ISSN 1173-5996 A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer Supervised by: M J Spearpoint Fire Engineering Research Report 02/2 May 2002 This report was presented as a project report as part of the ME (Fire) Degree at the University of Canterbury School of Engineering University of Canterbury Private Bag 4800 Christchurch, New Zealand Phone 643 364-2250 Fax 643 364-2758 www.civil.canterbury.ac.nz

Upload: others

Post on 15-Apr-2020

13 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

ISSN 1173-5996

A Comparison Between Predicted and Actual Behaviour of Domestic Smoke

Detectors in a Realistic House Fire

by

DR Brammer

Supervised by:

M J Spearpoint

Fire Engineering Research Report 02/2

May 2002

This report was presented as a project report as part of

the ME (Fire) Degree at the University of Canterbury

School of Engineering

University of Canterbury

Private Bag 4800

Christchurch, New Zealand

Phone 643 364-2250

Fax 643 364-2758

www.civil.canterbury.ac.nz

Page 2: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Abstract

This report describes an investigation into various methods for predicting the

activation times for domestic ionisation and optical smoke detectors when detecting

flaming fires. The prediction methods studied were the temperature correlation

method where the detector is assumed to activate when the gas that surrounds it rises a

certain temperature above ambient, the pseudo-heat detector method in which an RTI

is assumed for the smoke detector, and Heskestad's method which is based on optical

density. The activation times predicted by these methods were then compared with

those that were recorded during actual fire tests within a full size two-storey test

house. The house was modelled on the field modelling software FDS.

Two test fires were considered in this study. Both were lounge chair fires in a room on

the ground floor of the house, and were flaming fires under vitiated conditions. The

energy output reached by the two fires was between 600 and 1000 kW. Data collected

during these tests included gas temperatures, optical density and the mass loss history

of the chairs. There were also a number of radiators throughout the house that were

left on for some time to heat the house before the fires were ignited.

It was found that there was little difference between the temperature correlation and

the pseudo-heat detector methods when a value for RTI of 1 my, sy, was considered. It

was also found that the use of an activation temperature of 20 oc above ambient

within the temperature correlation method was the most appropriate method for

predicting the activation times for the detectors. This value for activation temperature

is high compared with other researchers, but it is likely that the radiators within the

house created airflow currents that had an effect on the behaviour of the detectors.

Page 3: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Acknowledgements

A special thanks to my supervisor Mike Spearpoint for his support and guidance

during the course of this study.

Gratitude is expressed to Peter Coursey and Joost Stenfert-Kroese for providing ample

computing facilities as well as much technical advice. I found this advice to be

particularly useful during some of the more disheartening moments of my research.

I am also indebted to my classmates for their assistance during this study, especially

during similar disheartening moments.

I acknowledge the assistance of the staff of the Engineering School Library in finding

reference papers.

Finally, I would like to express my gratitude to the NZ Fire Service for not only

supporting the Fire Engineering programme at the University of Canterbury, but also

for funding my own scholarship.

ii

Page 4: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Table of Contents Page

Chapter 1 INTRODUCTION ..................................................................................... 1

1.1 Background To Study .................................................................................... 1

1.2 Objectives of Study ....................................................................................... 2

1.3 Behaviour of Smoke Detectors ...................................................................... 2

1.4 Cardington Tests ............................................................................................ 3

1.5 Fire Modelling Software .................... : ........................................................... 4

1.6 Scope of Study ............................................................................................... 5

1. 7 Outline of Report ........................................................................................... 6

Chapter 2 PREVIOUS RESEARCH .......................................................................... 8

2.1 Introduction ................................................................................................... 8

2.4.2 Pseudo-Heat Detector Method ................................................................. 11

2.4.4 Future Developments ............................................................................... 13

Chapter 3 FULL SCALE FIRE TESTS ................................................................... 16

3.1 Introduction ................................................................................................. 16

3.2 Description of House ................................................................................... 16

3.3 Instrumentation/Data Collection .................................................................. 18

3.4 Description of Tests ..................................................................................... 19

Chapter 4 COMPUTER MODELLING ................................................................... 22

4.1 Introduction ................................................................................................. 22

4.2 Configuration of House ............................................................................... 22

4.3 Grid Generation ........................................................................................... 23

4.4 Obstructions ................................................................................................. 26

4.5 Ambient Temperatures ................................................................................ 27

4.6 Derivation of HRR Curves .......................................................................... 29

4.7 Correction of Time Error ............................................................................. 35

4.8 Optical Density ............................................................................................ 35

4.9 Development of the House Domain Geometry ........................................... 36

Chapter 5 RESULTS AND DISCUSSION .............................................................. 38

5.1 Temperatures ............................................................................................... 38

5.2 Grid Sizes .................................................................................................... 38

5.3 Optical Density ............................................................................................ 42

5.4 Modelling of Smoke Detector Behaviour .................................................... 47

iii

Page 5: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

5.4.1 Temperature Correlation ...................................................................... 47

5.4.2 Pseudo-Heat Detector Method ............................................................. 51

5.4.3 Heskestad's Method ............................................................................ 55

5.5 Observations About Smoke Detector Modelling ......................................... 58

Chapter 6 CONCLUSIONS ..................................................................................... 60

6.1 House Domain Geometry ............................................................................ 60

6.2. Comparisons With Fire Behaviour .............................................................. 60

6.3. Comparisons With Smoke Detector Behaviour ........................................... 61

6.4. Further Research .......................................................................................... 61

REFERENCES ............................................................................................................ 63

Appendix A HOUSE DIMENSIONS, LOCATIONS OF INSTRUMENTATION 66

Appendix C FAMILIES OF CURVES FOR SIMULATIONS OF TEST CDT17. 77

Appendix D FAMILIES OF CURVES FOR SIMULATIONS OF TEST CDT20. 87

Appendix E FAMILIES OF CURVES FOR 75mm GRID SIMULATION ........... 97

iv

Page 6: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

List of Figures Page

Figure 3-1. Floor Plans for Test House ....................................................................... 18

Figure 3-2. Uncorrected Detector Activation Times, Test CDT17 ............................. 20

Figure 3-3. Uncorrected Detector Activation Times, Test CDT20 ............................. 20

Figure 4-1. Smokeview Image of House, View From South Wall .............................. 24

Figure 4-2. Smokeview Image of House, View From East Wall ................................ 25

Figure 4-3. Details of Balustrade to Stairs .................................................................. 26

Figure 4-4. Generation of Ambient Temperatures ...................................................... 28

Figure 4-5. Comparisons of Ambient Temperatures ................................................... 29

Figure 4-6. Mass Loss History- Test CDT17 ............................................................. 30

Figure 4-7. Derivation of HRR Curves -Test CDT17 ................................................ 31

Figure 4-8. Mass Loss History- Test CDT20 ............................................................. 31

Figure 4-9. Derivation of HRR Curves- Test CDT20 ................................................ 32

Figure 4-10. Unconected Lounge Temperatures- Test CDT17 ................................. 33

Figure 4-11. HRR Curve- Test CDT17 ...................................................................... 34

Figure 4-12. HRR Curve- Test CDT20 ...................................................................... 34

Figure 5-l. Lounge Temperatures - CDT17 ............................................................... 39

Figure 5-2. Lounge Temperatures- CDT20 ............................................................... 40

Figure 5-3. HRR Curves, Comparison of Grid Sizes- CDT17 .................................. 40

Figure 5-4. Lounge Temperatures, Comparison of Grid Sizes - CDT17 .................... 41

Figure 5-5. Entry Hall Temperatures, Comparison of Grid Sizes- CDT17 ............... 41

Figure 5-6. Bedroom 2 Temperatures, Comparison of G1id Sizes- CDT17 .............. 42

Figure 5-7. Lounge Optical Density- CDT17 ............................................................ 43

Figure 5-8. Bedroom 2 Optical Density- CDT17 ...................................................... 44

Figure 5-9. Lounge Optical Density- CDT20 ............................................................ 44

Figure 5-10. Bedroom 2 Optical Density- CDT20 .................................................... 45

Figure 5-11. Factored Lounge Optical Density- CDT17 ........................................... 45

Figure 5-12. Factored Bedroom 2 Optical Density- CDT17 ..................................... 46

Figure 5-13. Factored Lounge Optical Density- CDT20 ........................................... 46

Figure 5-14. Factored Bedroom 2 Optical Density- CDT20 ..................................... 47

Figure 5-15. Temperature Con-elation Method for Ionisation Detector- CDT17 ...... 49

Figure 5-16. Temperature Con-elation Method for Ionisation Detector- CDT20 ...... 49

Figure 5-17. Temperature Con-elation Method for Optical Detector - CDT 17 .......... 50

v

Page 7: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Figure 5-18. Temperature Correlation Method for Optical Detector- CDT20 .......... 50

Figure 5-19. HRR Curve for Collier's House Fire Test .............................................. 51

Figure 5-20. HRR Curve for Test CDT20 ................................................................... 51

Figure 5-21. Pseudo-Heat Detector Method for Ionisation Detector- CDT17 .......... 53

Figure 5-22. Pseudo-Heat Detector Method for Ionisation Detector- CDT20 .......... 53

Figure 5-23. Pseudo-Heat Detector Method for Optical Detector - CDT 17 ............... 54

Figure 5-24. Pseudo-Heat Detector Method for Optical Detector- CDT20 ............... 54

Figure 5-25. Heskestad's Method for Ionisation Detector- CDT17 .......................... 56

Figure 5-26. Heskestad's Method for Ionisation Detector- CDT20 .......................... 56

Figure 5-27. Heskestad's Method for Optical Detector- CDT17 .............................. 57

Figure Al. House Plans- Dimensions ......................................................................... 66

Figure A2. House Plans -Locations of Instrumentation ............................................. 67

Figure A3. House Plans- Locations and Ratings of Radiators ................................... 68

Figure Bl. Temperature Curve- No Balustrade ......................................................... 69

Figure B2. Diagram of Balustrade- 600mm High Horizontal ................................... 70

Figure B3. Temperature Curve- 600mm High Hmizontal.. ....................................... 70

Figure B4. Diagram of Balustrade- 800mm High Horizontal ................................... 71

Figure B5. Temperature Curve- 800mm High Horizontal.. ....................................... 71

Figure B6. Diagram of Balustrade- lOOOmm High Horizontal ................................. 72

Figure B7. Temperature Curve- lOOOmm High Horizontal.. ..................................... 72

Figure B 8. Diagram of Balustrade - 800mm High Cheque Pattern ............................ 73

Figure B9. Temperature Curve- 800mm High Cheque Pattern ................................. 73

Figure BlO. Diagram of Balustrade- lOOOmm High Cheque Pattern ........................ 74

Figure B11. Temperature Curve- lOOOmm High Cheque Pattern ............................. 74

Figure B 12. Diagram of Balustrade- 200mm High Soldiers ..................................... 7 5

Figure B13. Temperature Curve- 200mm High Soldiers ........................................... 75

Figure B14. Diagram of Balustrade- 200mm High Soldiers with Handrail .............. 76

Figure B15. Temperature Curve- 200mm High Soldiers Plus Handrail.. .................. 76

Figure C 1. HRR Curve - TestCDT17 ......................................................................... 77

Figure C2. Lounge Temperatures- Test CDT17 ........................................................ 78

Figure C3. Lounge Temperatures- Test CDT17 ........................................................ 78

Figure C4. Entry Hall Temperatures -Test CDT17 ................................................... 79 '

Figure C5. Stairs Temperatures- Test CDT17 ........................................................... 79

vi

Page 8: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Figure C6. Landing Temperatures -Test CDT17 ....................................................... 80

Figure C7. Bedroom 2 Temperatures- Test CDT17 .................................................. 80

Figure C8. Lounge Optical Density- Test CDT17 ..................................................... 81

Figure C9. Entry Hall Optical Density- Test CDT17 ................................................ 81

Figure ClO. Landing Hall Optical Density- Test CDT17 .......................................... 82

Figure C11. Bedroom 2 Optical Density- Test CDT17 ............................................. 82

Figure C12. Lounge Ionisation Detector Velocity- Test CDT17 .............................. 83

Figure C13. Hall Ionisation Detector Velocity- Test CDT17 .................................... 83

Figure C14. Landing Ionisation Detector Velocity- Test CDT17 ............................. 84

Figure C15. Bedroom 2 Ionisation Detector Velocity- Test CDT17 ......................... 84

Figure C17. Hall Optical Detector Velocity- Test CDT17 ........................................ 85

Figure C18. Landing Optical Detector Velocity- Test CDT17 .................................. 86

Figure C19. Bedroom 2 Optical Detector Velocity- Test CDT17 ............................. 86

Figure D 1. HRR Curve - TestCDT20 ......................................................................... 87

Figure D2. Lounge Temperatures -Test CDT20 ........................................................ 88

Figure D3. Lounge Temperatures- Test CDT20 ........................................................ 88

Figure D4. Entry Hall Temperatures- Test CDT20 ................................................... 89

Figure D5. Stairs Temperatures- Test CDT20 ........................................................... 89

Figure D6. Landing Temperatures- Test CDT20 ....................................................... 90

Figure D7. Bedroom 2 Temperatures - Test CDT20 .................................................. 90

Figure D8. Lounge Optical Density- Test CDT20 ..................................................... 91

Figure D9. Entry Hall Optical Density- Test CDT20 ................................................ 91

Figure DlO. Landing Hall Optical Density- Test CDT20 .......................................... 92

Figure D 11. Bedroom 2 Optical Density - Test CDT20 ............................................. 92

Figure D 12. Lounge Ionisation Detector Velocity - Test CDT20 .............................. 93

Figure D13. Hall Ionisation Detector Velocity- Test CDT20 .................................... 93

Figure D14. Landing Ionisation Detector Velocity- Test CDT20 ............................. 94

Figure D15. Bedroom 2 Ionisation Detector Velocity- Test CDT20 ......................... 94

Figure D16. Lounge Optical Detector Velocity- Test CDT20 .................................. 95

FigureD 17. Hall Optical Detector Velocity- Test CDT20 ........................................ 95

Figure D18. Landing Optical Detector Velocity- Test CDT20 ................................. 96

Figure D19. Bedroom 2 Optical Detector Velocity- Test CDT20 ............................. 96

Figure El. HRR Curve- TestCDT17 ......................................................................... 97

vii

Page 9: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Figure E2. Lounge Temperatures - TestCDT17 ......................................................... 97

Figure E3. Entry Hall Temperatures- TestCDT17 ..................................................... 98

Figure E4. Stairs Temperatures - TestCDT17 ............................................................ 98

Figure E5. Landing Temperatures- TestCDT17 ........................................................ 99

Figure E6. Bedroom 2 Temperatures- TestCDT17 .................................................... 99

viii

Page 10: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Chapter 1 INTRODUCTION

1.1 Background To Study

Most fire related deaths occur in residential dwellings, and as most fire deaths occur

as a result of smoke inhalation, it is typically accepted that the majority of these

deaths could be avoided if the installation of smoke detectors in houses was

mandatory. As part of the ongoing research into smoke detectors, it will be useful to

model the behaviour of detectors in realistic fires.

In the study into the effects of fire in the past, most tests that have involved realistic

fires have been conducted in single, well ventilated rooms which will not necessarily

replicate the behaviour or life hazards that would occur in a typical under ventilated,

multi-enclosure building or recreate the effects of interconnected spaces, corridors, or

consider the influence that any heating systems within the building will have on a

smoke detection system. While some fire studies have been performed in actual

houses, the fuel for such fires have not necessarily been representative and the data

collected has not always been extensive.

As part of ongoing research into the hazard assessment of domestic fires, the Building

Research Establishment (BRE) conducted a number of test fires within an actual

house within its test facility at Cardington, England. These tests considered the effects

of fires in upholstered furniture in a two-storey residence under vitiated conditions.

The results of these tests formed the basis for this study.

There are numerous advantages in comparing the outcomes of actual fires with

predicted results. These include providing some level of validation to the many

different computational methods that are available for predicting the effects of such

events. While there are a variety of published theories for modelling the behaviour of

smoke detectors, ranging from the extremely crude to the computationally complex,

different methods of prediction can produce very different outcomes. The more

complicated methods do not necessarily provide more accurate predictions.

1

Page 11: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

1.2 Objectives of Study

The objectives of this study are as follows:

1. Create an effective analysis model for the test house. Emphasis will be placed

on temperature and optical density, which is necessary for modelling the

behaviour of smoke detectors.

2. Investigate the effects of the physical features of the house. This will include

the consequences of modelling only a portion of the house, and the

significance of various obstructions to the flow of smoke.

3. Compare the predicted with the actual test behaviour.

4. Give recommendations as to parameters and methods of prediction for the

behaviour of smoke detectors for use within culTent analysis software.

1.3 Behaviour of Smoke Detectors

The performance of smoke detectors is dependent on the behaviour of smoke, and

smoke is difficult to model. Fires can either be smouldering or flaming depending on

the fuels and ventilation involved. The velocity and temperature of smoke both tend to

reduce with distance as the smoke migrates from the fire source. Smoke particles will

coagulate with travel which will effect the size distribution and some particles will be

deposited on smfaces en route, which will also alter the properties of the smoke. Some

studies into the behaviour of smoke have assumed that the particles are spherical in

shape whereas they are typically angular, which will alter optical properties of the

smoke, as does the smoke's colour. Furthermore, at some stage during a compartment

fire a window can break which will increase the level of ventilation into the

compartment, which will immediately affect the properties of the smoke. Every aspect

of this elTatic behaviour will have an influence on the performance of smoke

detectors.

There are commonly two different types of smoke detectors in domestic use. The

chamber inside an ionisation type of detector consists of two electrodes in which an

electric field is maintained by applying a voltage between the electrodes. A

radioactive source produces ionisation radiation. The ions produced are driven by the

applied electric field to the electrodes. This results in a small culTent flow between the

2

Page 12: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

electrodes, which can be measured by an electrometer. If aerosol particles enter the

chamber, ions attach to the pmiicles. Because the electrical mobility of the particle~ '

will be less than ions, the resulting reduction in cunent flow will be detected by the

electrometer and thus the alarm will be activated.

The functions of optical types of detectors are dependent on the properties of light

scatter from the smoke particles that migrate within the detector's chamber. Light

scatter is dependant on the particle's size, surface conditions and colour, and the light

source is a typically a light emitting diode (LED).

Numerous models exist for predicting the behaviour of smoke detectors, and more

complex models are under development. For the simplest method, refened to as the

temperature correlation method, the detector is assumed to activate when the gas

temperature that sunounds the detector achieves a certain activation temperature Tact

above ambient conditions. In another slightly more complex method, refened as the

pseudo-heat detector method, the response time index (RTI) is used as a measure of

sensitivity of the detection component

An important aspect of the behaviour of smoke detectors is the relative ease or

otherwise that smoke will have in entering the detector's chamber in order to be

detected. The characteristic length L, which has to be derived for a particular design of

detector as described by Bukowski et al., quantifies this transport delay.

1.4 Cardington Tests

The test house was a fairly standard two storey, three bedroom detached house of

typical 1970's design and construction as described by Spearpoint and Purser et al. All

of the test fires occuned in single lounge chairs within the fire room, which was a

lounge on the ground floor. In some cases additional furnishings were provided within

the fire room to further create realistic domestic fire scenarios.

The motivation for the tests was to examine the relationship between fuel load,

ventilation, detector activation and tenability. To monitor the progress of these tests,

3

Page 13: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

the house was fitted out with instruments to measure temperatures, gas concentrations,

heat flux, optical density, and for some tests video cameras were also installed. A

weighbridge was installed within the fire room to quantify the mass loss history for

the fire event. A number of domestic and commercial smoke detectors were also

placed at various locations around the house, and their activation times were logged.

A total of ten fire tests were performed within the house during this particular series

of tests.

Steps were taken to create different types of fires in the house assuming winter

occupancy. External doors and widows were closed to create vitiated conditions, and

several radiators were in operation before the test commenced so as to generate

airflow currents throughout the house. The internal door between the fire room and

the rest of the house varied between fully open to closed for different tests to alter the

level of ventilation available into the fire room.

There were significant variations in the smoke detector activation times for the

different types of fires. For flaming fires, in general the ionisation detectors activated

before the optical detectors. For smoulde1ing fires the reverse was true, although the

ionisation detectors did not activate at all. The results of these tests are available on a

CD-ROM database.

1.5 Fire Modelling Software

A fairly recent development in computer analysis is field modelling, which divides the

physical analysis space into a large number of prismatic cells. This is similar in

concept to the better-known zone modelling which divides a compartment into a small

number of distinct layers, and mass and energy balance are enforced within each

layer, while other models replicate other physical processes of gas flow. The gas

velocity, temperature and other prope1ties are assumed to be uniform within each cell

but are all functions of time. Likewise for field modelling, equations of conservation

of mass, momentum, energy and species are solved for each time step. The accuracy

of field models is dependant on the number of cells that the computational space has

been divided into, and so is the computational time for each fire scenario.

4

Page 14: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

The National Institute of Standards and Technology (NIST) has developed the

software package Fire Dynamics Simulator (FDS) that will simulate the mixing and

transport of the products of combustion by modelling fire dtiven fluid flow. The

ongoing development of Computational Fluid Dynamics (CFD) allows the modelling

of fires in complex geometties incorporating a variety of physical phenomena. One

such phenomenon is Large Eddy Simulation (LES), which is a simulation of the

turbulent mixing of the gaseous fuels and combustion products within the local

environment immediately surrounding the fire. The significance of LES is that it

determines the burning rate in most fires and controls the spread of smoke and hot

gases. However, it is extremely difficult to model, and the equation solving algotithms

of field models can suppress the effects of LES.

In these analyses, FDS was set to perform LES rather than the alternative Direct

Numerical Simulation (DNS), the latter being more suited to small scale combustion

experiments, not to multi-room enclosures because of the computational resources this

type of analysis requires.

Another useful feature of the FDS software package is SMOKEVIEW, which is a

software application that will provide a visual representation of the house being

modelled. The user can upload the house's geometry using SMOKEVIEW to check it

for correctness, and also upload various items of output such as temperature and

velocity to view this data.

1.6 Scope of Study

In this study of the behaviour of smoke detectors, two fire tests from the Cardington

house are chosen, and with the help of the analysis package FDS version 2 (which is

still under development), the temperatures, air velocity and optical density are

predicted. With this information the activation times for the domestic smoke detectors

within the house are predicted by three different methods, and are then compared with

the actual activation times that resulted during the fire tests.

5

Page 15: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

This study does not consider the commercial detectors, or the gas concentrations and

tenability limits within the house.

1. 7 Outline of Report

Chapter 2 justifies the analysis methods that were used in this study by refening to

previous research that covered similar ground. It also gives descriptions of the various

parameters that form the conclusions for this study, and gives ranges for typical values

for these parameters. Likely future developments in the modelling of fire and smoke

detector behaviour are also discussed.

Chapter 3 gives descriptions of the type of occupancy and the uses of the various

rooms within the test house. The two domestic type test fires (referred to as CDT17

and CDT20) that this study is based on are defined, and the relevant test data that was

gathered from these tests is described, as well as the instmmentation that was installed

inside the house to collect this data.

Chapter 4 discusses the process of modelling the features within the house, including

some of the difficulties that had to be overcome. The methods for both deriving and

correcting the heat release rate (HRR) curves for the test fires are given. The

modelling that was necessary to establish the air currents that were in place inside the

house because of the heating system before the tests commenced is also discussed, as

are some of the more interesting outcomes that were found while developing the

house domain geometry

Chapter 5 presents graphs of some of the more significant comparisons for

temperature, optical density, and makes some comparisons between different grid

sizes that were used during the analyses. Also presented are bar graphs that compare

the actual and predicted smoke detector activation times within each room for both

types of detector, for both fires, and for all three prediction methods. It also makes

some observations about the trends of the three prediction methods.

The significant conclusions from the previous chapter are emphasized in Chapter 6,

and recommendations for further research are also presented.

6

Page 16: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Plans of the test house, including dimensions, locations of measuring devices and

ratings for radiators are given in Appendix A. Diagrams and temperature curves for

the varying types of balustrades that were investigated are given in Appendix B.

Appendix C presents the family of curves for HRR, temperature and optical density

for the lOOmm grid analysis for test CDT17. Appendix D presents the same for test

CDT20, and Appendix E presents curves that compare the predictions for HRR and

temperatures between the 75mm and lOOmm grid size simulations for test CDT17.

7

Page 17: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Chapter 2 PREVIOUS RESEARCH

2.1 Introduction

There are numerous methods to emulate both the fire conditions within the house and

the behaviour of the smoke detectors. This chapter describes the modelling parameters

and methods of analysis that were utilized in this study.

This chapter justifies the methods of analysis by describing previous work involving

multi-compartment modelling, and the use of the fire simulation application FDS. It

also defines the various methods that were used to model the behaviour of the smoke

detectors, gives desc1iptions for the various parameters that this study was based on,

and gives a range of magnitudes of these parameters which were dedved from

previous research. There is also a general description of probable future developments

in fire and smoke detector modelling.

In later chapters, the results of the above mentioned methods are given with

recommendations as to the magnitudes of the parameters that most reasonably

replicate the results of the actual test fires that were considered in this study.

2.2 Validation of FDS

Fdday et al discusses simulations of a series of seven full-scale fire tests that were

performed in an enclosure that was approximately 18m x 12m x 6m high that had

little leakage. Instrumentation included in the test apparatus included thermocouples,

gas analysers, flow probes, optical density meters and heat flux meters. The fires that

were simulated were either propylene or heptane, were either a steady state or t2

growth, and ranged in size from 500 kW to 2 MW. Maximum temperatures ranged

from 115 oc to 370 °C. As an investigation into the effect of varying the grid sizes,

for vatious tests these ranged from 75mm to 600mm, and it was concluded that

reducing the grid sizes does not necessarily improve predictions of temperature. It was

also concluded that FDS is capable of providing accurate results for the scenados that

were tested.

8

Page 18: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

2.3 Multi-Compartment Modelling

Continuing on from the previous section on FDS, Cleary et al (2001) describes the

modelling of actual tests using FDS in a three-room suite and comparing predicted

and actual results. The enclosure that was tested had a total size of approximately 26m

x 15.5m x 2.9m high, had a HVAC system in operation, and the internal doors

between the rooms were fully open throughout the test. To model the suite for the

FDS analysis the entire enclosure was divided into grids which had a size of 150mm x

75mm x 27mm high, and the resulting smoke concentrations were converted into

extinction (related to optical density). The source of the fire was a flaming

polyurethane mat, which represented a medium t2 growth fire that peaked at

approximately 200 seconds. In the examination of the results there is some discussion

about some apparent enors in the predicted temperatures, and it is postulated that

these enors are due to the coarse grid that was chosen. It was concluded that FDS was

capable of emulating the environmental conditions that a detector may experience

dming an actual fire. More particularly that FDS was able to predict the transportation

of smoke, heat and gas species as is necessary to predict detector performance.

Collier reported on a series test fires within a typical New Zealand house. He

describes a number of fire tests in a typical three bedroom single storey dwelling with

a floor area of 69m2 to determine the smoke and gas movement, and temperatures

within the house. Some of these tests involved burning items of furniture causing both

flashover and non-flashover fires.

Instrumentation was installed within the house to measure air temperatures, smoke

spread, gas species' concentrations, heat radiation, and a weigh bridge was installed to

assess the mass loss history, although the results were compared with predictions

made with a zone model rather than FDS. The house was also fitted with domestic

smoke detectors. In one test, the source of the fire was a waste paper bin, the fire then

spread to a nearby curtain, and then involved a polyurethane foam rubber filled chair,

generating a fast t2 growth fire (as shown in a later chapter in Figure 5-19). All of the

house's internal doors were open, as were the external windows to the fire room.

There is no mention of a heating system within the house. It was concluded that the

activation times for smoke detectors could be predicted by determining when the gas

9

Page 19: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

temperatures in the smoke layer around the detector raises to approximately 2-4 oc above ambient, as long as smoke is present.

2.4 Modelling of Smoke Detector Behaviour

A common problem for designers is the uncettainty as to the fire's type and location,

as different types of detectors are more suited to different types of fires. Qualey et al.

reports the generally accepted view that ionisation detectors are more responsive to

invisible particles typically produced by flaming fires, whereas optical detectors are

more responsive to larger particles typically produced by smouldering fires. He also

states that the position of the detector in terms of ease of smoke entry into the sensor

chamber will have an impact on its behaviour.

Most domestic detectors operate under a principle where smoke has to flow into its

sensor chamber by some natural means, but there is often a delay in achieving this.

The sensing regions are enclosed for reasons of reducing the velocity normal to the

ion flow in ionisation detectors, to prevent the ingress of insects and to prevent

damage to the sensors. The temperature correlation method discussed below does not

take into consideration the difficulties that could exist with this time delay. The

pseudo-heat detector and Heskestad' s methods are an improvement in that they have

a level of dependence on velocity, but the time lag is not exclusively a function of

velocity as Cleary et al (2000) reports. His comments will be discussed later.

These difficulties aside, the prediction models considered in this study are discussed

below. Each model will be applied to the prediction of both ionisation and optical

detectors.

2.4.1 Temperature Correlations

The simplest method for predicting the behaviour of smoke detectors is to assume that

the detector will activate when the gas temperature around the detector rises to a

temperature of Tact above ambient. This method is more suited to higher energy fires,

and is not considered valid for all types of fuel.

10

Page 20: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Typical values for Tact range from 2- 4°C as reported by Collier (as discussed in

section 2.3 of this report) up to 13°C and even 20°C as discussed by Bukowski et al.

Notably, Peacock et al state that the zone modelling software application FAST has a

default value of 13 °C.

2.4.2 Pseudo-Heat Detector Method

While it is not a common prediction method for smoke detectors, it is feasible to use a

variation on the temperature correlation method to model smoke detectors as if they

are heat detectors. Schifihiti et al (1995) repmts the method concerned:

(2-1)

where Td = temperature of detector

t = time

u = gas velocity

Tg = temperature of gas

RTI = response time index

The response time index (RTI) is a measure of the sensitivity of the detector, and is

typically assumed to be negligible for smoke detectors.

The detector is assumed to activate when the temperature of the detector Td increases

from ambient by an amount Tact. Various values were given in the previous section

for the activation temperature Tact , although the use of these values is not necessarily

consistent with this particular prediction method.

2.4.3 Heskestad's Method

The activation time lag due to entry resistance has already been discussed above. A

well-reported method for allowing for these delays was proposed by Heskestad. In

general, the response time of a detector can be expressed as:

11

Page 21: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

JDu; 1 (D D ) ---;;;-=-;. uo- ui

where Dui = optical density inside detector

t = time

r = time constant

Duo = optical density outside detector

S b . . . L d . JDII. JD,, u stltutmg m T =- an assurnmg --' = --0

u' & Jt

~w =~(Duo -Dui)

where U

L

Rearranging:

= gas velocity around detector

= detector characteristic length

Published values for L differ markedly as shown in Table 2-1:

Researcher Ionisation (m) Optical (m)

Bukowski et al 1 - 2 1- 2

Schifihiti (2001) 1.8 - 9.5 5.3 - 13.0

Bjorkman et al 3.7 6.8

Table 2-1. Table of Values for Effective Length

(2-2)

Values for L are not widely published, and are a function of the design of the detector.

The aerodynamic properties of early detectors were extremely poor with relatively

high entry resistance. In an addendum to Bjorkman et al's paper, a description is given

12

Page 22: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

as to tests conducted in wind tunnels with the objective of deriving values for Lin the

late 1970's. Difficulties were faced because as smoke ages its properties would

change, and values found from the tests were never published.

Because of the historical modelling difficulties in estimating an optical density, a

proposal was made to replace the optical density terms in Equation 2-2 with

temperature rise and a detector material number (DMR). DMR was a function of the

fuel, combustion conditions and sensor design. However, as modern zone and CFD

model easily deal with soot, Bukowski et al makes the recommendation that

Heskestad's model should be revisited.

Cleary et al. (2000) reports that the effective length is acceptable for high velocities,

but a single parameter is not sufficient to model the behaviour over a full range of

operating conditions, especially with weak plumes at the beginning of a fire, which is

the time when a smoke detector would be expected to activate. A further alternative

method is proposed which is based around two parameters; a dwell time and a

characteristic mixing time, which are both based on the physical description of a

generic detector head.

Research into these issues continues, and no doubt there are several other variations

on Heskestad's model. But as this method is widely refened to, it is this method that

is considered in this study.

To predict the optical density for use in Equation 2-2, some input is required into the

fire model as to smoke yield Ys . Tewarson gives values for flexible polyurethane

foams between 0.13 to 0.23 kg/kg, although these values do not necessarily relate to

combustion modified foam, which was the padding to the chairs in the Cardington

tests. For the computer modelling in this study a nominal value of 0.10 kg/kg was

used, although it was later concluded that this value was too high.

2.4.4 Future Developments

As smoke ages, its properties can change markedly. Its temperature and velocity will

both drop, and it has been demonstrated that both of these behaviours can be

13

Page 23: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

adequately modelled. But with age, particles can also coagulate, change colour and

shape, particles can deposit on enclosure surfaces, and the level of ventilation into a

space can change very quickly which can alter the smoke's properties once again.

These latter behaviours will affect the response of smoke detectors, but no attempt has

been made to model any of them in any of the models described thus far.

The activation of ionisation detectors is caused by a decrease in the electric current in

its sensing chamber due to the blending of smoke and ions. An ionisation detector's

response is approximately proportional to the smoke particle's diameter, and as

Snegirev et al describes, if coagulation is not modelled then the response of ionisation

detectors will tend to be overestimated. An optical detector's activatiol). is based on

the intensity of light scattered by the smoke particles. As the light scattering

coefficient decreases with coagulation, if its coagulation is not modelled then the

response of optical detectors will tend to be underestimated. Snegirev et al presents

models that allow for coagulation.

However, combining coagulation into the models described in the previous sections in

some way will not adequately imitate the behaviour of smoke particles. Schifihiti

(2001) comments that while researchers often report optical density as obscuration

(although obscuration would more accurately be called attenuation since light may be

absorbed, reflected or refracted by the smoke), while such values are useful for

assessing visibility, neither ionisation or optical detectors operate under a principle of

light attenuation. Furthermore, detectors may use complex response algorithms, which

are generally not made known.

The combination of coagulation into smoke detector models is definitely a

progression, and such developments into detector modelling need to continue. Models

should also be developed for other behaviours such as the change of smoke particle

size and shape. Furthermore, Newman describes a model for ionisation detectors,

which is based on the sensitivity to an electrical charge carried by some aerosols.

Schifiliti (2001) also commented that developers of fire and smoke detector models

should work together so that models will evolve together.

14

Page 24: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

2.5 Modelling of Fire Behaviour

The development of the HRR history curve is dependant on the effective heat of

combustion Mi eff , which is a measure of how much energy is released when a unit

mass of material is combusted. The distinction must be made between the complete

heat of combustion when all of the fuel is consumed, and Mi eff when some residue

remains. It is generally assumed that Mieff will be constant throughout the fire, which

is typically not the case.

Previous research performed at the University of Canterbury by Girgis involved the

combustion of lounge chairs in an ISO room that measured 3.6m x 2.4m x 2.4m high

with the only ventilation being a standard width doorway. From his results it can be

derived that the average for Mieff varied between approximately 30-38 MJ/kg.

15

Page 25: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Chapter 3 FULL SCALE FIRE TESTS

3.1 Introduction

Although a series of ten similar tests emulating domestic fires were performed within

the Cardington house, this study is based on the results of only two. This chapter

provides descriptions of these two tests as well as the configuration of the test house.

Initially a description of the house's occupancy is given as well as the locations and

uses of the various rooms. Distinguishing features about the house are discussed, and

descriptions are given of the test fires, the relevant data collected from these tests, and

the instrumentation that was installed within the house to measure this data.

The test fires that were conducted within the house were modelled according to the

methods that were described in the previous chapter, and the results of these analyses

will be given in later chapters.

3.2 Description of House

The same house was used for all of the fire tests considered in this study. This test

house was one of a number of test structures inside the BRE test facility at

Cardington. It was a two storey, three-bedroom detached house of typical 1970's U.K.

design and construction. There was a lounge, entry hall, kitchen and dining room on

the ground floor, a bathroom and three bedrooms on the top floor as shown in Figure

3-1. :Dimensional plans are given in Appendix A. The kitchen, dining room, bathroom

and two bedrooms were sealed off from the rest of the house, and therefore from the

flow of smoke in the particular tests considered. These areas are shown shaded in

Figure 3-1. Most of the sealed off rooms were used to house measuring and recording

equipment for the tests. The internal doors to the lounge and bedroom 2 are fully open

750rnm, while the external doors and windows were closed to create vitiated fire

conditions, and the windows to the fire room were of wired glass to stop them from

breaking out. Lighting throughout the house was provided by standard incandescent

domestic light bulbs.

16

Page 26: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Because a heating system within the house can affect the behaviour of smoke

detectors, a number of radiators were located around the house to replicate winter

occupancy. Three were located upstairs; one in each bedroom. On the ground floor

there was one in the entry hall and one in the lounge (fire room) as shown in

Figure 3-1, and identified in more detail in Appendix A. These radiators were started

before ignition of the test fire and left for some time to create airflow currents

throughout the house. The radiator in the lounge was removed from the space shortly

before ignition to avoid it from being damaged by the chair-fire, but all of the other

radiators remained on for the duration of the test. The ambient temperatures that were

created varied around the house and tended to be higher within the upper floor, as

shown in Figure 4-5 in a later chapter. The ratings for the radiators varied between 1 -

2 kW, and are specifically given in Appendix A.

17

Page 27: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

a:::o Landing @fs

CD®

CD 0_16 a@®

Bedroom 2

Lounge

CD® 0 0@#1

Figure 3-1. Floor Plans for Test House

3.3 Instrumentation/Data Collection

While the house had numerous items of measuring equipment to monitor the progress

of the fire, only a portion of this instrumentation is pertinent to the tests that are

studied. Four pairs of ionisation and optical smoke detectors were located within the

house, one pair in the lounge, entry hall, landing and bedroom 2 as shown in

18

Page 28: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Figure 3-1. Optical density meters were located in the lounge, in the entry hall by the

lounge door on the landing, and within bedroom 2, all at 1.5m above the floor. There

were several thermocouple trees within the house, which located thermocouples at

varying heights. Tree #1 was near the middle of the lounge and is designated as #1 in

Figure 3-1, tree #2 was also in the lounge but nearer to the door to the hall, tree #3

was near the same door but within the entry hall, tree #4 was on the stairs, tree #5 was

on the landing and #6 was located near the middle of bedroom 2. There was also a

weighbridge in the lounge, which allowed the mass of the chair to be measured

continuously throughout the fire tests. From this instrumentation the temperatures at

various heights could be measured, as well as optical density, mass loss history, and

the activation times for the various detectors. This information is available on a

CD-ROM database available from BRE.

3.4 Description of Tests

Two fires were considered in this study, referred to by the BRE researchers as CDT17

and CDT20. Both tests were performed on single chairs with timber frames,

upholstered with combustion modified high-resilient foam (CMHR) with a fire

retardant (FR) cotton cover. Both chairs weighed 23.8 kg including 4.7 kg of foam.

The fires took place on a weighbridge in the lounge on the ground floor.

The test fires were started by an electrical igniter and match head, which lit a small

wooden cdb on the seat of the chairs. Both chairs developed flaming fires, and after

approximately 720 seconds both fires had self-extinguished without completely

consuming the chair that had been ignited.

19

Page 29: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Lounge

Hall

Landing

Bedroom

• Ionisation

D Optical

0 60 120 180 240 300 360 420 480

UncotTected tirre after ignition (sees)

Figure 3-2. Uncorrected Detector Activation Times, Test CDT17

Lounge

Hall

Landing

Bedroom

• Ionisation

D Optical

0 60 120 180 240 300 360 420 480

UncotTected tirre after ignition (sees)

Figure 3-3. Uncorrected Detector Activation Times, Test CDT20

The activation times for both types of smoke detectors for tests CDT17 and CDT20

are presented in Figures 3-2 and 3-3 respectively. The activation times are described

as uncolTected as desclibed late in Section 4.7. While as expected the detectors in the

lounge activated first, and within bedroom 2last. But for CDT 17 the detectors on top

20

Page 30: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

of the landing activated before the ones in the entry hall, while for CDT20 the reverse

was true. In each room the ionisation detector responded before the optical.

21

Page 31: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Chapter 4 COMPUTER MODELLING

4.1 Introduction

Having defined the test house and the methods for modelling and analyzing the data

that was collected, this chapter goes on to describe the process of modelling the house

and the two test fires that were studied.

This chapter begins with a discussion on emulating the features within the house, and

goes on to describe the derivation of the heat release curves for the test fires. Some of

the difficulties that were faced are also discussed, and schematic diagrams of the

house are given. It also discusses some corrections that were necessary to the test data

that was collected. The method for establishing the airflows that were present before

the tests began is desctibed, as is the method for calculating the amount of soot that

was generated from the fire. Finally, some of the more interesting findings while

developing the house model are given.

The results of this modelling process, are analysed by the methods that were defined in

an earlier chapter, and the results of these analyses are given in the next chapter.

4.2 Configuration of House

To analyse the house in FDS, an accurate representative model must be constructed.

While this house has been described in several documents, there are a number of

discrepancies in the information given as to the sizes of the rooms and locations of

instrumentation. The dimensions and locations that were adopted in this study are

given in Appendix A. From the schematic drawings of the house model shown in

Figure 4-1 and 4-2 it can be seen that only a part of the house was modelled.

Figure 4-1 shows the entry hall on the ground floor and landing on the top floor, and

the open doorway that leads to bedroom 2. The kitchen/dining room on the left hand

side was sealed off from the path of the smoke, as was bedroom 3 on the right hand

side of the top floor. Figure 4-2 shows most of the smoke path from the lounge on the

right hand side of the ground floor, through the open door into the entry hall, up the

stairs to the landing above, and through a doorway again and into bedroom 2.

22

Page 32: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Some concessions were necessary to accommodate a working model. As FDS requires

some form of ventilation into the analysis space to prevent pressure build-up, a vent

was positioned at the location of the front door, and is one grid in width as shown in

Figure 4-2. In addition to this the chair was assumed to remain at a constant height

throughout the fire.

FDS allows thermal boundary conditions to be set for surfaces. For the simulations the

internal walls were assumed to be Gib board, and the external walls and top floor

ceiling are adiabatic (i.e. they will not permit heat loss).

To analyse the simulation, measuring points were located at various locations around

the house model to collect the following data:

• Temperature at the locations which represent thermocouple trees #1 (lounge),

#3 (entry hall), #4 (stairs), #5 (landing) and #6 (bedroom 2).

• Visibility at 1.5m above the floor in the lounge, entry hall, landing and

bedroom 2 to compare the results of the simulation with the actual test data.

• Temperature, visibility and two perpendicular velocities in the global u and v

directions at the locations of all eight smoke detectors (four ionisation and four

optical).

4.3 Grid Generation

FDS calculates within a rectilinear grid within a rectangular domain defined by the

user. The obstructions and ventilation must conform to the defined grid. In developing

the model for this study a lOOmm grid size was adopted initially. While this size

suited the house in many respects, it created difficulties in the following areas:

• Internal doors are 750mm wide, which cannot be modelled with a lOOmm

grid.

• Ventilation as mentioned in the previous section had to be lOOmm wide.

• Balustrades also had to be the same width.

23

Page 33: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

• There were difficulties with modelling the sloping ceiling over the stairs as

will be discussed later.

As the chair was positioned at an angle to the grid layout, it had to be positioned over

an anay of cells as can be seen in the lounge of Figure 4-2. The chair was assumed to

have a size of 800mm x 800mrn, and the collection of grids that make up the chair

have a combined area equal to this.

Figure 4-1. SMOKEVIEW Image of House, View From South Wall

24

Page 34: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Bedroom 3

Entry Hall

Figure 4-2. SMOKEVIEW Image of House, View From East Wall

Later in the study, in order to check the sensitivity of the choice of grid size, another

simulation was developed which had a glid size of 75mm. While this glid size

allowed nanower ventilation and balustrades, and allowed the 750mm doorways to be

modelled at their actual width, it created the following difficulties:

• Wall thickness was 75mm instead of the actual lOOmm.

• Floor thickness was 225mm instead of the actual 200mm.

The difficulties with the sloping ceiling and balustrades remained, as will be discussed

in the next section.

25

Page 35: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

4.4 Obstructions

As mentioned above, it was not possible to model a 750mm internal doorway with a

lOOmm grid. To assess the sensitivity over the choice of doorway size, two successive

simulations were performed with 700mm and 800mm doorway sizes. When analyzing

the results from the two simulations by comparing the temperatures in all four rooms,

there was barely a discemable difference between the two door sizes. Subsequent to

this, the study was based on the 800mm door width.

Figure 4-3. Details of Balustrade to Stairs

In the test house the balustrades to the stairs were on an angle that matched the slope

of the stairs. As this was also difficult to model within the allocated grid structure,

several attempts were made to emulate these balustrades as are presented in

Appendix B. The option chosen is shown in Figure 4-3. This was chosen because it

most closely emulates the temperatures in the stair thermocouple tree (tree #4).

A further difficulty arose because there was a sloped ceiling above a portion of the

stairs. Because of the grid structure this slope had to be modelled as a series of steps,

which can be seen in Figure 4-1. This creates difficulties for the airflow in that as the

26

Page 36: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

hot gases from the fire move up the stairwell, eddies will be created in these steps in

the ceiling which will change the flow pattern near this feature.

The effects of gas flow around light bulbs, smoke detectors (both domestic and

commercial) or the instrumentation within the house have not been considered in this

study.

4.5 Ambient Temperatures

The varying ambient temperatures at valious locations around the house can have an

effect on the activation times of the detectors, and so can the heating system within

the house. There were five radiators in the house, three upstairs and two downstairs.

However, two radiators were located in bedrooms 1 and 3 which had their doors

closed for the duration of the tests. In light of all of this, two extra investigations took

place:

• How long do the radiators have to be left on to create steady ambient

temperatures within the house?

• Do the radiators in bedrooms 1 and 3 have to be considered in the simulations

given that they were behind closed doors?

A simulation with three radiators was run for some time to answer the first question,

and the results are shown in Figure 4-4. This graph presents the temperature plots for

a number of thermocouple trees as indicated in the key. It also shows that the

simulations have to be run for at least 600 seconds for steady conditions to be

achieved.

To investigate whether the extra radiators in bedrooms 1 and 3 had any significant

impact on ambient temperatures, two consecutive simulations were petformed, one

with three radiators and the other with five. For the five-radiator simulation there were

wall openings near the door locations to bedrooms 1 and 3 similar to those at the front

door on the ground floor. Figure 4-5 presents the temperatures at valious heights for

different thermocouple trees located in valious rooms, and compares the ambient

27

Page 37: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

temperatures for both simulations at 600 seconds, with little difference between the

two.

With this information it was decided that with future simulations the radiators would

be left for an incipient phase of 600 seconds before the chair fire began, and that only

three radiators would be modelled in the house. The radiator in the lounge would stop

at the same time that the chair fire started, and all of the other radiators would remain

in operation for the duration of the simulation.

30 .. • • •T#1

29

28 --T#3

27

E Q)

26 --T#4 ... :::1

N 25 ----T#4 ~ E 24 Q)

1-

23 --T#5

22

-·-·-T#6 21

20 0 120 240 360 480 600 720 840 960 1080

Tme (sees)

Figure 4-4. Generation of Ambient Temperatures

28

Page 38: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

30

29

28

27 0 ~ (j)

26 .... ii 25 ... (j) 0.. E 24 (j) ....

23

22

21

20

Lounge Lounge Hall Haa Stalts Stairs 2.34m 1.69m 2.34m 1.69m 2.88m 2.25m

Figure 4-5. Comparisons of Ambient Temperatures

• CDT17

• 3 Radiators

o 5 Radiators

Stalts Landing Landing Bedrm 2 Bedrm 2 1.60m 2.34m 1.69m 2.36m 1.71m

Figure 4-5 also compares the predicted ambient temperatures with those for test

CDT17. This shows that the predicted temperatures are overestimated in the lounge,

and tend to switch from overestimated to underestimated in the direction that gases

would migrate in a fire, i.e. from the lounge up to bedroom 2. The predicted

temperatures varied from approximately 24°C to 29°C.

During later stages of the study it was decided to model soot production, which is

related to HRR. While FDS is able to model soot, it seemed unable to discern between

the various sources of the total HRR. In other words, the radiators produced soot. To

circumvent this problem it was decided that, for simulations when soot behaviour was

required, there would be no radiators in the house, and the ambient temperatures

throughout the house would be set at 27°C.

4.6 Derivation of HRR Curves

FDS is able to model non-steady fire behaviour by allowing the inclusion of time­

dependant boundary conditions. The user can input fractions of heat release rate at

specific times, which FDS then combines with the input value for heat release rate per

unit area (HRRPUA) to emulate the required fire behaviour.

29

Page 39: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

The actual HRR curve was not measured during the actual tests because of the

difficulties in doing so. As this information is fundamental to the modelling of the

fire, the HRR was derived from the mass loss history. This history from test CDT17 is

shown in Figure 4-6. The values for the mass burning rate rh were then derived, as

shown on Figure 4-7 after being multiplied by the effective heat of combustion Mleff.

Figure 4-7 also shows the idealized trend of the HRR curve that was input into FDS.

Simulations were then run based on this data, and the resulting temperatures were

compared with those, which were measured during the actual fire test. The HRRPUA

was adjusted and the simulations rerun until a good match existed between the

magnitudes of the predicted and actual temperatures in the lounge as shown in Figure

4-10. Having derived a good match for temperatures, the corresponding HRR for the

actual test was deemed to have been found. Figure 4-7 compares the HRR curve from

the temperature matching simulation output with that derived from the mass loss

history (CDT 17) which both demonstrate a similar trend.

6.0

5.0

4.0 01 ~ rn rn 3.0 0

..J rn (I) Ill

:::i! 2.0

1.0

0.0 0 120 240 360 480 600 720

T1100 (sees)

Figure 4-6. Mass Loss History - Test CDT17

30

840

Page 40: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

1000

900

800

700

~ 600 c

500 a: a: :I: 400

300

200

100

0 0 120 240 360 480

Tllll9 (sees)

Figure 4-7. Derivation ofHRR Curves- Test CDT17

6.0

5.0

4.0 0) ~ -f/) f/) 3.0 0

...J f/) f/) (II

:E 2.0

1.0

0.0 0 120 240 360 480

T~rm (sees)

Figure 4-8. Mass Loss History - Test CDT20

31

600

-rom (x A. Haft)

••••••. k:lealised

--Sirulation Oulput

720 840

600 720 840

Page 41: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

1000

900 -COT2o (x .A Heft)

••••• : • k:leallsed 800

- Slrrulation Output 700

;: 600 c. a: 500 a: :X: 400

300

200

100

0 0 120 240 360 480 600 720

Tirre (sees)

Figure 4-9. Derivation of HRR Curves -Test CDT20

Figures 4-8 and 4-9 show the same plots for CDT20. Because of the rather erratic

mass loss curve, the family of curves for HRR does not match as well as the previous

test.

With this method the heat of combustion can only be determined after a suitable

match of temperatures has been attained. Karlsson et al. desctibe the relationship

between HRR (Q) and heat of combustion as:

Q = 1hM/eff ... (4-1)

where 1h = mass burning rate

This will derive the average effective heat of combustion. It was found that 11H eff

was approximately 30 MJ/kg for test CDT17 and 34 MJ/kg for test CDT20. These

values are consistent with the range of values of 30 - 38 MJ/kg that Girgis derived, as

discussed earlier.

32

840

Page 42: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Figures 4-11 and 4-12 compare the HRR of tests CDT17 and CDT20 respectively

with a medium t2 growth curve after a 160 and 150 second incipient phases for test

CDT17 and CDT20 respectively. Both tests show a good match for the medium t2

growth curves. While the first peak in HRR for both tests occurs about the same time

and has approximately the same magnitude, the second peak for CDT20 occurs

earlier, and has an approximately 60% higher magnitude, and the duration of the fire

is less compared to CDT17. While the two test fires have a lot of similarities, they had

quite different outcomes as to detector response, as will be discussed later.

500 --2.34m

450 ------ ·CDT1 --1.69m

400 ••••••• CQT1

350 --0.73m

~ 300 --·---·CDT1

~ :J

f1 250 8. E {!!.

200

150

100 ..........

50

0 0 120 240 360 480 600 720 840

Tum(secs)

Figure 4-10. Uncorrected Lounge Temperatures- Test CDT17

33

Page 43: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

1000

900

800

700

~ 600

500 a: 0: J:

400

300

200

100

0 ..

0 120 240

Figure 4-11. HRR Curve- Test CDT17

1000

900

800

700

600 ~ ~

500 a: a: J:

400

300

200

100

0 0 120 240

Figure 4-12. HRR Curve- Test CDT20

360 480 Tlrre (sees)

' . .. . . . . . . .

360 480 Trre (sees)

34

---COT17

•• • - • • • Medium f-l Fll'e Growth

600 720 840

-CDT20

·----- · Mediumf-l Fire Growth

600 720 840

Page 44: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

4.7 Correction of Time Error

Figure 4-10 presents the temperature plots in the lounge for test CDT17 at various

thermocouple heights, as indicated by the key. It should be noted that the trace for the

predicted temperatures are in advance of the test temperatures by a few seconds. As

an electric igniter lit a timber crib on the seat of the chair to start the fire, it could be

that there is some error between the recorded time for the start of the test and the

actual test start time. In light of this some corrections were made to the test times to

accommodate these differences.

Figure 4-13 compares the predicted and actual test temperature readings for test

CDT17 after a correction of -10 seconds was applied to the test time. Figure 4-14

considers CDT20 with a -15 second correction included. These plots show a closer

match between the two traces than the earlier plots. Note that this time correction was

also applied to the detector activation times given in Figures 3-2 and 3-3.

4.8 Optical Density

The soot density in the environment around the detector D110

is required by

Heskestad's method. This is quantified by the optical density, which is a value derived

by FDS after the input of a specific value for soot yield from combustion. As

discussed in Section 4.5, extra simulations that did not include radiators were

performed to assess the soot density throughout the house.

For this study a nominal value for the soot yield Ys of 0.10 kg/kg was assumed. From

this information, FDS calculates a distance that correlates with the visibility distance S

as:

S=C.K ... (4-2)

where C =constant

K = light extinction coefficient

35

Page 45: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

The constant C is related to the intensity of visibility of signs, and in FDS it has the

default value of 3. As Mulholland discusses, this distanceS is related to the optical

density as follows:

D110

= K /2.3 ... (4-3)

The sensitivity of detectors is commonly reported in terms of obscuration Obs. As

Schifihiti (2001) discusses, obscuration is related to optical density in the following

equations:

Percent obscuration per unit distance l:

Optical density per unit distance l:

D = _!Lao(!_) uo l I

0

where l = unit distance

I= intensity of light beam through smoke

I o = initial intensity of light beam

In Heskestad's method, the value of D110

found by FDS is equated to the optical

density inside the detector Dui after entry delays. Dui is then compared against the

preset activation density for the specific detector. In this study this activation density

was the reasonably high figure of 0.14m-1, as discussed by Mulholland for black

smoke. As Brozovsky et al. states, Underwriters Laboratories (UL) require smoke

detectors to respond within the range for optical density of 0.007 to 0.058m-1.

4.9 Development of the House Domain Geometry

During the development of the house's computational domain, the effects of several

different modelling functions of FDS and features of the house were investigated.

This section discusses the ramifications of these differences.

36

Page 46: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

The domain used to analyse the house was developed by initially creating a

representation of the lounge (fire room) only. This was later extended to include the

entire ground floor, and later the top floor was added. For the lounge computational

domain only, it was found that the location of the chair within the room affected the

HRR curve. The chair was located fairly close to the wall as shown in Figure 4-2, and

its closeness had an effect on the HRR curve. This is undoubtedly because the closer

the chair is to the wall the lesser volume of air can be entrained into the fire's plume.

Furthermore, as the volume of the entire computational domain increased, the amount

of ventilation into the analysis volume changed, which also affected the HRR curve.

What can be determined from this is that any model should emulate the location of the

fire as closely as possible, and that only modelling a single room in a multi-room

enclosure does not necessarily adequately emulate the effects of a fire, even within the

fire room.

There has already been some discussion earlier in this chapter about the difficulties of

accommodating the balustrades within the domain. As the balustrades have to fit

within the allocated grid layout, several different arrangements of balustrade elements

were considered. The balustrade layout finally chosen was the one that most closely

matched the temperature profile on the stairs that was attained during the actual fire

test, based on a model of the ground floor only without the function of radiators. The

results of this analysis are presented in Appendix B. This includes a comparison with

a simulation where no balustrade was included in the domain at all, which

demonstrates that the presence of balustrades cools temperatures down.

Also discussed earlier was the setting to disallow the creation of eddies within the

sloped ceiling above the staircase. Consecutive simulations revealed that not allowing

these eddies increases the temperatures within the upper floor by approximately 5°C.

Another feature of the house that had an effect on temperatures was the incorporation

of the internal walls as Gib board. This had the consequences of increasing the

temperatures in the fire room by approximately 20°C, and had a lesser effect on the

temperatures on the first floor.

37

Page 47: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Chapter 5 RESULTS AND DISCUSSION

5.1 Temperatures

Plots of predicted and actual test temperatures for tests CDT 17 and CDT20 were

shown earlier in Figures 4-13 and 4-14 respectively after the correction of the time

error as discussed earlier. These show a good match between predicted and actual

temperatures at heights of 2.34m and 1.69m above the floor for the both fire tests. A

lesser match was derived at a height of 0.73m, but a match at this lower height is of

lesser importance for modelling the behaviour of detectors at ceiling level. These

same plots are shown in Figures 5-1 and 5-2 at a larger scale over the initial 360

second time period, which is the time period in which most of the detectors in the

house had activated. Once again these plots show a reasonably good match at height

of 2.34m and 1.69m, with a lesser match at a height of 0.73m. A full family of curves

of temperature for all five thermocouple trees that were modelled is presented in

Appendix C for fire test CDT17 and Appendix D for test CDT20.

5.2 Grid Sizes

As stated earlier, most of this study was performed assuming a grid size of 100mm.

To ascertain the significance that the choice of grid size has on the results, one fire

test (CDT17) was also analysed with a grid size of 75mm. The match between the

plots of HRR is shown in Figure 5-3. Unfortunately, the 75mm grid simulation

overestimates the HRR. This is indicative of the fact that the input value for HRRPUA

was slightly overestimated rather than an error is the results of FDS. Nonetheless there

is a close match between the trends of the two plots.

Plots of temperatures in the lounge, entry hall and bedroom 2 are shown in

Figures 5-4 to 5-6 respectively. While the overestimation in HRRPUA makes itself

known at the height of 2.34m in Figure 5-4, this effect is much less obvious at the

lower two heights in this figure. Moreover, in Figures 5-5 and 5-6 there is little

difference between the results of the two grid sizes, particularly at the greater heights.

From these results, and considering the overestimation in HRRPUA, it can be

determined that there is little difference between the 75mm and lOOmm grid sizes in

38

Page 48: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

terms of the prediction of temperatures, which agrees with the findings of Friday et al.

as discussed earlier.

It should be noted that while there is little difference between the two grid sizes in

terms of temperature, there was a significant difference in computational resources. In

fact the calculation time for the 75mm grid model was four times longer than the

lOOmm grid for the same analysis volume.

A full family of curves of temperature for all five thermocouple trees that were

modelled with a 75mm gird size is presented in Appendix E for fire test CDT 17.

100 --FDS2.34m

·······COT17 80 --FDS1.69m

••••••. CQT17

E 60 --FDS0.73m e "' ·······COT17 ~ <I> 0.

E <I>

40 1-

20

Lounge

.·· ..... ~·

... .. r . .. t

,. .·

0~------~------~--------~-------r------~------~

0 60 120 180 Trre(secs)

Figure 5-l. Lounge Temperatures- CDT17

39

240 300 360

Page 49: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Lounge 100.----------.------------------~r-~~---.------~~~

--FDS2.34m

E ~

~ '-CI) a.

80

60

E 40 Cl)

1-

• • • •• • • ClJT2o

--FDS1.69m • • ••• • . ClJT2o

--FDS0.73m ••••••• ClJT20

.· .· .. · ,·

,J

. . ..... /

.. . ' . .

20 ::.-"-. :: . - .. - .... - ..... - •... -. - .. - ..... -.- ........ -.-. -. - . -. - . ······ ~ ... .·

.···" ·' .... •'

0~------~------~-------.------~------~------~ 0 60 120 180

lima (sees)

Figure 5-2. Lounge Temperatures- CDT20

800 ---75rrrn Grid

700

·- ·- • • · 100rrrnGrld 600

500 ;; e. 400 a: a: J:

300

200

100

0

0 120 240 360 480 Tirre (sees)

240

600

Figure 5-3. HRR Curves, Comparison of Grid Sizes - CDT17

40

300 360

720 840

Page 50: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Lounge 500

--2.34m-75nmGrld

..•... ·100nmGrld 400

--1.69m- 75nm Grid

0 ..••.. -100nmGrld L 300 ~. --0.73m-75nmGrld

~ ••••• ··100nmGrld ., 1§-200 ., 1-

100

0 0 120 240 360 480 600 720 840

lime (sees)

Figure 5-4. Lounge Temperatures, Comparison of Grid Sizes - CDT17

Entry Hall 300

--1.69 • 75mm Grid

·•· .... 10QmmGrid 250

--0.73m· 75mmGrid

...... -100mmGrid

~ 200

~ .a 150 ~ Q) Q.

E Q)

100 1-

50

0 0 120 240 360 480 600 720 840

Troo (sees)

Figure 5-S. Entry Hall Temperatures, Comparison of Grid Sizes - CDT17

41

Page 51: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Bedroom 2 300

--2.36m- 75mnGrld

•.•. --·100mnGrld 250

--0.75m· 75mnGrld

..... -·100mnGrld ~ 200 p CD ..... :::>

150 <U ..... CD c. E CD 100 1-

50

0 0 120 240 360 480 600 720 840

Trre (sees)

Figure 5-6. Bedroom 2 Temperatures, Comparison of Grid Sizes - CDT17

5.3 Optical Density

As discussed earlier, the simulations that attempted to model the production of smoke

did not include the house's radiators because of the difficulties associated with these

radiators producing their own smoke. The initial estimate for smoke yield was

nominally taken as 0.10 kg/kg, and the results of these simulations are presented in

Figures 5-7 and 5-8 within the lounge and bedroom 2 only for test CDT17, and

Figures 5-9 and 5-10 for test CDT20. As expected the rise in optical density in the

bedroom trails that in the lounge by about 120 seconds. For both tests, the trend of the

increase in optical density is well modelled. Unfortunately, the prediction of density is

overestimated in the first 300 seconds of each simulation, as these figures show. The

significance of this inaccuracy is that this is the time at which most of the smoke

detectors within the house had activated. A full family of curves of optical density for

all four rooms within the house is presented in Appendix C for fire test CDT17 and

Appendix D for test CDT20.

The inaccuracy in these predictions caused difficulties in applying Heskestad's

method, as will be discussed later in this chapter. As a means of attempting to draw

some useful conclusions about this particular prediction method, the results for optical

density that were derived from FDS were arbitrarily halved. The results of this

42

Page 52: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

factored reduction can be seen in Figures 5-11 to 5-14 for the same rooms and tests as

the unfactored results discussed above. These figures show that the trends in increase

of optical density does not match as well as previously, but the magnitudes of actual

and predicted optical density are more equal near the actual activation times. These

results were still used in an investigation into Heskestad' s method, as will be

discussed later.

Lounge 5.----------r----------------------r----------------------.

:§ ,....

.~ "' 0:: Q)

0 'iii .g c. 0

--FDS1.5m

....... rom 4 +---------'

3

2

0 60 120 180 240 300 Tirre (sees)

Figure 5-7. Lounge Optical Density- CDT17

43

360 420 480 540 600

Page 53: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Bedroom 2 5r---------~------------------------------------~--------.

--FDS1.5m

•••• •• .(l)T17 4+-------'

:€ ,.... ~ 3 :f;' (/) c: G> 0 (ij ,g 2 0. 0

o~--~--------~~~cr~~~---,----~----~--~--~ 0 60 120 160 240 300

lirre (sees)

Figure S-8. Bedroom 2 Optical Density - CDT17

Lounge

360 420 480 540 600

5.---~----.------------------.~--------~~--:-~-----. \,.,. .... )." \

~ ,....

.~ (/)

c: Q)

0 (ij

~ 0. 0

--FDS1.5m

• ...... CDf20 4+--------'

3

2

0 60 120 180 240 300 lime (sees)

Figure S-9. Lounge Optical Density- CDT20

44

360 420 480

" ' •· ~ . ' ~ \ .

' .... •'

540

..

600

Page 54: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Bedroom 2 5.-------~-------------------------------,--------~

--FDS1.5m

••••••. a:>T20 4+--------'

:§ ..... ;: 3 "" "' c (J)

0

(ij 2 ~ 0

0 60 120 180 240 300 360 lirre (sees)

Figure 5-10. Bedroom 2 Optical Density- CDT20

'

420

• • ' ' r ... ..... ,

480 540 600

Lounge 5r---------.-------------------------------------------~

:§ ..... ~

~ (/) c Ql

0 (ij .!.! c. 0 "0 ~ ~ 0

"' u.

--FDS1.5m

....... aJT17 4+-------'

3

2

0 60 120 180 240 300 lirre (sees)

360

Figure 5-11. Factored Lounge Optical Density- CDT17

45

420 480 540 600

Page 55: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Sr---------.---------------------------------·----------~ Bedroom 2

---FDS1.5m

·······COT17 4+-----_j

0 60 120 180 240 300 Trm(secs)

360

, •' ,

• , ... ~ ... ,

420

Figure 5-12. Factored Bedroom 2 Optical Density - CDT17

5

4 I ,.... ~

~ Ul

3 r:: <I> 0 (ij 0

E. 0 2 "0 ~ 0 0 ro u.

0

--FDS1.5m

·······C0120

60 120 180 240 300 Tlllll (sees)

360

Figure 5-13. Factored Lounge Optical Density - CDT20

46

420

480 540 600

480 540

Page 56: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Bedroom 2 5~------~------------------------------------~

--FDS1.5m

••••••. 0)1'20

4+-------'

0 60 120 180 240 300 TJOO (sees)

360 420

.. I ..

Figure 5-14. Factored Bedroom 2 Optical Density- CDT20

5.4 Modelling of Smoke Detector Behaviour

I . ,. ........ . ,- ..... I

I .

480 540 600

Three prediction methods were considered in this study as was discussed in Chapter 2.

The results for the predictions of activation times are compared with the actual

activation times for both fire tests.

5.4.1 Temperature Correlation

The results of the analysis of activation times for the ionisation detectors from test fire

CDT 17 are shown in Figure 5-15 for the temperature correlation method. The

ionisation and optical detectors were located in the lounge, entry hall, landing and

bedroom 2. Taldng the lounge as an example, if the activation temperature Tact is 4 °C,

then the predicted activation time is 64 seconds. If Tact is l3°C the prediction time is

129 seconds, and if 20°C then the time is 178 seconds. This is compared in

Figure 5-15 with the test activation time of 110 seconds. Considering all four

ionisation detectors, if Tact = 4 oc then there is a significant error in the lounge, a

lesser error in the entry hall, but a good match on the top floor. If Tact = 13 oc then

there is a reasonably good match for all detectors except the landing. Meanwhile the

Tact = 20°C option would appear to be unreasonably high for this detector.

47

Page 57: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

However, the situation is quite different for test CDT20 as shown in Figure 5-16. In

this case the same options as to activation temperatures are given, but the option of

Tact = 20°C goes from being too high in the previous test to not being high enough.

The predicted times for the optical detectors for test CDT1 7 is presented in Figure 5-

17. In this case, Tact = 20°C provides a good match in the lounge and entry hall, but

provides up to a 45% error on the upper floor of the house. Conversely, if Tact had the

significantly lower value of 10°C, then while there will be a reasonably good match

for the upper floor detectors, but errors of up to 30% in the lounge. But for test

CDT20 in Figure 5-18 the activation temperature of 20°C will underestimate the

activation times in every case.

From the results of this method, and more particularly from the results of test CDT20,

it will be hard to justify an activation temperature of less than 20°C. This value is

significantly higher than the 2-4°C range of values given by Collier, and the types of

fires cannot explain the significant difference between these two values. Figure 5-19

compares the HRR curve from Collier's fire with a fast t2 growth fire, whereas Figure

5-20 compares CDT20 with a medium t2 growth fire. From these two figures it can be

seen that both fires had a t2 growth, although while CDT20 was vitiated and

extinguished itself, sprinklers that were manually operated at approximately 260

seconds extinguished the Collier fire. The only other significant difference between

the two fires was the fact that CDT20 had airflow currents setup within the test house

before the fire started. This is presumed not to have occurred in the Collier test.

Collier did not specify the type of foam in the chair that was burnt.

48

Page 58: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Hall

296

Bedroom

0 60 120 180 240 300

Time after ignition (sees)

[J Tact= 4°C

[J Tact= 13 °C

[J Tact = 20°C

• CDT17

373

360 420 480

Figure 5-15. Temperature Correlation Method for Ionisation Detector - CDT17

Hall

Bedroom

0 60 120 180 240 300

Time after ignition (sees)

CTact=4°C

[J Tact= 13°C

[J Tact = 20°C

• CDT20

415

360 420 480

Figure 5-16. Temperature Correlation Method for Ionisation Detector- CDT20

49

Page 59: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Lounge

Hall

Landing

Bedroom

0 60 120 180 240 300

Time after ignition (sees)

CJ Tact= 4°C

CJ Tact= 13°C

D Tact= 20°C

• CDT 17

395

360 420 480

Figure 5-17. Temperature Correlation Method for Optical Detector- CDT17

Hall

Bedroom

0 60 120 180 240 300

Time after ignition (sees)

D Tact= 4°C

CJ Tact= l3°C

D Tact= 20°C

• CDT20

360 420

5

480

Figure 5-18. Temperature Correlation Method for Optical Detector- CDT20

50

Page 60: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

1000 --Conier

900 ••••••. Fast I" Rre Growth

800 . 700 :

I

: 600 . ~

. . . 500 .

IE I

400

300

200

100

0 0 120 240 360 480 600

lime (sees)

Figure 5-19. HRR Curve for Collier's House Fire Test

1000 --CDT20

900 ••••••. lltledlum 12 Rre Grow t

800 . . . '

700

600 ;r:-e

500 a: a: I

400

0 120 240 360 480 600 T1100 (sees)

Figure 5-20. HRR Curve for Test CDT20

5.4.2 Pseudo-Heat Detector Method

The results of the analysis of activation times for the ionisation detectors from the fire

test CDT17 and CDT20 are shown in Figure 5-21 and 5-22 respectively for the

pseudo-heat detector method. All of the investigations in this method were performed

with a value of RTI = 1 m \ti sv.. It is interesting to note that the times predicted from

51

Page 61: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

this method are within 5 seconds of those predicted from the temperature conelation

method, which are shown in Figures 5-15 and 5-16.

The predicted activation times for the optical detectors from tests CDT 17 and CDT20

shown in Figures 5-23 and 5-24 respectively. The results for these two tests follow a

similar trend to the results of the temperature correlation method, in that for Tact = 20°C a good match is attained for the ground floor during test CDT17, but provides up

to 45% errors on the top floor. But for CDT20, this activation temperature will

underestimate the activation times in each case.

52

Page 62: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Hall

294

Bedroom

0 60 120 180 240 300

Time after ignition (sees)

D Tact= 4°C

D Tact= 13 °C

0 Tact= 20°C

• CDT17

375

360 420 480

Figure 5-21. Pseudo-Heat Detector Method for Ionisation Detector- CDT17

Hall

Bedroom

r----"""T""---.---.-----------1 0 Tact = 4°C 170

0 60 120 180 240 300

Time after ignition (sees)

0 Tact= 13 °C

0 Tact= 20°C

• CDT20

415

360 420 480

Figure 5-22. Pseudo-Heat Detector Method for Ionisation Detector- CDT20

53

Page 63: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Lounge

Hall

Landing

Bedroom

,......----~--.----.----------1 0 Tact= 4°C

0 60 120 180 240 300

Time after ignition (sees)

0 Tact= 13°C

0 T act= 20°C

• CDT17

360 420

Figure 5-23. Pseudo-Heat Detector Method for Optical Detector - CDT17

Hall

Bedroom

.------r------.--r---------1 0 Tact = 4 oc 0 Tact= 13 °C

o Tact= 20°C

•CDT20

5

480

0 60 120 180 240 300 360 420 480

Time after ignition (sees)

Figure 5-24. Pseudo-Heat Detector Method for Optical Detector- CDT20

54

Page 64: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

5.4.3 Heskestad's Method

As discussed earlier, there were difficulties in applying the results of the FDS

simulations to this method because of the overestimation of optical density in the

early stages (first 300 seconds) of both fire tests. This overestimation led to the

predicted activation times being extremely low compared to the actual times. But in

order to proceed with some level of investigation of Heskestad' s method, the values

for the predicted optical density were arbitrarily halved.

The values for optical density that FDS calculates are derived from the value for

smoke yield Ys that was input by the user. In this study Ys was given the value of

0.10 kg/kg, which is slightly lower than the range of values given by Tewarson for

flexible polyurethane foams. However, the upholstery in the chairs for these test fires

was a type of combustion-modified foam, and Tewarson's values might not be suited

to these types of foams. In addition to this, the slope of the optical density curve in

Figures 5-11 to 5-14 is quite flat at the early stages, which means that the predicted

activation times will be highly sensitive to the environment over this initial period.

As discussed in Chapter 4, the value for the activation density for the detectors is

0.14 m-1 as discussed by Mulholland for black smoke. This value was applied to both

types of detectors. The values for effective length L are based on the values presented

in Table 2-1.

Given the level of deviations that have gone into the simulation data while

investigating this method, there is little point in trying to compare the results of this

investigation with the other two. However, it should be noted that the trend in the

activation times of these results is similar to those of the other methods.

55

Page 65: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Hall

Bedroom

0 60 120 180 240 300

Time after ignition (sees)

OL=3.7m

0 L = 6.0m

OL=9.5m

.CDT17

341

360 420

Figure 5-25. Heskestad's Method for Ionisation Detector- CDT17

Lounge

Hall

Landing

Bedroom

0 60 120 180 240 300

Time after ignition (sees)

OL=3.7m

OL = 6.0m

OL=9.5m

•CDT20

15

360 420

Figure 5-26. Heskestad's Method for Ionisation Detector- CDT20

56

480

480

Page 66: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Lounge

Hall

Landing

Bedroom

0 60 120 180 240 300

Time after ignition (sees)

Cl L = 6.8m

Cl L = 13.0m

DL = 15 .0m

• CDT17

383

360 420

Figure 5-27. Heskestad's Method for Optical Detector- CDT17

Lounge

Hall

Landing

Bedroom

0 60 120 180 240 300

Time after ignition (sees)

Cl L = 6.8m

Cl L = 13.0m

Cl L = 15.0m

•CDT20

360

425

420

Figure 5-27. Heskestad's Method for Optical Detector- CDT20

57

480

480

Page 67: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

5.5 Observations About Smoke Detector Modelling

It is interesting to note that two chair-fire scenarios, where the chairs' upholstery and

fabric cover, mass, and location within the fire room are the same, as is the level of

ventilation into the fire room, can yield quite different results in terms of the

behaviour of the fire. This is indicative of the unpredictability of fire, and hence of the

smoke generated.

Other researchers have reported the significance of a critical velocity, below which

the lag times for the detectors increase markedly. This phenomenon will affect both

the pseudo-heat detector and Heskestad's methods. As Brozovsky et al reports, the

magnitude of this critical velocity is in the order of 0.16 m/s. The velocities predicted

in this study are presented in Appendices C and D, which show that generally the

velocities at the actual activation times are generally above 0.2 m/s. The only

exception is the ionisation detector in bedroom 2 during test CDT17 (the longer

duration fire), where the velocity is around this critical value. Therefore, as the

predicted velocities are generally higher than the critical value, the concept of critical

velocity has no significance in these analyses.

Looking at Figures 5-15 to 5-28, for test CDT20 (the high HRR, short duration fire),

the detector activation times were longer than those for CDT17. However, for the

temperature correlation method the predicted activation times are longer for CDT17

then they are for CDT20. This trend is repeated for the pseudo-heat detector method.

Heskestad's method exhibits a similar trend for the top floor, but not the ground floor

where the trend is the reverse. All three methods tend to over predict the activation

times for CDT17 and under predict those for CDT20.

Another interesting feature of the results is the trend in the activation times for the

different rooms. For test CDT17 the detectors on the landing activated before those in

the entry hall, whereas for CDT20 the reverse occurred. However, for all three

methods for predicting the detectors' behaviour, the general trend was for the

activation times to be commensurate with the distance that the particular detector was

from the source of the fire.

58

Page 68: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

There is little difference between the results of the temperature correlation method and

the pseudo-heat detector method where RTI has the value of 1 mv2 s'h. In other words,

the simpler temperature conelation method is not significantly less accurate than the

pseudo-heat detector method. Looking at Figures 5-15 to 5-18 it seems that the most

prudent prediction approach would be to use the temperature correlation method with

an activation temperature of 20°C, as this will tend to provide a predicted time

somewhere between the two fire scenarios considered in this study. As this value is

higher than the values recommended by other researchers, it can be hypothesised that

the air cunents in the house that were set up by the radiators have a significant effect

on the behaviour of the detectors. This should not be surprising considering that it is

generally accepted that smoke detectors should not be positioned immediately

adjacent to grilles for HV AC systems.

While it may seem amiss to apply the same value for Tact to both the ionisation and

optical detectors, given the debatable nature of the results, it is difficult to justify a

more refined approach.

59

Page 69: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Chapter 6 CONCLUSIONS

This study modelled the results. of an earlier investigation into two chair fires in the

ground floor of a two-storey house to assess firstly whether the effects of these fires

could be modelled with a field model, and secondly whether the behaviour of the

domestic smoke detectors could also be satisfactorily predicted. The conclusions

drawn from this study are collated below:

6.1 House Domain Geometry

• From the results of this study it can be seen that the house could be

successfully modelled by FDS using the geometry discussed in this report.

• The allocation of the physical properties of Gib board to the intemal walls, the

corrugated sloped ceiling over the stairs, and the inclusion of balustrades all

had some impact on the gas temperatures and behaviour within the house.

• The location of the chair within the fire room, and the creation of only part of

the house for modelling had a more significant effect on the gas and fire

behaviour. This is indicative of the importance of including the entire

collection of rooms when modelling multi room enclosures.

• There was little difference between the results of the lOOmm and 75mm grid

size geometries.

6.2. Comparisons With Fire Behaviour

• It was difficult to achieve good matches for temperature and optical density at

the early stages of the fires. Unfortunately this is the time when smoke

detectors are expected to activate.

• There were reasonably good matches between the predicted and actual

temperatures for the duration of the tests as a whole. These matches were

better at the upper levels within each room.

• FDS was able to predict the trends for optical density, although there were

significant errors in magnitude.

60

Page 70: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

6.3. Comparisons With Smoke Detector Behaviour

• The general trend of the activation sequences of the detectors throughout the

house was emulated.

• In the modelling of houses, it could be non-conservative to assume that there

will not be any heating system regardless of the occupancy, or to assume that

its effects will be negligible.

• There is little difference between the temperature correlation and pseudo-heat

detector methods of predicting smoke detector behaviour with a low value of

RTI.

• Activation times for both ionisation and optical detectors can be predicted by

the use the temperature correlation method with Tact = 20°C.

It is important to note that these conclusions relate to flaming fires and domestic

ionisation and optical smoke detectors.

6.4. Further Research

In terms of the FDS modelling software:

• The estimations for soot yield should have the ability to differentiate between

the sources of the total HRR. This will avoid the difficulty of the radiators

producing soot.

• Models should be developed to emulate particle coagulation, and the change in

particle size and shape.

• As modelling software has developed in the past, it has evolved in ways that

have not been useful to researchers into detector behaviour. Fire and detection

models should progress together, so that useful detection models are derived.

With this particular series of fire tests:

• Investigate the results of the Cardington tests to investigate whether the

inconsistent results between the two fire scenmios considered in this study for

61

Page 71: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

the domestic detectors are also apparent for the commercial detectors that were

monitored during the same tests, or was one of the tests studied a flawed test.

• Consider other tests with domestic detectors to investigate whether more

definite findings develop.

• Further investigate the soot yield to see if better predictions of optical density

can be attained.

• If better results are derived, reinvestigate Heskestad's method to see if more

consistent results can be found by this method.

62

Page 72: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

REFERENCES

Bjorkman, J, Kokkala, M A and Ahola, H 1992. "Measurements of the Characteristic

Lengths of Smoke Detectors". Fire Technology, Vol28, No 2, pp 99- 106.

Brozovsky, E, Motevalli, V and Custer, R L P 1995. "A First Approximation Method

for Smoke Detector Placement Based on Design Fire Size, Critical-Velocity,

and Detector Aerosol Entry Lag Time". Fire Technology Fourth Quarter, pp

336-354.

BRE, CD Rom of Cardington Test Results, Fire Research Station, Building Research

Establishment, UK.

Bukowski, R Wand Averill, J D 1998. "Methods for Predicting Smoke Detector

Activation". Fire Suppression and Detection Research Application Symposium,

Research and Practice: Bridging the Gap. National Fire Protection Research

Foundation, USA, pp64 - 72.

Cleary, T, Chernovsky, A, Grosshandler, Wand Anderson, M 2000. "Particulate

Entry Lag in Spot Type Smoke Detectors". Proceedings, Sixth Intemational

Symposium on Fire Safety Science. International Association for Fire Safety

Science, USA.

Cleary,T, Donnelly, M, Mulholland, G and Farouk, B 2001. "Fire Detector

Performance Predictions in a Simulated Multi-Room Configuration".

Proceedings, AUBE '01, Twelfth lntemational Conference on Automatic Fire

Detection. National Institute of Standards and Technology, USA, pp 455-469.

Collier, PC R 1996. "Fire in a Residential Building: Comparisons Between

Experimental Data and a Fire Zone Model". Fire Technology, Vol32, No 3, pp

195-217.

63

Page 73: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Friday, P A and Mowrer, F W 2001. Comparison of FDS Model Predictions With

FMJSNL Fire Test Data. NIST Report OCR 01-8 10. National Institute of

Standards and Technology, USA.

Girgis, N 2000. Full-Scale Compartment Fire Experiments on Upholstered Fumiture.

Fire Engineering Research Report, University of Canterbury, NZ.

Heskestad, G 1975. "Generalized Characteristics of Smoke Entry and Response for Products-of-Combustion Detectors". Proceedings, 7th Intemational Conference

on Problems of Automatic Fire Detection. Rheinish-Westfalischen Techischen

Hochschule Aachen, pp 267-310.

Karlsson, B and Quintiere, J G 2000. Enclosure Fire Dynamics. CRC Press, Boca

Raton, FL USA.

McGrattan, K B, Forney, G P. Floyd, J E and Hostikka, 5 2001. Fire Dynamics

Simulator (Version 2)- User's Guide. Report NISTIR 6784 (Draft). National

Institute of Standards and Technology, USA.

Mulholland, G W 1995. "Smoke Production and Properties". Section 2/Chapter 15,

SFPE Handbook of Fire Protection Engineering, Second Edition, Society of

Fire Protection Engineers, USA.

Newman, J S 1994. "Modified Theory for the Characterization of Ionization Smoke

Detectors". Proceedings, Fourth Intemational Symposium on Fire Safety

Science. International Association for Fire Safety Science, USA, pp 785 - 792.

Peacock, R D, Reneke, P A, Jones, W W, Bukowski, R Wand Forney, G P 1997. A

User's Guide for FAST: Engineering Tools for Estimating Fire Growth and

Smoke Transport. NIST Special Publication 921, National Institute of Standards

and Technology, USA.

64

Page 74: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Purser, D A, Rowley, J A, Fardell, P J and Bensilum, M 1999. "Fully Enclosed

Design Fires For Hazard Assessment In Relation to Yields of Carbon Monoxide

and Hydrogen Cyanide". Proceedings, Eighth Intemational Conference.

Interscience Communications, UK, pp 1163- 1169.

Qualey, J R, Desmarais, Land Pratt, J 2001. "Response-Time Comparisons of

Ionization and Photoelectric/Heat Detectors". Proceedings, AUBE '01, Twelfth

Intemational Conference on Automatic Fire Detection. National Institute of

Standards and Technology, Gaithersburg, Maryland, USA, pp 283- 299.

Schifiliti, R P 2001. "Fire Detection Modeling- The Research-Application Gap".

Proceedings, AUBE '01, Twelfth Intemational Conference on Automatic Fire

Detection. National Institute of Standards and Technology, USA, pp 529 - 560.

Schifiliti, R P, Meacham, B J and Custer, L P 1995. "Design of Detection Systems"

Section 4/Chapter 1, SFPE Handbook of Fire Protection Engineering, Second

Edition, Society of Fire Protection Engineers, USA.

Snegirev, A Y, Makhviladze, G M and Roberts, J P 2001. "The Effect of Particle

Coagulation and Fractal Structure on the Optical Properties and Detection of

Smoke". Fire Safety Joumal, Vol36, No 1, pp 73- 95.

Spearpoint, M J 1996. The Response of Domestic Smoke Alanns to Fires in a Typical

Dwelling. FRDG Publication No 16/96, Home Office Fire Research and

Development Group, UK.

Tewarson, A 1995. "Generation of Heat and Chemical Compounds in Fires".

Section 3/Chapter 4, SFPE Handbook of Fire Protection Engineering, Second

Edition, Society of Fire Protection Engineers, USA.

65

Page 75: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Appendix A HOUSE DIMENSIONS, LOCATIONS OF INSTRUMENTATION

Plan North

t Bedroom 1

600

r-~ l

Bathroom Landing

down

Top Floor 1 ... 3000

, ..

Dining Room

Kitchen

I Bedroom 2

750

~--~

Bedroom 3 -

0 0 co

·,l~ 2400 ·' 4200 ..,

lounge

Entry Hall

Ground Floor 1~-... ------2-40_0 _ __. .. -11 1... uoo ~ I Figure Al. House Plans - Dimensions

66

0 0 ......

0 0 ('j ('j

0 0 ...

Page 76: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

KEY 0

0 0 t:l 1 1 Optical Density Meter .... ~

0 CCI

I Q) Ionisation Detector ~ Q)-@ Optical Detector . ods §

-'-1 I @-~ Thermocouple Tree at I

1J 40 1700

r- .____, ~1 Lr-

I 1700 ~ +-a:::o-r g r~'5 ::: ~ CD®-..

1900 2 0 .... il~

Top Floor

0 1 500..1 1550

m I I ....

._CD®

.. 1550

,., ~0 ~ It) ...

0 0

t ... _l~ l~

a:::o-+ ®-+-®#3 0

~ 1 l"e CD ~

~ 1 tOO '6001 I •

18601

~~ ! i I 0

I I 0 I 10

• Ground Floor

Figure A2. House Plans - Locations of Instrumentation

67

Page 77: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Plan North

t Bedroom 1

l Bathroom

Landing

down -+-+-+-_,_.-1-

Top Floor

Dining Room

I ..

~ Kitchen

Ground Floor

Bedroom 2

0 0 0 ....

(~ 1 kW

Bedroom 3

0 0 co

Lounge 1..-

0 0 ~ ....

~·· I 1.5 kW I

tooo I 1 tOO

Entry Hall I --i I I up I I I I I

Figure A3. House Plans - Locations and Ratings of Radiators

68

Page 78: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Appendix B INVESTIGATION INTO TYPES OF BALUSTRADES

Section 4.4 discusses difficulties with accommodating the balustrades into the house

domain geometry. As the balustrades have to fit within the allocated grid layout,

several different arrangements of balustrade elements were considered. The balustrade

layout finally chosen was the one that most closely matched the temperature profile

on the stairs that was attained during the actual fire test, based on a model of the

ground floor only without the function of radiators. This section presents the results of

the investigation into the types of balustrades.

Stairs ~0,---~~~~~~---.----------------------------------~

- FDS 2.25m No Balustrade

• • • ·CDT17 300

--FDS 0.95m No Balustrade ••••••. aJT17

250 +--------------_J

~ Gl 200

~ lii ~ 150 Gl 1-

100

50

0 120 240

... ·"·--·---- .. -........... .. ..... f

360 480 600 Time (sees)

Figure Bl. Temperature Curve- No Balustrade

69

720 840

Page 79: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

0 0 (!)

Figure B2. Diagram of Balustrade - 600mm High Horizontal

Stairs - Comparing 600 Balustrade With Actual Test $Or-----------------------.----------------------------------,

- FDS 2.25m Wrth 0.6m Balustrade ••• ·a:IT17

300 --FDS 0.95m Wrth 0.6m Balustrade

• •.. · -·a:>T17 250~--------------------~

E ~ 200 .i3 ~ <1> c. 150 E <1> ....

100 .. ~ .. ---..... 50

!:'···-.. -0

0 120 240 360 480 600 720 840

TJOO (sees)

Figure B3. Temperature Curve- 600mm High Horizontal

70

Page 80: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

0 0 00

Figure B4. Diagram of Balustrade - 800mm High Horizontal

350

300

250 ~

0 e., !!! 200 .a f! :g_ 150 E Q)

1-100

50

0 0

Stairs -Comparing 800 Balustrade With Actual Test

- FDS 2.25m Wrth O.Sm Balustrade

• • • ~COT17 --FDS 0.95m Wrth 0.8m Balustrade

••••••. COT17

120 240 360 480 600 Tlml (sees)

Figure BS. Temperature Curve - 800mm High Horizontal

71

.......... __ _

-.- .. -...

720 840

Page 81: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

0 0 0

Figure B6. Diagram of Balustrade- lOOOmm High Horizontal

Stairs ~0.-----~-=~~~~~-,-----..-------------,r--------~

- FOS 2.25m With 1m Balustrade

300 •• • -COT17

--FOS 0.95m with 1m Balustrade ••••••. CQT17

250 +--------------'

~ ~200 .a <U Gi E'150 Q)

1-

100

50

0 120 240 360 480 600 T~~re (sees)

Figure B7. Temperature Curve -lOOOmm High Horizontal

72

.... --........

720 840

Page 82: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

0 0 OC)

Figure BS. Diagram of Balustrade - 800mm High Cheque Pattern

Stairs 3~r---~~~~~~~~~--------------------------------~ - FDS 2.25m Wrth O.Bm Balustrade

300 ••• ·<XlT17

--FDS 0.95m Wrth o.am Balustrade

•••. ···COT17 2~ +-----------__J

100

~ , ea••:••

0 120 240

....................... ., ..... -"

360 480 T11rn (sees)

600

Figure B9. Temperature Curve- 800mm High Cheque Pattern

73

.... ---... ~

720 840

Page 83: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

0 0 0

Figure BlO. Diagram of Balustrade- lOOOmm High Cheque Pattern

Stairs 350 ,-----=-=---=-=-:-::--::--:--:--:---1---- -~~---~-----~--­

- FDS 2.25m Wrth 1.0m Balustrade

- - - ·a11'17 300

--FDS 0.95m With 1.0m Balustrade

••.•• ··a:>T17 250 +------------'

100

50

0 120 240 360 480 600 Tirre (sees)

Figure Bll. Temperature Curve- 1000mm High Cheque Pattern

74

720

-........... .... ...............

840

Page 84: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

0 0 (X)

Figure B12. Diagram of Balustrade- 200mm High Soldiers

Stairs 350.-----~~=-~~~~~-,,---------------------------------~

- FDS 2.25m Wrth O.Sm Balustrade

• • • ·CDT17 300

---FDS 0.95m Wrth O.Sm Balustrade

·······CDT17 250 i---------------------___j

0 ~ 200

~ :g, 150 E <I> 1-

100 ............. .. -- ... .. ..........

0~--~---r--~--~--~----.---~--~---r---.--~---,----~~

0 120 240 360 480 600 720 840 Tare (sees)

Figure B13. Temperature Curve- 200mm High Soldiers

75

Page 85: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

0 0 0

Figure B14. Diagram of Balustrade- 200mm High Soldiers with Handrail

Stairs 3~r-----~--------------~--------------------------------~

- FOS 2.25m Wrth 1.0m Balustrade ••. -rom

300 --FOS 0.95m Wrth 1.0m Balustrade ....... rom

2~~--------------------~

E ~ 200

~ 4; E" 1~ Q)

1-

100

~~~--·------···---··-·· , ....

~~ -.......

0~--~--~--~--~--~--.---.---.---.---.---~--~--~--~

0 120 240 360 480 600 7'?.0 840 T11re (sees)

Figure BlS. Temperature Curve- 200mm High Soldiers Plus Handrail

76

Page 86: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Appendix C FAMILIES OF CURVES FOR SIMULATIONS OF TEST CDT17

Throughout this report, graphs have been presented for predicted HRR, temperature,

optical density, and discussions have taken place about predicted velocity. This

section presents the full family of curves for test CDT17.

1000 --COT17

900 ••••••. Medlumt2 Fire Growth

800

700

600 ~~

c 500 a:

a: J:

400

300

200

100

0 ..

0 120 240 360 480 600 720 840 lime (sees)

Figure Cl. HRR Curve- TestCDT17

77

Page 87: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

500

400

~ 300 ~

~ Q) 0.

200 E Q)

1-

100

--.- FDS 2.34m

..•.. ··CDT17

--FOS1.69m

••..... am7

--FOS0.73m

·••· · ··CDT17

Lounge

.. '\

'

0~~~~~--~~--~--~~--~~--~~--~~ 0 12Q 240 360 480 600 720 840

Tl!llil (sees)

Figure C2. Lounge Temperatures - Test CDT17

Lounge 100

--FDS2.34m

....... aJT17

80 --·-FDS 1.69m

~ .....• ·a:>T17

60 --FDS0.73m ,. Ql . . .... . ...• ··a:>T17 I

~ .. ... , ... . Q) ... . 0. .. E 40 .. ... Q) . . 1- .. . ...... "*

20

0 0 60 120 180 240 300 360

Trre (sees)

Figure C3. Lounge Temperatures - Test CDT17

78

Page 88: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Entry Hall 300

--FDS1.69m

·· ·····CDT17 250

--FDS0.73m ....... aJf17

E 200 Q) ..... :::J

~ 150 Q) Cl. E Q)

1- 100 .. ... • <II ... --.

50

0 0 120 240 360 480 600 720 840

Tffi) (sees)

Figure C4. Entry Hall Temperatures -Test CDT17

Stairs 300

--FDS2.88m ....... (l)T17

250 --FDS2.25m ....... (l)T17

E 200

<ll .....

~ 150 ..... Q) Cl. E Q) 100 1- ...

~· . .. . . ... ..... -~-; ..

50 ,• .. 0

0 120 240 360 480 600 720 840 lirre (sees)

Figure CS. Stairs Temperatures - Test CDT17

79

Page 89: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Landing 140

--FDS2.34m

120 ·······COT17 --FDS0.73m ....... cor11

100 6 ~ Cl) 80 ::; iii iii

60 0. E Cl)

1-40

• ::,. :: =:: .. !--

20

0 0 120 240 360 480

Trre (sees)

Figure C6. Landing Temperatures -Test CDT17

Bedroom 2 140

--. FDS 2.36m

120 ....... COT17

100 --FDS0.75m 6 ....... COT17 ~

~ 80 ::J iii iii 60 0. E Ql

1-40

.- ............................ ---· .. 20

0 120 240 360 480 Trre (sees)

Figure C7. Bedroom 2 Temperatures- Test CDT17

80

600 720

600 720

~- --. ......... -.... _

840

....... ........ ........

840

Page 90: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Lounge 5,----------.----------------------,-----------------------~

~ "' c <I> 0 lil ,g c.. 0

---FDS1.5m

....... am? 4+------_j

3

2

0 60 120 180 240 300

llme (sees) 360

Figure CS. Lounge Optical Density - Test CDT17

Haa

420 480 540 600

5,--------.------------------------,----------------------~ ----FDS 1.5m

••••••. aJf17 4+----__J

? ~ 3 ~ "' c <I> 0

~ 2 E. 0

••\ I . ' . . ,. ,, .

. -•" 0~--~~==~~~~·~-~~--~----~----~----~----~----~----~

0 60 120 180 240 300 Tine (sees)

360

Figure C9. Entry Hall Optical Density- Test CDT17

81

420 480 540 600

Page 91: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Landing 5.---------~--------------------------------<r------------,

--FDS1.5m

··· ····ffiT17 4+--------'

~ 3 (/) c: Q)

0 iii ,g 2 0. 0

0 60 120 180 240 300 360 420 lime (sees)

Figure ClO. Landing Hall Optical Density- Test CDT17

Bedroom 2 5

--FDS1.5m

·······COT17 4

~ 3 ~

·(/) c: Q)

0 a;

2 ,g 0. 0

0 60 120 180 240 300 360 420 lime (sees)

Figure Cll. Bedroom 2 Optical Density - Test CDT17

82

480 540 600

480 540 600

Page 92: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

~

Je .§. ~ 0 .2 <I> >

--tJ.Vel

....... v-Vel 0.8 +----____.j

0.6

0.4

0.2

Lounge Ionisation Detector

' . ,,

O~L---~----~~----~----~------~----~----~----~ 0 60 120 180 240

Tune (sees) 300 360

Figure C12. Lounge Ionisation Detector Velocity - Test CDT17

--tJ.Vel

•· · ... · V·Vel 0.8+-----

Je 0.6 ,!§. ~ 0 .2

<I> 0.4 >

0 60 120

Hall Ionisation Detector

180 240 Tme(secs)

300

Figure C13. Hall Ionisation Detector Velocity - Test CDT17

83

360

420 480

420 480

Page 93: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Landing Ionisation Detector

--tJ.Vet

·······V-Ve1 0.8+----

-!!! 0.6 .§.

-~ 0

..Q Ql 0.4 >

0.2

0~----~~~~----~~----~----~----~----~~--~ 0 60 120 180 240

Tme (sees) 300 360

Figure C14. Landing Ionisation Detector Velocity- Test CDT17

~

Je 5 ~ ()

.S! Ql >

--lJ.Vel

....... v-vet 0.8 +----.-.1

0.6

0.4

0.2

0 60 120

Bedroom 2 Ionisation Detector

180 240 Ture (sees)

300 360

Figure Cl5. Bedroom 2 Ionisation Detector Velocity- Test CDT17

84

420 480

420 480

Page 94: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

~ .§. ~ 0

_g Q)

>

Lounge Optical Detector

--U.Vel

•· · · · · · V-Vel 0.8 t----____J

0.6

0.4

0.2

0~~--~----~------.-----~-----r----~~----~----~ 0 60 120 180 240

TllOO (sees) 300 360 420 480

Figure C16. Lounge Optical Detector Velocity - Test CDT17

U) ..... E ....... ~ 0 _g Q)

>

Hall Optical Detector

--U.Vel

..•.... V-Vel 0.8 t------'

0.6

0.4

0.2

Or---~~~~~~~~~~~~~~~~~~~~~~~~~

0 60 120 180 240 Trre (sees)

300 360 420 480

Figure C17. Hall Optical Detector Velocity- Test CDT17

85

Page 95: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Landing Optical Detector

--lJ-Vel

....... v-v 0.8+------'

.!!! 0.6

..§_ ~ 0

..9 Q) 0.4 >

0.2

0+--~-~~--.---~----.----~----.-------r-----~

0 60 120 180 240 lirre {sees)

300 360

Figure C18. Landing Optical Detector Velocity- Test CDT17

--lJ-Vel

· · · · · • · V-Vel 0.8+-----'

~ 0.6 .!!! ..§_ ~ 0 ..2

0.4 cD >

0.2

0 60 120

Bedroom 2 Optical Detector

180 240 Ture (sees)

300 360

Figure C19. Bedroom 2 Optical Detector Velocity- Test CDT17

86

420 480

420 480

Page 96: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Appendix D FAMILIES OF CURVES FOR SIMULATIONS OF TEST CDT20

Throughout this report, graphs have been presented for predicted HRR, temperature,

optical density, and discussions have taken place about predicted velocity. This

section presents the full family of curves for test CDT20.

1000 --COT20

900 - - - - - •. Medium t2 Fire Growth

800

700

600 ~-~ 500 a: a: :z:

400

300

200

100

0 0 120 240 360 480 600 720 840

Tlll16 (sees)

Figure Dl. HRR Curve- TestCDT20

87

Page 97: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Lounge 500

--FDS2.34m - ...... C01'20

400 --FDS1.69m ....•. ·C01'20 --FDS0,73m

E - ...... C01'20

~ 300

::s 'til Qi 0..

200 E Q)

1-

100

0 120 240 360 480 600 Tvre (sees)

Figure D2. Lounge Temperatures - Test CDT20

Lounge 100.----------.------------------~--~r,---•• -------.~~

--FDS 2.34m .•

80

60

40

.. .. .. .. • .. . C01'20 • f ••

--FDS 1.69m .-·· ~

.. . ....... ·C01'20 ,./

--FDS0.73m :'

•••.... C01'20 •••• ... •' ...

;'

.

.. ..... ....

... ... -... ··

.... •'

,• ,.~

0~-------r------~--------~-------r------~------~ 0 60 120 180

Tvre (sees)

Figure D3. Lounge Temperatures- Test CDT20

88

240 300 360

Page 98: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Entry Hall 350

--FDS1.69m

300 ·······COT20

250 --FDS0.73m

~ ....... (X)T20 <ll 200 ~ <I>

150 a. E <I> 1-

100

50

0 0 120 240 360 480 600

Tlrne (sees)

Figure D4. Entry Hall Temperatures - Test CDT20

Stairs 300,---~---r------------------------~~IHK---~

---FDS 2.88m ••••••• CQT2o

250 --FDS2.25m

·······COT20 ~ 200+-----___J ~ ~ ;:3

1ii .. Q) a. E Q)

1-

150

100

0+---~----,---~----~----~--~----~--~----~--~ 0 120 240 360 480 600

Tlll19 (sees)

Figure DS. Stairs Temperatures - Test CDT20

89

Page 99: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Landing 160

--FDS2.34m

140 ...•.. ·COT20

120 --FDS0.73m

~ ·······COT20 100

Q)

;:; ~ 80 Q) 0. E 60 Q)

t-

40 ----------- ............

20

0 0 120 240 360 480 600

lirm (sees)

Figure D6. Landing T'emperatures - Test CDT20

Bedroom 2 140

--FDS2.36m

120 •..•.. ·COT20

100 --FDS0.75m

E ·······COT20 Q) 80 .... ~ :u 60 0. E Q)

t-40

-----------------------20

0+-----~----~----~----.-----~----,-----~-----r----~----~

0 120 240 360 480 .600

Trre (sees)

Figure D7. Bedroom 2 Temperatures- Test CDT20

90

Page 100: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Lounge 5r-----------.-------------------~~----------~--~--------~

~ "' c: Q)

0 Cii

~ 0

--FDS1.5m

••••••• (X)T2Q

4 +---------____)

3

2

0 60 120 180 240 300 Tune (sees)

360

Figure DS. Lounge Optical Density - Test CDT20

Hall

\. ... ··,)·"

420 480

' . ' . ' ..

' ...... ·.

540 600

5r--------.--------------------~.-------------------~~-----FDS1.5m

....... COT2o 4 +-------------~

.~

"' c: Q)

0 Cii 2 ~ c. 0

0 60 120 180 240 300 360 lirrs (sees)

Figure D9. Entry Hall Optical Density- Test CDT20

91

420 480 540 600

Page 101: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Landing 5r---------.---------------------------~r-------------~

--FDS1.5m

.... ···C0120 4 +----------'

.!§ .... ~ 3 ~ 1/J c Q)

0 "iii .!.! 2 c. 0

0~----~--~~~~~--~----~~--~----~----~----~----~ 0 60 120 180 240 300 360 420 480 540 600

Ttme (sees)

Figure DlO. Landing Hall Optical Density- Test CDT20

Bedroom 2 5r---------.-----------------------------------r-----------,

--FDS1.5m

....... aJT20 4+------~

:[ :::. 3 ~ 1/J c Q)

0

"iii 2 ~ 0

0 60 120 180 240 300 Ture (sees)

360

Figure Dll. Bedroom 2 Optical Density- Test CDT20

92

420

• .. . .. r-·· .... .

480

r·• -· .

540 600

Page 102: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

~ 5 .~ 0

.Q <I> >

Lounge Ionisation Detector

--lJ-Vel

....... v-Vel 0.8 +-----__j

0.6

0.4

0.2

O~L---~------~----~------~----~------~----~----~ 0 60 120 180 240

lirre (sees) 300 360 420 480

Figure D12. Lounge Ionisation Detector Velocity- Test CDT20

..!!! 5 >-"" 0 0 Gi >

Hall Ionisation Detector

--lJ-Vel

••••••. V·Vel 0.8 .t---'---'

0.6

0.4

0.2

o~~--~~~~~~~~~~~~~~~~~~~~dfi~~~~~~

0 60 120 180 240 Tme(secs)

300 360 420 480

Figure D13. Hall Ionisation Detector Velocity- Test CDT20

93

Page 103: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Landing Ionisation Detector

--U-Vel

·· • · · · · V-Vel 0.8 -1-----'

~ 0.6 .§.

.~ 0 .2 CD 0.4 >

0.2

0~------~~--~-------r------.-------.-------r-----~------~ 0 60 120 180 240

Tme (sees) 300 360

Figure Dl4. Landing Ionisation Detector Velocity - Test CDT20

--U-Vel

·• • ·•·· V·Ve! 0.8 +-----___.J

~ 0.6 .§. ~ ()

.2 0.4 CD

>

0.2

0 60 120

Bedroom 2 Ionisation Detector

180 240 Tlroo (sees)

300 360

Figure DlS. Bedroom 2 Ionisation Detector Velocity- Test CDT20

94

420 480

420 480

Page 104: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Lounge Optical Detector

--lJ.Vel

·······V·Vel 0.8 +--------.J

~ 0.6 .!!! .s £ 0 .Q

0.4 Q)

>

0,2

o~L---~----~------~----~----~------.------r----~ 0 60 120 180 240

Thoo (sees) 300 360

Figure D16. Lounge Optical Detector Velocity- Test CDT20

,....... .!!! ..s >.

;t:: 0

..Q <I> >

--lJ.Vel

· · ·• .• · V-Vel 0.8-t----.J

0.6

0.4

0 60 120

Hall Optical Detector

180 240 Trne (sees)

300

Figure D17. Hall Optical Detector Velocity- Test CDT20

95

360

420 480

420 480

Page 105: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

--U.Vel

·······V 0.8 -!-------'

~ 0.6 .§_ .£;-0

..Q

~ 0.4

0.2

Landing Optical Detector

0+---~~~~--~------~-----~-----,-------r------,-----~

0 60 120 180 240 Thre (sees)

300 360

Figure D18. Landing Optical Detector Velocity - Test CDT20

~

~ .§_ >-.:= 0

..Q Ql >

--IJ.Vel

· ·· · · · · V·Vel 0.8 -!-------'

0.6

0.4

0.2

0 60 120

Bedroom 2 Optical Detector

180 240 Trm(secs)

300 360

Figure D19. Bedroom 2 Optical Detector Velocity -Test CDT20

96

420 480

420 480

Page 106: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

AppendixE FAMILIES OF CURVES FOR 75mm GRID SIMULATION

During this study, an investigation took place to assess what impact the choice of grid

size has on the results of the simulations. This investigation was performed by

comparing 75mm and lOOmm grid size simulations for CDT17. This section presents

the results of this investigation.

800r------------,----------------------------------------------, --75nmGrkl

700 ....•. -100nmGrid

600 +---------~

500

~ a: 400 a: I

300

200

100

0 120 240

Figure El. HRR Curve - TestCDT17

360 480 600 720 840 Twre (sees)

Lounge 500~-------------~~-------------------------,~------------~

400

0 ~300 e ~ :::1

--2.34m· 75mmGrid

....... 1oonmGrid

--1.69m • 75mm Grid

....... 10onmGrid

---0.73m· 75nmGrid

....... 100mmGrid E' 200 -1------------__J Q)

1-

0 120 240 360 lirre (sees)

Figure E2. Lounge Temperatures - TestCDT17

97

480 600 720 840

Page 107: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Entry Hall 300 ~ 1.69- 75mnGrid

••••••• 100mnGrid 250

-0.73m· 75mnGrid

....... 1QOmnGrid 0 200 e.... <I> ... ~ 150 <I> c. E <I> 100 I-

50

0 0 120 240 360 480 600 720 840

Tim! (sees)

Figure E3. Entry Hall Temperatures - TestCDT17

Stairs 300

--2.88m • 75mn Grid

....... 10mnGrid 250

--225m· 75mn Grid

••••. ··100mnGrid 0 200 e.... ~

~ 150 ... <ll c. E <ll

100 I-

50

0 0 120 240 360 480 600 720 840

Tlroo (sees)

Figure E4. Stairs Temperatures - TestCDT17

98

Page 108: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

Bedroom 2 300

--2.36m· 75nmGrkl

....... 1QOnmGrid 250

--0.75m· 75nmGrid

•••.••. 1(JOnmGrid

E 200

~ .a 150 !"! <I> c. E <I> 100 1-

50

0 0 120 240 360 480 600 720 840

lin-e (sees)

Figure E6. Bedroom 2 Temperatures - TestCDT17

99

Page 109: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

FIRE ENGINEERING RESEARCH REPORTS

95/1 Full Residential Scale Backdraft I B Bolliger

95/2 A Study of Full Scale Room Fire Experiments P AEnright

95/3 Design of Load-bearing Light Steel Frame Walls for J T Gerlich Fire Resistance

95/4 Full Scale Limited Ventilation Fire Experiments D JMillar

95/5 An Analysis of Domestic Sprinkler Systems for Use in FRahmanian New Zealand

96/1 The Influence of Non-Uniform Electric Fields on MABelsham Combustion Processes

96/2 Mixing in Fire Induced Doorway Flows J M Clements

96/3 Fire Design of Single Storey Industrial Buildings B W Cosgrove

96/4 Modelling Smoke Flow Using Computational Fluid TN Kardos Dynamics

96/5 Under-Ventilated Compartment Fires - A Precursor to ARParkes Smoke Explosions

96/6 An Investigation of the Effects of Sprinklers on MWRadford Compartment Fires

97/1 Sprinkler Trade Off Clauses in the Approved Documents GJBarnes

97/2 Risk Ranking of Buildings for Life Safety JWBoyes

97/3 Improving the Waking Effectiveness of Fire Alarms in T Grace Residential Areas

97/4 Study of Evacuation Movement through Different Building PHolmberg Components

97/5 Domestic Fire Hazard in New Zealand KDJirwin

97/6 An Appraisal of Existing Room-Corner Fire Models D C Robertson

97/7 Fire Resistance of Light Timber Framed Walls and Floors GCThomas

97/8 Uncertainty Analysis of Zone Fire Models AM Walker

97/9 New Zealand Building Regulations Five Years Later TM Pastore

98/1 The Impact of Post-Earthquake Fire on the Built Urban RBotting Environment

98/2 Full Scale Testing of Fire Suppression Agents on Unshielded MJDunn Fires

98/3 Full Scale Testing of Fire Suppression Agents on Shielded N Gravestock Fires

98/4 Predicting Ignition Time Under Transient Heat Flux Using A Henderson Results from Constant Flux Experiments

98/5 Comparison Studies of Zone and CFD Fire Simulations A Lovatt

98/6 Bench Scale Testing of Light Timber Frame Walls P Olsson

98/7 Exploratory Salt Water Experiments of Balcony Spill Plume EYYii Using Laser Induced Fluorescence Technique

99/1 Fire Safety and Security in Schools RACarter

Page 110: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

99/2 A Review of the Building Separation Requirements of the JM Clarke New Zealand Building Code Acceptable Solutions

99/3 Effect of Safety Factors in Timed Human Egress Simulations KMCrawford

99/4 Fire Response of HV AC Systems in Multistorey Buildings: MDixon An Examination of the NZBC Acceptable Solutions

99/5 The Effectiveness of the Domestic Smoke Alarm Signal C Duncan

99/6 Post-flashover Design Fires RFeasey

99/7 An Analysis of Furniture Heat Release Rates by the Nordtest J Firestone

99/8 Design for Escape from Fire I J Garrett

99/9 Class A Foam Water Sprinkler Systems DB Hipkins

99/10 Review of the New Zealand Standard for Concrete Structures MJinwood (NZS 3101) for High Strength and Lightweight Concrete Exposed to Fire

99/12 An Analytical Model for Vertical Flame Spread on Solids: GANorth An Initial Investigation

99/13 Should Bedroom Doors be Open or Closed While People are D L Palmer Sleeping? - A Probabilistic Risk Assessment

99/14 Peoples Awareness of Fire S J Rusbridge

99/15 Smoke Explosions B J Sutherland

99/16 Reliability of Structural Fire Design JKS Wong

99/17 Heat Release from New Zealand Upholstered Furniture T Enright

00/1 Fire Spread on Exterior Walls FNPBong

00/2 Fire Resistance of Lightweight Framed Construction PCRCollier

00/3 Fire Fighting Water: A Review of Fire Fighting Water S Davis Requirements (A New Zealand Perspective)

00/4 The Combustion Behaviour of Upholstered Furniture HDenize Materials in New Zealand

00/5 Full-Scale Compartment Fire Experiments on Upholstered N Girgis Furniture

00/6 Fire Rated Seismic Joints MJames

00/7 Fire Design of Steel Members KRLewis

00/8 Stability of Precast Concrete Tilt Panels in Fire LLim

00/9 Heat Transfer Program for the Design of Structures Exposed JMason to Fire

00/10 An Analysis of Pre-Flashover Fire Experiments with Field C Nielsen Modelling Comparisons

00/11 Fire Engineering Design Problems at Building Consent Stage PTeo

00/12 A Comparison of Data Reduction Techniques for Zone Model S Weaver Validation

00/13 Effect of Surface Area and Thickness on Fire Loads HWYii

00/14 Home Fire Safety Strategies P Byrne

00/15 Accounting for Sprinkler Effectiveness in Performance MFeeney Based Design of Steel Buildings in Fire

Page 111: A Comparison Between Predicted and Actual Behaviour of ... · A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire by DR Brammer

00/16

01/1

01/2

01/3

01/4

01/5

01/6

01/7

01/8

01/9

01/10

01/11

01/12

01/13

02/1

02/2

02/3

02/4

02/5

02/6

02/7

02/8

02/9

02/10

02/11

A Guideline for the Fire Design of Shopping Centres

Flammability of Upholstered Furniture Using the Cone Calorimeter

Radiant Ignition of New Zealand Upholstered Furniture Composites

Statistical Analysis of Hospitality Industry Fire Experience

Performance of Gypsum Plasterboard Assemblies Exposed to Real Building Fires

Ignition Properties of New Zealand Timber

Effect of Support Conditions on Steel Beams Exposed of Fire

Validation of an Evacuation Model Currently Under Development

2-D Analysis of Composite Steel - Concrete Beams in Fire

Contribution of Upholstered Furniture to Residential Fire Fatalities in New Zealand

The Fire Safety Design of Apartment Buildings

Smoke Alarm Ownership in Relation to Socio-Economic Factors in Christchurch

Accounting for Sprinkler Effectiveness in Performance Based Design of Steel Buildings for Fire

Equivalent Fire Resistance Ratings of Construction Elements Exposed to Realistic Fires

Performance of Expanded Polystyrene Insulated Panel Exposed to Radiant Heat

A Comparison Between Predicted and Actual Behaviour of Domestic Smoke Detectors in a Realistic House Fire

Development of Bench-Scale Testing of Sprinkler and Smoke Detector Activation/Response Time

The Effect of Door Angle on Fire Induced Flow Through a Doorway

Implementation of a Glass Fracture Module for the BRANZ Fire Compartment Fire Zone Modelling Software

Assessing the Feasibility of Reducing the Grid Resolution in FDS Field Modelling

Fire Safety Design of Ferrymead Heritage Park

Experimental Results for Pre-Flashover Fire Experiments in Two Adjacent ISO Compartments

Measurement of Magnitude and Direction of Hot Gas Flow in a Fire Compartment with a Five-hole Probe

Assessment of the Current False Alarm Situation from Fire Detection Systems in New Zealand and the Development of an Expert System for Their Identifications

Performance of Unprotected Steel and Composite Steel Frames Exposed to Fire

School of Engineering University of Canterbury

Private Bag 4800, Christchurch, New Zealand

Phone 643 364-2250 Fax 643 364-2758

JMMcMillan

A Coles

FChen

TY A Chen

B H Jones

CKNgu

J Seputro

A Teo

R Welsh

CRWong

SWu

NBuchanan

MFeeney

JNyman

GBaker

DBrammer

KS Chin

LRClark

RParry

N Patterson

MRangi

L Rutherford

J Schulz

YFTu

CWastney