete as

i d

25 mtrs

31 Supply of 1.1KV grade, XLPE nsulated, and overall sheathed, stranded aluminium conductor, flat steel strip/ wire armoured cables conforming to IS: 7098/ Part I (with latest amendments). The cable shall bear ISI certification mark.

a. 31a. 3 Core,2.5 sq. mm ( Aviation warning light) Colour: - Red, Black & Green 100 mtrs

Page 5 Specifications for GLR & OHT

Specification for Internal Electrification for GLR & OHT at CISF housing-MCF Hassan.

Sn Description of items Qty Unit Rate Amount.

b. 31b.4 Core, 16 Sq.mm (for DB) Colour: - Red, Yellow, Blue & Black. 70 mtrs

32 laying of 1.1 kV grade FRLS ,XLPE cables armoured aluminium conductor cables. 32a.In ground, in hard / soft soil, 750mm below ground level including transportation of cable 70 mtrs to site , excavation, refilling with sand and baked bricks on top and sides and providing cable route / joint markers complete as per specifications and as per drawing no.CED/ELE/S/8 and 10.32b. In existing trench / on cable tray, on wall / floor / ceiling / above false ceiling / below false 100 mtrs floor including transportation of cable to site, removing of trench / false ceiling/ false flooring covers and reclosing the covers after laying the cables in goodcondition with supply of all necessary materials complete as required.

33 Providing end terminations for 1.1 kV grade XLPE insulated armoured , aluminium conductor cables including supply of cable gland, lugs, neoprene bushes and other materials and tools required completewith terminal connections, earthing of gland and as required

a. 33a. 3 Core,2.5 sq. mm ( Aviation warning light) 2 Nos.

b. 33b. 4 Core, 16 Sq.mm ( incoming cable for DB) 2 Nos.

- Sub total

Page 6 Specifications for GLR & OHT

Annexture:- C BOM for street & Periphery lighting for New CISF Accommodations

Sn. Description of items Qty Unit Rate in Rs.

Amount in Rs.

1 Supply,erection and commissioning of steel tubular poles inclusive of foundation for the pole complete as per detailes specification and also including 2 nos of 50 dia. GI pipe and bends to take cables from ground up to junction box including clamp and all fixing meterials complete as required and as per the enclosed drawing No;- CED/ELE/S/12

16 Nos

Supply of pole.pp gPoles confirming to IS 2713. The poles shall be made out of high tensile strength steel. The pole should be supplied with pre welded suitable base plate and rib plate.Pole height: 9 meters.Supply of single arm bracket. Arm bracket suitable for the poles above shall be hot dip galvanized to at least 65 microns. The cross arm of the bracket shall extend to 2 meters of lateral distance and shall be at an angle of 110 degree from the pole.Dia of the cross arm shall be 60 mm.No welding to be done after galvanizing.Make: Bajaj / Metalcoat/ Shubam or Equivalent.

2 Supply,erection and commissioning of stepped pole for pheryphery lighting inclusive of foundation for the pole complete as per detailes specification and also including 2 nos of 50 dia. GI pipe and bends to take cables from ground up to junction box including clamp and all fixing meterials complete as required and as per enclosed drawing No;- CED/ELE/S/14

14 Nos

The poles shall be made of Heavy duty GI “C” class with ISI marked.Poles confirming to IS 2713Pole height = 9 meter.Make: Bajaj / Metalcoat/ Shubam or Equivalent.Shall have provision for earthing wire termination (earth boss).

3 Supply of Street Integral light luminaries (among enclosed approved list) 16 nos.Deep drawn aluminium 150 W Metal halide luminarie with integral control gear consisting ballast, igniter and power factor improvement capacitor. With Heat resistant flat glass covering the lamp (supply shall consist of ballast, igniter, PF improvement capacitor and lamp.

4 Supply of Integral flood light luminaries. (for periphery lighting) 28 nos.250 W Metal halide (among enclosed approved list)Epoxy gray / black powder coated, die cast Aluminium housing. Built in control gear. Aluminium reflector, heat resistant toughened clear glass cover, with mounting bracket and accessories.

SITC of street & Periphery lighting for proposed New CISF Accommodations in New land at MCF ,Hassan

Street lighting CISF qtrs. Page 1

(supply shall consist of ballast, igniter, PF improvement capacitor and lamp).5 Supply of Post top lantern luminaries(Integral), Integral type 70 W metal halide luminarie, with alloy

cast spigot, Decorative acrylic bowl and Aluminium top cover,Spigot shall consist of Ballast, igniter, & PF improvement capacitor & lamp. Make: Bajaj JUNO JODC 1 X 70 MH DE, Metal coats.

2 nos

6 Supply of 16 sq. mm ,4 core,Al.cable 2000 MtrsSupplying of 1.1Kv grade, XLPE insulated, over all sheathed, Stranded Aluminum conductor, flat or round armored cable confirming to IS -7098 part I (with latest amendment). Core Colour: - Red, Yellow, Blue and Black

Shall be supplied in drums ( least 500 meters in single length).(among enclosed approved list)7 Supply of Automatic Illumination level based switching unit. 1 no

Having a switching range of 10 to 60 lux.Wait time 30 to 90 seconds.Operating voltage range : 185 – 275 V AC, 50 Hz.Maximum load : 15 kW ( 5kW per phase)Operating humidity range : upto 95 % RH at 40 deg. COver voltage trip levels.Auto high voltage sense and trip: above 270 V ACAuto high voltage sense and reset: below 255V ACUnder voltage trip levelsAuto low voltage sense and trip: Below 150 V AC

Auto low voltage sense and reset: above 165 V AC

Bypass / Override facility for continous ON and OFF for maintenance. Make: Bajaj, Crompton, GE, Wipro, Philips, L&T, Schnider, Elpro, Kakatia.

8 Laying one run of 4 core, 16sq. mm, 1100 volts grade PVC insulated, PVC sheathed armoured Aluminium cable. The cable shall be laid in ground hard soil , 750 mm below ground level including transportation of cable to site and excavation. Refilling with sand and baked bricks on top and sides and providing cable joint / route marker (at least one for every 15 meters)complete as per specifications. The work shall be carried out as per the drawing no: CED/ELE/S/8 &for cable laying drawing no: CED/ELE/S/19 (for root markers).

2000 Mtrs

Street lighting CISF qtrs. Page 2

9 Providing coil/Spiral earthing. 30 nos.Using 8 SWG GI wire for street light pole, GI wire buried to a minimum depth of 1.5. M. with excavation refilling and connecting GI wire to pole using GI bolt and nut complete as per drawing no:CED/ELE/S/5 enclosed and as directed by EIC- Electrical

10 Installation of street & Pheryphery light fitting. 44 nos.Street light & Pheriphery light fitting such as MH fitting on existing RCC pole including supply of necessary meterials as required and including supply of PVC weather proof terminal box of suitable size (IP 65) interconnecting cable,supply & fixing of 1 No. 10 Amps SPMCB for control, 1 no. of 16 Amps 4 way cable connector as a terminal block, MS clamp earthing bolt provision complete as required.

11 Installation of post top lantern fitting with 32 mm dia Class "C " GI pipe 600 mm long including cutting,welding,threading and supply of all accessories like GI pipe, interconnecting cables, bolts,nuts,MS terminal box control fuse for installation including painting ,earthing, grouting of bolts with pedestal and water proffing around the prdestal complete as required

2 Nos.

12 Installation Automatic Illumination level based switching unit. 1 nos.Installation with supply of materials required for installation like inter connecting cables, bolts, nuts & clamps etc.,

13 Cable terminations 70 endsTermination of 1. 1 kV grade 3 ½ core armoured cable of 16 Sq. mm cables. Including supply of Heavy duty flange type brass gland, Heavy duty long barrel type copper lugs for cable cores and armour earthing.Crimping lugs with appropriate tools, and taping of lugs with colour coded insulation tape. (in units of one end termination). Size:-16 sq. mm

Total

Street lighting CISF qtrs. Page 3