Page 1 Prepared by: PTD-M/BD

8BK80 PANELS

Page 2: 8BK80 Modified

Page 2 Prepared by: PTD-M/BD

8BK80

8BK80 air-insulated, metal-cladMedium Voltage Switchgear

Page 3: 8BK80 Modified

Page 3 Prepared by: PTD-M/BDNote: Special Execution on request

Up to 3150A

3.6 kV

Up to 4000A

10kV

40kVp

26.3/31.5/44kA

66/80/110kAp

26.3/31.5/44kA

Nominal Current of Feeders

Rated Continuous Current of Busbar

Rated Power freq withstand voltage

Rated Lightning Impulse withstand Voltage

Rated Short Circuit Breaking Current

Rated Short Circuit Making Current

Rated Short time withstand Current (3sec)

12/ 38/ 95 kV BIL available on request

Product Rating

7.2kV

20kV

60kVp

26.3/31.5/44kA

26.3/31.5/44kA

66/80/110kAp

Up to 3150A

Up to 4000A

12kV

28kV

75kVp

26.3/31.5/44kA

26.3/31.5/44kA

66/80/110kAp

Up to 3150A

Up to 4000A

Page 4: 8BK80 Modified

Page 4 Prepared by: PTD-M/BD

Circuit Breaker

Siemens Make Vacuum Interrupter

Tulip contacts- Better current

carrying capacity

Improved contact arm design

Enclosed pole- increased reliability

Sealed for life gear box ensures

reliability of mechanism

Page 5: 8BK80 Modified

Page 5 Prepared by: PTD-M/BD

•Mechanism kinematics and interrupter force designed to ensure smooth operation

•Tested for Mechanical endurance of 10,000 operations (M2 class)

•Mechanical de-latching for spring charging motor ensures motor protection even under cut off switch failure

•Low arc energy with Vacuum technology means less erosion of contact & longer life

•Constant dielectric strength for a long period of time

Vacuum Circuit Breaker

Page 6: 8BK80 Modified

Page 6 Prepared by: PTD-M/BD

Use of maintenance-free Siemens Vacuum Circuit Breaker

on withdrawable truck means low life cycle costs.

Vacuum Circuit Breaker

Page 7: 8BK80 Modified

Page 7 Prepared by: PTD-M/BD

CB Chamber

All operations behind closed doors

Ramp for floor leveling

Truck type design – No CB handling

trolley

VCB truck earthing even in test

condition

Tested for 1,000 insertion &

withdrawals of CB truck as against 25

specified in IEC

Page 8: 8BK80 Modified

Page 8 Prepared by: PTD-M/BD

CB chamber

Busbar chamber shutter: Gravity

operated

Cable chamber shutter: Spring

operated

Padlocking of shutters

Independently lockable shutters

Guide rails for better alignment

Page 9: 8BK80 Modified

Page 9 Prepared by: PTD-M/BD

Busbar chamber

Better heat dissipation due to hollow,

triangular main busbar & round feeder

connections

Easy assembly of busbars at site

Design w/o sharp edges: reduced

electrical stress

Design facilitating more cooling air

Patented design of busbars with

increased capacity for heat dissipation

Reduced no. of joints: better thermal

capacity* Sleeving & BB shrouds optional

Page 10: 8BK80 Modified

Page 10 Prepared by: PTD-M/BD

Alternative 1:-

Panel standard depth of 1750mm containing:

a) 1 set of CT

b) 2 runs of cable termination

More equipments in the standard cable chamberMore equipments in the standard cable chamber Reducing the depth of typical Incomer panels thus saving vast Reducing the depth of typical Incomer panels thus saving vast spacespace Cable chamber with three different alternatives/configurationCable chamber with three different alternatives/configuration

Alternative 2:-

Panel standard depth of 1750mm containing:

a) 2 sets of CTs

b) earth switch

c) draw out PT from rear*

d) 2 runs of cable termination

Cable chamber

Withdrawable PT on VCB trolley also available

Page 11: 8BK80 Modified

Page 11 Prepared by: PTD-M/BD

Cable chamber

Alternative 3:-

Panel standard depth of 1750mm containing:

a) 2 sets of CTs

b) Earth Switch

c) 3 runs of cable termination

Alternative 4:-

Panel standard depth of 1750mm containing:

a) 2 sets of CTs

b) Up to 4 runs of cable termination

Page 12: 8BK80 Modified

Page 12 Prepared by: PTD-M/BD

End terminations eliminated by direct cable termination on C.T: less overheating problems

First set of C.T is sliding: Easy removal for maintenance

Both secondaries of C.Ts can be accessed easily

Cable chamber

No need to disconnect the cable for removal of first set of CT

Page 13: 8BK80 Modified

Page 13 Prepared by: PTD-M/BD

•For additional equipments/cables rear boxes of different sizes

are available: enhanced flexibility

•Full Height rear boxes are provided for the utter most safety of

the operator

•Cable size up to 630sqmm for three core and 1000 sqmm for

single core cable can be accommodated

•LV Box Height adjustable as per customer requirement

•Easy accessibility of both the CTs in case of two CTs for ease in

maintenance

Customer Benefits from cable chamber

Page 14: 8BK80 Modified

Page 14 Prepared by: PTD-M/BD

7.2 kV 12 kV

Available executions

3.6 kV

Note: Special Execution on request

Circuit breaker panel

Metering panel

Bus-Coupler +Adaptor

Cabling panel

Incoming/Outgoing in same panel

Page 15: 8BK80 Modified

Page 15 Prepared by: PTD-M/BD

8BK80: Benefits

1. Peace of Mind.

2. Saves Lives.

3. Increases Productivity.

4. Saves Money.

Page 16: 8BK80 Modified

Page 16 Prepared by: PTD-M/BD

8BK80: Benefit no.1

Peace of Mind

Page 17: 8BK80 Modified

Page 17 Prepared by: PTD-M/BD

Fully Type tested product

Di-electric tests

Temperature rise test

Short time withstand

Short circuit test & test duty

Double earth fault test

Mechanical endurance test

Ingress Protection Test

Cable charging

Capacitor Switching

STC/Making/Mechanical Operation of

Earthing switch

Internal Arc: 12kV 31.5kA for 0.1sec

Fulfilling all the mandatory type tests requirements of new IEC 62271-200/100

Both on main circuit and auxiliary circuit

STC test on main circuit, earth circuit and on sliding contact of earth circuit

Product is tested for solidly as well non-solidly earthed system

Separately tested for all three chambers

Page 18: 8BK80 Modified

Page 18 Prepared by: PTD-M/BD

Peace of Mind: How?

Easy rack-in / rack-out of switching devicethrough ramps and truck

Page 19: 8BK80 Modified

Page 19 Prepared by: PTD-M/BD

89290

42821

111

4213

5 32

416

311

479

245

86

22

10

3814

6

> 35000 8BK80 Panels in service worldwide

NepalBhutanSri-LankaBangladeshMaldivesMauritiusOmanQatarKuwaitJordan

KenyaZambiaEthiopiaTanzania

Brunei

A true international switchgear

Peace of Mind: How?

Page 20: 8BK80 Modified

Page 20 Prepared by: PTD-M/BD

Well Documented Quality Systems and Procedures

Peace of Mind: How?

Page 21: 8BK80 Modified

Page 21 Prepared by: PTD-M/BD

Peace of Mind 1.1 Factory assembled, fully type tested switchgear as per IEC 62271-200.

1.2 Testing of VCB inside the panel.

1.3 Preventive mechanical interlocks.

1.4 Siemens Vacuum switching technology.

Benefit Features

Peace of Mind: How?

Page 22: 8BK80 Modified

Page 22 Prepared by: PTD-M/BD

Peace of Mind 1.5 More tolerant to floor levelling.

1.6 Quality management according toISO 9001-2000

1.7 Design based on global best practise sharing and experience.

1.8 Routine Testing on 100% manufactured panels

1.9 Siemens Guarantee.

Benefit Features

Peace of Mind: How?

Page 23: 8BK80 Modified

Page 23 Prepared by: PTD-M/BD

8BK80: Benefit no.2

Saves Lives

Page 24: 8BK80 Modified

Page 24 Prepared by: PTD-M/BD

Forecast: Saves Lives

How much: Even one life!

How soon: As soon as you energize Siemens 8BK80 switchgear

Page 25: 8BK80 Modified

Page 25 Prepared by: PTD-M/BD

All operations behind closedDoor!

1. All switching operations including emergency manual

operations.

2. Operation of Earthing Switch.

3. Rack-in / rack-out operation of VCB truck.

4. Emergency manual charging of VCB operating mechanism.

Operator safety:

Saves Lives: How?

Page 26: 8BK80 Modified

Page 26 Prepared by: PTD-M/BD

Front door interlocks as per IEC 62271-200

1. Racking of VCB truck from Test to Service position not possible until the front door is closed and locked.

2. Front door cannot be closed and locked until the LV control plug is securely connected.

3. Front door cannot be opened until the VCB is switched OFF and racked out in Test position.

Operator safety:

Saves Lives: How?

Page 27: 8BK80 Modified

Page 27 Prepared by: PTD-M/BD

Partition class: PM

1. Earthed metallic shutters and partitions ensure partition class PM.

2. Class PM ensures no electric field in the opened compartment and no electrical field change in the adjacent compartments.

3. Thus partition class PM ensures safe maintenance when the switching device chamber is opened while keeping the bus bars as well as cables under charged conditions.

8BK80: Safest Switchgear

Saves Lives: How?

Page 28: 8BK80 Modified

Page 28 Prepared by: PTD-M/BD

Classification of the 8BK80 according to IEC 62271-200

Construction and design

Partition class PM (metallic)

Loss of service continuity category LSC2B

Compartment accessibility (standard)

– Bus bar compartment Tool-based

– Switching-device compartment Interlock-based

– Low-voltage compartment Tool-based

– Connection compartment Tool-based

Saves Lives: How?

Page 29: 8BK80 Modified

Page 29 Prepared by: PTD-M/BD

Compartmentalisation features

Metal enclosed switchgear – Designs acc. to Part 200

Access control Ÿinterlock-controlledŸprocedure-basedŸtool-based

Accessible compartment

Loss of service continuity LSC 1 LSC 2A LSC 2B

Non- accessible compartment

Partition class PM (metal) PI (non-metal)

Insulation medium ŸAmbient airŸFluid (gas or liquid)

Internal Arc Classification

Compartmentalisation features

Metal enclosed switchgear – Designs acc. to Part 200

Access control Ÿinterlock-controlledŸprocedure-basedŸtool-based

Accessible compartment

Loss of service continuity LSC 1 LSC 2A LSC 2B

Non- accessible compartment

Partition class PM (metal) PI (non-metal)

Insulation medium ŸAmbient airŸFluid (gas or liquid)

Internal Arc Classification IAC A FLR …kV…kA for …sec

Maintainability

Service continuity

Operator’s safety

Purpose

Classification based on purpose

Classification As per IEC 62271-200

Page 30: 8BK80 Modified

Page 30 Prepared by: PTD-M/BD

Internal arc classification

Classification IAC

Accessibility Type A

– Front Accessible

– Rear Accessible

– Lateral Accessible

Test current kA 31.5

Test duration s 0.1

Classification of the 8BK80 according to IEC 62271-200

Tested separately for each compartment i.e. BB, CB and cable compartment

Saves Lives: How?

Page 31: 8BK80 Modified

Page 31 Prepared by: PTD-M/BD

• Safety of operating personnel ensured by tests for

verifying the internal arc classification.

• Internal arc tests in accordance with IEC 62271-200,

Annex A.

• The switchgear complies with criteria 1 to 5 specified in

the mentioned standards for the basic version up to 31.5

kA (IAC 31.5 kA 0.1 sec. AFLR).

Internal arc classification

Saves Lives: How?

Page 32: 8BK80 Modified

Page 32 Prepared by: PTD-M/BD

Class A–Criterion 1

Correctly secured doors and covers do not open. Deformations are accepted conditionally.

–Criterion 2No fragmentation of enclosures occurs within the time specified for test. Projections of small parts up to 60 g are accepted.

–Criterion 3Arcing does not cause holes in the accessible sides up to a height of 2 m.

–Criterion 4Indicators do not ignite due to the effect of hot gases. Ignition caused by glowing particles rather than hot gases is allowed. Ignitions as a result of paint or sticker burning are also excluded.

–Criterion 5The enclosure remains connected to its earthing point.

8BK80: Complies with All Criterion for Internal Arc

IEC 62271-200 Definitions of the classification criteria

Page 33: 8BK80 Modified

Page 33 Prepared by: PTD-M/BD

Successfully Internal Arc Tested - If this failure happened in your 8BK80, no one would even be hurt.

Saves Lives: How?

Page 34: 8BK80 Modified

Page 34 Prepared by: PTD-M/BD

Vacuum Circuit Breaker means no explosion is possible.

Saves Lives: How?

Page 35: 8BK80 Modified

Page 35 Prepared by: PTD-M/BD

Which interrupter would you prefer?

Vacuum interrupters: no seals and gaskets &hence no vacuum loss.

Saves Lives: How?

Page 36: 8BK80 Modified

Page 36 Prepared by: PTD-M/BD

1. Arc medium free from toxic by-products2. Does not explode.3. Environment friendly and compatible.

Saves Lives: How?

Page 37: 8BK80 Modified

Page 37 Prepared by: PTD-M/BD

Saves Lives 1.1 All operations behind closed front door.

1.2 Front door interlocks with VCB.

1.3 Partition class PM.

1.4 Internal Arc Classification switchgear: IAC A FLR 31.5kA for 0.1sec

Benefit Features

Saves Lives: How?

Page 38: 8BK80 Modified

Page 38 Prepared by: PTD-M/BD

Saves Lives 1.5 Siemens vacuum switching technology.

1.6 Secured earthing of switching device in Service and Test position.

Benefit Features

Saves Lives: How?

Page 39: 8BK80 Modified

Page 39 Prepared by: PTD-M/BD

8BK80: Benefit no.3

Increased Productivity

Page 40: 8BK80 Modified

Page 40 Prepared by: PTD-M/BD

Loss of Service Continuity category LSC2B-PMMaintenance in switching device compartment

possible without de-energising the corresponding cable connections and bus bars.

Metallic and earthed shutters and partitions. Safe to touch

Increased Productivity: How?

Page 41: 8BK80 Modified

Page 41 Prepared by: PTD-M/BD

Use of maintenance-free Siemens Vacuum Circuit Breakermeans no interruption in power supply.

Increased Productivity: How?

Page 42: 8BK80 Modified

Page 42 Prepared by: PTD-M/BD

IncreasesProductivity

1.1 LSC2B-PM Switchgear.

1.2 Use of Vacuum switching technology.

Benefit Features

Increased Productivity: How?

Page 43: 8BK80 Modified

Page 43 Prepared by: PTD-M/BD

8BK80: Benefit no.4

Saves Money

Page 44: 8BK80 Modified

Page 44 Prepared by: PTD-M/BD

Effect On Floor Space

C.B Chamber

CableChamber

Cutout for Power Cable

C.B Chamber

CableChamber

Cutout for Power Cable

C.B Chamber

CableChamber

Cutout for Power Cable

C.BChamber

Cutout for Power Cable

CableChamber

C.BChamber

Cutout for Power Cable

CableChamber

C.BChamber

Cutout for Power Cable

CableChamber

I/C OG1 OG2 I/C OG1 OG2

Saving in space of

1.44sqm for

3 panels

2 Sets Of CTD/O PT3 Runs of Cab

1Sets Of CT2 Runs of Cab

1 Sets Of CT2 Runs of Cab 2 Sets Of CT

D/O PT3 Runs of Cab

1 Sets Of CT2 Runs of Cab

1 Sets Of CT2 Runs of Cab

Presently 600 mm rear box

Saves Money: How?

Page 45: 8BK80 Modified

Page 45 Prepared by: PTD-M/BD

Use of maintenance-free Siemens Vacuum Circuit Breakeron withdrawable truck means

low maintenance costs.

Saves Money: How?

Page 46: 8BK80 Modified

Page 46 Prepared by: PTD-M/BD

Use of maintenance-free Siemens Vacuum Circuit Breakermeans less life cycle cost.

Saves Money: How?

Page 47: 8BK80 Modified

Page 47 Prepared by: PTD-M/BD

Vacuum remainsconstant over time

A vacuum is a non-deteriorating extinguishing medium; no maintenance is required.

Saves Money: How?

Page 48: 8BK80 Modified

Page 48 Prepared by: PTD-M/BD

Oxidization-free contactsin vacuum

Oxidized contacts require maintenance.

Saves Money: How?

Page 49: 8BK80 Modified

Page 49 Prepared by: PTD-M/BD

OilOil

SF6SF6

VacuumVacuum

Breaking Current, kABreaking Current, kA

Low arc energy with vacuum technology; Very less erosion of contacts.

Saves Money: How?

Page 50: 8BK80 Modified

Page 50 Prepared by: PTD-M/BD

Faster Installation: Foundation Plan

C.BChamber

Cutout for Power Cable

CableChamber

1750

162

1030

400800

476

388

Only three fixing holes are required for mounting of the panel

Saves Money: How?

Page 51: 8BK80 Modified

Page 51 Prepared by: PTD-M/BD

Switchgear installation, operation and maintenance without any special tools and tackles means

low life cycle cost.

Saves Money: How?

Page 52: 8BK80 Modified

Page 52 Prepared by: PTD-M/BD

Reliable After Sales Service- Reduced downtime

Saves Money: How?

Page 53: 8BK80 Modified

Page 53 Prepared by: PTD-M/BD

Saves Money 1.1 Siemens Vacuum Technology: Less maintenance cost.

1.2 Faster Installation: Less installation cost.

1.3 Less total life cycle cost.

1.4 Use of recyclable material: saves money and environment

1.5 More equipment in same depth: reduced dimensions of room means less construction cost

Benefit Features

Saves Money: How?

Page 54: 8BK80 Modified

Page 54 Prepared by: PTD-M/BD

8BK80: Benefits’ summary

1. Peace of Mind.

2. Saves Lives.

3. Increases Productivity.

4. Saves Money.

Page 55: 8BK80 Modified

Page 55 Prepared by: PTD-M/BD

•Less Maintenance •Less Space

•Less Civil Work

Less Installation Time

•Energized Busbars during Maintenance

•Faster Maintenance

Safest switchgear

AIS for the 21st CENTURY

8BK80

Customer Benefits: Summary