a simple transformer model for analysis of … · a simple transformer model for analysis of...

6
A SIMPLE TRANSFORMER MODEL FOR ANALYSIS OF TRANSFERRED LIGHTNING SURGES FROM MV TO LV LINES Alexandre Piantini Welson Bassi Jorge M. Janiszewski Nelson M. Matsuo Institute of Electrotechnics and Energy Polytechnic School University of São Paulo Av. Prof. Luciano Gualberto, 1289, 05508-900, São Paulo - SP (Brazil) Tel.: + 55 11 818 4720 - Fax: + 55 11 212 9251 - E-mail: [email protected] ABSTRACT This paper presents a distribution transformer model which has been developed aiming at the analysis of transferred lightning surges from MV to LV lines, taking into account the load conditions, as well as the experiments that were conducted for the verification of its validity. The results of the comparisons between measured and calculated voltages indicate that the proposed model can be an useful tool for the evaluation of transferred surges, taking into account the compromise between accuracy and simplicity. Some examples of the applicability of the model, in terms of the calculation of surges in LV networks are also presented. INTRODUCTION Voltage and current surges transferred from the medium voltage lines are important sources of disturbances on secondary circuits. Such transients, usually caused by direct or nearby lightning, have to be dealt with in any analysis of the performance of overhead distribution lines. A common way of calculating the voltages on the low- voltage side is to represent the transformer by a capacitive network. This method, however, may be highly inaccurate, as has been demonstrated by laboratory tests. Furthermore, although more sophisticated models have been proposed [1], their validity is usually limited to no-load conditions. In this paper a simple distribution transformer model is developed, aiming at the analysis of voltages and currents transferred to the low-voltage side, taking into account the load conditions, when lightning strikes the primary conductors. As the main motivation for the study was related to the surges on the low-voltage network, the transformer is considered to be protected by a set of arresters at the MV side. Under this condition it can be considered linear, and therefore it is treated as a quadripole. TRANSFORMER MODEL Transformer characteristics Initially, tests were performed on a distribution transformer commonly used in Brazil (three-phase, with rated power of 30 kVA, 13.8 kV - 220/127 V, delta-star connection), so as to determine its characteristics in terms of input, output and transference impedance as a function of frequency. As the transformer was supposed to be protected by arresters, it was assumed that the voltages on the three phases have approximately the same amplitude. The input impedance Z11 was then obtained with the HV terminals interconnected and with the LV terminals in open circuit. Voltage signals of approximately 16 V peak-to-peak, in the frequency range of 10 kHz to 1 MHz, were applied to the HV terminals. A digital storage oscilloscope with sampling rate of 500 MS/s and bandwidth of 300 MHz was used for measuring the applied voltage and the current at the HV terminals 1 (external) and 2 (middle), as well as the phase shift between voltage and current signals. A probe associated with an amplifier was used for current measurements. Fig. 1 shows the circuit used for the determination of Z11. For each frequency its modulus was calculated by the ratio of the amplitudes of the voltage at point P1 and the current at point P3. The phase shift was given by the difference in time between the zero crossings of the voltage and current signals. The output impedance Z22 was obtained analogously. For the determination of the transfer impedance Z21 the calculations considered, with reference to Fig. 1, the voltage transferred to secondary (at the point P2) and the current at the point P3. Fig. 1 - Circuit for the determination of the transformer input impedance Z11. G: signal generator; amp.: amplifier; osc.: oscilloscope.

Upload: vodieu

Post on 18-Jan-2019

216 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: A SIMPLE TRANSFORMER MODEL FOR ANALYSIS OF … · A SIMPLE TRANSFORMER MODEL FOR ANALYSIS OF TRANSFERRED LIGHTNING SURGES FROM MV TO LV ... rate of 500 MS/s and bandwidth of 300 MHz

A SIMPLE TRANSFORMER MODEL FOR ANALYSIS OF TRANSFERREDLIGHTNING SURGES FROM MV TO LV LINES

Alexandre Piantini Welson Bassi Jorge M. Janiszewski Nelson M. MatsuoInstitute of Electrotechnics and Energy Polytechnic School

University of São PauloAv. Prof. Luciano Gualberto, 1289, 05508-900, São Paulo - SP (Brazil)

Tel.: + 55 11 818 4720 - Fax: + 55 11 212 9251 - E-mail: [email protected]

ABSTRACT

This paper presents a distribution transformer model whichhas been developed aiming at the analysis of transferredlightning surges from MV to LV lines, taking into accountthe load conditions, as well as the experiments that wereconducted for the verification of its validity. The results ofthe comparisons between measured and calculatedvoltages indicate that the proposed model can be an usefultool for the evaluation of transferred surges, taking intoaccount the compromise between accuracy and simplicity.Some examples of the applicability of the model, in terms ofthe calculation of surges in LV networks are alsopresented.

INTRODUCTION

Voltage and current surges transferred from the mediumvoltage lines are important sources of disturbances onsecondary circuits. Such transients, usually caused bydirect or nearby lightning, have to be dealt with in anyanalysis of the performance of overhead distribution lines.A common way of calculating the voltages on the low-voltage side is to represent the transformer by a capacitivenetwork. This method, however, may be highly inaccurate,as has been demonstrated by laboratory tests. Furthermore,although more sophisticated models have been proposed[1], their validity is usually limited to no-load conditions.

In this paper a simple distribution transformer model isdeveloped, aiming at the analysis of voltages and currentstransferred to the low-voltage side, taking into account theload conditions, when lightning strikes the primaryconductors. As the main motivation for the study wasrelated to the surges on the low-voltage network, thetransformer is considered to be protected by a set ofarresters at the MV side. Under this condition it can beconsidered linear, and therefore it is treated as a quadripole.

TRANSFORMER MODELTransformer characteristics

Initially, tests were performed on a distribution transformercommonly used in Brazil (three-phase, with rated power of30 kVA, 13.8 kV - 220/127 V, delta-star connection), so asto determine its characteristics in terms of input, output andtransference impedance as a function of frequency. As thetransformer was supposed to be protected by arresters, itwas assumed that the voltages on the three phases haveapproximately the same amplitude. The input impedanceZ11 was then obtained with the HV terminalsinterconnected and with the LV terminals in open circuit.Voltage signals of approximately 16 V peak-to-peak, in thefrequency range of 10 kHz to 1 MHz, were applied to theHV terminals. A digital storage oscilloscope with samplingrate of 500 MS/s and bandwidth of 300 MHz was used formeasuring the applied voltage and the current at the HVterminals 1 (external) and 2 (middle), as well as the phaseshift between voltage and current signals. A probeassociated with an amplifier was used for currentmeasurements.

Fig. 1 shows the circuit used for the determination of Z11.For each frequency its modulus was calculated by the ratioof the amplitudes of the voltage at point P1 and the currentat point P3. The phase shift was given by the difference intime between the zero crossings of the voltage and currentsignals. The output impedance Z22 was obtainedanalogously. For the determination of the transferimpedance Z21 the calculations considered, with referenceto Fig. 1, the voltage transferred to secondary (at the pointP2) and the current at the point P3.

Fig. 1 - Circuit for the determination of the transformer input impedanceZ11. G: signal generator; amp.: amplifier; osc.: oscilloscope.

Page 2: A SIMPLE TRANSFORMER MODEL FOR ANALYSIS OF … · A SIMPLE TRANSFORMER MODEL FOR ANALYSIS OF TRANSFERRED LIGHTNING SURGES FROM MV TO LV ... rate of 500 MS/s and bandwidth of 300 MHz

Figs. 2 to 4 present the curves, as functions of frequency, ofthe transformer impedances.

Z11 [ohms]

0

5000

10000

15000

20000

25000

30000

35000

10 100 1000

Fase Z11 [graus]

-120

-100

-80

-60

-40

-20

0

10 100 1000

Frequency [kHz]

Fig. 2 - Transformer input impedance Z11 as function of frequency.

Z22 [ohms]

0

200

400

600

800

1000

1200

1400

10 100 1000Frequency [kHz]

Fase Z22 [graus]

-80

-60

-40

-20

0

20

40

60

80

100

10 100 1000

Frequency [kHz]

Fig. 3 - Transformer output impedance Z22 as function of frequency.

Z21 [ohms]

0

50

100

150

200

250

10 100 1000Frequency [kHz]

Fase Z21 [graus]

-150

-100

-50

0

50

100

10 100 1000

Frequency [kHz]

Fig. 4 - Transformer transfer impedance Z21 as function of frequency.

As the HV terminals were short-circuited, the inductiveeffect of the windings is practically eliminated, since theprimary windings are connected in delta. This explains theessentially capacitive behaviour of the input impedanceZ11. On the other hand, as the LV windings are connectedin star, the inductive effect of the windings leads to apredominantly inductive behaviour of the output impedanceZ22 up to the frequency of approximately 750 kHz. Thetransfer impedance Z21 has a more complex frequency-dependent behaviour, alternating between capacitive andinductive characteristics, with various ressonance points.

Considering these results, simulations were then made inorder to obtain a circuit, as simple as possible, that couldreasonably reproduce the transformer behaviour in thefrequency range adopted in this study (from 10 kHz to1MHz). After some attempts the model shown in Fig. 5,composed by resistive, inductive and capacitive elements,was considered to be representative of the transformer.

Fig. 5 - Transformer model for calculation of transferred surges.

Frequency [kHz]

Z11 [kΩ]

Z11 phase [degrees]

Z22 [kΩ]

35

30

25

20

15

10

5

0

0

-20

-40

-60

-80

-100

-120

1.4

1.2

1.0

0.8

0.6

0.4

0.2

0

100

80

60

40

20

0

-20

-40

-60

-80

Z22 phase [degrees]

0.25

0.2

0.15

0.1

0.05

0

Z21 [kΩ]

100

50

0

-50

-100

-150

Z21 phase [degrees]

Page 3: A SIMPLE TRANSFORMER MODEL FOR ANALYSIS OF … · A SIMPLE TRANSFORMER MODEL FOR ANALYSIS OF TRANSFERRED LIGHTNING SURGES FROM MV TO LV ... rate of 500 MS/s and bandwidth of 300 MHz

Validation

Two kinds of tests were performed in order to verify thevalidity of the transformer model. In the simplestconfiguration, impulse voltages (1.2/50 µs waveform) withamplitudes of approximately 8 kV were applied to thehigh-voltage terminals interconnected, and the voltagestransferred to the secondary side were measured underdifferent load conditions. Figs. 6 to 8 present somecomparisons between measured (at terminals X1 and X2)and calculated transferred voltages, obtained for differentload conditions.

voltage [V]

-200

-150

-100

-50

0

50

100

150

200

0 10 20 30 40

time [us]

terminal X1terminal X2

(a)

voltage [V]

-200

-150

-100

-50

0

50

100

150

200

250

time [us]

0 10 20 30 40

(b)

Fig. 6 - Voltages transferred to the secondary under no-load conditions.a) measured b) calculated

voltage [V]

-10

0

10

20

30

40

50

60

time [us]

terminal X1terminal X2

0 4 8 16 2012

(a)

voltage [V]

-20

-10

10

20

30

40

50

time [us]

0 4 12 16 2080

(b)

Fig. 7 - Voltages transferred to the secondary (resistive load of 100 Ω).a) measured b) calculated

voltage [V]

-10

-5

0

5

10

15

20

25

30

35

time [us]

terminal X1

terminal X2

0 20 40 60 80 100

(a)

voltage [V]

-5

0

5

10

15

20

25

30

time [us]

0 20 40 60 80 100

(b)

Fig. 8 - Voltages transferred to the secondary (resistive load of 50 Ω).a) measured b) calculated

The second configuration included also the presence of asimulated low-voltage line and of a medium voltage ZnOarrester (rated current of 10 kA). Either resistors orcapacitors, placed at the end of the line and connectedbetween phases and neutral, were used to simulate differentload types. Impulse currents with amplitudes of about 5 kAwere applied to the arrester; the voltages were measurednot only at the transformer terminals (low-voltage side) butalso at the end of the line. The arrester was connectedeither to the HV terminals short-circuited or only to theterminal H1, as shown in Fig. 9. Fig. 10 shows the currentinjected into the circuit.

200

150

100

50

0

-50

-100

-150

-200

250

200

150

100

50

0

-50

-100

-150

-200

60

50

40

30

20

10

0

-10

50

40

30

20

10

0

-10

-20

35

30

25

20

15

10

5

0

-5

-10

30

25

20

15

10

5

0

-5

Page 4: A SIMPLE TRANSFORMER MODEL FOR ANALYSIS OF … · A SIMPLE TRANSFORMER MODEL FOR ANALYSIS OF TRANSFERRED LIGHTNING SURGES FROM MV TO LV ... rate of 500 MS/s and bandwidth of 300 MHz

X3X2

X1X0

impulse generator

surgearrester

d = 0,11 m

R1

shunt

reference

L3L2L1 L0

R2

Line heighth = 1,1 m

line lengthL = 19 m

Fig. 9 - Test configuration. Shunt resistor = 2.62 mΩ;R1 = 4.5 Ω; R2 = 2.5 Ω.

-1

0

1

2

3

4

5

time [5 us/div]

kA

Fig. 10 - Current injected into the test circuit.

Figs. 11 to 14 present some comparisons between measuredand calculated phase-to neutral voltages at the loads, indifferent situations. For the calculations, the ATP(Alternative Transients Program) was used.

-10

-5

5

10

15

time [5us/div]

kV

VL1-VL0VL2-VL0VL3-VL0

0

(a)

0 5 10 15 20 25 30

(b)

Fig. 11 - Phase-to neutral voltages at the loads (capacitances of 40 nF).Arrester connected only to terminal H1.a) measured b) calculated

-4

-2

2

4

6

8

kV

no load45 ohms

0

time [5 us/div](a)

0 5 10 15 20 25 30

(b)

Fig. 12 - Phase-to neutral voltages at L1 (VL1 - VL0), for two conditions:without loads and with resistive loads of 45 Ω. Arrester connected only

to terminal H1. a) measured b) calculated

-10

-5

0

5

10

15

tempo [5 us/div]

kV

1 nF

40 nF

(a)

0 5 10 15 20 25 30

(b)

Fig. 13 - Phase-to neutral voltages at L1 (VL1 - VL0). Loads representedby capacitances of 1 nF and 40 nF. Arrester connected only to

terminal H1. a) measured b) calculated

time [5us/div]

NO LOAD

15

10

5

0

-5

-10

[kV]

8

6

4

2

0

-2

-4

[kV]

15

10

5

0

-5

-10

[kV]

Page 5: A SIMPLE TRANSFORMER MODEL FOR ANALYSIS OF … · A SIMPLE TRANSFORMER MODEL FOR ANALYSIS OF TRANSFERRED LIGHTNING SURGES FROM MV TO LV ... rate of 500 MS/s and bandwidth of 300 MHz

-10

-5

0

5

10

15

tempo [5us/div]

kV

PR’s em H1

PR’s em H1H2H3

(a)

0 5 10 15 20 25 30

(b)

Fig. 14 - Phase-to neutral voltages at L1 (VL1 - VL0). Loads representedby capacitances of 40 nF. Arrester connected to terminalsH1, H2 and H3 (short-circuited) and only to terminal H1.

a) measured b) calculated

The results show that the proposed model gives areasonable representation of the distribution transformer interms of voltages transferred to the secondary. As shown inthe comparisons relative to the simplest test circuit, thedifferences between measured and calculated voltages tendto increase as the impedance connected to low-voltageterminals decreases. The relatively good results obtainedfor the more complex test configuration indicates that themodel is also adequate to more realistic situations.

LIGHTNING SURGES TRANSFERRED TO THE LVNETWORK

With the transformer represented by the model previouslyobtained, simulations were then performed with the ATP, inorder to calculate voltages transferred to the secondary insome typical situations, such as in that presented in Fig. 15.

In this topology the primary and secondary lines arepartially coupled, and the transformer is placed at the end ofthe primary line.

The possibility of the occurrence of flashovers in theprimary and secondary circuits, as well as from the neutralconductor to the ground, was taken into account by meansof the switches shown in Fig. 15. They were placed at everypole; the Vxt characteristic curves were calculated using thestandardised lightning impulse waveform (1,2/50 µs), withthe integration method presented in [2].

The points labelled as D1, D2, ... and E1, E2, ..., in Fig.15,represent the poles, with a span distance of 30 m. Rc and Rsrepresent the ground resistances of the consumers. Differentvalues were assumed for the ground resistances of thepoles: Rt (effectively grounded) and Rp (not effectivelygrounded). The values of Rp were defined as twice thevalues of Rt, as obtained in tests reported in [3].

The consumers loads, connected between phase and neutral,were represented by a resistor of 30 Ω in parallel with acapacitance of 4 nF. The impedance modulus of thisassociation lies in the range of the values presented in [4].

The lightning current, injected in the primary line at the D3point (90 m distant of the transformer), was represented bya triangular waveform with a peak value of 31 kA, time tocrest of 2 µs and time to half-value 50 µs. A typical VxIcurve was used for representing the characteristic of theZnO primary arrester.

For illustration purposes, Figs 16 to 18 show someexamples of calculated voltages transferred to thesecondary (each phase-to-neutral) in the case of a directstrike on the MV line at the point D3. In Fig. 16 thevoltages were calculated at the point D1 (located 30 m fromthe transformer). Fig. 17 refers to voltages at point D5 (150m far from the transformer) while the Fig.18 shows thevoltages at the transformer terminals. Ground resistances of100 Ω were assumed for Rt and Rc.

Another application of the transformer model forcalculating surges in LV networks as well as associatedcurrents and charges in protective devices is presented in[5].

time [5us/div]

Fig. 15 – Line configuration used in the simulations

SA’s in H1SA’s in H1,H2,H3

15

10

5

0

-5

-10

[kV]

Page 6: A SIMPLE TRANSFORMER MODEL FOR ANALYSIS OF … · A SIMPLE TRANSFORMER MODEL FOR ANALYSIS OF TRANSFERRED LIGHTNING SURGES FROM MV TO LV ... rate of 500 MS/s and bandwidth of 300 MHz

0 5 10 15 20 25-10

- 5

0

5

10

15

( 5) BFDA 1 - ND1 ( 6) BFDB1 - ND1 ( 7) BFDC1 - ND1

0 5 10 15 20 25

Fig. 16 - Phase-to-neutral voltages on the secondary line (at point D1).

5 10 15 20 25- 10

0

10

20

30

40

[kV]

(21) BFDA 5 - ND5 (22) BFDB5 - ND5 (23) BFDC5 - ND5

0 5 10 15 20 25

Fig. 17 - Phase-to-neutral voltages on the secondary line (at point D5).

5 10 15 20 25- 10

- 5

0

5

10

15

[kV]

( 1) BFA0 - N0 ( 2) BFB0 - N0 ( 3) BFC0 - N0

0 5 10 15 20 25

Fig. 18 - Phase-to-neutral voltages on the secondary line

(at the transformer terminals).

CONCLUSIONS

A simple model for representation of distributiontransformers was developed, aiming at the calculation ofsurges transferred to the secondary. The results of thecomparisons between measured and calculated voltagesindicate that the proposed model can be an useful tool forthe evaluation of transferred surges, taking into account thecompromise between accuracy and simplicity.

ACKNOWLEDGEMENT

The authors greatly acknowledge the Center of Excellencein Distribution of Electrical Energy (CED) for supportingthis work.

REFERENCES

[1] Vaessen, P.T. "Transformer model for highfrequencies". IEEE Trans. on Power Delivery, v. 3,no 4, pp. 1761-1768.

[2] Darveniza, M.; Vlastos, A. E. "The GeneralizedIntegration Method for Predicting Impulse Volt-Time Characteristics for Non-Standard WaveShapes - a Theoretical Basis". IEEE Transactionson Electrical Insulation, vol. 23, no. 3, June 1988,pp. 373-381.

[3] Sekioka,S.; Yamamoto, K.; Yokoyama, S."Measurements of a Concrete Pole Impedance withan Impulse Current Source". In: InternationalConference on Power Systems Transients, Lisbon,September 3-7, 1995.

[4] Hoidalen, H. K. "Lightning-induced voltages in low-voltage systems and its dependency on voltage lineterminations". In: International Conference onLightning Protection, 24, Birmingham, 1998.

[5] W. Bassi, N. M. Matsuo, A. Piantini, "Currents andcharge absorbed by low-voltage SPDs in overheaddistribution systems due to lightning". (Submitted tothe 11th International Symposium on High VoltageEngineering, London, 1999)

15

10

5

0

-5

-10

[kV]

40

30

20

10

0

-10

[kV]

15

10

5

0

-5

-10

[kV]