a review of droop controlled, grid-forming inverters in

19
1 A Review of Droop Controlled, Grid-Forming Inverters in CERTS Microgrid and Their Potential Impact on Bulk Power Systems Wei Du Senior Research Engineer Pacific Northwest National Laboratory April 20, 2020 WECC Model Validation Working Group Annual Meeting This work is partially funded by the Microgrid R&D program, which is funded by the U.S. Department of Energy’s (DOE) Office of Electricity. The Microgrid R&D Program is managed by Mr. Dan Ton.

Upload: others

Post on 06-Apr-2022

4 views

Category:

Documents


0 download

TRANSCRIPT

1

A Review of Droop Controlled, Grid-Forming Inverters in CERTS Microgrid and Their Potential

Impact on Bulk Power Systems

Wei Du

Senior Research Engineer

Pacific Northwest National Laboratory

April 20, 2020

WECC Model Validation Working Group Annual Meeting

This work is partially funded by the Microgrid R&D program, which is

funded by the U.S. Department of Energy’s (DOE) Office of Electricity.

The Microgrid R&D Program is managed by Mr. Dan Ton.

2

OUTLINE

➢ Grid-Forming & Grid-Following Concept

➢ A brief introduction

➢ Droop-Control for Grid-Forming Inverters in CERTS Microgrid

➢ Controller design, simulation, and field tests in CERTS/AEP test bed

➢ Comparison of grid-following and grid-forming inverter

➢ Distribution-level networked microgrids

➢ Transmission systems (Hawaiian Island of Oahu)

➢ Discussion: How should inverters respond to faults in a highly inverter-penetrated bulk power system?

3

Voltage Source Inverter

Grid-Following (Current Source) Grid-Forming (Voltage Source)

+ Current control (PLL+ current loop)

+ Control P & Q

- Do not control voltage and frequency

- Cannot work without a grid

+ Voltage & frequency control

+ Can work in islanded mode

- No direct control of current

- Overload/over-current Issues

At the beginning of disturbance, the inverter

output current is approximately constant,

then external controls adjust Id and Iq.

At the beginning of disturbance, the inverter

internal voltage is constant, then external

controls adjust E and ω.

4

Droop Control for Grid-Forming Inverters in

CERTS Microgrid

5

Sources

Loads

60 kW Tecogen Inverter-

coupled IC engine-generator

Static Switch

http://certs.lbl.gov/certs-der-pubs.htmlAEP/CERTS Microgrid Test Bed

• AEP/CERTS Microgrid: one of the earliest inverter-based microgrids in the world

(constructed in 2006), funded by DOE

• Principle Investigator: Prof. Bob Lasseter from University of Wisconsin-Madison

• The CERTS Microgrid Program has been running for almost 20 years

A 100% Grid-Forming-Inverter-based Microgrid

6

Droop Control for Grid-Forming Inverter

• Two ideal voltage sources cannot be paralleled. The coupling reactance XL is very

important for grid-forming inverters

➢ If XL is well designed (e.g., 5%-20%): P∝δ, Q∝E

• Droop Control: Parallel multiple voltage sources in a microgrid

➢ P vs. f droop ensures the phase angles are synchronized (1% P-f droop)

➢ Q vs. V droop avoids large circulating vars between voltage sources (5% Q-V droop)

P vs. f droop Q vs. V droop

δ P ω δ (Negative feedback control)

[1] Du, W., Chen, Z., Schneider, K. P., Lasseter, R. H., Pushpak, S., Tuffner, F. K., & Kundu, S. (2019). A Comparative Study of Two Widely

Used Grid-Forming Droop Controls on Microgrid Small Signal Stability. IEEE Journal of Emerging and Selected Topics in Power Electronics.

Time/s 2.80 3.00 3.20 3.40 3.60 3.80 ...

...

...

0

10

20

30

40

50

60

70

80

P [

kW]

P_A1 P_A2

-10.0

-5.0

0.0

5.0

10.0

Q [

kvar]

Q_A1 Q_A2

58.00

58.50

59.00

59.50

60.00

60.50

61.00

Fre

quency

[H

z]

f_A1 f_A2

7

A Two-Grid-Forming Inverter Microgrid

Z1

A1

XLA1

Z2

K

A2

XLA2

(EA1,δA1) (EA2,δA2)

Load 1 Load 2

Scenario 1: Normal Load Switching

Time/s 2.80 3.00 3.20 3.40 3.60 3.80 ...

...

...

-500

-400

-300

-200

-100

0

100

200

300

400

500

Voltage [

V]

Van Vbn Vcn

-150

-100

-50

0

50

100

150

200

A1 C

urr

ent

[A]

IA1a IA1b IA1c

-150

-100

-50

0

50

100

150

200

A2 C

urr

ent

[A]

IA2a IA2b IA2c

Voltages and currents P, Q, f

Q-V droop (5%) mitigates

circulating vars

• Grid-forming inverters respond to load changes

instantaneously because they are voltage sources

• Assume no inverters are overloaded

Pmax = 60 kW

Frequency is much more stable than synchronous

machine dominated system

A 0.33 p.u. Load Step

8

0

20

40

60

80

A1 Power kW

A2 Power kW

-500

0

500

Load Voltage Phase a

Load Voltage Phase b

Load Voltage Phase c

0 0.2 0.4 0.6 0.8 1

-100

0

100

Time Seconds

A1 3 Phase Currents

A2 3 Phase Currents

Overload

Scenario 2: Partial Overload

Without Pmax Controller

• When one source is dispatched near its

maximum generation, a load step can result in

overload

• Overload can collapse dc bus of inverters,

stall the synchronous generators, etc.

A Two-Source System

Z1

A1

XLA1

Z2

K

A2

XLA2

(EA1,δA1) (EA2,δA2)

Load 1 Load 2

0 10 20 30 40 50 60 70 8059

59.2

59.4

59.6

59.8

60

60.2

60.4

60.6

Power[kW]

Fre

quency[H

z]

P

max=60kW

Pset-A2

=5kW

Pset-A1

=55kW

PA2

=20kW PA1

=70kW

Without Pmax Controller

9

0

20

40

60

80

A1 Power kW

A2 Power kW

-500

0

500

Load Voltage Phase a

Load Voltage Phase b

Load Voltage Phase c

0 0.2 0.4 0.6 0.8 1

-100

0

100

Time Seconds

A1 3 Phase Currents

A2 3 Phase Currents

Overload

Without Pmax Controller

• When one source is dispatched near its

maximum generation, a load step can result in

overload

• Overload can collapse dc bus of inverters,

stall the synchronous generators, etc.

A Two-Source System

Z1

A1

XLA1

Z2

K

A2

XLA2

(EA1,δA1) (EA2,δA2)

Load 1 Load 2

0 10 20 30 40 50 60 70 8059

59.2

59.4

59.6

59.8

60

60.2

60.4

60.6

Power[kW]

Fre

quency[H

z]

P

max=60kW

Pset-A2

=5kW

Pset-A1

=55kW

PA2

=20kW PA1

=70kW

Without Pmax Controller

-+

mp

Pset

P ++

ω0

+

kppmax+kipmax/s

+

+

-

-+

+

Pmin

0

0

Pmax

P

ω

kppmax+kipmax/s

Δω +

Overload Mitigation Controller:

Change the phase angle between sources: Dd

Scenario 2: Partial Overload

10

0

20

40

60

80

A1 Power kW

A2 Power kW

-500

0

500

Load Voltage Phase a

Load Voltage Phase b

Load Voltage Phase c

0 0.2 0.4 0.6 0.8 1

-100

0

100

Time Seconds

A1 3 Phase Currents

A2 3 Phase Currents

Overload

Without Pmax Controller

With Pmax Controller

• Transfer the extra load to non-overloaded

sources by reducing the frequency rapidly

• The change of phase angle redistributes

power flow between sources

A Two-Source System

Z1

A1

XLA1

Z2

K

A2

XLA2

(EA1,δA1) (EA2,δA2)

Load 1 Load 2

0 10 20 30 40 50 60 70 8059

59.2

59.4

59.6

59.8

60

60.2

60.4

60.6

Power[kW]

Fre

quency[H

z]

P

max=60kW

Pset-A2

=5kW

Pset-A1

=55kW

PA2

=20kW PA1

=70kW

With Pmax ControllerWithout Pmax Controller

0 10 20 30 40 50 60 70 8059

59.2

59.4

59.6

59.8

60

60.2

60.4

60.6

Power[kW]

Fre

quency[H

z]

P

max=60kW

PA2

=30kW

Pset-A1

=55kW

Pset-A2

=5kW

PA1

=60kW

Scenario 2: Overload Transfer

0

20

40

60

80

59.6

59.8

60

0 0.2 0.4 0.6 0.8 1

2

3

4

Time Seconds

A1 Power kW

A2 Power kW

A1 Frequency Hz

A2 Frequency Hz

Phase Angle Degree

-500

0

500

-100

0

100

Load Voltage Phase a

Load Voltage Phase b

Load Voltage Phase c

A1 3 Phase Currents

A2 3 Phase Currents

Overload

Change of Phase Angle

[1] Du, Wei, Robert H. Lasseter, and Amrit S. Khalsa. "Survivability of autonomous microgrid

during overload events." IEEE Transactions on Smart Grid 10, no. 4 (2018): 3515-3524.

11

How do high-penetration of grid-forming/grid-following

inverters impact the transient stability of distribution-

level networked microgrids?

➢ Comparison of Grid-Following and Grid-Forming

12

An Islanded IEEE 123-Node Test Feeder with High Penetration of Inverters

• Synchronous Generators: 3*600 kW

• 6 Inverters: 1400 kW

• Peak Load: 2150 kW + 490 kvar

• Inverter Penetration: 65% (compared

to peak load)

• Substation voltage is lost due to

extreme weather events, three

microgrids work as an islanded

networked microgrid

• Contingency: Loss of Generator 3

Simulation of a Modified IEEE 123-Node Test Feeder

Synchronous

GeneratorGrid-Forming or

Grid-Following

Inverter

[1] Du, Wei, et al. "Modeling of Grid-Forming Inverters for Transient Stability Simulations of an all Inverter-based

Distribution System." 2019 IEEE PES ISGT. IEEE, 2019.

13

Grid-Forming (direct voltage control):

measure P & Q, control f & VGrid-Following (PLL + current loop):

measure f & V, control P & Q

Frequency-Power Droop

Voltage-Reactive Power Droop

0.02s 5% droop 0.25s

0.02s 0.2s5% droop

5% droop

Power-Frequency Droop

Reactive Power-Voltage Droop

• Inverter uses voltage source

representation

• Grid-Forming: Internal voltages

are three-phase balanced

• Grid-Following: Inject three-

phase balanced currents

• GridLAB-D: Three-phase,

phasor-based simulation

software developed by PNNL for

unbalanced distribution systems

XLE δa

E ω

XL

E ω

XLE δc

E ω

E δb Distribution

System

Network

Solution

Inverter Controller

Pi,Qi,Vgi

E,ω

14

Grid-Following

Simulation of a Modified IEEE 123-Node Test Feeder

• Grid-Forming inverters can improve frequency stability

• Grid-Forming inverters response to load changes

instantaneously (voltage source)

• Grid-Following inverters respond to frequency change

slowly

Grid-Forming

Major improvement

5% P-f droop for both grid-following and grid-forming

15

Impact on Bulk Power Systems

➢ A Case Study of Hawaiian Island of Oahu

16

Loss of a 200MW generator (1080MW load, 540 MW PV)

Hawaiian island of Oahu

(50% distributed PV)

Total system load

Grid-following: Frequency-Watt (5% droop)

Grid-forming: CERTS inverter (1% droop)

[1] Elkhatib, Mohamed E., Wei Du, and Robert H. Lasseter. "Evaluation of Inverter-based Grid Frequency Support using Frequency-Watt

and Grid-Forming PV Inverters." In 2018 IEEE Power & Energy Society General Meeting (PESGM), pp. 1-5. IEEE, 2018.

• User-written models of grid-forming and grid-following inverters developed in PSS/E

• Assume PV has sufficient headroom

Load trippingFrequency

Major improvement

17

Discussion: How should inverters respond to faults in a

highly-inverter penetrated bulk power system?

6 p.u. over-current

18

CERTS grid-forming inverter’s response to faults [1]Momentary cessation of BPS-Connected IBR during faults

(Source: NERC BPS-connected IBR guideline report)

• Current sources are immune to faults, while voltage sources provide high fault currents

• Grid-following control can limit fault currents from inverters, reducing the cost of products

• However, for a 100% inverter-based bulk power system (BPS), limiting fault currents of Inverter-

based resources (IBRS) may cause system-wide low voltage during faults, potentially affect

millions of customers at the distribution level

As IBRs continue to increase in BPS, we need to consider how should

inverters inject fault currents to support voltage during faults.

[1] Lasseter, Robert H., et al. "CERTS microgrid laboratory test bed." IEEE Transactions on Power Delivery 26.1 (2010): 325-332.

Thank you

Wei [email protected]

19

This work is partially funded by the Microgrid

R&D program, which is funded by the U.S.

Department of Energy’s (DOE) Office of

Electricity. The Microgrid R&D Program is

managed by Mr. Dan Ton.