1 R.I.B.A. (Royal Institute of British Architects) C.P.D. (Continuous Professional Development) Presentation Active Smoke & Fire Barriers Speaker Chuck Lewis – Coopers © Copyright of A. Cooper Group of Companies Limited

Upload: others

Post on 15-Jun-2021

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

1

R.I.B.A.(Royal Institute of British Architects)

C.P.D.(Continuous Professional Development)

PresentationActive Smoke & Fire

Barriers

SpeakerChuck Lewis – Coopers

© Copyright of A. Cooper Group of Companies Limited

Page 2: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

2

Introduction

to

Active Smoke Barriers

© Copyright of A. Cooper Group of Companies Limited

Page 3: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

3

Learning Aims

Introduction to Smoke Barriers

~What, where and why are they used, application specific

~What is the difference between them?

~What is the legislation you need to be aware of, and how must the manufacturer comply with this?

~What is the critical performance criteria?

© Copyright of A. Cooper Group of Companies Limited

Page 4: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

4

What is SHEVS?

Smoke and heat exhaust ventilation systems (SHEVS) create a smoke free layer above the floor level by removing smoke and heat, thereby improving the conditions for safe evacuation and/or rescue and the property protection permitting the fire to be fought whilst in its early stages.

The use of smoke and heat exhaust ventilation systems to create these smoke free layers has become widespread and is an integral part of building design.

Extract from BS EN12101-1:2006

© Copyright of A. Cooper Group of Companies Limited

Page 5: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

5

Smoke Barriers; Why are they used?

Smoke barriers are and important and critical part of this system where permitted within the SHEVS design.

The smoke barrier shall control the movement of the fire effluent in the event of a fire.

If smoke barriers are not in their fire operational position, the system (SHEVS) will not perform as designed.

However, in the event that other elements of the SHEVS do not function, smoke barriers in their fire operational position will provide essential smoke containment and channelling.

Extract from BS EN12101-1:2006

© Copyright of A. Cooper Group of Companies Limited

Page 6: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

6

Why are they used?

~To Stop Rapid Spread of SmokeThroughout Buildings

~Assist Occupants with Safe Evacuation

~Assist Emergency Services

~Used as a Life Safety Product

© Copyright of A. Cooper Group of Companies Limited

Page 7: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

7

The fire effluent will rapidly spread through a building

© Copyright of A. Cooper Group of Companies Limited

Page 8: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

8

Smoke Barriers contained smoke to the point of extraction

© Copyright of A. Cooper Group of Companies Limited

Page 9: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

9

What is an Active Smoke Barrier?

~ Like a large electrically operated roller blind

~ Concealed above a ceiling out of view

~Fire resistant fabric

~Weighted Bottom Bar

~Activated by an Alarm Signal

© Copyright of A. Cooper Group of Companies Limited

Page 10: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

10

Where are they used?

Void Edge Screen

Smoke barrier deployed beneath the edge of a balcony or projecting canopy. Void edge screens can either be use to create a smoke reservoir beneath the balcony or canopy or to restrict the length of spill edge in order to create a more compact spill plume

© Copyright of A. Cooper Group of Companies Limited

Page 11: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

11

Where are they used?

Channeling Screens

Smoke barrier used as channelling screens beneath a balcony or gases from a room opening to the spill edge

© Copyright of A. Cooper Group of Companies Limited

Page 12: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

12

Where are they used?

Reservoir Blinds

Region within a construction works limited or bordered by smoke barriers or structural elements so as to retain a thermally buoyant smoke layer in the event of a fire

© Copyright of A. Cooper Group of Companies Limited

Page 13: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

13

Where are they used?

© Copyright of A. Cooper Group of Companies Limited

Page 14: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

14

Where are they used?

Faceted/Segmented Atrium Void Application

© Copyright of A. Cooper Group of Companies Limited

Page 15: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

15

Where are they used?

Smoke Barriers

Clear

Smoke Logged

© Copyright of A. Cooper Group of Companies Limited

Page 16: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

16

Where are they used?

© Copyright of A. Cooper Group of Companies Limited

Page 17: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

17

Smoke Barrier Applications

~ Smoke reservoir boundaries

~Channelling screens

~Void edge screens

~Void sealing screens

~Corridor containment

~Shop unit containment

~Escalator containment

~Stairwell containment

~Elevator/Lift

© Copyright of A. Cooper Group of Companies Limited

Page 18: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

18

What is the relevant legislation?

BS EN12101-1:2006 Smoke and heat control systems. Specifications for smoke curtains

BS7346-3:1990 Smoke and heat control systems. Specifications for smoke curtains

BS476-6:1989 Fire tests on building materials and structures. Methods of test for fire propagation for products

BS476-7:1997 Fire tests on building materials and structures. Methods of test to determine the classification of the surface spread of flame of products

ISO9001:2000 Quality systems. Model for quality assurance in design, development, production, installation and servicing

© Copyright of A. Cooper Group of Companies Limited

Page 19: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

19

Types of Smoke Barrier

Static Smoke Barriers: (SSB)

Static smoke barriers shall be fixed in their fire operational position at all times and according to their design classification.

Active Smoke Barriers: (ASB)

Active Smoke Barriers shall be defined according to their application, e.g. life safety protection or property protection, method of operation and external initiations.

© Copyright of A. Cooper Group of Companies Limited

Page 20: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

20

Life Safety Application

The application of the smoke and heat control system in its fire operational

condition for the period of time required for the occupants of the premise to be alerted, and to be able to exit the premise, with the smoke and heat control system assisting in

the protection of the means of escape.

© Copyright of A. Cooper Group of Companies Limited

Page 21: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

21

ASB Categories

ASB1:

Smoke Barriers which fail safe in/to the fire operational position (not lower than 2.5m above the finished floor level or in any location hazardous to occupants or objects), in a controlled manner when all consumable primary and auxiliary power sources are removed, in the event of wiringor system corruption, or any combination thereof.

ASB2:

Smoke Barriers which move to/stay in the fire operational position (not lower than 2.5m above the finished floor level or in any location hazardous to occupants or objects), in a controlled manner upon external initiation but requiring a consumable power source in order to move to or be maintained in the fire operational position.

© Copyright of A. Cooper Group of Companies Limited

Page 22: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

22

ASB Categories

ASB3:

Smoke Barriers, conforming to type ASB1, which can be deployed to any height.

ASB4:

Smoke Barriers conforming to ASB2, which can be deployed to any height.

© Copyright of A. Cooper Group of Companies Limited

Page 23: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

23

ASB1 & ASB3 Smoke Barriers are “fit for purpose”

ASB1 and ASB3 do notrequire fire rated

ASB Categories

© Copyright of A. Cooper Group of Companies Limited

Page 24: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

24

Fitness for Purpose

The ability of a product, process or service to serve a

defined purpose under specific conditions.

© Copyright of A. Cooper Group of Companies Limited

Page 25: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

25

Performance Requirements and Classifications

~Temperature/time classification

~Reliability and durability of Active Smoke Barriers

~Response time of Active Smoke Barriers

~Smoke leakage (containment efficiency)

© Copyright of A. Cooper Group of Companies Limited

Page 26: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

26

Classification Temp °C Timemin

D30 600 30

D60 600 60

D90 600 90

D120 600 120

Temperature/Time

© Copyright of A. Cooper Group of Companies Limited

Page 27: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

27

Reliability & Durability

BS EN12101-1:2006 requires only – 1,000 Test Cycles

This should be done taking into account: ~capacity limits of motors; ~breaking loads; ~tear strength; ~flexural strength; ~maximum anticipated drop

*BS7346-3:1990 – 2,000 Test Cycles

© Copyright of A. Cooper Group of Companies Limited

Page 28: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

28

Response Times of Active Smoke Barriers

Controlled rates of descent

Active Smoke Barrier specimens types ASB1 and ASB2 shall commence movement immediately upon initiation or any initiation failure and move to their

operational position, in all operating modes, at a velocity range of between 0.06m/s and 0.30m/s.

Active Smoke Barriers types ASB3 and ASB4 which may be located in critical areas of a construction

works, e.g. escape routes, entrances/exits to escalators or stairways, shall have a velocity range of 0.06 –

0.15m/s.

© Copyright of A. Cooper Group of Companies Limited

Page 29: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

29

Safety Considerations

Active Smoke Barriers with long barrier movements while that cannot be fully deployed within 60s can nevertheless provide progressive

protection.

Such operation should not compromise SHEVS design e.g. if one barrier is designed to protect multiple floors around an atrium, when the fire occurs on a lower floor, the protection to higher

floors may be delayed.

© Copyright of A. Cooper Group of Companies Limited

Page 30: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

30

Safety Considerations

Precautions should be taken to ensure that descending barriers that provide full containment

do not cause injury, panic or confusion etc.

The use of visual or audible warnings devices and partial and progressive descent of barriers The barrier should be designed to return to a safe

condition in the event of a failure or malfunction etc.

Where this is for Life Safety it should Fail-Safe by ‘Gravity’

© Copyright of A. Cooper Group of Companies Limited

Page 31: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

31

Smoke Leakage (containment efficiency)

For functional reasons gaps may be required between the barrier and the construction works, and for angled and adjacent barriers. In these cases any gap should not exceed:

~ 20mm for barriers which travel up to and including 2m;~ 40mm for barriers which travel from 2m up to and including 6m;~ 60mm for barriers which travel more than 6m.

These gaps should not prejudice the‘fitness for purpose’

of the system.© Copyright of A. Cooper Group of Companies Limited

Page 32: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

32

Smoke Leakage (containment efficiency)

Overlapping barriers and conjoining bottom bars will reduce the problems of leakage and deflection.

Overlapping barriers and conjoining bottom bars will reduce the Overlapping barriers and conjoining bottom bars will reduce the problems of leakage and deflection.problems of leakage and deflection.

© Copyright of A. Cooper Group of Companies Limited

Page 33: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

33

Smoke Leakage (permeability of materials)

Smoke Barriers shall be manufactured from materials with a

maximum leakage rate of 25m3/h/m2 at 25Pa.

© Copyright of A. Cooper Group of Companies Limited

Page 34: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

34

Deflection

Movement of a smoke barrier when subjected to the buoyant force of the hot smoke, the movement of air, air pressure, or any combination thereof

Any movement can allow excessive smoke leakage. Avoid placing the barrier between columns or ensure sufficient linear bottom bar weight is applied or the use of side guides and/or channels for retention

Extract from BS EN12101-1:2006

© Copyright of A. Cooper Group of Companies Limited

Page 35: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

35

Deflection

Curtain between columns. Large gaps at sides and reduced smoke layer depth protection.

Extract from BS EN12101-1:2006

© Copyright of A. Cooper Group of Companies Limited

Page 36: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

36

Curtain between columns. Gaps at sides and reduced

smoke layer depth.

Non conjoined, adjacent curtains, either in-line or

angled.

Deflection

Extract from BS EN12101-1:2006

© Copyright of A. Cooper Group of Companies Limited

Page 37: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

37

Architectural Considerations

© Copyright of A. Cooper Group of Companies Limited

Page 38: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

38

Architectural Considerations

© Copyright of A. Cooper Group of Companies Limited

Page 39: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

39

Architectural Considerations

© Copyright of A. Cooper Group of Companies Limited

All in one curved ceiling

interfaces

All in one corner ceiling

interfaces

Page 40: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

40

Architectural Considerations

© Copyright of A. Cooper Group of Companies Limited

All in one curved ceiling interfaces

Page 41: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

41

General testing requirements – extract from BS EN12101-1:2006 - Annex A

Test sequence for initial type testing

The tests shall be carried out in the following sequence:

a) reliability and durability; 1,000 test operationsb) default operation to fire position; even without a consumable power sourcec) response time; at a controlled rate of descent all modesd) permeability;e) temperature/time.

© Copyright of A. Cooper Group of Companies Limited

Page 42: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

42

What is Fail-Safe?ASB1: Smoke barriers which fail safe in/to the fire operational position, in a controlled manner when all consumable primary and auxiliary power sources are removed, in the

event of wiring or system corruption, or any combination thereof.

Fail Safe by Gravity

Control Control EquipmentEquipment

MotorMotor

MainsMains GeneratorGenerator BatteryBattery BMSBMS

© Copyright of A. Cooper Group of Companies Limited

Page 43: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

43

Introduction

to

Fire Barriers

© Copyright of A. Cooper Group of Companies Limited

Page 44: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

44

Learning Aims

Introduction to Fire Barriers

~What, where and why are they used, applicationspecific

~What is the legislation you need to be aware of, andhow must the manufacturer comply with this?

~What is the critical performance criteria?

© Copyright of A. Cooper Group of Companies Limited

Page 45: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

45

What are Fire Barriers?

~Like a large electrically operated roller blind

~Concealed above a ceiling out of view

~Contained in side guide channels

~Fire resistant fabric

~Weighted Bottom Bar

~Activated by an Alarm Signal

© Copyright of A. Cooper Group of Companies Limited

Page 46: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

46

What are Fire Barriers?

© Copyright of A. Cooper Group of Companies Limited

Page 47: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

47

Where are they used?

~Separating Element (wall/ceiling)~Compartmentise areas (non load bearing walls/ceilings) ~Void, Escalator, Stairwell Separation~Lift Lobbies~Basement Separation

Or in place of:

~Fire Shutters~Fire Doors~Fire Rated Glazing

© Copyright of A. Cooper Group of Companies Limited

Page 48: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

48

Where are they used?

© Copyright of A. Cooper Group of Companies Limited

Page 49: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

49

Where are they used?

Separation of Shop from Mall with Partial Drop

© Copyright of A. Cooper Group of Companies Limited

Page 50: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

50

What is the relevant legislation?

~No planned British or European Standards

~Currently classed as doorsets/shutter assemblies

~Requirement for fire resistance is for integrity only -not insulation

~Need to prevent fire & smoke travel

~Integrity to same level as the compartment

~30, 60, 90, 120, 240mins fire barriers are available

© Copyright of A. Cooper Group of Companies Limited

Page 51: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

51

What is the relevant legislation?

PAS121:2007 Specification for active fire curtain barrier assemblies and active fire curtain barrier assemblies with smoke rating

BS EN1634-1:2000 Fire resistance tests for door and shutter assemblies. Fire doors and shutters

BS EN1364-1:1999 Fire resistance tests for non-load bearing elements for Walls

BS EN1364-2:1999 Fire resistance tests for non-load bearing elements for Ceilings

BS EN1363-1:1999 Fire resistance tests. General requirements

BS EN1363-2:1999 Fire resistance tests. Alternative and additional procedures

BS EN12101-1:2006 Smoke and heat control systems. Specifications for smoke curtains

ISO9001:2000 Quality systems. Model for quality assurance in design, development production, installation and servicing

© Copyright of A. Cooper Group of Companies Limited

Page 52: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

52

DH 30 Standard 30

DH 60 heating 60

DH 90 curve 90

DH 120 BS EN1363-1 120

Standard Classification Categories for Smoke Barriers

Classification Temperature Time°C min

© Copyright of A. Cooper Group of Companies Limited

Page 53: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

53

Fire Barriers

~Unlike fire shutters, fire barriers contain smoke

~Same requirements as smoke barriers used for life safety applications

~In addition side guides are required

~The barrier also needs to be held within the guide rails and should be capable of withstanding both pressure and impact

© Copyright of A. Cooper Group of Companies Limited

Page 54: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

54

Fire Testing

Up to 240 mins Integrity

Complete with

Overlap

© Copyright of A. Cooper Group of Companies Limited

Page 55: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

55

Fire Testing

© Copyright of A. Cooper Group of Companies Limited

Page 56: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

56

Impact TestingBS5324-2:1992

© Copyright of A. Cooper Group of Companies Limited

Page 57: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

57

Ambient Smoke Leakage TestBS476-31.1:1983

Full Size = 3x3m3.15m3/h/m2

© Copyright of A. Cooper Group of Companies Limited

Page 58: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

58

Signage

© Copyright of A. Cooper Group of Companies Limited

Page 59: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

59

Means of Escaping

© Copyright of A. Cooper Group of Companies Limited

Page 60: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

60

Means of Escaping

© Copyright of A. Cooper Group of Companies Limited

Page 61: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

61

Atrium Application

© Copyright of A. Cooper Group of Companies Limited

Page 62: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

62

Factory Application

© Copyright of A. Cooper Group of Companies Limited

Page 63: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

63

Lift Lobby Application

© Copyright of A. Cooper Group of Companies Limited

Page 64: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

64

Warehouse Compartment Application

© Copyright of A. Cooper Group of Companies Limited

Page 65: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

65

Horizontal Fire Barriers

Assessed Dimensions

5x12m

© Copyright of A. Cooper Group of Companies Limited

Page 66: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

66

Serving Hatch Application

© Copyright of A. Cooper Group of Companies Limited

Page 67: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

67

Corridor Application

© Copyright of A. Cooper Group of Companies Limited

Page 68: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

68

Window Boundary Application

© Copyright of A. Cooper Group of Companies Limited

Page 69: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

69

Escalator Application

© Copyright of A. Cooper Group of Companies Limited

Page 70: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

70

Marine Application

© Copyright of A. Cooper Group of Companies Limited

Page 71: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

71

Domestic Application

© Copyright of A. Cooper Group of Companies Limited

Page 72: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

72

Domestic Application

© Copyright of A. Cooper Group of Companies Limited

Page 73: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

73

Operating Modes

~Gravity Fail Safe Descent(as required by BS EN12101-1:2006)

~Mains Power Descent / Ascent(as required by BS EN12101-1:2006)

~Emergency Power Descent / Ascent(as required by BS EN12101-1:2006)

~Controlled Rates of Descent in all modes(as required by BS EN12101-1:2006)

~Variable & Synchronisable Speed Settings

© Copyright of A. Cooper Group of Companies Limited

Page 74: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

74

Status of Smoke & Fire Barriers

~If smoke barriers are not in their fire operational position, the SHEVS will not

perform as designed.

~In the event that other elements of the SHEVS do not function, barriers in their fire

operational position will provide essentialsmoke containment and channelling.

~If fire barriers are not in their fire operational position fire separation will not be instigated

which could lead to loss of life.

© Copyright of A. Cooper Group of Companies Limited

Page 75: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

75

Life Safety Application

~When every thing fails

~Loss of all power supplies

~Failure of batteries

~Wiring corruption

~Then the barrier must move to its fire operational position

~IF NOT….

© Copyright of A. Cooper Group of Companies Limited

Page 76: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

76

CoopersEdward House

Penner RoadHavant

HampshirePO9 1QZ

United Kingdom

t: +44 (0)2392 454405f: +44 (0)2392 [email protected]

Company Information

© Copyright of A. Cooper Group of Companies Limited

Page 77: A Coopers Presentation To Brakel Aero N.V By Andrew Cooper Coopers Blinds Ltdfe.hkie.org.hk/FireDigest/Document/Images/... · 2011. 6. 24. · BS EN12101-1:2006 Smoke and heat control

77

Dubai Community Theater & Arts CentreDubai International Finance Centre

Mall of the Emirates Shopping Centre, DubaiFortnum & Mason, London

Adidas Store, ParisDundrum Shopping Centre, Dublin

Xanadu Shopping Centre, SpainLangham Place Shopping Centre, Hong Kong

Wembley Stadium, LondonGreater London Authority (London Major's Office), London

Peter Jones Store, LondonThe Royal Exchange, London

The Royal Albert hall, LondonSwiss Re Tower, London

Case Studies