Tam ilN adu Telecom C ircle Tam ilN adu Telecom C ircle A PRESENTATION ON A PRESENTATION ON ENERGY SAVING ENERGY SAVING IN IN BASEMENT CAR PARK VENTILATION BASEMENT CAR PARK VENTILATION FOR FOR THE ADMINISTRATIVE BUILDING AT THE ADMINISTRATIVE BUILDING AT GREAMS ROAD , GREAMS ROAD , CHENNAI CHENNAI . .

Upload: kassia

Post on 16-Jan-2016

123 views

Category:

Documents


6 download

DESCRIPTION

A PRESENTATION ON ENERGY SAVING IN BASEMENT CAR PARK VENTILATION FOR THE ADMINISTRATIVE BUILDING AT GREAMS ROAD , CHENNAI. ADMIN BUILDING AT GREAMS ROAD, CHENNAI. Proposed Hi-Tech Admn. Bldg Consists of 2 Towers- G+8 / G+5 and has a common lower and upper level Basement - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: A    PRESENTATION    ON ENERGY SAVING IN BASEMENT CAR PARK VENTILATION FOR

1Tamil Nadu Telecom CircleTamil Nadu Telecom CircleTamil Nadu Telecom CircleTamil Nadu Telecom Circle

A PRESENTATION ONA PRESENTATION ON

ENERGY SAVINGENERGY SAVING

ININ

BASEMENT CAR PARK VENTILATIONBASEMENT CAR PARK VENTILATION

FOR FOR

THE ADMINISTRATIVE BUILDING ATTHE ADMINISTRATIVE BUILDING AT

GREAMS ROAD ,GREAMS ROAD , CHENNAICHENNAI..

Page 2: A    PRESENTATION    ON ENERGY SAVING IN BASEMENT CAR PARK VENTILATION FOR

2

ADMIN BUILDING AT GREAMS ROAD, CHENNAI

• Proposed Hi-Tech Admn. Bldg Consists of 2 Towers- G+8 / G+5 and has a common lower and upper level Basement

• Capacity of Basement – Parking for 157 cars & 97 two-wheelers.

• Area of Basement (covers Towers 1&2)– Lower Basement 4664 sq.m– Upper Basement 4437 sq.m

• Ceiling height of basements - 2.2 Mtr

Page 3: A    PRESENTATION    ON ENERGY SAVING IN BASEMENT CAR PARK VENTILATION FOR

3

• Car Parking area in Basements are fully enclosed.

• Enclosed Under-ground parking area requires Mechanical Ventilation.

• In absence of Ventilation, Parking facility presents several Internal Air Quality problems.

• Most serious is the emission of high levels of Carbon-Monoxide(CO)

• CO is easily absorbed by Haemoglobin in Human Blood and can Inhibit Oxygen delivery to Body and can cause adverse health effects varying from headache to death

Page 4: A    PRESENTATION    ON ENERGY SAVING IN BASEMENT CAR PARK VENTILATION FOR

4

• The NATIONAL BUILDING CODE OF INDIA – 2005 Specifies the following parameters for Ventilation:

CO level- within 29mg/cu.m (25 ppm) with

Peak level not to exceed 137 mg/cu.m.(125 ppm)

As per ASHRAE Max Level for CO

8 hrs exposure – 25ppm

1 Hour exposure- 35 ppm

Air change requirement as per NBC for Basement Car Parking :

– 9 to 12 ACPH under normal conditions

( For Design purpose 10 ACPH is used)– 30 ACPH in case of fire emergency

Page 5: A    PRESENTATION    ON ENERGY SAVING IN BASEMENT CAR PARK VENTILATION FOR

5

DUCTED VENTILATION

• The Conventional Ventilation System is the ducted Ventilation system. This has:

-Provision of Fresh air fan and Exhaust Air Fans with ducting arrangement as per requirement.

- To be operated based on timing control.

- Full capacity of Fans has to be operated irrespective of Smoke level or CO Concentration.

Page 6: A    PRESENTATION    ON ENERGY SAVING IN BASEMENT CAR PARK VENTILATION FOR

6

DUCTLESS VENTILATION The Modern method of Ventilation system is the Ductless Ventilation

system in which :- No Ducts are required.- Only Fresh Air Fans, Exhaust Air Fans and Jet Fans required.- CFD(Computational Fluid Dynamics) analysis, is utilised to decide the number and location of Jetfans for effective and optimum performance.- A group of approximately 4 Nos of Jet Fans are controlled by one CO Sensor and Integrated with IBMS.- When the CO level exceeds threshold value, CO Sensors extends signal to IBMS and accordingly the corresponding group of Jet Fans are triggered.- When CO level exceeds threshold value in approximately 50% of CO Sensors per Basement , then Fresh Air/ Exhaust Fans are switched ON through IBMS along with jet fans

Page 7: A    PRESENTATION    ON ENERGY SAVING IN BASEMENT CAR PARK VENTILATION FOR

7

ADVANTAGES OF DUCTLESS VENTILATION

• No ducts: duct system and accessories are eliminated.

• Improved air quality and efficient Operation• Optimum use of Car Park Space & Optimisation of

Head room for Vehicles and Pedestrians.• Flexibility in installation,quicker installation• Effective smoke management • During Fire Conditions, the volume of air to be

handled is of the order of 1.25 lakh CFM. Under this situation ductless system fares better compared to ducted system.

Page 8: A    PRESENTATION    ON ENERGY SAVING IN BASEMENT CAR PARK VENTILATION FOR

8

How energy saving is achieved in Ductless Ventilation?

• Ducts are associated with pressure drop,hence higher size F.A/E.F. are reqd.

• Jetfans are located using CFD Analysis in a manner that they help FA/EF to suck/exhaust air respectively, hence smaller size(HP) FA/EFreqd.

• During low traffic in Basement, depending upon CO level concentration, only a group of Jetfans may be switched ON by IBMS to distribute/ dilute CO concentration, while in ducted system higher capacity FA/EF have to be kept ON most of the time.

Page 9: A    PRESENTATION    ON ENERGY SAVING IN BASEMENT CAR PARK VENTILATION FOR

9

JET FAN

Page 10: A    PRESENTATION    ON ENERGY SAVING IN BASEMENT CAR PARK VENTILATION FOR

10

Construction / Characteristics of a Jet Fan

1 - Casing made of Sheet Steel2- Special silencers at the inlet and outlet side3- Inlet cone(s) 4- Protection guard(s)5- mounting brackets for ceiling suspension-Suitable for 300deg C operation for 1 hour- Speed : 1450 / 2900 rpm – Dual speed- CFM : 1900 / 3800 - KW : 0.3 / 1.5-Sound level : 53 / 71 dB-Area Served by each Fan – 280 sq.mtr.(Approx)

123 2 3

4 4

5 5

Page 11: A    PRESENTATION    ON ENERGY SAVING IN BASEMENT CAR PARK VENTILATION FOR

11

Comparison between Ducted & Ductless system:Capital Cost of Ducted System :

1. First Basement CFM KW Cost

Fresh Air Fan 38477X1No 22.5X1 No. 435600X1No

( 50 mm SP) 21764X1 No 18.5X1 No 220000X1No

Exhaust Air fan 38477X3 Nos 18.5X3 Nos 396000X3Nos

(40 mm SP) 21764X3Nos 15.0X3 Nos 188800X3Nos

2. Second basement

Fresh Air fan 38857X1 No 22.5X1 No. 435600X1No

(50 mm SP) 12354X1No 7.5X1 No. 153110X1No

6103X1No 4.0X1 No. 111160X1No

Exhaust air fans 38857X3 Nos 18.5X3 Nos 396000X3Nos

( 40 mm SP) 12354X3Nos 5.5X3 Nos 153110X3Nos

6103X3Nos 2.2X3 Nos 111160X3Nos

Total Cost Rs. 50,90,680.00

Cost of ducting and electrical panel ,cabling i/c

cable tray, etc

Rs. 20,00,000.00

Grand total of Capital cost Rs. 70,90,680.00

Page 12: A    PRESENTATION    ON ENERGY SAVING IN BASEMENT CAR PARK VENTILATION FOR

12

Comparison between Ducted & Ductless system:

• Ducted system

Operating Cost :• Assumption : All Fans Operation for 2 Hours (Peak

Hour), for Balance 6 Hours (Lean Period) Half an Hour ON & Half an Hour OFF.

• So, Total operating time=5 hrs/day.• Total unit consumption assuming 5hrs operation/day• =134.7 KW x 5 hrs = 673.5 KWH/day.• Running cost per annum assuming Rs.7/- per unit rate• = 673.5 x 25 days X 12 months X Rs.7/-

• = Rs. 14,14,350/- per annum.

Page 13: A    PRESENTATION    ON ENERGY SAVING IN BASEMENT CAR PARK VENTILATION FOR

13

Comparison between Ducted & Ductless system:Capital Cost for Ductless System :

1. First Basement CFM KW Capital Cost

Exhaust Air fan 38477X3 Nos 15.0X3 Nos 396000X3Nos

(25 mm SP) 21764X3Nos 9.3X3 Nos 171635X3Nos

2. Second basement

Fresh Air fan 38857X1 No 18.5X1 No. 396000X1No

(40 mmSP) 12354X1No 7.5X1 No. 153110X1No

6103X1No 4.0X1 No. 111160X1No

Exhaust air fans 38857X3 Nos 15.0X3 Nos 396000X3Nos

(25 mmSP) 12354X3Nos 5.5X3 Nos 153110X3Nos

6103X3Nos 2.2X3 Nos 111160X3Nos

Total Cost Rs. 43,43,985.00

Cost of Fresh Air fans & Exhaust Air Fans =Rs. 43,43,985.00 Cost of providing 32Nos. jet fans =Rs.31,99,680.00 Add cost of CO sensors, wiring control systems Electrical Panel & Cabling =Rs.15,00,000.00 Total Capital Cost =Rs. 90,43,665.00

Page 14: A    PRESENTATION    ON ENERGY SAVING IN BASEMENT CAR PARK VENTILATION FOR

14

Comparison between Ducted & Ductless system:• Ductless system• Operating cost :• I.Peak 2 hrs - All jet fans, fresh/exhaust fans ON.• a) Jet fans(32X0.3KW) =9.6 KWX2hrs = 19.2 units• b) Fresh air and exhaust fan =77.0 KW X 2hrs = 154.0 units

• II. For balance 6 hrs (Fresh air & Exhaust fan OFF)a)25% (2 groups i.e. approx. 8 fans ) jet fans ON

for 2 hrs =9.6KWX25%x2hrs = 4.8 unitsb)12.5% (1 group i.e. approx. 4 fans ) jet fans ON

for 2 hrs = 9.6KWX12.5%x2hrs= 2.4 unitsc) For 2 hours (consisting of 4 durations of ½ hr. each)

all Fans are OFF = Nil . . Total units/day = 180.40 units

Energy cost/annum = 180.40X 25 days X 12 months X Rs.7/- = Rs. 3,78,840.00Maintanence Cost for Jet fans p.a = Rs. 75,000.00Total Operating Cost per annum = Rs. 4,53,840.00

Page 15: A    PRESENTATION    ON ENERGY SAVING IN BASEMENT CAR PARK VENTILATION FOR

15

Calculation of Payback period

Ducted Ductless

1. Fresh air & Exhaust fans Rs. 50.90 lakhs Rs. 43.43 lakhs

2. Ducting and electrical panel and cabling, cable tray,CO sensors. Rs. 20.00 lakh Rs. 15.00

lakhs3. Jet fans NIL Rs. 32.00 lakhs

Total cost Rs. 70.90 lakhs Rs. 90.43 lakh

Capital cost for ducted System Rs. 70.90 lakhsCapital cost for ductless System Rs. 90.43 lakhsAdditional capital cost Rs. 19.53 lakhs

Savings in Operating cost/ Annum by providing jet fans = Rs. (14,14,350/- - 4,53,840/-)

= Rs. 9,60,510/- per annum.Pay back period = 19.53 x 12 months

9.60= 24.41 months

Or Say 24 months