8DA10 and 8DB10Single and Double BusbarFlexible and powerful
Page 2 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
Infrastructure & Cities
Welcome!
Page 3 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
Main Applications for Medium-Voltage Switchgear
Power transmissionHigh and extra-high voltage > 72 kVPrimary distribution levelMedium voltage up to 40.5 kVup to 40 kA (3s)
Secondary distribution levelMedium voltage up to 24 kVup to 25 kA (1s)
Distribution levelLow voltage < 1 kV
8DJ10/20 8DH10 SIMOSEC
8DAB10 NXPLUS NXPLUS C
Power generationPower stations
G
x xx xxx xx x
x
Page 4 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
Technical features and general informationTechnical DataTypical Overview, fixtures and fittingsPanel Desgin
• Circuit-breaker Panel• Busbar• Operation• Metering• Low-Voltage Compartment• Cable Connection• Feeder Earthing, Cable Testing• Interlocks
Classification according to IEC 62 271-200Customer‘s Benefit
8DA/B10Content
Page 5 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DA/B10Technical Features
Up to 40.5 kV, 40 kA (3s), 5000 A busbar, 2500 A feederMetal-enclosedSingle-busbar system ( 8DA10 )Double-busbar-system ( 8DB10 )Gas-insulatedHermetically single-pole enclosedFactory-assembled, type-tested switchgear according to IEC 62 271-200
Page 6 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DA/B10 General Information
Market introduction in March 1982Worldwide successful operationThe gas-insulated circuit-breaker switchgear for application in nearly all branches like Airports & Ports Automotive Buildings
Cement Industries Chemicals & Pharma MiningOil & Gas Paper Industries Steel & Aluminium Utilities Transportation & Railways
More than 63,900 panels 8DA/B (September 2011) deliveredOur experiences are based on more than 130,000 delivered panels for gas-insulated circuit-breaker switchgear (primary distribution level)
Page 7 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DA10 Technical Data
2350
1625
600
IP3XD
IP65
2500
5000
40
40
100
100
185
85
50/60
40,5
2350
1625
600
IP3XD
IP65
2500
5000
40
40
100
100
170
70
50/60
36
2350
1625
600
IP3XD
IP65
2500
5000
40
40
100
100
125
50
50/60
24
2350mmHeight ( Standard )
1625mmDepth
600mmWidth
Dimensions
IP3XDSecondary part
IP65Degree of protection Primary part
2500ARated normal current of feeder
5000ARated normal current of busbar
40kARated short-circuit breaking current
40kARated short-time withstand current, 3 s
100kARated short-circuit making current
100kARated peak withstand current
75kVRated lightning impulse withstand voltage
20kVRated short-duration power-frequency withstand voltage
50/60HzRated frequency
12kVRated voltage
Page 8 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DB10 Technical Data
2350
2665
600
IP3XD
IP65
2500
5000
40
40
100
100
185
85
50/60
40,5
2350
2665
600
IP3XD
IP65
2500
5000
40
40
100
100
170
70
50/60
36
2350
2665
600
IP3XD
IP65
2500
5000
40
40
100
100
125
50
50/60
24
2350mmHeight ( Standard )
2665mmDepth
600mmWidth
Dimensions
IP3XDSecondary part
IP65Degree of protection Primary part
2500ARated normal current of feeder
5000ARated normal current of busbar
40kARated short-circuit breaking current
40kARated short-time withstand current, 3 s
100kARated short-circuit making current
100kARated peak withstand current
75kVRated lightning impulse withstand voltage
20kVRated short-duration power-frequency withstand voltage
50/60HzRated frequency
12kVRated voltage
Page 9 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DA11/8DA12 ( Traction Power Supply ) Technical Data
220145kV
11060kV
27,517,5kVRated operation voltage
50/60
2000
2500
31,5
80
2350
865/1245
600
IP3XD
IP65
125
50
16,7
15
2350mmHeight ( Standard )
865/1245mmDepth ( 1-pole, 2-pole )
600mmWidth
Dimensions
IP3XDSecondary part
IP65Degree of protection Primary part
2000ARated normal current of feeder
2500ARated normal current of busbar
31,5kARated short-circuit breaking current
80kARated short-circuit making current
200kVRated lightning impulse withstand voltage EarthIsolation
95kVRated short-duration power-frequency withstand voltage EarthIsolation
HzRated frequency
25kVRated voltage
Page 10 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DA10 Typical Overview
Circuit-breaker Panel Disconnector Panel Bus Sectionalizer
Page 11 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DA10 Fixtures and Fittings Circuit-breaker Panel
Page 12 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DA10 Fixtures and Fittings Disconnector Panel
Page 13 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DA10 Fixtures and Fittings Bus Sectionalizer
Page 14 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DA10 Fixtures and Fittings Bus Sectionalizer without additonal required space
Page 15 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
Circuit-Breaker Panel 8DA10 Single-Busbar System
Busbar housingLight-metal vessel
Circuit-breaker housing Light-metal vessel
Cable connection Inside-cone system
Low-voltage compartmentInstallation of secondary devices
Operating mechanism for three-position switchDisconnector and earthing switch
Operating mechanism for circuit-breaker Vacuum switching technology
Page 16 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
Circuit-Breaker Panel 8DB10 Double-Busbar System
Busbar housingLight-metal vessel
Circuit-breaker housing Light-metal vessel
Cable connection Inside-cone system
Three-position switch housingLight-metal vessel
Low-voltage compartmentInstallation of secondary devices
Operating mechanism for three-position switchDisconnector and earthing switch
Operating mechanism for circuit-breaker Vacuum switching technology
Page 17 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
Circuit-Breaker Panel 8DA11/121-Pole and 2-Pole Traction Systems
Busbar housingLight-metal vessel
Circuit-breaker housingLight-metal vessel
Cable connection Inside-cone system
Low-voltage compartmentInstallation of secondary devices
Operating mechanism for three-position switchDisconnector and earthing switch
Operating mechanism for circuit-breaker Vacuum switching technology
Page 18 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DA/B10Busbar current up to 5000A
Three-position switch
Pole housing
Busbar
Busbar
Busbar housing
Twin busbar housing
Busbar up to 4000 A
Busbar 5000 AExample 8DA10
Page 19 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DA10 Operation of Three-position Switch
Switch position indicatorDisconnector switch
Operating shaftDisconnector switch
Switch position indicatorCircuit-breaker switch
Operating shaftEarthing switch
Switch position indicatorEarthing switch
Preselection key
Page 20 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DA10 Operation
Switch position indicatorCircuit-breaker switch
Switch position indicatorDisconnector switch
Operating shaftDisconnector switch / Earthing switch
Preselection key
Switch position indicatorEarthing switchON pushbuttonCirciut-breaker switch
OFF pushbuttonCirciut-breaker switch
De-earthing interlock
Raedy-for-service indicator
Filling valve
Opening for charging thecircuit-breaker spring by hand
“Spring charged” indicator
Counter
Page 21 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DA/B10Current Measurement
Ring-core current transformersMain circuit as primary part without dielectric and thermal problems Secondary part accessible outside the enclosure without dangerFree of dielectrically stressed cast-resin parts
Current transformerFitted at cablehousing
Current transformerFitted at busbar
Current transformerFitted at pole housing
Current transformerFitted at cable
Page 22 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DA/B10Voltage Measurement
Voltage transformerSingle-pole insulatedMetal-enclosedPlug-in typeAt the busbar:Surge-proof for 80 % UPrepeat test with connected transformer
Voltage TransformerFitted at busbar
Type 4MT3Type 4MU4
Voltage TransformerFitted at cabelhousingType 4MT7Type 4MU3
Page 23 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DA/B10Low-Voltage Compartment
Height: 850 mm1200 mm (option)
Removable, bus wires and control cables plugged in (via 6 or 10-pole coded module plug connectors)Panel control via conventional control devices or digital bay controllerCustomer-specific equipment (protection, control, metering, annunciation)Wiring in H07VK, optionally also heat-resistant and halogen-free
Page 24 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DA/B10Panel Connection – Inside Cone according to IEC 50 181
Maintenance-free due to inside cone plug-in systemFor connection type sizes2, 3 und 4 (depending on cablecross section)1 to 6 cables possible per phaseCable connection with different connection types / sizes realisablePlug-in voltage transformer and surge arrester realisable
Single cable connection Multiple cable connection
Page 25 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DA/B10Fully Insulated Bar Connections
Fully insulated bar
for rated normal current up to 2500 A
Gas-insulated bar
for rated normal current up to 2500 A
Page 26 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DA/B10Cable Earthing with the Circuit-Breaker
1) Close three-position switch / Earthed positionEarthing preparedElectrical OFF-signals are suppressed
2) Close circuit-breaker switch / ON positionOutgoing / Feeder earthed
3) Secure switch position “Outgoing/Feeder earthedwith padlock
Circuit-breaker is blocked mechanicallySignal: Outgoing / Feeder earthed (option)
1)
2) 3)
Page 27 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DA/B10 Cable testing
Cable test with DC voltage or AC voltage 0.1 HzThree-position switch and circuit-breaker in OFF positionCable fault location with lightning impulse voltageFull operating voltage at the busbar
Page 28 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DB10 Typical Overview
Circuit-breaker Panel Bus Coupler Bus Sectionalizer
Page 29 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DB10 Fixtures and Fittings Circuit-breaker Panel
Page 30 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DB10 Fixtures and Fittings Bus Coupler
Page 31 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DB10 Fixtures and Fittings Bus Sectionalizer
Page 32 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DB10 Operation
Switch position indicatorCircuit-breaker switch
Raedy-for-service indicatorsFilling valves
Switch position indicatorEarthing
Switch position indicatorDisconnector switch BB1
Opening for charging thecircuit-breaker spring by hand
“Spring charged” indicator
Counter
Switch position indicatorDisconnector switch BB2
Preselection key
Operating shaftDisconnector switch BB2
ON pushbuttonCirciut-breaker switch
OFF pushbuttonCirciut-breaker switch
De-earthing interlock
Page 33 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DA/B10Interlocks (Selection)
Interlocks are designed according to IEC 62 271-200Standard interlocks
Three-position disconnector against circuit-breaker – mechanicalDisconnector against earthing switch (within three-position disconnector) – mechanical Locking device at the circuit-breaker switchLocking device at the three-position disconnector switch
Additional interlocksElectromagnetic interlock at the three-position switch / disconnector switchElectromagnetic interlock at the three-position switch / earthing switch
Page 34 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
Special feature - Single-pole enclosure
L1L2L3
Example 8DA10
Advantage of single-pole enclosure
Exclude phase-to-phase short circuits.
In worst case only phase-to-earth short circuits couldhappen.
Minimizing of fault risks.
Page 35 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
Special feature - Multiple-Vessel-Principle 8DA10
Busbar and circuit-breaker are single-pole enclosed within different vessels
Measures in case of faults at circuit-breaker or cable connection:
Shut down of the busbar is not necessary
Replacement of panels is possible, while busbar is under high voltage operation
Single-phase enclosure
2 Compartments
6 Vessels
► Shut down is only for the damaged panel necessary
Page 36 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
Special feature - Multiple-Vessel-Principle 8DB10
Busbar and switching devices are single-pole enclosed within different vessels
Measures in case of faults at switching devices or cable connection:
Shut down of the busbar is not necessary
Replacement of panels is possible, while busbar is under high voltage operation
Single-phase enclosure
5 Compartments
15 Vessels
► Shut down is only for the damaged panel necessary
Page 37 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
Statement 8DA10 and 8DB10
Maximum reliability of supply
No disconnecting of the busbar while outgoing feeder will be repaired or replaced.
Extension 8DB10 without shutdown of the busbar.
Special feature - Multiple-Vessel-Principle
Page 38 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DA/B10Classification according to IEC 62 271-200
Partition Class: PMLoss of Service Continuity Category: LSC 2BAccessibility of Compartments:
Busbar compartment: tool-based Switching device compartment: tool-based Low-voltage compartment: tool-based Cable compartment: tool-based
Internal arc classification: IAC A FLR 40 kA 1 s
Page 39 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DA/B10Customer’s Benefit
Security of Operation, ReliabilityPersonal SafetyEnvironmental IndependenceCompactnessMaintenance-free Design for DevicesEconomy, Ecology
Page 40 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DA/B10Security of Operation, Reliability
Our solutionHermetically enclosed systemCurrent transformers outside the gas compartmentsMetal-enclosed voltage transformers plugged in from outsideHermetically enclosed busbar systemModular designMinimum use of insulating materialType and routine tests, quality managementNC production processes
Your benefitTwo and three-phase short circuits not possible because of single-phase encapsulationIndependent of the environment, maintenance-free,no condensation, no oxidationFast transformer replacement possibleNo dielectric and dynamic stress for current transformersRestriction of failure by compartmentReduced fire loadMTBF (> 3,000 years at the moment)
Page 41 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DA/B10 Maximum Security of Operation
Separate compartments for busbar and circuit-breaker offer a maximum degree of availability
Busbar ( in operation )
Attention: High voltage
Feeder earthed ( earthing )
Circuit-breaker
Access without danger to current transformer, feeder voltage transformer, cable plugs, operating mechanisms
Page 42 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DA/B10Personal Safety
Your benefitTouching of live parts excluded,extremely high degree of protection of the primary partAccidental opening of vessel excludedAccess to switching devices not required due to maintenance-free designMaloperation excludedVerification of safe isolation from supply without opening the enclosure
Our solutionHermetically enclosed systemInternal arc classified according to IEC 62 271-200 for 1 sLogical mechanical interlocksCapacitive voltage detection systemMake-proof earthing throughthe circuit-breaker
Page 43 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DA/B10Environmental Independence
Our solutionHermetically encapsulationHermetically enclosed pressure systemMaintenance-free switching devices and operating mechanisms,no adjustment and lubricationHermetically enclosed busbar systemEnclosed cable plugs,screened, independent of the environment
Your benefitInsensitive to aggressive environments (salt water, tropical areas, dust, humidity, chemical pollutants),no oxidation of contacts and bolted joints, no condensation,no pollution layers on insulators, no resinifying greaseContinuous insulation qualityNo ingress of foreign bodies, small animalsIndependent of site altitude
Page 44 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DA/B10Compactness
Our solutionSF6-insulation,compact constructionCombined disconnector and earthing switch,compact switch designSIPROTEC bay controller: Digital control, interlocking and protection system,compact secondary systems with high functional density
Your benefitMinimum space requirements, building volume saved, efficient use of existing rooms, reduced volume for new constructions, compact design reduces transport and installation costs to a minimumEconomic use of space in urban areas,installation in conurbation, load centres to minimise transmission losses
Page 45 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DA/B10Maintenance-free Design for Devices
Our solutionHermetically enclosed pressure systemMaintenance-free switching devices and operating mechanisms,no adjustment and lubricationHermetically enclosed busbar systemEnclosed cable plugs,screened, independent of the environment
Your benefitMaximum reliability of supply and availability,no shutdowns for maintenanceSealed for lifetime(according IEC 62 271-200)Low maintenance costs,minimized operational costsHighly economic investment
Page 46 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DA/B10Economy, Ecology
Our solutionMaintenance-free switchgearCompact constructionEconomic productionSF6 only used in hermetically sealed pressure system100 % SF6-recycling by means of special toolsIdentified, recyclable insulating materialListing of all materials used
Your benefitMinimized operator expenses, high availabilityReduced transport costsMinimum requirements regarding the buildingMinimized transmission losses by installation in load centresReliable, calculable disposal
Page 47 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DA/B10MTBF (1)
The term major failures and minor failures are taken from the CIGRE publication of the work group 13.06 “Reliability of High Voltage Switchgears”.
Definition:
MTBFMeantime between failure
Major failure (MF)Complete failure of a panel which causes the lack of one or more of its fundamentalfunctions.NOTE: A major failure will result in an immediate change in the system operating e.g. the backup protective equipment being required to remove the fault, or will result in mandatory removal from service for non scheduled maintenance (Intervention required within 30 minutes).
Minor failure (mF)Failure of a panel other than a major failure or any failure, even complete, of a constructional element or a sub-assembly which does not cause a major failure of the panel.
MTTFMeantime to failure
Page 48 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DA/B10MTBF (2)
Download from the Intranet
Page 49 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DA/B10 References Selected Projects (1)
Kulmbach / Germany
8DA10 / 16 panels
24 kV / 16 kA (3s) / 1250 A
First SIEMENS gas-insulated medium-voltage switchgear (March 1982)
Page 50 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DA/B10 References Selected Projects (2)
Tibet / China
8DA10
205 panels
40.5 kV / 31.5 kA (3s) / 1250 A
Site altitude: 3000 – 5000 m
Page 51 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DA/B10 References Selected Projects (3)
GECOL / Libya
8DA10 and 8DB10
1398 panels
36 kV / 40 kA (3s) / 2500 A
Page 52 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DA/B10 References Selected Projects (4)
Emirates Palace Hotel
8DB10
117 panels
12 kV / 31,5 kA (3s) / 2500 A
Page 53 October 1st 2011 Infrastructure & Cities Sector / IC LMV MV 28DA/B10
© Siemens AG 2008
8DA/B10, the gas-insulated switchgear up to
40,5 kV, 40 kA (3 s), 5000 A busbar, 2500 A feeder