a b c d - commscope...route x-connect cabling through cable bracket brackets are typical on both...

2
4 3 2 1 1 2 3 4 D C B A C B A 1 2 DIMENSIONS IN INCHES THIRD ANGLE PROJECTION DRAWING NUMBER COMMSCOPE, INC. 102.6mm [4.04] 600mm [23.6] 2200mm [86.6] 250mm [9.8] 449.6mm [17.7] 75.2mm [2.96] 474.5mm [18.7] ITEM DESCRIPTION CATALOG QTY 010 600mm WIDW X 2200.00mm HIGH RACK FRAME ASSEMBLY 46 RACK SPACE AT 44.45mm (1.75") SPACINGS RAC-MC2200 1 030 133.35mm HIGH BLANK PANEL AUX-BPP5219M 1 040 VERTICAL X-CONNECT WIRING DUCT (PUTTY) (65.02mm WIDE X 125.98mm DEEP) AUX-XCD001 26 050 227.58mm LONG CABLE SUPPORT BAR (PUTTY) AUX-CB9001 16 060 116.84mm DEEP CABLE SUPPORT BRACKET (PUTTY) AUX-HB1946 14 070 UPPER HORIZONTAL CABLE TROUGH (PUTTY) (133.35MM HIGH X 138.68mm DEEP) ---- 1 071 HORIZONTAL CABLE TROUGH (PUTTY) (133.35mm HIGH X 138.68mm DEEP) ---- 1 072 CABLE RETAINERS FOR LOWER TROUGH (PUTTY) AUX-0XCRB5 2 091 1/2-AMP, GMT TYPE FUSE (RED) F-1/2 13 092 RACK GROUNDING KIT RAC-MX0617 1 093 6500mm RACK FLOOR TEMPLATE DRAWING ---- 1 094 600mm X 300mm RACK INSULATOR PAD AUX-0X1029 1 095 BAY LINE-UP INSTALLATION REFERENCE DRAWING ---- 1 DATE DWN MCO REV 25-FEB-17 PSC 8000019856 A SHT. OF DWN: P. SALAZAR DO NOT SCALE DRAWING ENGR: P. SALAZAR A REV 660000502 C SIZE ALL DIMS AND TOLERANCES .XX: # N/A ARE INCHES UNLESS .XXX: # N/A OTHERWISE SPECIFIED ANGULAR: # N/A DSX SKELETON BAY FRONT X-CONNECT TITLE © 2016 COMMSCOPE, INC.CONFIDENTIAL NOTICE: THESE DRAWINGS AND SPECIFICATIONS ARE THE PROPRIETARY PROPERTY OF COMMSCOPE, INC.AND MAY BE USED ONLY FOR THE SPECIFIC PURPOSE AUTHORIZED IN WRITING BY COMMSCOPE, INC. 227.58mm [8.96] REAR VERTICAL CABLE BARS (ITEM 050) EQUIPMENT CABLE TIE-DOWN TYPICAL ON BOTH SIDES 116.84mm [4.60] DEEP HORIZONTAL CABLE BARS (ITEM 060) ADC NOTES: 1. USE M-6 RACK SCREWS TO MOUNT ITEMS ON THE RACK UNLESS OTHERWISE SPECIFIED. 2. A COPY OF THIS DRAWING IS INCLUDED WITH THE BAY. SHIP ITEM 091 THROUGH 099 WITH THE BAY, 3. MOUNT (4) RACK GROUND POST TERMINAL ON THE INSIDE SURFACE (4) ON EACH CHANNEL (2) ON TOP AND (2) ON BOTTOM APPLY NO-OX GEL (ITEM 101) ON ANY EXPLOSED METAL. 4. MOUNT WIRING DUCT ON THE FRONT, CABLE SUPPORT BARS AND BRACKETS ON THE BACK AS SHOWN. 5. CUSTOMER WIRING NOTES, TABLE AND DETAILS ARE FOR CUSTOMER USE ONLY. 6. MOUNT REAR SUPPORT BRACKET (ITEM 013) ON THE BASE AS SHOWN ON SHEET 2. PLACE LABEL (ITEM 012) PRINTED "REMOVE/DISCARD" ON BRACKET (ITEM 013). 7. USE ITEM 071 & 072 TO CREATE LOWER CABLE TROUGH 8 SEE PAGE 2 FOR ASSEMBLY DETAIL. CUSTOMER REFERENCE NOTES: 9. THIS CONFIGURATION IS SPACED FOR 5.25" HIGH MODULES. BOTH FRONT AND BACK CABLING MANAGEMENTS ARE PROVIDED. 10. GMT TYPE FUSES OF THE PROPER AMPERAGE ARE REQUIRED TO REPLACE "DUMMY" FUSES IN THE FUSE PANEL TO ACTIVATE MODULES. SEE WIRING NOTES FOR ADC STANDARD WIRING, AND WIRING TABLE FOR TERMINAL CONNECTIONS AND FUSE POSITIONS. CONNECT POWER TO THE FUSE PANEL BEFORE REPLACING FUSES. 11. NEVER INSTALL TELEPHONE EQUIPMENT IN A WET LOCATION OR DURING A LIGHTNING OR ELECTRICAL STORM. WHEN INSTALLING OR MODIFYING TELEPHONE LINES, DISCONNECT LINES AT THE NETWORK INTERFACE BEFORE WORKING WITH UNINSULATED LINES OR TERMINALS. 12. CONNECT OFFICE FRAME GROUND TO THE RACK USING THE PROPER GAUGE WIRE AND THE APPROPRIATE LUG CONNECTOR. REFER TO YOUR OFFICE GROUNDING REQUIREMENT MANUAL. 13. PEEL-OFF RACK MASKING WHEN ATTACHING GROUND LUG ON THE RACK. METAL TO METAL CONTACT IS REQUIRED TO ACHIEVE PROPER GROUNDING. ALWAY APPLY NO-OX GEL ON ANY EXPLOSED/UNPAINTED METAL. 14. IT IS RECOMMENDED TO MOUNT MODULE POSITION 1 ON THE TOP, BELOW THE BLANK PANEL WHEN EQUIPMENT CABLE ENTERS THROUGH THE FLOOR. FOR OVER-HEAD CABLE ENTRY, START MODULE POSITION 1 AT THE BOTTOM, ABOVE THE LOWER CABLE TROUGH. CUT-OUT ON THE RACK BASE PROVIDED FOR CABLE ENTRY (PASS-THROUGH) 15 2O 25 3O 35 4O 45 ITEM 040 (FRONT) 8 ITEM 050 (REAR) ITEM 060 (REAR) BAY ID LABEL (ITEM 016) ITEM 030 INSIDE OPENING LOWER CABLE TROUGH ITEM 071) (SEE NOTE 7) UPPER CABLE TROUGH (ITEM 070) M-12 CLEARANCE HOLE (2) PER SIDE (3) M-16 THREADED HOLES ARE PROVIDED ON THE TOP OF THE RACK 1 5 1O 15 2O 25 3O 35 4O 45 REMOVE A/C CUT-OUT COVER PLATE TO INSTALL A/C OUTLET (TYPICAL FRONT & BACK) FRAME GROUND MOUNTING HOLES ARE PROVIDED ON TOP RAIL (MASKED, M-6 TAPPED) BASE DETAIL REMOVE BASE COVER TO ACCESS HOLES INSIDE THE BASE OF THE RACK BACKSIDE A/C OUTLET COVER PLATE FRONTSIDE A/C OUTLET COVER PLATE FRAME GROUND MOUNTING HOLES TYPICAL ON BOTH CHANNEL (MASKED, M-6 TAPPED) LOWER CABLE TROUGH MAY BE REMOVE DURING RACK INSTALLATION (4) ANGLED SLOT FOR ANCHORING RACK TO THE FLOOR 1 5 1O FRONT ELEVATION IBF-RSC021 CATALOG NUMBER

Upload: others

Post on 04-Jul-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

4

3

2

11

2

3

4

DCBA

CBA

1 2

DIMENSIONS IN INCHESTHIRD ANGLE PROJECTION

DRAWING NUMBER

COMMSCOPE, INC.

102.6mm[4.04]

600mm[23.6]

2200mm[86.6]

250mm[9.8]

449.6mm[17.7]

75.2mm[2.96]

474.5mm[18.7]

ITEM DESCRIPTION CATALOG QTY

010600mm WIDW X 2200.00mm HIGH RACK FRAME ASSEMBLY

46 RACK SPACE AT 44.45mm (1.75") SPACINGSRAC-MC2200 1

030 133.35mm HIGH BLANK PANEL AUX-BPP5219M 1

040VERTICAL X-CONNECT WIRING DUCT (PUTTY)

(65.02mm WIDE X 125.98mm DEEP) AUX-XCD001 26

050 227.58mm LONG CABLE SUPPORT BAR (PUTTY) AUX-CB9001 16

060 116.84mm DEEP CABLE SUPPORT BRACKET (PUTTY) AUX-HB1946 14

070UPPER HORIZONTAL CABLE TROUGH (PUTTY)

(133.35MM HIGH X 138.68mm DEEP)---- 1

071HORIZONTAL CABLE TROUGH (PUTTY)(133.35mm HIGH X 138.68mm DEEP)

---- 1

072 CABLE RETAINERS FOR LOWER TROUGH (PUTTY) AUX-0XCRB5 2

091 1/2-AMP, GMT TYPE FUSE (RED) F-1/2 13

092 RACK GROUNDING KIT RAC-MX0617 1

093 6500mm RACK FLOOR TEMPLATE DRAWING ---- 1

094 600mm X 300mm RACK INSULATOR PAD AUX-0X1029 1

095 BAY LINE-UP INSTALLATION REFERENCE DRAWING ---- 1

DATEDWNMCOREV A

25-FEB-17PSC8000019856A

SHT. OFDWN: P. SALAZAR

DO NOT SCALE DRAWING ENGR: P. SALAZAR

AREV660000502

CSIZE

ALL DIMS AND TOLERANCES .XX:�#� N/AARE INCHES UNLESS .XXX:�#� N/AOTHERWISE SPECIFIED ANGULAR:�#� N/A

DSX SKELETON BAYFRONT X-CONNECT

TITLE© 2016 COMMSCOPE, INC.CONFIDENTIAL NOTICE: THESE DRAWINGS AND SPECIFICATIONSARE THE PROPRIETARY PROPERTY OF COMMSCOPE, INC.AND MAY BE USED ONLY FOR THESPECIFIC PURPOSE AUTHORIZED IN WRITING BY COMMSCOPE, INC.

227.58mm [8.96] REAR VERTICAL CABLE BARS

(ITEM 050) EQUIPMENT CABLE TIE-DOWN TYPICAL ON BOTH SIDES

116.84mm [4.60] DEEP HORIZONTAL CABLE BARS

(ITEM 060)

ADC NOTES: 1. USE M-6 RACK SCREWS TO MOUNT ITEMS ON THE RACK UNLESS OTHERWISE SPECIFIED. 2. A COPY OF THIS DRAWING IS INCLUDED WITH THE BAY. SHIP ITEM 091 THROUGH 099 WITH THE BAY, 3. MOUNT (4) RACK GROUND POST TERMINAL ON THE INSIDE SURFACE (4) ON EACH CHANNEL (2) ON TOP AND (2) ON BOTTOM APPLY NO-OX GEL (ITEM 101) ON ANY EXPLOSED METAL. 4. MOUNT WIRING DUCT ON THE FRONT, CABLE SUPPORT BARS AND BRACKETS ON THE BACK AS SHOWN. 5. CUSTOMER WIRING NOTES, TABLE AND DETAILS ARE FOR CUSTOMER USE ONLY. 6. MOUNT REAR SUPPORT BRACKET (ITEM 013) ON THE BASE AS SHOWN ON SHEET 2. PLACE LABEL (ITEM 012) PRINTED "REMOVE/DISCARD" ON BRACKET (ITEM 013). 7. USE ITEM 071 & 072 TO CREATE LOWER CABLE TROUGH 8 SEE PAGE 2 FOR ASSEMBLY DETAIL. CUSTOMER REFERENCE NOTES: 9. THIS CONFIGURATION IS SPACED FOR 5.25" HIGH MODULES. BOTH FRONT AND BACK CABLING MANAGEMENTS ARE PROVIDED. 10. GMT TYPE FUSES OF THE PROPER AMPERAGE ARE REQUIRED TO REPLACE "DUMMY" FUSES IN THE FUSE PANEL TO ACTIVATE MODULES. SEE WIRING NOTES FOR ADC STANDARD WIRING, AND WIRING TABLE FOR TERMINAL CONNECTIONS AND FUSE POSITIONS. CONNECT POWER TO THE FUSE PANEL BEFORE REPLACING FUSES. 11. NEVER INSTALL TELEPHONE EQUIPMENT IN A WET LOCATION OR DURING A LIGHTNING OR ELECTRICAL STORM. WHEN INSTALLING OR MODIFYING TELEPHONE LINES, DISCONNECT LINES AT THE NETWORK INTERFACE BEFORE WORKING WITH UNINSULATED LINES OR TERMINALS. 12. CONNECT OFFICE FRAME GROUND TO THE RACK USING THE PROPER GAUGE WIRE AND THE APPROPRIATE LUG CONNECTOR. REFER TO YOUR OFFICE GROUNDING REQUIREMENT MANUAL. 13. PEEL-OFF RACK MASKING WHEN ATTACHING GROUND LUG ON THE RACK. METAL TO METAL CONTACT IS REQUIRED TO ACHIEVE PROPER GROUNDING. ALWAY APPLY NO-OX GEL ON ANY EXPLOSED/UNPAINTED METAL. 14. IT IS RECOMMENDED TO MOUNT MODULE POSITION 1 ON THE TOP, BELOW THE BLANK PANEL WHEN EQUIPMENT CABLE ENTERS THROUGH THE FLOOR. FOR OVER-HEAD CABLE ENTRY, START MODULE POSITION 1 AT THE BOTTOM, ABOVE THE LOWER CABLE TROUGH.

CUT-OUT ON THE RACK BASE PROVIDED FOR CABLE ENTRY (PASS-THROUGH)

15

2O

25

3O

35

4O

45

ITEM 040 (FRONT) 8ITEM 050 (REAR)ITEM 060 (REAR)

BAY ID LABEL (ITEM 016)

ITEM 030

INSIDE OPENING

LOWER CABLE TROUGH ITEM 071)

(SEE NOTE 7)

UPPER CABLE TROUGH

(ITEM 070)

M-12 CLEARANCE HOLE (2) PER SIDE

(3) M-16 THREADED HOLES ARE PROVIDED ON THE

TOP OF THE RACK

1

5

1O

15

2O

25

3O

35

4O

45

REMOVE A/C CUT-OUT COVER PLATE TO INSTALL A/C OUTLET (TYPICAL FRONT & BACK)

FRAME GROUND MOUNTING HOLES ARE PROVIDED ON TOP RAIL (MASKED, M-6 TAPPED)

BASE DETAIL

REMOVE BASE COVER TO ACCESS HOLES INSIDE THE BASE OF THE RACK

BACKSIDE A/C OUTLET COVER PLATE

FRONTSIDE A/C OUTLET COVER PLATE

FRAME GROUND MOUNTING HOLES TYPICAL ON BOTH CHANNEL (MASKED, M-6 TAPPED)

LOWER CABLE TROUGH MAY BE REMOVE DURING

RACK INSTALLATION

(4) ANGLED SLOT FOR ANCHORING RACK TO THE FLOOR 1

5

1O

FRONT ELEVATION

IBF-RSC021

CATALOG NUMBER

4

3

2

11

2

3

4

DCBA

CBA

2 2

DIMENSIONS IN INCHESTHIRD ANGLE PROJECTION

DRAWING NUMBER

COMMSCOPE, INC.

228.60mm[9.00]

152.40mm[6.00]

529.84mm[20.86]

196.088mm[7.72] 249.936mm

[9.84]

599.16mm[23.59]

395.22mm[15.56]

142.24mm[5.60]

58.42mm[2.30]

CUSTOMER WIRING TABLE (REF. ONLY)

FROM DSX PANEL TO FUSE PANEL FUSE POSITION AMPERAGEPANEL POSITION TERMINAL ROW P/N

DSX MODULEPOSITION 1

-48V NEG (-)1

POSITION 1(1/2 AMP)GND POS (+)

DSX MODULEPOSITION 2

-48V NEG (-)2

POSITION 2(1/2 AMP)GND POS (+)

REPEATED WIRING PATTERN

DSX MODULEPOSITION 13

-48V NEG (-)13

POSITION 13(1/2 AMP)GND POS (+)

SHT. OFDWN: P. SALAZAR

DO NOT SCALE DRAWING ENGR: P. SALAZAR

AREV660000502

CSIZE

ALL DIMS AND TOLERANCES .XX:�#� N/AARE INCHES UNLESS .XXX:�#� N/AOTHERWISE SPECIFIED ANGULAR:�#� N/A

DSX SKELETON BAYFRONT X-CONNECT

TITLE© 2016 COMMSCOPE, INC.CONFIDENTIAL NOTICE: THESE DRAWINGS AND SPECIFICATIONSARE THE PROPRIETARY PROPERTY OF COMMSCOPE, INC.AND MAY BE USED ONLY FOR THESPECIFIC PURPOSE AUTHORIZED IN WRITING BY COMMSCOPE, INC.

CUSTOMER REFERENCE WIRING NOTES: 15. THE FOLLOWING NOTES ARE WIRING PROCEDURES PER ADC STANDARDS. 16. MODULE POSITION 1 COUNT STARTS FROM THE TOP, BELOW THE FUSE PANEL WHEN EQUIPMENT CABLES ENTER FROM THE FLOOR. MODULE POSITION 1 COUNT STARTS FROM THE BOTTOM, ABOVE THE LOWER TROUGH WHEN EQUIPMENT CABLES ENTER ABOVE THE RACK. 17. USE COLOR CODED INSULATED WIRES TO IDENTIFY WIRE CONNECTIONS. 18. BLUE OR RED WIRE FOR BATTERY (-48VDC), BLACK WIRE FOR BATTERY RETURN (GND) AND GREEN WIRE FOR CHASSIS/FRAME GROUND. OTHER WIRE COLOR MAY BE USED AS THEY ARE DETERMINED BY LOCAL PRACTICES. 19. CRIMP PROPER TYPE & SIZE TERMINAL LUG ON WIRE END BEFORE TERMINATING ON ANY SCREW-DOWN TERMINAL. 20. TERMINATE LUGS ON MODULE TERMINALS AND ROUTE THE OTHER END OF THE POWER WIRES TO THE BACKSIDE OF THE FUSE PANEL. WIRE-WRAP ON ITS RESPECTIVE PIN POSITION ON THE FUSE PANEL OUTPUT TERMINALS. SECURE ALL WIRING ON THE BAY. 21. TERMINATE GREEN WIRES TO THE CHASSIS GROUND TERMINAL OF EACH MODULE AND ROUTE THE OTHER END UP TO THE GROUND POST

TERMINALS LOCATED INSIDE THE RACK CHANNEL .

RACK INSTALLATION NOTES: 22. USE RACK ISOLATOR PAD INCLUDED WITH THIS BAY AS YOUR FLOOR TEMPLATE. 23. POSITION PAD ON THE EXACT LOCATION OF THE BAY, NOTE FRONT & BACK SIDE. MARK THE FLOOR, NOTE TO ALWAY PLACE YOUR MARK ON THE CENTER OF ANY SLOT (IF PREMITTED). 24. FILE ALL SHARP EDGES AFTER DRILLING AND CUTTING. USE EDGE PROTECTOR AROUND CABLE ENTRY HOLES. 25. USE THE PROPER INSTALLATION KIT DICTATED BY THE OFFICE/SITE REQUIREMENTS. 26. REMOVE THE REAR/BASE SUPPORT BRFACKET BEFORE INSTALLING THIS BAY IN PLACE. 27. SEE "PAD DETAIL" FOR ISOLATOR PAD DIMENSION. 28. M-12 HARDWARE ARE PROVIDED WITH THIS BAY TO BOLT RACK SIDE TO SIDE. DO NOT OVER-TIGHTEN NUT, THIS MAY CAUSE RACK TO BOW.

VERTICAL CABLE DUCT ASSEMBLY

REAR/BASE SUPPORT BRACKET THIS BRACKET WILL HELP KEEP

THE BAY STANDING ON IT UPRIGHT POSITION BEFORE INSTALLATION. CUSTOMER TO REMOVE AND DISCARD

BRACKET DURING BAY INSTALLATION

EQUIPMENT CABLE (IN/OUT) SUPPORT BARS ARE PROVIDED ON BOTH SIDE OF THE BAY

USE THIS BARS TO TIE-DOWN

CABLES SECURELY IN PLACE

HORIZONTAL BARS ARE PROVIDED ACROSS THE BACKSIDE FOR SECURING IN/OUT CABLE HARNESS

FEEDING INTO EACH MODULE

ROUTE X-CONNECT CABLING THROUGH CABLE BRACKET BRACKETS ARE TYPICAL

ON BOTH SIDE OF THE BAY

(2) LARGE HOLES ARE PROVIDED ON BOTH SIDE OF THE RACK FOR A/C CABLE PASS-THROUGH

GROUND LUG MOUNTING HOLES ARE PROVIDED INSIDE BOTH CHANNEL FOR FRAME GROUND

TERMINATION ON THE RACK BASE REMOVE THE BASE COVER

TO ACCESS MOUNTING HOLES

REMOVABLE BASE COVER

"REMOVE/DISCARD" LABEL

USE THIS HOLE FOR BOLTING RACK SIDE-BY-SIDE

20.625mm X 71.425mm [.812 X 2.812]

45�$� ANGLED SLOTS

�n�38.10mm [1.50]

PAD DETAIL

BACKSIDE

USE THESE HOLES FOR RACK FRAME GROUND ENTRY

040