80-a2012-rop

31
Report on Proposals 2012 Annual Revision Cycle NOTE: The proposed NFPA documents addressed in this Report on Proposals (ROP) and in a follow-up Report on Comments (ROC) will only be presented for action when proper Amending Motions have been submitted to the NFPA by the deadline of April 6, 2012. The June 2012 NFPA Conference & Expo will be held June 11–14, 2012, at the Mandalay Bay Convention Center, Las Vegas, NV. During the meeting, the Association Technical Meeting (Tech Session) will be held June 13–14, 2012. Documents that receive no motions will not be presented at the meeting and instead will be forwarded directly to the Standards Council for action on issuance. For more information on the rules and for up-to-date information on schedules and deadlines for processing NFPA documents, check the NFPA website (www.nfpa.org) or contact NFPA Standards Administration. ISSN 1079-5332 Copyright © 2011 All Rights Reserved NFPA and National Fire Protection Association are registered trademarks of the National Fire Protection Association, Quincy, MA 02169. National Fire Protection Association® 1 BATTERYMARCH PARK, QUINCY, MA 02169-7471 A compilation of NFPA ® Technical Committee Reports on Proposals for public review and comment Public Comment Deadline: August 30, 2011

Upload: ekhlasur-rahman

Post on 29-Sep-2015

224 views

Category:

Documents


1 download

DESCRIPTION

Sop

TRANSCRIPT

  • Report onProposals

    2012 Annual Revision Cycle

    NOTE: The proposed NFPA documents addressed in this Report on Proposals (ROP) and in a follow-up Report on Comments (ROC) will only be presented for action when proper Amending Motions have been submitted to the NFPA by the deadline of April 6, 2012. The June 2012 NFPA Conference & Expo will be held June 1114, 2012, at the Mandalay Bay Convention Center, Las Vegas, NV. During the meeting, the Association Technical Meeting (Tech Session) will be held June 1314, 2012. Documents that receive no motions will not be presented at the meeting and instead will be forwarded directly to the Standards Council for action on issuance. For more information on the rules and for up-to-date information on schedules and deadlines for processing NFPA documents, check the NFPA website (www.nfpa.org) or contact NFPA Standards Administration.

    ISSN 1079-5332 Copyright 2011 All Rights Reserved

    NFPA and National Fire Protection Association are registered trademarks of the National Fire Protection Association, Quincy, MA 02169.

    National Fire Protection Association1 BATTERYMARCH PARK, QUINCY, MA 02169-7471

    A compilation of NFPA TechnicalCommittee Reports on Proposals for public review and comment

    Public Comment Deadline: August 30, 2011

  • Information on NFPA Codes and Standards Development

    I. Applicable Regulations. The primary rules governing the processing of NFPA documents (codes, standards, recommended practices, and guides) are the NFPA Regulations Governing Committee Projects (Regs). Other applicable rules include NFPA Bylaws, NFPA Technical Meeting Convention Rules, NFPA Guide for the Conduct of Participants in the NFPA Standards Development Process, and the NFPA Regulations Governing Petitions to the Board of Directors from Decisions of the Standards Council. Most of these rules and regulations are contained in the NFPA Directory. For copies of the Directory, contact Codes and Standards Administration at NFPA Headquarters; all these documents are also available on the NFPA website at www.nfpa.org.

    The following is general information on the NFPA process. All participants, however, should refer to the actual rules and regulations for a full understanding of this process and for the criteria that govern participation.

    II. Technical Committee Report. The Technical Committee Report is defined as the Report of the Technical Committee and Technical Correlating Committee (if any) on a document consisting of the ROP and ROC. A Technical Committee Report consists of the Report on Proposals (ROP), as modified by the Report on Comments (ROC), published by the Association.

    III. Step 1: Report on Proposals (ROP). The ROP is defined as a report to the Association on the actions taken by Technical Committees and/or Technical Correlating Committees, accompanied by a ballot statement and one or more proposals on text for a new document or to amend an existing document. Any objection to an action in the ROP must be raised through the filing of an appropriate Comment for consideration in the ROC or the objection will be considered resolved. IV. Step 2: Report on Comments (ROC). The ROC is defined as a report to the Association on the actions taken by Technical Committees and/or Technical Correlating Committees accompanied by a ballot statement and one or more comments resulting from public review of the Report on Proposals (ROP). The ROP and the ROC together constitute the Technical Committee Report. Any outstanding objection following the ROC must be raised through an appropriate Amending Motion at the Association Technical Meeting or the objection will be considered resolved.

    V. Step 3a: Action at Association Technical Meeting. Following the publication of the ROC, there is a period during which those wishing to make proper Amending Motions on the Technical Committee Reports must signal their intention by submitting a Notice of Intent to Make a Motion. Documents that receive notice of proper Amending Motions (Certified Amending Motions) will be presented for action at the annual June Association Technical Meeting. At the meeting, the NFPA membership can consider and act on these Certified Amending Motions as well as Follow-up Amending Motions, that is, motions that become necessary as a result of a previous successful Amending Motion. (See 4.6.2 through 4.6.9 of Regs for a summary of the available Amending Motions and who may make them.) Any outstanding objection following action at an Association Technical Meeting (and any further Technical Committee consideration following successful Amending Motions, see Regs at 4.7) must be raised through an appeal to the Standards Council or it will be considered to be resolved.

    VI. Step 3b: Documents Forwarded Directly to the Council. Where no Notice of Intent to Make a Motion (NITMAM) is received and certified in accordance with the Technical Meeting Convention Rules, the document is forwarded directly to the Standards Council for action on issuance. Objections are deemed to be resolved for these documents. VII. Step 4a: Council Appeals. Anyone can appeal to the Standards Council concerning procedural or substantive matters related to the development, content, or issuance of any document of the Association or on matters within the purview of the authority of the Council, as established by the Bylaws and as determined by the Board of Directors. Such appeals must be in written form and filed with the Secretary of the Standards Council (see 1.6 of Regs). Time constraints for filing an appeal must be in accordance with 1.6.2 of the Regs. Objections are deemed to be resolved if not pursued at this level.

    VIII. Step 4b: Document Issuance. The Standards Council is the issuer of all documents (see Article 8 of Bylaws). The Council acts on the issuance of a document presented for action at an Association Technical Meeting within 75 days from the date of the recommendation from the Association Technical Meeting, unless this period is extended by the Council (see 4.8 of Regs). For documents forwarded directly to the Standards Council, the Council acts on the issuance of the document at its next scheduled meeting, or at such other meeting as the Council may determine (see 4.5.6 and 4.8 of Regs).

    IX. Petitions to the Board of Directors. The Standards Council has been delegated the responsibility for the administration of the codes and standards development process and the issuance of documents. However, where extraordinary circumstances requiring the intervention of the Board of Directors exist, the Board of Directors may take any action necessary to fulfill its obligations to preserve the integrity of the codes and standards development process and to protect the interests of the Association. The rules for petitioning the Board of Directors can be found in the Regulations Governing Petitions to the Board of Directors from Decisions of the Standards Council and in 1.7 of the Regs.

    X. For More Information. The program for the Association Technical Meeting (as well as the NFPA website as information becomes available) should be consulted for the date on which each report scheduled for consideration at the meeting will be presented. For copies of the ROP and ROC as well as more information on NFPA rules and for up-to-date information on schedules and deadlines for processing NFPA documents, check the NFPA website (www.nfpa.org) or contact NFPA Codes & Standards Administration at (617) 984-7246.

  • 2012 Annual Revision Cycle ROP Contents

    by NFPA Numerical Designation

    Note: Documents appear in numerical order.

    NFPA No. Type Action Title Page No.

    13 P Standard for the Installation of Sprinkler Systems ......................................................................................... 13-1 13D P Standard for the Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes ............................................................................................................................ 13D-1 13R P Standard for the Installation of Sprinkler Systems in Residential Occupancies up to and Including Four Stories in Height ................................................................................................. 13R-1 20 P Standard for the Installation of Stationary Pumps for Fire Protection ........................................................... 20-1 24 P Standard for the Installation of Private Fire Service Mains and Their Appurtenances ................................ .24-1 51 P Standard for the Design and Installation of Oxygen-Fuel Gas Systems for Welding, Cutting, and Allied Processes51-1 55 P Compressed Gases and Cryogenic Fluids Code.55-1 61 P Standard for the Prevention of Fires and Dust Explosions in Agricultural and Food Processing Facilities...61-1 72 P National Fire Alarm and Signaling Code ..................................................................................................... 72-1 80 P Standard for Fire Doors and Other Opening Protectives ................................................................................ 80-1

    101A P Guide on Alternative Approaches to Life Safety ...................................................................................... 101A-1 105 P Standard for the Installation of Smoke Door Assemblies and Other Opening Protectives ...................................................................................................................................... 105-1 110 P Standard for Emergency and Standby Power Systems ................................................................................. 110-1 111 P Standard on Stored Electrical Energy Emergency and Standby Power Systems......................................... 111-1

    291 P Recommended Practice for Fire Flow Testing and Marking of Hydrants ................................................... 291-1 301 P Code for Safety to Life from Fire on Merchant Vessels .............................................................................. 301-1 400 P Hazardous Materials Code ............................................................................................................................ 400-1 402 P Guide for Aircraft Rescue and Fire-Fighting Operations ............................................................................. 402-1 415 P Standard on Airport Terminal Buildings, Fueling Ramp Drainage, and Loading Walkways ..................... 415-1 424 P Guide for Airport/Community Emergency Planning .................................................................................. 424-1 450 P Guide for Emergency Medical Services and Systems .................................................................................. 450-1 472 P Standard for Competence of Responders to Hazardous Materials/Weapons of Mass Destruction Incidents ...................................................................................................................... 472-1 473 P Standard for Competencies for EMS Personnel Responding to Hazardous Materials/Weapons of Mass Destruction Incidents ...................................................................................... 473-1 555 P Guide on Methods for Evaluating Potential for Room Flashover555-1

  • 654 P Standard for the Prevention of Fire and Dust Explosions from the Manufacturing, Processing, and Handling of Combustible Particulate Solids654-1 1001 P Standard for Fire Fighter Professional Qualifications1001-1 1122 P Code for Model Rocketry....1122-1 1124 P Code for the Manufacture, Transportation, Storage, and Retail Sales of Fireworks and Pyrotechnic Articles1124-1 1127 P Code for High Power Rocketry...1127-1 1128DS N Draft Standard for Standard Method of Fire Test for Flame

    Breaks1128DS-1 1129DS N Draft Standard for Standard Method of Fire Test for Covered Fuse on Consumer

    Fireworks1129DS-1 1144 P Standard for Reducing Structure Ignition Hazards from Wildland Fire .1144-1 1221 P Standard for the Installation, Maintenance, and Use of Emergency Services Communications Systems.1221-1 1500 P Standard on Fire Department Occupational Safety and Health

    Program..1500-1 1582 P Standard on Comprehensive Occupational Medical Program for Fire Departments1582-1 1801 P Standard on Thermal Imagers for the Fire Service.1801-1 1917 N Standard for Automotive Ambulances....1917-1

    TYPES OF ACTION

    P Partial Revision C Complete Revision N New Document R Reconfirmation W Withdrawal

  • iii

    Agricultural Dusts 61 Standard for the Prevention of Fire and Dust Explosions in Agricultural and Food Processing Facilities P 61-1 Aircraft Rescue and Fire Fighting 402 Guide for Aircraft Rescue and Fire-Fighting Operations P 402-1 424 Guide for Airport/Community Emergency Planning P 424-1 Airport Facilities 415 Standard on Airport Terminal Buildings, Fueling Ramp Drainage, and Loading Walkways P 415-1 Ambulances 1917 Standard for Automotive Ambulances N 1917-1 Automatic Sprinkler Systems 13 Standard for the Installation of Sprinkler Systems P 13-1 Residential Sprinkler Systems 13D Standard for the Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes P 13D-1 13R Standard for the Installation of Sprinkler Systems in Residential Occupancies up to and Including Four Stories in Height P 13R-1 Private Water Supply Piping Systems 24 Standard for the Installation of Private Fire Service Mains and Their Appurtenances P 24-1 291 Recommended Practice for Fire Flow Testing and Marking of Hydrants P 291-1 Fire and Emergency Services Protective Clothing Equipment Electronic Safety Equipment 1801 Standard on Thermal Imagers for the Fire Service P 1801-1 Emergency Medical Services 450 Guide for Emergency Medical Services and Systems P 450-1 Fire Doors and Windows 80 Standard for Fire Doors and Other Opening Protectives P 80-1 105 Standard for the Installation of Smoke Door Assemblies and Other Opening Protectives P 105-1 Fire Pumps 20 Standard for the Installation of Stationary Pumps for Fire Protection P 20-1 Fire Service Occupational Safety and Health 1500 Standard on Fire Department Occupational Safety and Health Program P 1500-1 1582 Standard on Comprehensive Occupational Medical Program for Fire Departments P 1582-1 Forest and Rural Fire Protection 1144 Standard for Reducing Structure Ignition Hazards from Wildland Fire P 1144-1 Handling and Conveying of Dusts, Vapors, and Gases 654 Standard for the Prevention of Fire and Dust Explosions from the Manufacturing Processing, and Handling of Combustible Particulate Solids P 654-1 Hazard and Risk of Contents and Furnishings 555 Guide on Methods for Evaluating Potential for Room Flashover P 555-1 Hazardous Chemicals 400 Hazardous Materials Code P 400-1 Hazardous Materials Response Personnel 472 Standard for Competence of Responders to Hazardous Materials/ Weapons of Mass Destruction Incidents P 472-1 473 Standard for Competencies for EMS Personnel Responding to Hazardous Materials/Weapons of Mass Destruction Incidents P 473-1 Industrial and Medical Gases 51 Standard for the Design and Installation of Oxygen-Fuel Gas Systems for Welding, Cutting, and Allied Processes P 51-1 55 Compressed Gases and Cryogenic Fluids Code P 55-1 Merchant Vessels 301 Code for Safety to Life from Fire on Merchant Vessels P 301-1

  • iii

    National Electrical Code Emergency Power Supplies 110 Standard for Emergency and Standby Power Systems P 110-1 111 Standard on Stored Electrical Energy Emergency and Standby Power Systems P 111-1 Professional Qualifications Fire Fighter Professional Qualifications 1001 Standard for Fire Fighter Professional Qualifications P 1001-1 Public Emergency Service Communication 1221 Standard for the Installation, Maintenance, and Use of Emergency Services Communications Systems P 1221-1 Pyrotechnics 1122 Code for Model Rocketry P 1122-1 1124 Code for the Manufacture, Transportation, Storage, and Retail Sales of Fireworks and Pyrotechnic Articles P 1124-1 1127 Code for High Power Rocketry P 1127-1 1128DS Draft Standard for Standard Method of Fire Tests for Flame Breaks N 1128DS-1 1129DS Draft Standard for Standard Method of Fire Test for Covered Fuse on Consumer Fireworks N 1129DS-1 Safety to Life Alternative Approaches to Life Safety 101A Guide on Alternative Approaches to Life Safety P 101A-1 Signaling Systems for the Protection of Life and Property 72 National Fire Alarm Code P 72-1

  • v

    COMMITTEE MEMBER CLASSIFICATIONS1,2,3,4

    The following classifications apply to Committee members and represent their principal interest in the activity of the Committee. 1. M Manufacturer: A representative of a maker or marketer of a product, assembly, or system, or portion thereof,

    that is affected by the standard. 2. U User: A representative of an entity that is subject to the provisions of the standard or that voluntarily uses the

    standard. 3. IM Installer/Maintainer: A representative of an entity that is in the business of installing or maintaining a product,

    assembly, or system affected by the standard. 4. L Labor: A labor representative or employee concerned with safety in the workplace. 5. RT Applied Research/Testing Laboratory: A representative of an independent testing laboratory or independent

    applied research organization that promulgates and/or enforces standards. 6. E Enforcing Authority: A representative of an agency or an organization that promulgates and/or enforces

    standards. 7. I Insurance: A representative of an insurance company, broker, agent, bureau, or inspection agency. 8. C Consumer: A person who is or represents the ultimate purchaser of a product, system, or service affected by the

    standard, but who is not included in (2). 9. SE Special Expert: A person not representing (1) through (8) and who has special expertise in the scope of the

    standard or portion thereof. NOTE 1: Standard connotes code, standard, recommended practice, or guide. NOTE 2: A representative includes an employee. NOTE 3: While these classifications will be used by the Standards Council to achieve a balance for Technical Committees, the Standards Council may determine that new classifications of member or unique interests need representation in order to foster the best possible Committee deliberations on any project. In this connection, the Standards Council may make such appointments as it deems appropriate in the public interest, such as the classification of Utilities in the National Electrical Code Committee. NOTE 4: Representatives of subsidiaries of any group are generally considered to have the same classification as the parent organization.

  • FORM FOR COMMENT ON NFPA REPORT ON PROPOSALS 2012 ANNUAL REVISION CYCLE

    FINAL DATE FOR RECEIPT OF COMMENTS: 5:00 pm EDST, August 30, 2011

    For further information on the standards-making process, please contact the Codes and Standards Administration at 617-984-7249 or visit www.nfpa.org/codes.

    For technical assistance, please call NFPA at 1-800-344-3555.

    FOR OFFICE USE ONLY

    Log #:

    Date Recd:

    Please indicate in which format you wish to receive your ROP/ROC electronic paper download (Note: If choosing the download option, you must view the ROP/ROC from our website; no copy will be sent to you.)

    Date 8/1/200X Name John B. Smith Tel. No. 253-555-1234

    Company Email

    Street Address 9 Seattle St. City Tacoma State WA Zip 98402

    ***If you wish to receive a hard copy, a street address MUST be provided. Deliveries cannot be made to PO boxes.

    Please indicate organization represented (if any) Fire Marshals Assn. of North America

    1. (a) NFPA Document Title National Fire Alarm Code NFPA No. & Year NFPA 72, 200X ed.

    (b) Section/Paragraph 4.4.1.1

    2. Comment on Proposal No. (from ROP): 72-7

    3. Comment Recommends (check one): new text revised text deleted text

    4. Comment (include proposed new or revised wording, or identification of wording to be deleted): [Note: Proposed text should be in legislative format; i.e., use underscore to denote wording to be inserted (inserted wording) and strike-through to denote wording to be deleted (deleted wording).]

    Delete exception.

    5. Statement of Problem and Substantiation for Comment: (Note: State the problem that would be resolved by your recommendation; give the specific reason for your Comment, including copies of tests, research papers, fire experience, etc. If more than 200 words, it may be abstracted for publication.)

    A properly installed and maintained system should be free of ground faults. The occurrence of one or more ground faults should be required to cause a trouble signal because it indicates a condition that could contribute to future malfunction of the system. Ground fault protection has been widely available on these systems for years and its cost is negligible. Requiring it on all systems will promote better installations, maintenance and reliability.

    6. Copyright Assignment

    (a) I am the author of the text or other material (such as illustrations, graphs) proposed in the Comment.

    (b) Some or all of the text or other material proposed in this Comment was not authored by me. Its source is as follows: (please identify which material and provide complete information on its source)

    I hereby grant and assign to the NFPA all and full rights in copyright in this Comment and understand that I acquire no rights in any publication of NFPA in which this Comment in this or another similar or analogous form is used. Except to the extent that I do not have authority to make an assignment in materials that I have identified in (b) above, I hereby warrant that I am the author of this Comment and that I have full power and authority to enter into this assignment.

    Signature (Required)

    PLEASE USE SEPARATE FORM FOR EACH COMMENT

    Mail to: Secretary, Standards Council National Fire Protection Association 1 Batterymarch Park Quincy, MA 02169-7471 OR

    Fax to: (617) 770-3500 OR Email to: [email protected]

  • FORM FOR COMMENT ON NFPA REPORT ON PROPOSALS 2012 ANNUAL REVISION CYCLE

    FINAL DATE FOR RECEIPT OF COMMENTS: 5:00 pm EDST, August 30, 2011

    For further information on the standards-making process, please contact the Codes and Standards Administration at 617-984-7249 or visit www.nfpa.org/codes.

    For technical assistance, please call NFPA at 1-800-344-3555.

    FOR OFFICE USE ONLY

    Log #:

    Date Recd:

    Please indicate in which format you wish to receive your ROP/ROC electronic paper download (Note: If choosing the download option, you must view the ROP/ROC from our website; no copy will be sent to you.)

    Date Name Tel. No.

    Company Email Street Address City State Zip

    ***If you wish to receive a hard copy, a street address MUST be provided. Deliveries cannot be made to PO boxes.

    Please indicate organization represented (if any)

    1. (a) NFPA Document Title NFPA No. & Year

    (b) Section/Paragraph

    2. Comment on Proposal No. (from ROP):

    3. Comment Recommends (check one): new text revised text deleted text

    4. Comment (include proposed new or revised wording, or identification of wording to be deleted): [Note: Proposed text should be in legislative format; i.e., use underscore to denote wording to be inserted (inserted wording) and strike-through to denote wording to be deleted (deleted wording).]

    5. Statement of Problem and Substantiation for Comment: (Note: State the problem that would be resolved by your recommendation; give the specific reason for your Comment, including copies of tests, research papers, fire experience, etc. If more than 200 words, it may be abstracted for publication.)

    6. Copyright Assignment

    (a) I am the author of the text or other material (such as illustrations, graphs) proposed in the Comment.

    (b) Some or all of the text or other material proposed in this Comment was not authored by me. Its source is as follows: (please identify which material and provide complete information on its source)

    I hereby grant and assign to the NFPA all and full rights in copyright in this Comment and understand that I acquire no rights in any publication of NFPA in which this Comment in this or another similar or analogous form is used. Except to the extent that I do not have authority to make an assignment in materials that I have identified in (b) above, I hereby warrant that I am the author of this Comment and that I have full power and authority to enter into this assignment.

    Signature (Required)

    PLEASE USE SEPARATE FORM FOR EACH COMMENT

    Mail to: Secretary, Standards Council National Fire Protection Association 1 Batterymarch Park Quincy, MA 02169-7471 OR

    Fax to: (617) 770-3500 OR Email to: [email protected]

  • Sequence of Events Leading to Issuance of an NFPA Committee Document

    Step 1 Call for Proposals

    Proposed new document or new edition of an existing document is entered into one of two yearly revision cycles, and a Call for Proposals is published.

    Step 2 Report on Proposals (ROP)

    Committee meets to act on Proposals, to develop its own Proposals, and to prepare its Report. Committee votes by written ballot on Proposals. If two-thirds approve, Report goes forward. Lacking two-thirds approval, Report returns to Committee.

    Report on Proposals (ROP) is published for public review and comment. Step 3 Report on Comments (ROC)

    Committee meets to act on Public Comments to develop its own Comments, and to prepare its report. Committee votes by written ballot on Comments. If two-thirds approve, Report goes forward. Lacking two-thirds approval, Report returns to Committee.

    Report on Comments (ROC) is published for public review. Step 4 Association Technical Meeting

    Notices of intent to make a motion are filed, are reviewed, and valid motions are certified for presentation at the Association Technical Meeting. (Consent Documents that have no certified motions bypass the Association Technical Meeting and proceed to the Standards Council for issuance.)

    NFPA membership meets each June at the Association Technical Meeting and acts on Technical Committee Reports (ROP and ROC) for documents with certified amending motions.

    Committee(s) vote on any amendments to Report approved at NFPA Association Technical Meeting. Step 5 Standards Council Issuance

    Notification of intent to file an appeal to the Standards Council on Association action must be filed within 20 days of the NFPA Association Technical Meeting.

    Standards Council decides, based on all evidence, whether or not to issue document or to take other action, including hearing any appeals.

  • The Association Technical Meeting

    The process of public input and review does not end with the publication of the ROP and ROC. Following the completion of the Proposal and Comment periods, there is yet a further opportunity for debate and discussion through the Association Technical Meeting that takes place at the NFPA Annual Meeting.

    The Association Technical Meeting provides an opportunity for the final Technical Committee Report (i.e., the ROP and ROC) on each proposed new or revised code or standard to be presented to the NFPA membership for the debate and consideration of motions to amend the Report. The specific rules for the types of motions that can be made and who can make them are set forth in the NFPA Regulations Governing Committee Projects (Regs), which should always be consulted by those wishing to bring an issue before the membership at an Association Technical Meeting. The following presents some of the main features of how a Report is handled.

    The Filing of a Notice of Intent to Make a Motion. Before making an allowable motion at an Association Technical Meeting, the intended maker of the motion must file, in advance of the session, and within the published deadline, a Notice of Intent to Make a Motion. A Motions Committee appointed by the Standards Council then reviews all notices and certifies all amending motions that are proper. The Motions Committee can also, in consultation with the makers of the motions, clarify the intent of the motions and, in certain circumstances, combine motions that are dependent on each other together so that they can be made in one single motion. A Motions Committee report is then made available in advance of the meeting listing all certified motions. Only these Certified Amending Motions, together with certain allowable Follow-Up Motions (that is, motions that have become necessary as a result of previous successful amending motions) will be allowed at the Association Technical Meeting.

    Consent Documents. Often there are codes and standards up for consideration by the membership that will be noncontroversial and no proper Notices of Intent to Make a Motion will be filed. These Consent Documents will bypass the Association Technical Meeting and head straight to the Standards Council for issuance. The remaining documents are then forwarded to the Association Technical Meeting for consideration of the NFPA membership.

    What Amending Motions Are Allowed. The Technical Committee Reports contain many Proposals and Comments that the Technical Committee has rejected or revised in whole or in part. Actions of the Technical Committee published in the ROP may also eventually be rejected or revised by the Technical Committee during the development of its ROC. The motions allowed by NFPA rules provide the opportunity to propose amendments to the text of a proposed code or standard based on these published Proposals, Comments, and Committee actions. Thus, the list of allowable motions include motions to accept Proposals and Comments in whole or in part as submitted or as modified by a Technical Committee action. Motions are also available to reject an accepted Comment in whole or part. In addition, Motions can be made to return an entire Technical Committee Report or a portion of the Report to the Technical Committee for further study.

    The NFPA Annual Meeting, also known as the NFPA Conference & Expo, takes place in June of each year. A second Fall membership meeting was discontinued in 2004, so the NFPA Technical Committee Report Session now runs once each year at the Annual Meeting in June.

    Who Can Make Amending Motions. NFPA rules also define those authorized to make amending motions. In many cases, the maker of the motion is limited by NFPA rules to the original submitter of the Proposal or Comment or his or her duly authorized representative. In other cases, such as a Motion to Reject an accepted Comment, or to Return a Technical Committee Report or a portion of a Technical Committee Report for Further Study, anyone can make these motions. For a complete explanation, the NFPA Regs should be consulted.

  • Action on Motions at the Association Technical Meeting. In order to actually make a Certified Amending Motion at the Association Technical Meeting, the maker of the motion must sign in at least an hour before the session begins. In this way a final list of motions can be set in advance of the session. At the session, each proposed document up for consideration is presented by a motion to adopt the Technical Committee Report on the document. Following each such motion, the presiding officer in charge of the session opens the floor to motions on the document from the final list of Certified Amending Motions followed by any permissible Follow-Up Motions. Debate and voting on each motion proceeds in accordance with NFPA Regs. NFPA membership is not required in order to make or speak to a motion, but voting is limited to NFPA members who have joined at least 180 days prior to the Association Technical Meeting and have registered for the meeting. At the close of debate on each motion, voting takes place, and the motion requires a majority vote to carry. In order to amend a Technical Committee Report, successful amending motions must be confirmed by the responsible Technical Committee, which conducts a written ballot on all successful amending motions following the meeting and prior to the document being forwarded to the Standards Council for issuance.

    Standards Council Issuance

    One of the primary responsibilities of the NFPA Standards Council, as the overseer of the NFPA codes and standards development process, is to act as the official issuer of all NFPA codes and standards. When it convenes to issue NFPA documents, it also hears any appeals related to the document. Appeals are an important part of assuring that all NFPA rules have been followed and that due process and fairness have been upheld throughout the codes and standards development process. The Council considers appeals both in writing and through the conduct of hearings at which all interested parties can participate. It decides appeals based on the entire record of the process as well as all submissions on the appeal. After deciding all appeals related to a document before it, the Council, if appropriate, proceeds to issue the document as an official NFPA code or standard. Subject only to limited review by the NFPA Board of Directors, the decision of the Standards Council is final, and the new NFPA code or standard becomes effective twenty days after Standards Council issuance.

  • 80-1

    Report on Proposals A2012 Copyright, NFPA NFPA 80Kurt A. Roeper, Ingersoll-Rand Security Technologies, OH [M] (Alt. to Thomas R. Janicak)Thomas M. Rubright, William S. Trimble Company, Inc., TN [M] (Alt. to Keith E. Pardoe) Emmanuel A. Sopeju, Underwriters Laboratories of Canada, Canada [RT] (Alt. to Matthew E. Schumann)Garry Stewart, The Doorman Service Company, Inc., WA [IM] (Alt. to Daniel R. Bernacki) David V. Tomecek, Hughes Associates, Inc., CO [SE] (Alt. to Bruce G. Campbell)John Woestman, The Kellen Company, IA [M] (Alt. to David A. San Paolo)

    Nonvoting

    John G. Degenkolb, Carson City, NV (Member Emeritus)Joseph N. Saino, Memphis, TN [SE] (Member Emeritus) Staff Liaison: Kristin Collette

    Committee Scope: This Committee shall have primary responsibility for documents on the installation and maintenance of fire doors, windows, shutters, and other equipment used to restrict the spread of fire, including arrangements for automatic operation in case of fire. This includes installation to protect buildings against external fire and to restrict the spread of fire within buildings. Vault and record room doors are covered by the Technical Committee on Record Protection.

    This list represents the membership at the time the Committee was balloted on the text of this edition. Since that time, changes in the membership may have occurred. A key to classifications is found at the front of this book.

    The Technical Committee on Fire Doors and Windows is presenting two Reports for adoption, as follows:

    Report I: The Technical Committee proposes for adoption, amendments to NFPA 80, Standard for Fire Doors and Other Opening Protectives, 2010 edition. NFPA 80 is published in Volume 6 of the 20011 National Fire Codes and in separate pamphlet form.

    The report on NFPA 80 has been submitted to letter ballot of the Technical

    Committee on Fire Doors and Windows, which consists of 25 voting members. The results of the balloting, after circulation of any negative votes, can be found in the report.

    Report II: The Technical Committee proposes for adoption, amendments to NFPA 105, Standard for Smoke Door Assemblies and Other Opening Protectives, 2010 edition. NFPA 105 is published in Volume 8 of the 2011 National Fire Codes and in separate pamphlet form.

    The report on NFPA 105 has been submitted to letter ballot of the Technical Committee on Fire Doors and Windows, which consists of 25 voting members. The results of the balloting, after circulation of any negative votes, can be found in the report.

    Report of the Committee on

    Fire Doors and Windows

    Bruce G. Campbell, ChairHughes Associates, Inc., CO [SE]

    Calvin A. Banning, AREVA NP, Inc., TX [SE]Chad E. Beebe, American Society for Healthcare Engineering, WA [U]Daniel R. Bernacki, International Door Association, OH [IM] David S. Cha, Northwestern Memorial Hospital, IL [U]Paul R. Coleman, Hillsboro, OR [SE]William Conner, Bill Conner Associates LLC, IL [SE] Rep. American Society of Theater ConsultantsJerrold S. Gorrell, Theatre Safety Programs, AZ [IM] Rep. US Institute for Theatre TechnologyJeffrey E. Gould, FM Approvals/FM Global, MA [I]Steven C. Hahn, Lawrence Roll-Up Doors, Inc., CA [M] Rep. Door & Access Systems Manufacturers Assn. InternationalHarold D. Hicks, Jr., Atlantic Code Consultants, PA [SE]Thomas R. Janicak, Ceco Door Products, IL [M] Rep. Steel Door InstituteWilliam E. Koffel, Koffel Associates, Inc., MD [M] Rep. Glazing Industry Code CommitteeNancy L. Kokesh, Intertek Testing Services, WI [RT]Keith E. Pardoe, Door and Hardware Institute, VA [M]Vernon J. Patton, First Energy Corporation, OH [U]James S. Peterkin, Heery International, PA [U] Rep. NFPA Health Care SectionSteven P. Reynolds, The Peelle Company Ltd., Canada [M] Rep. National Elevator Industry Inc. (VL to Issue: Elevators)Ronald Rispoli, Entergy Corporation, AR [U]Thomas A. Salamone, AKF Engineers, NY [SE]David A. San Paolo, The Maiman Company, MO [M] Rep. Window & Door Manufacturers AssociationMichael L. Savage, Sr., Middle Department Inspection Agency, Inc., MD [E]Matthew E. Schumann, Underwriters Laboratories Inc., IL [RT]Michael Tierney, Builders Hardware Manufacturers Association, CT [M] Robert Van Becelaere, Ruskin Manufacturing, MO [M]Anthony W. Yuen, University of California, CA [U]

    Alternates

    Scott K. Anderson, FM Global, MA [I] (Alt. to Jeffrey E. Gould)Brian D. Black, BDBlack Codes, Inc., NY [M] (Alt. to Steven P. Reynolds)Richard Cookson, The Cookson Company, AZ [M] (Alt. to Steven C. Hahn) John G. Crowther, AREVA NP, Inc., TX [SE] (Alt. to Calvin A. Banning)Vickie J. Lovell, InterCode Incorporated, FL [M] (Alt. to William E. Koffel)

  • 80-2

    Report on Proposals A2012 Copyright, NFPA NFPA 80_______________________________________________________________ 80-1 Log #CP2 Final Action: Accept in Principle(Entire Document)_______________________________________________________________ Submitter: Technical Committee on Fire Doors and Windows, Recommendation: Review entire document to: 1) Update any extracted material by preparing separate proposals to do so, and 2) review and update references to other organizations documents, by preparing proposal(s) as required. Substantiation: To conform to the NFPA Regulations Governing Committee Projects. Committee Meeting Action: Accept in PrincipleThe Committee has reviewed the referenced documents and, assuming there may be additional revisions necessary, will make final updates at the ROC meeting. Committee Statement: The committee has reviewed any extracted sections as well as references to other organizations documents. To ensure that the most current edition is referenced the committee will take action on this at the ROC meeting. Number Eligible to Vote: 25 Ballot Results: Affirmative: 24 Ballot Not Returned: 1 Patton, V._______________________________________________________________ 80-2 Log #CP13 Final Action: Accept(1.1.4)_______________________________________________________________ Submitter: Technical Committee on Fire Doors and Windows, Recommendation: Revise text to read as follows: 1.1.4* This standard does not cover fire resistantance resistance rated glazing materials and horizontally sliding accordion or folding assemblies fabricated for use as walls and tested as wall assemblies in accordance with NFPA 251, Standard Methods of Tests of Fire Resistance of Building Construction and Materials.Substantiation: The proposed change is strictly editorial. It corrects an error in the current edition of the standard and replaces it with the proper terminology used throughout the standard. Committee Meeting Action: AcceptNumber Eligible to Vote: 25 Ballot Results: Affirmative: 24 Ballot Not Returned: 1 Patton, V._______________________________________________________________ 80-3 Log #1 Final Action: Accept in Principle(Chapter 2, Annex D, and Annex L)_______________________________________________________________ Note: This Proposal originates from Tentative Interim Amendment 80-10-1 (TIA 950) issued by the Standards Council on August 6, 2009.Submitter: Bruce G. Campbell, Hughes Associates, Inc.Recommendation: 1. Revise Chapter 2 to read as follows:2.3 Other Publications.2.3.1 ASME Publications. American Society of Mechanical Engineers, Three Park Avenue, New York, NY 10016-5990.ASME A17.1/CSA B44-07, Safety Code for Elevators and Escalators, 2004 including Addenda ASME A17.1a-2005 and ASME A17.1S-2005 2007.2.3.2 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959.ASTM A 36, Standard Specification for Carbon Structural Steel, 2005. ASTM A36 / A36M 08. ASTM D 4157, Standard Test Method for Abrasion Resistance of Textile Fabrics (Oscillatory Cylinder Method), 2002. 2007. ASTM D 5034, Standard Test Method for Breaking Strength and Elongation of Textile Fabrics (Grab Test), 2001. 2008.ASTM D 6193, Standard Practice for Stitches and Seams, 1997 (2004).2.3.3 CSA Publications. Canadian Standards Association, 500 Spectrum Way, Suite 100, Mississauga, ON L4W 5N6, Canada.CSA B44, Safety Code for Elevators, 2004.2.3.43 BHMA Publications. Builders Hardware Manufacturers Association, 335 Lexington Avenue, 17th Floor, New York, NY 10017.ANSI/BHMA A156.1, Standard for Butts and Hinges, 2000 2006. ANSI/BHMA A156.4, Standard for Door Controls (Closers), 2000. ANSI/BHMA A156.17, Standard for Self Closing Hinges & Pivots, 2004.2.3.54 GSA Publications. U.S. General Services Administration, 1800 F Street, N.W., Washington, DC 20405.Federal Specification A-A-1923A, Shield Expansion (Lag, Machine and Externally Threaded Wedge), 1995. Federal Specification A-A-1924A, Shield, Expansion (Self Drilling Tubular Expansion Shell Bolt), 1995. Federal Specification A-A-55614, Shield, Expansion (Non-Drilling Expansion Anchors), 1995.2.3.65 SMACNA Publications. Sheet Metal and Air Conditioning Contractors National Association, 4201 Lafayette Center Drive, Chantilly, VA 20151-1209. Fire, Smoke and Radiation Damper Installation Guide for HVAC Systems, 2002. 2.3.76 UL Publications. Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 6062-2096.UL 9, Standard for Fire Tests of Window Assemblies, 2000.

    UL 10A, Standard for Tin-Clad Fire Doors, 1998. UL 14C, Swing Hardware for Tin-Clad Doors Mounted Singly and in Pairs, 1999 2006. UL 33, Standard for Heat Responsive Links for Fire-Protection Services, 2003. UL 555, Standard for Fire Dampers, 1996 2006.2. Revise D.2 and D.10 as follows. D.2 The hourly designation indicates the duration of the fire test exposure and is known as the fire protection rating. Fire protection ratings of fire doors meeting this standard should be as determined and reported by a testing agency in accordance with NFPA 252, Standard Methods of Fire Tests of Door Assemblies. (See ASTM E 2074, Standard Test Method for Fire Tests of Door Assemblies, Including Positive Pressure Testing of Side-Hinged and Pivoted Swinging Door Assemblies; UL 10B, Standard for Safety Fire Tests of Door Assemblies; UL 10C, Standard for Positive Pressure Fire Tests of Door Assemblies; and CAN4-S104-M80, Standard Method for Fire Test of Door Assemblies.)D.10 The hourly designation indicates the duration of the fire test exposure and is known as the fire protection rating. Fire protection ratings of windows meeting this standard should be as determined and reported by a testing agency in accordance with NFPA 257, Standard on Fire Test for Window and Glass Block Assemblies. (See ASTM E 2010, Standard Test Method for Positive Pressure Fire Tests of Window Assemblies; UL 9, Standard for Safety Fire Tests of Window Assemblies; and CAN4-S106-M80, Standard Method for Fire Test of Window and Glass Block Assemblies.)3. Revise Annex L to read as follows: L.1 Referenced Publications. The documents or portions thereof listed in this annex are referenced within the informational sections of this standard and are not part of the requirements of this document unless also listed in Chapter 2 for other reasons.L.1.1 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 72, National Fire Alarm and Signaling Code, 2007 2010 edition. NFPA 80A, Recommended Practice for Protection of Buildings from Exterior Fire Exposures, 2007 edition. NFPA 82, Standard on Incinerators and Waste and Linen Handling Systems and Equipment, 2004 2009 edition. NFPA 101, Life Safety Code, 2006 2009 edition. NFPA 105, Standard for the Installation of Smoke Door Assemblies and Other Opening Protectives, 2007 2010 edition. NFPA 232, Standard for the Protection of Records, 2007 edition. NFPA 251, Standard Methods of Tests of Fire Resistance of Building Construction and Materials, 2006 edition. NFPA 252, Standard Methods of Fire Tests of Door Assemblies, 2003 2008 edition. NFPA 257, Standard on Fire Test for Window and Glass Block Assemblies, 2007 edition. NFPA 288, Standard Methods of Fire Tests of Floor Fire Door Assemblies Installed Horizontally in Fire ResistanceRated Floor Systems, 2007 edition. Fire Protection Handbook, 19th, 2002, Section 12, Chap 5, Confinement of Fire in Buildings, pp. 12103 to 12108, Protection of Openings. Fire Protection Handbook, 20th, 2008, Section 18, Chap 1, Confinement of Fire in Buildings, pp. 1815 to 18121, Protection of Openings. SFPE Handbook of Fire Protection Engineering, 3rd 4th edition, 2002 2008.L.1.2 Other Publications. L.1.2.1 AMCA Publications. Air Movement & Control Association International, Inc., 30 W. University Drive, Arlington Heights, IL 60004. AMCA 503, Fire, Ceiling (Radiation), Smoke and Fire/Smoke Dampers Application Manual, 2003 2008.L.1.2.2 ASME Publications. American Society of Mechanical Engineers, Three Park Avenue, New York, NY 10016-5990. ASME A17.1/CSA B44, Safety Code for Elevators and Escalators, 2007.ASME A17.1/CSA B44, Handbook on Safety Code for Elevators and Escalators, 2004 2007.L.1.2.3 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P. O. Box C700, West Conshohocken, PA 19428-2959. ASTM D 5034, Standard Test Method for Breaking Strength and Elongation of Textile Fabrics (Grab Test), 2001. ASTM E 90, Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements, 2002 2004. ASTM E 413, Classification for Rating Sound Insulation, 2004. ASTM E 2010, Standard Test Method for Positive Pressure Fire Tests of Window Assemblies, 2001.ASTM E 2074, Standard Test Method for Fire Tests of Door Assemblies, Including Positive Pressure Testing of Side-Hinged and Pivoted Swinging Door Assemblies, 2000e1.L.1.2.4 CSA Publications. Canadian Standards Association, 500 Spectrum Way, Suite 100, Mississauga, ON L4W 5N6. CSA B44, Safety Code for Elevators, 2004.L.1.2.54 ISO Publications. International Organization for Standardization, 1, rue de Varemb, Case postale 56, CH-1211 Geneve 20, Switzerland. ISO 3009, Fire Resistance Tests Glazed Elements, 1976/Amd 1:1984.L.1.2.65 NAAMM/HMMA Publications. National Association of Architectural Metal Manufacturers/Hollow Metal Manufacturers Association, 8 South Michigan Avenue, Suite 1000, Chicago, IL 60603.

  • 80-3

    Report on Proposals A2012 Copyright, NFPA NFPA 80 NAAMM/HMMA-862, Guide Specifications for Commercial Security Hollow Metal Doors and Frames, 2003. NAAMM/HMMA-863, Guide Specifications for Detention Security Hollow Metal Doors and Frames, 5th ed., 2005. NAAMM/HMMA-866, Guide Specifications for Stainless Steel Hollow Metal Doors and Frames, 2001.L.1.2.76 SMACNA Publications. Sheet Metal and Air Conditioning Contractors National Association, 4201 Lafayette Center Drive, Chantilly, VA 20151-1209. Fire, Smoke and Radiation Damper Installation Guide for HVAC Systems, 2002. L.1.2.87 UL Publications. Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096. UL 9, Standard for Safety Fire Tests of Window Assemblies, 2000. UL 10B, Standard for Safety Fire Tests of Door Assemblies, 1997 2008. UL 10C, Standard for Positive Pressure Fire Tests of Door Assemblies, 1998. UL 752, Standard for Safety Bullet-Resisting Equipment, 2005. Fire Resistance Directory, 2005 2008.L.1.2.98 ULC Publications. Underwriters Laboratories of Canada, 7 Underwriters Road, Toronto, Ontario M1R 3B4, Canada. CAN4-S104-M80, Standard Method for Fire Test of Door Assemblies, 1988. CAN4-S106-M80, Standard Method for Fire Test of Window and Glass Block Assemblies, 1980.L.1.2.109 U.S. Government Publication. U.S. Government Printing Office, Washington, DC 20402. Title 16, Code of Federal Regulations, Part 1201, Standard for Architectural Glazing, January 6, 1977. L.1.2.1110 Additional Publications.Law, Margaret, Heat Radiation from Fires and Building Separation, Fire Research Technical Paper No. 5, London, 1963. Law, Margaret, Safe Distances from Wired Glass Screening a Fire, Institution of Fire Engineers Quarterly, London, 1969. Nelson, Harold E., Radiant Energy Transfer in Fire Protection Engineering Problem Solving, Fire Technology, Vol. 4, No. 3, August 1968, pp. 196205.L.2 Informational References. The following documents or portions thereof are listed here as informational resources only. They are not a part of the requirements of this document.L.2.1 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 82, Standard on Incinerators and Waste and Linen Handling Systems and Equipment, 2004 2009 edition. NFPA 232, Standard for the Protection of Records, 2007 edition.L.2.2 ANSI Publications. American National Standards Institute, 25 West 43rd Street, 4th floor, New York, NY 10036. ANSI A133.1, Tin-Clad Fire Doors Mounted Singly and in Pairs, 1993. ANSI Z97.1, Safety Performance Specifications and Methods of Test for Safety Glazing Materials Used in Buildings, 2004.Substantiation: EMERGENCY NATURE: This TIA updates the references in NFPA 80. The TCs action on ROP 80-2, which requested that the committee update all references to other organizations documents, was to complete this task at the ROC stage but it was not addressed. Throughout this current revision process for NFPA 80, Standard for Fire Doors and Other Opening Protectives, the Technical Committee overlooked updates to other organizations references. References to ASTM E2074 and ASTM E 2010 have been withdrawn by ASTM and are removed as references in Annex D. This TIA, which is of emergency nature as defined by the Regulations Governing Committee Projects Section 5.2 (a), updates the references throughout the document. Committee Meeting Action: Accept in PrincipleAccept proposed revisions with the following modification: ASME A17.1-2007/CSA B44-07, Safety Code for Elevators and Escalators, 2004 including Addenda ASME A17.1a-2005 and ASME A17.1S-2005 .Committee Statement: The Committee has reviewed the referenced documents and, assuming there may be additional revisions necessary, will make final updates at the ROC meeting. Number Eligible to Vote: 25 Ballot Results: Affirmative: 24 Ballot Not Returned: 1 Patton, V._______________________________________________________________ 80-4 Log #23 Final Action: Accept(2.3.6)_______________________________________________________________ Submitter: John F. Bender, Underwriters Laboratories Inc.Recommendation: Revise text to read as follows:2.3.6 UL Publications. Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096. ANSI/UL 9, Standard for Fire Tests of Window Assemblies, 2004, Revised April 2005 2009.ANSI/UL 10A, Standard for Tin-Clad Fire Doors, 1998, Revised March 2003 2009.ANSI/UL 14C, Swing Hardware for Tin-Clad Fire Doors Mounted Singly and in Pairs, 2006, Revised 2008. ANSI/UL 33, Standard for Heat Responsive Links for Fire-Protection Services, 2003, Revised September 2005 2010. ANSI/UL 555, Standard for Fire Dampers, 2006, Revised 2010.

    Substantiation: Add ANSI approval designation to ANSI/UL 10A and ANSI/UL 14C and update referenced standards to most recent revisions. Committee Meeting Action: AcceptNumber Eligible to Vote: 25 Ballot Results: Affirmative: 24 Ballot Not Returned: 1 Patton, V._______________________________________________________________ 80-5 Log #CP18 Final Action: Accept(3.3.x Sill)_______________________________________________________________ Submitter: Technical Committee on Fire Doors and Windows, Recommendation: Add new definition to read as follows:3.3.x Sill. The bottom part of an opening over which a fire door closes. Substantiation: Currently, there is no definition of sill in NFPA 80. Providing this definition clarifies the use of the term throughout the document and supports the changes made in 80-13 (Log #CP17). Committee Meeting Action: AcceptNumber Eligible to Vote: 25 Ballot Results: Affirmative: 24 Ballot Not Returned: 1 Patton, V._______________________________________________________________ 80-6 Log #CP3 Final Action: Accept(3.3.46 Field Modifications)_______________________________________________________________ Submitter: Technical Committee on Fire Doors and Windows, Recommendation: Revise text as follows: 3.3.46* Field Modifications. Changes,not otherwise permitted by this standard, made to a listed assembly or component after it has been manufactured. A.3.3.46 During installation, preparations made to fire door assemblies, such as those contained in Chapter 4, are not considered to be field modifications.Substantiation: This change clarifies the application of Section 5.1.2 on field modifications and also provides further clarification to the Authority Having Jurisdiction as to what changes to a fire door should be regulated as a field modification. The change also helps to differentiate between modifications to a fire door assembly and those allowable changes necessary for job site preparation work. Committee Meeting Action: AcceptNumber Eligible to Vote: 25 Ballot Results: Affirmative: 24 Ballot Not Returned: 1 Patton, V.Comment on Affirmative: JANICAK, T.: Recent discussions have indicated that the language as proposed will need clarification. I believe the intent of the committee is to permit the provisions of Section 4.1.3 to be performed during the useful life of the fire door and not only during the initial installation. The appendix note included with this proposal can be clarified as follows: Preparations made to fire door assemblies as defined in Section 4.3.1 can be performed throughout the useful life of the fire door. They are not to be considered Field Modifications as defined in Section 3.3.46. PARDOE, K.: Substantiation: Section 5.1.2 should be 5.1.4 in New Chapter 5 (80-17 Log #CP15). _______________________________________________________________ 80-7 Log #16 Final Action: Accept(3.3.50 Fire Door Assembly)_______________________________________________________________ Submitter: Kurt A. Roeper, Ingersoll-Rand Security TechnologiesRecommendation: Revise text to read as follows: 3.3.50 Fire Door Assembly. Any combination of a fire door, a frame, hardware, and other accessories that together provide a specific degree of fire protection or fire resistance to the opening.Substantiation: Fire door assemblies provide either fire protection or fire resistance, depending upon the application. Revising the definition as proposed clarifies this fact. Committee Meeting Action: AcceptNumber Eligible to Vote: 25 Ballot Results: Affirmative: 22 Negative: 2 Ballot Not Returned: 1 Patton, V.Explanation of Negative: KOFFEL, W.: I disagree with the revision to the definition. Fire resistance rated doors (and glazing) are not considered opening protectives by the building codes. Paragraph 1.1.4 states that the standard does not address fire resistance rated glazing and certain types of doors. If the change is appropriate, it would seem as if the same change should be made to the definition of fire window assembly. If we consider a fire resistance rated door an opening protective, it would be regulated by the opening protection limits in the building codes. PARDOE, K.: I agree with Mr. Koffels comment that was circulated on March 25th.

  • 80-4

    Report on Proposals A2012 Copyright, NFPA NFPA 80_______________________________________________________________ 80-8 Log #4 Final Action: Accept(3.3.114 Smoke Damper)_______________________________________________________________ Submitter: Glossary of Terms Technical Advisory Committee, Recommendation: Adopt the preferred definition of Smoke Damper from NFPA 5000. Smoke Damper. A device within an operating (dynamic) air distribution system to control the movement of smoke. Substantiation: This definition is the preferred definition from the Glossary of Terms. Your technical committee has the following options: a) Adopt the preferred definition b) Modify the term to make it unique c) Request that the Standards Council reassign responsibility for the term d) Request that the Standards Council authorize a second preferred definitionCommittee Meeting Action: AcceptNumber Eligible to Vote: 25 Ballot Results: Affirmative: 24 Ballot Not Returned: 1 Patton, V._______________________________________________________________ 80-9 Log #CP20 Final Action: Accept(4.2.5 and 6.1.2)_______________________________________________________________ Submitter: Technical Committee on Fire Doors and Windows, Recommendation: 1. Revise text to read as follows:6.1.2* Components. A fire door assembly shall consist of components that are separate products incorporated into the assembly and are allowed to have their own subcomponents. A.6.1.2 The normal components of a fire door assembly include a door, a door frame, hinges, a lock or latch, and a closing device. They also include, but are not limited to, an astragal, a split astragal, an automatic louver, a coordinator, flush or surface bolts, gasketing, a holder/release device, protection plates, and glazing materials. 4.2.5 Components. 4.2.5.1 A fire door assembly shall consist of components that are separate products incorporated into the assembly and are allowed to have their own subcomponents. 4.2.5.2* Except where restricted by individual published listings, a fire door assembly shall be permitted to consist of the labeled, listed, or classified components of different organizations that are acceptable to the AHJ. A.4.2.5.2 Because component elements that are not part of an assembly listing can be interchanged on a listed fire door it is the intent of this committee to permit a component part listed by one organization acceptable to the Authority Having Jurisdiction to be installed on a door listed by another such organization. 2. Revise Annex K as follows and renumber as needed:K.1 Except where restricted by individual published listings, a fire door assembly is permitted to consist of the labeled, listed, or classified components of different organizations that are acceptable to the AHJ Substantiation: The text is consistent with industry practice. In previous editions of the standard, this information has been contained partly in Chapter 6 and partly in the annex but this was not the appropriate location for the requirement. Moving both sections to Chapter 4 allows the requirement to be applied to all fire doors. This change is consistent with changes made by other model Codes. Committee Meeting Action: AcceptNumber Eligible to Vote: 25 Ballot Results: Affirmative: 24 Ballot Not Returned: 1 Patton, V._______________________________________________________________ 80-10 Log #17 Final Action: Accept(4.3.3)_______________________________________________________________ Submitter: Kurt A. Roeper, Ingersoll-Rand Security TechnologiesRecommendation: Revise text to read as follows: 4.3.3 Fire doors furnished with or prepared for fire exit hardware shall bear a label stating Fire Door to Be Equipped with Fire Exit Hardware. Substantiation: Section 4.3.2 recognizes that fire doors and builders hardware are permitted to be supplied separately, yet 4.3.3 only covers situations where fire exit hardware is furnished with fire exit hardware. The proposed language reflects the current industry practice as well as the provisions of manufacturers labeling procedures. Committee Meeting Action: AcceptNumber Eligible to Vote: 25 Ballot Results: Affirmative: 24 Ballot Not Returned: 1 Patton, V.

    _______________________________________________________________ 80-11 Log #11 Final Action: Accept in Principle(4.4.3.1 and A.4.4.3.1)_______________________________________________________________ Submitter: Thomas Zaremba, Roetzel and AndressRecommendation: Add at the end of current section 4.4.3.1:Vision panel kits consisting of multiple pieces (stick kits) shall be installed by the manufacturer of the door or a distributor with inspection service procedure under label service. Installation of two piece metal vision panel kits shall be permitted in the field. Revise Appendix A.4.4.3.1: The 2010 version of NFPA 80 has been modified to now require that stick kits containing multiple parts be installed by the door manufacturer. Otherwise, two piece metal vision panels in new wood fire doors may be have the glazing and light kits installed in the fieldat the door manufacturer or under theat manufacturers label service. This ensures that all components of complex stick kitsthe glazed assembly in the new wood door have been properly installed per the manufacturers follow-up service procedure. Substantiation: As currently, written, this provision is unduly restrictive in limiting installation of all light kits in new wood doors to the door manufacturer. Installation by the door manufacturer or a distributor under label service is important when stick kits involving multiple parts, including special clips or tapes, are involved. However, it is totally unnecessary when two piece metal kits are involved since those are made to fit only the cutout in the door and when glass is furnished, it can only fit those kits. The installation of two piece metal kits are routinely and properly installed in the field without special training or qualifications. Committee Meeting Action: Accept in PrincipleRevise text to read as follows: 4.4.3.1 For new wood doors, glazing materials in vision panels shall be installed in labeled glass light kits or in accordance with the fire door listing and shall be installed in accordance with inspection service procedure under label service or by certified or listed personnel. Committee Statement: Over the past years, there has been discussion in the fire door industry regarding glazing certification programs and there is currently a need for a certification and listing requirement for these products. This new requirement is providing an option for compliance by offering both label service and listed personnel. Listed personnel would be required to meet the definition of listed as contained in Chapter 3. The committee will review this requirement at the ROC stage to determine if an adequate glazing certification program has been developed for the time of publication of the 2013 edition of this document. In the event that a program has not been developed the committee will take appropriate action to reevaluate this requirement as needed. Number Eligible to Vote: 25 Ballot Results: Affirmative: 21 Negative: 3 Ballot Not Returned: 1 Patton, V.Explanation of Negative: HAHN, S.: I agree with Mr. Hicks comments. Changing the terms certified or listed to qualified would offer consistency with other sections of the Standard. HICKS, JR., H.: I find it very difficult to promote a code change that establishes a requirement for certification or listing of individuals when no such program exists. The certification process should be developed first and verified that it is functioning and providing sufficient numbers of certified individuals to avoid the appearance of writing a requirement around a specific individual or individuals. SAN PAOLO, D.: No glazing certification program exists, and thereby cannot be referenced by this document. The language should remain unchanged from the 2010 edition. _______________________________________________________________ 80-12 Log #6 Final Action: Accept in Principle(4.7.5.1.1, 4.7.5.1.2, and A.4.7.5.1)_______________________________________________________________ Note: This Proposal originates from Tentative Interim Amendment 80-10-2 (TIA 1001) issued by the Standards Council on October 20, 2010.Submitter: Joseph R. Hetzel, Door & Access Systems Manufacturers Association Recommendation: Add new text to read as follows: 4.7.5.1.1 Where fusible links are installed on both sides of the wall, a sleeve shall be installed through the wall to provide an open pathway for the cable/chain connecting the fusible links. 4.7.5.1.2 The sleeve shall be a 1/

    2-in. (13-mm) diameter galvanized steel

    conduit or pipe, with ends de-burred, and fitted with a collar or bushing at each end to secure the sleeve around the wall and allow free movement of the cable/chain through the sleeve upon fusing of the links. A.4.7.5.1 Wall sleeves required for the installation of fire door fusible links on both sides of a wall are unlike many other wall penetrations for pipes, conduits, ducts and the like. Such sleeves must remain open and unobstructed for free movement of the fusible link cable/chain upon fusing of the links. Firestopping or other sealants should not be used on sleeves because they can encumber movement and prevent automatic closing of a fire door in a fire event.

  • 80-5

    Report on Proposals A2012 Copyright, NFPA NFPA 80

    Sash chain or steel cable

    Washer (optional)Set collar or bushing in. EMT conduit or pipe

    Concrete, masonry,or approved non-masonry

    Substantiation: Rolling steel fire door manufacturers have become aware of an increasing trend towards more frequent and recurring questions from AHJs regarding the correct installation of wall sleeves for through-wall fusible links. Sleeves are referred to, but the method of installing such wall sleeves is inadequately documented in NFPA 80. AHJs are reluctant to accept manufacturers installation instructions, even though such instructions are referenced throughout NFPA 80. This matter is also outside the scope of listing agencies, as they regulate the manufacturing but not the installation of fire door products. Emergency Nature: The incorrect installation of a sleeve, or the misguided attempt to seal it, can create the potential for a life threatening condition resulting from a fire door being prevented from automatically closing. Committee Meeting Action: Accept in PrincipleAdd new text to read as follows: 4.7.5.1.1 Where fusible links are installed on both sides of the wall, a sleeve shall be installed through the wall to provide an open pathway for the cable or chain connecting the fusible links. 4.7.5.1.2 The sleeve shall be a -in. (13-mm) diameter galvanized steel conduit or pipe, with ends de-burred, and fitted with a collar or bushing at each end to secure the sleeve around the wall and allow free movement of the cable or chain through the sleeve upon fusing of the links. A.4.7.5.1 Wall sleeves required for the installation of fire door fusible links on both sides of a wall are unlike many other wall penetrations for pipes, conduits, ducts and the like. Such sleeves must remain open and unobstructed for free movement of the fusible link cable or chain upon fusing of the links. Firestopping, other sealants, or other materials should not be used on sleeves because they can encumber movement and prevent automatic closing of a fire door in a fire event.Committee Statement: The committee accepts the proposed text with a modification to remove the '/' to clarify the intent of the requirement is to provide an open pathway for either cables or chains. In addition, the committee has added or other materials to the proposed annex language to more clearly address the fact that nothing should be used on sleeves that may prevent or encumber the free movement of the chain or cable. Introducing any other possible obstructions to the sleeve should not occur. Number Eligible to Vote: 25 Ballot Results: Affirmative: 23 Abstain: 1Ballot Not Returned: 1 Patton, V.Explanation of Abstention: KOFFEL, W.: In accordance with the policy of the Standards Council, I will abstain from balloting from this item. _______________________________________________________________ 80-13 Log #CP17 Final Action: Accept(4.8.2)_______________________________________________________________ Submitter: Technical Committee on Fire Doors and Windows, Recommendation: Revise text to read as follows: 4.8.2.1 In buildings with noncombustible floors, special sill construction a sill shall not be required, provided the floor structure is extended through the door opening. 4.8.2.2 In buildings with combustible floors or combustible floor coverings, special sill construction a sill shall be required if the floor structure is extended through the door opening, as combustible floor construction shall not be permitted to extend through the door opening. Substantiation: There is no guidance in NFPA 80 for what is intended by a special sill. The term is confusing and should be clarified. This proposed change clarifies the application of the section regarding the installation of sills and when sills are required. Committee Meeting Action: AcceptNumber Eligible to Vote: 25 Ballot Results: Affirmative: 24 Ballot Not Returned: 1 Patton, V.

    _______________________________________________________________ 80-14 Log #9 Final Action: Reject(4.8.4.1)_______________________________________________________________ Submitter: John A. Lee, Hughes Associates, Inc.Recommendation: Revised text to read as follows: 4.8.4.1 The clearance under the bottom of a door shall be a maximum of 3/4 in. 3/8 in. with a tolerance of +1/8 in.Substantiation: The existing section specifies a clearance of 3/4 in under the door, which is inconsistent with the NFPA 252 (2008) test assembly clearance of 3/8 in. under the bottom of the door, as well as the 2001 and earlier California Building Code (CBC) Standard 7-2 for Fire Door Tests, which also specify a 3/8 in. bottom gap. Similarly, the 2007 CBC (and 2006 IBC) reference both NFPA 252 and 80 almost interchangeably throughout Chapter 7. Because NFPA 80 provides no information or guidance as to why the clearance at the bottom of a door is allowed to be twice that which was tested, these apparent anomalies cause enforcement issues in the field. It is proposed to make the installed door bottom clearance consistent with the test condition, while adding a practical tolerance to account for field conditions (uneven floor, etc.,). Committee Meeting Action: RejectCommittee Statement: The test method is not the code. There is a reason that the gaps specified in the standard are smaller than whats allowed in the field. They represent a worse case condition. In the test, the bigger the gap, the more cooling air is drawn into the furnace and keeps the bottom rail cooler. The NFPA 80 limitation on the undercut size is related to limiting air flow into the fire room, not containing the fire. The fire test has no measurement or criteria for air flow under the door. There is currently no evidence that would suggest the current NFPA 80 limitations have resulted in any performance problems in the field. Number Eligible to Vote: 25 Ballot Results: Affirmative: 24 Ballot Not Returned: 1 Patton, V._______________________________________________________________ 80-15 Log #CP12 Final Action: Accept(4.8.4.1 and A.4.8.4.1)_______________________________________________________________ Submitter: Technical Committee on Fire Doors and Windows, Recommendation: Revise as follows: 4.8.4.1* The clearance under the bottom of a door shall be a maximum of 3/4 in. (19 mm). A.4.8.4.1 The maximum clearance of 3/

    4 in. (19 mm.) under fire doors as

    permitted by this standard is the accepted practice in the industry. NFPA 252, Standard Methods of Fire Tests of Door Assemblies, is a test standard, not an installation standard, and prescribes clearances and tolerances for swinging doors installed in the test wall opening. The test procedures as specified in NFPA 252 represent a worse case condition for the fire test. Substantiation: The proposed annex language provides clarification as to why there is a difference between the permitted clearance under the bottom of fire doors in NFPA 80 and the clearance used as part of the prescribed NFPA 252 test. It has been brought to the committees attention that there may be confusion in the field as to why the 3/

    4 is permitted by this standard. This

    annex language provides the necessary background information and clarification regarding the intent of the 3/

    4 permission.

    Committee Meeting Action: AcceptNumber Eligible to Vote: 25 Ballot Results: Affirmative: 24 Ballot Not Returned: 1 Patton, V._______________________________________________________________ 80-16 Log #10 Final Action: Accept in Principle(4.9.1)_______________________________________________________________ Submitter: Keith Pardoe, Door and Hardware InstituteRecommendation: Revise text to read as follows: 4.9.1 Upon completion of installation, all fire door and fire window assemblies shall be tested to confirm operation of the automatic closing device and full closure and inspected in accordance with 5.2 Inspections. Substantiation: As currently worded, 4.9.1 does not require newly installed fire doors and fire windows to be inspected to the same level of detail as required under 5.2. Since 4.9.1 specifically addresses the closing device and the units ability to reach full closure, newly installed fire door and fire windows are not thoroughly scrutinized to ensure they fully comply with NFPA 80 immediately upon installation. Now that annual inspections of fire door assemblies are beginning to take place around the country, it makes sense to make sure the fire doors and fire windows are initially installed correctly. Committee Meeting Action: Accept in PrincipleSee committee action on Proposal 80-17 (Log #CP15). Committee Statement: The committee has reorganized Chapter 5 in Proposal 80-17 (Log #CP15). This reorganization relocates the requirements for testing and inspection required upon the completion of installation of a fire door into Chapter 5. The changes made there should meet the submitters intent. Number Eligible to Vote: 25 Ballot Results: Affirmative: 24 Ballot Not Returned: 1 Patton, V.

    Figure A.4.7.5.1 Sleeve Installation for Fusible Links on Both Sides of Wall.

  • 80-6

    Report on Proposals A2012 Copyright, NFPA NFPA 80_______________________________________________________________ 80-17 Log #CP15 Final Action: Accept(Chapter 5)_______________________________________________________________ Submitter: Technical Committee on Fire Doors and Windows, Recommendation: 1. Delete Section 4.9.4.9* Testing. 4.9.1 Upon completion of installation, all fire door and fire window assemblies shall be tested to confirm operation of the automatic closing device and full closure. 4.9.2 Resetting of the automatic closing device shall be in accordance with the manufacturers written instructions. 4.9.3 A written record shall be maintained and shall be made available to the AHJ.2. Delete current Chapter 5 in its entirety and replace with the following: Chapter 5 to Inspection, Testing Care and Maintenance

    5.1* General.A.5.1 Walls with openings have less fire resistance than unpierced walls. Fire doors, shutters, and fire windows are designed to protect the opening under normal conditions of use, with clear spaces on both sides of the opening. Where the opening is not used and combustible material could be piled against or near the door, window, or shutter, the designed protection cannot be expected.

    5.1.1 Application.

    5.1.1.1 This chapter shall cover the inspection, testing and maintenance of fire doors and fire windows.

    5.1.1.2 The requirements of this chapter shall apply to new and existing installations.

    5.1.2 Operability.

    5.1.2.1 Doors, shutters, and windows shall be operable at all times.

    5.1.2.2 Doors, shutters, and windows shall be kept closed and latched or arranged for automatic closing.

    5.1.3 Replacement. Where it is necessary to replace fire doors, shutters, windows or their frames, glazing materials, hardware, and closing mechanisms, replacements shall meet the requirements for fire protection and shall be installed and tested as required by this standard for new installations.

    5.1.4 Repairs and Field Modifications.

    5.1.4.1 Repairs shall be made, and defects that could interfere with operation shall be corrected without delay.

    5.1.4.2 Field Modifications.

    5.1.4.2.1 In cases where a field modification to a fire door or a fire door assembly is desired, the laboratory with which the product or component being modified is listed shall be contacted and a description of the modifications shall be presented to that laboratory.

    5.1.4.2.2 If the laboratory finds that the modifications will not compromise the integrity and fire resistance capabilities of the assembly, the modifications shall be permitted to be authorized by the laboratory without a field visit from the laboratory.

    5.2* Inspections and Testing.A.5.2 Fire doors, shutters, and windows are of no value unless they are properly maintained and closed or are able to close at the time of fire. A periodic inspection and maintenance program should be implemented and should be the responsibility of the property management.

    5.2.1* Upon completion of the installation fire door and window assemblies shall be inspected and tested in accordance with Section 5.2.4. A.5.2.1 Hinges, catches, closers, latches, and stay rollers are especially subject to wear.

    5.2.2 A written record of all inspections and testing shall be signed by the inspector and kept for inspection by the AHJ.

    5.2.3 Acceptance Testing.

    5.2.3.1 Acceptance testing of fire door and window assemblies shall be performed by individuals with knowledge and understanding of the operating components of the type of door being subject to testing.

    5.2.3.2 Before testing, a visual inspection shall be performed to identify any damaged or missing parts that can create a hazard during testing or affect operation or resetting.

    5.2.3.3 Acceptance testing shall include the closing of the door by all means of activation.

    5.2.3.4 Swinging Doors with Builders Hardware or Fire Door Hardware

    5.2.3.4.1 Fire door assemblies shall be visually inspected from both sides to assess the overall condition of door assembly.

    5.2.3.4.2 As a minimum, the following items shall be verified:

    (1) No open holes or breaks exist in surfaces of either the door or frame.(2) Glazing, vision light frames, and glazing beads are intact and securely

    fastened in place, if so equipped.(3) The door, frame, hinges, hardware, and noncombustible threshold are

    secured, aligned, and in working order with no visible signs of damage.(4) No parts are missing or broken.(5) Door clearances do not exceed clearances listed in 4.8.4 and 6.3.1.7.(6) The self-closing device is operational; that is, the active door

    completely closes when operated from the full open position.(7) If a coordinator is installed, the inactive leaf closes before the active

    leaf.(8) Latching hardware operates and secures the door when it is in the

    closed position.(9) Auxiliary hardware items that interfere or prohibit operation are not

    installed on the door or frame.(10) No field modifications to the door assembly have been performed

    that void the label.(11) Meeting edge protection, gasketing and edge seals, where required,

    are inspected to verify their presence and integrity.(12) Labels shall be clearly visible and legible.

    5.2.3.5 Horizontally Sliding, Vertically Sliding, and Rolling Doors.

    5.2.3.5.1 Fire door assemblies shall be visually inspected from both sides to assess the overall condition of door assembly.

    5.2.3.5.2 The following items shall be verified:(1) No open holes or breaks exist in surfaces of either the door or frame.(2) Slats, endlocks, bottom bar, guide assembly, curtain entry hood, and

    flame baffle are correctly installed and intact.(3) Glazing, vision light frames, and glazing beads are intact and securely

    fastened in place, if so equipped.(4) Curtain, barrel, and guides are aligned, level, plumb, and true.(5) Expansion clearance is maintained in accordance with manufacturers

    listing.(6) Drop release arms and weights are not blocked or wedged.(7) Mounting and assembly bolts are intact and secured.(8) Attachments to jambs are with bolts, expansion anchors, or as

    otherwise required by the listing.(9) Smoke detectors, if equipped, are installed and operational.(10) No parts are missing or broken.(11) Fusible links, if equipped, are in the location; chain/cable, s-hooks,

    eyes, and so forth, are in good condition (i.e., no kinked or pinched cable, no twisted or inflexible chain); and links are not painted or coated with dust or grease.

    (12) Auxiliary hardware items that interfere or prohibit operation are not installed on the door or frame.

    (13) No field modifications to the door assembly have been performed that void the label.

    (14) Verify that doors have an average closing speed of not less than 6 in./sec (152 mm/sec) or more than 24 in./sec (610 mm/sec).

    5.2.3.6 Closing Devices

    5.2.3.6.1 All fire doors and fire window assemblies shall be inspected and tested to check for proper operation and full closure.

    5.2.3.6.2 Resetting of automatic-closing device shall be done in accordance with the manufacturers instructions.

    5.2.3.6.3 Rolling Steel Doors.

    5.2.3.6.3.1 Rolling steel fire doors shall be drop tested twice.

    5.2.3.6.3.2 The first test shall be to check for proper operation and full closure.

    5.2.3.6.3.3 A second test shall be done to verify that the automatic-closing device has been reset correctly.

    5.2.3.7* Fusible links, release devices, and any other moveable parts shall not be painted.A.5.2.3.7 Movable parts of the door assembly can include but are not limited to stay rollers, gears, and closing mechanisms.

    5.2.4 Periodic Inspection and Testing

  • 80-7

    Report on Proposals A2012 Copyright, NFPA NFPA 805.2.4.1* Periodic inspections and testing shall be performed not less than annually.A.5.2.4 Doors subject to high volume use and abuse may warrant an increased frequency of inspection. Components including but not limited to hinges, catches, closers, latches, and stay rollers are especially subject to wear.

    5.2.4.2 As a minimum, the provisions of Section 5.2.3 shall be included in the periodic inspection and testing procedure.

    5.2.4.3 Inspection shall include an operational test for automatic-closing doors and windows to verify that the assembly will close under fire conditions.

    5.2.4.4Assembly shall be reset after a successful test.

    5.2.4.5 Resetting of the release mechanism shall be done in accordance with manufacturers instructions.

    5.2.4.6 Hardware shall be examined, and inoperative hardware, parts, or other defects shall be replaced without delay.

    5.2.4.7 Tin-clad and kalamein doors shall be inspected for dry rot of the wood core.

    5.2.4.8 Chains or cables employed shall be inspected for excessive wear, stretching and binding.

    5.2.5 Maintenance

    5.2.5.1 All fire door and fire window assemblies shall be maintained in accordance with the manufacturers instructions.

    5.2.5.2 Guides and bearings shall be kept well lubricated to facilitate operation.

    5.2.5.3 Chains or cables on biparting, counterbalanced doors shall be checked, and adjustments shall be made, to ensure latching and to keep the doors in proper relation to the opening.

    5.2.5.4 Prevention of Door Blockage.

    5.2.5.4.1 Door openings and the surrounding areas shall be kept clear of anything that could obstruct or interfere with the free operation of the door.

    5.2.5.4.2 Where necessary, a barrier shall be built to prevent the piling of material against sliding doors.

    5.2.5.4.3 Blocking or wedging of doors in the open position shall be prohibited.

    5.2.5.5 Closing Mechanisms.

    5.2.5.5.1 Self-closing devices shall be kept in working condition at all times.

    5.2.5.5.2 Swinging doors normally held in the open position and equipped with automatic-closing devices shall be operated at frequent intervals to ensure operation.

    5.3 Repair of Fire Doors and Windows.

    5.3.1 Damaged glazing material shall be replaced with labeled glazing.

    5.3.2 Replacement glazing materials shall be installed in accordance with their individual listing.

    5.3.3 Any breaks in the face covering of doors shall be repaired without delay.

    5.3.4 Where a fire door, frame, or any part of its appurtenances is damaged to the extent that it could impair the doors proper emergency function, the following actions shall be performed:

    (1) The fire door, frame, door assembly, or any part of its appurtenances shall be repaired with labeled parts or parts obtained from the original manufacturer.

    (2) The door shall be tested to ensure emergency operation and closing upon completion of the repairs.

    5.3.5 If repairs cannot be made with labeled components or parts obtained from the original manufacturer or retrofitted in accordance with Section 5.4, the fire door frame, fire door assembly, or appurtenances shall be replaced.

    5.3.6 When holes are left in a door or frame due to changes or removal of hardware or plant-ons, the holes shall be repaired by the following methods:

    (1) Install steel fasteners that completely fill the holes(2) Fill the screw or bolt holes with the same material as the door or frame

    5.4 Retrofit Operators.

    5.4.1 The operator, governor, and automatic-closing device on rolling steel fire doors shall be permitted to be retrofitted with a labeled retrofit operator under the conditions specified in 5.4.2 through 5.4.5.

    5.4.2 The retrofit operator shall be labeled as such.

    5.4.3 The retrofit operator shall be installed in accordance with its installation instructions and listing.

    5.4.4 The installation shall be acceptable to the AHJ.

    5.4.5 The retrofit operator shall be permitted to be provided by a manufacturer other than the original manufacturer of the rolling steel fire door on which it is retrofitted, provided its listing allows it to be retrofitted on that manufacturers doors.

    5.5 Removal of Door or Window. Where a fire door or fire window opening is no longer in use, the opening shall be filled with fire resistance rated construction equivalent to that of the wall.

    5.6* Performance-Based Option.A.5.6 See Annex J for information regarding performance based inspection, testing, and maintenance options for fire door assemblies.

    5.6.1 As an alternate means of compliance with 5.2.4, subject to the AHJ, fire door assemblies shall be permitted to be inspected, tested, and maintained under a written performance based program.

    5.6.2 Goals established under a performance-based program shall provide assurance that the fire door assembly will perform its intended function when exposed to fire conditions.

    5.6.3 Technical justification for inspection, testing, and maintenance intervals shall be documented in writing.

    5.6.4 The performance