AEED, Advanced Energy Engineering & Design, Inc CHATTANOOGA, TN 37405 BUS. (423) 752-3438 FAX (423) 752-1369 P.O. BOX 4934 408 McCALLIE AVE inc. AEED JOB NO. 029-15 COPYRIGHT NOTICE THE DRAWINGS ARE THE PROPERTY OF RIVER STREET ARCHITECTURE LLC. ANY USE, REUSE, REPRODUCTION, DISPLAY OR SALE OF THESE DRAWINGS WITHOUT THE EXPRESS WRITTEN CONSENT OF THE ARCHITECT IS STRICTLY PROHIBITED. 714 cherry street, chattanooga, tennessee 37402 p.423 634 0806 f.423 752 8499 www.river-st-architecture.com Release Date: Project No.: 3/31/2015 10:17:24 AM 12055 GATEWAY WEST BLVD, EL PASO , TX COURTYARD BY MARRIOTT ZARAGOZA HOTEL PARTNERS, LLC FIRE PROTECTION FP0.1 COVER SHEET FIRE PROTECTION GENERAL NOTES ABBREVIATIONS AFC - ABOVE FINISHED CEILING AFF - ABOVE FINISHED FLOOR AFG - ABOVE FINISHED GRADE ALV - ALARM VALVE BMS - BUILDING MANAGEMENT SYSTEM Cr - CROSS DPV - DRY PIPE VALVE E - 90 DEGREE ELBOW FACP- FIRE ALARM CONTROL PANEL FBO - FURNISHED BY OTHERS FP - FIRE PUMP GV - GATE VALVE JP - JOCKEY PUMP NTS - NOT TO SCALE FA - FIRE ALARM EE - 45 DEGREE ELBOW BFP - BACK FLOW PREVENTER BFG - BELOW FINISH GRADE AHJ - AUTHORITY HAVING JURISDICTION BV - BUTTERFLY (wafer) CHECK VALVE CV - SWING CHECK VALVE DeL V - DELUGE VALVE (E) - EXISTING FS - FLOW SWITCH GC - GENERAL CONTRACTOR NIC - NOT IN CONTRACT IAW - IN ACCORDANCE WITH PAV - PREACTION VALVE PIV - POST INDICATOR VALVE FLEXIBLE CONNECTION SYMBOLS RECESSED PENDANT SPRINKLER (RESIDENTIAL TYPE) Lt.E - LONG TURN ELBOW PA - PUBLIC ADDRESS OS&Y - OUTSIDE SCREW & YOKE OC - ON CENTER St - STRAINER T- TEE-FLOW TURNED 90 DEGREES TS - TAMPER SWITCH UG - UNDERGROUND UNO - UNLESS NOTED OTHERWISE WCV - BUTTERFLY (wafer) CHECK VALVE HORIZONTAL SIDEWALL SPRINKLER FIRE PROTECTION LEGEND UPRIGHT SPRINKLER 1. SCOPE OF WORK A. THE CONTRACTOR IS RESPONSIBLE FOR ALL WORK, MATERIALS, AND LABOR REQUIRED TO SATISFY A COMPLETE WORKING SYSTEM WHETHER SPECIFIED OR IMPLIED. B. THE WORK IS TO BE PERFORMED IN STRICT COMPLIANCE WITH NFPA 13 (2002 EDITION), ALL CODES AND OTHER NFPA REGULATIONS GOVERNING WORK OF THIS NATURE. C. THE CONTRACTOR SHALL EXAMINE THE PROPOSED SITE AND SHALL DETERMINE FOR HIMSELF THE CONDITIONS THAT MAY EFFECT THE WORK BEFORE SUBMITTING ANY PROPOSAL. NO ALLOWANCE SHALL BE MADE IF THE CONTRACTOR FAILS TO MAKE SUCH EXAMINATIONS. D. ALL EQUIPMENT AND MATERIALS SHALL BE AS SPECIFIED OR AN "APPROVED EQUAL" BY THE ENGINEER OR ARCHITECT. 2. PERMITS A. THE CONTRACTOR SHALL SECURE ALL PERMITS OR APPLICATIONS AND PAY ANY AND ALL FEES. B. THE CONTRACTOR SHALL BE A LICENSED FIRE SPRINKLER CONTRACTOR. 3. SHOP DRAWINGS A. SUBMIT A MATERIAL LIST AND SHOP DRAWINGS FOR MAJOR EQUIPMENT TO THE ARCHITECT/ENGINEER AND STATE FIRE MARSHALL FOR APPROVAL. THE CONTRACTOR SHALL SUBMIT SIX SETS OF SHOP DRAWINGS AND THEY SHALL BE CLEARLY LABELED. 4. SPRINKLER HEADS A. WHERE SPRINKLER HEADS ARE INSTALLED IN ACOUSTICAL CEILING TILES, HEADS SHALL BE CENTERED IN THE TILE. B. SPRINKLER HEADS ARE TO BE PROVIDED IN THE STYLE AND COLOR/FINISH AS SPECIFIED ON THE DRAWING. HOWEVER, CONTRACTOR TO CONFIRM WITH OWNER/ARCHITECT PRIOR TO PURCHASE THAT THE SPECIFIED COLOR/FINISH IS ACCEPTABLE. 5. SPRINKLER PIPING A. PIPE SHALL BE MADE TO ANY OF THE SPECIFICATIONS LISTED. WELDING WILL NOT BE PERMITTED IF THERE ARE ANY SPRINKLERS CONNECTED THERETO. x ASTM A53 x ASTM A120 x ASTM A135 B. PIPING MATERIAL MAY BE SCHEDULE 10 (THINWALL) PROVIDED JOINTS ARE MADE BY ROLL-GROOVE COUPLING. THREADING WILL NOT BE PERMITTED ON SCHEDULE 10 (THINWALL). C. PIPING MATERIAL MAY BE SCHEDULE 40 WITH FLANGED, ROLL-GROOVED COUPLINGS, OR THREADED JOINTS. D. DRY SPRINKLER PIPING SHALL BE SLOPED TO DRAIN. LOW POINT DRAINS SHALL BE PROVIDED AT ANY CHANGE IN PITCH. 6. PIPE SUPPORTS A. ALL HANGERS MUST BE AN NFPA 13 APPROVED TYPE. NO SPRINKLER PIPING IS TO BE SUPPORTED FROM ANY MECHANICAL OR ELECTRICAL DEVICES. B. ALL PIPE SHALL BE SUPPORTED FROM THE BUILDING STRUCTURE IN A NEAT AND WORKMANLIKE MANNER. VERTICAL RISERS SHALL BE SUPPORTED AT EACH FLOOR LEVEL WITH STEEL PIPE CLAMPS. THE USE OF WIRE OR STRAP METAL HANGERS TO SUPPORT PIPES WILL NOT BE PERMITTED. HANGING PIPES FROM OTHER PIPES WILL NOT BE PERMITTED. PIPING SHALL BE CAREFULLY COORDINATED BEFORE INSTALLATION WITH OTHER SYSTEMS AND EQUIPMENT IN CHASES AND OTHER CONGESTED AREAS. C. SEISMIC PERFORMANCE: FIRE-SUPPRESSION PIPING BRACING SHALL BE IN ACCORDANCE TO NFPA 13. 7. WORKING PLANS A. THE DRAWINGS INCLUDED AS PART OF THIS SET OF CONSTRUCTION DOCUMENTS ARE TO PROVIDE ENGINEERING DESIGN INTENT. THE CONTRACTOR SHALL PREPARE WORKING DRAWINGS (AS DEFINED BE NFPA 13) WHICH SHALL INCLUDE HYDRAULIC CALCULATIONS AND WILL BE SUBMITTED TO THE ENGINEER AND FIRE MARSHALL FOR APPROVAL. 8. TESTS A. ACCEPTANCE AND HYDROSTATIC TESTS TO BE PERFORMED IN ACCORDANCE WITH CHAPTER 10 OF NFPA 13. 9. MISCELLANEOUS A. DO NOT SCALE THIS DRAWING FOR EXACT DIMENSIONS. VERIFY ALL FIGURES, CONDITIONS, AND DIMENSIONS AT THE JOB SITE. B. THE SPRINKLER PLANS ARE INTENDED TO BE DIAGRAMATIC. THEY ARE NOT INTENDED TO SHOW EVERY ITEM IN ITS EXACT LOCATION. 10. GUARANTEE A. MATERIALS, EQUIPMENT AND INSTALLATION SHALL BE GUARANTEED FOR PERIOD OF ONE(1) YEAR FROM DATE OF ACCEPTANCE. DEFECTS WHICH APPEAR DURING THAT PERIOD SHALL BE CORRECTED AT THE SPRINKLER CONTRACTOR'S EXPENSE. HAZARD CLASSIFICATIONS A. OFFICES AND CONFERENCE AREAS: LIGHT HAZARD B. GUEST ROOMS: LIGHT HAZARD C. MECHANICAL EQUIPMENT ROOMS: ORDINARY HAZARD, GROUP 2 D. LAUNDRY ROOM: ORDINARY HAZARD, GROUP 1 E. PORTE COCHERE ORDINARY HAZARD, GROUP 1 F. ELECTRICAL ROOM: ORDINARY HAZARD, GROUP 1 FLOW TEST DATA DATA PROVIDE BY: EL PASO FIRE DEPARTMENT DATE: 12-30-2014 TEST PERFORMED BY: CHRISTOPHER TIJERINA TEST HYDRANT: 10835 STATIC PRESSURE: 145 PSI RESIDUAL PRESSURE: 143 PSI FLOW: 787 GPM REQUIRED CONDITIONS: DESIGN AREA #1: 70 PSI @ 641 GPM (W/ 250 GPM HOSE ALLOWANCE) DESIGN AREA #2: 50 PSI @ 148 GPM (W/ 100 GPM HOSE ALLOWANCE) DESIGN AREA #3: 50 PSI @ 176 GPM (W/ 100 GPM HOSE ALLOWANCE) SAFETY FACTOR: 109% (MINIMUM 10% REQUIRED) ADEQUATE WATER SERVICE AVAILABLE: YES DRY SYSTEM VOLUME: 73 GALLONS FLOW SWITCH FLOOR CONTROL VALVE PENDANT SPRINKLER UPRIGHT SPRINKLER STANDPIPE DDCA - DOUBLE DETECTOR CHECK VALVE ASSEMBLY FDC - FIRE DEPARTMENT CONNECTION RECESSED PENDANT SPRINKLER (COMMERCIAL TYPE) FP0.1 FIRE PROTECTION - COVER SHEET FP1.2 FIRE PROTECTION - 2ND FLOOR PLAN 04/27/15 PROGRESS SET x FIRE PROTECTION SHEET INDEX TITLE # DATE FP1.1 FIRE PROTECTION - 1ST FLOOR PLAN FP1.3 FIRE PROTECTION - 3RD FLOOR PLAN FP1.4 FIRE PROTECTION - 4TH FLOOR PLAN FIRE PROTECTION - DETAILS FP2.1 ISSUE LOG x x x x x 90 % CD x x x x x x 05/20/15 x x x x x x 100 % REVIEW SET 06/25/15

Upload: others

Post on 05-Jul-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 90 % CD - F.T. James...AEED, Advanced Energy Engineering & Design, Inc CHATTANOOGA, TN 37405 BUS. (423) 752-3438 FAX (423) 752-1369 P.O. BOX 4934 inc.408 McCALLIE AVE AEED JOB NO.029-15

AEED,

Advanced Energy Engineering & Design, Inc

CHATTANOOGA, TN 37405

BUS. (423) 752-3438

FAX (423) 752-1369

P.O. BOX 4934

408 McCALLIE AVE

inc.

AEED JOB NO.029-15

COPYRIGHT NOTICE

THE DRAWINGS ARE THE

PROPERTY OF RIVER STREET

ARCHITECTURE LLC. ANY USE,

REUSE, REPRODUCTION,

DISPLAY OR SALE OF THESE

DRAWINGS WITHOUT THE

EXPRESS WRITTEN CONSENT

OF THE ARCHITECT IS

STRICTLY PROHIBITED.

71

4 ch

erry stre

et, ch

atta

no

og

a, te

nn

esse

e 3

74

02

p.4

23

6

34

0

80

6 f.4

23

7

52

8

49

9 w

ww

.rive

r-st-a

rch

ite

ctu

re

.co

m

Release Date:

Project No.:

3/3

1/2

01

5 1

0:1

7:2

4 A

M

12055 G

AT

EW

AY

W

ES

T B

LV

D, E

L P

AS

O , T

X

CO

UR

TY

AR

D B

Y M

AR

RIO

TT

ZA

RA

GO

ZA

H

OT

EL P

AR

TN

ER

S, LLC

FIRE PROTECTION

FP0.1

COVER SHEET

FIRE PROTECTION GENERAL NOTES

ABBREVIATIONS

AFC - ABOVE FINISHED CEILING

AFF - ABOVE FINISHED FLOOR

AFG - ABOVE FINISHED GRADE

ALV - ALARM VALVE

BMS - BUILDING MANAGEMENT SYSTEM

Cr - CROSS

DPV - DRY PIPE VALVE

E - 90 DEGREE ELBOW

FACP- FIRE ALARM CONTROL PANEL

FBO - FURNISHED BY OTHERS

FP - FIRE PUMP

GV - GATE VALVE

JP - JOCKEY PUMP

NTS - NOT TO SCALE

FA - FIRE ALARM

EE - 45 DEGREE ELBOW

BFP - BACK FLOW PREVENTER

BFG - BELOW FINISH GRADE

AHJ - AUTHORITY HAVING JURISDICTION

BV - BUTTERFLY (wafer) CHECK VALVE

CV - SWING CHECK VALVE

DeL V - DELUGE VALVE

(E) - EXISTING

FS - FLOW SWITCH

GC - GENERAL CONTRACTOR

NIC - NOT IN CONTRACT

IAW - IN ACCORDANCE WITH

PAV - PREACTION VALVE

PIV - POST INDICATOR VALVE

FLEXIBLE CONNECTION

SYMBOLS

RECESSED PENDANT SPRINKLER (RESIDENTIAL TYPE)

Lt.E - LONG TURN ELBOW

PA - PUBLIC ADDRESS

OS&Y - OUTSIDE SCREW & YOKE

OC - ON CENTER

St - STRAINER

T- TEE-FLOW TURNED 90 DEGREES

TS - TAMPER SWITCH

UG - UNDERGROUND

UNO - UNLESS NOTED OTHERWISE

WCV - BUTTERFLY (wafer) CHECK VALVE

HORIZONTAL SIDEWALL SPRINKLER

FIRE PROTECTION LEGEND

UPRIGHT SPRINKLER

1. SCOPE OF WORK

A. THE CONTRACTOR IS RESPONSIBLE FOR ALL WORK, MATERIALS, AND LABOR REQUIRED TO SATISFY A COMPLETE WORKING SYSTEM

WHETHER SPECIFIED OR IMPLIED.

B. THE WORK IS TO BE PERFORMED IN STRICT COMPLIANCE WITH NFPA 13 (2002 EDITION), ALL CODES AND OTHER NFPA REGULATIONS

GOVERNING WORK OF THIS NATURE.

C. THE CONTRACTOR SHALL EXAMINE THE PROPOSED SITE AND SHALL DETERMINE FOR HIMSELF THE CONDITIONS THAT MAY EFFECT THE

WORK BEFORE SUBMITTING ANY PROPOSAL. NO ALLOWANCE SHALL BE MADE IF THE CONTRACTOR FAILS TO MAKE SUCH

EXAMINATIONS.

D. ALL EQUIPMENT AND MATERIALS SHALL BE AS SPECIFIED OR AN "APPROVED EQUAL" BY THE ENGINEER OR ARCHITECT.

2. PERMITS

A. THE CONTRACTOR SHALL SECURE ALL PERMITS OR APPLICATIONS AND PAY ANY AND ALL FEES.

B. THE CONTRACTOR SHALL BE A LICENSED FIRE SPRINKLER CONTRACTOR.

3. SHOP DRAWINGS

A. SUBMIT A MATERIAL LIST AND SHOP DRAWINGS FOR MAJOR EQUIPMENT TO THE ARCHITECT/ENGINEER AND STATE FIRE MARSHALL

FOR APPROVAL. THE CONTRACTOR SHALL SUBMIT SIX SETS OF SHOP DRAWINGS AND THEY SHALL BE CLEARLY LABELED.

4. SPRINKLER HEADS

A. WHERE SPRINKLER HEADS ARE INSTALLED IN ACOUSTICAL CEILING TILES, HEADS SHALL BE CENTERED IN THE TILE.

B. SPRINKLER HEADS ARE TO BE PROVIDED IN THE STYLE AND COLOR/FINISH AS SPECIFIED ON THE DRAWING. HOWEVER, CONTRACTOR

TO CONFIRM WITH OWNER/ARCHITECT PRIOR TO PURCHASE THAT THE SPECIFIED COLOR/FINISH IS ACCEPTABLE.

5. SPRINKLER PIPING

A. PIPE SHALL BE MADE TO ANY OF THE SPECIFICATIONS LISTED. WELDING WILL NOT BE PERMITTED IF THERE ARE ANY SPRINKLERS

CONNECTED THERETO.

ASTM A53

ASTM A120

ASTM A135

B. PIPING MATERIAL MAY BE SCHEDULE 10 (THINWALL) PROVIDED JOINTS ARE MADE BY ROLL-GROOVE COUPLING. THREADING WILL NOT

BE PERMITTED ON SCHEDULE 10 (THINWALL).

C. PIPING MATERIAL MAY BE SCHEDULE 40 WITH FLANGED, ROLL-GROOVED COUPLINGS, OR THREADED JOINTS.

D. DRY SPRINKLER PIPING SHALL BE SLOPED TO DRAIN. LOW POINT DRAINS SHALL BE PROVIDED AT ANY CHANGE IN PITCH.

6. PIPE SUPPORTS

A. ALL HANGERS MUST BE AN NFPA 13 APPROVED TYPE. NO SPRINKLER PIPING IS TO BE SUPPORTED FROM ANY MECHANICAL OR

ELECTRICAL DEVICES.

B. ALL PIPE SHALL BE SUPPORTED FROM THE BUILDING STRUCTURE IN A NEAT AND WORKMANLIKE MANNER. VERTICAL RISERS SHALL BE

SUPPORTED AT EACH FLOOR LEVEL WITH STEEL PIPE CLAMPS. THE USE OF WIRE OR STRAP METAL HANGERS TO SUPPORT PIPES WILL

NOT BE PERMITTED. HANGING PIPES FROM OTHER PIPES WILL NOT BE PERMITTED. PIPING SHALL BE CAREFULLY COORDINATED

BEFORE INSTALLATION WITH OTHER SYSTEMS AND EQUIPMENT IN CHASES AND OTHER CONGESTED AREAS.

C. SEISMIC PERFORMANCE: FIRE-SUPPRESSION PIPING BRACING SHALL BE IN ACCORDANCE TO NFPA 13.

7. WORKING PLANS

A. THE DRAWINGS INCLUDED AS PART OF THIS SET OF CONSTRUCTION DOCUMENTS ARE TO PROVIDE ENGINEERING DESIGN INTENT.

THE CONTRACTOR SHALL PREPARE WORKING DRAWINGS (AS DEFINED BE NFPA 13) WHICH SHALL INCLUDE HYDRAULIC CALCULATIONS

AND WILL BE SUBMITTED TO THE ENGINEER AND FIRE MARSHALL FOR APPROVAL.

8. TESTS

A. ACCEPTANCE AND HYDROSTATIC TESTS TO BE PERFORMED IN ACCORDANCE WITH CHAPTER 10 OF NFPA 13.

9. MISCELLANEOUS

A. DO NOT SCALE THIS DRAWING FOR EXACT DIMENSIONS. VERIFY ALL FIGURES, CONDITIONS, AND DIMENSIONS AT THE JOB SITE.

B. THE SPRINKLER PLANS ARE INTENDED TO BE DIAGRAMATIC. THEY ARE NOT INTENDED TO SHOW EVERY ITEM IN ITS EXACT LOCATION.

10. GUARANTEE

A. MATERIALS, EQUIPMENT AND INSTALLATION SHALL BE GUARANTEED FOR PERIOD OF ONE(1) YEAR FROM DATE OF ACCEPTANCE.

DEFECTS WHICH APPEAR DURING THAT PERIOD SHALL BE CORRECTED AT THE SPRINKLER CONTRACTOR'S EXPENSE.

HAZARD CLASSIFICATIONS

A. OFFICES AND CONFERENCE AREAS: LIGHT HAZARD

B. GUEST ROOMS: LIGHT HAZARD

C. MECHANICAL EQUIPMENT ROOMS: ORDINARY HAZARD, GROUP 2

D. LAUNDRY ROOM: ORDINARY HAZARD, GROUP 1

E. PORTE COCHERE ORDINARY HAZARD, GROUP 1

F. ELECTRICAL ROOM: ORDINARY HAZARD, GROUP 1

FLOW TEST DATA

DATA PROVIDE BY: EL PASO FIRE DEPARTMENT

DATE: 12-30-2014

TEST PERFORMED BY: CHRISTOPHER TIJERINA

TEST HYDRANT: 10835

STATIC PRESSURE: 145 PSI

RESIDUAL PRESSURE: 143 PSI

FLOW: 787 GPM

REQUIRED CONDITIONS:

DESIGN AREA #1: 70 PSI @ 641 GPM (W/ 250 GPM HOSE ALLOWANCE)

DESIGN AREA #2: 50 PSI @ 148 GPM (W/ 100 GPM HOSE ALLOWANCE)

DESIGN AREA #3: 50 PSI @ 176 GPM (W/ 100 GPM HOSE ALLOWANCE)

SAFETY FACTOR: 109% (MINIMUM 10% REQUIRED)

ADEQUATE WATER SERVICE AVAILABLE: YES

DRY SYSTEM VOLUME: 73 GALLONS

FLOW SWITCH

FLOOR CONTROL VALVEPENDANT SPRINKLER

UPRIGHT SPRINKLER

STANDPIPE

DDCA - DOUBLE DETECTOR CHECK VALVE ASSEMBLY

FDC - FIRE DEPARTMENT CONNECTION

RECESSED PENDANT SPRINKLER (COMMERCIAL TYPE)

FP0.1 FIRE PROTECTION - COVER SHEET

FP1.2 FIRE PROTECTION - 2ND FLOOR PLAN

04/27/15

P

R

O

G

R

E

S

S

S

E

T

x

FIRE PROTECTION SHEET INDEX

TITLE#

DATE

FP1.1 FIRE PROTECTION - 1ST FLOOR PLAN

FP1.3 FIRE PROTECTION - 3RD FLOOR PLAN

FP1.4 FIRE PROTECTION - 4TH FLOOR PLAN

FIRE PROTECTION - DETAILSFP2.1

ISSUE LOG

x

x

x

x

x

9

0

%

C

D

x

x

x

x

x

x

05/20/15

x

x

x

x

x

x

1

0

0

%

R

E

V

I

E

W

S

E

T

06/25/15

Page 2: 90 % CD - F.T. James...AEED, Advanced Energy Engineering & Design, Inc CHATTANOOGA, TN 37405 BUS. (423) 752-3438 FAX (423) 752-1369 P.O. BOX 4934 inc.408 McCALLIE AVE AEED JOB NO.029-15

S

S

S

S S

S

S

SS

GYP-1

GYP-1

GYP-1

ACT-1

GYP-1

ACT-3

GYP-1

GYP-1

GYP-1

ACT-1

ACT-1

ACT-1

ACT-3

ACT-3

LAUNDRY

150

BREAK ROOM

143

MEN

141

WOMEN

140

CORRIDOR

144

CORRIDOR

1000

LINEN

149

WORK ROOM

153

ACT-1

ACT-3

OFFICE

148

ENGINEER

145

KING

133

KING

131

QQ - HEARING

129

KING

128

KING

130

KITCHEN

166

S BAR

165

LOBBY

163

MEETING ROOM

167

RECEPTION

162

MARKET

VESTIBULE

160

PBX

152

SWITCH GEAR

151

KING - HEARING

107

ACC. QQ -

SHOWER

105

QQ

103

KING

101

QQ

102

ACC. KING -

SHOWER

104

CT-2HR

WATER /

MECHANICAL

146

L54

L54L54

L54

L54

L54

L54

L54L54

L54 L54

L54 L54

L54L54

L54 L54

L54 L54

L54 L54

L31

L57

L57 L57

L10 L10 L10

L10 L10 L10 L10

L10L10L10L10

L10 L10

L10

L29

L10

L10

L10 L10

L31

L31

L31

L31

L22

L22

L22

L22

L22

L22L22

L22

L57

L57

L60 L60

L60

L57

D04

L60

L60

L54

L54

L54

L54

L54

L54

L57

L57L57 L57 L57L57L57

L60 L60 L60

L60L60

D04 D04

L60

L33

L33

L33L33L33

L33L33L33

L33

L33

L33 L33

L33

L29 L29

L29L29

L33

L33

L31

L29

L22

L22

L33L33L33L33

L33 L33

L33L33

L31L31

L33 L33

ACT-1

ACT-1

ACT-1

ACT-1

GYP-1

GYP-1

GYP-1

D93

GYP-EX

GYP-EX

GYP-EX

GYP-1

GYP-1

GYP-1

ACT-1

L33

L33

A0.7

GYP-EX

GYP-EX

GYP-EX

GYP-EX

GYP-EX

GYP-EX

GYP-EX

GYP-EX

GYP-EX

GYP-EX

409

GYP-1

ACT-1

ACT-1

ACT-1

400

408

400

400

409

L57

L31

L31

GYP-1

L57

GYP-1

D93

FIRE MAIN ENTERS BUILDING

SEE SHEET FP2.1 FOR RISER DETAIL

ELECTRONIC ALARM BELL

4" CLASS 1

COMBINATION RISER

4" CLASS 1 MANUAL WET

STANDPIPE

DRY PENDANTS FOR WALK-IN

COOLER AND FREEZER

FIRE MAIN (SEE CIVIL FOR CONTINUATION AND

LOCATION OF DDCA, PIV, AND FDC.)

SLEEVE PIPE WALL-PENETRATION WATERTIGHT

DESIGN AREA 1

SLEEVE PIPE WALL-PENETRATION

WATERTIGHT

DESIGN AREA 4

FP1.1

1

SCALE: 1/8"= 1'-0"

FIRE PROTECTION - SPRINKLER - 1ST FLOOR

AEED,

Advanced Energy Engineering & Design, Inc

CHATTANOOGA, TN 37405

BUS. (423) 752-3438

FAX (423) 752-1369

P.O. BOX 4934

408 McCALLIE AVE

inc.

AEED JOB NO.029-15

COPYRIGHT NOTICE

THE DRAWINGS ARE THE

PROPERTY OF RIVER STREET

ARCHITECTURE LLC. ANY USE,

REUSE, REPRODUCTION,

DISPLAY OR SALE OF THESE

DRAWINGS WITHOUT THE

EXPRESS WRITTEN CONSENT

OF THE ARCHITECT IS

STRICTLY PROHIBITED.

71

4 ch

erry stre

et, ch

atta

no

og

a, te

nn

esse

e 3

74

02

p.4

23

6

34

0

80

6 f.4

23

7

52

8

49

9 w

ww

.rive

r-st-a

rch

ite

ctu

re

.co

m

Release Date:

Project No.:

3/3

1/2

01

5 1

0:1

7:2

4 A

M

12055 G

AT

EW

AY

W

ES

T B

LV

D, E

L P

AS

O , T

X

CO

UR

TY

AR

D B

Y M

AR

RIO

TT

ZA

RA

GO

ZA

H

OT

EL P

AR

TN

ER

S, LLC

FIRE PROTECTION

FP1.1

SPRINKLER

1ST FLOOR

FIRE PROTECTION PLAN NOTES

1. ALL TAMPER AND FLOW SWITCHES MUST BE CONNECTED TO A MONITORED FIRE

ALARM SYSTEM.

2. FIRE PROTECTION CONTRACTOR TO OBTAIN OWNER/ARCHITECT APPROVAL OF

SPRINKLER TYPE AND FINISH PRIOR TO PURCHASING.

3. FIRE PROTECTION CONTRACTOR TO PROVIDE COVERAGE AS INDICATED ON

DRAWING.

4. SEE ARCHITECTURAL DRAWINGS FOR SMOKE AND FIRE RATED WALLS.

5. SPRINKLER SYSTEMS SHALL BE EQUIPPED WITH FLOOR CONTROL VALVE

ASSEMBLIES ( SEE SHEET FP2.1 FOR DETAIL) AT ALL CONNECTIONS TO RISERS.

SPRINKLER HEAD SCHEDULE (FOR THIS SHEET)

SYMBOL

QTY

MFG. SIN TYPE RESPONSE TEMPERATURE K-FACTOR DESCRIPTION

39 VICTAULIC V2740 PENDANT

QUICK

155 °F 4.9

WHITE, SEMI-RECESSED PENDANT SPRINKLER (RESIDENTIAL TYPE)

130 VICTAULIC V2707 PENDANT

QUICK

155 °F 5.6

WHITE, SEMI-RECESSED PENDANT SPRINKLER (COMMERCIAL TYPE)

22 VICTAULIC V3608 PENDANT

QUICK

175 °F 8.0

BRASS, DRY PENDANT SPRINKLER

1 VICTAULIC V2707 PENDANT

QUICK

155 °F 5.6

BRASS, LAUNDRY CHUTE PENDANT SPRINKLER

8 VICTAULIC V2703 UPRIGHT

QUICK

155 °F 5.6

BRASS, UPRIGHT SPRINKLER

4 VICTAULIC V3410 SIDEWALL

QUICK

155 °F 8.0

WHITE, SIDEWALL SPRINKLER

Page 3: 90 % CD - F.T. James...AEED, Advanced Energy Engineering & Design, Inc CHATTANOOGA, TN 37405 BUS. (423) 752-3438 FAX (423) 752-1369 P.O. BOX 4934 inc.408 McCALLIE AVE AEED JOB NO.029-15

KING

201

QQ

203

QQ

205

KING

207

KING

209

KING

211

KING

213

KING

215

QQ

217

QQ

219

KING

221

KING

223

KING

225

QQ

227

QQ

229

KING

231

KING

233

KING

230

KING

228

QQ

226

KING

224

KING

222

QQ

220

QQ

218

ACC. QQ INLINE

SUITE

216

KING

210

KING

208

KING

206

ACC. KING

204

QQ

202

KING

214

ELECTRICAL

2005

LINEN

2004

COMPUTER/

COMM ROOM

GYP-1

ACT-1

ICE

D04

L60L60

L60

L57

L60 L60

L57

L60 L60

D04

L57

L60 L60

L60L60

D04

L57

L60 L60

L60 L60

D04

L60 L60

L60

L57

L60

L54

L54

L54

L54

L54

L54

L57

L60L60

L60 L60

D04

GYP-1

L60 L60

L57

L60 L60

D04

L60

L57

L60 L60

L60

D04

L60

L57

L57

L57

L29 L29

L33

L33 L33

L33

L31

L31

ACT-1ACT-1ACT-1ACT-1

GYP-1

GYP-1

ACT-1ACT-1ACT-1ACT-1ACT-1ACT-1ACT-1ACT-1ACT-1 ACT-1 ACT-1

4" CLASS 1 MANUAL WET

STANDPIPE

4" CLASS 1

COMBINATION RISER

FP1.2

1

SCALE: 1/8"= 1'-0"

FIRE PROTECTION - SPRINKLER - 2ND FLOOR

AEED,

Advanced Energy Engineering & Design, Inc

CHATTANOOGA, TN 37405

BUS. (423) 752-3438

FAX (423) 752-1369

P.O. BOX 4934

408 McCALLIE AVE

inc.

AEED JOB NO.029-15

COPYRIGHT NOTICE

THE DRAWINGS ARE THE

PROPERTY OF RIVER STREET

ARCHITECTURE LLC. ANY USE,

REUSE, REPRODUCTION,

DISPLAY OR SALE OF THESE

DRAWINGS WITHOUT THE

EXPRESS WRITTEN CONSENT

OF THE ARCHITECT IS

STRICTLY PROHIBITED.

71

4 ch

erry stre

et, ch

atta

no

og

a, te

nn

esse

e 3

74

02

p.4

23

6

34

0

80

6 f.4

23

7

52

8

49

9 w

ww

.rive

r-st-a

rch

ite

ctu

re

.co

m

Release Date:

Project No.:

3/3

1/2

01

5 1

0:1

7:2

4 A

M

12055 G

AT

EW

AY

W

ES

T B

LV

D, E

L P

AS

O , T

X

CO

UR

TY

AR

D B

Y M

AR

RIO

TT

ZA

RA

GO

ZA

H

OT

EL P

AR

TN

ER

S, LLC

FIRE PROTECTION

FP1.2

SPRINKLER

2ND FLOOR

FIRE PROTECTION PLAN NOTES

1. ALL TAMPER AND FLOW SWITCHES MUST BE CONNECTED TO A MONITORED FIRE

ALARM SYSTEM.

2. FIRE PROTECTION CONTRACTOR TO OBTAIN OWNER/ARCHITECT APPROVAL OF

SPRINKLER TYPE AND FINISH PRIOR TO PURCHASING.

3. FIRE PROTECTION CONTRACTOR TO PROVIDE COVERAGE AS INDICATED ON

DRAWING.

4. SEE ARCHITECTURAL DRAWINGS FOR SMOKE AND FIRE RATED WALLS.

5. SPRINKLER SYSTEMS SHALL BE EQUIPPED WITH FLOOR CONTROL VALVE

ASSEMBLIES ( SEE SHEET FP2.1 FOR DETAIL) AT ALL CONNECTIONS TO RISERS.

SPRINKLER HEAD SCHEDULE (FOR THIS SHEET)

SYMBOL

QTY

MFG. SIN TYPERESPONSE TEMPERATURE K-FACTOR DESCRIPTION

109 VICTAULIC V2740 PENDANT

QUICK

155 °F 4.9

WHITE, SEMI-RECESSED PENDANT SPRINKLER (RESIDENTIAL TYPE)

27 VICTAULIC V2707 PENDANT

QUICK

155 °F 5.6

WHITE, SEMI-RECESSED PENDANT SPRINKLER (COMMERCIAL TYPE)

1 VICTAULIC V2707 PENDANT

QUICK

155 °F 5.6

BRASS, LAUNDRY CHUTE PENDANT SPRINKLER

4 VICTAULIC V2703 UPRIGHT

QUICK

155 °F 5.6

BRASS, UPRIGHT SPRINKLER

Page 4: 90 % CD - F.T. James...AEED, Advanced Energy Engineering & Design, Inc CHATTANOOGA, TN 37405 BUS. (423) 752-3438 FAX (423) 752-1369 P.O. BOX 4934 inc.408 McCALLIE AVE AEED JOB NO.029-15

KING

301

QQ

303

QQ

305

KING

307

KING

309

KING

311

KING

313

KING

315

QQ

317

QQ

319

KING

321

KING

323

KING

325

QQ

327

QQ

329

KING

331

KING

333

KING

330

KING

328

QQ

326

KING

324

KING

322

QQ

320

QQ

318

ACC. QQ INLINE

SUITE

316

KING

310

KING

308

KING

306

ACC. KING

304

QQ

302

KING

314

ELECTRICAL

3005

LINEN

3004

COMPUTER/

COMM ROOM

GYP-1

ACT-1

ICE

D04

L60L60

L60

L57

L60 L60

L57

L60 L60

D04

L57

L60 L60

L60L60

D04

L57

L60 L60

L60 L60

D04

L60 L60

L60

L57

L60

L54

L54

L54

L54

L54

L54

L57

L60L60

L60 L60

D04

GYP-1

L60 L60

L57

L60 L60

D04

L60

L57

L60 L60

L60

D04

L60

L57

L57

L57

L29 L29

L33

L33 L33

L33

L31

L31

ACT-1ACT-1ACT-1ACT-1

GYP-1

GYP-1

ACT-1ACT-1ACT-1ACT-1ACT-1ACT-1ACT-1ACT-1ACT-1 ACT-1 ACT-1

4" CLASS 1 MANUAL WET

STANDPIPE

4" CLASS 1

COMBINATION RISER

FP1.3

1

SCALE: 1/8"= 1'-0"

FIRE PROTECTION - SPRINKLER - 3RD FLOOR

AEED,

Advanced Energy Engineering & Design, Inc

CHATTANOOGA, TN 37405

BUS. (423) 752-3438

FAX (423) 752-1369

P.O. BOX 4934

408 McCALLIE AVE

inc.

AEED JOB NO.029-15

COPYRIGHT NOTICE

THE DRAWINGS ARE THE

PROPERTY OF RIVER STREET

ARCHITECTURE LLC. ANY USE,

REUSE, REPRODUCTION,

DISPLAY OR SALE OF THESE

DRAWINGS WITHOUT THE

EXPRESS WRITTEN CONSENT

OF THE ARCHITECT IS

STRICTLY PROHIBITED.

71

4 ch

erry stre

et, ch

atta

no

og

a, te

nn

esse

e 3

74

02

p.4

23

6

34

0

80

6 f.4

23

7

52

8

49

9 w

ww

.rive

r-st-a

rch

ite

ctu

re

.co

m

Release Date:

Project No.:

3/3

1/2

01

5 1

0:1

7:2

4 A

M

12055 G

AT

EW

AY

W

ES

T B

LV

D, E

L P

AS

O , T

X

CO

UR

TY

AR

D B

Y M

AR

RIO

TT

ZA

RA

GO

ZA

H

OT

EL P

AR

TN

ER

S, LLC

FIRE PROTECTION

FP1.3

SPRINKLER

3RD FLOOR

FIRE PROTECTION PLAN NOTES

1. ALL TAMPER AND FLOW SWITCHES MUST BE CONNECTED TO A MONITORED FIRE

ALARM SYSTEM.

2. FIRE PROTECTION CONTRACTOR TO OBTAIN OWNER/ARCHITECT APPROVAL OF

SPRINKLER TYPE AND FINISH PRIOR TO PURCHASING.

3. FIRE PROTECTION CONTRACTOR TO PROVIDE COVERAGE AS INDICATED ON

DRAWING.

4. SEE ARCHITECTURAL DRAWINGS FOR SMOKE AND FIRE RATED WALLS.

5. SPRINKLER SYSTEMS SHALL BE EQUIPPED WITH FLOOR CONTROL VALVE

ASSEMBLIES ( SEE SHEET FP2.1 FOR DETAIL) AT ALL CONNECTIONS TO RISERS.

SPRINKLER HEAD SCHEDULE (FOR THIS SHEET)

SYMBOL

QTY

MFG. SIN TYPERESPONSE TEMPERATURE K-FACTOR DESCRIPTION

109 VICTAULIC V2740 PENDANT

QUICK

155 °F 4.9

WHITE, SEMI-RECESSED PENDANT SPRINKLER (RESIDENTIAL TYPE)

27 VICTAULIC V2707 PENDANT

QUICK

155 °F 5.6

WHITE, SEMI-RECESSED PENDANT SPRINKLER (COMMERCIAL TYPE)

1 VICTAULIC V2707 PENDANT

QUICK

155 °F 5.6

BRASS, LAUNDRY CHUTE PENDANT SPRINKLER

4 VICTAULIC V2703 UPRIGHT

QUICK

155 °F 5.6

BRASS, UPRIGHT SPRINKLER

Page 5: 90 % CD - F.T. James...AEED, Advanced Energy Engineering & Design, Inc CHATTANOOGA, TN 37405 BUS. (423) 752-3438 FAX (423) 752-1369 P.O. BOX 4934 inc.408 McCALLIE AVE AEED JOB NO.029-15

KING

401

QQ

403

QQ

405

KING

407

KING

409

KING

411

KING

413

KING

415

QQ

417

QQ

419

KING

421

KING

423

KING

425

QQ

427

QQ

429

KING

431

KING

433

KING

430

KING

428

QQ

426

KING

424

KING

422

QQ

420

QQ

418

ACC. QQ INLINE

SUITE

416

KING

410

KING

408

KING

406

ACC. KING

404

QQ

402

KING

414

ELECTRICAL

4005

LINEN

4004

COMPUTER/

COMM ROOM

GYP-1

ACT-1

ICE

D04

L60L60

L60

L57

L60 L60

L57

L60 L60

D04

L57

L60 L60

L60L60

D04

L57

L60 L60

L60 L60

D04

L60 L60

L60

L57

L60

L54

L54

L54

L54

L54

L54

L57

L60L60

L60 L60

D04

GYP-1

L60 L60

L57

L60 L60

D04

L60

L57

L60 L60

L60

D04

L60

L57

L57

L57

L29 L29

L33

L33 L33

L33

L31

L31

ACT-1ACT-1ACT-1ACT-1

GYP-1

GYP-1

ACT-1ACT-1ACT-1ACT-1ACT-1ACT-1ACT-1ACT-1ACT-1 ACT-1 ACT-1

4" CLASS 1 MANUAL WET

STANDPIPE

4" CLASS 1

COMBINATION RISER

FP1.4

1

SCALE: 1/8"= 1'-0"

FIRE PROTECTION - SPRINKLER - 4TH FLOOR

AEED,

Advanced Energy Engineering & Design, Inc

CHATTANOOGA, TN 37405

BUS. (423) 752-3438

FAX (423) 752-1369

P.O. BOX 4934

408 McCALLIE AVE

inc.

AEED JOB NO.029-15

COPYRIGHT NOTICE

THE DRAWINGS ARE THE

PROPERTY OF RIVER STREET

ARCHITECTURE LLC. ANY USE,

REUSE, REPRODUCTION,

DISPLAY OR SALE OF THESE

DRAWINGS WITHOUT THE

EXPRESS WRITTEN CONSENT

OF THE ARCHITECT IS

STRICTLY PROHIBITED.

71

4 ch

erry stre

et, ch

atta

no

og

a, te

nn

esse

e 3

74

02

p.4

23

6

34

0

80

6 f.4

23

7

52

8

49

9 w

ww

.rive

r-st-a

rch

ite

ctu

re

.co

m

Release Date:

Project No.:

3/3

1/2

01

5 1

0:1

7:2

4 A

M

12055 G

AT

EW

AY

W

ES

T B

LV

D, E

L P

AS

O , T

X

CO

UR

TY

AR

D B

Y M

AR

RIO

TT

ZA

RA

GO

ZA

H

OT

EL P

AR

TN

ER

S, LLC

FIRE PROTECTION

FP1.4

SPRINKLER

4TH FLOOR

FIRE PROTECTION PLAN NOTES

1. ALL TAMPER AND FLOW SWITCHES MUST BE CONNECTED TO A MONITORED FIRE

ALARM SYSTEM.

2. FIRE PROTECTION CONTRACTOR TO OBTAIN OWNER/ARCHITECT APPROVAL OF

SPRINKLER TYPE AND FINISH PRIOR TO PURCHASING.

3. FIRE PROTECTION CONTRACTOR TO PROVIDE COVERAGE AS INDICATED ON

DRAWING.

4. SEE ARCHITECTURAL DRAWINGS FOR SMOKE AND FIRE RATED WALLS.

5. SPRINKLER SYSTEMS SHALL BE EQUIPPED WITH FLOOR CONTROL VALVE

ASSEMBLIES ( SEE SHEET FP2.1 FOR DETAIL) AT ALL CONNECTIONS TO RISERS.

SPRINKLER HEAD SCHEDULE (FOR THIS SHEET)

SYMBOL

QTY

MFG. SIN TYPERESPONSE TEMPERATURE K-FACTOR DESCRIPTION

109 VICTAULIC V2740 PENDANT

QUICK

155 °F 4.9

WHITE, SEMI-RECESSED PENDANT SPRINKLER (RESIDENTIAL TYPE)

27 VICTAULIC V2707 PENDANT

QUICK

155 °F 5.6

WHITE, SEMI-RECESSED PENDANT SPRINKLER (COMMERCIAL TYPE)

1 VICTAULIC V2707 PENDANT

QUICK

155 °F 5.6

BRASS, LAUNDRY CHUTE PENDANT SPRINKLER

4 VICTAULIC V2703 UPRIGHT

QUICK

155 °F 5.6

BRASS, UPRIGHT SPRINKLER

Page 6: 90 % CD - F.T. James...AEED, Advanced Energy Engineering & Design, Inc CHATTANOOGA, TN 37405 BUS. (423) 752-3438 FAX (423) 752-1369 P.O. BOX 4934 inc.408 McCALLIE AVE AEED JOB NO.029-15

AEED,

Advanced Energy Engineering & Design, Inc

CHATTANOOGA, TN 37405

BUS. (423) 752-3438

FAX (423) 752-1369

P.O. BOX 4934

408 McCALLIE AVE

inc.

AEED JOB NO.029-15

COPYRIGHT NOTICE

THE DRAWINGS ARE THE

PROPERTY OF RIVER STREET

ARCHITECTURE LLC. ANY USE,

REUSE, REPRODUCTION,

DISPLAY OR SALE OF THESE

DRAWINGS WITHOUT THE

EXPRESS WRITTEN CONSENT

OF THE ARCHITECT IS

STRICTLY PROHIBITED.

71

4 ch

erry stre

et, ch

atta

no

og

a, te

nn

esse

e 3

74

02

p.4

23

6

34

0

80

6 f.4

23

7

52

8

49

9 w

ww

.rive

r-st-a

rch

ite

ctu

re

.co

m

Release Date:

Project No.:

3/3

1/2

01

5 1

0:1

7:2

4 A

M

12055 G

AT

EW

AY

W

ES

T B

LV

D, E

L P

AS

O , T

X

CO

UR

TY

AR

D B

Y M

AR

RIO

TT

ZA

RA

GO

ZA

H

OT

EL P

AR

TN

ER

S, LLC

FIRE PROTECTION

FP2.1

DETAILS

SCALE: NONE

RISER DETAIL

PIPE

FIRE RESISTANT

SILICONE FOAM SEALER

CUT OPENING IN MASONRY WALL

LARGER THAN SLEEVE, THEN FORM &

FILL WITH EXPANSIVE TYPE GROUT.

PIPE INSULATION (WHERE REQ'D)

ESCUTCHEON PLATE ON ONE

OR BOTH SIDES WHERE

PIPING IS EXPOSED

PIPE SLEEVE

ANCHOR LUGS (MIN. 3 REQ'D)

EXISTING POURED CONCRETE

OR C.M.U. WALL.

NOTES:

1. FOR INTERIOR WALLS

AND BELOW GRADE

WALLS.

SEAL SPACE AROUND

PIPE WITH FIREPROOF

CAULKING.

PIPE SLEEVE

FINISHED FLOOR

5/8" ∅ BOLT

FURNISH LEAD

SHIELDS FOR BRASS

OR COPPER PIPING

PIPE

3/8" THK. STEEL X 1/2" MIN.

PIPE CLAMP WITH EXTENTION

ARMS

SCALE: NONE

PIPE RISER SUPPORT DETAIL

SCALE: NONE

PIPE SLEEVE THROUGH WALL DETAIL

SCALE: NONE

UPRIGHT & PENDANT INSTALLATION DETAIL

PENDANT

SPK'R. HEAD

1" BRANCH

LINE

1" BRANCH

LINE

INCREASER

UPRIGHT

SPK'R. HEAD

BRANCH LINE

SPRINKLER MAIN

WELDED.

EMERY PAPER. ATTACHMENT MAY BE SPOT

SMOOTH SCREW HEADS WITH FILE OR

SHEET METAL SCREWS AT 2" ON CENTER.

A

FRONT ELEVATION

SECTION A-A

6"

RADIUS.

CHUTE

WALL

1"

20 GAUGE STEEL

SPRINKLER

SHIELD

3"

18 "

SCALE: NONE

PENDANT HEAD IN LAUNDRY CHUTE DETAIL

FINISHED FLOOR

2 1/2" FDV (WITH 1-1/2" ADAPTER)

4" FIRE MAIN

2" DRAIN RISER

SECTIONAL DRAIN VALVE

TEST VALVE

UNION WITH CORROSION RESISTANT ORIFICE

SIGHT GLASS

3" 3"

TO SYSTEM

WATERFLOW SWITCH-VANE TYPE

INDICATING TYPE FLOOR CONTROL

VALVE WITH TAMPER SWITCH

(1ST FLOOR ONLY)

CHECK VALVE

ISOLATION BUTTERFLY

VALVE

INSPECTOR'S TEST CONNECTION

TO SYSTEM

TYPICAL FLOOR CONTROL VALVE DETAIL

SCALE: NONE

FIRE SERVICE PIPING

12" A.F.F.

BLIND FLANGE UNTIL READY

TO CONNECT TO INSIDE FIRE

PIPING

CAST IRON FLANGE

AND SPIGOT PIECE

CAST IRON BELL

AND SPIGOT PIPE

RODS

TYPICAL FLOOR PENETRATION DETAIL

SCALE: NONE

VICTAULIC 7C7 RISER MOUNTED

AIR COMPRESSOR (1/6 HP)

TO CLASS 1 MANUAL STANDPIPE SYSTEM

TO CLASS 1 COMBINATION STANDPIPE SYSTEM

VICTAULIC 768 2-1/2" DRY SYSTEM VALVE

1ST FLOOR WET SYSTEM

VICTAULIC 751 4" ALARM CHECK

VALVE

MONITORED BUTTERFLY VALVE (TYP.)

SYSTEM DRAIN

TO CITY MAIN

FINISHED FLOOR

4" FIRE MAIN

24"

PLUG

TEE

TO WET SYSTEM

SPRINKLER BARREL

TYCO DSB DRY SPRINKLER

BOOT & SEALANT KIT

SEALANT

INSULATED FREEZER

STRUCTURE

DRY TYPE

PENDENT SPRINKLER WITH WIDE

FLANGED RECESSED ESCUTCHEON2-1/4" DIA. MOUNTING PLATE CLEARANCE

HOLE

INSULATED FREEZER CEILING STRUCTURE

1-3/4" DIA. SPRINKLER

BARREL CLEARANCE HOLE

2-NYLON ZIP-TIE CLAMPS AS PER

INSTALLATION MANUAL

COOLER/FREEZER DRY PENDANT DETAIL

SCALE: NONE

SPRINKLER MAIN

1" BRANCH

LINE

SEMI-RECESSED

PENDANT SPK'R. HEAD

FINISHED SURFACE

FINISHED SURFACE

1" BRANCH

LINE

SIDEWALL PENDANT DETAIL

SCALE: NONE