8BK80 air-insulated, metal-cladMedium Voltage Switchgear
Page 3 Prepared by: PTD-M/BDNote: Special Execution on request
Up to 3150A
3.6 kV
Up to 4000A
10kV
40kVp
26.3/31.5/44kA
66/80/110kAp
26.3/31.5/44kA
Nominal Current of Feeders
Rated Continuous Current of Busbar
Rated Power freq withstand voltage
Rated Lightning Impulse withstand Voltage
Rated Short Circuit Breaking Current
Rated Short Circuit Making Current
Rated Short time withstand Current (3sec)
12/ 38/ 95 kV BIL available on request
Product Rating
7.2kV
20kV
60kVp
26.3/31.5/44kA
26.3/31.5/44kA
66/80/110kAp
Up to 3150A
Up to 4000A
12kV
28kV
75kVp
26.3/31.5/44kA
26.3/31.5/44kA
66/80/110kAp
Up to 3150A
Up to 4000A
Page 4 Prepared by: PTD-M/BD
Circuit Breaker
Siemens Make Vacuum Interrupter
Tulip contacts- Better current
carrying capacity
Improved contact arm design
Enclosed pole- increased reliability
Sealed for life gear box ensures
reliability of mechanism
Page 5 Prepared by: PTD-M/BD
•Mechanism kinematics and interrupter force designed to ensure smooth operation
•Tested for Mechanical endurance of 10,000 operations (M2 class)
•Mechanical de-latching for spring charging motor ensures motor protection even under cut off switch failure
•Low arc energy with Vacuum technology means less erosion of contact & longer life
•Constant dielectric strength for a long period of time
Vacuum Circuit Breaker
Page 6 Prepared by: PTD-M/BD
Use of maintenance-free Siemens Vacuum Circuit Breaker
on withdrawable truck means low life cycle costs.
Vacuum Circuit Breaker
Page 7 Prepared by: PTD-M/BD
CB Chamber
All operations behind closed doors
Ramp for floor leveling
Truck type design – No CB handling
trolley
VCB truck earthing even in test
condition
Tested for 1,000 insertion &
withdrawals of CB truck as against 25
specified in IEC
Page 8 Prepared by: PTD-M/BD
CB chamber
Busbar chamber shutter: Gravity
operated
Cable chamber shutter: Spring
operated
Padlocking of shutters
Independently lockable shutters
Guide rails for better alignment
Page 9 Prepared by: PTD-M/BD
Busbar chamber
Better heat dissipation due to hollow,
triangular main busbar & round feeder
connections
Easy assembly of busbars at site
Design w/o sharp edges: reduced
electrical stress
Design facilitating more cooling air
Patented design of busbars with
increased capacity for heat dissipation
Reduced no. of joints: better thermal
capacity* Sleeving & BB shrouds optional
Page 10 Prepared by: PTD-M/BD
Alternative 1:-
Panel standard depth of 1750mm containing:
a) 1 set of CT
b) 2 runs of cable termination
More equipments in the standard cable chamberMore equipments in the standard cable chamber Reducing the depth of typical Incomer panels thus saving vast Reducing the depth of typical Incomer panels thus saving vast spacespace Cable chamber with three different alternatives/configurationCable chamber with three different alternatives/configuration
Alternative 2:-
Panel standard depth of 1750mm containing:
a) 2 sets of CTs
b) earth switch
c) draw out PT from rear*
d) 2 runs of cable termination
Cable chamber
Withdrawable PT on VCB trolley also available
Page 11 Prepared by: PTD-M/BD
Cable chamber
Alternative 3:-
Panel standard depth of 1750mm containing:
a) 2 sets of CTs
b) Earth Switch
c) 3 runs of cable termination
Alternative 4:-
Panel standard depth of 1750mm containing:
a) 2 sets of CTs
b) Up to 4 runs of cable termination
Page 12 Prepared by: PTD-M/BD
End terminations eliminated by direct cable termination on C.T: less overheating problems
First set of C.T is sliding: Easy removal for maintenance
Both secondaries of C.Ts can be accessed easily
Cable chamber
No need to disconnect the cable for removal of first set of CT
Page 13 Prepared by: PTD-M/BD
•For additional equipments/cables rear boxes of different sizes
are available: enhanced flexibility
•Full Height rear boxes are provided for the utter most safety of
the operator
•Cable size up to 630sqmm for three core and 1000 sqmm for
single core cable can be accommodated
•LV Box Height adjustable as per customer requirement
•Easy accessibility of both the CTs in case of two CTs for ease in
maintenance
Customer Benefits from cable chamber
Page 14 Prepared by: PTD-M/BD
7.2 kV 12 kV
Available executions
3.6 kV
Note: Special Execution on request
Circuit breaker panel
Metering panel
Bus-Coupler +Adaptor
Cabling panel
Incoming/Outgoing in same panel
Page 15 Prepared by: PTD-M/BD
8BK80: Benefits
1. Peace of Mind.
2. Saves Lives.
3. Increases Productivity.
4. Saves Money.
Page 16 Prepared by: PTD-M/BD
8BK80: Benefit no.1
Peace of Mind
Page 17 Prepared by: PTD-M/BD
Fully Type tested product
Di-electric tests
Temperature rise test
Short time withstand
Short circuit test & test duty
Double earth fault test
Mechanical endurance test
Ingress Protection Test
Cable charging
Capacitor Switching
STC/Making/Mechanical Operation of
Earthing switch
Internal Arc: 12kV 31.5kA for 0.1sec
Fulfilling all the mandatory type tests requirements of new IEC 62271-200/100
Both on main circuit and auxiliary circuit
STC test on main circuit, earth circuit and on sliding contact of earth circuit
Product is tested for solidly as well non-solidly earthed system
Separately tested for all three chambers
Page 18 Prepared by: PTD-M/BD
Peace of Mind: How?
Easy rack-in / rack-out of switching devicethrough ramps and truck
Page 19 Prepared by: PTD-M/BD
89290
42821
111
4213
5 32
416
311
479
245
86
22
10
3814
6
> 35000 8BK80 Panels in service worldwide
NepalBhutanSri-LankaBangladeshMaldivesMauritiusOmanQatarKuwaitJordan
KenyaZambiaEthiopiaTanzania
Brunei
A true international switchgear
Peace of Mind: How?
Page 20 Prepared by: PTD-M/BD
Well Documented Quality Systems and Procedures
Peace of Mind: How?
Page 21 Prepared by: PTD-M/BD
Peace of Mind 1.1 Factory assembled, fully type tested switchgear as per IEC 62271-200.
1.2 Testing of VCB inside the panel.
1.3 Preventive mechanical interlocks.
1.4 Siemens Vacuum switching technology.
Benefit Features
Peace of Mind: How?
Page 22 Prepared by: PTD-M/BD
Peace of Mind 1.5 More tolerant to floor levelling.
1.6 Quality management according toISO 9001-2000
1.7 Design based on global best practise sharing and experience.
1.8 Routine Testing on 100% manufactured panels
1.9 Siemens Guarantee.
Benefit Features
Peace of Mind: How?
Page 23 Prepared by: PTD-M/BD
8BK80: Benefit no.2
Saves Lives
Page 24 Prepared by: PTD-M/BD
Forecast: Saves Lives
How much: Even one life!
How soon: As soon as you energize Siemens 8BK80 switchgear
Page 25 Prepared by: PTD-M/BD
All operations behind closedDoor!
1. All switching operations including emergency manual
operations.
2. Operation of Earthing Switch.
3. Rack-in / rack-out operation of VCB truck.
4. Emergency manual charging of VCB operating mechanism.
Operator safety:
Saves Lives: How?
Page 26 Prepared by: PTD-M/BD
Front door interlocks as per IEC 62271-200
1. Racking of VCB truck from Test to Service position not possible until the front door is closed and locked.
2. Front door cannot be closed and locked until the LV control plug is securely connected.
3. Front door cannot be opened until the VCB is switched OFF and racked out in Test position.
Operator safety:
Saves Lives: How?
Page 27 Prepared by: PTD-M/BD
Partition class: PM
1. Earthed metallic shutters and partitions ensure partition class PM.
2. Class PM ensures no electric field in the opened compartment and no electrical field change in the adjacent compartments.
3. Thus partition class PM ensures safe maintenance when the switching device chamber is opened while keeping the bus bars as well as cables under charged conditions.
8BK80: Safest Switchgear
Saves Lives: How?
Page 28 Prepared by: PTD-M/BD
Classification of the 8BK80 according to IEC 62271-200
Construction and design
Partition class PM (metallic)
Loss of service continuity category LSC2B
Compartment accessibility (standard)
– Bus bar compartment Tool-based
– Switching-device compartment Interlock-based
– Low-voltage compartment Tool-based
– Connection compartment Tool-based
Saves Lives: How?
Page 29 Prepared by: PTD-M/BD
Compartmentalisation features
Metal enclosed switchgear – Designs acc. to Part 200
Access control Ÿinterlock-controlledŸprocedure-basedŸtool-based
Accessible compartment
Loss of service continuity LSC 1 LSC 2A LSC 2B
Non- accessible compartment
Partition class PM (metal) PI (non-metal)
Insulation medium ŸAmbient airŸFluid (gas or liquid)
Internal Arc Classification
Compartmentalisation features
Metal enclosed switchgear – Designs acc. to Part 200
Access control Ÿinterlock-controlledŸprocedure-basedŸtool-based
Accessible compartment
Loss of service continuity LSC 1 LSC 2A LSC 2B
Non- accessible compartment
Partition class PM (metal) PI (non-metal)
Insulation medium ŸAmbient airŸFluid (gas or liquid)
Internal Arc Classification IAC A FLR …kV…kA for …sec
Maintainability
Service continuity
Operator’s safety
Purpose
Classification based on purpose
Classification As per IEC 62271-200
Page 30 Prepared by: PTD-M/BD
Internal arc classification
Classification IAC
Accessibility Type A
– Front Accessible
– Rear Accessible
– Lateral Accessible
Test current kA 31.5
Test duration s 0.1
Classification of the 8BK80 according to IEC 62271-200
Tested separately for each compartment i.e. BB, CB and cable compartment
Saves Lives: How?
Page 31 Prepared by: PTD-M/BD
• Safety of operating personnel ensured by tests for
verifying the internal arc classification.
• Internal arc tests in accordance with IEC 62271-200,
Annex A.
• The switchgear complies with criteria 1 to 5 specified in
the mentioned standards for the basic version up to 31.5
kA (IAC 31.5 kA 0.1 sec. AFLR).
Internal arc classification
Saves Lives: How?
Page 32 Prepared by: PTD-M/BD
Class A–Criterion 1
Correctly secured doors and covers do not open. Deformations are accepted conditionally.
–Criterion 2No fragmentation of enclosures occurs within the time specified for test. Projections of small parts up to 60 g are accepted.
–Criterion 3Arcing does not cause holes in the accessible sides up to a height of 2 m.
–Criterion 4Indicators do not ignite due to the effect of hot gases. Ignition caused by glowing particles rather than hot gases is allowed. Ignitions as a result of paint or sticker burning are also excluded.
–Criterion 5The enclosure remains connected to its earthing point.
8BK80: Complies with All Criterion for Internal Arc
IEC 62271-200 Definitions of the classification criteria
Page 33 Prepared by: PTD-M/BD
Successfully Internal Arc Tested - If this failure happened in your 8BK80, no one would even be hurt.
Saves Lives: How?
Page 34 Prepared by: PTD-M/BD
Vacuum Circuit Breaker means no explosion is possible.
Saves Lives: How?
Page 35 Prepared by: PTD-M/BD
Which interrupter would you prefer?
Vacuum interrupters: no seals and gaskets &hence no vacuum loss.
Saves Lives: How?
Page 36 Prepared by: PTD-M/BD
1. Arc medium free from toxic by-products2. Does not explode.3. Environment friendly and compatible.
Saves Lives: How?
Page 37 Prepared by: PTD-M/BD
Saves Lives 1.1 All operations behind closed front door.
1.2 Front door interlocks with VCB.
1.3 Partition class PM.
1.4 Internal Arc Classification switchgear: IAC A FLR 31.5kA for 0.1sec
Benefit Features
Saves Lives: How?
Page 38 Prepared by: PTD-M/BD
Saves Lives 1.5 Siemens vacuum switching technology.
1.6 Secured earthing of switching device in Service and Test position.
Benefit Features
Saves Lives: How?
Page 39 Prepared by: PTD-M/BD
8BK80: Benefit no.3
Increased Productivity
Page 40 Prepared by: PTD-M/BD
Loss of Service Continuity category LSC2B-PMMaintenance in switching device compartment
possible without de-energising the corresponding cable connections and bus bars.
Metallic and earthed shutters and partitions. Safe to touch
Increased Productivity: How?
Page 41 Prepared by: PTD-M/BD
Use of maintenance-free Siemens Vacuum Circuit Breakermeans no interruption in power supply.
Increased Productivity: How?
Page 42 Prepared by: PTD-M/BD
IncreasesProductivity
1.1 LSC2B-PM Switchgear.
1.2 Use of Vacuum switching technology.
Benefit Features
Increased Productivity: How?
Page 43 Prepared by: PTD-M/BD
8BK80: Benefit no.4
Saves Money
Page 44 Prepared by: PTD-M/BD
Effect On Floor Space
C.B Chamber
CableChamber
Cutout for Power Cable
C.B Chamber
CableChamber
Cutout for Power Cable
C.B Chamber
CableChamber
Cutout for Power Cable
C.BChamber
Cutout for Power Cable
CableChamber
C.BChamber
Cutout for Power Cable
CableChamber
C.BChamber
Cutout for Power Cable
CableChamber
I/C OG1 OG2 I/C OG1 OG2
Saving in space of
1.44sqm for
3 panels
2 Sets Of CTD/O PT3 Runs of Cab
1Sets Of CT2 Runs of Cab
1 Sets Of CT2 Runs of Cab 2 Sets Of CT
D/O PT3 Runs of Cab
1 Sets Of CT2 Runs of Cab
1 Sets Of CT2 Runs of Cab
Presently 600 mm rear box
Saves Money: How?
Page 45 Prepared by: PTD-M/BD
Use of maintenance-free Siemens Vacuum Circuit Breakeron withdrawable truck means
low maintenance costs.
Saves Money: How?
Page 46 Prepared by: PTD-M/BD
Use of maintenance-free Siemens Vacuum Circuit Breakermeans less life cycle cost.
Saves Money: How?
Page 47 Prepared by: PTD-M/BD
Vacuum remainsconstant over time
A vacuum is a non-deteriorating extinguishing medium; no maintenance is required.
Saves Money: How?
Page 48 Prepared by: PTD-M/BD
Oxidization-free contactsin vacuum
Oxidized contacts require maintenance.
Saves Money: How?
Page 49 Prepared by: PTD-M/BD
OilOil
SF6SF6
VacuumVacuum
Breaking Current, kABreaking Current, kA
Low arc energy with vacuum technology; Very less erosion of contacts.
Saves Money: How?
Page 50 Prepared by: PTD-M/BD
Faster Installation: Foundation Plan
C.BChamber
Cutout for Power Cable
CableChamber
1750
162
1030
400800
476
388
Only three fixing holes are required for mounting of the panel
Saves Money: How?
Page 51 Prepared by: PTD-M/BD
Switchgear installation, operation and maintenance without any special tools and tackles means
low life cycle cost.
Saves Money: How?
Page 52 Prepared by: PTD-M/BD
Reliable After Sales Service- Reduced downtime
Saves Money: How?
Page 53 Prepared by: PTD-M/BD
Saves Money 1.1 Siemens Vacuum Technology: Less maintenance cost.
1.2 Faster Installation: Less installation cost.
1.3 Less total life cycle cost.
1.4 Use of recyclable material: saves money and environment
1.5 More equipment in same depth: reduced dimensions of room means less construction cost
Benefit Features
Saves Money: How?
Page 54 Prepared by: PTD-M/BD
8BK80: Benefits’ summary
1. Peace of Mind.
2. Saves Lives.
3. Increases Productivity.
4. Saves Money.
Page 55 Prepared by: PTD-M/BD
•Less Maintenance •Less Space
•Less Civil Work
Less Installation Time
•Energized Busbars during Maintenance
•Faster Maintenance
Safest switchgear
AIS for the 21st CENTURY
8BK80
Customer Benefits: Summary